ATT.1 - Telecom Loads Under UPS & Generator Supply

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Electrical Load and Heat Dissipation for ELV Equipment

General Information
Date 16/7/2020
Project Name/ No: QP- New Laboratory
Prepared by : Eng.Islam Kamel
Checked By : Eng. Ahmed Hegy

UPS / Emergency
Switches Load Heat Dissipation
No. System Equipment Power (W) No. of units Total (W) Feed Ref Drawing Ref Room
(W) (BTU/hr)
(Yes/No)

LAB Building
1 Structure Cabling System Data Rack ‐ Passive Components 200 2 400 Yes 4154‐25‐16‐11‐560‐001 TER Room (B1‐GF‐39)

2 Structure Cabling System Data Rack ‐ Ac ve Components 10000 10000 2 20000 Yes 4154‐25‐16‐11‐560‐001 TER Room (B1‐GF‐39)

3 Structure Cabling System Data Rack ‐ Ac ve Components 200 2 400 Yes 4154‐25‐16‐11‐560‐001 TER Room (B1‐GF‐39)

4 CCTV System CCTV Rack 4000 4000 1 4000 Yes Control Room ((B1‐GF‐40)

5 CCTV System Server & NVR 3000 1 3000 Yes Control Room ((B1‐GF‐40)

6 CCTV System Workstation + Screen 1000 1 1000 Yes 4154‐25‐16‐11‐351‐001 Control Room (B1‐GF‐40)

7 CCTV System PTZ CAMERA 50 4 200 YES 4154‐25‐16‐11‐355

8 CCTV System LED Screen 300 3 900 Yes 4154‐25‐16‐11‐351‐001 Control Room (B1‐GF‐40)

9 Access Control System ACP 200 1 200 No 4154‐25‐16‐11‐451‐001 TER Room (B1‐GF‐39)

10 Access Control System Dual Reader interface Module 200 14 2800 No 4154‐25‐16‐11‐451‐001 _

11 Access Control System Door Controller 200 5 1000 No 4154‐25‐16‐11‐451‐001 _

12 Public Address System PA\GA Rack 1000 1 1000 Yes 4154‐25‐16‐11‐560‐001 TER Room (B1‐GF‐39)

4154‐25‐16‐11‐560‐001,
13 BMS DDC 300 9 2700 No _
4154‐25‐16‐11‐561‐001

14 Audio Video System Audio Visual Rack 1000 2 2000 No 4154‐25‐16‐11‐560‐001 B1‐GF‐41 & B1‐GF‐42

15 FA System FACP 1000 2 2000 Yes 4154‐25‐15‐66‐001‐001 Reception (B1‐GF‐03)

16 FA System HSSD Panel 300 10 3000 Yes 4154‐25‐15‐66‐001‐001

Telecom Normal Loads (KW) = 44.6

Telecom Normal Loads (KW) @ 25% Design Margin = 55.8


Telecom loads under
Telecom UPS Loads (KW) 35.9
UPS also supplied under Generator

Security Gate Building

1 FA System Repeater panel 300 1 300 No

2 Access Control System Dual Reader interface Module 200 2 400 Yes

Telecom Normal Loads (KW) = 0.7

Telecom Normal Loads (KW) @ 25% Design Margin = 0.9

Telecom loads under


Telecom UPS Loads (KW) = 0.4
UPS also supplied under Generator

LAB Substation Building

1 BMS DDC 300 2 600 Yes

2 FA System FACP 1000 1 1000 Yes

3 FA System HSSD Panel 300 3 900 Yes

Telecom Normal Loads (KW) = 2.5

Telecom Normal Loads (KW) @ 25% Design Margin = 3.1

Telecom loads under


Telecom UPS Loads (KW) = Self-contained battery back-up
2.5