Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 47

I SYSTEM DESIGN DATA

A. DESIGN BASIS OF HVAC SYSTEM

1. DESIGN CRITERIA

i. The Site Adapt Architects/ Engineer shall consider the latest issue of the applicable Codes and
standard issued by the concern bodies.

ii. The basic aims of the HVAC, and ventilation systems are :
 To maintain comfort conditions by means of temperature, humidity control and
providing adequate fresh air. (in A.C. Areas)

 Low flow fans system to maintain desire conditions.

 To exhaust foul air/ fumes generated in toilet/pantries.

 Following is the Table containing HVAC Cooling and ventilation loads.

iii. Basis of Weather data:


 Site location: Ludhiana (Punjab)

 Outdoor Design Conditions:


Based on the out door design conditions for various seasons have been considered as
follows:

Ambient Conditions:

Season DB( Dry Bulb) WB( Wet Bulb) RH (Relative


(˚C) (˚F) (˚C) (˚F) Humidity (%)
Summer 43.3 110 23.9 75 20
Monsoon 35.0 95 26.6 80 52
Winter 7.2 45 5.0 41 70

Indoor Design Conditions: For all areas


DB : 75.0˚F ± 2˚F (24 +/ 1 Deg C)
RH : Less than 60% (uncontrolled)
Service areas such as Toilet shall be provided with mechanical forced ventilation system.

1
iv. The Basis of design for Air conditioning

S.No. Parameter Location Value

1 Occupancy Office/Meeting etc. As per sitting layout

2 Lighting Load Office 2.0 watt/ sqft

3 Fresh Air All area AS PER ASHRAE STD.


62.1-2019

4 Wall U Factor 0.38 BTU/hr/Ft2 / 0F

5 Glass U Factor 1.1 BTU/hr/Ft2 / 0F

6 Toilet Exhaust 15 ACPH

7 Working Hall areas 6 ACPH

3. SYSTEM DESIGN

3.1 It is proposed to install DX VRF/VRV Units system for office at first floor & Second
floor.

3.2 It is proposed to 20HP ODU for Second floor and 16HP ODU for First and both ODU’s
shall be placed on existing terrace as shown in drawings.

3.3 All cabins/conference/Meeting & work station areas shall be go with Hi-wall VRV
indoor units.

3.4 All second-floor indoor units shall be connected with 20HP ODU.

3.5 All first-floor indoor units shall be connected with 16HP ODU.

3.6 It is proposed to install industrial propeller fans for normal exhaust on each floor.

3.7 It is proposed to install Industrial wall fans for air circulation on first floor, these fans
proposed due to height constraint. All fans shall be located in drawing.

2
3.8 It is proposed to install HVLS fans for air circulation on ground and second floor, these
fans proposed as we have sufficient height. All fans shall be located in drawing.

3.9 It is proposed to install ducted inline fans for office area toilet on second and first floor.

3.10 It is proposed to install small propeller fans for working floor common toilets.

3.11 All HVLS fans shall have their own controller and shall be located on near by column.

3.12 System will be complete with electrical panel, cabling & earthing etc.

4. ITEMS TO BE PROVIDED BY OTHER AGENCIES

4.1 Provision of 3 Ph, 415 Volts, 50 Hz A.C. supply for VRV outdoor units HVLS
fansetc., 1 Ph, 230 Volts, 50 Hz A.C. supply for all indoor unit & Inline fans.

4.2 Drainage system near the units.

4.3 Carpentry work such as wooden frame for grills/diffusers.

4.4 Under deck insulation.

******

3
II Ventilation System

1. General :

The ventilation fans shall be complete in all respects and shall generally comply with the
following specifications given below and as per BS 5720 : 1979 code of practice for
mechanical ventilation and as per IS : 3103 – 1975 (Reaffirmed 1999) code of practice of
industrial ventilation.

2. Exhaust Fans (Propeller Type) :

2.1 The exhaust fans shall be direct – direct, three or four blade type, mounted on a steel
mounting plate.

2.2 The fan blades shall be of pressed steel of aerofoil design for high efficiency and
static pressure.

2.3 The mounting frame shall be of cast/sheet steel with steel brackets to connect the
frame with the fan/motor assembly. Rubber mounts shall be provided between the
mounting frame and the mounting brackets.

2.4 Motor shall be easily replaceable single/three phase, permanent split capacitor or shaded
pole for shall sizes, totally enclosed with pre lubricated sleeves or ball bearing, designed
for quiet operation.

Motor shall suitable for either horizontal or vertical as per site requirement.

2.5 The fan motor shall be to totally enclosed squirrel cage type.

3. Exhaust Fans (Axial flow type) :

3.1 The exhaust fans shall be Axial flow type with steel hub and blades, mounted directly
on the shaft of a totally enclosed motor.

3.2 The fan blades shall be of pressed steel of aerofoil design for high efficiency and
static pressure.

3.3 The mounting frame shall be of cast/sheet steel with steel brackets to connect the
frame with the fan/motor assembly. Rubber mounts shall be provided between the mounting
frame and the mounting brackets.

3.4 The fan motor shall be to totally enclosed squirrel cage type and suitable for operation on
415 +/- 10% volts, 50 Hz, AC supply with `H’ class insulation.

4
3.5 The fan shall be selected for lowest noise level and it shall not exceed more than 80
db(A) at a distance of 1 m around the equipments.

3.6 Fan performance shall be based on test conducted in accordance to AMCA.

3.7 The motor assemble shall be fire rated for high performance application (250 oC for
minimum of 2 hours operation).

3.8 All required accessories on required as per site requirement.

3.9. Outlet velocity for normal operation shall not exceeds-12m/s and for emergency fans-
15m/s.

4. Inline Fans :

The fan shall be complete with centrifugal impeller, timer, MCB, direct driven motor,
vibration isolators.

4.1 Housing

The housing shall be constructed of hot rolled GSS sheet metal construction. Housing
metal parts shall be either spot welded or screwed or mounted together with Rivets. The
housing shall indicate arrow showing rotation, make, model and duty conditions.

4.2 Fan Wheel

Fan wheel shall be forward/backward curved type, fan wheel shall be statically and
dynamically balanced.

4.3 Ball Bearing

The ball bearing shall be completely maintenance free and can be used in any mounting
position, at maximum indicated temperature. The bearing lubricant shall be suitable for a
minimum ambient temperature of minus 15O C. For application at maximum indicated
ambient temperature life expectancy LIO is 40,000 hours minimum.

4.4 Fan Motor

Fan shall be supplied with built in Thermal contact (TK). At the critical high temperature
point (`B’ = 130 C or `F’ = 155O C) the Thermal contact will open and break the power
supply to the fan. Fan motor shall have insulation class `B’ or class `F’ and protection
class IP44 or IP54.

4.5 Fan Drive

5
The fan shall be direct driven type.

4.6 Painted

Complete fan assembly and other steel components shall either be GSS or expoxy
painted.

5.0 Exhaust and Fresh Air Units.

1. TYPE

The Exhaust/fresh air Units shall be horizontal/vertical of Draw through type having pre
(MERV-8) filter section, and fan sections with direct/belt driven DIDW blower, as per
schedule of quantities.

2. CAPACITY

The air moving and coil capacities shall be as shown in schedule of quantities.

3. CASING

The housing/ casing of the air handling unit shall be of double skin construction. The
housing shall be so made that it can be delivered at site in total/ semi knock down
conditions depending upon the construction. The framework shall be of extruded
aluminium hollow sections. All the members shall be assembled thru mechanical joints to
make a sturdy and strong framework for various sections.

Double skin panels shall be made of 0.6 mm pre-plasticized / pre coated Galvanized
sheet steel and 0.6 mm galvanized sheet inside with insulation of 25+/- 2 mm thick CFC
free PUF injected insulation of 40+ 2kg/m3 density.

The panels shall be bolted /screwed to the framework with soft rubber gasket in between
to make the joints airtight. Suitable doors with powder coated hinges and latches shall be
provided for access to various panels for maintenance.

The Fan and the motor arrangement shall be mounted on to the common framework. The
entire housing i.e. The Unit shall be mounted on GI Base channel framework.

4. MOTOR AND DRIVE

4.1 Fan motor shall be totally enclosed fan cooled type in IP-55 construction suitable for AC
supply of 415 + 10% V, 3 phases, 50 Hz, IE-3, Motor shall be selected for quiet operation.

6
4.2 DIDW Centrifugal Fans

The fan shall be forward curved, double inlet double width type. The wheel &
housing shall be fabricated from heavy gauge galvanized steel. The fan impeller shall
be mounted on a solid shaft supported to housing with angle iron frame & pillow
block heavy duty ball. The fan shall be selected for lowest noise level. The impeller &
fan shaft shall be statically and dynamically balanced. The fan outlet velocity shall not
be more than 1800 fpm. Fan housing with motor shall be mounted on a common steel
base mounted in side the air handling housing on anti vibration springs mounts or cushy
foot mount The fan outlet shall be connected to casing with the help of fire retardant
canvass. The fan shall be direct driven type. Another fire retardant canvass connection
shall be provided at unit outlet to connect the ducts

5. PRE FILTERS

Each unit shall be provided with a 50 mm thick factory assembled pre filter section
containing cleanable synthetic type air filters having anodized aluminium frame.
The media shall be supported with HDP mesh on one side and aluminium mesh on other
side. Filters face velocity shall not exceed 500 Feet per Minute.

******

7
III-VARIABLE REFRIGERANT FLOW TYPE SYSTEM (VRF SYSTEM)

1. VARIABLE REFRIGERANT FLOW TYPE SYSTEM (VRF System)

The system selected should be modular system, with number of indoors connected to
centrally located outdoor units, as per detail designing given in the tender. The outdoor
units for all the system shall be air cooled type and mounted on terrace of the building.
Indoor units in various areas shall be as per enclosed drawings/Bill of Quantities.

All the VRF air conditioners shall be fully factory assembled, wired, internally piped &
tested. The outdoor unit shall be pre charged with first charge of R410A/407 refrigerant.
Additional charge shall be added as per refrigerant piping at site. All the units shall be
suitable for operation with 415 V + 10%, 50 Hz + 3%, 3 Phase supply for outdoor units
& 220 V + 10%, 50 Hz + 3%, 1 Phase supply for indoor units.

The VRF system shall provide stable, trouble free & safe operation, with flexibility of
operating desired indoor units. The outdoor units must be capable of delivering exact
capacity proportional to the number of indoor units switched on & the heat load in the air
conditioned area. The proportional operation shall be achieved by varying speed of the
compressor in the outdoor units.

The operation of the VRF system shall be through independent wired/ wireless remote
controllers as specified. The entire system shall be integrated with intelligent building
management system of leading vendors like Honeywell / Johnson Controls /
Siemens/Schneider etc, through BAC Net Gateway. The detailing of operation required
through BMS system are detailed under specifications of BMS system.

The system shall be multi-split system with inverter driven scroll compressor for
application with R410A/407 refrigerant and shall be composed of ceiling type indoor
units / 4-way cassette type indoor units / 2-way cassette type indoor units / wall type
indoor unit / floor type indoor unit and an outdoor unit as specified in tender drawings &
Bill of Quantities, with a distributed refrigeration cycle, electrical components and
enclosing cabinets. Both indoor units and outdoor unit shall be properly assembled,
internally piped and wired, thoroughly tested and charged with refrigerant at factory and
shall be topped up at site after erection.

8
Additional charge of refrigerant should be supported by engineering calculation. Each
refrigeration cycle shall be equipped with rotary/scroll compressor, a solenoid valve, a
heat exchanger, an accumulator, and a 4-way valve and flare connection parts.

2. SPECIFICATION OF OUTDOOR UNITS

Outdoors units of the VRV system shall be compact air cooled type.

All the compressors of the outdoor units must be hermetically sealed Inverter type. Each
module of outdoor unit must have all inverter compressors, suitable to operate at heat
load proportional to indoor requirement.

“Anti Corrosive” treatment (Blue Fins) for Al. fins of Condenser Coils is mandatory. The
treatment should be suitable for areas of high pollution and salt laden air.

The outdoor units must be suitable for up to 150 m refrigerant piping between outdoor
unit & the farthest indoor units, total piping of 300 m for all the indoor units. Allowable
level difference between outdoor unit & indoor units shall be 50 m in case of outdoor
unit on top & 40 m in case of outdoor unit at bottom. Allowable level difference between
various indoor units connected to one out door unit shall be up to 15 m.

Back up operation, in case of failure of one of the compressors of outdoor unit, for single
module outdoor units or failure of one of the modules in case of multiple module outdoor
units shall be possible. The VRV outdoor unit shall always be supplying at least 33% of
back up operation, of the full load capacity.

The outdoor unit shall employ system of equal run time for all the compressors, inverter
or on/ off type, within each out door unit – Single Module or Multi Module.

The outdoor units shall be suitable to operate within an ambient temperature range of – 5
Deg C to 45 Deg C, in cooling mode &– 20 Deg C to 15 Deg C in heating mode.

Air cooled condenser shall have Axial Flow, upward throw fan, directly coupled to fan
motors with minimum IP 55 protection. The outdoor unit condenser fan shall be able to
develop external static pressure up to 6 mm of H2O.

The entire operation of outdoor units shall be through independent remotes of indoor
units. No separate Start/ Stop function shall be required.

Starter for the Outdoor Unit compressor shall “Direct on Line” type. Inverter compressor
of the unit shall start first & at the minimum frequency, to reduce the inrush current

9
during starting. Refrigerant control in the outdoor unit shall be through Electronic
Expansion Valve. Complete refrigerant circuit, oil balancing/ equalizing circuit shall be
factory assembled & tested.

The compressor(s) shall be hermetically sealed rotary/scroll and designed for continuous
operation even at high ambient temperatures of Delhi.

All condensing unit should have invertors driven scroll compressor. All invertors driven
scroll compressor should have protection for electronic circuits and elimination of
electromagnetic sound, which may interfere with the control function of the machine.
The unit shall have safety device such as high-pressure switch, fan motor safety
thermostat, invertors overload protector, fusible plugs and fuses for trouble free operation
of the unit. The condenser shall be air cooled, made of Cu. tubes with extended
Aluminum fins. The condenser coil shall be multi-pass, cross-finned tube type, equipped
with highly efficient Aluminum fins, mechanically bonded to oxygen free copper tubes.
The coil shall be cleaned, dehydrated and tested or leakage at the factory. The Cabinets
shall be fabricated out of heavy gauge steel, properly formed for close fit and structural
rigidity. All access panels shall be so constructed as to be quickly and easily removable.
All outside surface shall be finished with powder coating for protection against humid
weather. The condenser fans shall be stepped control depending on no. of compressor
operational & ambient condition, driven and designed to achieve low condensing
temperatures & operate continuously and silently. One out-door unit should be capable to
be connected up-to 16 nos. various indoor unit. All out-door units shall have BMS
compatible communicable controller.

Noise level of outdoor units shall be as per manufacturer standard catalogue, but vendor
must insure the same at the time of commissioning.

The outdoor units shall confirm to Technological Guideline for Harmonic Suppression –
JAEG 9702-1995. High Harmonic Environmental Target Level for Power Distribution
system shall be 5%.

Outdoor units shall be complete with following safety devices:


 High pressure switch
 Fan driver overload protector
 Over current relay
 Inverter Overload Protector
 Fusible Plug

Unit shall be supplied with


 Installation manual
 Operation Manual
 Connection Pipes
 Clamps
Units shall be available in configuration 5 HP, 8 HP upto 60 HP, within increments of 2
HP as specified in tender drawings & Bill of Quantities.

10
3. SPECIFICATIONS FOR INDOOR UNITS

The cooling coils shall be made of Copper Tubing having extended Aluminum fins. The
evaporator coil shall be multi-pass, cross finned tube type, equipped with highly efficient
Aluminum fins, and mechanically bonded to seamless, oxygen free copper tubes. The
coil shall be cleaned, dehydrated and tested for leakage at factory. The cooling coils
circuit shall be fed with liquid refrigerant through the expansion devise

and distributor. The indoor unit shall have two-speed fan motor. The blower shall be
statically and dynamically balanced and designed for silent operation at required airflow
rates against required static pressure. The filters shall be washable synthetic media type
arranged for convenient cleaning and replacement. The drain pan shall be fabricated
out of heavy sheet steel, insulated with 1/4” expanded polyethylene sheet. The casing
shall be of heavy gauge G.I., duly powder coated for weather protection. All indoor units
to be supplied with EU-3 i.e. 20 micron filters.

4. WALL/Cassette MOUNTED UNITS

Wall/ceiling mounted units must be compact & stylish design that does not detract from
the décor of the room.

Each indoor unit must have electronic expansion valve operated by microprocessor
thermostat based temperature control to deliver cooling/ heating as per the heat load of
the room.

The unit must have provision of adding drain pump kit if required & specified. The drain
pump must be suitable to lift drain up to 1000 mm from the bottom of the unit.

Unit must be insulated with sound absorbing thermal insulation material, Polystyrene/
Polyethylene foam. Noise level of the unit shall be as per manufacturer standard
catalogue, but vendor must insure the same at the time of commissioning.

The unit shall be supplied with Resin Net filter with Mold Resistance. The filter shall be
easy to remove, clean & re install.

The unit grille must be washable with soap solution. It shall be possible to set minimum
5 steps of discharge angle by remote controller. It shall be possible to fit drain pipe from
either side of the unit (Left or right)

The unit will be connected in series to a suitable out door unit & it must be possible to
operate the unit independently, through corded/ cordless remote specified in the bill of
quantities. The unit will be further connected to Intelligent Building Management System
(To be supplied by other vendors) & it shall be possible to operate the unit through this
IBMS system.

The unit shall be supplied with following from the factory –

11
Operation Manual
Installation Manual
Installation panel
Paper pattern for installation
Insulation tape/ Clamps/ Screws
The unit must be available in following capacities –
0.8 HP, 1 HP, 1.25 HP, 1.6 HP, 2.0 HP, 2.5 HP

5. CONTROLS SYSTEM FOR VRV AIR CONDITIONING SYSTEM

5.1 WIRED REMOTE CONTROLLER

Wired remote controller shall be supplied as specified in the “Bill of Quantities”.

The controller must have large crystal display screen, which displays complete operating
status.
The digital display must allow setting of temperature with 1 Deg C interval.

Remote shall be able to individually program by timer the respective times for operation
start and stop within a maximum of 72 hours

Remote must be equipped with thermostat sensor in the remote controller that will make
possible more comfortable room temperature control

The remote shall be able to monitor room temperature & preset temperature by
microcomputer & can select cool/ heat operation mode automatically.

The remote must constantly monitor malfunctions in the system & must be equipped
with a “self-diagnosis function” that let know by a message immediately when a
malfunction occurs.

It shall be possible to wire the remote up to 500 RMT.

5.2 WIRELESS REMOTE CONTROLLER

Wireless remote controller shall be supplied as specified in the “Bill of Quantities”


The same operation modes & settings as with wired remote controllers must be possible.
Compact light receiving unit to be mounted into wall or ceiling shall be included.

5.3 CENTRAL REMOTE CONTROLLER

Central Remote controller shall be supplied as specified in the “Bill of Quantities”

Following functions shall be possible


 Control Max 64 Groups (128 indoor units)
 Zone control
 Malfunction code display

12
 All the functions available with wired remote controller
 It should be possible to wire the remote to 1000m

6. BUILDING MANAGEMENT SYSTEM (BAC NET GATEWAY)

The VRV system supplied must be suitable for communication between VRV &
intelligent building management system of other reputed vendors, like Siemens,
Honeywell, Johnson Controls, through BAC Net gateway.
The BAC Net gate way shall utilize the standard communication protocol for the HVAC
industry, to provide easy connection between VRV system & BMS.
The joint Matching Test shall be conducted by VRV vendor with the selected BMS
vendor & entire be commissioned & balance.
Complete operation & monitoring of VRV air conditioning system shall be possible
through the BMS system.

Following major functions shall be possible via BAC net interface on BMS

Monitoring Air conditioning status monitoring


Indoor unit error monitoring
Indoor air inlet temperature monitoring
Filter choke sign monitoring
Control, Operation & Start/ Stop control
Setting Temperature adjustment mode setting
Remote control setting
Temperature setting
Filter sign reset
Display Air conditioner operation setting & status
Set temperature
Indoor unit error
Indoor air inlet temperature
Filter sign

The BAC Net gate way shall be as per ASHRAE 135, Data link - IEE802.3,
BACnet/IP, conformance Class 3, with RS232C port.
BAC Net gateway hard ware shall be suitable for operation between -10 Deg C to 50 Deg
C & humidity range between 0% to 98%, without condensation.

7. AIR CONDITIONING MANAGEMENT SYSTEM

The VRV system supplied must be provided with PC based air conditioning management
system, form the supplier of VRV equipment’s. The required hard ware must be selected,
suitable for up to minimum 128 indoor units.
The air conditioning management system, in broad terms must undertake following
functions
Energy efficiency functions
Control & optimization of system

13
Operation & monitoring
Expanded network functions
Complete operation & monitoring of VRV air conditioning system shall be possible
through this PC based system.

Following major functions shall be possible:

Air conditioning status monitoring


Monitoring Indoor unit error monitoring
Indoor air inlet temperature monitoring
Filter choke sign monitoring
Control, Operation & Start/ Stop control
Setting Temperature adjustment mode setting
Remote control setting
Temperature setting
Filter sign reset
Display Air conditioner operation setting & status
Set temperature
Indoor unit error
Indoor air inlet temperature
Filter sign
Measurement Accurate operation time
Number of switching times
Power consumption (Optional with KWH meter)
Room temperature
Outdoor temperature
Printing History,
Statistics & Setting information

 The A/C management system must be able to connect to existing LANs.


 Remote monitoring of the complete HVAC system shall be possible.
 System shall be capable to take external signal like Security/ Fire for forced shut off.
 Required hardware shall be suitable for operation between -10 Deg C to 50 Dg C &
humidity range, of 0% to 98%, without condensation.

NOTE:-ALL OUT-DOOR UNITS SHALL BE MOUNTED ON MS ANGLE FRAME


STRUCTURE. THE MS ANGLE FRAME STRUCTURE SHALL BE
PAINTED WITH EPOXY PAINT. THE SHADE OF THE PAINT SHALL
BE APPROVED BY APPROVED BY THE ARCHITECT.

8. CONTROLS AND INTERLOCKING

All electrical control devices should be enclosed in the indoor and outdoor units. The
compressor should be protected against breakdown by a quick response over current
relay, a high-pressure switch, a wraparound type oil heater and a discharge gas
thermistor.

14
In addition to the compressor protection devices, the indoor / outdoor fan motor should
be protected by an internal thermostat.

The indoor fan motor shall be directly supplied with the power source from the control
circuit. The functions of these control devices shall compose an electrical sequence of
manual starting and stopping, automatic continuous operation whenever the room
thermostat requires, and the protection devices allow the operation.

The remote control switch should be designed to provide simple operation such as
On/Off, temperature and fan speed only without trouble shooting functions.

The remote control should be BMS compatible for centralized monitoring. All
units/remote control shall have COM port for required interface with BMS.

The required software with open protocol to transfer readings on the BMS shall be
in your scope.

9. REFRIGERANT PIPING WITH COVERING

The indoor and outdoor units shall be connected with 16G Hard Copper refrigerant
piping as per VRV/VRF AC manufacturer requirements. All piping connections for the
units should be performed inside the unit. The refrigerant piping should be insulated with
EPDM Rubber foam/ Nitrile Rubber of minimum 12 MM thick (or as recommended by
manufacturer).

10.0 DRAIN PIPING

Condensate from the evaporator unit shall be drained through properly installed drain
piping designed to prevent any accumulation of condensate in the drain pan.

Drain piping shall be made of 1.1/4" dia / 2" dia rigid UPVC pipe of 6 Kg/Sq cm.
pressure rating with water tight threaded connections, leading from the room unit to a
suitable drain point. Complete drain piping shall be made leak proof and water tight by
means of precise installation and the use of leak proof sealant/adhesives.

Insulation of drain piping will be done by elastomeric EPDM Rubber foam / EPDM
to be done with thickness recommended by manufacturer.

This system includes the AC VRV ODU system comprising of the following:

Technical Data

AIRCONDITIONERS 16 HP 18HP 20HP 22HP

Compressor
1. Make/Model

15
2. Type 100% All Inverter
3. Nominal Capacity
4. Nos per unit
5. Power Supply / phase

Evaporator coil
1. Face area
2. Rows deep
3. Fins/inch
4. Air out evaporator O CDB

Evaporator fan
1. Rated air quantity
2. RPM
3. No of fans
4. Power supply
5. Interconnecting cable size

Condenser coil
1. Face Area
2. Rows deep
3. Air entering condenser O CDB
4. Outside Design Condition O CDB

Condenser Fan
1. Diameter
2. Rate air quantity
3. R.P.M
4. No. of Fans.

Condenser Fan Motor


1. Power supply
2. R.P.M.

Total Power consumed (KW)

Overall Dimensions

Refrigerant R410A

16
IV SPLIT SYSTEM AIRCONDITIONERS

1. SCOPE

The contractor shall supply, installation, testing and commissioning of split system air
conditioners as per schedule of quantity enclosed. The system shall be complete in all
respects and comply with the specifications as given below.

2. OUTDOOR UNIT - CONDENSING UNITS

2.1 Each condensing unit shall be complete with hermetic Invertor/rotary/scroll


compressor(s), aircooled condenser, condenser fans with motors, internal piping,
switches and internal wiring and shall be enclosed in a weather proof out door type
housing.

2.2 The compressor shall be hermetic, with enclosed gas cooled motor. The compressor's
shall be suitable for green refrigerant.

2.3 The condenser coil shall be air cooled type with aluminium fins and copper tubes and
necessary refrigerant connections. The copper tubes shall not be less than 1/2" O.D.

2.4 The condenser air fans shall be propeller type direct driven, each complete with motor.
The air quantity and area of the condenser shall be adequate for working in the specified
out door conditions.

2.5 The casing shall be fabricated from galvanised steel, zinc phosphated and finished with
baked enamel paint. The casing shall make the whole unit fully weather proof, suitable
for out door installation.

2.6 The unit shall include a remote control assembly with thermostat and speed switches.

2.7 The necessary charge of refrigerant gas and lubricated oil shall be provided to run
the system.

3. INDOOR UNIT

3.1 HIGH WALL MOUNTED TYPE

17
The unit shall be decorative wall mounted type. The cabinet is constructed out of durable
flame resistance body and shall include pre filter, fan section, coil section, etc. The
body shall be light in weight. The indoor unit shall be of approved model & colour by
Engineer-in-charge.

The fan shall be aerodynamically designed diffuser turbo fan type. The fan shall be
mounted directly on motor shaft having supported from housing. The fan shall be direct
driven type.

The cooling coil shall be of seamless copper tubes, and shall have continuous aluminium
fins. The fins shall be spaced by collars forming integral part of the fins. The tubes shall
be staggered in the direction of air flow. The fins shall be uniformly bonded to the tubes
by mechanical expansion of the tubes. The coils shall be tested against leaks.

Unit shall have filter cleanable type of resin net (with mold resistant) fixed to an
intergrally moulded plastic frame. The filter should be slid away type but neatly inserted.

Unit shall have a external attractive casing for supply and return air.

Control

Each unit shall be with corded remote controller to operate maintain inside conditions.

Testing

The indoor unit shall be tested to measure air quantity and coil performance by
measuring temperature difference, and then calculating the capacity.

3.2 CASSETTE TYPE UNITS

The units shall be ceiling mounted type. The housing of the unit shall be of powder
coated galvanized steel and shall include pre filter, fan section, coil section, etc. The
body shall be light in weight and shall be able to suspend from four corners.

The fan shall be Aerodynamically designed diffuser turbo fan type. The fan shall be
mounted directly on motor shaft having supported from housing. The fan shaft shall be
statically and dynamically balanced. The fan shall be direct driven type.

The cooling coil shall be of seamless copper tubes, and shall have continuous aluminium
fins. The fins shall be spaced by collars forming integral part of the fins. The
tubes shall be staggered in the direction of air flow. The fins shall be uniformly bonded
to the tubes by mechanical expansion of the tubes. The coils shall be tested against
leaks.

Unit shall have filter cleanable type of resin net (with mold resistant) fixed to an
intergrally moulded plastic frame. The filter should be slid away type but neatly inserted.

18
Unit shall have a external attractive panel for supply and return air. Unit shall have
two/four way supply air grilles on sides and return air grille in centre.

Each unit shall have high lift drain pump, fresh air intake provision (if required), low gas
level detection system.

Each unit shall have an electronic expansion valve which control refrigerant flow rate in
respond to load variations of room (wherever specified).

The computerized PID control shall be used to maintain a correct room temperature.
Each unit to be provided with microprocessor thermostat for cooling & heating. The unit
shall be capable to program its life cycle, through microprocessor based panel, for equal
running and idle period of the unit.

Control

Each unit shall be with corded remote controller to operate maintain inside conditions.

Testing

The indoor unit shall be tested to measure air quantity and coil performance by
measuring temperature difference, and then calculating the capacity.

4. AIR CURTAIN UNIT

4.1 Scope

The scope of this section comprises the supply, erection, testing and commissioning of
Air Curtains units conforming these Specifications and in accordance with the
requirements of the Drawings and of Schedule of Quantities.

4.2 Type

The Air Curtain units are Centrifugal Type Non Re-Circulating, preferably installed
horizontal to the ground. Installed with anchor fasteners to the wall or mounted to the
ceiling or frame with proper supports. The discharge nozzle shall be uniform all through,
and the Air curtain shall fully cover the Door opening.

4.3 Capacity

The Air Curtain should be sized according to the width of the Door, and Air throw shall
be selected as per the height of the Door, or the capacities shall be as shown on Drawings
and indicated in Schedule of Quantities.

4.4 Cabinets

19
Cabinets are constructed of 18 SWG CRC iron sheet steel and powder coated. Corners
are rounded without break lines. The cabinets have good finish and the access panels and
the mountings are so provided for easy removal. All the nuts and bolts visible are nickel
coated.

4.5 Blower Housing

The blower housing are constructed of pre coated sheet of 26 SWG Thickness, with
plastic Molded end plate in ABS 300 with plastic Inward cones. The Housing is
engineered in vortex design so as to provide the required outlet velocity with minimum
noise level.
4.6 Fans

Fans installed in Air Curtain are centrifugal, forward curved double inlet, lightweight
Dynamically balanced made in Plastic (ABS 300 Fire Retardant / Anti Static) by the
process of Injection Molding. Impellors have Die Cast Aluminum double-ended Hubs.
Blades are made in Aerodynamic Design. Performance of Impellor is tested as per
AMCA Standards and Guaranteed.

4.7 Motor

Motor are 220  10% volts, 50 cycles single phase, four pole with START & RUN type
capacitors. Motors have been provided with Thermal overload protectors. The Core is
made in “CRNO” (Cold Rolled Non Oriented) Silicon Sheet. Motors have extended shaft
on both the sides, with 15mm as the shaft Diameter. The Motors have 2RS Grade of
Bearings, for friction free and noise less movement.

4.8 Motor Mounting

Motor Mounting have been so provided that it should have 24 Nos. of vibration isolators
between each motor and the chassis, so placed that it can dampen vibration in all the axis
i.e. X, Y and Z. Vibration isolator are made in silicon rubber, to resist Temperature rise.

4.9 Painting

Powder Coating is done on the unit. The colour of the powder used is Ivory from a
reputed manufacturer. Proper treatment shall be done on each panel before powder
coating. The Machines are even available in Stainless Steel Grade.

4.10 The air curtain shall be controlled by limit switch operation and shall start when the dock
door shutter is opened.

5. MISCELLANEOUS

5.1 The unit shall have control panel, housing the starting switches, contactor, relays etc.

5.2 Isolation pads shall be provided under the units.

20
5.3 Drain line shall be provided from fan coil unit upto drain trap. (To be priced separately).

5.4 Suitable M.S. angle iron supporting frame shall be provided for the condensing unit and
supporting arrangement for the indoor units.

5.5 Interconnecting power and control cabling shall be provided between condensing unit
and evaporator unit.

******
V Control Panel, Motors and Switchgears

1. General :

1.1 The motor and switchgears required for various items shall generally be as per
specifications given below all electric motors shall be suitable for 3 phase, 50 cycles, 415
volts A.C. Supply +/- 10%.

2. Switch Panel Board :

2.1 The main L.T. Panel board shall be extendible type on both sides, having in it all
switches, starters and accessories and completely factory prewired. It shall be suitable
for voltage systems upto 500 volts, 3 phase, 50 Hz, 4 wire supply capable of
functioning satisfactorily in temperatures of 45oC and rupturing capacity not below 35
MVA.

2.2 The boards shall be fabricated from 2.0 mm thick, cold rolled M.S. sheets. The front
opening door panels shall be from 2 mm thick, cold rolled M.S. Sheets. Suitable
stiffners shall be used in fabricating the housing. A clear space of 450 mm shall be left
at the bottom. All steel members shall first be degreased, then descaled using dilute
sulphuric acid and a suitable phosphating process then the boards shall be given 2 coats
of red oxide primer and finished with stove enamel finish. The switch board shall be
dust proof and vermin proof. The panel shall generally confirm to is 8623 (fully
confirmity not called for). It shall be flush in front and back. The panel shall have front
and rear access.

2.3 Cable compartment of adequate size shall be provided in the main distribution board
for easy termination of all incoming and outgoing cables entering from bottom or top.
Adequate support shall be provided in cable compartment to support cables. All
incoming and outgoing switch terminals shall be brought out to terminal blocks in cable
compartments.

2.4 Air break draw out type circuit breakers shall be conform to IS : 2516

2.5 All switches below upto 32 Amps. shall be MCB of required rating and all switches 63
Amps and above shall be MCCB.

21
2.6 No MCCB/MCB, starter or accessories shall be provided in the bottom 450 mm of the
panel.

2.7 The bus bars shall be of aluminium strips of minimum specified ratings with PVC
sleeves of appropriate colour. There shall be adequate clearance between phase to phase
and phase to neutral strips.

2.8 Items such as ammeters, switches etc shall be located close to the corresponding
switchgear, and otherwise all items shall be arranged in a neat symmetrical pattern.
2.9 Every starter/contactor etc. shall be controlled by a switch of adequate rating as
listed above.

2.10 A voltmeter and ammeter shall be provided to indicate incoming voltage alongwith a
rotary phase selection switch.

2.11 Ammeters shall be provided for all motors of 10 HP and higher ratings. An ammeter to
measure total current consumption should also be provided in such cases.

2.12 Each switch, ammeter etc. shall be provided with a name plate to indicate controlled
items.

2.13 Panel fabrication drawings shall be got approved before fabrication.

2.14 All ammeters and voltmeters where specified shall be of 144 x 144 mm size.

2.15 Neon type indicating lamps in approved colours shall be provided for the 3 phases and
for on status of all controlled devices.

2.16 All the switches/breakers shall be interlocked with door so that the unit cannot be
closed unless the unit door is closed. The interlock shall also prevent opening the unit
door unless the switch/breaker is in off position.

2.17 Defeat arrangement shall be provided for deliberate inspection of switch/breaker


without having to switch off the unit.

2.18 All the units pertaining to a motor shall be incorporated in one cabin i.e. switch, starter,
cts ammeter single phasing preventor, indicating lamps, etc.

2.19 All the switch gear shall be earthed to the earth bus.

2.20 Earth shall be extended to each compartment to the door by means if a flexible, insulated
copper conductor with crimped legs on either side.

2.21 Etched plastic name plates shall be provided for all the incoming, outgoing switch
gears etc.

22
2.22 The doors of the switch compartments and cable access shall be hinged type and that of
busbars shall be fixed type.

2.23 The knobs of the hinged doors shall be provided with a locking arrangement to prevent
them from falling down when they are unscrewed for opening the doors.

2.24 All panel doors shall have rubber gasket.

2.25 All the control and auxiliary wiring shall be carried out with PVC insulated copper
conductor of proper colour code.

2.26 Ammeters for all the motors upto 50 HP shall be direct reading type.

2.27 Ammeters for motors of 50 HP and above and for incoming current shall be operated
with a selector switch.

2.28 Each panel shall be provided with suitable size of earth bus at the rear of the panel and
two earth terminals on either side.

2.29 Suitable printed PVC ferrules shall be provided for all the conductors for easy
identification.

2.30 The power wiring from the switches/unit breakers to the starters shall be carried out
using colour coded, PVC insulated copper conductors crimped with lugs.

2.31 The out going of starter shall also be PVC insulated colour coded copper conductor
crimped with lugs and terminated on a terminal block of proper rating.

2.32 A danger notice plate of 200 mm x 150 mm of mild steel at least 2 mm thick vitreous
enamelled white on both sides and with inscriptions in signal red colour on front side
shall be provided on the panel board.

3. Subsidiary Panels (With Multiple Switches) :

3.1 Subsidiary panels shall be provided for equipment located away from the plant room,
such as air handling units, cooling towers etc.

3.2 The construction of these panel should be similar to the main panel.

3.3 The sub panel shall be wall hung type and as compact as possible.

3.4 The bus bars shall be of aluminium strips of minimum specified ratings with PVC
sleeves of appropriate colour. There shall be adequate clearance between phase to phase
and phase to neutral strips.

3.5 Every starter/contactor etc. shall be controlled by a switch of adequate rating.

23
3.6 A voltmeter and ammeter shall be provided to indicate incoming voltage alongwith a
rotary phase selection switch.

3.7 Each switch, ammeter etc. shall be provided with a name plate to indicate controlled
items.

3.8 Panel fabrication drawings shall be got approved before fabrication.

3.9 All ammeters and voltmeters where specified shall be of 96 x 96 mm size.

3.10 All the switches/breakers shall be interlocked with door so that the unit cannot be
closed unless the unit door is closed. The interlock shall also prevent opening the unit
door unless the switch/breaker is in off position.

3.11 Defeat arrangement shall be provided for deliberate inspection of switch/breaker without
having to switch off the unit.

3.12 All the switch gear shall be earthed to the earth bus.

3.13 Etched plastic name plates shall be provided for all the incoming, outgoing switch
gears etc.

3.14 The doors of the switch compartments and cable access shall be hinged type and that of
busbars shall be fixed type.

3.15 The knobs of the hinged doors shall be provided with a locking arrangement to prevent
them from falling down when they are unscrewed for opening the doors.

3.16 The doors shall have rubber gasket.

3.17 All the control and auxiliary wiring shall be carried out with PVC insulated copper
conductor of proper colour code.

3.18 Each panel shall be provided with suitable size of earth bus at the rear of the panel and
two earth terminals on either side.

3.19 Suitable printed PVC ferrules shall be provided for all the conductors for easy
identification.

3.20 The power wiring from the switches/unit breakers to the starters shall be carried out
using colour coded, PVC insulated copper conductors crimped with lugs.

3.21 The out going of starter shall also be PVC insulated colour coded copper conductor
crimped with lugs and terminated on a terminal block of proper rating.

24
3.22 A danger notice plate of 200 mm x 150 mm of mild steel at least 2 mm thick vitreous
enamelled white on both sides and with inscriptions in signal red colour on front side
shall be provided on the panel board.

3.23 Neon type indicating lamps in approved colours shall be provided for the 3 phases and
for on status of all controlled devices.

4. Subsidiary Panels (With Single Switch) :


4.1 Subsidiary panels shall be provided for equipment located away from the plant room,
such as air handling units, cooling towers etc.

4.2 The construction of these panel should be similar to the main panel and shall have all
related accessories.

4.3 The sub panel shall be wall hung type and as compact as possible.

4.4 Every starter shall be controlled by a switch of adequate rating.

4.5 A voltmeter shall be provided to indicate incoming voltage alongwith a rotary phase
selection switch.

4.6 Each switch, voltmeter etc. shall be provided with a name plate to indicate controlled
items.

4.7 Panel fabrication drawings shall be got approved before fabrication.

4.8 The voltmeter where specified shall be of 96 x 96 mm size.

4.9 All the switches shall be interlocked with door so that the unit cannot be closed unless
the unit door is closed. The interlock shall also prevent opening the unit door unless the
switch is in off position.

4.10 Defeat arrangement shall be provided for deliberate inspection of switch without having
to switch off the unit.

4.11 All the switch gear shall be earthed to the earth bus.

4.12 Etched plastic name plates shall be provided for all the incoming, outgoing switch gears
etc.

4.13 The doors of the switch compartments and cable access shall be hinged type and that of
busbars shall be fixed type.

4.14 The knobs of the hinged doors shall be provided with a locking arrangement to prevent
them from falling down when they are unscrewed for opening the doors.

4.15 The doors shall have rubber gasket.

25
4.16 All the control and auxiliary wiring shall be carried out with PVC insulated copper
conductor of proper colour code.

4.17 Each panel shall be provided with suitable size of earth bus at the rear of the panel and
two earth terminals on either side.

4.18 Suitable printed PVC ferrules shall be provided for all the conductors for easy
identification.

4.19 The power wiring from the switches/unit breakers to the starters shall be carried out
using colour coded, PVC insulated copper conductors crimped with lugs.

4.20 The out going of starter shall also be PVC insulated colour coded copper conductor
crimped with lugs and terminated on a terminal block of proper rating.

4.21 A danger notice plate of 200 mm x 150 mm of mild steel at least 2 mm thick vitreous
enamelled white on both sides and with inscriptions in signal red colour on front side
shall be provided on the panel board.

4.22 Neon type indicating lamps in approved colours shall be provided for the 3 phases and
for on status of all controlled devices.

5. Squirrel Cage Motors :

5.1 The squirrel cage motors shall be either screen protected or totally enclosed fan cooled,
depending on the application and as stated in “schedule of equipment” all motors shall
conform to IS 325/1978 motors shall also confirm to IS=1231 for foot mounted motors
and IS:2223 for flange mounted motors.

5.2 The stator windings shall be with class b insulation.

5.3 Motors shall be provided with ball/roller bearings. Bearings shall have ample capacity to
deal with any axial thrust. Suitable grease nipple shall be provided for regreasing the
bearings.

5.4 Motors shall be provided with a cable box for terminating the PVC insulated, PVC
sheathed armoured aluminium cables.

6. Starters :

6.1 The type of starters to be provided for the motors shall be as follows :

6.1.1 Squirrel cage motors upto 7.5 HP : direct on line.

6.1.2 Squirrel cage motors above 7.5 HP: automatic star delta. (Except compressor motor).

26
6.1.3 Compressor motor: automatic auto transformer starter.

6.1.4 All starters shall have auxiliary contacts for interlocking different machines, connecting
indicating lights, controls, alarms, etc.

6.1.5 All starters shall be provided with separate single phasing preventors.

6.2 Direct On-Line Starters


6.2.1 These starters shall have heavy duty air break contactors of suitable rating.

6.2.2 These starters shall be complete with adjustable overload relays on all three phases,
single phase preventing device and under voltage release. The starters should be "hand
reset" type.

6.2.3 The "No Volt Coil " of these starters shall be 220 volts whenever any controls on
safety devices are connected in the starters circuits, otherwise standard 415 volts coils
may be used. There shall be on-off push button for each starter unless remote operation
of the starter is required.

6.3 Motor starter shall be in accordance with IS 1882 the starter shall be totally enclosed
metal clad , dust and vermin proof construction. The starter shall be of continuous
rating.

6.4 Contactors shall have the number of poles as required for appropriate duty. The making
capacity of the starters shall be as per AC 23 of ISS.

6.5 Installation of Motor

6.5.1 Installation of the motor shall be in accordance with IS-900.

6.5.2 The motor along with its driven machine or equipment shall be provided with vibration
isolation arrangement motors shall generally be provided with slide rails fixed to the
base units nuts and bolts to facilitate belt installation and subsequent belt tension.

6.5.3 Motors shall be wired as per the detailed specifications and drawings all the motor
frame shall be earthed with 2 Nos. of earthing conductors.

6.5.4 Motors shall be tested at works in accordance with the relevant indian standard
specifications and test certificates shall be furnished in tripticate.

Note : Rubber mats of 1100 volts capacity shall be laid in front of panel as per site
requirement, and no extra shall be paid.

7. Painting :

27
All sheet steel work shall undergo a process of degreasing, pickling in acid, cold
rinsing, phosphating, passivating and then sprayed with a high corrosion resistant primer.
The primer shall be baked in oven. The finishing treatment shall be by application of
synthetic enamel paint of approved shade and stoved.

*****

VI AIR DISTRIBUTION

SHEET METAL WORK:

1. GENERAL

This section comprises of supply, fabrication, installation and testing of all sheet metal
ducts and supply, installation, testing and balancing of grilles, registers and diffusers, in
accordance with these specifications and the general arrangement is shown on the
Drawings.

2. DUCT MATERIAL

Galvanizing shall be Class VII – light coating of zinc, nominal 80 gm/sq. m surface area
and Lock Forming Quality prime material along with mill test certificates. In addition, if
deemed necessary, samples of raw material, selected at random by owner’s site
representative shall be subject to approval and tested for thickness and zinc coating at
contractor's expense.

Note:
Ducting sheet thickness variation more than +/- 0.01 mm shall not be allowed.

3. FABRICATIONS STANDARD AND EQUIPMENT

All duct construction and installation shall be in accordance with IS.655.2006 and SMACNA
standards as specified in BOQ.

28
In addition ducts shall be factory fabricated utilizing the following machines to provide the
requisite quality of ducts.
 Coil (Sheet metal in Roll Form) line to facilitate location of longitudinal seams at
corners/folded edges only, for required duct rigidity and leakage free characteristics. No
longitudinal seams permitted along any face side of the duct.
 All ducts, transformation pieces and fittings to be made on CNC profile cutter for requisite
Accuracy of dimensions, location and dimensions of notches at the folding lines.
 All edges to be machine treated using lock formers, flingers and rollers for turning up
edges.

GAUGES, BRACING BY SIZE OF DUCTS

All ducts shall be fabricated from galvanized steel/ Aluminium of the following
thickness, as indicated as below:

IS – 655 –2006

29
SMACNA – 2005 --- 500 PA -TDF DUCTS

30
JTR and MPT shall be provided with tie rod of minimum 6mm dia with suitable gasket and
washer etc., to ensure zero leakage.
In case MPT installation is not possible due to site constraint, the quoted rates shall include the
cost of external bracing in lieu of MPT. The external bracing shall be made of MS angle of size
25mm x 25mm x 3mm and painted with primer and two coats Aluminium paint.

31
4. DUCT CONSTRCUTION
All ducts shall be fabricated and installed in workmanlike manner, conforming to relevant
SMACNA codes.
 Ducts so identified on the Drawings shall be acoustically lined and insulated from outside as
described in the section “Insulation” and as indicated in schedule of Quantities. Duct dimensions
shown on drawings, are overall sheet metal dimensions inclusive of the acoustic lining where
required and indicated in Schedule of quantities. The fabricated duct dimensions should be as
per approved drawings and care should be taken to ensure that all connecting sections are
dimensionally matched to avoid any gaps.
 Ducts shall be straight and smooth on the inside with longitudinal seams shall be airtight and
at corners only which shall be either Pittsburgh or snap button as per SMACNA practice, to
ensure air tightness.
 All ducts up to 75cms width within conditioned spaces shall have slip and drive (C & S/SS)
joints. The internal ends of slip joints shall be in the direction of airflow. Care should be taken to
ensure that S/SS Cleats are mounted on the longer side of the duct and Cleats on the shorter side.
Ducts and accessories within ceiling spaces, visible from air‐conditioned areas shall be provided
with two coats of mat black finish paint.
‐Changes in dimensions and shape of ducts shall be gradual (between 1:4 and 1:7). Air‐turns
(vanes) shall be installed in all bends and duct collars designed to permit the air to make the turn
without appreciable turbulence.
 Ducts shall be fabricated as per details shown on Drawings. All ducts shall be rigid and shall
be adequately supported and braced where required with standing seams, tees, or angles, of
ample size to keep the ducts true to shape and to prevent buckling, vibration or breathing.
 All sheet metal connection, partitions and plenums, required to confine the flow of air to and
through the filters and fans, shall be constructed of 18 gauge GSS / 16gauge aluminium,
thoroughly stiffened with 25mm x 25mm x 3mm galvanized steel angle braces and fitted with all
necessary inspection doors as required, to give access to all parts of the apparatus. Access doors
shall be not less than 45cm x 45cm in size.
 Plenums shall be shop/factory fabricated panel type and assembled at site. Fixing of
galvanized angle flanges on duct pieces shall be with rivets heads inside i.e. towards GS sheet
and riveting shall be done from outside.

32
 Self adhesive Neoprene rubber / UV resistant PVC foam lining 5mm nominal thickness
instead of felt shall be used between duct flanges and between duct supports in all ducting
installation.

5. INSTALLATION PRATICE
All ducts shall be installed generally as per tender drawings, and in strict accordance with
approved shop drawings to be prepared by the Contractor:

 The Contractor shall provide and neatly erect all sheet metal work as may be required to carry
out the intent of these Specifications and Drawings. The work shall meet with the approval of
Owner’s site representative in all its parts and details
 All necessary allowances and provisions shall be made by the Contractor for beams, pipes, or
other obstructions in the building, whether or not the same are shown on the drawings. Where
necessary to avoid beams or other structural work, plumbing or other pipes, and conduits, the
ducts shall be transformed, divided or curved to one side (the required area being maintained) all
as per the site requirements.
If a duct cannot be run as shown on the drawings, the contractor shall install the duct between
the required points by any path available in accordance with other services and as per approval
of owner’s site representative.
 All ductwork shall be independently supported from building construction. All horizontal
ducts shall be rigidly and securely supported, in an approved manner, with trapeze hangers
formed of galvanized steel rods and galvanized steel angle/channel or a pair of brackets,
connected by galvanized steel rod under ducts. The spacing between supports should be not
greater than 2.0 meter. All vertical ductwork shall be supported by structural members on each
floor slab. Duct supports may be through galvanized steel insert plates left in slab at the time of
slab casting. Galvanized steel cleat with a hole for passing the hanger rods shall be welded to the
plates. Trapeze hanger formed of galvanized steel rods shall be hung through these cleats.
Wherever use of metal insert plates is not feasible, duct support shall be through dash/anchor
fastener driven into the concrete slab by electrically operated gun. Hanger rods shall then hang
through the cleats or fully threaded galvanized rods can be screwed
into the anchor fasteners.

33
 Ducting over furred ceiling shall be supported from the slab above or from beams after
obtaining approval of Owner’s site representative. In no case shall any duct be supported from
false ceiling hangers or be permitted to rest on false ceiling. All metal work in dead or furred
down spaces shall be erected in time to occasion no delay to other contractor’s work in the
building.

 Where ducts pass through brick or masonry openings, it shall be provided with 25mm thick
TF quality expanded polystyrene around the duct and totally covered with fire barrier mortar for
complete sealing.

 All ducts shall be totally free from vibration under all conditions of operation. Whenever
ductwork is connected to fans, air handling units or blower coil units that may cause vibration in
the ducts, ducts shall be provided with a flexible connection, located at the unit discharge.
Flexible connections shall be constructed of fire retarding flexible heavy canvas sleeve at least
10cm long securely bonded and bolted on both sides. Sleeve shall be made smooth and the
connecting ductwork rigidly held by independent supports on both sides of the flexible
connection. The flexible connection shall be suitable for pressure at the point of installation.

 Duct shall not rest on false ceiling and shall be in level from bottom. Taper pieces shall taper
from top.

6. DAMPERS

All dampers shall be of Galvanised iron construction with louver dampers of robust
construction and tightly fitted. The design, method of handling, and control shall be
suitable for the location and service required.

The damper shall be of opposed blade type. The sheet thickness of blade shall be 0.8 mm
and of the frame shall be 1.0 mm.

Dampers shall be provided with suitable links, levers and quadrants as required for their
proper operation; control or setting devices shall be made robust, easily operable and
accessible through suitable access doors in the ducts. Every damper shall have an
indicating device clearly showing the damper position at all times.

34
Dampers shall be placed in ducts and at every branch of supply air duct connections,
whether or not indicated on the drawings, for the proper volume control and balancing of
the system.

All the dampers at grille collars shall be of extruded aluminium construction with louver
dampers of robust construction and tightly fitted to the grilles/diffusers at factory.

7. FIRE & SMOKE DAMPERS

i) Fire dampers shall be provided in all supply air ducts and return air ducts (where
provided), return air passage in the air – handling unit room and at all floor
crossings. Access door will be provided in the duct before each set of fire
dampers.

ii) Fire dampers shall be multi blade louvers type. The blade should
remain in the air stream in open position and shall allow maximum
free area to reduce pressure drop and noise in the air passage. The
blades and frame shall be constructed with minimum 1.6mm thick
galvanized sheet and shall be factory fitted in a sleeve made out of
1.6mm galvanized sheet of minimum 400mm long. It shall be
complete with locking device, motorized actuator and control panel.

iii) Fire dampers shall be motorized smoke and fire dampers type. It
shall be supplied with spring loaded UL stamped fusible link to
close fire damper in the event of rise in duct temperature. Fire
damper shall also close on receipt of fire alarm signal to cut off air
supply instantaneously. An electric limit switch shall also be
operated by the closing of fire damper, which in turn shall switch off
power supply to AHU blower motor.

iv) Fire dampers shall be CBRI tested and certified for 90 minutes rating against
collapse and flame penetration as per UL 555 – 195. (Under writers laboratories).

v) Fire dampers shall be compatible with the fire detection system of building and
shall be capable of operating automatically through an electric motor on receiving
signal from fire alarm panel.

ii) Necessary wiring from fire alarm panel up to AHU electric panel shall
be provided by the other sub associates of fire alarm package and
further from AHU electric panel to fire damper shall be provided by
air conditioning contractor.

iii) Zero leakage dampers shall be defined leakage classes by the


maximum allowable leakage throw a closed damper at 4 inches water

35
gauge measured in cfm per sq.ft. of damper area. All zero leakage
dampers shall be as per class I (8 cfm per sq.ft. at 4 inch WG).

viii) Suitable size actuator shall be used to modulate/control the dampers. Assembly of
both fire damper / zero leakage damper and actuator shall be UL tested.

8. FUSIBLE LINK FIRE DAMPER

Fire Dampers meeting or exceeding the following specification shall be furnished and
installed at locations shown in the plans or described in the schedules.
Dampers shall be CBRI certified and meet the fire resistance rating of 90minutes and
shall be UL555 classified. Fire Damper frame shall be galvanized steel of 1.6mm
thickness, formed into a structural hat channel in 4-piece construction with integral
overlapping gusset reinforcements (screws are not acceptable) in each corner to assure
square corners. Top and Bottom frame members shall be low profile design to maximize
the free area on small dampers. Damper Blades shall be single skin galvanized steel of
1.6mm thickness and must have 3 accurately roll formed longitudinal grooves for
reinforcement and proper closure and operation. The blades shall be arranged in parallel
to provide positive shut off. Each Blade shall have axles supported on both sides with
sintered bronze self-lubricating bearings turning in an extruded hole in the frame. All
Blades shall be interconnected using linkage concealed in the frame and must be operated
by a heavy duty spring.
Each Damper shall be operated through a UL stamped fusible link rated at 74 Degree C.
The closing of the fire damper shall be through a heavy duty spring mounted under
appropriate tension on a jackshaft running across the width of the damper, to close the
blades in the event of fusible link disintegration.

Option of indication of Blade Position should be made available either through a manual
lever or thru an electrically operated open/close switch (if needed by the specifier).
Each Damper shall be supplied with a factory mounted sleeve made from Minimum
1mm thick galvanized steel of minimum 508mm length.

The Contractor must provide an access door of size 600mm x 600mm, in the duct close
to the damper to facilitate periodic inspection and maintenance of the damper.

Fire dampers shall be CBRI tested and certified for 90 minutes rating against collapse
and flame penetration as per UL 555 – 195. (Under writers’ laboratories).

9. SUPPLY AIR REGISTERS/GRILLES

Supply air registers shall be of approved make and of aluminium construction with
individually adjustable bars. Supply air registers shall be linear type, with removable
key-operated volume control dampers. The outer frame shall be made from drawn
aluminium sections.

All registers shall be selected in consultation with the Engineer.-in-charge, Different


spaces shall require horizontal or vertical face bars, and different width of margin

36
frames. All grilles in processing area shall be double louvered, dock door supply grille
should be linear with 0deg angle and other linear grille shall be 15degC.selection should
be required as per shop drawings.

All registers shall have a soft, continuous rubber gasket between the periphery of the
register and the surface on which it has to be mounted.

Registers shall be adjustable pattern as such grill bar shall be pivotable to provide pattern
with 0 to 100 degree horizontal arc and upto 30 degree deflection up or down. Bars shall
hold deflection settings under all conditions of velocity and pressure.
Bars longer than 45 cm shall be reinforced by a set back vertical member.
Registers shall be given a rust inhibiting prime coat and factory applied powder coated
finish of approved colour. Selection of grille shall be as per requirement with final GFC
drawings.
10. SUPPLY AIR DIFFUSERS
Diffusers shall be of approved make and of Aluminium construction, square / rectangular
in shape with flush fixed pattern or adjustable flow pattern. Diffusers for different
spaces shall be selected in consultation with the Engineer-in-charge.

All supply air diffusers shall be equipped with removable key-operated volume control
dampers. Anti-smudge ring may be required in specific applications. The outer shell
and diffusing assembly shall be made out of powder coated drawn aluminium section
respectively.

11. EYE BALL TYPE JET NOZZELS

The jet nozzels shall be made out of drawn sections of aluminium. The nozzels shall
have the air control arrangement and the adjustable angle for throw. The nozzels shall be
complete with butterfly type dampers, mounting ring, air tight gaskets and fixing
arrangement. The jet nozzels shall generally be of circular shape. Selections of the same
shall be submitted before placing the order. All nozzles shall be selected based on
airquantity, throw & pressure drop.

12. OUTSIDE AIR LOUVERS

Exhaust/Fresh air louvers of 112mm thick high performance (55% free area) drainable
fixed louver type powder coated Aluminium frame and blades. Mullions to be sliding
interlock type with integral internal drain. Jamb and mullion drains to be open on front
face in order to direct water away from inside of louver. Blades to be one piece
extrusions with gutters design to catch and direct water to jumb and mullion drains.
Fastners to be aluminium. Louvers to have framed 13 mm mesh removable mill finish
aluminium bird screens. All louvers for toilet exhaust shall be design with velocity of
500FPM.

13. TESTING AND BALANCING


After completion of the installation of the complete air distribution system, all ducts shall
be tested for air leaks. Before painting the interiors, air distribution system shall be

37
allowed to run continuously for 48 hours for driving away any dust or foreign material
lodged within ducts during installation.
The entire air distribution system shall be balanced using approved anemometer. Air
quantities at the fan discharge and at various outlets shall be identical to, or less than 5
percent in excess of, those specified and quoted. Leakage in each air distribution system
shall be within 3 percent so that supply air volume at each fan shall be identical to, or no
greater than 3 percent in excess of, the total air quantity measured at all supply outlets
served by the fan. Branch duct adjustments shall be made by volume or splitter dampers.
Dampers shall be permanently marked after air balance is complete so that these can be
restored to their correct position if disturbed at any time. Complete air balance report
shall be submitted to the Engineer.-in-charge. for scrutiny and approval, and six copies
of the approved report shall be provided with completion documents.

38
VII Electric Wiring

1. General :

The electric wiring of motors for compressors, pumps, air handling units etc. As well
as controls, heaters etc. and earthing of all equipment shall be carried out as per
specifications given hereunder.

2. Wiring for Motors, Heaters etc :

2.1 The wiring for above equipment shall be carried out in conduits or using PVC armoured
cables.

2.2 The PVC armoured power cable for use on 415 volts system shall be 3 or 3.5 core
with aluminium conductors and be of 1100 volts grade, as per IS 1554 part I-1964.
The cross section of the cable shall be to suit the load or rating of the equipment. The
cable shall be aluminium conductor PVC insulated single wire/strip armoured with
overall PVC sheathing.

2.2.1 The cables shall be laid as per IS-1255/1967, Indian Standard Code of Practice.

2.2.2 The cables shall be laid, as per drawings or along a short and convenient route between
switch board and the equipment, either in trenches, on wall or on hangers, supported
from the slab. Cable routing shall be checked on the site to avoid interference with
structure, equipment etc. Where more than one cables are running close to each other,
proper spacing should be provided between them.

2.2.3 The radius of bends of the cable should not be less than 12 times the radius of cable
to prevent undue stress and damage at the bends, the cables should be supported with
wooden cleats fixed on M.S. Supports, when running in trenches, wall or
ceiling suspended hangers. When laid under ground the cables should be covered with
fine soft earth and protected with cement concrete covering. Suitable G.I. Pipe
shall be used wherever the cable comes out of the connected surface and clamped
properly.

2.2.4 Wooden bushes shall be provided at the ends of pipes through which cables are taken
in walls and floors.

2.2.4 All cables shall be terminated using suitable size cable glands and packing.

2.3 The wiring in conduits shall be 1100 volts grade.

39
2.3.1 The conduits used shall be of high quality, all joints shall be made with sockets. The
bends and elbows shall have inspection covers fixed with grease free screws. The joints
shall be water tight. Approved metal saddles shall be used to secure the exposed
conduits at a space of 1 meter or less. The connection of the conduit to switches etc.,
shall be secured by a check nut and ebonite bushes provided at the ends of conduits.

2.3.2 Flush inspection covers shall be provided in case of concealed, recessed conduits. The
staples for the conduits shall not be spaced more than 0.60 meters apart. Before filling
up the chase with concrete the conduits should be given a coat of rust proof paint.

2.3.3 The wires shall be drawn only after all the conduits have been properly fixed in
position.

3. Control Wiring :

3.1 Control cables shall be 650 volts grade as per IS 1554 made from copper conductor of
1.5/2.5 sq. mm PVC insulated single multi core unarmoured with an overall PVC
sheathing.

3.2 The cables and conduits wiring shall be carried out as per details given under 2.2 and
2.3 above.

4. Earthing :

4.1 All equipment connected with electric supply shall also be provided with double
earthing continuity conductors. The size of copper earthing conductors shall be :-
___________________________________________________________
Size of phase wire sq.mm size of copper conductor
Aluminium tape/wire (swg)
___________________________________________________________

300 25 mm x 6 mm (strip)
185 20 mm x 3 mm (strip)
150 20 mm x 3 mm (strip)
120 12 mm x 3 mm (strip)
95 4 Swg
70 4 Swg
50 6 Swg
35 8 Swg
25-6 8 Swg
4 10 Swg

Note :- GSS earthing conductors of equivalent size may be used in lieu of copper earth
mentioned above.

40
5. Miscellaneous :

5.1 The final connections to the equipment shall be through flexible connections in case of
conduit wiring and also where the equipment is likely to be moved back and forth, such
as on slide rails.

5.2 An isolator switch shall be provided at any motor which is separated from the main
switch panel by a wall or partition or other barrier or is more than 15 metres away from
the main panel.

5.3 Two separate and distinct earthing conduits shall be connected from the equipment upto
the main switch board panel.

5.4 The branch lines from the main panel to each equipment shall be separated and should
not criss cross other lines.

5.5 The entire installation shall be tested as per electricity rules and I.S.S 732-1973 with
amendments 1,2 & 3 prior to the commissioning of the plant and a suitable test report
furnished by a competent and authorised person. The test report will be obtain by
contractor himself at his own expenses.

5.6 All exposed switch board panels, conduits, hangers etc. shall be given 2 coats of
suitable paint of approved colour, when all work has been completed.

******

41
VIII MODE OF MEASUREMENT

Representatives from the Contractor and Consultants shall conduct a joint inspection of the
equipment. All the discrepancies observed either incomplete works or defective work shall be
clearly indicated in the joint inspection report.

An approved metallic tape shall be used at site and utmost care shall be taken to see that the same
is preserved in good conditions throughout the period of execution. Each equipment shall be
measured as one unit and classified based on the type and capacity of equipment complete unit
with all components and accessories required for the specific duty.

The unit rates quoted for various components shall be deemed to be for finished works. Hence
contractors are discouraged to provide split –up / break-up elements of unit rate for these items for
effecting the payment or measurement purpose. However the owner have a right to cause a
technical examination of the works and the final bill of the contractor including all supporting
vouchers abstracts etc to be made available at the time payment of the final bill.

The entire refrigeration unit/Chillers with all accessories, starters, controls, control panels,
control wiring, vibration mounts, flow switch, local control stations, floor mounting MS angle iron
base, wall mounting MS angle brackets, protection grill for condensing unit, suspension
arrangement, refrigerant piping, refrigerant charge, oil, erection, commissioning and testing shall
be regarded as one unit for the purposes of measurement and payment. Refrigeration piping and
its insulation will also form a part of refrigeration/chillers unit and hence no measurement will be
carried out for the same.

Each air handling unit shall be measured as one unit and classified based on the capacity complete
with fan section, filler section, drain pan, motor and drive assembly, thermal insulation, unit
mounted isolation pads, accessories (motorized VCDs, Flexible connection, limit switch, marine
light) etc. as specified.
Each pump shall be measured as one unit including associated motor, thermal insulation, base
frame, vibration mounts, accessories etc as specified.

All sheet metal ducting complete with duct supports, hangers, vibration isolation pads, turning
vanes, girth angles, flanges and gaskets, access panels, turning vanes, erected in position shall be
measured externally (external surface area of ducts before application of insulation) and paid per
unit area. All duct dampers such as manual control splitter damper, vanes etc. shall be included in
the duct area. No separate measurement and payment will be made for splitter damper, vanes or
for any other above mentioned accessories.

The quoted unit rate for external surface of ducts shall include all wastage allowances, flanges and
gaskets for joints nuts and bolts, hangers, and angles with double nuts for supports, rubber strips of

42
5 mm thick between duct and supports, vibration isolators, suspension where specified or required,
inspecting chambers, access panel, splitter damper with quadrant and lever for position indicator,
turning vanes, straightening vanes and all other accessories required to complete the duct
installation as per the specification.

All volume control damper sections with operating linkages, locking, quadrant, sheet steel
enclosure, frame, erection, supporting etc., shall be measured on the basis of damper cross
sectional area and paid per unit area. Each volume control damper for which sizes are given in
BOQ shall be regarded as one unit for the purpose of measurement and payment.

Intake louvers with bird screen, sheet steel louvers and control damper, frame, erection etc., shall
be measured on the basis of cross sectional area and paid per unit area. For inlet louver for which
sizes are given in BOQ shall be regarded as one unit for the purpose of measurement and payment.
Exhaust louvers with bird screen, sheet steel louvers, frame, erection etc., shall be measured on the
basis of cross sectional area and paid per unit area. For exhaust louver for which sizes are given in
BOQ shall be regarded as one unit for the purpose of measurement and payment.

The fresh air and exhaust air louvers shall be with 80mm pitch and preferably in one piece.

Side wall grilles shall be measured on the basis of the core area excluding the margin flange and
paid per unit area. The unit rate for side wall grilles shall include necessary wooden frames and
accessories as specified.
Supply air Ceiling diffusers and return air diffuser shall be measured on the basis of the core area
excluding the margin flange and paid per unit area. For Supply air Ceiling diffusers and return air
diffuser for which sizes are given in BOQ shall be regarded as one unit for the purpose of
measurement and paid on the basis of number of quantity.

Note: Grills and diffuser are not allowed to rest on the false ceiling and hence the ACMV
contractor shall suspend them from the ceiling slab through adjustable suspension system
cost of this suspension shall be included in the price of the grilles and diffuser.

Canvass connection measurement shall be made by measuring the exposed surface area of the
canvass connection, in Sq.m; For double canvass connection only the outer surface area shall be
considered for measurement. (Not applicable for AHU flexible connection).

Area of duct insulation finished as per specification shall be calculated on the basis of finished duct
area before insulation (less openings larger than 0.2 sqmt) and paid as per the unit rate. No
additional payment shall be made for flange insulation.

Acoustic insulation shall be calculated on basis of external duct size. Area of openings larger than
0.2 sqmt shall be reduced from the duct surface area for the measurement of insulation/acoustic
lining measurement and paid for the net area.
Room acoustic insulation shall be calculated on the basis of the finished area and paid for the
actual insulated surface area.

43
Duct opening bigger than 0.2 sqmt shall be left uninsulated/un-acoustic lined. No measurement
shall be payable for material wastage on account of duct opening/cutting larger than 0.2 sqmt.

All painting shall form part of the cost of equipment, piping, structural support, etc. No separate
payment shall be admissible.

All fabricated items/works rates are deemed to be inclusive of two coats of primer painting and
one coat of enamel paint of approved colour.

The unit rate for the earthing station shall include excavation, plate electrode, watering pipes, soil
treatment, masonry chamber etc., and shall be treated as one unit of measurement.

The payment for the cables shall be on the basis of linear measurements and the unit rate includes
the cost of cables double earthing of G.I conductor and clamps, installation, commissioning and
testing, cable marks or ceiling support etc. Gland earthing form the part of motor cost. No claim
for balance cable remaining after the completion of work will be entertained. No extra payment
will be made for any miscellaneous work associated with cable laying.

The distribution board shall be considered as one unit and shall include:

a) Incoming and outgoing feeders


b) Interconnections, controls and instrument wiring
c) Meters, relays, indicating lamps, CTS, control fuses etc.
d) Supporting structure, sheet steel enclosure.
e) Installation and testing.

All water pipes shall be measured net length as laid or fixed and measured linear over all fittings
such as bends junction etc., and given in running meters. The length shall be taken along the
center-lines of the pipes and fittings. The unit rate of piping shall also include cost of supports,
fittings such as tees, elbows, bends, end caps, flanges reducer, thermo wells, drain plugs and other
accessories for completion piping installation.

Length of other fittings (valves and strainers) which are paid under appropriate item shall not be
re-measured under linear measurement, but they will be measured by number and paid separately.
Where they are insulated, the unit rate shall include cost of insulation.

The BOQ specified for ducting, piping does not include wastages in ducting and piping. The unit
rate quoted shall include the same and no separate payment will be made for the wastages.
Supply, installation, testing and commissioning of direct driven propeller fans (Wall mounted)
complete with motor, motor mounting plates, vibration isolator, wire guard, bird screen (brass fly
proof mesh 6mm hole and 20G wire) gravity louvers for weather protection, cowl, power cabling
(5RM/unit) with double earthing etc., shall be regarded as one unit for the purpose of measurement
and payment. Supply, installation, testing and commissioning of treated fresh air unit complete
with fan, motor, motor mounting plates, heat recovery wheel, vibration isolator, wire guard, bird
screen (brass fly proof mesh 6mm hole and 20G wire) gravity louvers for weather protection,

44
cowl, power cabling (5RM/unit) with double earthing etc., shall be regarded as one unit for the
purpose of measurement and payment.

Measurement for pipe insulation shall be on the basis of center line measurement of the installed
pipe strictly on the same basis as the piping measurements described earlier. The linear
measurements shall be taken before the application of the insulation. The elbows, Tees, and
bends shall be considered strictly by linear measurements along the center line of pipes and no
special rate shall be applicable for insulation of any accessories, fixtures or fittings whatsoever
and for any bending, vapour barrier, cladding and fixing materials. All valves, strainers etc are
separately measures by their number and size and will be on unit basis. Each toilet exhaust fan
shall be measured as one unit and classified based on flow rate capacity complete with fan
section, motor and drive assembly, vibration isolator, mounting brackets etc.

Each split Air conditioner shall be measured as one unit and classified based on capacity,
complete with indoor unit, outdoor condensing unit, cordless remote controller, air purifying
filter, washable grille, evaporator unit mounting brackets etc.

Each expansion tank shall be measured as one unit and classified based on storage capacity and
type such as closed expansion tank or atmospheric expansion tank.
Closed expansion tank will be measured on unit basis consists of polypropylene tank, complete
with make-up, quick fill, drain and overflow valves and connection, protected with insulation
and Aluminium cladding, FRP coated steel strands, hydraulic balancing equalizers etc.
Each ductable Air conditioner shall be measured as one unit and classified based on cooling
capacity and dehumidified airflow rate and consists of indoor unit with DX type cooling coil,
filter, blower drive motor, compressors, safety and operating controls, outdoor air cooled
condensers, coils, propeller fans, mounting brackets, interconnecting refrigerant piping,
electrical cabling, earthing, drain piping and microprocessor panel.
The refrigerant piping rates are for set of pipes as applicable. The average length of all circuits
(one or more) shall be considered for payment of refrigerant pipe length. For example in multi
circuit unit, the ref pipe length of circuit 1, 2 & 3 is L1, L2 & L3 respectively. In such case the
average of L1, L2 & L3 shall be considered for payment of refrigerant pipe length of that unit.

All the Material Handling Equipment (MHE) shall be quoted for monthly rate. The monthly rate
shall include minimum 30 working days operation @ 10 hours operation per day. The working
hours shall be the actual hours when the MHE is put to beneficial use, as per site requirement. In
case working hours are more than 10 in a calendar day, these shall be paid as per the hourly rate.
Holidays, breakdowns, idle hours are not payable.
To derive the hourly rate, the monthly rate shall be divided by 300 and paid as per the approved
measurement sheet for extended hours. The extended deployment of MHE must be verified on
weekly basis and signed by the PMC Mechanical Engineer & Amazon PM. The deployment of
MHE needs to be commensurate with the work progress at site and prior approval needs to be
taken in writing from the PMC Mechanical Engineer & Amazon PM.

We agree to the above Special Technical Conditions

45
(Signature of the Bidder)

******

IX LIST OF APPROVED `MAKES'

S.No. Items Acceptable Makes


1. Inline fan Caryaire/Airflow/ Systemaire/Sphere

2. Industrial Propeller fan Caryaire /GE / Daspass /Crompton

3. Decorative Propeller fan Usha/Khaitan/Havells

4. VRV System Daikin/Mitsubishi-Electric/Carrier-Midea/LG/


Samsung

5. HVLS Auster/Kelly/Greenheck/Nutech

6. Industrial Air Circulators Daspass/Crompton/Havells

7. Grilles/diffuser/damper/Nozzles Caryaire/Flowel/Systemaire/Airflow

8. GI Sheet for Ducts etc. Jindal/Tata/Sail/Bhushan

9. Electrical

9.1 Starter/ Contactor/Switches gears Siemens/ABB/Schneider

9.2 LT panel Advance/Arihant/Neptune

9.3 Connector/Terminals Elmex/Connectwel/Hensel

9.4 Lugs/Gland Dowel/Comet/Braco/Action

9.5 Power Cables & Control Cables Havells/Polycab/KEI

9.6 Cable Tray SMC/MEM/Airtech

46
10. Pipes

10.1 UPVC Prakash/AKG/Polypack/Prince

10.2 G.I. Jindal/Tata/Mukut

10.3 Copper Piping Rajco/Mandev/Mexflow

11. MS work Kamdhenu/Capital/Rana

12. Weather proof coating CISBOND/Pidility/CISCHEM

13. Nitrile rubber Armaflex/Supreme/K-flex

14. Fastners & fittings etc Wurth/Hilti/Rawplug

15. Adhesive/coatings (Pipe, Duct Pidilite/Cisbond/Cischem/Mechduct


etc.)

16. Air curtain Mitzvah/Systemaire/ Euronix

17. Paint Nerolec/Asian/Shalimar

18. Welding Rods Victor/Advani/Universal

19. Drain Pump Aspen

******

47

You might also like