Professional Documents
Culture Documents
Datasheet - CyberMate Precision Cooling Unit For Data Center-20170718-DB
Datasheet - CyberMate Precision Cooling Unit For Data Center-20170718-DB
com
Data Center Cooling Outdoor Cabinet Cooling Energy Saving Solutions Customized Solutions
■ CyberMateTM series CRAC ■ DC series air conditioner ■ EC series indoor battery cooler ■ Customized air conditioners
■ CyberMateTM series modular CRAC ■ EC series air conditioner ■ ES series heat exchanger
■ CyberMateTM series laboratory precision CRAC ■ HC series combo air conditioner ■ FX series BTS free cooling unit
■ CyberMate TM
series museum & wine cellar CRAC ■ EX series heat exchanger ■ DC series split DC air conditioner
■ iFreecooling TM
series self-adaptive multi-joint ■ EM series cabinet monitor ■ SC series combo air conditioner
energy-saving system ■ MC series air conditioner for power with free cooling
■ XRow TM
series row-based cooling unit industry outdoor cabinet ■ ERG series heat pipe
■ XRackTM series embedded cooling ■ MX series heat exchanger for
■ XUnitTM small data center cooling solution power industry outdoor cabinet
■ XSpaceTM series big data center cooling solution ■ TC series LCD air conditioner
■ XContainerTM series container cooling solution
■ Data center free cooling energy-saving system
■ Data center heat pipe system TM
S h e n z h e n E n v i c o o l Te c h n o l o g y C o . , L t d .
Address: Building 9, Hongxin Industrial Park, Guanlan, Longhua District, Shenzhen, China
Tel: +86 (755) 6683 3272 Fax: +86 (755) 2958 8895 P.C: 518110
Http: www.envicool.com Email: intlsales@envicool.com
R&D Center
Date Center
01 The continual growing OPEX has become the bottleneck of the TCO control in data center.
02 Improving the energy efficiency and enhancing the management level are the key actions
Psychrometric Air-
conditioning to reduce the TCO of the data center. Low power consumption and easy manageability are
Performance Testing appreciated in the construction of data center.
Lab
The power consumption for cooling system is a significant part, while accounting it as 30-45% of
the overall power consumption in a data center. Therefore, energy efficiency of CRAC unit will
attract great attention.
With the popularity of the green data center concept, the energy effciency standards for precision
cooling units keep increasing. More and more data centers are applying the CRAC units with
Production Line and Warehouse
high energy efficiency and integration of free cooling function.
[Company Profile]
Shenzhen Envicool Technology Co., Ltd. is a hi-tech enterprise which specializes in research and development (R&D), CyberMateTM Series Precision Cooling Unit:
manufacturing, marketing of climate control products and solutions for Data Center and Data Access Stations. The team
masters the world class cooling technology, precise control technology, mechanical design technology and has obtained
With high AEER system design and team work function, CyberMate TM meets the cooling
series patents around temperature control. demand and reduces the PUE of the data center.
Envicool has various products, which are widely used in China and overseas markets, including CRAC for data center, air
conditioner for telecom outdoor enclosure, free cooling unit (FCU), heat exchanger, battery cabinet and so on.
Envicool has obtained ISO9001, ISO14001 and OHSAS18001. The products are CCC, CE, UL and TUV certified. Envicool Annual Energy Efficiency Ratio(AEER) :
adopts the Integrated Product Development (IPD) process to develop products and technologies, and utilizes the JIT and
TQC supply chain management modes to meet the customers' requirement efficiently. ∑ the heat removed from the room
AEER = (All year round)
As an associate member of China Communications Standard Association, Envicool takes an active part in the revision of ∑ CRAC cooling electricity consumption
relevant industry standards.
[Certifications] Applications
Computer room and data center
Switch room and mobile center station in telecommunication
High-tech environment and lab
Industrial automation control room and precision manufacturing workshop
ISO14001 ISO9001 OHSAS18001 CE CCC UL China Energy-saving Certification
Standard test room and calibration center
Envicool
UPS and battery room
Test room in hospital
Biochemical culture chamber
National Hi-Tech Shenzhen Hi-Tech Patents Member of CCSA Data Center Awards
Certification Certification
www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool
EVO
controller Wide Range of Cooling Capacity EVO Monitoring System
• 26kW ~ 100kW
• RS485 interface as standard
• Single circuit indoor unit, dual circuit indoor unit
• Optional SNMP and TCP/IP interface
• Single circuit condenser, dual circuit condenser
Efficient scroll • Optional GPRS DTU, SMS for alarm and maintenance
reminding
compressor
Various Cooling System Type
Envicool
• Air cooled/Water cooled/Glycol cooled
• Dual Cool including: Chilled water+Air cooled, Chilled
Efficient water+Water cooled (Glycol)
EC fans • Dual Cool: Air cooled+iFreecoolingTM
• Dual Cool : Air cooled+Direct free cooling
Owlet fan with
variable frequency
fan speed control
www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool
Data Sheet of CyberMateTM DX Units (Air Cooled, Water Cooled, Glycol Cooled) Data Sheet of CyberMateTM Dual Cool Units (DX +CW)
Model 526 530 535 540 546 740 746 755 765 770 780 790 799 Model 526 530 535 540 546 740 746 755 765 770 780 790 799
Power Supply 380V 3Ph - 50Hz Power Supply 380V 3Ph - 50Hz
Air Discharge Upflow / Downflow
05 Air Discharge Upflow / Downflow
Performance Specification
06 Performance Specification
Total (kW) 26.8 30.9 35.9 40.3 46.9 40.7 47.6 55.6 65.8 71.6 80.2 92.6 100.2
Total Cooling Capacity (kW) 26.8 30.9 35.9 40.3 46.9 40.7 47.6 55.6 65.8 71.6 80.2 92.6 100.2 Sensible (kW) 24.2 27.9 32.6 36.4 42.3 36.8 42.9 50.2 59.3 64.5 72.7 83.6 90.6
DX
Sensible Cooling Capacity (kW) 24.2 27.9 32.6 36.4 42.3 36.8 42.9 50.2 59.3 64.5 72.7 83.6 90.6
FLA-A 28.9 31.9 39.4 41.9 49.0 44.3 49.0 52.4 59.7 64.1 71.8 84.3 86.2
FLA-A 28.3 31.3 38.7 41.2 48.0 43.6 48.0 51.3 58.5 62.9 69.3 82.5 84.3
Total (kW) 33.6 33.6 44.2 44.2 56.4 44.2 56.4 59.1 73.5 76.4 89.2 92.5 92.5
Quantity of Compressor 1 1 1 1 1 2 2 2 2 2 2 2 2 CW/
Sensible (kW) 29.2 29.2 37.7 37.7 48.6 37.7 48.6 51.2 63.2 66.0 77.8 81.7 81.7
Indoor Fan Section Glycol
Flow Rate (m3/h) 5.8 5.8 7.6 7.6 9.7 7.6 9.7 10.1 12.6 13.1 15.3 15.9 15.9
Airflow - m3/h 8000 9000 10000 11000 13000 11000 13000 14000 17000 18000 21500 23000 25000
Quantity of Compressor 1 1 1 1 1 2 2 2 2 2 2 2 2
Quantity of Fan 1 1 1 1 2 1 2 2 2 2 2 2 2 Indoor Fan Section
Reheat Section Airflow - m3/h 8000 9000 10000 11000 13000 11000 13000 14000 17000 18000 21500 23000 25000
Capacity (kW) 6 6 9 9 9 9 9 9 9 9 9 9 9 Quantity of Fan 1 1 1 1 2 1 2 2 2 2 2 2 2
Humidifier Section Reheat Section
Capacity (kg/h) 6 6 6 6 10 6 10 10 10 10 10 10 10 Capacity (kW) 6 6 9 9 9 9 9 9 9 9 9 9 9
Humidifier Section
Connection Size
Capacity (kg/h) 6 6 6 6 10 6 10 10 10 10 10 10 10
Liquid Pipe - OD (mm) 16 16 16 16 16 16 16 16 16 16 16 16 16
Connection Size
Gas Pipe - OD (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22
DX Liquid Pipe - OD (mm) 16 16 16 16 16 16 16 16 16 16 16 16 16
Inlet Pipe of Humidifier (Female) G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2"
DX Gas Pipe - OD (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22
Drain Pipe - ID (mm) 25 25 25 25 25 25 25 25 25 25 25 25 25 CW Inlet/Outlet DN32 DN32 DN40 DN40 DN40 DN40 DN40 DN40 DN50 DN50 DN50 DN50 DN50
Physical Data Inlet Pipe of Humidifier (Female) G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2"
Width (mm) 1050 1050 1400 1400 1700 1400 1700 1700 2100 2100 2550 2550 2550 Drain Pipe - ID (mm) 25 25 25 25 25 25 25 25 25 25 25 25 25
Depth (mm) 890 890 890 890 890 890 890 890 890 890 890 890 890 Physical Data
Height (mm) 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 Width (mm) 1050 1050 1400 1400 1700 1400 1700 1700 2100 2100 2550 2550 2550
Depth (mm) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Weight (kg) 365 370 410 415 530 415 535 550 720 730 800 820 825
Height (mm) 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990
Water/Glycol Cool Unit Parameter
Weight (kg) 395 400 460 465 600 465 595 620 820 830 920 925 940
Inlet/Outlet Connection (mm) 35.0 42.0 42.0 42.0 54.0 42.0 54.0 54.0 54.0 63.0 63.0 70.0 70.0
Water/Glycol Cool Unit Parameters
Water Flow Rate - m3/h 6.0 7.0 8.2 9.2 10.7 9.2 10.8 12.5 14.9 16.4 18.3 21.0 22.8 Inlet/Outlet Connection (mm) 35.0 42.0 42.0 54.0 54.0 42.0 54.0 54.0 54.0 63.0 63.0 70.0 70.0
Pressure Drop (kPa) 86.0 99.2 76.0 83.1 94.7 82.8 95.4 75.1 85.6 93.1 71.0 77.6 82.5 Water Flow Rate - m3/h 6.0 7.0 8.2 9.2 10.7 9.2 10.8 12.5 14.9 16.4 18.3 21.0 22.8
Inlet/Outlet Connection (mm) 35.0 42.0 42.0 54.0 54.0 42.0 54.0 54.0 54.0 63.0 63.0 70.0 70.0 Pressure Drop (kPa) 86.0 99.2 76.0 83.1 94.7 82.8 95.4 75.1 85.6 93.1 71.0 77.6 82.5
Glycol
Flow Rate - m3/h 7.1 8.3 9.6 10.8 12.6 10.8 12.7 14.7 17.6 19.3 21.6 24.7 26.8 Inlet/Outlet Connection (mm) 35.0 42.0 42.0 54.0 54.0 42.0 54.0 54.0 54.0 63.0 63.0 70.0 70.0
(40%) Glycol
Pressure Drop (kPa) 99.8 76.6 86.0 95.8 75.3 95.4 112.9 84.8 99.3 73.3 79.1 88.2 95.0 Flow Rate - m3/h 7.1 8.3 9.6 10.8 12.6 10.8 12.7 14.7 17.6 19.3 21.6 24.7 26.8
(40%)
Breakers & Cables Pressure Drop (kPa) 99.8 76.6 86.0 95.8 75.3 95.4 112.9 84.8 99.3 73.3 79.1 88.2 95.0
Breakers & Cables
Indoor Recommended Air Break Switch (A) 50 50 63 63 80 63 80 80 100 100 125 125 125
Indoor Recommended Air Break Switch (A) 50 50 63 63 80 63 80 80 100 100 125 125 125
Unit Cables (mm2) 10 10 10 16 16 16 16 16 16 16 25 25 25
Unit Cables (mm2) 10 10 16 16 16 16 16 16 16 16 25 25 25
Outdoor Recommended Air Break Switch (A) 20 20 20 20 20 20 20 20 20 20 20 20 20 Outdoor Recommended Air Break Switch (A) 20 20 20 20 20 20 20 20 20 20 20 20 20
Unit Cables (mm2) 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Unit Cables (mm2) 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Envicool
Remark: Remark:
Return air condition: 24℃ / 50% RH. Return air condition: 24℃ / 50% RH.
Water/Glycol low control valve: standard two-way valve, Water/Glycol low control valve: standard two-way valve,
optional three-way valve. optional three-way valve.
EC fan configured as standard. EC fan configured as standard.
Electronic expansion valve as standard. Electronic expansion valve as standard.
*:For modularized system, fan quantity is 2. *:For modularized system, fan quantity is 2.
www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool
iFreecooling TM Technology Data Sheet of CyberMateTM Dual Cool Units (Air Cooled + iFreecooling)
Making full use of the natural cold source by stopping the compressor running in low ambient temperature, the power Model 526 530 535 540 546 740 746 755 765 770 780 790 799
consumption of the cooling system and PUE of the data center is greatly reduced. Power Supply 380V 3Ph - 50Hz
07 Protect the temperature, humidity and cleanness of data center from outside and ensure its high reliability Air Discharge Upflow / Downflow
TM
08 When iFreecooling runs in low ambient temperature, the compressor system will save more than 96% energy, whole cooling Performance Specification of DX Unit
system will save more than 70% energy, and 25%~35% reduction for the energy consumption of data center will be realized. Total Cooling Capacity (kW) 26.8 30.9 35.9 40.3 46.9 40.7 47.6 55.6 65.8 71.6 80.2 92.6 100.2
TM
iFreecooling can run together with DX both in the Spring and Autumn to make best use of free cooling Sensible Cooling Capacity (kW) 24.2 27.9 32.6 36.4 42.3 36.8 42.9 50.2 59.3 64.5 72.7 83.6 90.6
TM
One iFreecooling system can work together with multiple DX units FLA-A 28.3 31.3 38.7 41.2 48.0 43.6 48.0 51.3 58.5 62.9 69.3 82.5 84.3
Quantity of Compressor 1 1 1 1 1 2 2 2 2 2 2 2 2
Indoor Fan Section
Airflow - m3/h 8000 9000 10000 11000 13000 11000 13000 14000 17000 18000 21500 23000 25000
Quantity of Fan 1 1 1 1 2 1 2 2 2 2 2 2 2
Reheat Section
Capacity (kW) 6 6 9 9 9 9 9 9 9 9 9 9 9
Power consumption
Humidifier Section
of condenser fan
Capacity (kg/h) 6 6 6 6 10 6 10 10 10 10 10 10 10
Power consumption
of indoor unit fan
Connection Size of DX Unit
Power consumption
of iFreecooling system Liquid Pipe - OD (mm) 16 16 16 16 16 16 16 16 16 16 16 16 16
Power consumption
of compressor
Gas Pipe - OD (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22
Inlet Pipe of Humidifier (Female) G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2"
Drain Pipe - ID (mm) 25 25 25 25 25 25 25 25 25 25 25 25 25
Physical Data of DX Unit
Width (mm) 1050 1050 1400 1400 1700 1400 1700 1700 2100 2100 2550 2550 2550
Power consumption Power consumption Power consumption Power consumption
of common CRAC of CyberMate of CyberMate + of iFreecooling in
iFreecooling in Spring low ambient temperature
and Autumn
Depth (mm) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Height (mm) 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990
Weight (kg) 410 420 440 445 560 445 565 580 760 770 840 850 865
Indoor Recommended Air Break Switch (A) 50 50 63 63 80 63 80 80 100 100 125 125 125
Annual energy saving rate ≥ 35% Unit Cables (mm ) 2
10 10 16 16 16 16 16 16 16 16 25 25 25
Annual energy saving rate ≥ 25% Outdoor Recommended Air Break Switch (A) 20 20 20 20 20 20 20 20 20 20 20 20 20
Unit Cables (mm2) 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Annual energy saving rate ≥ 15%
Remark:
Envicool
Return air condition: 24℃ / 50% RH.
EC fan configured as standard.
Electronic expansion valve as standard.
*:For modularized system, fan quantity is 2.
www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool
Data Sheet of CyberMateTM Dual Cool Units (DX + Direct Free Cooling) CyberMateTM (>20kW) Air Cooled Condenser
Model 526 530 535 540 546 740 746 755 765 770 780 790 799
Strengthen aluminum alloy enclosure and stainless steel
Power Supply 380V 3Ph 50Hz
connection parts
Air Discharge Upflow / Downflow
Variable frequency fan speed control, efficient energy saving
09 Performance Specification
Bionic-type fan, low noise
10 Total Cooling Capacity (kW) 26.8 30.9 35.9 40.3 46.9 40.7 47.6 55.6 65.8 71.6 80.2 92.6 100.2 TM
Integrated iFreecooling design
Sensible Cooling Capacity (kW) 24.2 27.9 32.6 36.4 42.3 36.8 42.9 50.2 59.3 64.5 72.7 83.6 90.6 Adapting to various climate conditions
FLA-A 28.3 31.3 38.7 41.2 48.0 43.6 48.0 51.3 58.5 62.9 69.3 82.5 84.3 Single/dual circuit design
Quantity of Compressor 1 1 1 1 1 2 2 2 2 2 2 2 2
Indoor Fan Section
Airflow - m3/h 8000 9000 10000 11000 13000 11000 13000 14000 17000 18000 21500 23000 25000
Quantity of Fan 1 1 1 1 2 1 2 2 2 2 2 2 2
Reheat Section
Capacity (kW) 6 6 9 9 9 9 9 9 9 9 9 9 9
Humidifier Section
Capacity (kg/h) 6 6 6 6 10 6 10 10 10 10 10 10 10
Connection Size of DX Unit
Liquid Pipe - OD (mm) 16 16 16 16 16 16 16 16 16 16 16 16 16
Gas Pipe - OD (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22 Type I Type V
Inlet Pipe of Humidifier (Female) G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2"
Drain Pipe - ID (mm) 25 25 25 25 25 25 25 25 25 25 25 25 25 Data Sheet of CyberMate (>20kW) Air Cooled Condenser
TM
Envicool
DC035 1 1650 1270 653 DN32 130 I
Remark: DC040 1 1650 1270 653 DN32 145 I
Return air condition: 24℃ / 50% RH. DC050 2 1950 1270 653 DN40 180 I
DC060 2 1950 1270 653 DN40 220 I
EC fan configured as standard. DC070 2 2450 1270 653 DN50 240 I
Electronic expansion valve as standard. DC080 2 2450 1270 653 DN50 260 I
*:For modularized system, fan quantity is 2. DC090 3 3650 1270 653 DN65 320 I
DC100 3 3650 1270 653 DN65 330 I
DC120 3 3650 1270 653 DN65 380 I
DC280 6 3660 2200 1840 DN65 1050 V
DC380 8 4760 2200 1840 DN80 1400 V
www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool
CyberMateTM Series of CW Unit Data Sheet of CyberMateTM Modular Chilled Water Unit
Model 40 50 60 70 80 90 100 120 130 150 160 180 200
Highlights of CW Unit Design Highlights of CW Unit Design Power Supply 380V 3Ph - 50Hz
11 Air Discharge Upflow / Downflow
12 High Reliability EVO Display System Performance Specification
• High quality components with strict authentication • 7-inch, 800x480 dot matrix true color touch screen Total Cooling Capacity (kW) 45.3 50.0 60.4 70.7 80.4 93.9 100.0 126 131.7 150.0 160.8 181.2 202.2
• Running test in factory before delivery of each unit • Temperature and humidity curves
Sensible Cooling Capacity (kW) 39.4 43.6 52.6 63.5 73.6 83.1 87.2 112.1 120.9 130.8 140.2 157.8 170.8
• Graphical display of device running status
• Multi-level password protection FLA-A 14.7 14.7 14.8 26.3 26.3 26.3 26.3 31.9 31.9 31.9 32.4 32.4 32.4
High Energy Efficiency Flow Rate - m /h 3
7.8 8.6 10.4 12.1 13.8 16.1 17.1 21.6 22.6 25.7 27.6 31.1 34.7
• Precise valve and variable airflow control, adjust Indoor Fan Section
the cooling capacity output and airflow to suit the
EVO Storage System
Airflow - m3/h 11400 11400 14000 20800 24400 22800 22800 33000 34200 34200 37200 42000 42000
temperature change of rack • Multiple history alarms, expanded storage of history
• EVO controller to ensure optimum cooling efficiency alarms is provided Quantity of Fan 1 1 1 2 2 2 2 3 3 3 3 3 3
• Efficient EC fan, continuous airflow adjustment, optional • The running data will be stored every 60 seconds, Reheat Section
EC fan under floor design • and the history data can be maintained. The relevant
• Efficient electrode humidifier to realize precise humidity • data can be read directly through the computers Capacity (kW) 6 6 6 9 9 9 9 9 9 9 9 9 9
control Humidifier Section
• Efficient dehumidification design to ensure absolute
Capacity (kg/h) 6 6 6 10 10 10 10 10 10 10 10 10 10
humidity control EVO Data Collection System
Connection Size
• Able to connect multiple temperature/humidity sensors
High Adaptability and detect the temperature/humidity of the inlet/outlet air Inlet Size DN40 DN50 DN50 DN50 DN50 DN65 DN65 DN65 DN65 DN65 DN80 DN80 DN80
• Various air discharge including downflow, upflow and so of racks Outlet Size DN40 DN50 DN50 DN50 DN50 DN65 DN65 DN65 DN65 DN65 DN80 DN80 DN80
on • Control mode selected according to the rack cooling
Inlet Pipe of Humidifier (Female) G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2"
• Multiple monitoring interface demand, precise air supply to realize energy saving
Drain Pipe - ID (mm) 25 25 25 25 25 25 25 25 25 25 25 25 25
• Customized design available
EVO Team Work Function Physical Data
Width (mm) 850 850 850 1700 1700 1700 1700 2550 2550 2550 2550 2550 2550
Wide Range of Cooling Capacity • Group multiple units easily
• Shared temperature and humidity setting Depth (mm) 890 890 1000 890 890 890 890 890 890 890 1000 1000 1000
• 50kW -200kW • Team work mode: demand management, trend
Height (mm) 1975 1975 1975 1975 1975 1975 1975 1975 1975 1975 1975 1975 1975
management, rotation and standby (lead/lag), realizing
adaptive energy saving Weight (kg) 280 280 300 510 510 540 540 820 820 820 880 880 950
• Dual-coil unit can match the dual pipelined chilled water EVO Monitoring System Recommended Air Break Switch (A) 20 20 20 40 40 40 40 40 50 50 50 50 50
system design to increase the system reliability • RS485 interface as standard Cables (mm ) 2
4 4 4 6 6 6 6 6 6 6 6 6 6
• Optional SNMP and TCP/IP interface
• Optional GPRS DTU, SMS for alarm and maintenance
reminding Remark:
Return air condition: 24℃ / 50% RH.
Water/Glycol Low Control Valve: standard two-way
valve, optional three-way valve.
Envicool
*:EC fan configured as standard.
www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool
Envicool
Low noise level for condenser with compressor placed in indoor unit
Various options and SFA capability