Professional Documents
Culture Documents
CRS 4154 0 TQ 0004
CRS 4154 0 TQ 0004
DOCUMENT NUMBER, REV & TITLE: 4154-0-TQ-0004, REV. 2, TECHNICAL QUERY #4 - GENERATOR LOAD LAST REVISION STATUS: 2
1.4 The emergency switchboard to feed all the essential loads and UPS.
Kindly note that as per discussion with Lab. Specialist and QP Mechanical Engr.,
Why HVAC loads are considered on Generator as Kahramaa supply is HVAC loads considered remains conceptually the same to be connected to
2.1 very reliable. There is no Generator supply in existing chemical Generator except for all chillers which will be connected under "non-essential
laboratory. loads". Refer to Rev. S2 Key Single-Line Diagram, drawing no. 4154-25-16-32-
001 for details.
Kindly note that as per Shell DEP, it requires to provide power supply with
1. The power supply from kahramaa is highly reliable. Consultant is
provision for redundancy (ie. N+1) as well as back-up for UPS loads and standby
well aware of the redundancy they are considering in their design.
generator is mandatory when critical loads require power for extended time
QP do not have record of any such power failures in MIC/Refinery.
period. Refer to attachment 2 for details.
2 What is the impact of power failure? whether impact can be Kindly note that as per discussion with Lab. Specialist and QP Mechanical Engr.,
mitigated by any emergency repose plan such as evacuating from the HVAC loads considered remains conceptually the same to be connected to
laboratory or by connecting the exhaust fans to Emergency Generator except for all chillers which will be connected under "non-essential
generator, instead of connecting HVAC load to the emergency loads". Refer to Rev. S2 Key Single-Line Diagram, drawing no. 4154-25-16-32-
generator 001 for details.
Kindly note that according to the power capacity required for Admin zone
HVAC, it was only foreseen with 2-Nos. 5.06kW rated AHUs (eg. 25‐04‐HAH‐A,
Duty & 25‐04‐HAH‐B, Standby) under MCC-2 Panel. Therefore it was considered
to connect the same along with MCC Panel supplying Lab HVAC as it is
impractical to make a separate MCC Panel just to supply the two (2) Admin zone
3. Clarify if lab zone HVAC only is proposed to connect or Both Lab & AHUs. Moreover, in reference to Electrical Utility Data, Rev. S2 with the
Admin zone HVAC included? document no. 4154-25-16-30-111-S2, it can be noted that the Admin HVAC load
is only less than 1% compared to the total loads foreseen connected to the
generator, and with that small percentage of power contribution to emergency
load, it doesn't affect the total power requirement to size an indicative
generator rating. Furthermore, all the sizing and emergency load rating shall be
verified and updated in the detailed design stage.