Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

Special Cables

Type of Fire Fighting Fire Resistance Low Smoke


Fire Alarm
Cables (Flame Retardand ) (Fire Rated) (Halogen Free)

In crowded places
Fire Alarm Systems..
with people...
Special cases.. Emergency Circuits.. This cable are required
which transmit signals
This cable main priority to the notification
This cable is
is stopping the spread This cable ensure (Indicating) device
Used in preferable to use as
of fire continued functionality Circuits such as
it does
of the circuit for a alarm sounders, horns,
not release smoke in
(preventing a fire from certain period despite strobes and other
case of fire so that
growing) the fire remote signaling
people do not
equipment.
suffocate.

Emergency Circuits
1-EM.Lighting
Special Project 2-Exit Sign Fire Alarm System Place that crowded
1-Gas station 3-Smoke Exhaust with pepole
2-Power Station 4-Fire Exhaust Eq. cables for :-
Application
3-Petrochemical Plant 5-Smoke & Fire shutter 1-Alarm sounders 1-Hospital
4-Oil Platform 6-EM. Power supply 2-Horns 2-Hotels.. Etc
5-Industrial Areas 7-EM.plug socket 3-Strobes .. Etc
8-Hydrant Equipment

We do not use it at
places that have no
people like
pump room as it is
This Cables Actually when we say The selection of this
over cost and it does
Notes doesn’t spread fire Fire Resistance this cable size depend on
not required .
in addition to means MICA insulation voltadge drop
self-extinguishing
but it use in place
that crowded with
pepole like hotels.
Low Smoke
Halogen Free

According to Sweedy Low Smoke Halogen Free Cable atalogue

This cables are NOT Fire rated & coated with LS0H :-

SCCC CU/XLPE/LSHF
MCCC CU/XLPE/LSHF
MCCC CU/XLPE/SWA/LSHF

According to Sweedy Fire Resistance Cable atalogue

This cables are Fire rated & coated with LS0H :-

1-SCCC CU/MICA/XLPE/LSHF
(May use to feed single phase load like panel in Operating room..etc )
(According to the conditions and needs of the project)
2-MCCC CU/MICA/XLPE/LSHF
(May be use incase of fire pump exist indoor )
(May be use incase of fire pump exist outdoor if it is in pipe)
3-MCCC CU/MICA/XLPE/SWA/LSHF
(May be use incase of fire pump exist in outdoor if it is not be in pipe)
Fire Alarm Cable

According to Sweedy Fire Alarm Cable atalogue


According to Sweedy Special Cable atalogue

There are 2 type of cables :-

MCCC PVC/PVC - Unscreen


MCCC PVC/PVC - Screened

1-we use Screened shielding incase of power cables and fire cables are extended next
to each other as electromagnetic interference between it.

2-In the absence of any extended power cables next to the fire cable ,
we use Unscreen as there is no electromagnetic occurance
Unscreen VS Screened Fire Cable

Most common use Stranded not solid or fiexible


Fire Resistance
(Fire Rated)

used in :-
According to Sweedy Fire Resistance Cable atalogue

Fire rated means MICA


This cables are fire rated & coated with LS0H :-

1-SCCC CU/MICA/XLPE/LSHF
(May use to feed single phase load like panel in Operating room..etc )
(According to the conditions and needs of the project)
2-MCCC CU/MICA/XLPE/LSHF
(May be use incase of fire pump exist indoor )
(May be use incase of fire pump exist outdoor if it is in pipe)
3-MCCC CU/MICA/XLPE/SWA/LSHF
(May be use incase of fire pump exist in outdoor if it is not be in pipe)
In Fire Resistance Cable atalogue
we select the NO. of core as per your project requirment
Fire Fighting
(Flame Retardand )
Flame Retardand cable its Insulation & Outer sheath is
FR-PVC (Flame Retardand)