Professional Documents
Culture Documents
AS Briefing For Posting To NGCP Website - 2020-2020-11-18-08-40-06
AS Briefing For Posting To NGCP Website - 2020-2020-11-18-08-40-06
AS Briefing For Posting To NGCP Website - 2020-2020-11-18-08-40-06
Providers
Ancillary Services
SYSTEM REQUIREMENTS
Generators provide these services to the grid customers
Energy Supply
Serve the energy demand
of consumers
Ancillary Services
Ancillary Services are support services necessary to sustain the
transmission capacity and energy that are essential in maintaining
the power quality, reliability, and security of the grid.
Control the frequency within the limits of 59.7Hz to 60.3Hz as per PGC
110
120
125
130
135
145
115
140
2:57:32 PM
2:58:48 PM
3:00:04 PM
3:01:20 PM
3:02:36 PM
3:03:52 PM
3:05:08 PM
3:06:24 PM
3:07:40 PM
3:08:56 PM
3:10:12 PM
3:11:28 PM
3:12:44 PM
3:14:00 PM
3:15:16 PM
3:16:32 PM
3:17:48 PM
3:19:04 PM
3:20:20 PM
Time
3:21:36 PM
3:22:52 PM
3:24:08 PM
3:25:24 PM
3:26:40 PM
3:27:56 PM
3:29:12 PM
3:30:28 PM
3:31:44 PM
3:33:00 PM
3:34:16 PM
3:35:32 PM
3:36:48 PM
3:38:04 PM
3:39:20 PM
3:40:36 PM
3:41:52 PM
59.65
59.75
59.80
59.90
60.00
60.05
60.15
60.25
60.30
60.35
60.40
59.70
59.85
59.95
60.10
60.20
frequency
Illustration of Regulating Reserve Response
Grid frequency
The generator providing RR mirrors the change in grid frequency, in order to maintain the frequency as close to 60Hz as possible.
Technical Requirements for Regulating Reserve
operate in an automatic frequency sensitive mode or Free Governor Mode with
Primary Response RR deadband of +/-0.15Hz with maximum response time of 5 seconds and sustainable for
25 seconds
Secondary Response operate in an Automatic Generation Control (AGC) of the SCADA/EMS of the National
Control Center or manual adjustment of load with specific instructions from the SO.
RR Maximum response time is 25 seconds and sustainable for 30 minutes
Speed governing
Generating units shall be fitted with a fast-acting speed-governing system to provide
system frequency control under normal operating conditions.
• overall speed-droop characteristic of 5% or better. 5% speed-droop for thermal plants; 3% speed-droop for hydro.
• a ramp rate of at least 5MW/minute.
• capable of accepting raise and lower signals from its AGC.
Pmin
Pmin of the generating unit shall not be part of the RR capacity.
Generating unit must already be spinning/synchronized to the grid at the start of its RR schedule.
Functions of Contingency Reserve
Provides generating capacity necessary to respond to infrequent, but
usually large, failures of generating units and/or transmission tie lines.
Total CR capacity per grid shall be equivalent to the largest generating unit
online, which includes its scheduled capacity for energy supply plus its
scheduled capacity for AS, if any. This is computed on an hourly basis.
Illustration of Contingency Reserve Response
DEMAND GENERATION DEMAND GENERATION DEMAND GENERATION
CR
CR DR CR DR DR
Secondary
Response CR
• Operate in an Automatic Generation Control (AGC) of the SCADA/EMS of the National Control Center or
manual adjustment of load with specific instructions from the SO
Pmin
Pmin of the generating unit shall not be part of the CR capacity.
• Generating unit must already be spinning/synchronized to the grid at the start of its CR schedule.
Dispatchable Reserve
Generating units that have fast start capability which can synchronize
within 15 minutes upon dispatch instruction of SO, and can sustain its
output for a minimum period of 8 hours.
The generating unit scheduled for DR shall be on shutdown, and shall only
synchronize to the grid upon dispatch instruction.
Illustration of Dispatchable Reserve Response
DEMAND GENERATION DEMAND GENERATION
CR DR
DR CR
UNDERVOLTAGE OVERVOLTAGE
230 kV
Below 207kV 207kV – 218.5kV 241.5kV – 253kV Above 253kV
(218.5kV – 241.5kV)
Reactive Power for Voltage Control
Low voltage may result to
tripping of generators,
High demand results to low Extremely low demand, on the
overheating of motors and poor
voltage on the load side due to other hand, results to
performance of electrical
an increase in current flow. overvoltage
equipment (e.g. flickering or
dimming of light bulbs)
Generating unit must operate beyond the range of 0.85 lagging power factor or
0.90 leading power factor, but within the unit’s capability curve.
In order to optimize the available ancillary services, NGCP now allows the CR
and DR providers to also provide RPS at the same time.
CAPABILITY CURVE
Black Start Service
The BSS providers should be able to energize a section of the network without the
use of external power sources, allowing further connection of transmission circuit,
and demand to be progressively connected, until the network is re-integrated.
BSS providers must be put on-line and ready to extend power within 30 minutes
upon receipt of dispatch instruction, and can sustain the operation for at least 12
hours.
BSS may be offered as available along with other AS types, since all other AS will be
canceled when a system black out occurs. Thus, during restoration, only BSS is
operating.
AS Nomination, Scheduling and Dispatch
AS capacity (for RR, CR, and DR) and AS availability (for RPS
and BSS) shall be nominated day-ahead by the AS Provider
Dispatchable Reserve 400 - 480 400 – 460 40-80 40-80 90-140 90-140
Notes:
1. Maximum allocation per plant will be set at 20% of the grid requirement.
2. Offers may vary for every hour, and every month of the year, depending on the power
plant’s operations.
3. Gencos with existing Non-firm AS contracts may re-negotiate for Firm AS contract.
Ancillary Services Rates for Firm Capacity
AS Type Firm AS Capacity Payment
Rate
Regulating Reserve PhP 2.25/kW/hr
Contingency Reserve PhP 1.50/kW/hr
Dispatchable reserve PhP 0.85/kW/hr
The abovesaid rates are for the Capacity Payment (CP) of the Firm Capacity, which is in essence the “reservation
fee” for the generating unit as it will be dedicated for Ancillary Service once scheduled, and can no longer be
traded for energy supply. The formula shall be:
CP = Undispatched Scheduled Capacity x Firm AS Capacity Payment Rate
There is an additional payment for Incidental Energy (IE) which will cover the cost of Variable O&M and actual
fuel consumed for the dispatch of Ancillary Service (“G”). Any energy revenue from the WESM will be deducted in
order to avoid double compensation. The formula shall be:
IE = [G x (Firm AS Capacity Payment Rate+VOM+Actual Fuel Cost)] – WESM Revenue
Ancillary Services Rates for RPS
Incidental kVARh Rate: Php 4.00 / kVARh
Where:
Base kVARh = corresponding kVARh at 0.85 power factor lagging or 0.9 power factor leading, for the unit’s MW
loading. For clarity, the MW loading is the unit’s Pmin, or RTD schedule, whichever is greater.
Energy Payment