TAN DELTA TEST REPORT

SITE: IOC PHDPL DURGAPUR


DATE OF TESTING: 24/04/2024

TRANSFORMER NAME PLATE DETAILS

MAKE: KIRLOSKAR; RATING: 6/8 MVA; HV RATED VOLTAGE: 33 KV;


LV RATED VOLTAGE: 6.6 KV; HV RATED CURRENT: 105/140 A;
LV RATED CURRENT: 502/669.4 A; VECTOR GROUP: Dyn11; SL NO: UG051/02

1. (HV- 33KV WINDING) TO (LV- 6.6KV WINDING)


UST MODE:
Applied Volt mA Power Loss(mW) Capacitance % D.F
(KV) (nF)
2 3.409 23.63 5.3442 0.341
5 8.465 145.2 5.3443 0.340
10 16.77 527.7 5.3433 0.316

2. (HV- 33KV WINDING) TO (LV- 6.6KV WINDING)


GST-G MODE:
Applied Volt mA Power Loss(mW) Capacitance % D.F
(KV) (nF)
2 1.165 33.35 1.8273 1.416
5 2.912 310.0 1.8428 2.126
10 6.008 2567.0 1.9019 4.271

3. (HV- 33KV WINDING) TO (LV- 6.6KV WINDING)


GST-BG MODE:
Applied Volt mA Power Loss(mW) Capacitance % D.F
(KV) (nF)
2 4.522 55.72 7.1709 0.615
5 11.33 454.2 7.1864 0.800
10 22.73 3082.0 7.2446 1.357

Tested By Witnessed By Witnessed By

Date Date Date


4. (LV- 6.6KV WINDING) TO (HV- 33KV WINDING)
UST MODE:
Applied Volt mA Power Loss(mW) Capacitance % D.F
(KV) (nF)
2 3.383 23.21 5.3446 0.341
5 8.419 143.0 5.3446 0.339

5. (LV- 6.6KV WINDING) TO (HV- 33KV WINDING)


GST-G MODE:
Applied Volt mA Power Loss(mW) Capacitance % D.F
(KV) (nF)
2 3.143 32.84 4.9310 0.516
5 7.757 200.0 4.9311 0.515

6. (LV- 6.6KV WINDING) TO (HV- 33KV WINDING)


GST-BG MODE:
Applied Volt mA Power Loss(mW) Capacitance % D.F
(KV) (nF)
2 6.455 54.63 10.276 0.423
5 16.25 345.6 10.276 0.422

Tested By Witnessed By Witnessed By

Date Date Date