Report No.: HBA 11133 P Sheet-no: 3
One end of the sample was firmly fixed to a rigid mounting surface of the test equipment and the load was
applied to the other (free) end of the sample to obtain the required bending moment at the fixed end. The
direction of the load passes through and was perpendicular to the longitudinal axis of the arrester. The
force was applied by a hydraulic cylinder and measured by a force transducer. The deflection was
measured by a string potentiometer.
Test setup of bending breaking moment test of surge arrester housing type 3EP6 210-3PJ41-2XA1
Report No.: HBA 11133 P Sheet-no: 6
Three samples used before for the test to verify the specified short-term load (SSL) were tested. The test
samples were tested without internal parts. On each sample, the bending load was increased smoothly
until breaking occurs within 30 s to 90 s.
28
26
24
22
Bending moment / kNm
20
18
16
14
12
10
0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
28
26
24
22
Bending moment / kNm
20
18
16
14
12
10
0
0 5 10 15 20 25 30 35 40 45 50 55
Time / s
Report No.: HBA 11133 P Sheet-no: 7
5.3 Test result of breaking loads and calculation of mean breaking load (MBL)
The mean breaking load was measured to 29.6 kNm. The specified short-term load (SSL) of the surge
arrester series 3EP6 is 18 kNm. Therefore the measured mean breaking load (MBL) is 1.64 times higher
than the specified short-term load (SSL).
The tightness was measured at an ambient temperature of 20 °C before and after the test.
Test results see sheet-no. 11, the test setup see sheet-no. 13.
The partial discharge level was measured at 1.05 times the continuous operating voltage before and after
the test. The noise level was 0.1 pC. Test results see sheet-no. 11, the test circuit see sheet-no. 12.
Report No.: HBA 11133 P Sheet-no: 8
One end of the sample was including bottom insulating parts firmly fixed to a rigid mounting surface of the
test equipment and the load was applied to the other (free) end of the sample to obtain the required
bending moment at the fixed end. The direction of the load passes through and was perpendicular to the
longitudinal axis of the arrester. The force was applied by a hydraulic cylinder and measured by a force
transducer. The deflection was measured by a string potentiometer.
Test setup to verify the specified short-term load (SSL) of surge arrester type 3EP6 210-3PJ41-2XA1
Report No.: HBA 11133 P Sheet-no: 9
On each sample, the bending load was increased smoothly to SSL, tolerance +5% / -0%, within 30 s to
90 s. When the test load was reached, it was maintained for 60 s to 90 s. During this time the deflection
was measured. Then the load was released smoothly and the residual deflection was recorded. The
residual deflection was measured in the interval 1 min to 10 min after the release of the load.
SSL - Bending test at surge arrester type 3EP6 210-3PJ41-2XA1, Unit No. 000301
20
19
18
17
16
15
14
Bending moment / kNm
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
SSL - Bending test at surge arrester type 3EP6 210-3PJ41-2XA1, Unit No. 000301
20
19
18
17
16
15
Bending moment / kNm
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0 60 120 180 240 300 360 420 480 540 600 660 720 780
Time / s
Report No.: HBA 11133 P Sheet-no:10
SSL - Bending test at surge arrester type 3EP6 210-3PJ41-2XA1, Unit No. 000301
14
13
12
11
10
9
Deflection / mm
0
0 60 120 180 240 300 360 420 480 540 600 660 720 780
Time / s
Remaining
Unit no. Bending moment Maintained time permanent
deflection
kNm s mm
7 Test evaluation
The specified short-term load (SSL) of the surge arrester series 3EP6 is 18 kNm. The mean breaking
load was measured to 29.6 kNm. Therefore the measured mean breaking load (MBL) is 1.64 times higher
than the specified short-term load (SSL). The required value is MBL ≥ 1.2 SSL.
Visual inspection of the test samples after the test did not show any visible mechanical damages.
The measured remaining permanent deflections were in a range between 1.3 to 1.8 mm. The required
value is ≤ 3 mm.
Report No.: HBA 11133 P Sheet-no:11
8 Scope of validity
With respect to the identical design of all metal-oxide surge arrester series 3EP6, this test result is valid
for all other heights of metal-oxide surge arresters series 3EP6.
Report No.: HBA 11133 P Sheet-no:12
TS
C
CM
Tr
ZM
AC PD
RSH
u PDLevel i
Tr ... Transformer
TS ... Test sample
Voltage measurement: u
Capacitive divider: CH = 0.62nF, CN = 29µF
GLP3
The pressure p2 in the vessel was decreased to 500 mbar and kept there for 10 minutes while the
distance between the inductive sensor and the pressure relief diaphragm was measured. If the distance
decreases permanently within a certain range during the test duration of 10 minutes, the arrester unit is
tight. If the distance does not change or even increases, the arrester unit is not tight.
One end of the sample was firmly fixed to a rigid mounting surface of the test equipment and the load was
applied to the other (free) end of the sample to obtain the required bending moment at the fixed end. The
direction of the load passes through and was perpendicular to the longitudinal axis of the arrester. The
force was applied by a hydraulic cylinder and measured by a force transducer. The deflection was
measured by a string potentiometer.
Test setup of bending breaking moment test of surge arrester housing type 3EP6 210-3PJ41-2XA1
Report No.: HBA 11133 P Sheet-no: 6
Three samples used before for the test to verify the specified short-term load (SSL) were tested. The test
samples were tested without internal parts. On each sample, the bending load was increased smoothly
until breaking occurs within 30 s to 90 s.
28
26
24
22
Bending moment / kNm
20
18
16
14
12
10
0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
28
26
24
22
Bending moment / kNm
20
18
16
14
12
10
0
0 5 10 15 20 25 30 35 40 45 50 55
Time / s
Report No.: HBA 11133 P Sheet-no: 7
5.3 Test result of breaking loads and calculation of mean breaking load (MBL)
The mean breaking load was measured to 29.6 kNm. The specified short-term load (SSL) of the surge
arrester series 3EP6 is 18 kNm. Therefore the measured mean breaking load (MBL) is 1.64 times higher
than the specified short-term load (SSL).
The tightness was measured at an ambient temperature of 20 °C before and after the test.
Test results see sheet-no. 11, the test setup see sheet-no. 13.
The partial discharge level was measured at 1.05 times the continuous operating voltage before and after
the test. The noise level was 0.1 pC. Test results see sheet-no. 11, the test circuit see sheet-no. 12.
Report No.: HBA 11133 P Sheet-no: 8
One end of the sample was including bottom insulating parts firmly fixed to a rigid mounting surface of the
test equipment and the load was applied to the other (free) end of the sample to obtain the required
bending moment at the fixed end. The direction of the load passes through and was perpendicular to the
longitudinal axis of the arrester. The force was applied by a hydraulic cylinder and measured by a force
transducer. The deflection was measured by a string potentiometer.
Test setup to verify the specified short-term load (SSL) of surge arrester type 3EP6 210-3PJ41-2XA1
Report No.: HBA 11133 P Sheet-no: 9
On each sample, the bending load was increased smoothly to SSL, tolerance +5% / -0%, within 30 s to
90 s. When the test load was reached, it was maintained for 60 s to 90 s. During this time the deflection
was measured. Then the load was released smoothly and the residual deflection was recorded. The
residual deflection was measured in the interval 1 min to 10 min after the release of the load.
SSL - Bending test at surge arrester type 3EP6 210-3PJ41-2XA1, Unit No. 000301
20
19
18
17
16
15
14
Bending moment / kNm
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
SSL - Bending test at surge arrester type 3EP6 210-3PJ41-2XA1, Unit No. 000301
20
19
18
17
16
15
Bending moment / kNm
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0 60 120 180 240 300 360 420 480 540 600 660 720 780
Time / s
Report No.: HBA 11133 P Sheet-no:10
SSL - Bending test at surge arrester type 3EP6 210-3PJ41-2XA1, Unit No. 000301
14
13
12
11
10
9
Deflection / mm
0
0 60 120 180 240 300 360 420 480 540 600 660 720 780
Time / s
Remaining
Unit no. Bending moment Maintained time permanent
deflection
kNm s mm
7 Test evaluation
The specified short-term load (SSL) of the surge arrester series 3EP6 is 18 kNm. The mean breaking
load was measured to 29.6 kNm. Therefore the measured mean breaking load (MBL) is 1.64 times higher
than the specified short-term load (SSL). The required value is MBL ≥ 1.2 SSL.
Visual inspection of the test samples after the test did not show any visible mechanical damages.
The measured remaining permanent deflections were in a range between 1.3 to 1.8 mm. The required
value is ≤ 3 mm.
Report No.: HBA 11133 P Sheet-no:11
8 Scope of validity
With respect to the identical design of all metal-oxide surge arrester series 3EP6, this test result is valid
for all other heights of metal-oxide surge arresters series 3EP6.
Report No.: HBA 11133 P Sheet-no:12
TS
C
CM
Tr
ZM
AC PD
RSH
u PDLevel i
Tr ... Transformer
TS ... Test sample
Voltage measurement: u
Capacitive divider: CH = 0.62nF, CN = 29µF
GLP3
The pressure p2 in the vessel was decreased to 500 mbar and kept there for 10 minutes while the
distance between the inductive sensor and the pressure relief diaphragm was measured. If the distance
decreases permanently within a certain range during the test duration of 10 minutes, the arrester unit is
tight. If the distance does not change or even increases, the arrester unit is not tight.
2 Index
Sheet-no.
1 Test Report .................................................................................................................................................1
2 Index ...........................................................................................................................................................2
3 Technical data of the surge arrester type 3EP6 120-2PD31-2DA1............................................................3
4 Dimensional drawing of the arrester ...........................................................................................................4
5 Environmental tests ....................................................................................................................................5
5.1 Temperature cycling test .....................................................................................................................5
5.2 Salt mist test........................................................................................................................................5
5.3 Test result............................................................................................................................................5
6 Scope of validity..........................................................................................................................................6
7 Annex..........................................................................................................................................................6
Report No.: HBA 11054 P Sheet: 3
5 Environmental tests
The environmental tests were performed on one complete arrester type 3EP6 120-2PD31-2DA1 with a
height of H= 1459 mm, see drawing no. ET HP AR / 27068293-1300 on sheet-no.4. The environmental
tests consist of the temperature cycling test and the salt mist test in order to demonstrate by accelerated
test procedures that the sealing mechanism and exposed metal combinations of the arrester are not
impaired by environmental conditions.
Before and after the tests the leakage check was performed.
After initial measurement the temperature cycling test was performed according to IEC 600068-2-14 with
10 cycles -35°C to +50°C with a temperature change gradient of 1 K/min and a duration of 3 h at each
temperature level. The temperature cycling test was carried out by “TechnoLab” (Am Borsigturm 46, D-
13507 Berlin, Germany) and is documented in the investigation report No. A120260 (see annex 1).
After temperature cycling test the salt mist test according to IEC 600068-2-11 was carried out by the test
laboratory “TechnoLab” (Am Borsigturm 46, D-13507 Berlin, Germany) and is documented in the
investigation report No. A120260 (see annex 1).
Visual inspection of the test sample after the test did not reveal any damages, see Photo. 5 of the
investigation report No. A120260 in annex 1.
The pressure p2 in the vessel was decreased to 500 mbar and kept there for 10 min. while the distance
between the inductive sensor and the pressure relief diaphragm was measured. If the distance decreases
permanently within a certain range during the test duration of 10 min., the arrester unit is tight. If the
distance does not change or even increases, the arrester unit is not tight.
6 Scope of validity
With respect to the identical design of all surge arrester units series 3EP6, this test result is valid for all
other heights of metal oxide surge arrester series 3EP6.
7 Annex
Annex 1: Investigation report No. A120260
Untersuchungsbericht / Investigation Report
customer’s
Technolab’s
denomination/description of sample
sample number
sample/s
Surge arrester
3EP6 120-2PD31-2DA1
120260-1
Unit No. 281959
Photo 1
Photo 2
Table 1
2
120260-Siemens ESS SF+HC Report.doc
Die Prüfergebnisse beziehen sich ausschließlich auf die übergebenen Prüfgegenstände / Test results are only relevant to the test objects submitted.
Die Prüfgegenstände werden 3 Monate aufbewahrt, sofern diese bei TechnoLab verbleiben. / Test objects/Samples are stored for three months, if remaining with TechnoLab.
Untersuchungsbericht / Investigation Report
Diagram 1 - Extended diagram of one temperature cycle (x-axis: time in minutes, y-axis: temperature in °C)
3
120260-Siemens ESS SF+HC Report.doc
Die Prüfergebnisse beziehen sich ausschließlich auf die übergebenen Prüfgegenstände / Test results are only relevant to the test objects submitted.
Die Prüfgegenstände werden 3 Monate aufbewahrt, sofern diese bei TechnoLab verbleiben. / Test objects/Samples are stored for three months, if remaining with TechnoLab.
Untersuchungsbericht / Investigation Report
Photo 3
4
120260-Siemens ESS SF+HC Report.doc
Die Prüfergebnisse beziehen sich ausschließlich auf die übergebenen Prüfgegenstände / Test results are only relevant to the test objects submitted.
Die Prüfgegenstände werden 3 Monate aufbewahrt, sofern diese bei TechnoLab verbleiben. / Test objects/Samples are stored for three months, if remaining with TechnoLab.
Untersuchungsbericht / Investigation Report
Photo 4
5
120260-Siemens ESS SF+HC Report.doc
Die Prüfergebnisse beziehen sich ausschließlich auf die übergebenen Prüfgegenstände / Test results are only relevant to the test objects submitted.
Die Prüfgegenstände werden 3 Monate aufbewahrt, sofern diese bei TechnoLab verbleiben. / Test objects/Samples are stored for three months, if remaining with TechnoLab.
Report No.: HBA 10986 P Sheet: 2
2 Index
Sheet-no.
1 Test Document .........................................................................................................................................1
2 Index.........................................................................................................................................................2
3 Technical data of arresters.......................................................................................................................3
3.1 3EP6 468-3PF43-2XA1.......................................................................................................................3
3.2 3EP6 420-3PJ42-2XA1 .......................................................................................................................3
3.3 3EP6 396-3PR42-2XA1 ......................................................................................................................4
3.4 3EP6 240-4PJ51-2XA1 .......................................................................................................................4
4 Dimensional drawing ................................................................................................................................5
4.1 3EP6 468-3PF43-2XA1.......................................................................................................................5
4.2 3EP6 420-3PJ42-2XA1 .......................................................................................................................6
4.3 3EP6 396-3PR42-2XA1 ......................................................................................................................7
4.4 3EP6 240-4PJ51-2XA1 .......................................................................................................................8
5 Radio interference voltage (RIV) test .......................................................................................................9
5.1 Test Result for type 3EP6 468-3PF43-2XA1 ......................................................................................9
5.2 Picture of test setup 3EP6 468-3PF43-2XA1....................................................................................10
5.3 Test Result for type 3EP6 420-3PJ42-2XA1.....................................................................................11
5.4 Picture of test setup 3EP6 420-3PJ42-2XA1 ....................................................................................12
5.5 Test Result for type 3EP6 396-3PR42-2XA1 ....................................................................................12
5.6 Picture of test setup 3EP6 396-3PR42-2XA1 ...................................................................................13
5.7 Test Result for type 3EP6 240-4PJ51-2XA1.....................................................................................14
5.8 Picture of test setup 3EP6 240-4PJ51-2XA1 ....................................................................................15
5.9 Technical data of test circuit, radio interference voltage test ............................................................16
Report No.: HBA 10986 P Sheet: 3
4 Dimensional drawing
At first the test samples were energized at 1.15 times the continuous operating voltage of the arrester
(Uc). The voltage then was decreased to 1.05 times Uc. After holding this level for 5 minutes the test
voltage was decreased stepwise to 0.5 times Uc and raised again stepwise to 1.05 times Uc, holding this
value for 5 minutes. Finally the test voltage was decreased stepwise to 0.5 times Uc. The amplitude of
voltage steps was 0.1 Uc. For each step the RIV-level was measured at a measuring frequency of
0.75 MHz on an impedance of 300 in the earth line of the coupling capacitor. The measuring system
was calibrated with a pulse generator at 50 pC.
The RIV-level X dB measured on the 300 - - impedance was converted to µV on 300 - - impedance
according to the following equation:
URIV = 1µV * 10 X (dB-1) / 20
Noise 0 34 45
level
The measured RIV- Levels were below the maximal allowable value of 2500 µV on 300according to
IEC 60099-4 Ed. 2.2 (2009).
Report No.: HBA 10986 P Sheet: 10
The following diagram shows the RIV- Levels versus applied voltage during the last series of voltage
decrease.
Radio interference characteristic of surge arrester type 3EP6 468-3PF43-2XA1
1400
1200
1000
RIV Level / µV
800
600
400
200
0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
Uc*x
Noise 0 36 56
level
The measured RIV- Levels were below the maximal allowable value of 2500 µV on 300according to
IEC 60099-4 Ed. 2.2 (2009).
The following diagram shows the RIV- Levels versus applied voltage during the last series of voltage
decrease.
Radio interference characteristic of surge arrester type 3EP6 420-3PJ42-2XA1
1000
900
800
700
RIV Level / µV
600
500
400
300
200
100
0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
Uc*x
Report No.: HBA 10986 P Sheet: 12
Noise 0 35 50
level
The measured RIV- Levels were below the maximal allowable value of 2500 µV on 300according to
IEC 60099-4 Ed. 2.2 (2009).
Report No.: HBA 10986 P Sheet: 13
1400
1200
1000
RIV Level / µV
800
600
400
200
0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
Uc*x
Noise 0 35 50
level
The measured RIV- Levels were below the maximal allowable value of 2500 µV on 300according to
IEC 60099-4 Ed. 2.2 (2009).
900
800
700
RIV Level / µV
600
500
400
300
200
100
0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
Uc*x
Report No.: HBA 10986 P Sheet: 15
CK
TS
C C
H
L
Tr
Zm
M
CN
u
Tr..... Transformer
F.... Resistance at measuring frequency fm >10 k
TS.... Test sample
Voltage measurement: u
AC peak voltmeter Haefely, Type 51
Voltage divider (CH+CN) Haefely, Type CW 1200/380
5 Measurement protokoll
Report No.: HBA 10863 P Sheet: 6
Surge arrester type 3EP6 210-3PJ41-2XA1 in gastight wrapping at the beginning of the testing period
Report No.: HBA 10863 P Sheet: 7
Measurement of SF6 Concentration in the top of the wrapping at the end of the testing period
Report No.: HBA 10863 P Sheet: 8
Measurement of SF6 Concentration at the bottom of the wrapping at the end of the testing period
7 Test evaluation
The measured leakage rate of 0.2 *10-6 Pa * m3/s is less than the maximum seal leak rate acc.
IEC 60099-4 / 2009 (1*10-6 Pa * m3/s).
8 Scope of validity
With respect to the identical design of all metal-oxide surge arrester series 3EP6, this test result is valid
for all other heights of metal-oxide surge arresters series 3EP6.
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Notes
Accreditation
The PEHLA-Testing Laboratory Berlin-Siemensstadt has been approved by the DAkkS (German accreditation body)
according to EN ISO/IEC 17025 for tests in the field of high-voltage switchgear and controlgear and power
engineering equipment (Registration-No. D-PL-12072-04).
STL-Member
PEHLA is founder member of the SHORT-CIRCUIT TESTING LIAISON (STL) which has been established in 1969.
STL is a forum for the international cooperation of the testing organisations with the further full members ASTA (UK),
CESI (IT), CPRI (IND), ESEF (FR), KEMA (NL), SATS (NO, SE, FI), STLNA (US, CA) and JSTC (JP). In the frame-
work of EC, STL (EU) has been recognised in 1992 by EOTC as agreement group.
PEHLA-Documents
A Type Test Certificate
is issued for type tests which have successfully been carried out in full compliance with the relevant specifications or
standards and STL Guides valid at the time of the test. For these tests the test object must be clearly identified by
technical description, drawings and additional specifications.
A Test Document
is issued for parts of type tests which have successfully been carried out in full compliance with the relevant
specifications or standards and STL Guides valid at the time of test. For these tests the test object must be clearly
identified by technical description, drawings and additional specifications.
A Test Report
is issued for all other tests which have been carried out according to specifications, standards or "PEHLA-Richtlinien"
(PEHLA Guides) and/or clients‘ instructions. Similarly, this test report contains all test results, details of the conditions
under which the tests were carried out, also details relating to the behaviour of the test object, and its condition after
the tests.
A Test Confirmation
is issued immediately after the tests. It confirms that the tests have been conducted and is valid only until publishing
the detailed results in an entire document.
Addresses
Office: PEHLA-Geschäftsstelle
Hallenweg 40
68219 Mannheim
Germany
Internet: www.pehla.com
Manufacturer: Siemens AG
E T HP AR MF
Nonnendammallee 104
13629 Berlin
Germany
Client: Siemens AG
E T HP AR R&D 2
Nonnendammallee 104
13629 Berlin
Germany
02SE1108
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Table of Contents
Cover Sheet.................................................................................................................................................. 1
Notes ............................................................................................................................................................ 2
Table of Contents ......................................................................................................................................... 3
List of Test Participants ................................................................................................................................ 4
Technical Data of Test Object ...................................................................................................................... 5
List of Identified Drawings ............................................................................................................................ 6
Drawing of Test Object ................................................................................................................................. 7
Technical Data of Test Circuit ...................................................................................................................... 8
Circuit Diagram............................................................................................................................................. 9
Test Results - High-current Short-circuit Test at 65 kA.............................................................................. 10
Test Results - High-current Short-circuit Test at 25 kA.............................................................................. 11
Test Results - High-current Short-circuit Test at 12 kA.............................................................................. 12
Test Results - Low-current Short-circuit Test ............................................................................................. 13
Photos of Test Object ................................................................................................................................. 14
List of Symbols and Abbreviations Used in Oscillograms .......................................................................... 18
Oscillograms............................................................................................................................................... 19
14PE0402
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Representatives of Client:
Further Participants:
51PE0402
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Test object: Metal-oxide surge arrester with pressure relief device (porcelain housing)
Designation: 3EP6 288-4PJ51-2XA1
Manufacturer: Siemens AG, E T HP AR MF, Berlin
Serial No.: K/00000290; K/00000292; K/00000293; K/00000296
Year of manufacture: 2011
Drawing No.: E T HP AR / 802-62747
Further data: -
Remarks: The test sample was the largest unit of the 3EP6 series
320SE1110
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
The manufacturer has submitted to the testing laboratory drawings and other data containing sufficient
information to unambiguously identify by type the essential details and parts of the test object presented
for test.
The drawings have been stamped and signed by the manufacturer in order to guarantee that the
drawings or data schedules truly represent the test object to be tested.
Further these drawings have been stamped and signed by PEHLA representatives and are kept
at the client.
with the test documents at the test laboratory.
The testing laboratory has checked that drawings and data schedules adequately represent the essential
details and parts of the test object to be tested, but is not responsible for the accuracy of the detailed
information.
The drawing(s) contained in this document are identical with the checked, stamped and signed drawings.
1)
Remarks: Included in this document
52PE0402
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
317SE0407
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Remarks: -
12dSE0407
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Circuit Diagram
Single-phase Direct Test
AD
G UTO TO
AD
ITO
T Transformer
44-17bSE1008
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Test Results
Short-circuit Tests
Test No. 2) 7 3) 8 - -
K/0000
Test object No. - - -
0290
Applied voltage kV 28.7 26.1 - -
Peak short-circuit current kA 212 169 - -
Short-circuit current First cycle kA 78.0 74.2 - -
Last cycle kA 64.9 59.0 - -
Duration ms 209 219 - -
4)
Equivalent short-circuit current Current kA 71.6 66.7 - -
Duration ms 200 200 - -
X/R 19 - - -
Time to arc ignition ms - 0.5 - -
5)
Time to vent ms - 3.7 - -
Duration of open flames s - - - -
Internal parts outside the circular enclosure - no - -
Test result (P/N) - P - -
Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed along the surface of the active part inside the arrester housing
2)
Tests 1 - 6: Equipment tests, oscillograms are not included in this document
3)
Prospective test for the following test
4)
Calculated using Simpson’s Rule
5)
Arc detected with outside placed optical arcing detector (see sketch on sheet 9)
322SE0902
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Test Results
Short-circuit Tests
Test No. 2) 11 3) 13 - -
K/0000
Test object No. - - -
0292
Applied voltage kV 31.5 30,8 - -
Peak short-circuit current kA 50.1 42.4 - -
Short-circuit current First cycle kA 27.6 26.9 - -
Last cycle kA 27.6 26.8 - -
Duration ms 203 204 - -
4)
Equivalent short-circuit current Current kA 27.7 26.9 - -
Duration ms 200 200 - -
X/R 25 - - -
Time to arc ignition ms - 0.5 - -
5)
Time to vent ms - 4.8 - -
Duration of open flames s - - - -
Internal parts outside the circular enclosure - no - -
Test result (P/N) - P - -
Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed along the surface of the active part inside the arrester housing
2)
Tests 9 - 10 and 12: Equipment tests, oscillograms are not included in this document
3)
Prospective test for the following test
4)
Calculated using Simpson’s Rule
5)
Arc detected with outside placed optical arcing detector (see sketch on sheet 9)
322SE0902
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Test Results
Short-circuit Tests
Test No. 2) 15 3) 16 - -
K/0000
Test object No. - - -
0293
Applied voltage kV 32.3 31.7 - -
Peak short-circuit current kA 23.5 20.3 - -
Short-circuit current First cycle kA 13.1 13.1 - -
Last cycle kA 13.1 12.8 - -
Duration ms 202 202 - -
4)
Equivalent short-circuit current Current kA 13.2 12.9 - -
Duration ms 200 200 - -
X/R 41 - - -
Time to arc ignition ms - 0.5 - -
5)
Time to vent ms - 7.2 - -
Duration of open flames s - - - -
Internal parts outside the circular enclosure - no - -
Test result (P/N) - P - -
Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed along the surface of the active part inside the arrester housing
2)
Test 14: Equipment test, oscillograms is not included in this document
3)
Prospective test for the following test
4)
Calculated using Simpson’s Rule
5)
Arc detected with outside placed optical arcing detector (see sketch on sheet 9)
322SE0902
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Test Results
Short-circuit Tests
Test No. 2) 22 - - -
K/0000
Test object No. - - -
0296
Applied voltage kV 148 - - -
Peak short-circuit current A 1964 - - -
Short-circuit current First cycle A 779 - - -
Last cycle A 754 - - -
Duration s 1.02 - - -
3)
Equivalent short-circuit current Current A 763 - - -
Duration s 1 - - -
X/R - - - -
Time to arc ignition ms 0.8 - - -
4)
Time to vent ms 232 - - -
Duration of open flames s - - - -
Internal parts outside the circular enclosure no - -
Test result (P/N) P - - -
Legend: P: Passed in terms of the applied standard N: Not passed in terms of the applied standard
1)
Remarks: The fuse wire was placed along the surface of the active part inside the arrester housing
2)
Tests 17 - 21: Equipment tests, oscillograms are not included in this document
3)
Calculated using Simpson’s Rule
4)
Arc detected with outside placed optical arcing detector (see sketch on sheet 9)
322SE0902
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
311SE0407
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
311SE0407
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
311SE0407
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
311SE0407
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Oscillogram No.: 1 - 22
Abbreviation in Description
oscillograms
Remarks: The amplitude scaling of the individual signals is apparent at the labels on the right
side of the oscillograms, as a value taken from the upper to the lower borderline of the
inner graphic area.
61SE0707
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Oscillograms
Oscillogram No.: 7
316SE1103
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Oscillogram No.: 8
316SE1103
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Oscillogram No.: 11
316SE1103
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Oscillogram No.: 13
316SE1103
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Oscillogram No.: 15
316SE1103
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Oscillogram No.: 16
316SE1103
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Oscillogram No.: 22
316SE1103
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 2
The Prüffeld der Schaltwerke, Berlin has been approved by the DAkkS (German accreditation body) according to EN
ISO/IEC 17025 for tests in the field of high-voltage switchgear and controlgear and power engineering equipment
(Registration-No. D-PL-11055-10).
Under reference to EN ISO/IEC 17025 the Prüffeld der Schaltwerke states the following:
- The accreditation of the Prüffeld der Schaltwerke or any of its test reports by themselves in no way constitute or
imply product approval by DAkkS or any other body.
- If someone refers to a test in an accredited Prüffeld der Schaltwerke this reference shall include the accreditation
body, i.e. DAkkS, the relevant scope of the accreditation and the appropriate registration number.
DAkkS -Documents
A Certificate
is issued for type tests which have successfully been carried out in full compliance with the relevant specifications or
standards valid at the time of the test. For these tests the equipment under test must be clearly identified by technical
description, drawings and additional specifications.
A Test Document
is issued for parts of type tests which have successfully been carried out in full compliance with the relevant
specifications or standards valid at the time of test. For these tests the equipment under test must be clearly identified
by technical description, drawings and additional specifications.
A Test Report
is issued for all other tests which have been carried out according to specifications, standards and/or clients
instructions. Similarly, this test report contains all test results, details of the conditions under which the tests were
carried out, also details relating to the behaviour of the equipment during test, and its condition after the tests.
A Test Confirmation
is issued immediately after the tests. It confirms that the tests have been conducted and is valid only until publishing
the detailed results in an entire document.
Addresses
Testing Station: Prüffeld der Schaltwerke, Berlin
Siemens AG
E T HS TI LAB HV
Nonnendammallee 104
13629 Berlin
Germany
Client: Siemens AG
E T HP AR S
Nonnendammallee 104
D-13629 Berlin
03DE0804
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 3
Table of Contents
Cover Sheet.................................................................................................................................................. 1
Documents and Addresses .......................................................................................................................... 2
Table of Contents ......................................................................................................................................... 3
List of Test Participants ................................................................................................................................ 4
Technical Data of Test Object ...................................................................................................................... 5
List of Identified Drawings Surge arrester .................................................................................................... 6
Drawings of Test Object (one-unit)............................................................................................................... 7
Drawings of Test Object (two-units) ............................................................................................................. 8
Circuit Diagram - Insulation withstand tests – Lightning & Switching impulse voltage ................................ 9
Circuit Diagram - Insulation withstand tests - Power frequency voltage .................................................... 10
Test Results - Dry power frequency withstand voltage test ....................................................................... 11
Test Results - Wet power frequency withstand voltage test ...................................................................... 13
Test Results - Dry lightning impulse withstand voltage test ....................................................................... 15
Test Results – Dry Switching impulse withstand voltage test .................................................................... 18
Test Results – Wet Switching impulse withstand voltage test ................................................................... 21
Photos of Test Object - Power frequency withstand voltage test............................................................... 24
Photos of Test Object - Lightning & Switching impulse withstand voltage test.......................................... 25
Notes .......................................................................................................................................................... 26
14PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 4
Representatives of Client:
Further Participants:
51PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 5
Test object: Housings of porcelain housed metal oxide surge arrester series 3EP6
Designation: 3EP6 288-4PJ51-2XA1, 3EP6 576-4PJ52-2XA1
Manufacturer: Siemens AG, E T HP AR MF
Serial No.: -
Year of manufacture: 2011
Drawing No.: 802-62793 & 802-62800
Further data:
16PE0511
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 6
The manufacturer has submitted to the testing laboratory drawings and other data containing sufficient
information to unambiguously identify by type the essential details and parts of the test object presented
for test.
The drawings have been stamped and signed by the manufacturer in order to guarantee that the
drawings or data schedules truly represent the test object to be tested.
Further these drawings have been stamped and signed by testing station representatives and are kept
at the client.
with the test documents at the test laboratory.
The testing laboratory has checked that drawings and data schedules adequately represent the essential
details and parts of the test object to be tested, but is not responsible for the accuracy of the detailed
information.
The drawing(s) contained in this document are identical with the checked, stamped and signed drawings.
Remarks: -
52PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 7
18PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 8
18PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 9
Circuit Diagram
Insulation withstand test (Lightning & Switching impulse voltage)
32PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 10
Circuit Diagram
Insulation withstand test (Power frequency voltage)
M Measuring Device
32PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 11
Test Results
Dry power frequency withstand voltage test
Condition k1 k2 kt U
/kV
Power-frequency voltage Dry 1.002 0.980 0.982 565
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 12
Condition k1 k2 kt U
/kV
Power-frequency voltage dry 0.999 0.989 0.988 856
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 13
Test Results
Wet power frequency withstand voltage test
Condition k1 k2 kt U
/kV
Power-frequency voltage wet 1.003 1.000 1.003 591
1.003 1.000 1.003 606
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 14
Condition k1 k2 kt U
/kV
Power-frequency voltage wet 1.004 1.000 1.004 856
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 15
Test Results
Dry lightning impulse withstand voltage test
Condition k1 k2 kt U
/kV
Lightning impulse dry 0.998 0.983 0.981 1121
withstand voltage test 0.998 0.985 0.983 1170
1.2/50µs
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 16
Oscilogramms
771kV -345kV
551kV K1
-576kV
K1
330kV
-806kV
110kV
-1036kV
0kV
-1151kV
0 10.0µs 20.0µs 30.0µs 40.0µs 50.0µs 0 10.0µs 20.0µs 30.0µs 40.0µs 50.0µs
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 17
Condition k1 k2 kt U
/kV
Lightning impulse
withstand voltage test dry 0.999 0.989 0.987 1983
1.2/50µs
Oscilogramms
1371kV
K1
-979kV
980kV
K1
-1371kV
588kV
-1762kV
-1958kV
196kV
0kV
0 10.0µs 20.0µs 30.0µs 40.0µs 50.0µs 0 10.0µs 20.0µs 30.0µs 40.0µs 50.0µs
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 18
Test Results
Dry Switching impulse withstand voltage test
Condition k1 k2 kt U
/kV
Switching impulse
withstand voltage test dry 1.001 0.979 0.980 847
250/2500µs
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 19
Oscilogramms
581kV
-583kV
415kV
-750kV
-833kV
249kV
K1
83kV
0kV
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 20
Condition k1 k2 kt U
/kV
Switching impulse
withstand voltage test dry 0.999 0.990 0.989 1264
250/2500µs
Oscilogramms
879kV
-626kV
628kV
-876kV
377kV
K1
-1126kV
-1251kV
126kV
0kV
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 21
Test Results
Wet Switching impulse withstand voltage test
Condition k1 k2 kt U
/kV
Switching impulse
withstand voltage test wet 1.002 1.000 1.002 730
250/2500µs
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 22
Oscilogramms
582kV
-583kV
416kV
-749kV
-832kV
250kV
K1
83kV
0kV
24PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 23
Condition k1 k2 kt U
/kV
Switching impulse
withstand voltage test wet 1.003 1.000 1.003 1150
250/2500µs
The test sample has passed the test without any flashover.
Oscilogramms
-578kV
809kV
-809kV
578kV
-1040kV
347kV
K1
-1155kV
116kV
0kV
AC Transformer
Test object
18DE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 25
Impulse generator
Test object
18PE0402
Prüffeld der Schaltwerke, Berlin
Report No.: 11-093-HH Sheet: 26
Notes
1. The Prüffeld der Schaltwerke (Testing Station of Siemens Schaltwerke), Siemens AG, Berlin points
out that it has been approved by the DAkkS (German accreditation body) for rendering the following
testing services
Mechanical tests
Temperature-rise tests
Environmental tests
Dielectric tests
Power tests (e.g. switching capacity, load switching, short-time current tests, etc.)
on high-voltage switchgear and controlgear and on power engineering equipment.
The approval was given under registration No. D-PL-11055-10. Testing service beyond the scope
certified cannot be regarded as testing service of an approved testing station. No test documents will
made out for them.
2. In the Prüffeld der Schaltwerke, Siemens AG, Berlin, all tests will be carried out according to
EN ISO/IEC 17025 and the pertinent international and national tests specifications. Moreover, all
criteria specified by the accreditation authority will be taken into account in the tests.
3. The Prüffeld der Schaltwerke, Siemens AG, Berlin points out that its accreditation or its test
documents do not imply that the accreditation authority or another authority have acknowledged the
product tested.
4. Test documents or parts thereof may not be used or released by the purchaser for advertising
purposes if the accreditation authority considers their use as misleading. Reproduction in extracts of
the tests documents is acceptable only on condition of the prior consents of the Prüffeld der
Schaltwerke, Siemens AG, Berlin. Copying the cover sheet is an exception.
If test documents or extracts thereof are to be used for advertising purposes or publication, the
agreement of the Prüffeld der Schaltwerke, Siemens AG, Berlin must be obtained in due time before
utilization. If necessary, the Prüffeld der Schaltwerke, Siemens AG, Berlin will obtain the accreditation
authority’s consent.
5. If reference is to be made in one way or other to the utilization of the Prüffeld der Schaltwerke,
Siemens AG, Berlin as approved testing laboratory, this must be worded as follows:
"Tested by the Testing Station of Siemens Schaltwerke Berlin, a testing laboratory approved by the
DAkkS (German accreditation body) for tests on ' high-voltage switchgear and controlgear and power
engineering equipment ' under registration No. D-PL-11055-10."
6. The Prüffeld der Schaltwerke applies the internal procedure PSW-IA 020 for determining the
uncertainties of measurement. As long as no explicit statements are made, the uncertainties required
by the relevant standards have been complied with.
18DE0402