Datasheet - DC05HDNC1A - User Manual - 50010181
Datasheet - DC05HDNC1A - User Manual - 50010181
用户手册
DC 系列空调器
深圳市英维克科技有限公司
Shenzhen Envicool Technology Co., Ltd.
CONTENTS
1.1 前言............................................................................................................................................ 14
1.2 产品特性 .................................................................................................................................... 14
1.3 空调器描述 ................................................................................................................................ 14
1.4 符合标准.................................................................................................................................... 15
2 安装和操作 ......................................................................................................................... 15
2.1 拆除包装和检验........................................................................................................................ 15
2.2 安装前准备 ................................................................................................................................ 15
2.3 空调器机械安装........................................................................................................................ 16
2.4 电气安装.................................................................................................................................... 16
2.5 安装查检表 ................................................................................................................................ 18
2.6 开机步骤.................................................................................................................................... 18
3 系统功能介绍 ..................................................................................................................... 19
3.1 功能............................................................................................................................................ 19
3.2 运行控制模式 ............................................................................................................................ 19
3.2.1 制冷运行控制 ......................................................................................................................... 19
3.2.2 加热运行(选配) ................................................................................................................. 19
3.2.3 器件控制模式 ......................................................................................................................... 20
3.3 自测............................................................................................................................................ 20
3.4 排氢/应急风扇(选配) ........................................................................................................... 20
3.5 故障............................................................................................................................................ 20
3.6 机组菜单结构............................................................................................................................ 21
4 技术参数 ............................................................................................................................. 23
4.1 几何尺寸.................................................................................................................................... 23
5 日常维护 ............................................................................................................................. 24
Shenzhen Envicool Technology Co., Ltd.
1 Brief Introduction
1.1 Foreword
Note: All of the operations of this product shall be performed by professional engineers and
technicians.
This manual shall only be used as the guide for the installation and operation of the
DC05HDNC1A DC Cabinet Air Conditioner. It introduces the functions and regular
maintenances of the unit.
1.2 Features
High reliability.
Intelligent control.
Frequency regulated and energy-saving.
Offering dry contact and RS485 intelligent communication interface.
Cabinet Ambient
Inner cycle
External cycle
1.4 Standards
Table 1.1 Applicable standards of products
Standard Description
GB/T 17626.7-1998 EMC
GB4706.1 Safety of household appliances or similar electric appliance
Environmental conditions existing in the application of
GB4798.1
electric and electronic product – Storage
Environmental conditions existing in the application of
GB4798.2
electric and electronic product – Transportation
Environmental conditions existing in the application of
GB4798.3
electric and electronic product – Use
CE Third-party certification
The standard package of this product is carton. To remove the package, remove
the external straps first, and then open the top cover and pull out the carton.
Please check the packing list and accessory bags in the carton.
Note:
1. When the package is removed, make sure that the air conditioner is placed
vertically. It cannot be placed horizontally or upside down.
2. When the external package is removed, please check carefully whether the
appearance of the air conditioner is damaged or whether there is any oil stain. If
any damage is found, please report this with the barcode number on the package
to the retailer or Envicool.
3. If there is no need to install the product immediately or it needs to be transported
to other place, please repack the air conditioner after the checking.
4. To protect the environment, it is recommended to recycle the packing cartons.
The placement of the equipment inside the cabinet shall be proper. For example, any
obstruction to the internal cycle air inlet and outlet of the air conditioner should be
avoided.
The layout of drainage channels should be fully considered.
For mechanical installation, please refer to Fig.2.1, and fix the Air Conditioner on the cabinet.
Please select proper wire diameter and circuit protection device according to the
air conditioner nameplate and technical parameters.
Please perform the electrical connection in accordance with the following steps:
Wiring diagram:
Signal cable:
Signal cable includes: communication cable and alarm output cable.
1. Monitoring output:
The unit’s RS485 communication cable adopts RJ45 port, please refers to Fig.2.2 for
wiring.
2. Alarm output:
The unit provides alarm output dry contact. If there is no alarm, the dry contact is close.
When there is alarm, the dry contact will open. Contact capacity: resistive load
5A@30VDC/5A@277VAC. Please refer to Fig.2.2 for wiring.
Please check the following check list when the electrical connection and the air
conditioner installation are completed.
1. There is no obvious obstacle near the internal cycle air inlet and outlet of the
air conditioner.
Firstly make sure the DC voltage is in accordance with the standard, and then close the DC
power input switch. 30s later the internal cycle fan of the unit will be started. After delay about
3min, the unit select operation mode according to the unit’s parameter setting and indoor/outdoor
temperature. The interface shown as follows.
The system controls the air conditioner’s operation according to the cabinet internal temperature.
The unit provides the self testing function for the onsite test. The self testing procedures are
as below:
3.5 Alarm
The cabinet air conditioner provides the following alarm information. Please refer to table 3.1
for the setting point.
If the alarm hasn’t been recovered, the alarm information will be still on, until the alarm has
been eliminated. And you can check the alarm statistics through entering the alarm menu shown
as Fig.3.2.
The unit controller adopts the 96x32 LCD, which contains 7 buttons for the setting.
The operation interface is as shown in the following figure.
↑: Up button, which is used to increase the setting value or select the previous
record/menu.
↓: Down button, which is used to decrease the setting value or select the next
record/menu.
←: Left button, which is used to select the previous bit of the data.
→: Right button, which is used to select the next bit of the data.
ESC: Quit button, which is used to return to the previous page menu.
If there is no keyboard operation for consecutively 60s under any interface after
startup, it will automatically return to the normal display interface.
When any button is pressed after the system is powered up, the backlight will turn
on. If there is no keyboard operation for consecutively 60s, the backlight will be
off.
The factory default operation password of the unit is “0001”. You can change it
according to your needs. To change it, you need to press ENTER on the normal
display interface to enter the password input interface, press the LEFT button or
RIGHT button to select the bits for change, and press the UP/DOWN button to
change the relevant digits, and finally press ENTER button to confirm the change.
If the password is incorrect, the interface will display the error message, and the
unit setting cannot be changed. If the password is correct, you can enter the main
menu and edit the unit setting.
error
password
Main Menu
Set Point
Alarm Menu
Status Menu
System Fun
Diagnosis
VersionInfo
Restore
Active Alarm
Set Point
Sensor Value Run Status
Warn: 00/00
Addr : 01H NoAlarm
Delay : 30S Tin1: 24.2℃ InFan : Run
CoolSP : 35℃ Tin2: 25.2℃ Comp : Run
CoolΔT: 05℃ Tout : 30.0℃ Heater: Stop VersionInfo
HeatSP: 15℃ Tp : 10.2℃ OutFan: Stop Diagnosis
HeatΔT: 05℃ Te : 40.5℃ EmsFan: Stop Name :BP-R05
INHT : 55℃ Tc : 30.3℃ SoftVer: 1.0
SelfTest
Band : 05℃ Vdc: 50.5V Monitor: 1.2
INHT1 : 55℃ Vac: 50.5V
Band : 05℃ Amp : 1.2A
INLT : 05℃
Band : 05℃
InFan : 35℃
Note: This diagram is unit menu structure, not the real factory setting.
Remarks:
In1: Internal return temperature sensor1
In2: Internal return temperature sensor2
Out: External ambient temperature sensor
Tp: Evaporator coil temperature sensor
Te: Compressor exhaust pipe temperature sensor
Cond: Condenser coil temperature sensor
4 Technical Parameters
4.1 Physical dimensions
320
15 10
30
20 10
315
34
52
96.5
161
202
42 250
583
545
550
480
569
94
42.5 250
154
232.5
62
5 Daily maintenance
To ensure the normal operation of the air conditioner, please perform regular
maintenances for it by referring to Table 5.1.
1 简介
1.1 前言
注意:任何针对本产品的操作必须由专业的工程技术人员进行。
本手册只能用于指导 DC05HDNC1A 直流机柜空调的安装和操作。手册内容包
含机组的功能描述和定期维护。
1.2 产品特性
可靠性高。
智能控制。
直流变频,高效节能。
提供干节点、RS485 智能通讯接口。
1.3 空调器描述
这款空调是针对通信行业的交流电源供应不足的情况而特别设计的,由-48V 直流
电源供电。该产品属于直流变频空调,具有制冷量自动调节功能,且风机自动调速,能
有效降低噪声水平。
空调器内循环从上部吸入热空气,冷空气从下部排出空调器。外部循环从下部吸入
外界冷空气,经过热交换后热空气从上部排出空调器。见图 1.1
机柜外环境
机柜
柜 柜
内 外
循 循
环 环
风 风
路 路
图 1.1 功能示意图
DC 系列空调器 用户手册
14
深圳市英维克科技有限公司
注意:在运输、储存及使用中,必须严格按照包装上的指示保持直流机柜空调器竖直向上放置。
直流机柜空调产品的应用范围:
电网适用范围:
直流电源:-48VDC (-36~-60V DC)
外循环温度:-15℃~55℃
1.4 符合标准
表 1.1 产品适用的标准
标准 标准描述
GB/T 17626.7-1998 电磁兼容性
GB4706.1 家用和类似用途电器的安全
GB4798.1 电工电子产品应用环境条件-储存
GB4798.2 电工电子产品应用环境条件-运输
GB4798.3 电工电子产品应用环境条件-使用
CE 第三方认证
2 安装和操作
2.1 拆除包装和检验
本产品标准采用纸箱包装,拆除包装时,先将包装外部的打包带拆除,打开
纸箱上盖并将纸箱抽出。注意清点包装箱内的装箱清单和附件包。
注意:
1. 拆除包装后,请确保空调竖立放置,不能平倒。
2. 拆除外部的包装后,请仔细检查空调器外观是否有损伤或者油污。如果发现了任何损伤,
请在一周内连同包装外的条形码编号报告销售商或者英维克公司。
3. 如果产品不是立即安装或者需要转运到其它地区,请在检查完后重新对空调器进行包装。
4. 为了保护环境,我们建议对包装纸箱进行回收利用。
2.2 安装前准备
安装前注意:
机柜内部设备的摆放。如尽量避免对空调器内循环进/出风口有阻拦。
DC 系列空调器 用户手册
15
深圳市英维克科技有限公司
考虑好排水通道的布置。
2.3 空调器机械安装
图 2.1 机械安装示意图
2.4 电气安装
空调器电气安装包括如下工作:
连接电源线
连接通信及告警输出线缆
注意:所有电气连接都必须符合国家和当地电气规范要求,安装前断开所有的
空调电源。
根据空调铭牌和技术参数选择合适的线径以及电路保护装置。
按照以下步骤进行电气连接:
1. 确认空调电源断开。
2. 按照电源端子示意图将电源线与输入端子连接。
3. 将电源输入端子可靠连接在机组的电源插头处,并将固定螺钉紧固。
4. 将电源线另一端按照定义接入到电源上。
5. 将通信及告警输出线缆按照定义接入到输入端子上。
DC 系列空调器 用户手册
16
深圳市英维克科技有限公司
6. 将通信及告警输出端子可靠连接到机组的通信及告警输出插头处,并将
固定螺钉紧固。
7. 用万用表测试电源输入线是否有短路,断路现象。
8. 用万用表测试通信及告警输出线缆是否有短路,断路现象。
电器接线示意:
图 2.2 电器接线示意图
电源输入线缆:
-48V 直流电源输入线缆。
信号线缆:
信号线缆包括通信线缆、公共告警输出线缆两部分。
1、 监控输出:
机组 RS485 通信线缆采用 RJ45 接口,接线参考接线示意图 2.1。
2、 公共告警输出:
机组提供公共告警干节点,无告警输出时干节点为闭合状态,有告警输出时
干节点为断开状态。触点容量:阻性负载 5A@30VDC/5A@277VAC。接线参考接线
示意图 2.2。
DC 系列空调器 用户手册
17
深圳市英维克科技有限公司
排氢/应急风扇接线示意图:
注意:排氢风机干接点最大容量为: 直流排氢风机:0.5A /48V。
直流风机:
图 2.3 直流排氢风机输入端口接线示意图
2.5 安装查检表
在空调器的机械和电气安装完毕后,请核对下列查检表。
1、空调器的内外循环的进/出风口附近无明显的阻挡物;
2、空调器竖直安装,且所有安装螺钉已经紧固;
3、电源线已经准确可靠接驳;
4、告警输出线可靠接驳;
5、RS485 线缆已经可靠接驳;
6、风机可以自由顺畅转动,无异声;
7、用钳型电流表测量输入电压是否符合:直流电压在-45~-57VDC。
2.6 开机步骤
先确认输入的直流电压都符合要求。闭合直流电源输入空开,开机 30s 后室
内循环风机运行。延时一段时间后(3min 左右)直流机柜空调会按照设定的参数
并参考室内、外循环温度自动选择运行模式。显示界面如下所示:
DC 系列空调器 用户手册
18
深圳市英维克科技有限公司
开机界面 正常显示界面
3 系统功能介绍
3.1 功能
机柜空调的运行是根据机柜内部的温度,自动对空调系统的工作进行控制的。
3.2 运行控制模式
3.2.1 制冷运行控制
当温度达到(制冷控制点+制冷灵敏度)时,空调将大冷量输出运行。当柜内温度小于制冷控制点
时,制冷停止运行。
表 3.1 用户参数设置点
3.2.2 加热运行(选配)
加热开启点=加热停止点 - 加热灵敏度,当机柜内部温度低于加热开启点,开始加热运行,当
机柜内部温度高于加热停止点停止加热。
表 3.2 加热参数设置点
DC 系列空调器 用户手册
19
深圳市英维克科技有限公司
3.2.3 器件控制模式
1、内风机控制模式:
在系统正常运行时,内风机按正常风速运行。
2、外风机控制模式:
通风模式:外风机停止运行
制冷模式:外风机的转速取决于冷凝器的温度,冷凝器温度越高,外风机的转速就越快;冷凝
器温度越低,外风机的转速就越慢。
3、压缩机控制模式:
通风模式:压缩机停止运行
制冷模式:压缩机的转速取决于回风温度和设定值的温差;温差越大,转速越快;温差越小,
转速越慢。
3.3 自测
机组提供自测供现场检测使用。自测程序如下:
1、若压缩机没关闭,关闭压缩机;
2、内风机运行 60S;
3、压缩机下限速运行,外风机 50%转速运行 60S;
4、压缩机上限速运行,外风机 100%转速运行 60S;
5、若选配电加热,开启电加热 120S;
6、若选配排氢风扇,开启排氢风扇 120S;
7、关闭内、外风机,压缩机、电加热、排氢风扇;
8、自测结束,系统自动进入正常控制模式运行。
3.4 排氢/应急风扇(选配)
定时排氢:按照柜内环境需求,排氢风扇实现自动循环排氢以及强制通风功能,
自动循环排氢每次排氢间隔时间为 24 小时,排氢时间为 5 分钟。
强制通风:当压机无制冷能力(包括:压机故障、停电)时且柜内温度高于排
氢风扇开启点(应急点+5)且柜内温度比柜外温度高 3 度时,开启排氢风扇。
3.5 故障
机柜空调器提供如下告警信息,设定点按照表 3.1。
DC 系列空调器 用户手册
20
深圳市英维克科技有限公司
图 3.1 告警界面
表 3.2 告警内容及参数设置点
告警内容中文 缺省值 设置范围 单位 告警条件
无告警 -- -- -- 无任何告警
柜内高温告警 40 [25~70] ℃ 内循环温度高于高温告警点
柜内低温告警 0 [-20~10] ℃ 内循环温度低于低温告警点
柜内温感失效 -- -- -- 内循环温度传感器失效
柜外温感失效 -- -- -- 外循环温度传感器失效
系统高压告警 -- -- -- 系统高压(或外风机故障)
压缩机故障 -- -- -- 系统无制冷能力
烟感告警 -- -- -- 外接烟雾传感器触发告警
门禁告警 -- -- -- 外接门禁触发告警
水淹告警 -- -- -- 外接水浸传感器触发告警
防雷器故障告警 -- -- -- 外接防雷器故障触发告警
震动告警 -- -- -- 外接震动传感器触发告警
盘管温感失效 -- -- -- 盘管温度传感器失效
排气温感失效 -- --- --- 排气温度传感器失效
EEPROM 故障 -- --- --- EEPROM 故障
3.6 机组菜单结构
控制器操作界面
DC 系列空调器 用户手册
21
深圳市英维克科技有限公司
ON/OFF:开/关机键,操作此键对机组进行开/关机;
↑:上移键,对设置值进行增加或者选择上一条记录/菜单;
↓:下移键,对设置值进行降低或者选择下一条记录/菜单;
←:左移键,选择前一位数据;
→:右移键,选择后一位数据;
ENTER:回车键,确认输入;
ESC:退出键,返回上一屏菜单;
开机后,在任何界面下,如果持续 60 秒无键盘操作,自动返回正常显示界面。
机组上电后,按任意键,背光灯亮,如果持续 60 秒无键盘操作,背光灯灭。
机组出厂的操作密码为“0001”用户可根据需要自行修改。在正常显示界面按
回车进入密码输入界面,按左移键、右移键选择需要输入的位,按上下键做修改,
输入完毕按回车键确认。如果密码不正确,界面显示错误信息,不能修改机组设定。
如果密码正确,进入主菜单,可以对机组设定进行编辑。
关机界面 启动界面 正常界面 密码输入界面
关 机 中 文 外 温 :26.5℃ 密 码 : ****
ShutDown English 制冷
密码错误
不能修改参数
主菜单
运行设定
告警菜单
系统状态
系统功能
系统状态
环境状态
输出状态
内 1 : 24.2℃
当前告警 内 2 : 25.2℃ 内风机:运行
运行设定 外 温 : 25.2℃ 压缩机:运行 系统版本
告 警 : 00 / 00 盘 管 : 10.2℃ 电加热:停止
系统诊断
地 址 : 01H 无告警 排 气 : 50.5℃ 外风机: 运行 名 称 : BP-R05
延 时 : 30s 冷 凝 : 50.5℃ 风扇 :停止 软 件 : 1.0
系统自测
制 冷 点 : 23℃ Vdc : 50.5V 监 控 : M1.2
灵 敏 度 : 03℃ Vac : 220.0V
加 热 点 : 10℃ 电 流 : 0.12A
灵 敏 度 : 05℃
内 高 温 : 30℃
回 差 : 05℃
预 高 温 : 30℃
回 差 : 05℃
内 低 温 : 05℃
回 差 : 05℃
内 风 机 : 23℃
注:此图仅为菜单结构图,不代表出厂参数配置。
DC 系列空调器 用户手册
22
深圳市英维克科技有限公司
环境状态说明:
内 1:表示内回风口温度传感器 1
内 2:表示内回风口温度传感器 2
室外:表示外部环境温度传感器
盘管:表示蒸发器盘管上的温度传感器
排气:表示压缩机排气管温度传感器
冷凝:表示冷凝器盘管上的温度传感器
4 技术参数
4.1 几何尺寸
320
15 10
30
20 10
315
161
202
42 250
583
545
550
480
569
94
42.5 250
154
232.5
62
DC 系列空调器 用户手册
23
深圳市英维克科技有限公司
5 日常维护
表 5.1 日常维护表
检查项目 步骤内容描述 维护周期
接线 目视检查是否有松脱 1年
风扇异常 拨动风扇,转动是否顺畅,有无异响 1年
排水孔 目视检查排水孔是否脏堵 6 个月
冷凝器 检查冷凝器清洁状况,用压缩空气清洁冷凝器 6 个月
DC 系列空调器 用户手册
24
Declaration:
This manual shall not be reproduced without the written approval of Envicool.
Envicool reserves the right to update the product without notice.
声明:
版权所有,禁止任何未经授权的拷贝和抄袭。
厂家对产品持续升级进行的资料更改,恕不另行通知