BEDFORD Drive MANUAL For Encoder 2
BEDFORD Drive MANUAL For Encoder 2
L- PHASE,
N-NEUTRAL
U, V, W to MOTOR
Control terminals:
Encoder terminals:
Drive program:
Basic parameters:
Put F116-1 press open or close command, after finish auto tuning check
motor direction by press open and close if direction ok means no problem
otherwise interchange two motor wires and repeat auto-tune process again.
2. After first step close the door completely then go to parameter FA-25 it
indicates 000 or 001.first open the door completely and check the how
many pulses it indicates then put same value by adding extra 5 pulses in
parameter F6-02
3. Put F0-02-3, Now you switch off the Drive power and ON then check
drive operation by press open and close button.
4. If you satisfied with operation put drive into external terminal mode by
parameter F0-02-1.
5. If you need speed adjustment check door open and close parameters
Note: for reset the drive put parameter FP-01-1 (for restore the parameters
into default values.)