TAC IR3 E&I Report 23062021
TAC IR3 E&I Report 23062021
INSTRUCTIONS:
1.
Job #
Location Teak AC
Job Description Troubleshoot unit Jacket water pump fail to start.
Isolate field control panel main breaker for jacket water pump motor.
Check for continuity from breaker to contactor. OK.
De-isolate and check L1- 276V, L2-276, L3-276, to contactor. OK.
Check for 120v supply from relay to coil A. OK.
Check for 120v supply to function switch OK.
Check return from switch to coil no supply.
Check for slack connection, noted return from switch poorly terminated. Same
was corrected.
INSTRUCTIONS:
1.
Continue checks for slack connections.
BETWEEN PHASES
L1-L2:0Ω
L2-L3:0Ω
L1-L3:0Ω.
PS. No picture shown due to camera battery power.