Envicool · Data Center and Equipment Thermostat Expert

Data Center Cooling Outdoor Cabinet Cooling Energy Saving Solutions Customized Solutions
■ CyberMateTM series CRAC ■ DC series air conditioner ■ EC series indoor battery cooler ■ Customized air conditioners
■ CyberMateTM series modular CRAC ■ EC series air conditioner ■ ES series heat exchanger
■ CyberMateTM series laboratory precision CRAC ■ HC series combo air conditioner ■ FX series BTS free cooling unit
■ CyberMate TM
series museum & wine cellar CRAC ■ EX series heat exchanger ■ DC series split DC air conditioner
■ iFreecooling TM
series self-adaptive multi-joint ■ EM series cabinet monitor ■ SC series combo air conditioner
energy-saving system ■ MC series air conditioner for power with free cooling
■ XRow TM
series row-based cooling unit industry outdoor cabinet ■ ERG series heat pipe
■ XRackTM series embedded cooling ■ MX series heat exchanger for
■ XUnitTM small data center cooling solution power industry outdoor cabinet
■ XSpaceTM series big data center cooling solution ■ TC series LCD air conditioner
■ XContainerTM series container cooling solution
■ Data center free cooling energy-saving system
■ Data center heat pipe system TM

Precision Cooling Unit for Data Center

S h e n z h e n E n v i c o o l Te c h n o l o g y C o . , L t d .
Address: Building 9, Hongxin Industrial Park, Guanlan, Longhua District, Shenzhen, China
Tel: +86 (755) 6683 3272 Fax: +86 (755) 2958 8895 P.C: 518110
Http: www.envicool.com Email: intlsales@envicool.com

� Envicool reserves updating right without notice.

Save paper for the protection of forest resources


CyberMateTM Precision Cooling Unit for Data Center
Envicool

R&D Center
Date Center
01 The continual growing OPEX has become the bottleneck of the TCO control in data center.
02 Improving the energy efficiency and enhancing the management level are the key actions
Psychrometric Air-
conditioning to reduce the TCO of the data center. Low power consumption and easy manageability are
Performance Testing appreciated in the construction of data center.
Lab
The power consumption for cooling system is a significant part, while accounting it as 30-45% of
the overall power consumption in a data center. Therefore, energy efficiency of CRAC unit will
attract great attention.
With the popularity of the green data center concept, the energy effciency standards for precision
cooling units keep increasing. More and more data centers are applying the CRAC units with
Production Line and Warehouse
high energy efficiency and integration of free cooling function.

[Company Profile]
Shenzhen Envicool Technology Co., Ltd. is a hi-tech enterprise which specializes in research and development (R&D), CyberMateTM Series Precision Cooling Unit:
manufacturing, marketing of climate control products and solutions for Data Center and Data Access Stations. The team
masters the world class cooling technology, precise control technology, mechanical design technology and has obtained
With high AEER system design and team work function, CyberMate TM meets the cooling
series patents around temperature control. demand and reduces the PUE of the data center.
Envicool has various products, which are widely used in China and overseas markets, including CRAC for data center, air
conditioner for telecom outdoor enclosure, free cooling unit (FCU), heat exchanger, battery cabinet and so on.
Envicool has obtained ISO9001, ISO14001 and OHSAS18001. The products are CCC, CE, UL and TUV certified. Envicool Annual Energy Efficiency Ratio(AEER) :
adopts the Integrated Product Development (IPD) process to develop products and technologies, and utilizes the JIT and
TQC supply chain management modes to meet the customers' requirement efficiently. ∑ the heat removed from the room
AEER = (All year round)
As an associate member of China Communications Standard Association, Envicool takes an active part in the revision of ∑ CRAC cooling electricity consumption
relevant industry standards.

[Certifications] Applications
„ Computer room and data center
„ Switch room and mobile center station in telecommunication
„ High-tech environment and lab
„ Industrial automation control room and precision manufacturing workshop
ISO14001 ISO9001 OHSAS18001 CE CCC UL China Energy-saving Certification
„ Standard test room and calibration center

Envicool
„ UPS and battery room
„ Test room in hospital
„ Biochemical culture chamber
National Hi-Tech Shenzhen Hi-Tech Patents Member of CCSA Data Center Awards
Certification Certification

www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool

Configuration Nomenclature for CyberMateTM CyberMateTM Series of DX Unit (26kW - 100kW)


Function Code Description
03 1 Series Name CyberMateTM CyberMate CRAC Highlights of DX Unit Design Functions of EVO Control System
04 5 DX, single circuit
7 DX, dual circuit
2 Series Code
0 CW, cooling capacity < 100kW High Reliability EVO Display System
1 CW, cooling capacity ≥ 100kW • High quality components with strict • 7-inch, 800x480 dot matrix true color touch screen
3 Cooling 0~9 DX: 50-50kW. certification • Temperature and humidity curves
4 Capacity 0~9 CW: 50-50kW (serial code is 0), 50-150kW (serial code is 1) • Running test of each unit in factory • Graphical display of device running status
B Cooling before delivery • Multi-level password protection
5 Function H Cooling, Reheating
P Cooling, Reheating, Humidifying High Energy Efficiency EVO Storage System
E EC fan • EVO controller ensures optimum cooling efficiency
6 Fan Type • Multiple history alarms, expanded storage of history
I AC fan • Efficient EC fan, continuous airflow adjustment, optional EC alarms is provided
F Downflow fan under floor design • The running data will be stored every 60 seconds, and
S Downflow, fan under floor • Efficient and quiet flexible scroll compressor the history data can be maintained. The relevant data
7 Air Discharge
U Upflow, plenum • High efficiency with precision electronic expansion valve,
can be read directly through the computers
D Upflow, duct precision cooling control
1 380V 3Ph-50Hz • Efficient electrode humidifier to realize precise humidity control
• Efficient dehumidification design to ensure absolute humidity
8 Power Supply 2 220V 1Ph-50Hz
control
EVO Data Collection System
3 Other power input • High efficiency, low noise and variable frequency control for • Able to connect multiple temperature/humidity sensors
A Air cooled condenser fan and detect the temperature/humidity of the inlet/outlet
F Dual cool: Air cooled + iFreecoolingTM • Integrated iFreecoolingTM indirect free cooling technology air of racks
W Water cooled • Utilization of natural cold source by integrating direct free • Control mode selected according to the rack cooling
G Glycol cooled cooling with damp filter. demand, precise air supply to realize energy saving
9 System Type N Integrated direct free cooling and humidification curtain
C Chilled water: Single coil High Adaptability
T Chilled water: Dual coil • Various air discharge choices including downflow, upflow and EVO Team Work Function
D Dual cool: Chilled water + Air cooled so on • Group multiple units easily, 32 units at most
• Multiple monitoring interface • Shared temperature and humidity setting
R Dual cool: Glycol + Free cooling
• Suitable for variable ambient temperature conditions (Optional • Team work mode: demand management, trend
Special
10 X Customized. 1 means R407C refrigerant. M means modular unit low temperature startup kits) management, rotation and standby (lead/lag), realizing
Requirements
• Customized design available adaptive energy saving

EVO
controller Wide Range of Cooling Capacity EVO Monitoring System
• 26kW ~ 100kW
• RS485 interface as standard
• Single circuit indoor unit, dual circuit indoor unit
• Optional SNMP and TCP/IP interface
• Single circuit condenser, dual circuit condenser
Efficient scroll • Optional GPRS DTU, SMS for alarm and maintenance
reminding
compressor
Various Cooling System Type

Envicool
• Air cooled/Water cooled/Glycol cooled
• Dual Cool including: Chilled water+Air cooled, Chilled
Efficient water+Water cooled (Glycol)
EC fans • Dual Cool: Air cooled+iFreecoolingTM
• Dual Cool : Air cooled+Direct free cooling
Owlet fan with
variable frequency
fan speed control

www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool

Data Sheet of CyberMateTM DX Units (Air Cooled, Water Cooled, Glycol Cooled) Data Sheet of CyberMateTM Dual Cool Units (DX +CW)
Model 526 530 535 540 546 740 746 755 765 770 780 790 799 Model 526 530 535 540 546 740 746 755 765 770 780 790 799
Power Supply 380V 3Ph - 50Hz Power Supply 380V 3Ph - 50Hz
Air Discharge Upflow / Downflow
05 Air Discharge Upflow / Downflow
Performance Specification
06 Performance Specification
Total (kW) 26.8 30.9 35.9 40.3 46.9 40.7 47.6 55.6 65.8 71.6 80.2 92.6 100.2
Total Cooling Capacity (kW) 26.8 30.9 35.9 40.3 46.9 40.7 47.6 55.6 65.8 71.6 80.2 92.6 100.2 Sensible (kW) 24.2 27.9 32.6 36.4 42.3 36.8 42.9 50.2 59.3 64.5 72.7 83.6 90.6
DX
Sensible Cooling Capacity (kW) 24.2 27.9 32.6 36.4 42.3 36.8 42.9 50.2 59.3 64.5 72.7 83.6 90.6
FLA-A 28.9 31.9 39.4 41.9 49.0 44.3 49.0 52.4 59.7 64.1 71.8 84.3 86.2
FLA-A 28.3 31.3 38.7 41.2 48.0 43.6 48.0 51.3 58.5 62.9 69.3 82.5 84.3
Total (kW) 33.6 33.6 44.2 44.2 56.4 44.2 56.4 59.1 73.5 76.4 89.2 92.5 92.5
Quantity of Compressor 1 1 1 1 1 2 2 2 2 2 2 2 2 CW/
Sensible (kW) 29.2 29.2 37.7 37.7 48.6 37.7 48.6 51.2 63.2 66.0 77.8 81.7 81.7
Indoor Fan Section Glycol
Flow Rate (m3/h) 5.8 5.8 7.6 7.6 9.7 7.6 9.7 10.1 12.6 13.1 15.3 15.9 15.9
Airflow - m3/h 8000 9000 10000 11000 13000 11000 13000 14000 17000 18000 21500 23000 25000
Quantity of Compressor 1 1 1 1 1 2 2 2 2 2 2 2 2
Quantity of Fan 1 1 1 1 2 1 2 2 2 2 2 2 2 Indoor Fan Section
Reheat Section Airflow - m3/h 8000 9000 10000 11000 13000 11000 13000 14000 17000 18000 21500 23000 25000
Capacity (kW) 6 6 9 9 9 9 9 9 9 9 9 9 9 Quantity of Fan 1 1 1 1 2 1 2 2 2 2 2 2 2
Humidifier Section Reheat Section
Capacity (kg/h) 6 6 6 6 10 6 10 10 10 10 10 10 10 Capacity (kW) 6 6 9 9 9 9 9 9 9 9 9 9 9
Humidifier Section
Connection Size
Capacity (kg/h) 6 6 6 6 10 6 10 10 10 10 10 10 10
Liquid Pipe - OD (mm) 16 16 16 16 16 16 16 16 16 16 16 16 16
Connection Size
Gas Pipe - OD (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22
DX Liquid Pipe - OD (mm) 16 16 16 16 16 16 16 16 16 16 16 16 16
Inlet Pipe of Humidifier (Female) G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2"
DX Gas Pipe - OD (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22
Drain Pipe - ID (mm) 25 25 25 25 25 25 25 25 25 25 25 25 25 CW Inlet/Outlet DN32 DN32 DN40 DN40 DN40 DN40 DN40 DN40 DN50 DN50 DN50 DN50 DN50
Physical Data Inlet Pipe of Humidifier (Female) G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2"
Width (mm) 1050 1050 1400 1400 1700 1400 1700 1700 2100 2100 2550 2550 2550 Drain Pipe - ID (mm) 25 25 25 25 25 25 25 25 25 25 25 25 25
Depth (mm) 890 890 890 890 890 890 890 890 890 890 890 890 890 Physical Data
Height (mm) 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 Width (mm) 1050 1050 1400 1400 1700 1400 1700 1700 2100 2100 2550 2550 2550
Depth (mm) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Weight (kg) 365 370 410 415 530 415 535 550 720 730 800 820 825
Height (mm) 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990
Water/Glycol Cool Unit Parameter
Weight (kg) 395 400 460 465 600 465 595 620 820 830 920 925 940
Inlet/Outlet Connection (mm) 35.0 42.0 42.0 42.0 54.0 42.0 54.0 54.0 54.0 63.0 63.0 70.0 70.0
Water/Glycol Cool Unit Parameters
Water Flow Rate - m3/h 6.0 7.0 8.2 9.2 10.7 9.2 10.8 12.5 14.9 16.4 18.3 21.0 22.8 Inlet/Outlet Connection (mm) 35.0 42.0 42.0 54.0 54.0 42.0 54.0 54.0 54.0 63.0 63.0 70.0 70.0
Pressure Drop (kPa) 86.0 99.2 76.0 83.1 94.7 82.8 95.4 75.1 85.6 93.1 71.0 77.6 82.5 Water Flow Rate - m3/h 6.0 7.0 8.2 9.2 10.7 9.2 10.8 12.5 14.9 16.4 18.3 21.0 22.8
Inlet/Outlet Connection (mm) 35.0 42.0 42.0 54.0 54.0 42.0 54.0 54.0 54.0 63.0 63.0 70.0 70.0 Pressure Drop (kPa) 86.0 99.2 76.0 83.1 94.7 82.8 95.4 75.1 85.6 93.1 71.0 77.6 82.5
Glycol
Flow Rate - m3/h 7.1 8.3 9.6 10.8 12.6 10.8 12.7 14.7 17.6 19.3 21.6 24.7 26.8 Inlet/Outlet Connection (mm) 35.0 42.0 42.0 54.0 54.0 42.0 54.0 54.0 54.0 63.0 63.0 70.0 70.0
(40%) Glycol
Pressure Drop (kPa) 99.8 76.6 86.0 95.8 75.3 95.4 112.9 84.8 99.3 73.3 79.1 88.2 95.0 Flow Rate - m3/h 7.1 8.3 9.6 10.8 12.6 10.8 12.7 14.7 17.6 19.3 21.6 24.7 26.8
(40%)
Breakers & Cables Pressure Drop (kPa) 99.8 76.6 86.0 95.8 75.3 95.4 112.9 84.8 99.3 73.3 79.1 88.2 95.0
Breakers & Cables
Indoor Recommended Air Break Switch (A) 50 50 63 63 80 63 80 80 100 100 125 125 125
Indoor Recommended Air Break Switch (A) 50 50 63 63 80 63 80 80 100 100 125 125 125
Unit Cables (mm2) 10 10 10 16 16 16 16 16 16 16 25 25 25
Unit Cables (mm2) 10 10 16 16 16 16 16 16 16 16 25 25 25
Outdoor Recommended Air Break Switch (A) 20 20 20 20 20 20 20 20 20 20 20 20 20 Outdoor Recommended Air Break Switch (A) 20 20 20 20 20 20 20 20 20 20 20 20 20
Unit Cables (mm2) 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Unit Cables (mm2) 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

Envicool
Remark: Remark:
ƒ Return air condition: 24℃ / 50% RH. ƒ Return air condition: 24℃ / 50% RH.
ƒ Water/Glycol low control valve: standard two-way valve, ƒ Water/Glycol low control valve: standard two-way valve,
optional three-way valve. optional three-way valve.
ƒ EC fan configured as standard. ƒ EC fan configured as standard.
ƒ Electronic expansion valve as standard. ƒ Electronic expansion valve as standard.
*:For modularized system, fan quantity is 2. *:For modularized system, fan quantity is 2.

www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool

iFreecooling TM Technology Data Sheet of CyberMateTM Dual Cool Units (Air Cooled + iFreecooling)
„ Making full use of the natural cold source by stopping the compressor running in low ambient temperature, the power Model 526 530 535 540 546 740 746 755 765 770 780 790 799
consumption of the cooling system and PUE of the data center is greatly reduced. Power Supply 380V 3Ph - 50Hz
07 „ Protect the temperature, humidity and cleanness of data center from outside and ensure its high reliability Air Discharge Upflow / Downflow
TM
08 „ When iFreecooling runs in low ambient temperature, the compressor system will save more than 96% energy, whole cooling Performance Specification of DX Unit
system will save more than 70% energy, and 25%~35% reduction for the energy consumption of data center will be realized. Total Cooling Capacity (kW) 26.8 30.9 35.9 40.3 46.9 40.7 47.6 55.6 65.8 71.6 80.2 92.6 100.2
TM
„ iFreecooling can run together with DX both in the Spring and Autumn to make best use of free cooling Sensible Cooling Capacity (kW) 24.2 27.9 32.6 36.4 42.3 36.8 42.9 50.2 59.3 64.5 72.7 83.6 90.6
TM
„ One iFreecooling system can work together with multiple DX units FLA-A 28.3 31.3 38.7 41.2 48.0 43.6 48.0 51.3 58.5 62.9 69.3 82.5 84.3
Quantity of Compressor 1 1 1 1 1 2 2 2 2 2 2 2 2
Indoor Fan Section
Airflow - m3/h 8000 9000 10000 11000 13000 11000 13000 14000 17000 18000 21500 23000 25000
Quantity of Fan 1 1 1 1 2 1 2 2 2 2 2 2 2
Reheat Section
Capacity (kW) 6 6 9 9 9 9 9 9 9 9 9 9 9

Power consumption
Humidifier Section
of condenser fan
Capacity (kg/h) 6 6 6 6 10 6 10 10 10 10 10 10 10
Power consumption
of indoor unit fan
Connection Size of DX Unit
Power consumption
of iFreecooling system Liquid Pipe - OD (mm) 16 16 16 16 16 16 16 16 16 16 16 16 16
Power consumption
of compressor
Gas Pipe - OD (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22
Inlet Pipe of Humidifier (Female) G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2"
Drain Pipe - ID (mm) 25 25 25 25 25 25 25 25 25 25 25 25 25
Physical Data of DX Unit
Width (mm) 1050 1050 1400 1400 1700 1400 1700 1700 2100 2100 2550 2550 2550
Power consumption Power consumption Power consumption Power consumption
of common CRAC of CyberMate of CyberMate + of iFreecooling in
iFreecooling in Spring low ambient temperature
and Autumn
Depth (mm) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Height (mm) 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990
Weight (kg) 410 420 440 445 560 445 565 580 760 770 840 850 865

Suitable Regions for iFreecooling System TM Connection Size of iFreecooling TM


Liquid Pipe - OD (mm) 16 16 16 16 16 16 16 16 19 19 19 19 19
Gas Pipe - OD (mm) 22 22 22 22 22 22 22 22 28 28 28 28 28
Breakers & Cables

Indoor Recommended Air Break Switch (A) 50 50 63 63 80 63 80 80 100 100 125 125 125
Annual energy saving rate ≥ 35% Unit Cables (mm ) 2
10 10 16 16 16 16 16 16 16 16 25 25 25
Annual energy saving rate ≥ 25% Outdoor Recommended Air Break Switch (A) 20 20 20 20 20 20 20 20 20 20 20 20 20
Unit Cables (mm2) 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Annual energy saving rate ≥ 15%

Remark:

Envicool
ƒ Return air condition: 24℃ / 50% RH.
ƒ EC fan configured as standard.
ƒ Electronic expansion valve as standard.
*:For modularized system, fan quantity is 2.

www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool

Data Sheet of CyberMateTM Dual Cool Units (DX + Direct Free Cooling) CyberMateTM (>20kW) Air Cooled Condenser
Model 526 530 535 540 546 740 746 755 765 770 780 790 799
„ Strengthen aluminum alloy enclosure and stainless steel
Power Supply 380V 3Ph 50Hz
connection parts
Air Discharge Upflow / Downflow
„ Variable frequency fan speed control, efficient energy saving
09 Performance Specification
„ Bionic-type fan, low noise
10 Total Cooling Capacity (kW) 26.8 30.9 35.9 40.3 46.9 40.7 47.6 55.6 65.8 71.6 80.2 92.6 100.2 TM
„ Integrated iFreecooling design
Sensible Cooling Capacity (kW) 24.2 27.9 32.6 36.4 42.3 36.8 42.9 50.2 59.3 64.5 72.7 83.6 90.6 „ Adapting to various climate conditions
FLA-A 28.3 31.3 38.7 41.2 48.0 43.6 48.0 51.3 58.5 62.9 69.3 82.5 84.3 „ Single/dual circuit design
Quantity of Compressor 1 1 1 1 1 2 2 2 2 2 2 2 2
Indoor Fan Section
Airflow - m3/h 8000 9000 10000 11000 13000 11000 13000 14000 17000 18000 21500 23000 25000
Quantity of Fan 1 1 1 1 2 1 2 2 2 2 2 2 2
Reheat Section
Capacity (kW) 6 6 9 9 9 9 9 9 9 9 9 9 9
Humidifier Section
Capacity (kg/h) 6 6 6 6 10 6 10 10 10 10 10 10 10
Connection Size of DX Unit
Liquid Pipe - OD (mm) 16 16 16 16 16 16 16 16 16 16 16 16 16
Gas Pipe - OD (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22 Type I Type V
Inlet Pipe of Humidifier (Female) G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2" G1 / 2"
Drain Pipe - ID (mm) 25 25 25 25 25 25 25 25 25 25 25 25 25 Data Sheet of CyberMate (>20kW) Air Cooled Condenser
TM

Physical Data of DX Unit Quantity of Fan


Width (mm) 1050 1050 1400 1400 1700 1400 1700 1700 2100 2100 2550 2550 2550 Model Length (mm) Height (mm) Width (mm) Weight (kg) Liquid Line-OD (mm) Hot Gas Line-OD (mm) Type
(s)
Depth (mm) 890 890 890 890 890 890 890 890 890 890 890 890 890 CS25 1 1310 982 653 110 16 22 I
Height (mm) 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 CS32 1 1310 982 653 115 19 22 I
Weight (kg) 365 370 410 415 530 415 535 550 720 730 800 820 825 CS38 1 1610 982 653 130 19 22 I
Free Cooling Inlet Unit Specification CS46 1 1610 1270 653 140 19 28 I
Model FS1050 FS1050 FS1400 FS1400 FS1700 FS1400 FS1700 FS1700 FS2100 FS2100 FS2550 FS2550 FS2550 CS54 1 1910 1270 653 150 19 28 I
Airflow (m3/h) 7600 7600 9500 9500 12350 9500 12350 13300 16150 17100 20425 21850 21850 CS66 2 1910 1270 653 160 19 28 I
CS78 2 2410 1270 653 200 19 28 I
Sensible Cooling Capacity (kW) △ t=10℃ 25.7 25.7 38.9 38.9 45.7 38.9 45.7 53.6 64.0 68.6 77.9 97.2 97.2
CS86 2 2410 1270 689 240 19 28 I
Humidifying Capacity (kg/h) - - - - - - - - 29.0 30.7 36.7 39.2 39.2
CD46 1 1610 1270 653 140 19 22 I
Width (mm) 1050 1050 1400 1400 1700 1400 1700 1700 2100 2100 2550 2550 2550 CD54 1 2110 1270 653 160 19 28 I
Depth (mm) 600 600 600 600 600 600 600 600 600 600 600 600 600 CD66 2 2110 1270 653 170 19 28 I
Height (mm) 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 1990 CD78 2 2410 1270 653 200 19 28 I
Weight (kg) 100 100 140 140 160 140 160 160 200 200 240 240 240 CD86 2 2410 1270 689 220 19 28 I
Free Cooling Outlet Unit Specification
Model PF050-C PF050-C PF050-C PF050-C PF150-C PF050-C PF150-C PF150-C PF150-C PF150-C PF150-C PF150-C PF150-C Data Sheet of CyberMateTM Air Cooled+iFreecoolingTM Integrated Condenser
Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 Quantity of Liquid Line for Hot Gas Line Liquid Line for Hot Gas Line
Airflow (m3/h) 5000 5000 5000 5000 11000 5000 11000 11000 11000 11000 11000 11000 11000 Model Length (mm) Height (mm) Width (mm) Weight (kg) Type
Fan (s) DX-OD (mm) for DX-OD (mm) iF-OD (mm) for iF-OD (mm)
Width (mm) 500 500 500 500 1160 500 1160 1160 1160 1160 1160 1160 1160 CS32F 1 1480 1270 687 135 19 22 16 22 I
Depth (mm) 375 375 375 375 405 375 405 405 405 405 405 405 405 CS38F 1 1630 1270 687 150 19 22 16 22 I
Height (mm) 480 480 480 480 1035 480 1035 1035 1035 1035 1035 1035 1035 CS46F 1 2135 1270 687 170 22 28 16 28 I
Weight (kg) 35 35 35 35 50 35 50 50 50 50 50 50 50 CS54F 2 2135 1270 687 180 22 28 16 28 I
Breakers & Cables CS66F 2 2435 1270 687 210 22 28 16 28 I
CS78F 2 2435 1270 710 270 22 28 16 28 I
Indoor Recommended Air Break Switch (A) 50 50 63 63 80 63 80 80 100 100 125 125 125
CS86F 2 2835 1270 710 310 22 28 16 28 I
Unit Cables (mm2) 10 10 10 16 16 16 16 16 16 16 25 25 25
Outdoor Recommended Air Break Switch (A)
Unit Cables (mm2)
20
2.5
20
2.5
20
2.5
20
2.5
20
2.5
20
2.5
20
2.5
20
2.5
20
2.5
20
2.5
20
2.5
20
2.5
20
2.5
Data Sheet of CyberMateTM Air Cooled Condenser
Model Quantity of Fan (s) Length (mm) Height (mm) Width (mm) Connection Size Weight (kg) Type

Envicool
DC035 1 1650 1270 653 DN32 130 I
Remark: DC040 1 1650 1270 653 DN32 145 I
ƒ Return air condition: 24℃ / 50% RH. DC050 2 1950 1270 653 DN40 180 I
DC060 2 1950 1270 653 DN40 220 I
ƒ EC fan configured as standard. DC070 2 2450 1270 653 DN50 240 I
ƒ Electronic expansion valve as standard. DC080 2 2450 1270 653 DN50 260 I
*:For modularized system, fan quantity is 2. DC090 3 3650 1270 653 DN65 320 I
DC100 3 3650 1270 653 DN65 330 I
DC120 3 3650 1270 653 DN65 380 I
DC280 6 3660 2200 1840 DN65 1050 V
DC380 8 4760 2200 1840 DN80 1400 V

www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool

CyberMateTM Series of CW Unit Data Sheet of CyberMateTM Modular Chilled Water Unit
Model 40 50 60 70 80 90 100 120 130 150 160 180 200
Highlights of CW Unit Design Highlights of CW Unit Design Power Supply 380V 3Ph - 50Hz
11 Air Discharge Upflow / Downflow
12 High Reliability EVO Display System Performance Specification
• High quality components with strict authentication • 7-inch, 800x480 dot matrix true color touch screen Total Cooling Capacity (kW) 45.3 50.0 60.4 70.7 80.4 93.9 100.0 126 131.7 150.0 160.8 181.2 202.2
• Running test in factory before delivery of each unit • Temperature and humidity curves
Sensible Cooling Capacity (kW) 39.4 43.6 52.6 63.5 73.6 83.1 87.2 112.1 120.9 130.8 140.2 157.8 170.8
• Graphical display of device running status
• Multi-level password protection FLA-A 14.7 14.7 14.8 26.3 26.3 26.3 26.3 31.9 31.9 31.9 32.4 32.4 32.4
High Energy Efficiency Flow Rate - m /h 3
7.8 8.6 10.4 12.1 13.8 16.1 17.1 21.6 22.6 25.7 27.6 31.1 34.7
• Precise valve and variable airflow control, adjust Indoor Fan Section
the cooling capacity output and airflow to suit the
EVO Storage System
Airflow - m3/h 11400 11400 14000 20800 24400 22800 22800 33000 34200 34200 37200 42000 42000
temperature change of rack • Multiple history alarms, expanded storage of history
• EVO controller to ensure optimum cooling efficiency alarms is provided Quantity of Fan 1 1 1 2 2 2 2 3 3 3 3 3 3
• Efficient EC fan, continuous airflow adjustment, optional • The running data will be stored every 60 seconds, Reheat Section
EC fan under floor design • and the history data can be maintained. The relevant
• Efficient electrode humidifier to realize precise humidity • data can be read directly through the computers Capacity (kW) 6 6 6 9 9 9 9 9 9 9 9 9 9
control Humidifier Section
• Efficient dehumidification design to ensure absolute
Capacity (kg/h) 6 6 6 10 10 10 10 10 10 10 10 10 10
humidity control EVO Data Collection System
Connection Size
• Able to connect multiple temperature/humidity sensors
High Adaptability and detect the temperature/humidity of the inlet/outlet air Inlet Size DN40 DN50 DN50 DN50 DN50 DN65 DN65 DN65 DN65 DN65 DN80 DN80 DN80

• Various air discharge including downflow, upflow and so of racks Outlet Size DN40 DN50 DN50 DN50 DN50 DN65 DN65 DN65 DN65 DN65 DN80 DN80 DN80
on • Control mode selected according to the rack cooling
Inlet Pipe of Humidifier (Female) G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2" G1/2"
• Multiple monitoring interface demand, precise air supply to realize energy saving
Drain Pipe - ID (mm) 25 25 25 25 25 25 25 25 25 25 25 25 25
• Customized design available
EVO Team Work Function Physical Data
Width (mm) 850 850 850 1700 1700 1700 1700 2550 2550 2550 2550 2550 2550
Wide Range of Cooling Capacity • Group multiple units easily
• Shared temperature and humidity setting Depth (mm) 890 890 1000 890 890 890 890 890 890 890 1000 1000 1000
• 50kW -200kW • Team work mode: demand management, trend
Height (mm) 1975 1975 1975 1975 1975 1975 1975 1975 1975 1975 1975 1975 1975
management, rotation and standby (lead/lag), realizing
adaptive energy saving Weight (kg) 280 280 300 510 510 540 540 820 820 820 880 880 950

Single coil and Dual coil Unit Breakers & Cables

• Dual-coil unit can match the dual pipelined chilled water EVO Monitoring System Recommended Air Break Switch (A) 20 20 20 40 40 40 40 40 50 50 50 50 50
system design to increase the system reliability • RS485 interface as standard Cables (mm ) 2
4 4 4 6 6 6 6 6 6 6 6 6 6
• Optional SNMP and TCP/IP interface
• Optional GPRS DTU, SMS for alarm and maintenance
reminding Remark:
ƒ Return air condition: 24℃ / 50% RH.
ƒ Water/Glycol Low Control Valve: standard two-way
valve, optional three-way valve.

Envicool
*:EC fan configured as standard.

www.envicool.com
CyberMateTM Precision Cooling Unit for Data Center
Envicool

CyberMateTM DX (6kW-20kW) Units Data Sheet of DX CyberMateTM (6kW-20kW) Units


Return air condition: 24℃ / 50%RH
Indoor Unit Model 505 505 508 508 512 516 520
Power Supply 220V 1Ph - 50Hz 380V 3Ph - 50Hz 220V 1Ph - 50Hz 380V 3Ph - 50Hz 380V 3Ph - 50Hz 380V 3Ph - 50Hz 380V 3Ph - 50Hz
13
Applications Air Discharge Upflow / Downflow
14 Performance Specification
„ IT Equipment Room Total (kW) 6.0 6.0 7.5 7.5 12.5 16.8 20.2
„ Small Data Center Sensible (kW) 5.0 5.0 6.9 6.9 11.3 15.3 18.3
AC
Fan FLA-A (Cooling) 14.0 14.0 17.3 6.8 12.8 12.9 17.9
„ Industrial Clean Room FLA-A (Cooling, Reheating,
27.7 18.6 44.6 15.9 21.9 22.0 27.0
Humidifying)
„ Constant Temperature and Humidity Process Workshop
Total (kW) - 6.1 - 7.6 12.6 16.9 20.4
„ Laboratory Sensible (kW) - 5.1 - 7.0 11.5 15.5 18.5
EC
„ Electric Power Equipment Room Fan FLA-A (Cooling) - 13.2 - 6.0 10.9 12.6 17.3
FLA-A (Cooling, Reheating,
- 17.8 - 15.1 19.9 21.7 26.4
„ Railway/Subway Machine Room Humiditifying)
Quantity of Compressor 1 1 1 1 1 1 1
„ Base Station and Small Telecom Switch Room Quantity of Fan 1 1 1 1 1 1 1
„ SME Telecom Switch Room Airflow (m3/h) 1500 1500 2300 2300 2700 4500 5500
Reheating Capacity (kW) 3 3 6 6 6 6 6
Humidifying Capacity (kg/h) - 2.8 - 2.8 2.8 6 6
Connection Size
Liquid Pipe - OD (mm) 9.52 9.52 9.52 9.52 12.7 12.7 12.7
Gas Pipe - OD (mm) 12.7 12.7 12.7 12.7 15.88 19 19
Features Inlet Pipe of Humidifier (Female) - G1 / 2" - G1 / 2" G1 / 2" G1 / 2" G1 / 2"
Drain Pipe - ID (mm) 19 19 19 19 19 25 25
„ Design of appearance and color consistent with IT equipments Physical Data
„ Intelligent precise control function for constant temperature and humidity Width (mm) 600 600 600 600 600 750 750
Depth (mm) 550 550 550 550 550 750 750
„ Design for the continuous 365X24 operation under full range of climate Height (mm) 1900 1900 1900 1900 1900 1950 1950
„ Long lifetime design with low operating and maintenance costs Weight (kg) 120 120 130 130 150 280 300
Outdoor Unit Specification
„ Large airflow supply with high SHR and low power consumption CyberMate CyberMate CyberMate CyberMate CyberMate CyberMate CyberMate
Outdoor Unit Model
„ Uniformity of room temperature by long-distance supply air 505EC 505EC 508EC 508EC 512EC 516EC 520EC
Width (mm) 800 800 800 800 800 1500 1500
„ Ensure room cleanness by high level air filter configuration and large air flow circuit Depth (mm) 360 360 360 360 360 360 360
„ Ultra-wide input power adaptability, automatic phase sequence switching function, Height (mm) 790 790 790 790 1240 1240 1240
Weight (kg) 45 45 45 45 60 100 110
optional automatic re-start and delayed startup function
Operating Temperature Range (Standard) -15 ~ 45℃ -15 ~ 45℃ -15 ~ 45℃ -15 ~ 45℃ -15 ~ 45℃ -15 ~ 45℃ -15 ~ 45℃
„ Remote monitoring and control through dry contact or RS485 communication interface Operating Temperature Range (with Low-
- 40 ~ 45℃ - 40 ~ 45℃ - 40 ~ 45℃ - 40 ~ 45℃ - 40 ~ 45℃ - 40 ~ 45℃ - 40 ~ 45℃
temerature Startup Kits)
with open protocol
Breakers & Cables
„ Menu-based large LCD display with multi-level password protection function Recommended Air Break Switch (A) 40 32 63 32 32 50 50
Outdoor Unit Power Cables (mm2) 3*1.5 3*1.5 3*1.5 3*1.5 3*1.5 3*1.5 3*1.5
„ Standby (master/slave) mode and rotating mode available
Main Power Cables (mm2) - Cooling 3*4 5*4 3*4 5*2.5 5*4 5*4 5*6
„ Self-diagnosis function, various system diagnosis, alarm, and protection function Main Power Cables (mm2) - Cooling,
3*6 5*4 3*10 5*4 5*6 5*6 5*6
Reheating, Humidifying
„ Parameter and operation/alarm record auto-protection under power loss
„ 300 maximum storage for history alarm record

Envicool
„ Low noise level for condenser with compressor placed in indoor unit
„ Various options and SFA capability