Professional Documents
Culture Documents
Determination of Geomagnetically Induced Current Flow in A Transformer From Reactive Power Absorption
Determination of Geomagnetically Induced Current Flow in A Transformer From Reactive Power Absorption
3, JULY 2013
I. INTRODUCTION Fig. 1. Terminal voltage and magnetizing current for a transformer under half-
cycle saturation.
and GIC can cause cascading failures, leading to massive dis- transformer tank temperature, transformer oil gassing, along
ruption of electrical power service. with transformer noise and vibration [13], [15]. The effective
1) Simulation of GIC in Power Systems: There is a substan- reactive power absorption of a transformer increases when
tial body of research devoted to the analysis of GIC in HV trans- that transformer’s magnetic core is saturated. This relationship
mission networks. In general, proposed techniques aim at deter- is almost linear and depends nearly entirely on the saturated
mining the electrical-field potential that causes GIC to circu- reactance of the transformer [9], [16], [17].
late in transmission lines through the neutral grounding points The installation of real-time neutral GIC monitors on every
of transformers [7]. Electric-field potentials at ground level de- transformer would be very useful but a rather expensive propo-
pend on many factors, such as the earth resistivity over large ge- sition. On the other hand, knowing the amount of GIC flowing
ographical areas as well as temporal and spatial variation of the into the neutral of a transformer does not provide a direct indi-
magnetic field during a GMD event. Once the induced poten- cation of whether the transformer will enter into half-cycle sat-
tials on transmission circuits are assessed with varying degrees uration. For instance, in the case of an autotransformer, it is not
of uncertainty and simplifying assumptions, the GIC currents possible to determine the extent of saturation from the neutral
circulating in transmission lines and transformers are then cal- GIC measurements alone.
culated by modelling the power system as a dc network where 3) Requirements of the Power System Controlling Authority:
the forcing functions (normally voltage sources) are estimated During a GMD event, the power system controlling authority
from the induced potentials [8]. (i.e., the system operator) needs to assess if any of the potential
Once the GIC currents are estimated, their potential effect on problems described earlier are or will be taking place. Since the
power apparatus has to be assessed. In the case of transformers, problems associated with GIC are caused by transformer satu-
two main areas of concern are the heating effects of harmonics ration and the subsequent generation of harmonics, the notion
caused by half-cycle saturation, and the heating caused by stray of assessing these effects directly, rather than through simula-
flux as the core goes in and out of saturation. These effects de- tions affected by different levels of uncertainty is quite attrac-
pend heavily on the construction and type of transformer. For tive. Control room energy-management systems (EMS) or su-
instance, banks of single-phase units are more susceptible than pervisory control and data acquisition (SCADA) continuously
three-phase units, while three-leg core-type units are the least measure and monitor real and reactive power in real time with
susceptible [9]. the existing infrastructure. A reliable relationship between mea-
From the point of view of protective relaying, susceptibility sured reactive power loss in a transformer, harmonic currents,
to GIC depends largely on the type and magnitude of harmonic and GIC flowing through the windings would directly provide
currents caused by transformer saturation, the type of relay, and the information needed to make practical operational decisions
the particular protective scheme. Thus, even if the GIC circu- in real time. The decisions could range from taking equipment
lating in the power network could be assessed with reasonable at risk out of service to reconfiguring the network to reducing
accuracy, the effect on the performance of the system and poten- the GIC impact on vulnerable equipment.
tial damage to equipment remains difficult to assess, especially This paper proposes an approach to obtain the relationships
in real time. between transformer reactive power loss and GIC from EMS re-
2) Measurement and Monitoring of GIC: Measuring GIC active power measurements. Unlike earlier work that acknowl-
directly is a way to get around the difficulties and uncertain- edged the correlation between GIC and reactive power absorp-
ties that arise from modeling it from fundamental principles tion [9], [16], this paper seeks to define that relationship and
(i.e., induced potentials at ground level). The generally accepted uses it to estimate GIC levels from measured reactive power
practice for measuring GIC on an electrical system is to install loss. Section II presents the proposed concept of employing
Hall-effect sensors on the neutral conductor of selected trans- transformer reactive power absorption to determine its satu-
formers. After appropriate filtering and conditioning, a mea- ration level and consequently the GIC. Section III shows an
surement of the dc current in the transformer neutral is ob- application of the technique on a simulation of a bank of a
tained [10], [11]. The Sunburst system, developed by the Elec- single-phase autotransformers modeled in the Electromagnetic
tric Power Research Institute (EPRI), uses this technique and Transients Program EMTDC/PSCAD [18]. In Section IV, the
has been implemented in the U.S. (primarily in the Northeast), effect of the path of the flow of GIC through the transformer
Manitoba (on a feeder supplying Minnesota) [5], and in Eng- windings is examined. Section V presents a case study using
land and Wales [12]. The Minnesota power system also uses GIC and reactive power measurements of the Hydro One net-
dc current measurement directly on a 500-kV phase conductor work obtained during a GMD event that took place in May 2005.
[13]. Hydro One has deployed an extensive GIC detection net- Discussions are presented in Section VI, with conclusions in
work [14]. In 2005, it had 12 monitoring stations transmitting Section VII.
real-time data directly to the operations and control center. In
preparation for the peak of the sunspot cycle 24 (2012–2014),
the number of GIC monitoring stations will be increased to 17. II. PROPOSED TECHNIQUE
Transformer neutral currents are sometimes used to trigger
alarms and fault recorders in order to facilitate the analysis Consider the simplified transformer representation shown in
of GIC incidents [6], [13], [15]. Parameters that are con- Fig. 2. This simplified model will be used to illustrate that reac-
sidered of interest with regard to the effects of GIC include tive power losses in a transformer are proportional to dc flux es-
system voltages and reactive power consumption as well as tablished in the core by dc currents flowing through its windings.
Authorized licensed use limited to: University of Otago. Downloaded on September 24,2023 at 22:43:08 UTC from IEEE Xplore. Restrictions apply.
1282 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 3, JULY 2013
Fig. 4. Flux linkages versus the current nonlinear characteristic with dc flux
offset.
(4)
Fig. 3. Flux linkages versus the current nonlinear characteristic.
since rms currents are practically zero during half a cycle.
The effective reactive power loss is given by
Core saturation effects can be approximated with a nonlinear
inductor in many types of transformer construction with dif- (5)
ferent degrees of accuracy [19]. Let us consider a single-phase
transformer. Core and eddy current losses are ignored. The non- Introducing (3) and (4) into (5)
linear characteristic in terms of flux linkages as a function of
current is shown in Fig. 3. The rms voltage at the terminals
of the nonlinear inductance is assumed to be sinusoidal. Since
losses are ignored
(6)
(1)
where is constant for a given terminal voltage
and the relationship between applied voltage and instantaneous
flux is
(7)
V. CASE STUDY 2: HYDRO ONE ESSA TS TRANSFORMER, Fig. 9 shows the measured neutral terminal GIC over the du-
MAY 15, 2005 GMD EVENT ration of the GMD event. In all figures in this section, the time
On May 15, 2005, the Hydro One GIC detection network axis is labeled in minutes from midnight May 13, 2005. The data
are presented for May 14th and 15th (minutes 0 to 2879).
recorded the effects of a relatively mild GMD event. During this
3) Calculation of Transformer Reactive Power Absorption:
event, there was no interruption of service, protective equipment
Through the use of bus capacitive voltage transducers (CVTs)
malfunction, or nuisance equipment tripping. GIC monitored
and transformer bushing current transformers (CTs), the real and
in the neutral of a 500-kV/230-kV/28-kV, 750-MVA autotrans-
reactive power flows through each transformer are recorded. In
former at Essa TS reached 30 A (10 A per phase). The trans- the case of Essa T4, since no load or reactive compensation is
former bank consists of three-single-phase units. The analysis connected to the tertiary winding, the net transformer reactive
presented in this section is based on Hydro One’s EMS historical power absorption is calculated as the difference between the
records from the GIC monitoring stations. The technique pro- reactive power flows in the primary and secondary terminals:
posed here takes instrument calibration drift into consideration.
(15)
A. Modified Technique
1) Nomenclature: This nomenclature is used exclusively for Any possible measurement or calibration error in the mea-
this case study to describe a modified technique needed to con- sured quantities will also be seen in the calculated ,
dition the real system data. and will need to be compensated for.
Authorized licensed use limited to: University of Otago. Downloaded on September 24,2023 at 22:43:08 UTC from IEEE Xplore. Restrictions apply.
MARTI et al.: DETERMINATION OF GEOMAGNETICALLY INDUCED CURRENT FLOW IN A TRANSFORMER FROM REACTIVE POWER ABSORPTION 1285
Fig. 10. Transformer reactive power absorption and measured neutral GIC.
Fig. 9. Measured transformer neutral current with error corrected.
(16)
Fig. 13. Absolute value of measured neutral GIC and estimated neutral GIC
when is not zero.
Luis Marti (M’79) received the MA.Sc. and Ph.D. Rajiv K. Varma (SM’09) received the B.Tech. and
degrees in electrical engineering from The Univer- Ph.D. degrees in electrical engineering from Indian
sity of British Columbia, Vancouver, BC, Canada, in Institute of Technology (IIT) Kanpur, Kanpur, India,
1983 and 1987, respectively. in 1980 and 1988, respectively.
He joined Ontario Hydro, Toronto, ON, Canada Currently, he is an Associate Professor and Hydro
(now Hydro One Networks), in 1989, where he is One Chair in Power Systems Engineering at the
currently responsible for the Special Studies Group. University of Western Ontario (UWO), London,
He is also an Adjunct Professor at Ryerson Univer- ON, Canada. Prior to this position, he was a faculty
sity, Toronto, ON, Canada, and University of Western member in the Electrical Engineering Department,
Ontario, London, ON, Canada. His research activities IIT Kanpur, from 1989 to 2001. He has co-authored
include the development of models for the family of a book Thyristor-Based FACTS Controllers for
Electromagnetic Transients Program programs, geomagnetically induced cur- Electrical Transmission Systems (IEEE/Wiley). His research interests include
rent simulation, grounding, induction coordination, electromotive-force (emf) FACTS, power systems stability, and grid integration of wind and photovoltaic
issues pertaining to transmission and distribution networks, and connection/op- solar power systems.
erational issues around the connection of renewable generation in distribution Prof. Varma was awarded the Government of India BOYSCAST Young Sci-
networks. entist Fellowship in 1992–1993 to conduct research on FACTS at UWO. He also
Dr. Marti has participated in a number of Canadian and international technical received the Fulbright grant from the U.S. Educational Foundation in India, to
organizations, such as the Canadian Standards Association, IEEE, and CIGRE. conduct research in FACTS at Bonneville Power Administration (BPA), Port-
land, OR, in 1988. He is the Chair of IEEE Working Group on “FACTS and
HVDC Bibliography” and is active on a number of other IEEE working groups.
He has co-delivered several tutorials on SVC sponsored by the IEEE Substations
Jonathan Berge (M’04) received the B.E.Sc., Committee. He has received many Teaching Excellence awards at the Faculty
M.E.Sc., and Ph.D. degrees in electrical engineering, of Engineering and university level at UWO.
environment and sustainability from the University
of Western Ontario, London, ON, Canada.
His research interests include atmospheric
phenomena in electrical power systems and the
interconnection of large wind power generators. He
is currently working on the application of distributed
photovoltaic generation to improve the performance
of distribution systems.
Authorized licensed use limited to: University of Otago. Downloaded on September 24,2023 at 22:43:08 UTC from IEEE Xplore. Restrictions apply.