Professional Documents
Culture Documents
Grooved 0910
Grooved 0910
C B
B
65F SI 150
˝
H4
AN
A C
Hinged Flange
Adapter Gasket
C
4" x 3"
Adapter Size Flange Bolt Torque Adapter Size Latch Bolt Torque
2˝ – 2-1/2˝ – 3˝ 100-130 ft./lbs. (135-175 N/M) All Sizes 40 ft./lbs. (55 N/M)
4˝ – 6˝ 200-250 ft./lbs. (270-340 N/M)
8˝ 300-400 ft./lbs. (400-540 N/M)
10” & 12” 400-500 ft./lbs. (540-670 N/M)
SHARED
FLANGE LATCH
BOLT BOLT
HOLE
SUPERVISORY TAMPER
SWITCH CIRCUITS
FIRE ALARM CONTROL PANEL
(VALVE FULLY OPEN) SUPERVISORY CIRCUIT
OPEN (RED)
NC
S1 CLOSED (YELLOW)
COM NO END OR LINE RESISTANCE
OR NEXT DEVICE
COMMON (WHITE)
GREEN
ACTUATOR CASE GROUND
OPEN (ORENGE)
NC VOLTAGE
S2 CLOSED (BLUE)
SOURCE
COM NO
COMMON (BLACK) AUXILIARY SIGNAL DEVICE
(BELL OR HORN)