Yccd Cu Condensing Units 52 158 KW
Yccd Cu Condensing Units 52 158 KW
YCCD-CU
TABLE 1
120 96.2
Cooling capacities at 7C saturated suction temperature and 35C condenser air entering temperature.
FEATURES
Refrigerant R407C. Two refrigerant circuits. Minimum base area/maximum capacity. Low weight , single power and control supplies.
BENEFITS
Zero ozone depletion value. System stand-by security. Minimum installation space. Easy to install. Ideal for maintenance operations Operator safety. Simple operation. High standard of quality control.
CONTENTS
Specification Accessories and Options Operating Limitations Sound Power Spectrum Cooling Capacities Physical Data Electrical Data Electrical Connections Dimensions Space Requirements
Accessible components. Residual current circuit breaker. Microprocessor control with visual display of temperatures and alarms. Manufactured to ISO 9001/EN 29001.
SPECIFICATION
The condensing units shall be completely factory assembled with all interconnecting refrigerant piping and wiring ready for field installation. YCCD-CU shall be pressure tested, evacuated and have a nitrogen holding charge and initial oil charge. The unit structure shall be of heavy gauge galvanised steel fastened with stainless steel screws and bolts. Galvanised steel parts shall be coated with baked-on powder paint (Desert Sand (RAL 1019)). The unit base is riveted and all internal sheet metal panels are not painted (60 to 150 only). Compressors YCCD-CU models 60, 75, 120 and 150 shall have two hermetic reciprocating compressors with internal motor protection housed in a separate acoustically lined enclosure. YCCD-CU models 90 and 105 shall have two scroll compressors and YCCD-CU models 170, 190 and 210 shall have four scroll compressors. Compressors on all models shall be mounted on rubber anti-vibration pads and have direct on line starting. The compressor motors shall be refrigerant gas cooled, with integral thermistor protection against overloads. The overload protection is automatically reset after approximately 8 seconds. The motor terminal boxes shall have IP-54 weather protection. The compressors shall be switched On and Off by the unit microprocessor to provide capacity control.
Page J.1 Doc. No. PC152/01.04/GB
Refrigerant Circuits Two complete refrigerant circuits of ACR copper, with brazed joints shall be provided on each unit. Refrigerant circuits shall include: service valves for refrigerant charging, discharge, suction and liquid line isolating (ball) valves and fusible plugs for over-pressure protection. Transducers and pressure switches shall be included on the high pressure circuits of all YCCD-CU models. Low pressure transducers shall be provided on the low pressure circuits of all models. Air Cooled Condensers The condenser coils shall be seamless copper tubes, arranged in staggered rows, mechanically expanded into corrugated aluminium fins. Integral sub-cooling will be included. Design working pressure of the coils shall be 28 bar g. All YCCD-CU models shall have a stepless fan speed controller fitted as standard, which operates on the basis of condensing pressure. Operation is possible down to -18C with the ISN control system. blades. Each fan will have a painted galvanised steel protection guard. The totally enclosed fan motors shall have IP-54 weather protection and thermocontact protection embedded in their windings. Power and Control Panel All controls and motor starting equipment necessary for full unit operation shall be factory wired and tested. Power and control components are accessed via individual doors on YCCD-CU models 60 to150. The power compartment shall have a door interlocked isolator and shall contain compressor and fan contactors, fuses and supply protection. The control compartment shall contain the YORK Integrated System Network YORK ISN control. The control will offer Building Management System (BMS) communication and display and print of unit operational and history data.
The microprocessor control will include: Status Key for display of:
Status of the unit and each refrigerant circuit System and unit safety fault messages
Display/Print Keys for display of: Ambient air temperature System pressures (each circuit) Operating hours and starts (each compressor) Load and unload timers and cooling demand Condenser fan status Print calls up to the liquid crystal display:
Operating data for the systems History of fault shutdown data for up to the last six fault
shutdown conditions An RS-232 port, in conjunction with this press-to-print button, is provided to allow hard copy print-outs via a separate printer. Entry Keys Setpoints Keys for programming:
The condenser fans shall be direct drive with aluminium aerofoil To program and modify system values
Set daily schedule/holiday for start/stop Manual override for servicing Cut-outs for low and high ambient temperature, high
discharge pressure and low suction pressure
STATUS
SYS SYS
1 2
Display/Print
OPER DATA
Entry
Setpoints
COOLING SETPOINTS SCHEDULE/ ADVANCE DAY
Unit
OPTIONS
CLOCK
HISTORY
ENTER /ADV
PROGRAM
ON
OFF
Low ambient temperature cutout setting Ambient air temperature Metric or Imperial data Discharge and suction pressure cutout settings System suction pressures System discharge pressures Anti-recycle timer status Anti-coincident system start timer condition Compressor run status Day, date and time Daily start/stop times Holiday status Automatic or manual system lead/lag control Lead system definition Compressor starts & operating hours (each compressor) Status of fan operation Run permissive status Number of compressors running Load & unload timer status
The operating program will be stored in non-volatile memory (EPROM) to eliminate chiller failure due to AC power failure/battery discharge. Programmed setpoints shall be retained in lithium battery backed RTC memory.
A Colour coded 12-button keypad. Customer terminal block for control inputs.
OPERATING LIMITATIONS
Model Ambient Air Entering Temperature Ambient Air External Static Pressure Maximum Saturated Suction Temperature Minimum Capacity Step Power Supply Voltage (400 10%) C Pa C % V 60 YCCD-CU 105 120 150 170 190 210 -18 to +43C 0 Pa (Standard Fans) / 80 Pa High Pressure Fans 12 12 12 12 50 25 20 400 V, 3 , 50 Hz (nominal) 75 90
TABLE 2
TABLE 3
Total dB(A) 87 87 88 89 90 90 93 94
Tolerance 2 dB(A) Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1
TABLE 4
Model
SST C
0 2 4 7 10 12 0 2 4 7 10 12 0 2 4 7 10 12 0 2 4 7 10 12 0 2 4 7 10 12 0 2 4 7 10 12 0 2 4 7 10 12 0 2 4 7 10 12 0 2 4 7 10 12
43
Cool kW 33.9 37.0 40.1 45.3 51.0 54.7 37.2 40.6 44.1 49.8 56.1 60.1 49.4 52.2 56.4 62.0 68.2 72.4 55.8 59.0 63.7 70.0 77.1 81.8 62.5 68.3 74.1 83.7 94.3 101.0 72.9 79.6 86.3 97.6 109.9 117.7 93.5 98.8 106.7 117.2 129.0 136.9 102.0 107.7 116.3 127.8 140.8 149.4 112.3 118.7 128.2 140.8 155.1 164.6 Power kW 17.2 18.7 19.9 21.9 23.5 24.3 20.2 21.8 23.2 25.6 27.5 28.4 29.4 29.9 30.5 31.3 32.1 32.9 34.4 35.1 35.7 36.7 37.6 38.6 32.8 35.5 37.8 41.7 44.8 46.3 40.7 44.1 47.0 51.8 55.6 57.5 55.3 56.4 57.4 58.9 60.5 62.0 62.9 64.1 65.3 67.0 68.8 70.5 65.2 66.4 67.6 69.4 71.2 73.0
YCCD-CU 210 YCCD-CU 190 YCCD-CU 170 YCCD-CU 150 YCCD-CU 120 YCCD-CU 105 YCCD-CU 90
YCCD-CU 75
YCCD-CU 60
Data outside of operating limits SST = Saturated suction temperature Power is total unit input power
PHYSICAL DATA
Model Nominal cooling capacity Number of refrigerant circuits Total capacity steps Compressor Number Theoretical displacement No. of cylinders Nominal speed Oil charge (per compressor) Oil type No. of loading stages Air Number of coils cooled Total coil face area Condenser Number of rows Fans Number of fans Nominal speed Total airflow Total power (standard fans) Total power (high pressure fans) Shipping Weight Sound power level (2) (3) Sound pressure level at 10 m Dimensions Length Width Height Model Nominal cooling capacity (1) Number of refrigerant circuits Total capacity steps Compressor Number Theoretical displacement No. of cylinders Nominal speed Oil charge (per compressor) Oil type No. of loading stages Air Number of coils cooled Total coil face area Condenser Number of rows Fans Number of fans Nominal speed Total airflow Total power (standard fans) Total power (high pressure fans) Shipping Weight Sound power level (2) (3) Sound pressure level at 10 m Dimensions Length Width Height kW
(1)
TABLE 5
kW
m/h rpm l % m
YCCD-CU 60 75 90 105 52.1 57.2 69.6 78.6 2 2 2 2 2 2 2 2 2 2 2 2 36.16 43.16 37.7 43.5 3 3 SCROLL SCROLL 2950 2950 2950 2950 2.8 2.8 4 6.6 098L00565-000 098L00637-000 50-100 50-100 50-100 50-100 2 2 2 2 4.3 4.3 4.3 4.3 2 2 3 3 2 2 2 2 910 910 910 910 5.3 5.3 5.2 5.0 0.96 0.96 0.96 0.96 1.96 1.96 1.96 1.96 618 638 756 796 87 87 88 89 56 56 57 58 2110 2110 2110 2110 1110 1110 1110 1110 1810 1810 1810 1810 YCCD-CU 170 131.7 2 4 4 72.5 SCROLL 2950 10.4
m/h rpm l % m
120 150 96.2 112.1 2 2 2 2 2 2 76.85 88.94 6 6 2950 2950 6.6 6.6 098L00565-000 50-100 50-100 2 2 6.1 6.1 3 4 3 3 910 910 7.5 7.2 1.44 1.44 2.94 2.94 856 916 90 90 59 59 2760 2760 1110 1110 1810 1810
190 210 143.6 158.2 2 2 4 4 4 4 81.2 87 SCROLL SCROLL 2950 2950 10.6 13.2 098L00637-000 20-50-70-100 25-50-75-100 25-50-75-100 4 4 4 8.7 8.7 8.7 3 3 4 3 3 3 910 910 910 12.3 12.3 11.7 2.94 2.94 2.94 4.2 4.2 4.2 1350 1380 1486 93 94 94 62 63 63 3450 3450 3450 1110 1110 1110 2170 2170 2170
(1) Data refers to 5C saturated suction temperature and 35C condenser air temperature (2) Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1 (3) Sound pressure level values refer to ISO standard 3744
TABLE 6
ELECTRICAL DATA
Operating Condition LRA
Current per Comp. Maximum(2) 17.8 22.5 23.0 29.0 39.8 47.5 18.8 23.0 29.0 (A) (A) DOL Starting Current per Comp. (A) 80 126 135 175 190 215 120 175 135 175 175 175
System
Sys. 1+ 2 Sys. 1+ 2 Sys. 1+ 2 Sys. 1+ 2 Sys. 1+ 2 Sys. 1+ 2 Sys. 1+ 2 Sys. 1+ 2 Sys. 1+ 2
Power Input at Nominal(1) per comp (kW) 9.3 11.0 12.7 15.0 18.1 22.4 9.6 15.0 12.7 15.0 15.0 15.0
Power Input at Max.(2) per comp (kW) 11.0 14.0 13.8 16.8 24.0 29.0 11.1 16.8 13.8 16.8 16.8 16.8
Current per Comp. Nominal(1) 14.9 18.2 21.5 26.5 31.4 37.8 16.9 21.5 26.5
(1) Nominal conditions taken at approximately 5oC saturated suction temperature and 35oC ambient temperature (2) Maximum conditions for the compressor taken at approximately 12oC saturated suction temperature and 43oC ambient temperature YCCD-CU
Number of fans Power input per fan (kW) Full load Amps per fan (A) Power input per fan (kW) Full load Amps per fan (A)
60
2 0.48 0.93 0.98 1.75
75
2 0.48 0.93 0.98 1.75
90
2
105
120
3 0.48 0.93 0.98 1.75
150
3 0.48 0.93 0.98 1.75
170
3 0.98 1.75 1.4 2.9
190
3 0.98 1.75 1.4 2.9
210
3 0.98 1.75 1.4 2.9
2 Standard Fans 0.48 0.48 0.93 0.93 High Pressure Fans 0.98 0.98 1.75 1.75
01 REMOTE START/STOP 02 1 EXTERNAL INTERLOCK 2 3 4 5 6 7 100 SYS.1 ZONE THERMOSTAT 101 102 SYS.2 ZONE THERMOSTAT 103 35 36 37 COMPRESSOR '1' ON 38 39 COMPRESSOR '2' ON 40 90 82 90 83 90 84 EVAPORATOR FAN/PUMP RELAY MAX 0,5 AMP. 230V REMOTE INDICATION INTERLOCK (OPTIONAL) CIRC PUMP ETC COMMON N.O. SYSTEM 1 GENERAL ALARM N.O. SYSTEM 2 GENERAL ALARM
01 REMOTE START/STOP 02 1 EXTERNAL INTERLOCK 2 3 4 5 6 7 100 SYS.1 ZONE THERMOSTAT 101 102 SYS.2 ZONE THERMOSTAT 103 35 36 37 SYS.1 COMPRESSOR '1' ON 38 39 SYS. COMPRESSOR '2' ON 40 41 SYS.2 COMPRESSOR '1' ON 42 43 SYS.2 COMPRESSOR '2' ON 44 90 82 90 83 90 84 EVAPORATOR FAN/PUMP RELAY MAX 0,5 AMP. 230V REMOTE INDICATION REMOTE INDICATION INTERLOCK (OPTIONAL) CIRC PUMP ETC COMMON N.O. SYSTEM 1 GENERAL ALARM N.O. SYSTEM 2 GENERAL ALARM
A
Lifting Point Lifting Point
C
C
Cable Entry
177
177
36,5
1037 1110
36,5
VIEW A
1100
D1 D2 E1 E2 E1 E2
B (+35 mm ONLY FOR TRANSPORT) 282 327 70 272 187 70
D2 D1
VIEW B
VIEW C
DIMENSION (mm) A 1756 1756 1756 1756 B 2110 2110 2110 2110 C 1810 1810 1810 1810
A
Cable Entry Lifting Point Lifting Point
C
C
177
177
36,5
1037 1110
36,5
VIEW A
1100
D1 D2 E1 E2 E1 E2
B (+35 mm ONLY FOR TRANSPORT) 282 327 70 272 187 70
D2 D1
VIEW B
VIEW C
2170
A
300 238 70 318
C D
C D B A
B A
1498 1558 1017
VIEW A
Suction Line MODEL YCCD-CU 170 190 210 A 1 5/8" 2 1/8" 2 1/8" C
SPACE REQUIREMENTS
3000 mm
A
1300 mm 1000 mm
VIEW A
1300 mm A= B=
1000 mm (Models 60 - 150) 1500 mm (Models 170 - 210) 1500 mm (Models 60 - 150) 2000 mm (Models 170 - 210)
1300 mm
1300 mm
1000 mm
1000 mm
NOTES