5XS
Diesel Generating Sets
STANDARD FEATURES
Set mount radiator with engine driven fan
Cooling system standard for 40°C ambient
Anti-vibration mounts between engine / alternator
and baseframe
Baseframe fuel tank
Protective grille for fan and rotating parts
Exhaust bellow and industrial silencer
12VDC starter motor and battery
Generator sets are CE Certified
Standard 3P manual output breaker
Coolant and oil drains with valve
®
Each LionRock generating set will go through
factory test at 0%, 25%, 50%, 75%, 100% and
110% of rated capacity
STANDARD AND QUALITY
Pictureshowswithoptions
All generator sets comply with international standards including
ISO8528, ISO3046, IEC60034, BS5000
Manufacturing standard certified to ISO9001, ISO14001,
ISO18001
Engine make & model: Perkins / 403D-15G CE certificate for generator set
Alternator make & model: Leroy Somer / TAL-A40-G RATING DEFINITION AS PER ISO8528
Prime - Output available with varying load for an unlimited time.
Frequency: 60Hz Average power output is 70% of the prime power rating. Typical
peak demand is 100% of prime rated kWe with 10% overload
Voltage: 230V capability for emergency use for a maximum of 1 hour in 12.
Control panel Std: LR2060 Standby - Output available with varying load during a normal
power supply failure. Average power output is 80% of the standby
Performance class ISO8528: G2 power rating. Typical annual operating time less than 500hours.
No overload is available.
Fuel Consumption
Load (%) Standby 100 75 50
(L/h) 4.9 4.3 3.2 2.2
* Fuel consumption data base on diesel fuel with the density of 0.85kg/L and conforming to BS2869: 2006, Class A2.
L W
Dimensions Weight Dual-wall Fuel Tank
Length (L) Width (W) Height (H) Dry Baseframe
mm mm mm kg litres
1800 750 1400 650 1000
LRP16.5XS
Engine
Technical Data Cooling System
Manufacturer: Perkins Coolant capacity with radiator: Litres 6.0
Model: 403D-15G Maximum coolant temperature: °C 112
Cylinders / Alignment: 3 / In Line Radiator air flow: m3/min 43.2
Combustion cycle: 4 Stroke Fan power: kW 0.3
Bore / Stroke: mm 84 / 90 External resistance: Pa 125
Aspiration: Naturally aspirated Thermostat operating temperature: °C 82~95
Cooling: Water
Compression ratio: 22.5:1 Energy Balance
Displacement: litres 1.496 Heat rejection to exhaust: kW 11.8
Governor: Mechanical Heat rejection to coolant: kW 15.2(JW)
Engine speed: RPM 1800 Heat rejection to ambient: kW 4.3
Prime power at rated RPM: kW 14.7
Maximum power at rated RPM: kW 16.2 Combustion Air
Speed regulation: % ±0.75 Air flow: L/s 20.5
BMEP: bar 7.22 Maximum intake restriction: kPa 6.4
Piston speed: m/s 5.4 Air filter: Dry element type
Fuel System
Fuel pump flow rate: L/hr 63
Pump lifting height: m 0.8
Engines
Alternator
Technical Data Technical Data
Manufacturer: Leroy Somer Efficiency at 0.8PF at 100%: % 87.1
Alternator model: TAL-A40-G Efficiency at 0.8PF at 75%: % 88.2
Rated voltage: V 230 Direct-axis transient reactance saturated, X'd: % 19.1
o
Prime rating @ 40 C: kVA 17 Direct-axis sub-transient reactance saturated, X"d: % 9.5
Standby rating @ 27oC: kVA 19 Short circuit ratio, Kcc: 0.45
Insulation class: H Excitation system: SHUNT
Winding pitch: 2/3 AVR model: R120
Number of wires: 12 Voltage regulation: % ±1
Protection: IP23 Short circuit current: kA 0.8
Altitude without derating: m ≤1000 Total harmonic distortion, THD at full linear load: % <5
Overspeed capability: RPM 2250 Waveform NEMA = TIF: <50
Air flow: m3 /s 0.1 Waveform IEC = THF: % <2
LRP16.5XS
Engines
Control System
Technical data
Model Protection
LR2060 Mechanical
Overspeed
Type High coolant temperature
Remote start Low oil pressure
Start up failure lock out
Manual mode Emergency Stop
Available local Electrical
Over and under frequency
Electrical measurement Over and under voltage
Voltage (P-P, P-N) Overload
Current Overcurrent
Frequency Power factor
Current unbalance
Power factor
Communication
Energy Meter USB (Programming)
kW
kWh Control
kVA Auto/Manual
Start/stop button
Mechanical measurement Alarm/fault acknowledge
Water temperature Menu button
Oil Pressure Display navigation buttons
Engine speed
Running hours Event log and memory
Number of start Up to 350 events
Battery voltage
Analogue input
Digital input/output 3
6/6
Options are shown in picture for reference only
Engines
Options:
Jacket water heater Spring type AV mounts Bearing temperature sensor
Low coolant level switch Acoustic enclosure Digital AVR upgrade
Electronic tank content gauge Anti-condensation heater
Battery float charger Winding thermistor
50°C radiator Winding temperature sensor
WARRANTY
®
LionRock Power provides one-source responsibility for the generator set and accessories.
Engine and alternator are guaranteed for a period of 12 months from the date of commissioning or 18 months from shipping (whichever comes
earlier).
After sales support for warranty service, backed by engine/alternator global service network in addition to local dealer. Refer to the warranty
documentation for details.
LRP16.5XS
Soundproof Canopy
L w Easy Transportable
Lifting points on both side of baseframe
Sound Pressure Levels
Anchor and drag points at baseframe ends
100% Load 60Hz
Prime: dBA@7m 70
* Measurement and calculation as per ISO 8528-10:1998
Unit 904, 9/F., Fu Hang Industrial Building, 1 Hok Yuen Street East,
Hung Hom, Kowloon, Hong Kong.
Tel: +852 2766 9787 Fax: +852 2766 9774
3Tech Corporate Limited www.3tech.net eMail: info@3tech.net For more complete information on 3Tech products, dealer services, and power solutions,
visit our website: www.3Tech.net
PM - GM - LRP16.5XS/60Hz/4PP/20201210
This document is not contractual - The 3Tech company reserves the right to modify any of the characteristics stated in this document without notice, in a constant effort to improve the quality of its products.