Download as pdf or txt
Download as pdf or txt
You are on page 1of 19

QUOTATION

ITEM (A): DIESEL DRIVEN FIRE PUMP

PUMP: Qty: 2
Flow : 1500 GPM
Head : 130 PSI
Type : Vertical Turbine
Manufacturer : Waterfall Pumps
Model : WF-14S4 VT
No. of Stage : 4
Speed : 1750 RPM
Listing : UL-Listed
Construction : Ductile Iron, Stainless Steel Impeller
Accessories : Filled Gauges, Air Release Valve&Vacuum Breaker,
Diesel Fuel Tank, Batteries with cables,
Flow Meter, Flame Arrestor, PRV,
Waste Cone, Low Level Float Switch (L.L.F.S)

DRIVER:
Type : Diesel Engine
Manufacturer : Kirloskar
Model : KFP6R-UF25
Speed : 2600 RPM
Rating : 225 HP
Listing : UL Listed & FM Approved
GEAR DRIVE:
Type : Angle Gear Drive
Manufacturer : Amarillo
Model : S200 A
Ratio : 3:2
Approval : FM Approved

CONTROLLER:
Type : GPD Controller
Manufacturer : Tornatech
Listing : UL-Listed & FM Approved
Supply : 220V/1ph/60Hz
Enclosure : NEMA 2

Phone: +971 4 26 333 25


Website: www.wfpumps.com | Email: info@wfpumps.com
Location: Dubai, UAE | P.O Box 446054
QUOTATION

ITEM (B): ELECTRIC DRIVEN JOCKEY PUMP

PUMP: Qty: 1
Flow : 20 GPM
Head : 145 PSI
Type : Submersible Jockey Pump
Model : 4RP3-22
Speed : 3500 RPM
Construction : Stainless Steel/Cast Iron
Accessories : Filled Gauge

DRIVER:
Type : Jockey Pump
Speed : 3500 RPM
Rating : 3 HP
Supply : 220V/3ph/60Hz
Enclosure : IP 68

CONTROLLER:
Type : JP3 Controller
Manufacturer : Tornatech
Listing : UL- Listed
Supply : 220V/3ph/60Hz
Enclosure : NEMA 2

Phone: +971 4 26 333 25


Website: www.wfpumps.com | Email: info@wfpumps.com
Location: Dubai, UAE | P.O Box 446054
Performance Curve WF-14S4 VT

100 140 1000


WF-14S4 VT
1500 GPM
Max. 140% at Shut-off 130.5 psi (91.8 m)
90 1750 RPM (4-Stage) 900
120

80 800

100
70 Rated 700
TOTAL HEAD (meters of head)

60 600
80

NPSH (m)
150% Rated
ɳ(%)

BHP
50 500

60
40 Min. 65% at 150% Rated 400

30 300
40

20 200

20
10 100

0 0 0
0 500 1000 1500 2000 2500
FLOW (GPM)
A B C D E F G H
ENGINE GEAR DRIVE NO. OF STAGES A B C D E F G H 150A 3 1353 1100 760 892.1 435 292.1 2728.3 1878.3
200A 3 1353 1100 760 949.3 435 349.3 2614.1 1935.3
KFP4R-UF15 150A 3 1353 1000 760 892.1 425 292.1 2139.3 1839.1
200A 4 1645 1100 760 949.3 435 349.3 2614.1 1935.3
250 4 1645 1300 900 949.3 500 349.3 2817.7 2091.3
200A 5 1937 1100 760 949.3 435 349.3 2614.1 1935.3
8 KFP6S-UF35 250/300 5 1937 1300 900 949.3 500 349.3 2817.7 2091.3 KFP6R-UF25 8
H200 4 1645 1100 760 936.5 435 336.5 2613.7 1938.5
250/300 6 2229 1300 900 949.3 500 349.3 2817.7 2091.3
3 1353 1100 760 949.3 435 349.3 2655.4 1935.3
250
4 1645 1100 760 949.3 435 349.3 2655.4 1935.3
H250 4 1645 1100 760 981 435 381 2702.6 1983

7 SIDE VIEW FRONT VIEW 7


G+15
-15

475

TOP VIEW
6 6
H+15
-15

500+2.5
-2.5
F
E+5

Ø200MM DISCHARGE
-5

Ø340MM O.D. FLANGE


12-Ø22 BOLTS 100
5 5

330
PN 16 STANDARD
D+10
-10

575+2.5
-2.5

Slab Thickness
190.5+2.5
-2.5

GROUTING 500+2.5
-2.5
F.F.L (25mm THICK)

Ø420 Ø420
4 4

X
C+10 B+10
-10
-10

3 Notes: 3
1. Column pipe(s) length, X vary as per the tank depth and
slab thickness.

Tank Depth
2. Minimum submergence requirement of pump model is

A+10
-10
1440 mm.
3. All dimensions are in mm unless otherwise specified.

WATERFALL
2 2
230

PUMPS
Ø281
MANUFACTURING
DRAWING TITLE:
305

B.O.T
G&A WF-14S4 VT PUMP WITH
DIESEL ENGINE KIRLOSKAR
PUMP MODEL: WF-14F4 VT, WF-14S4 VT SCALE:

1 For Preliminary Use. DRAWING No: M14S4VTGA-D-KRL NTS 1


Not For Construction Unless Engineering Drawings DRN BY: CHKD BY: APPD BY: DRN DATE: PAGE SIZE: REVISION No:
A4
Represent General Construction. M.J M.F M.I 04/03/2023 PAGE: R6
1 of 1
A B C D E F G H
www.wfpumps.com
KIRLOSKAR OIL ENGINES LIMITED
Engine Specification Basic Engine Model:
Kirloskar Oil Engines Limited KFP6R-UF25
Laxmanrao Kirloskar Road Khadki, Reference Number : ES - UF25 - 00
Pune - 411003 (India) Revision Date : 13.02.2014
Rev. Number : 01
Number of Cylinders……………………………….. 6
Aspiration…………………………………………….. Turbocharged, Aftercooled
Rotation *…………………………………………….. Counter - Clockwise
Engine Weight - lb (kg)…………………………. 1946 (883)
Compression ratio………………………………….. 17.6 : 1
3
Displacement - in. (L)………………………………. 395.4 (6.48)
Engine Type………………………………………….. 4 Stroke Cycle - Inline Construction
Bore & Stroke in. (mm)……………………………… 4.13 x 4.72 (105 x 120)
Installation Drawing………………………………….. 6H.2583.00.00
Wiring Diagram……………………………………… 4H.1364.22.0.00
Engine Series……………………………………….. R Series
* Ratation viewed from Flywheel end

ENGINE RATINGS BASELINES


Engines are rated at standard SAE conditions of 29.61 in. (7521 mm) Hg barometer and 77 0 F
(25 0 C) inlet air temperature [Approx 300 ft. (91.4 m) above sea level] by the testing laboratory
(As per SAE standard J1349).

A deduction of 3 percent from engine power rating at standard SAE conditions shall be made for
diesel engines for each 1000 ft. (305 m) altitude above 300 ft. (91.4 m).

A deduction of 1 percent from engine power corrected to standard SAE conditions shall be made
for diesel engines for every 10 0 F (5.6 0 C) above 77 0 F (25 0 C) ambient temperature.

Page 1 of 1
Engine Performance Curve Basic Engine Model :
Kirloskar Oil Engines Limited KFP6R-UF25
Laxmanrao Kirloskar Road Revision Date : 25.06.2009
Khadki, Pune - 411003 (India) Curve Number : EPC - UF25 - 00

Engine Family : R Series Engine Weight - Kg : 883


Displacement - In.3 (L) : 395.4 (6.48) Minimum Rating : 169 HP @ 1760 RPM
Compression Ratio : 17.6 : 1 Maximum Rating : 225 HP @ 2600 RPM
Number of Cylinders :6
Aspiration : Turbocharged,
Aftercooled
Fuel Pump : MOTORPAL

250
Engine Power Output
240
Engine Speed Power
RPM HP 230
1760 169 220 225
NGINE POWER (HP)

2100 191
210 203
2200 196
200
2350 203 191
196
2600 225 190
EN

180

170
169
160

150
1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700

ENGINE SPEED(RPM)

1 . Power Curves shown above represent gross engine performance capabilities obtained and corrected in
accordance with SAE J1349 conditions of 29.61 in Hg (100 kPa) barometric pressure [300 ft. (91.4 m)
altitude], 77 oF (25 oC) inlet air temperature with No. 2 diesel fuel

2 . The engine can be operated without changing the fuel setting up to 300 ft. (91.4 m) altitude and up to 77
o
F (25 oC) ambient temperature. To operate at high altitudes, the fuel rate of the engine should be
adjusted to limit performance by 3% per 1,000 ft. (305 m) above 300 ft. (91.4 m) altitude. To operate at
high ambient temperatures, the fuel rate of the engine should be adjusted to limit performance by 1%
per 10 oF above 77 oF (2% per 11 oC above 25 oC).

Page 1 of 1
Project:
Customer:
Engineer:
Pump Manufacturer:

Technical Data
Submittal Document
Model GPD
Diesel Engine Driven Fire Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are


for controllers covered under our standard
offering. Actual AS BUILT drawings may
differ from what is shown in this package.
November 2018
Project:
Customer:
Engineer:
Pump Manufacturer:

Technical Data
Submittal Document
Model JP3
Across the Line Start
Jockey Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are for controllers


covered under our standard offering. Actual AS BUILT
drawings may differ from what is shown in this package.
February 2019
model
33ATD
Sizes 2" - 3" - 4"
Air Release & Vacuum Breaker Valve
(Threaded & Flanged) with Throttling Air Control Device

• Automatically eliminates air pockets


• Easily serviced without removal from pipeline
• Simple, effective patented design
• Corrosion resistant internal parts
• Engineered for lasting service
• Sizes 2", 3" and 4" UL Listed
designed to protect pipelines from air lock and vacuum
collapse, the ClA-VAl model 33ATd Air Release and
Vacuum Breaker Valve eliminates air and prevents vacuum
formation in pipelines. A large venting orifice and large float
clearances freely exhaust or admits air during pipeline filling
or draining.

during normal pipeline operation, air accumulation and


buoyancy cause the floats to lower or lift. As the water level
lowers inside the valve, small amounts of accumulated air are
released through the small orifice. once air is released, the
patented float poppet system closes drip tight.
Valve servicing is simple because the entire float poppet
Flanged Inlet shown system, can be replaced without removal of the valve body
Threaded Inlet also available from the pipeline.

Installation Typical Applications


Series 33ATd is often installed upstream of check valves in • Standard Max. D.W.P. 300 psi for UL Listed assemblies
vertical pump discharges to throttle air out during start-up and (for Higher Operating Pressure Consult Factory)
to allow full air reentry when the pump stops. • Transmission pipeline high points
• Water treatment plant piping high points
Operation • Offshore platforms
Air Release Mode - Valve is normally open: • Vertical turbine pump discharge
When line is filled or pump started, air is throttled through the
air control device Td. As liquid fills the valve, float ball rises
to form a drip-tight closure and remaining air is exhausted
33A Flanged
High Performance

through small orifice. Air throttling can be adjusted by means


Combination Air Release
& Vacuum Breaker Valve

of adjusting the screw.


with a Series TD Throttling
Air Control Device

Vacuum Prevent Mode:


When line pressure drops below positive pressure and the
Shut-Off Valve

liquid level lowers, the float drops, unseating the valve and
Airline

allowing air into the line, thus preventing a vacuum. The


Gauge

spring loaded disc in the Td throttling air control device is


Meter Blow-Off

moved to the air intake position due to the negative pressure.


Main
581 Tee and
Gate
Check Valve Valve
Valve Sample
Cock

visit www.cla-val.com to learn


about our complete line of
fire protection products.
Well Casing

FLOW

Pump Column
Air Line

Note: Available for Sea Water Service (see material specifications


Dimensions (In Inches) MODEL 33ATD - 2", 3", and 4" Sizes
33A Pressure Class 300 Lb 33A Pressure Class 150 Lb 33A Pressure Class 300 Lb
Threaded Flanged (INLET) Flanged (INLET)
Valve Size 1"* 2" 3" 4" 2" 3" 4" 2" 3" 4"
A 11.81 16.50 18.50 20.00 17.75 21.75 23.50 18.00 22.00 23.75
B 4.13 7.50 9.25 9.25 7.50 9.25 9.25 7.50 9.25 9.25
Inlet (ANSI) 1" NPT 2" NPT 3" NPT 4" NPT 2" 3" 4" 2" 3" 4"
Outlet (NPT) 1" NPT 2" NPT 3" NPT 4" NPT 2" NPT 3" NPT 4" NPT 4" NPT 3" NPT 4" NPT
Number of Holes — — — — 4 4 8 8 8 8
Diameter of Bolts — — — — .625 .625 .625 0.75 0.75 0.75
Approximate calculated
25 29 38 40 39 48 50 41 55 58
shipping weight (lb.)
* 1" size is not Ul listed. Consult Factory for other available end options.

Pressure Ratings When Ordering,


Please Specify
B B

Throttling
Standard
Valve orifice Adjustment
maximum
Size dia.
Pressure 1. Catalog No.
1" .076" 300 psi 2. Valve Size
2" .076" 500 psi 3. Pressure Rating
3" & 4" .076" 300 psi 4. materials
6" .076" 300 psi
A
A

optional
3" & 4" upon request 300 psi
.125"
Note: maximum Pressure Rating for
Threaded Flanged
Ul listed 33ATd = 300 psi

Specifications
Standard Internals Materials of Construction
Float: Stainless Steel 304SS Standard,
T316 or monel optional (extra cost) • Nickel Aluminum Bronze (NAB) - ASTm B148 Alloy C95800
Balance internal parts Stainless Steel and delrin • monel - QQ-N-288 Comp B - ASTm A494 Grade m30H

Seals Nitrile Rubber or Viton® (extra cost) • Cast Steel - ASTm A216 Grade WCB
Note: Fluorocarbon is not a Ul listed Seal material • 316 Stainless Steel - ASTm A743 Grades CF3m and CFm8
Temperature Range: Water to 180° F • Super Austenitic Stainless Steel - ASTm A351 Grade
CK3mCuN (Smo 254)
Optional:
• Super duplex Stainless Steel - ASTm A890 Grade 5A
Fusion epoxy lined and coated (Ce3mN)
For well service throttling device on the outlet specify model Td

Valve Sizing Selection Air Release Capacity


Air-Vacuum Flow Capacity during pressurized pipeline operation, small pockets of entrapped
air will be released through the float actuated 0.076 or .125 inch
determine anticipated water flow and allowable pressure orifice. Use chart to determine discharge capacity.
differential for the pipeline application. Select valve from
chart to exhaust or admit air at the same rate as water filling
or draining (in CFS). For larger flows, two or more model
33ATd's may be installed in parallel

5
Pressure (psi)

1" 2" 3" 4"


4
Pressure (psi)

0
0 5 10 15 20 25 30 35 40 45

Flow Capacity in Cubic Feet Air/Sec. Air Flow Rate (scfm)

CLA-VAL ©
1701 Placentia Avenue • Costa Mesa CA 92627 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: info@cla-val.com • Website cla-val.com
Copyright Cla-Val 2020 Printed in USA Specifications subject to change without notice. e-33A Threaded & Flanged (R-11/2020)
MODELO
50B-4KG1KOL Globo
2050B-4KG1KOL Ángulo
Válvula de Alivio de Presión con Trim Anti Cavitación

• Para aplicaciones en plataformas marinas


e instalaciones en tierra
• El Asiento del Trim Anti Cavitación:
- Protege Contra Cavitación
Tamaños 3" a 8" - Reduce el Ruido y la Vibración
- Prolonga la Vida Útil de la Válvula
• Cumple con la norma NFPA 20
Las Válvulas de Alivio de Presión Cla-Val Modelo 50B-4KG1KOL Globo
y 2050B-4KG1KOL Angulo están diseñadas para aliviar los excesos de
LA
BLLED BY
presión en sistemas contra incendio, además de eliminar la posibilidad
ULC de daño interno por cavitación.
U N D E R W RIT

CANADA
OF

La válvula tiene las características de ajustar la presión de apertura a la


E

S E
LAB RI
O R AT O

Tamaños 3" a 8" requerida por el sistema, abrir rápidamente para mantener una presión
2050B-4KG1KOL (Ángulo) controlada y cerrar gradualmente para lograr una operación libre de
fenómenos transitorios (golpes de ariete).

Características y Beneficios del Asiento Anti Cavitación KOL


• Ideal para aplicaciones con altos diferenciales de presión
• Cumple con los flujos establecidos en las normas, requeridos por agencias de
aprobación
• Proporciona un ambiente de trabajo seguro, por prevenir daño en la válvula
• Asiento recubierto de teflón disponible en acero inoxidable tipo 316, monel y Acero
Inoxidable tipo Súper dúplex

Aplicaciones Tipicas
Válvula de Alivio para Plataformas Marinas Válvula de Alivio de Bomba
para Instalaciones en Tierra

WC-1 2050B-4KG1KOL
Waste Cone
Pressure Relief Valve with
Anti-Cavitation Trim

Main
33A High Performance Gate
Combination Air Release Valve
& Vacuum Breaker Valve

Shut-Off

System

Blow-Off
581
Check Valve Tee and
Valve

FLOW

Ver página 2 para lista de materiales


disponibles para aplicaciones
de agua de mar y servicios severos
Especificaciones Dimensiones
Tamaños Globo: 3” a 8” Bridadas; Angulo: 3” a 8” Bridadas
Aprobadas FM, UL y ULC listado B

150 y 300 ANSI


Conexiones
Presión: Clase 150: 175 psi Máximo; Clase 300:
Rangos de Trabajo 300 psi Máximo
G
Temperatura: Agua hasta 180 F Máximo
Rango de Ajuste Disponible en los siguientes rangos de presión de
alivio: 20-200 psi (clase 150)
100-300 psi (clase 300) Modelo 50B-4KG1KOL Globo Modelo 2050B-4KG1KOL Ángulo
Resina Epóxica para proteger superficies A H E
Recubrimiento húmedas de los componentes ferrosos de la
Opcional válvula principal. (Listada UL HNFX EX2855)

Materiales Estándares de la Válvula C


C
Cuerpo Principal y Tapa: Hierro Dúctil ASTM A 536
Internos de la Válvula Principal:
• Asiento de Acero Inoxidable recubierto de Teflón, Vástago de acero
Inoxidable
D F
Sistema de Pilotos de Control: Bronce Fundido con Internos
de acero Inoxidable
Materiales para Aplicaciones con Agua de Mar Recomendamos dejar espacio adecuado alrededor de la válvula para trabajo
de mantenimiento
y Servicios Severos
Tamaño (pulgadas) 3" 4" 6" 8" 10"
Materiales Listados Opcionales Extremos roscados 12.50 --- --- --- ---
• Bronce al Aluminio Níquel – ASTM B 148 Aleación C958000
A 150 Bridadas 12.00 15.00 20.00 25.38 29.75
• Monel - QQ-N-288 Comp B
• Acero Inoxidable 316 – ASTM A 743 GR CF8M 300 Bridadas 13.25 15.62 21.00 26.38 31.12
• Acero Inoxidable Súper Austenitico – UNS S31254 300 X 150 12.88 15.31 20.56 25.88 30.44
• Acero Inoxidable Súper Dúplex – UNS J93404 B 4.56 5.75 7.88 10.00 11.81
• Materiales de los Internos de la válvula y sistemas de pilotos de control
C 12.50 13.00 14.31 16.31 18.00
disponibles de acuerdo a la aplicación recomendada
D 2.66 3.19 4.31 5.31 9.25

Especificaciones de Compra Extremos roscados 6.25 --- --- --- ---


E 150 Bridadas 6.00 7.50 10.00 12.75 14.88
La Válvula de Alivio de Presión para Bomba Contra Incendio debe modu-
300 Bridadas 6.38 7.88 10.50 13.25 15.56
lar los excesos de presión, manteniendo constante la presión independi-
entemente de los cambios en la demanda del sistema. Debe estar contro- Extremos roscados 4.50 --- --- --- ---
lada por piloto y la presión de regreso no debe afectar su punto de ajuste. F 150 Bridadas 4.00 5.00 6.00 8.00 8.62
Debe ser actuada por la misma presión de la línea y abre de forma rápi- 300 Bridadas 4.38 5.31 6.50 8.50 9.31
da para mantener una presión constante en el sistema, cuando la deman- G&H 7.75 7.88 8.50 9.75 13.25
da en el sistema disminuye. Debe cerrar gradualmente para evitar gener-
ar golpes de ariete y cerrar herméticamente 5% debajo de la presión de Tamaño de Válvula (mm) 80 100 150 200 250
ajuste. Extremos roscados 318 --- --- --- ---
A 150 Bridadas 305 381 508 645 756
La válvula principal debe ser del tipo operada hidráulicamente, controlada
por piloto, tipo diafragma en globo o ángulo. Debe estar equipada con 300 Bridadas 337 397 533 670 790
asiento anti cavitación recubierto de teflón con un vástago ranurado guia- 300 X 150 327 389 522 657 773
do en dos puntos: inferior y superior y un disco resiliente con una sección
B 116 146 200 254 300
rectangular sujetado por 3 de sus partes. No se permiten válvulas con
empaques externos y el diafragma no debe ser usado como elemento de C 1318 330 363 414 457
sello. El piloto de Control debe ser una válvula del tipo diafragma, resorte, D 65 81 109 135 235
de acción directa, ajustable, diseñado para modular servicio que permita Extremos roscados 159 --- --- --- ---
el flujo cuando la presión del sistema excede el punto de ajuste en el
resorte. La válvula debe ser listada UL y aprobada Factory Mutual. Debe E 150 Bridadas 152 191 254 324 378
ser del Modelo 50B-4KG1KOL (globo) o Modelo 2050B-4KG1KOL (ángu- 300 Bridadas 162 200 267 337 395
lo) para Alivio de Presión como la fabricada por Cla-Val Newport Beach, Extremos roscados 114 --- --- --- ---
California.
F 150 Bridadas 102 127 152 203 219

*Nota Especial: 300 Bridadas 111 135 165 216 236


La Válvula Modelo 50B-4KG1KOL/2050B-4KG1KOL está disponible con G&H 197 200 216 248 337
brida de entrada clase ANSI 300 y brida de salida clase ANSI 150 para
sistemas de alta presión donde la clase 300 es requerida, para permitir la Capacidad de la Válvula
adaptación de un cono de descarga (generalmente suministrado con Tamaño de Válvula en Pulgadas 3" 4" 6" 8" 10"
brida clase 150) y de esta forma aliviar presión a la atmosfera. GPM Máximo, Recomendados
La válvula de alivio con bridas 300X150 está disponible bajo orden espe- 500 1000 2500 4000 11000
por NFPA 20
cial y Listada UL y aprobada FM.

Mexico/Central America Oficina


Av Empresarios No. 135, Piso 8 • Col. Puerta de Hierro 45116 Zapopan, Jalisco Ph: 52 (33) 80000579
Email: bmartinez@cla-val.com

PO Box 1325 • Newport Beach, CA 92659-0325 • Ph: 949-722-4800 • F: 949-548-5441 • info@cla-val.com • www.cla-val.com
© Copyright Cla-Val 2014 Printed in USA Specifications subject to change without notice. SE-50B-4KG1KOL (R-11/2014)
WC-1
Waste Cone
MODEL

• Available for Onshore and Offshore Applications


• Manufactured in Accordance with NFPA 20 Requirements
• Designed for use with UL/FM Approved Fire Pump
Pressure Relief Valves

Optional Materials for Seawater and Severe Service Applications:


• Nickel Aluminum Bronze (NAB) - ASTM B148 Alloy C95800
• Monel - QQ-N-288 Comp B - ASTM A494 Grade M30H
• Cast Steel - ASTM A216 Grade WCB
• 316 Stainless Steel - ASTM A743 Grades CF3M and CFM8
• Super Austenitic Stainless Steel - ASTM A351 Grade
CK3MCuN (SMO 254)
• Super Duplex Stainless Steel - ASTM A890 Grade 5A
(CE3MN)

Standards: Flanges
• Fusion Bonded Red Epoxy Coated • 150# Class (FF Standard)
• Ductile Iron - ASTM A536-65 • 300# Class (RF Standard)
• (2) 2’’ 316 SS Sight Glasses per WC-1 • Raised Face and Flat Faced Options
• Single Body Casting (No Welding)

Typical Application:
Fire Pump Relief

CLA-VAL ©
1701 Placentia Avenue • Costa Mesa CA 92627 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: info@cla-val.com • Website cla-val.com
Copyright Cla-Val 2019 Printed in USA Specifications subject to change without notice.
WC-1

Technical Data & Dimensions

ØE ØG
EQUALLY EQUALLY
SPACED SPACED

Ø A Ø AA ØCC ØC

INLET FLANGE BB OUTLET FLANGE

B
6" X 8" SIZE SHOWN

NUMBER DIAMETER NUMBER DIAMETER


SIZE PUMP PRESSURE WEIGHT
ØA ØAA B BB ØC ØCC ØE OF HOLES OF BOLTS ØG OF HOLES OF BOLTS
INLET X OUTLET GPM CLASS (IN LBS.)
(INLET) (INLET) (OUTLET) (OUTLET)

150LB – 7.50 – 8.25 – 10.00 .750 4 .625 .875 8 .750 34


3" X 5" 0 - 450
300LB 8.25 – 9.24 – 11.00 – .875 8 .750 .875 8 .750 53
150LB – 7.50 – 9.00 – 11.00 .750 4 .625 .875 8 .750 41
3" X 6" 450 - 500
300LB 8.25 – 9.69 – 12.50 – .875 8 .750 .875 12 .750 63
150LB – 9.00 – 9.00 – 11.00 .750 8 .625 .875 8 .750 43
4" X 6" 500 - 750
300LB 10.00 – 9.75 – 12.50 – .875 8 .750 .875 12 .750 70
150LB – 9.00 – 10.25 – 13.50 .750 8 .625 .875 8 .750 62
4" X 8" 750 - 1000
300LB 10.00 – 11.06 – 15.00 – .875 8 .750 1.000 12 .875 99
150LB – 11.00 – 10.25 – 13.50 .875 8 .750 .875 8 .750 67
6" X 8" 1000 - 1500
300LB 12.50 – 11.19 – 15.00 – .875 12 .750 1.000 12 .875 110
150LB – 11.00 – 11.50 – 16.00 .875 8 .750 1.000 12 .875 94
6" X 10" 1500 - 2500
300LB 12.50 – 12.63 – 17.50 – .875 12 .750 1.125 16 1.000 150
150LB – 13.50 – 13.00 – 19.00 .875 8 .750 1.000 12 .875 138
8" X 12" 2500 - 3500
300LB 15.00 – 14.25 – 20.50 – 1.000 12 .875 1.250 16 1.125 207
150LB – 13.50 – 14.00 – 21.00 .875 8 .750 1.125 12 1.000 173
8" X 14" 3500 - 5000
300LB 15.00 – 15.25 – 23.00 – 1.000 12 .875 1.250 20 1.125 255

Visit www.cla-val.com to learn


more about Cla-Val Fire
Protection Products

CLA-VAL
1701 Placentia Avenue • Costa Mesa CA 92627
800-942-6326 Fax: 949-548-5441 Web Site: cla-val.com E-mail: info@cla-val.com
CLA-VAL CANADA CLA-VAL EUROPE CLA-VAL UK CLA-VAL FRANCE CLA-VAL PACIFIC
4687 Christie Drive Chemin des Mésanges 1 Dainton House, Goods Station Road Porte du Grand Lyon 1 45 Kennaway Road
Beamsville, Ontario CH-1032 Romanel/ Tunbridge Wells ZAC du Champ du Périer Woolston, Christchurch, 8023
Canada L0R 1B4 Lausanne, Switzerland Kent TN1 2 DH England France - 01700 Neyron New Zealand
Phone: 905-563-4963 Phone: 41-21-643-15-55 Phone: 44-1892-514-400 Phone: 33-4-72-25-92-93 Phone: 64-39644860
E-mail sales@cla-val.ca E-mail: cla-val@cla-val.ch E-mail: info@cla-val.co.uk E-mail: cla-val@cla-val.fr www.cla-valpacific.com

E-WC-1 (R-03/2019)
E-mail: info@cla-valpacific.com
©COPYRIGHT CLA-VAL 2019 Printed in USA Specifications subject to change without notice.
GERAND ENGINEERING CO.
2300 EDGEWOOD AVE S, MINNEAPOLIS, MN 55426 952.374.1320 WWW.GERAND.COM

Fire Pump Test Meter Operating Instructions

BRASS VENT VALVES


METER
PLASTIC VENT HOSE

CONNECTING HOSE

VENTURI

VENTURI SHUT-OFF VALVE

Attached to the meter with a brass chain is an oblong metal tag with the suggested piping diagram of the
system on one side, and the following operating instructions on the reverse side:

1. Close system OSY valve “A”


2. Open by-pass valve and “B” butterfly throttle valve
3. Purge meter, located on venturi, as follows:
a) Open station shut-off valves on venturi, and vent valves attached to meter.
When a steady stream of water without air bubbles passes through the clear plastic hoses,
the meter is purged of air.
b) Close the vent valves after purging.
4. Start the fire pump, and read meter in GPM.
5. Refer to pump GPM requirement and adjust throttle valve to meet the requirement.
6.After the test, open valve “A” and close the by-pass and “B” valves.

*SPECIFY RAISED OR FLAT FACE


GERAND GPM METER - VENTURI PACKAGE
“B” - Butterfly Throttle Valve OSY or Indicating
Butterfly Bypass Valve Flow SUGGESTED
TO RESERVOIR Air Vent PIPING
OR WASTE
DIAGRAM

(2) (5)
Optional to
Pump Inlet Min. Straight Pipe Diameters same line size as Venturi

OSY Valve “A” OSY Valve


Flow
Supply from
City Main or
Reservoir To System
FIRE PUMP

You might also like