LRP16.

5XS
Diesel Generating Sets

STANDARD FEATURES
 Set mount radiator with engine driven fan
 Cooling system standard for 40°C ambient
 Anti-vibration mounts between engine / alternator
and baseframe
 Baseframe fuel tank
 Protective grille for fan and rotating parts
 Exhaust bellow and industrial silencer
 12VDC starter motor and battery
 Generator sets are CE Certified
 Standard 3P manual output breaker
 Coolant and oil drains with valve
®
 Each LionRock generating set will go through
factory test at 0%, 25%, 50%, 75%, 100% and
110% of rated capacity
STANDARD AND QUALITY
Pictureshowswithoptions
 All generator sets comply with international standards including
ISO8528, ISO3046, IEC60034, BS5000
 Manufacturing standard certified to ISO9001, ISO14001,
ISO18001
Engine make & model: Perkins / 403D-15G  CE certificate for generator set

Alternator make & model: Leroy Somer / TAL-A40-G RATING DEFINITION AS PER ISO8528
 Prime - Output available with varying load for an unlimited time.
Frequency: 60Hz Average power output is 70% of the prime power rating. Typical
peak demand is 100% of prime rated kWe with 10% overload
Voltage: 230V capability for emergency use for a maximum of 1 hour in 12.
Control panel Std: LR2060  Standby - Output available with varying load during a normal
power supply failure. Average power output is 80% of the standby
Performance class ISO8528: G2 power rating. Typical annual operating time less than 500hours.
No overload is available.

Power Ratings at 0.8 power factor


Voltage Standby Prime Maximum current
(V) kVA kW kVA kW (Amp)
230 16.5 13.2 15 12 52.17

Fuel Consumption
Load (%) Standby 100 75 50
(L/h) 4.9 4.3 3.2 2.2
* Fuel consumption data base on diesel fuel with the density of 0.85kg/L and conforming to BS2869: 2006, Class A2.

L W
Dimensions Weight Dual-wall Fuel Tank
Length (L) Width (W) Height (H) Dry Baseframe
mm mm mm kg litres
1800 750 1400 650 1000
LRP16.5XS
Engine
Technical Data Cooling System
Manufacturer: Perkins Coolant capacity with radiator: Litres 6.0
Model: 403D-15G Maximum coolant temperature: °C 112
Cylinders / Alignment: 3 / In Line Radiator air flow: m3/min 43.2
Combustion cycle: 4 Stroke Fan power: kW 0.3
Bore / Stroke: mm 84 / 90 External resistance: Pa 125
Aspiration: Naturally aspirated Thermostat operating temperature: °C 82~95
Cooling: Water
Compression ratio: 22.5:1 Energy Balance
Displacement: litres 1.496 Heat rejection to exhaust: kW 11.8
Governor: Mechanical Heat rejection to coolant: kW 15.2(JW)
Engine speed: RPM 1800 Heat rejection to ambient: kW 4.3
Prime power at rated RPM: kW 14.7
Maximum power at rated RPM: kW 16.2 Combustion Air
Speed regulation: % ±0.75 Air flow: L/s 20.5
BMEP: bar 7.22 Maximum intake restriction: kPa 6.4
Piston speed: m/s 5.4 Air filter: Dry element type

Lubrication System Exhaust


Oil capacity: Litres 6.0 Exhaust gas flow rate: L/s 56
Oil consumption at full load: L/hr 0.01 Exhaust gas temperature: °C 505
Minimum oil pressure: bar 1.2 Allowable back pressure: kPa 10.2
Maximum oil pressure: bar 3.6

Fuel System
Fuel pump flow rate: L/hr 63
Pump lifting height: m 0.8

Engines
Alternator
Technical Data Technical Data
Manufacturer: Leroy Somer Efficiency at 0.8PF at 100%: % 87.1
Alternator model: TAL-A40-G Efficiency at 0.8PF at 75%: % 88.2
Rated voltage: V 230 Direct-axis transient reactance saturated, X'd: % 19.1
o
Prime rating @ 40 C: kVA 17 Direct-axis sub-transient reactance saturated, X"d: % 9.5
Standby rating @ 27oC: kVA 19 Short circuit ratio, Kcc: 0.45
Insulation class: H Excitation system: SHUNT
Winding pitch: 2/3 AVR model: R120
Number of wires: 12 Voltage regulation: % ±1
Protection: IP23 Short circuit current: kA 0.8
Altitude without derating: m ≤1000 Total harmonic distortion, THD at full linear load: % <5
Overspeed capability: RPM 2250 Waveform NEMA = TIF: <50
Air flow: m3 /s 0.1 Waveform IEC = THF: % <2
LRP16.5XS
Engines
Control System
Technical data
Model Protection
 LR2060  Mechanical
 Overspeed
Type  High coolant temperature
 Remote start  Low oil pressure
 Start up failure lock out
Manual mode  Emergency Stop
 Available local  Electrical
 Over and under frequency
Electrical measurement  Over and under voltage
 Voltage (P-P, P-N)  Overload
 Current  Overcurrent
 Frequency  Power factor
 Current unbalance
 Power factor
Communication
Energy Meter  USB (Programming)
 kW
 kWh Control
 kVA  Auto/Manual
 Start/stop button
Mechanical measurement  Alarm/fault acknowledge
 Water temperature  Menu button
 Oil Pressure  Display navigation buttons
 Engine speed
 Running hours Event log and memory
 Number of start  Up to 350 events
 Battery voltage
Analogue input
Digital input/output  3
 6/6
Options are shown in picture for reference only

CONTROL SYSTEM OPTIONS


Features Alternative control modules
 Automatic mains failure  Wide range of control module options including:
 Fuel tank content in % ComAp
 Oil temperature gauge Deepsea
 Modbus SNMP Woodward
 Modbus TCP/IP Ethernet Smartgen etc.
 Extended input/output modules  Multiple generators parallel as well as parallel with mains
 RS485 Modbus power

Engines
Options:
 Jacket water heater  Spring type AV mounts  Bearing temperature sensor
 Low coolant level switch  Acoustic enclosure  Digital AVR upgrade
 Electronic tank content gauge  Anti-condensation heater
 Battery float charger  Winding thermistor
 50°C radiator  Winding temperature sensor

WARRANTY
®
 LionRock Power provides one-source responsibility for the generator set and accessories.
 Engine and alternator are guaranteed for a period of 12 months from the date of commissioning or 18 months from shipping (whichever comes
earlier).
 After sales support for warranty service, backed by engine/alternator global service network in addition to local dealer. Refer to the warranty
documentation for details.
LRP16.5XS
Soundproof Canopy

Stainless steel locks and handles on doors


 Black zinc die cast hinges on doors proven to withstand
extreme weather conditions
 Zinc plated standard fastener with stainless steel option
 Enclosure made of sheet steel pre-treated with zinc
phosphate prior to polyester powder coating

Secure, lockable doors prevent unauthorized access


Dimensions and Weights to control panel, fuel fill and battery
Length (L): mm 2250  Emergency stop buttons mounted on enclosure exterior
Width (W): mm 1000 surface
Height (H): mm 2100  All moving parts including Cooling fan, charging
Weight: kg 1200 alternator, belt are fully guarded
Fuel Tank Capacity: litres 1000

Hinged doors of 180 deg swing on both sides of the


enclosure for easy access and maintenance
 Lube oil and water drains hosed to baseframe side to
exterior
 Removable end panels allow access to radiator,
h
exhaust silencer and alternator rear
 Exhaust silencer inside enclosure

L w Easy Transportable
 Lifting points on both side of baseframe
Sound Pressure Levels
 Anchor and drag points at baseframe ends
100% Load 60Hz
Prime: dBA@7m 70
* Measurement and calculation as per ISO 8528-10:1998

Unit 904, 9/F., Fu Hang Industrial Building, 1 Hok Yuen Street East,
Hung Hom, Kowloon, Hong Kong.
Tel: +852 2766 9787 Fax: +852 2766 9774
3Tech Corporate Limited www.3tech.net eMail: info@3tech.net For more complete information on 3Tech products, dealer services, and power solutions,
visit our website: www.3Tech.net
PM - GM - LRP16.5XS/60Hz/4PP/20201210

This document is not contractual - The 3Tech company reserves the right to modify any of the characteristics stated in this document without notice, in a constant effort to improve the quality of its products.

You might also like