ELECTRICAL SPECIFICATIONS: OFFICE OF THE BUILDING OFFICIALS
1. ELECTRIC SERVICE SHALL BE OVERHEAD 220V., 1-PHASE, 2WIRE, 60 CYCLE PER SECOND. C.O. ----- CONVENIENCE OUTLET ----- PANEL BOARD
9. ALL WORKS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF PHILIPPINE ----- CIRCUIT BREAKER ----- CIRCUIT HOMERUN ELECTRICAL
ELECTRICAL CODE, RULES AND REGULATION OF THE LOCAL ENFORCING ELECTRIC UTILITY
COMPANY. ----- SERVICE ENTRANCE ----- FIRE EXTINGUISHER
SD SD SD
1
8
2ND FLOOR
IMPEDANCE DIAGRAM VOLTAGE DROP CALCULATION SHORT CIRCUIT CALCULATION
7
c
SD SD SD Voltage Drop ( VD ) = l ( sqrt ( R sq + Xl sq )
EXISTING TRANSFORMER , 100KVA / 230V ,1PHASE , % Z=1.6%
SD Where l = Line current
FIRST FLOOR Zs = .001 Compute value for feeder line
C4 R = line AC Resistance , Ohms
X = Line reactance @ 60Hz , Ohms SHORT CIRCUIT CURRENT CALCULATION ( PER UNIT METHOD )
SMOKE DETECTOR SINGLE LINE DIAGRAM 100M VA
SYSTEM DIAGRAM :
For 1- Set of 2 x 22.0 mm sq. ( Steel Conduit ) L=30M
from PEC Table 9.1.1.9
S Zt = .016 E 100 MVA
SMOKE DETECTOR TECH. SPECIFICATION TRANSFORMER Xl = 0.06 R= .31
DC12V (NETWORK TYPE) 100KVA ,230V ,1.04% TRANSFORMER Z=sqrt (.06 x .06 + .31 x .31 ) X 30 / ( 305 )= .031
OPERATING VOLTAGE
9BV BATT.(INDEPENDENCE OR WIRELESS TYPE)
100KVA ,230V ,1.57%
Convert cable impedance from ohm to "pu"
STATIC CURRENT <200uA Zw1 = .059 22 mm² ( L=30m) pu Z = ohm impedance x KVA base / (KVsquare x 1000)
S ALARM CURRENT <20mA
ALARM INDICATION: 22.0 mm² ( L=30m)
= .031 x 100 / ( .230 x .230 x 1000 ) = .059
RED LED FLASH
b
SOUND LEVEL >85dB/m (INDEPENDENCE OR WIRELESS TYPE) "a" MCB
X @ fault " a "
OPERATING TEMPERATURE 10 C~+50 C
OPERATING HUMIDITY <95% RH MCB
SIMPLIFIED DIAGRAM % VD= 1.15% SINGLE LINE DIAGRAM
DETECTING AREA 20 Sq.m
SOUND & FLASH MANN (INDEPENDENCE TYPE)
RF SIGNAL 315 MHz/433MHz (WIRELESS TYPE) 100 MVA
C8 S
ALARM OUTPUT
RELAY OUTPUT NO/NC (NETWORK TYPE) @ MCB X "a"
S
RADIO DISTANCE 100m(OPEN AREA WIRELESS TYPE) Z = .076 TRANSFORMER
1.0
SIZE 100 mm dia. x 35mm DEEP 100 KVA ,230V ,1.57%
S2(b,c) Length - 30 mtrs. Size of wire - 2 x 22 mm sq. ( Steel Conduit )
S EXECUTE CRITERION GB4715-1993
RA Total Current = 42.66Amps.
22mm² ( L=30m)
from PEC Table 9.1.1.9 UTILITY SHORT CIRCUIT AVAILABLE , 100MVA
GUTTER
S2 X USE : 100KVA BASE
C6 Xl = .06
MCB
R = .31
ROOF
E base Va
AC lsc = x Vd = 42.66( sqrt ( .06 x .06 + .31 x .31) ) x 30 x 2 / ( 305 m ) = 2.65Volts Compute PU value of Utility source ( pu Zs )
Z base V
SD % Vd = 2.65x 100 / 230V = 1.15 % Pu Zs =KVA base / Utility SC KVA=100/100,000=.001 pu
C3 lsc =
1.0 x 100,000
= 5720 AMPS. Compute PU for Transformer , ( pu Zt )
X "a"
REF .076 230 V
Pu Zt= Impedance in percent / 100=1.6/100=.016 pu
C7 GUTTER
Use : 10 Kaic Circiut Breaker
S3W S3W SERVICE ENTRANCE
2-22.0mm² THW CU.WIRE+ 1-5.5mm²THW
CU. WIRE(ground) IN 32mm Ø UPVC CONDUIT
h
PB ROOF KILOWATT HOUR
METER
S
d
d
S
2-22.0mm²+ 1-5.5mm² THW CU. WIRE (ground)
S3W
C5 C2
S(a)
SD
S2 SD 100 AT
C1 MAIN CB
S
S2 SD g
S(g)
S S
S S3W
C1 C2
15 AT 15 AT
a
S C3 C4
S
20 AT 20 AT
S
C5 C6
20 AT 30 AT
S3
2
6
S(d) SD
S2(e,f)
C7 C8
20 AT 30 AT
RIGHT OF WAY e
(3.00M WIDE)
f
ROOF LINE
e C9 C10
SPARE SPARE
5
3
4
GROUNDING