Proposed Bungalow Revised
Proposed Bungalow Revised
MUNICIPALITY OF CABUYAO
1 TABLE OF CONTENTS PROVINCE OF LAGUNA
A1 4 PERSPECTIVE OFFICE OF THE BUILDING OFFICIAL
SITE DEVELOPMENT PLAN
01 09
VICINITY MAP
LAND USE & ZONING
FLOOR PLAN
2 ROOF PLAN
A2 4
ELEVATIONS
ARCHITECTURAL
PROJECT SITE
BARANGAY MAMATID, CABUYAO, LAGUNA
02 09 CROSS SECTION
LONGITUDINAL ELEVATION
REFLECTED CEILING PLAN
SCHEDULE OF CEILING FINISHES
3
A3 4 GROUND FLOOR FINISHED
LAYOUT
03 09 CEILING DETAILS LINE & GRADE
SCHEDULE OF DOORS AND
WINDOWS
4
A4 4 PERIMETER FENCE LAYOUT
PERIMETER FENCE DETAILS
04 09
1 ARCHITECTURAL
S1 3 STRUCTURAL NOTES
05 09
PERSPECTIVE VICINITY MAP
NOT DRAWN TO SCALE NOT DRAWN TO SCALE
S T R U C T U R A L
FOUNDATION PLAN
2 TIE BEAM FRAMING PLAN
S2 3 ROOF BEAM FRAMING PLAN
ROOF FRAMING PLAN
06 09
TYPICAL COLUMN-FOOTING
DETAILS STRUCTURAL
3389
3389
2706
3 FOUNDATION PLAN
S3 3 TIE BEAM FRAMING PLAN
ROOF BEAM FRAMING PLAN
67730
07 09
ROOF FRAMING PLAN
W
6288
ALO
D B UNG ING
E D
POS BUIL
PRO ENTIAL
PLUMBING ELECTRICAL
I D
RES LIGHTING LAYOUT
1 POWER LAYOUT
12576
E1 1 GENERAL NOTES PLUMBING
21840
LEGENDS/SYMBOLS
08 09
SINGLE LINE DIAGRAM
6288
SERVICE DROP INSTALLATION
11696
WATERLINE LAYOUT
1 SEWERLINE LAYOUT
P O
PAR
SED S
KIN G
P1 4 DRAINAGE LAYOUT
PRO SPACE GENERAL NOTES
09 09
LEGENDS/SYMBOLS
W AY TYPICAL PLUMBING DESIGN
RIVE
O S ED D ELECTRICAL
P
PRO 7.00m
2900
2910
249
40
58190
MECHANICAL
85
SCALE 1:150 M
94
24
x'
1000
1000
F
KS KS TOP OF CEILING (OFFICE)+3.50M TOP OF CEILING (OFFICE)+3.50M
DIRTY MASTER'S
KITCHEN/ DINING TOP OF CEILING (HOUSE)+2.90M
2575
TOP OF CEILING (HOUSE)+2.90M
3076 ROOM ROOM
LAUNDRY
AREA KITCHEN
E
1350
T&B OFFICE/STORE FIN. FLR LINE+0.80M OFFICE/STORE FIN. FLR LINE+0.80M
2575
1:100 M
SHELVES SCALE SCALE 1:100 M
12822
BEDROOM
B C D E F F E D C B A
B
CASHIER
A 19 mm DROP
APEX OF ROOF +5.63M APEX OF ROOF +6.00M
PATIO CARPORT
3403
5322
TOP OF CEILING (OFFICE)+3.50M TOP OF CEILING (OFFICE)+3.50M
x
TOP OF CEILING (HOUSE)+2.90M TOP OF CEILING (HOUSE)+2.90M
5621 6973 F
F
1 2 3 4
12594
6195 6895
y 1 2 3 4 A B C D E F
F
APEX OF ROOF +5.63M APEX OF ROOF +5.63M
GA#24, SS 304 GUTTER,
SATIN FINISH
SEE TRUSS DETAILS
GA#24, PRE-PAINTED
SEE TRUSS DETAILS
HI-RIB LONG SPAN, G.I ROOFING
OFFICE/STORE FIN. FLR LINE+0.80M OFFICE/STORE OFFICE/STORE FIN. FLR LINE+0.80M OFFICE/STORE
GA#24, PRE-PAINTED,
PLAIN G.I FLASHING
CROSS SECTION LONGITUDINAL ELEVATION
A SCALE 1:100 M SCALE 1:100 M
6195 6896
12594
ROOF PLAN
SCALE 1:100 M
PROPOSED CONSTRUCTION OF BUNGALOW RESIDENTIAL BUILDING WITH PARKING SPACE FLOOR PLAN 2
CRIS EMANUELLE H. CASTOR
ROOF PLAN A2 4
ELEVATIONS 02 09
PROJECT LOCATION EVELYN L. ANTIOQUIA CROSS SECTION
PRC NO. : 0168420 12/07/26
PTR NO. : BTG 33336550 01/18/24 BARANGAY MAMATID, CABUYAO, LAGUNA LONGITUDINAL ELEVATION
ARCHITECTURAL
TIN NO. : 478-509-028-000 09/16/20
y 1 2 3 4 y' WALL ANGLE
1000
1000
400mm THK. CEILING WITH GYPSUM BOARD PAINTED WITH FLAT LATEX PAINT
FLAT CEILING (THICKNESS VARIES ON BEAM HEIGHT)
CF - 1
F CF - 2
FLAT CEILING
(T & B)
400mm THK. CEILING WITH HARDIFLEX PAINTED WITH FLAT LATEX PAINT
(THICKNESS VARIES ON BEAM HEIGHT) METAL DOUBLE FURRING CHANNEL
12mm. x 38mm. x 5m x 0.8mm. thk.
DIRTY MASTER'S
KITCHEN/ KITCHEN DINING
2575
ROOM
3076
CF - 1
LAUNDRY ROOM CF - 1
CF - 1
AREA METAL CARRYING CHANNEL 12mm x 38mm x 5m x
CF - 1
E 0.8mm thk.
METAL CARRYING CHANNEL
12mm x 38mm x 5m x 0.8mm thk.
D CEILING DETAILS
1350
T&B
CF - 2
T&B 4.5mm thk. FIBER CEMENT BOARD (HARDIFLEX) SCALE NTS
CF - 1
C
CASHIER
LIVING
ROOM
11695
2575
50 50 50 50
12822
CF - 1
600 X 600 mm UNPOLISHED SYNTHETIC REINFORCED CONCRETE
GRANITE TILE FLOOR FINISH STAIR (ON-FILL)
OFFICE/STORE 300
CF - 1 600 X 600 mm UNPOLISHED SYNTHETIC
4
B PORCH FLOOR LEVEL GRANITE TILE FLOOR FINISH 50
200
PLAIN CEMENT FLOOR FINISH 6 mm THK. NON-SKID METAL NOSING STRIP
A (PROVIDE FLOOR HARDENER) (SUBMIT SAMPLE)
200
2
600
200
PATIO REINFORCED CONCRETE STAIR
200
1
CARPORT
3403
TOP OF SIDEWALK
5322
100
NATURAL GRADE LINE
SPOT DETAILS (PATIO)
x SCALE 1:16M
5621 6973
12594 4000
900 900
F
500
F F
200
200 200
JAMB
JAMB
2600
750
2200
F F
2100
2100
2100
JAMB
750
y 1 2 3 4 y'
300
JAMB
200
12594 300
2425 3196 3395 2575 1000 FINISH FLOOR LINE
R.C. POST W/ ALUMINUM METAL DW-1 D-1 D-2 D-3
SCHEDULE OF FLOOR FINISHES CLADDING (COLOR: ROYAL BLUE)
x' 600 X 600 mm UNPOLISHED SYNTHETIC GRANITE TILE FLOOR FINISH SEE MANUFACTURER'S SPECS 6.35mm. THK. TEMPERED CLEAR GLASS w/ ETCHED 45mm. THK. PANEL DOOR SINGLE LEAF BEDROOM DOOR
FL-1 PVC SWING DOOR W/
1000
1000
ROOM FL-4 FOR APPROVAL BY END-USER) PROVIDE WATER BASE WATERPROOFING 1 - SET
FL - 1
3076
LAUNDRY ROOM FL - 3
AREA FL - 1 1 - SET
FL - 2
E
D
1350
T&B
FL - 4
T&B
FL - 4
C
CASHIER
LIVING
ROOM (DIVIDE INTO 2 EQUAL PARTS)
11695
FL - 1
2700 1200 600
BEDROOM
4216
2575
12822
FL - 3
600
OFFICE/STORE
FL - 1
800
F
1050
B
1100
F
1200
1350
A
200
2200
2150
200
1600
PATIO
FL - 2
1100
CARPORT
900
800
3403
RC COUNTER TOP w/
5322
PROPOSED CONSTRUCTION OF BUNGALOW RESIDENTIAL BUILDING WITH PARKING SPACE REFLECTED CEILING PLAN 3
SCHEDULE OF CEILING FINISHES A3 4
CRIS EMANUELLE H. CASTOR
PROJECT LOCATION
GROUND FLOOR FINISHED LAYOUT 03 09
EVELYN L. ANTIOQUIA CEILING DETAILS
PRC NO. : 0168420 12/07/26
PTR NO. : BTG 33336550 01/18/24 BARANGAY MAMATID, CABUYAO, LAGUNA SCHEDULE OF DOORS AND WINDOWS ARCHITECTURAL
TIN NO. : 478-509-028-000 09/16/20
3389
3389
2706
67730
OW
6288
UN GAL G
ED B DIN
R O POS IAL BUIL
P T
DEN
RESI
12576
21840
6288
11696
G
RKIN
S E D PA
PO
PRO SPACES
W AY
D DRIVE
E
POS 00m
PRO 7.
2900
2910
249
40
58190
857
SCALE 1:150 M
50X50mm STEEL TUBULAR GRILLS 50X50mm STEEL TUBULAR SLIDING GATE 50X50mm STEEL TUBULAR GRILLS
W/ PAINTED FINISH (COLOR: BLACK) W/ PAINTED FINISH (COLOR: BLACK) W/ PAINTED FINISH (COLOR: BLACK)
94
9190 12594
24
TIES
10mmØ RS BARS
1500
4@50mm
2@100mm
SIDEWALK FINISH FLOOR LINE
REST 200mm O.C.
PERIMETER FENCE
DETAILS FRONT ELEVATION)
VERT. BARS SCALE 1:60M
VARIES
1500
SIDEWALK FINISH FLOOR LINE
PERIMETER FENCE
SECTION
DETAILS (HOUSE)
600 SCALE 1:60M
450 REINFORCEMENTS
5-12mmØ RS BARS FENCE POST FENCE WALL
200
SPACED@104mm CONCRETE CONCRETE HOLLOW BLOCKS
SMOOTH FINISH PAINTED MASONRY ROUGH PLASTER FINISH
BOTHWAYS
VARIES
104
450
200
600
1800
SIDEWALK FINISH FLOOR LINE
PERIMETER FENCE
DETAILS (PARKING)
PLAN SCALE 1:60M
60
DIA. BEYOND OPPOSITE BOTTOM REINF.
DRAINS, ETC. C. UNLESS OTHERWISE SPECIFIED, ALL FOOTINGS SHALL REST ON DENSE SAND OR VERY HARD MAYBE USED AT THE OPTION OF FABRICATION UPON THE APPROVAL
°
FACE OF SUPPORT 19.05 mm CLEAR
F. IN CASE OF DISCREPANCIES AS TO THE LAYOUT DIMENSIONS AND ELEVATIONS BETWEEN CLAY. THIS MAY SOMETIMES REQUIRE OVEREXCAVATION ABOUT 1.00m FROM PRESCRIBED OF ENGINEER.
HEIGHT OF LINTEL
THE STRUCTURAL PLANS AND OTHER DRAWINGS, THE CONTRACTOR SHALL NOTIFY BOTH BOUNDARY LEVEL. SUCH OVEREXCAVATION SHALL BE REPLACED WITH WELL COMPACTED 10mm
EXTERIOR GIRDER 0.10
THE STRUCTURAL ENGINEERS AND OWNER'S REPRESENTATIVE OF SITE ENGINEER IN CRUSHED ROCK BACKFILL. COMPACTION SHALL BE 95% OF MDD BASED ON ASTM D698. EXTERIOR COLUMN INTERIOR COLUMN SUPPORT B. QUALITY CONTROL
WRITING BEFORE PROCEEDING WITH THE AFFECTED WORK. SUPPORT SUPPORT
D. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE 0.075m CLEAR FOR 0.20
1. REFER TO SPECIFICATIONS FOR QUALITY CONTROL TESTING
L1
L2
L3
FIG. 7
CONCRETE DEPOSITED AGAINST THE GROUND AND 0.05m FOR CONCRETE DEPOSITED SPAN L REQUIREMENTS.
SEE TABLE "B" FOR LENGTH FIG. 5
NOTE ON CONCRETE MIXES AND PLACING AGAINST FORMWORK. SEE TABLE"B"
OF LAPPED SPLICE 2. STEEL SHAPES
L + 0.40
A. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND LOCATIONS AT FOR LENGTH OF
EMBEDMENT EVERY BATCH OF STRUCTURAL STEEL SHAPE FOR FABRICATION
CONSTRUCTION JOINTS TO THE FIELD ENGINEER AT LEAST FOUR ( 4 ) DAYS PRIOR TO THE SHALL HAVE THE MANUFACTURER'S MILL CERTIFICATE SHOWING
TABLE "A"
POURING FOR APPROVAL.
B. WET CURING OF CONCRETE SHALL BE CONTINUOUS FOR MINIMUM PERIOD OF TEN ( 10 )
MASONRY UNITS TENSION BARS EMBEDMENT LENGTH & LAP SPLICES THEIR CHEMICAL AND PHYSICAL PROPERTIES.
IN CENTIMETERS 3. WELD FINISH
DAYS IMMEDIATELY AFTER POURING. SCHEDULE OF CHB & CERAMIC BLOCK REINFORCEMENT ALL WELDS SHALL FREE FROM UNDERCUTS, PINHOLES AND CRACKS.
C. THE CONTRACTOR SHALL FURNISH AND MAINTAIN ADEQUATE FORMS FOR SHORINGS BAR SIZE fc' = 20.7 MPa fc' = 17.2 MPa
BLOCK REINFORCEMENT NON-DESTRUCTIVE TESTING (DYE PENETRANT) MAYBE CONDUCTED
NOTES: DEFORMED
UNTIL THE CONCRETE MEMBERS HAVE ATTAINED THEIR SUFFICIENT STRENGTH FOR THICKNESS HORIZONTAL VERTICAL EMBEDMENT LAP EMBEDMENT LAP
A. MINIMUM LAPS AT SPLICE = 0.25m NOTES ON EMBEDDED PIPES IN CONCRETE AT WELDS DEEMED NOT IN CONFORMITY WITH THE SPECIFICATION
WORKING CONDITION ANTICIPATED. B. PROVIDE RIGHT ANGLED REINFORCEMENT AT 10 mm 30 30 30 30 AND SHALL BE TO CONTRACTOR'S ACCOUNT.
75 mm 10 mmØ AT 10 mmØ @ 600 mm O.C. A. ALL EMBEDDED PIPES FOR UTILITIES, ETC. SHALL BE MAXIMUM 100mmØ SINGLE RIGID
D. ALL CONCRETE WORKS SHALL BE DONE IN ACCORDANCE WITH THE ACI 318 - 14 EVERY CORNERS 0.92m LONG. 12 mm 30 36 30 30
100 mm 10 mmØ @ 600 mm O.C.
C. WHERE CHB OR CERAMIC BLOCK WALLS GALVANIZED IRON PIPES UNLESS OTHERWISE SPECIFIED OR APPROVED IN WRITING BY THE
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE AND ALL STRUCTURAL 3 LAYER 16 mm 36 45 30 43
150 mm 12 mmØ @ 600 mm O.C. ADJOIN COL., RC BEAMS & WALL DOWELS WITH 20 mm 36 55 39 61
STRUCTURAL ENGINEER. C. FABRICATION
STEEL WORK IN ACCORDANCE WITH THE LATEST EDITION OF THE A.I.S.C. SPECIFICATIONS 200 mm 12 mmØ AT 12 mmØ @ 600 mm O.C. THE SAME AS VERT. OR HOR. REINFORCEMENT 22 mm 52.5 62.5 57.5 65 B. SUCH PIPES WHEN SO EMBEDDED SHALL NOT TAKE UP MORE THAN FOUR ( 4 ) PERCENT OF 1. WELDS
IN SO FAR AS THEY DO NOT CONFLICT WITH THE REQUIREMENTS OF THE NATIONAL EVERY SHALL BE PROVIDED.
3 LAYER
25 mm 56 95 62 105 THE GROSS AREA OF THE CONCRETE MEMBER. ALL WELDED CONNECTIONS SHALL DEVELOP THE FULL STRENGTH OF
STRUCTURAL CODE OF THE PHILIPPINES AND LOCAL CODES. 28 mm 71 121 77 131 THE MEMBERS CONNECTED.
E. A.C.I. REFERS TO AMERICAN CONCRETE INSTITUTE, A.I.S.C. TO AMERICAN INSTITUTE OF 32 mm 93 158 101 172
a. LENGTH OF WELDS:
STEEL CONSTRUCTION AND A.S.T.M. TO AMERICAN SOCIETY FOR TESTING MATERIALS. PROVIDE STIFFENER COLUMN COLUMNS AND BEAMS AT EVERY 3000mm ON CENTER FOR CHB 36 mm 151 179 128 218
THE MINIMUM LENGTH OF FILLET SHALL NOT BE LESS THAN 4 TIMES
F. UNLESS OTHERWISE INDICATED IN PLANS OR NOTED IN THE SPECIFICATIONS, THE WALL, USE 4 - 12mmØ VERTICAL BARS WITH 10mmØ TIES @ 300mm ON CENTER. THE NOMINAL SIZE WHERE INTERMITTENT WELDS MAY BE USED, THE
MINIMUM 28th DAY CYLINDER COMPRESSIVE STRENGTH OF CONCRETE SHALL BE AS TABLE "B" NOTES ON COMPACTED FILL LENGTH OF SEGMENT SHALL NOT BE LESS THAN 4 TIMES THE WELD
FOLLOWS: COMPRESSION BARS EMBEDMENT LENGTH & LAP SPLICES A. FILL, BACKFILL AND SUB-GRADES UNDER SLABS AND FOOTINGS SHALL BE COMPACTED TO A SIZE WITH A MINIMUM OF 40mm.
1. FOOTINGS, FOOTING TIE BEAMS: fc' = 20.7 MPa ( 3000 psi ) NOTES ON CONCRETE WALLS IN CENTIMETERS MINIMUM 95% OF MAXIMUM DRY DENSITY BASED ON ASTM D-698 FOR EVERY LIFT IN b. END RETURN OF FILLET WELDS
2. COLUMN, PEDESTALS: fc' = 20.7 MPa ( 3000 psi ) A. ALL WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING SCHEDULE OF WALL
BAR SIZE fc' = 20.7 MPa fc' = 17.2 MPa ACCORDANCE WITH THE SPECIFICATIONS. SIDE OR END FILLET WELDS TERMINATING AT END OR SIDES SHALL
3. BEAMS AND GIRDERS: fc' = 20.7 MPa ( 3000 psi ) REINFORCEMENT UNLESS OTHERWISE INDICATED IN THE PLANS.
DEFORMED B. MAXIMUM LIFT THICKNESS FOR COMPACTION SHALL BE 250mm. BE RETURNED CONTINUOUSLY FOR A DISTANCE NOT LESS THAN
4. NON-LOAD BEARING WALL PARTITION, CATCH BASIN, SIDEWALK (IF ANY): fc' = EMBEDMENT LAP EMBEDMENT LAP
SCHEDULE OF CHB & CERAMIC BLOCK REINFORCEMENT C. MONITOR QUALITY OF COMPACTION USING AN INDEPENDENT TESTING LABORATORY USING TWICE THE NOMINAL SIZE OF WELD.
17.2 MPa ( 2500 psi ) 10 mm 20 30 20 30 ASTM D-1556 CRITERIA.
WALL REINFORCEMENT VERTICAL c. USE E70 ELECTRODES FOR ALL WELDS IN STRUCTURAL STEEL.
REMARKS 12 mm 20 30 21 34
THICKNESS HORIZONTAL VERTICAL SECTIONS D. OVERSIZED BOULDERS UNDERNEATH FOOTINGS SHALL BE REMOVED TO PROVIDE FULL 2. BOLTS
G. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION, 16 mm 23 32.5 26 42.5
100 mm 10 mmØ @ 250 mm O.C. 10 mmØ @ 300 mm O.C. HOR. BARS @
VERT. STAG.
20 mm 28 37.5 31 50
BEARING. CAVITY OF VOID EXPOSED SHALL BE BACKFILLED WITH LEAN CONCRETE. a. MINIMUM EDGE DISTANCE:
RE-HANDLING OR FLOWING. PLACING SHALL BE DONE PREFERABLY WITH BUGGIES, BARS
125 mm 10 mmØ @ 200 mm O.C. 10 mmØ @ 250 mm O.C. CENTER, VERT. 22 mm 25 45 27.5 57.5 THE MINIMUM EDGE DISTANCE OF BOLTS SHALL CONFORM TO THE
BUCKETS OR WHEELBARROWS. NO CHUTE WILL BE ALLOWED EXCEPT TO TRANSFER 150 mm 12 mmØ @ 250 mm O.C. 12 mmØ @ 300 mm O.C. BARS STAG. 25 mm 37 51 41 67.5
175 mm 12 mmØ @ 220 mm O.C. 12 mmØ @ 250 mm O.C. OUTSIDE
HOR. BARS
REQUIREMENTS OF AISC STEEL MANUAL 8TH EDITION. THE MAXIMUM
CONCRETE FROM HOPPERS TO BUGGIES, WHEELBARROWS OR BUCKETS IN WHICH CASE VERT. 28 mm 42 57.5 47 75
200 mm 10 mmØ @ 250 O.C.E.F 10 mmØ @ 300 O.C.E.F. BOTH FACES BARS EDGE DISTANCE FROM BOLT CENTER SHALL BE 12 TIMES THICKNESS
THEY SHALL NOT EXCEED SIX ( 6 ) METERS IN AGGREGATE LENGTH. 225 mm 10 mmØ @ 200 O.C.E.F. 10 mmØ @ 250 O.C.E.F. HOR. BARS SHALL 32 mm 46 64 52 85
OF PLATE BUT NOT TO EXCEED 150mm.
H. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS 250 mm 12 mmØ @ 300 O.C.E.F. 12 mmØ @ 350 O.C.E.F. BE OUTSIDE HOR. BARS \
36 mm 51 72
NOTES ON SLAB ON GRADE b. MINIMUM PITCH
UNLESS AUTHORIZED IN WRITING BY THE DESIGNER AND ONLY FOR UNUSUAL
REINFORCING BARS SHALL HAVE 25mm MINIMUM CLEAR CONCRETE COVER FROM FACE OF A. SLAB SHALL BE PLACED WITH A MAXIMUM WATER CEMENT RATIO OF 0.42. ANY ON CENTER SPACING OF BOLTS SHALL NOT BE LESS THAN 3 TIMES
CONDITIONS WHERE VIBRATION IS EXTREMELY DIFFICULT TO ACCOMPLISH. ANY POURING
WALL EXCEPT FOR WALLS IN CONTACT WITH THE GROUND WHERE A MINIMUM OF 62.5mm DISCREPANCY IN SUMP OR WORKABILITY SHALL BE REMEDIED BY THE USE OF PLASTICIZER. THE NOMINAL DIAMETER.
REQUIRES ONE SPARE VIBRATOR ALWAYS. C. IF BEAM REINFORCING BARS END IN A WALL, THE CLEAR DISTANCE FROM THE BAR TO THE
SHALL BE PROVIDED, AND FOR EXPOSED FACES OF FORMED WALLS WHERE THE MINIMUM B. ADDITION OF FLY ASH TYPE "F" IS REQUIRED TO MAXIMUM OF 15% OF CEMENT WEIGHT. 3. TOLERANCES
I. SAMPLING FOR COMPRESSIVE STRENGTH TESTS SHALL BE MADE IN ACCORDANCE WITH FARTHER FACE OF THE WALL SHALL NOT BE LESS THAN 25mm. EMBEDMENT LENGTH SHALL
SHALL BE 50mm CLEAR. C. SLABS SHALL CAST STRAIGHT TO FINISH. OVERTROWELLING SHALL BE DONE USING SOME VARIATIONS EXPECTED IN THE FINISH OVERALL DIMENSIONS OF
SPECIFICATIONS BUT NOT LESS THAN I SET FOR EACH DAY OF POUR. BE AS SHOWN IN TABLE "A" FOR TENSION BARS AND TABLE "B" FOR COMPRESSION BARS.
B. CARRY VERTICAL BARS AT LEAST 600mm ABOVE FLOOR LEVEL TO PROVIDE FOR SPLICES, HELICOPTER TROWEL. FRAMES SHALL NOT EXCEED THE ROLLING TOLERANCES FOR CROSS
J. PULVERIZED FLY ASH ( PFA ) MAY BE SUBSTITUTED TO MAX 15% BY WEIGHT OF D. IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS, USE 25mm DIAMETER BAR
WHEN NECESSARY STOP AT 50mm BELOW TOP SLAB OR SOLID BAND WHERE THE WALL D. BROADCAST OF CEMENT POWDER SHALL NOT BE ALLOWED DURING FINISHING OPERATIONS. SECTIONAL DIMENSIONS, CAMBER AND SWEEP PERMITTED UNDER ASTM
ORDINARY PORTLAND CEMENT TYPE 1. THIS REQUIREMENT IS ONLY MANDATORY FOR SEPARATORS SPACED ABOUT 90 CENTIMETERS ON CENTER. IN NO CASE SHALL THERE BE
ENDS. VERTICAL AND HORIZONTAL BARS SHALL BE SPLICED BY LAPPING A DISTANCE EQUAL SPECIFICATION A36.
MAT FOUNDATION FOR CCT AND BBT TANKS AND IS OPTIONAL ELSEWHERE. STRENGTH LESS THAN TWO ( 2 ) SEPARATORS BETWEEN LAYERS OF BARS.
AND WORKABILITY REQUIREMENTS NEED TO SATISFIED IRRESPECTIVE OF WHETHER OF 40 BAR DIAMETERS AND WIRED SECURELY WITH NO. 16 G.I. WIRE PROVIDED THAT SPLICES IN
E. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS OR STEEL SHAPES SHALL BE AS D. ERECTION
PFA HAS BEEN USED OR NOT. ADJACENT BARS ARE STAGGERED AT LEAST 1.60m O.C. (SEE FIG. 3)
SHOWN IN FIG. 6. 1. BRACING
40 DIA. b
NOTES ON CONCRETE SLABS 1.60 MIN THE FRAME OF STEEL STRUCTURE SKELETON SHALL BE CARRIED UP TRUE
1.60m O.C.
SEE NOTE
A. ALL SLAB REINFORCEMENT SHALL BE 20.0mm CLEAR MINIMUM FROM BOTTOM AND FROM 40 DIA. b NOTES ON EQUIPMENT & MACHINERY LAYOUT AND PLUMB, WITHIN THE LIMITS DEFINED IN SECTION 7(h) OF AISC CODE OF
TOP OF SLAB. WEB BARS NOTE: A. CONTRACTOR SHALL REFER TO OWNER FURNISHED EQUIPMENT DIAGRAMS AND LAYOUT TO STANDARD PRACTICE. TEMPORARY BRACING SHALL BE PROVIDED TO
B. UNLESS OTHERWISE DETAILED, IN CONTINUOUS SLAB HAVING SAME REINFORCEMENT SEE NOTE 18.75 mm CLEAR FOR JOIST RESIST ALL LOADS INCLUDING ERECTION EQUIPMENT.
37.50 mm CLEAR FOR BEAMS VERIFY WETHER DISCREPANCIES, THE OWNER AND THE ENGINEER SHOULD BE NOTIFIED IN
RUNNING IN ONE DIRECTION, REINFORCING BARS SHALL BE BENT UP, EXTENDED, OR CUT AS
h
FIG. 3 FIG. 6 & GIRDERS WRITING BEFORE PROCEEDING WITH ANY AFFECTED WORK. 2. ALIGNMENT
0.60
THE REINFORCING BARS NEAR THE SUPPORTS, THE SPACING OF THE BARS AT COLUMN
STRIPS SHALL BE APPROXIMATELY ONE AND ONE HALF ( 1 12 ) THAT IN THE MIDDLE OPEN
STRIPSBUT NO CASE GREATER THAN TWO AND ONE HALF (2 12 ) TIMES THE SLAB THICKNESS FIG. 4
NOR 45 CENTIMETERS..
2 - BARS
D. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION U - FORM
0.40
A
0.40
1000
1000
1000
1000
1000
1000
C1 - F1 C1 - F1 C1 - F1 C1 - F1 C1 - F1 C1 - F1 C1 - F1 C1 - F1 C1 - F1
WF - 1 WF - 1 WF - 1
TB - 1 TB - 1 TB - 1 TB - 1 TB - 1 RB - 1 RB - 1 RB - 1 RB - 1
F F F
2575
2575
2575
RB - 1
RB - 1
WF - 1
WF - 1
TB - 1
TB - 1
3076
3076
3076
RB - 1
WF - 1
RB - 1
RB - 1
TB - 1
TB - 1
C1 - F1 C1 - F1 C1 - F1 C1 - F1
E C1 - F1 C1 - F1 C1 - F1
E C1 - F1 C1 - F1 C1 - F1
E RB - 1
C1 - F1 C1 - F1
WF - 1 WF - 1 SLAB ON FILL
100mm THK. + FIN. WITH 10mm Ø TEMP. TB - 1 TB - 1 TB - 1 TB - 1 RB - 1 RB - 1 RB - 1 RB - 1
D D D
RB - 1
RB - 1
WF - 1
TB - 1
TB - 1
1350
1350
1350
BARS@350mm O.C. EACH WAY
WF - 1
WF - 1
RB - 1
C C C
WF - 1
WF - 1
C1 - F1 C1 - F1 C1 - F1 C1 - F1
11695
11695
11695
WF - 1
RB - 1
RB - 1
RB - 1
TB - 1
TB - 1
TB - 1
RB - 1
RB - 1
WF - 1
WF - 1
TB - 1
TB - 1
4216
4216
4216
2575
2575
2575
12822
12822
12822
WF - 1
C1 - F1 C1 - F1
WF - 1
B B B RB - 1 RB - 1
RB - 1
TB - 1
WF - 1 TB - 1 TB - 1
WF - 1
C1 - F1 C1 - F1 C1 - F1 C1 - F1
A WF - 1
WF - 1
A TB - 1 A RB - 1
C1 - F1 C1 - F1
3403
3403
5322
5322
5322
x x x
FOUNDATION PLAN TIE BEAM FRAMING PLAN ROOF BEAM FRAMING PLAN
SCALE 1:100 M SCALE 1:100 M SCALE 1:100 M
TIES
1 2 3 4 1 2 3 4 REINFORCEMENTS
10mmØ RS BARS
1000 4@50mm
5 - 12MM Ø REINF. STEEL BAR
2@100mm
SPACED AT 200MM O.C. BOTH WAYS 850
12594 12594 REST 200mm O.C.
6195 6895 6195 6895 200 200 200 200
VERT. BARS
12mmØ RS BARS
HT - 1 TWO LINES OF HT - 2 VERTICAL
F F
200
10mm Ø SAG RODS REINFORCEMENT
AS SHOWN 4-12MMØ RS BARS
GA#24, SS 304 GUTTER, TYPICAL PER BAY GA#24, SS 304 GUTTER,
200
SATIN FINISH SATIN FINISH
1000
300
850
HT - 1
200
TWO LINES OF TIES
10mm Ø SAG RODS LC - 150 x 50 x 1.2mm HT - 2
E AS SHOWN E PURLINS @ 700mm O.C., with 200 10MMØ RS BARS SECTION
600
200
TYPICAL PER BAY 50 x 50 x 5 x 100mm CLIP ANGLE +
HT - 1 450 REINFORCEMENTS
4-10mm Ø MACHINE BOLTS
5-12mmØ RS BARS
D D
7500
7500
200
SPACED@104mm
8292
8292
BOTHWAYS
C C HT - 2
C1F1
HT - 1 TYP. PLAN OF FOOTING
104
450
200
600
LC - 150 x 50 x 1.2mm
HT - 1
PURLINS @ 700mm O.C., with NATURAL GRADE LINE
50 x 50 x 5 x 100mm CLIP ANGLE +
200
HT - 2 TIES
B 4-10mm Ø MACHINE BOLTS
B GA#24, SS 304 GUTTER,
10MM Ø REINFORCED STEEL BAR SPACE AT
PLAN
GA#24, SS 304 GUTTER, 8- 50MM O.C., 10 - 100MM O.C., 4 - 150MM ON
SATIN FINISH
200
SATIN FINISH CN CENTER REST 200MM
HT - 1
A A TYPICAL
150
6195 6896 6195 6896
C2 - F2 DETAILS
1350
1500
12594 12594
300
TYPICAL
C1 - F1 DETAILS
SCALE 1:100M
FOUNDATION PLAN 2
PROPOSED CONSTRUCTION OF BUNGALOW RESIDENTIAL BUILDING WITH PARKING SPACE TIE BEAM FRAMING PLAN S2 3
CRIS EMANUELLE H. CASTOR ROOF BEAM FRAMING PLAN
PROJECT LOCATION ROOF FRAMING PLAN
06 09
EVELYN L. ANTIOQUIA
PRC NO. : 0168420 12/07/26 TYPICAL COLUMN-FOOTING DETAILS
PTR NO. : BTG 33336550 01/18/24 BARANGAY MAMATID, CABUYAO, LAGUNA STRUCTURAL
TIN NO. : 478-509-028-000 09/16/20
3389 TB-1
150 200
C2 - F2
3389 TB-1 WF - 2
C2 - F2
WF - 2
TB - 1
2706 TB-1
WF - 2
TB-1 WF - 2
C2 - F2 150mm thick C.H.B. 200mm thick C.H.B.
TB-1
C2 - F2
WF - 2
TB-1
C2 - F2
C2 - F2
C2 - F2
TB-1 WF - 2
WF - 2
C2 - F2
TB - 1
WF - 2
TB-1
C2 - F2
C.H.B. HOR. BARS C.H.B. HOR. BARS
TB-1 WF - 2
C2 - F2
6288
C2 - F2
500
500
TB-1 WF - 2
C2 - F2
10mm Ø @ EVERY 400mm O.C., 10mm Ø @ EVERY 400mm O.C.,
WF - 2
TB-1
VERT. BARS VERT. BARS
C2 - F2
FIN. GRD. LN. (HOUSE) FIN. GRD. LN. (HOUSE)
WF - 2
C2 - F2
TB - 1
TB-1 WF - 2
200
200
C2 - F2
TB-1 WF - 2
NAT. GRD. LN. 10mm Ø @ EVERY 3rd LAYER, NAT. GRD. LN. 10mm Ø @ EVERY 3rd LAYER,
C2 - F2
C2 - F2
WF - 2 C.H.B. HOR. BARS C.H.B. HOR. BARS
12576
TB-1
C2 - F2
TB-1 WF - 2
C2 - F2
C2 - F2
WF - 2
WF - 2
TB - 1
TB-1
C2 - F2
850
850
WF - 2
TB - 1
WF - 2
TB-1
C2 - F2
C2 - F2
TB-1 WF - 2
6288
12mm Ø @250mm O.C. 12mm Ø @250mm O.C.
C2 - F2
C2 - F2
250
250
WF - 2
C2 - F2 BARS BARS
WF - 2
TB-1
TB - 1
C2 - F2
100
100
TB-1 WF - 2
C2 - F2
11696 100mm THK. WELL-COMPACTED 100mm THK. WELL-COMPACTED
C2 - F2
WF - 2
GRAVEL FILL GRAVEL FILL
400 400
WF
2-
TB
-1
TYPICAL
WF - 1 WF - 2
C2
-F
SCALE 1:25 M
WF
-2
TB
-1
C2
-F
2
WF
-2
TB
3 EQUAL THREADS
-1
@ 300mm
C2
- F2
t=
C2 - F2 10mm Ø BARS @
10mm Ø @ SPACED AS
1
CENTER OF RUN
00
WF - 2
WF
C2 - F2
SHOWN, NOSING BARS
2-
m
TB
-1
TB - 1
m
2
WF -
C2 - F2
2900
+F
C2
-F2
WF -
2 TB - 1
C2 - F2
2910
PATIO FLOOR LEVEL 4
IN.
WF -
2 TB - 1
WF
C2 - F2
3
-2
TB
-1
WF -
2 TB - 1
F2
C2 -
3 EQUAL RISES,
C2
2
-F
TB - 1
2
2
WF -
800
200±=600
F2
C2 -
WF -
2 TB - 1
1
WF
F2
C2 -
-2
TB
-1
WF -
2 TB - 1
C2 - F2
TOP OF SIDEWALK
C2
-F
TB - 1
2
2
WF -
C2 - F2
WF -
2 TB - 1
10mm Ø @ 300mm O.C.,
WF
C2 - F2
NATURAL GRADE LINE MAIN BARS
-2
TB
250
-1
WF -
2 TB - 1
400
C2 - F2
1 - 10mm Ø
C2
WF -
2 TB - 1
FENCE
150
C2 - F2
GRAVEL FILL
WF -
2 TB - 1
FOUNDATION PLAN
WF
C2 - F2
-2
100 3 - 10mm Ø
TB
-1
WF -
2 TB - 1 SCALE 1:150 M
C2 - F2
C2
PATIO
-F
TB - 1
2
WF-2
C2 - F2
WF -
2 TB - 1
STAIR DETAILS
WF
C2 - F2
2-
TB
SCALE 1:25 M
-1
TB - 1
C2 - F2
WF - 2
400 400
C2
-F
TB - 1
2
WF - 2
C2 - F2
WF -
2 TB - 1
WF
C2 - F2
2-
TB
-1
4
249
WF - 2 TB - 1
C2
-F
2
TB - 1
6832
400 400 400 400
1156
L/4 L/4
BEAM DETAILS
SCALE 1:16 M
RB - 1
140
1000
200 x 300
2∠s- 50 x 50 x 3mm THK
6388
PROPOSED CONSTRUCTION OF BUNGALOW RESIDENTIAL BUILDING WITH PARKING SPACE FOUNDATION PLAN 3
TIE BEAM FRAMING PLAN
S3 3
CRIS EMANUELLE H. CASTOR
PROJECT LOCATION ROOF BEAM FRAMING PLAN 07 09
EVELYN L. ANTIOQUIA
PRC NO. : 0168420 12/07/26 ROOF FRAMING PLAN
PTR NO. : BTG 33336550 01/18/24 BARANGAY MAMATID, CABUYAO, LAGUNA STRUCTURAL
TIN NO. : 478-509-028-000 09/16/20
LEGEND ELECTRICAL SYMBOLS
PINLIGHT WITH COMPACT FLOURESCENT BULB
WALL BRACKET LAMP WITH COMPACT FLOURESCENT BULB
DUPLEX CONVENIENCE OUTLET
3 CIRCUIT HOMERUN FOR LIGHTING
y 1 2 3 4 y' y 1 2 3 4 y'
3 CIRCUIT HOMERUN FOR APPLIANCE OUTLETS
s-abc THREE GANG SWITCH
12594 12594
2425 3196 3395 2575 1000 2425 3196 3395 2575 1000
x' x'
1000
1000
1000
1000
F F
d d j j
2 4
DIRTY MASTER'S DIRTY MASTER'S
KITCHEN/ KITCHEN DINING KITCHEN/ KITCHEN DINING
2575
2575
ROOM ROOM
GENERAL NOTES AND SPECIFICATIONS
3076
3076
LAUNDRY ROOM s-ij LAUNDRY ROOM
e e
AREA AREA 1. THE ELECTRICAL INSTALLATION SHOWN ON THE PLANS SHALL CONFORM
1
E i i E WITH THE LATEST EDITION OF THE PHILIPPINE ELECTRIC CODE RULES
AND REGULATIONS OF THE LOCAL ELECTRIC COMPANY AND THE LOCAL
c c
GOVERNMENT WHERE THE PROJECT WILL BE CONSTRUCTED.
D D
1350
1350
s-h T&B T&B
s-cde h 2. ALL ELECTRICAL MATERIALS AND EQUIPMENT TO BE USED IN THIS
T&B 5 T&B PROJECT SHALL BE BRAND NEW AND OF APPROVED QUALITY AND BRAND.
C o
C
CASHIER
CASHIER
3 LIVING LIVING 3. ALL WIRING SHALL BE INSTALLED IN STANDARD ELECTRICAL uPVC
s-o
k b ROOM b g g ROOM CONDUIT PIPES RUN EMBEDDED INSIDE THE HOLLOW BLOCKS
11695
11695
LPP s-mn n LPP
BEDROOM BEDROOM AND CONCRETE STRUCTURES SLABS COLUMNS WALLS PARTITIONS AND
4216
4216
2575
2575
OR RUN CONCEALED BETWEEN DOUBLE WALL WOODEN PARTITIONS AND
12822
12822
s-fg
s-k
m INSIDE THE CEILING SPACES WHERE THE USE IF CONCEALED OR EMBEDDED
OFFICE/STORE OFFICE/STORE CONDUIT WIRING IS IMPRACTICABLE METAL MOULDING WIRING MAYBE USED.
f f
a a 4. UNLESS OTHERWISE INDICATED ON THE PLANS THE MINIMUM SIZE OF THE CONDUIT
B s-l l l
s-ab
B AND WIRE TO BE USED SHALL BE 20MMØ SCHED 40 AND 3.5MM² TW 600V INSULATION.
5. WHEREVER REQUIRED AND NECESSARY PULL BOXES AND JUNCTION BOXES
A A OF PROPER SIZES SHALL BE INSTALLED AT A CONVENIENT AND INCONSPICUOUS
LOCATIONS ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE PLANS NOR
PATIO PATIO MENTIONED ON THE SPECIFICATIONS.
CARPORT CARPORT 6. THE TYPE OF POWER SERVICE TO BE SUPPLIED SHALL BE SINGLE PHASE 220V AC
3403
3403
7. MOUNTING HEIGHT OF ELECTRICAL DEVICES SHALL BE AS FOLLOWS
5322
5322
A. WALL SWITCHES 1.37M ABOVE FINISH FLOOR LEVEL
B. CONVENIENCE OUTLETS 0.30M ABOVE FINISH FLOOR LEVEL
C. AIRCONDITIONING OUTLETS 2.00M ABOVE FINISH FLOOR LEVEL
x x D. PANEL BOARD 1.37M ABOVE FINISH FLOOR LEVEL
E. WASHING MACHINE OUTLET 1.50M ABOVE FINISH FLOOR LEVEL
F. KILOWATT HOUR METER 1.85M FROM GROUND TO CENTER OF METER
8. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE
SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER OR MASTER ELECTRICIAN
5621 6973 5621 6973
12594 12594
SCHEDULE OF LOADS
LINE SIDE LOAD SIDE NO OF NO OF OTHER VA PER AMP SIZE OF BRKS SIZE OF HOMERUN
CRT NO. LOAD DESCRIPTION
PROPERTY LINE
LIGHTS C.O. LOAD CIRCUIT LOAD/CRT F P T WIRE CONDUIT
1 40W LED LAMP 10 400 1.81 50 2 20 2-3.5mm² THHN 20mmØ PVC
NORMAL MANUAL 2 40W LED LAMP 9 360 1.63 50 2 20 2-3.5mm² THHN 20mmØ PVC
SERVICE TRANSFER SERVICE DROP
3 40W LED LAMP 6 240 1.09 50 2 20 2-3.5mm² THHN 20mmØ PVC
M SWITCH
ENTRANCE CAP 4 DUPLEX CONVENIENT OUTLET 10 1,800 8.18 50 2 20 3-3.5mm² THHN 20mmØ PVC
5 DUPLEX CONVENIENT OUTLET 4 720 3.27 50 2 20 3-3.5mm² THHN 20mmØ PVC
DRIP LOOP WIRES 6 SPARE 1 1,500 6.82 50 2 20 3-3.5mm² THHN 20mmØ PVC
100AT TOTAL LOAD OF THE BUILDING 5,020 22.81 AMPERES
G CONDUIT STRAPPED TO LIGHTING AND POWER USE 60 AT, 100AF 220V CIRCUIT BREAKER
CONCRETE POST PANEL BOARD D.F. ( DEMAND FACTOR ) = 75% I T =22.81 x 0.75 = 17.10 AMPERES
GEN SET 2-30mm2 THHN + 1-14mm2 THHN (G)
60AT in 50 mmØ PVC
5500
1 20A 20A 2
WATT HOUR METER GROUNDING WIRE
3 20A 20A 4
ENTRANCE ELL
5 20A 20A 6
PUBLIC ROAD
REGISTERED ELECTRICAL ENGINEER PROJECT TITLE OWNER SHEET CONTENTS SHEET NO.
LIGHTING LAYOUT
PROPOSED CONSTRUCTION OF BUNGALOW RESIDENTIAL BUILDING WITH PARKING SPACE 1
POWER LAYOUT
GENERAL NOTES
E1 1
CASHIER
CASHIER
LIVING LIVING LIVING
VAULT
ROOM ROOM ROOM DESIGNER.
SHELVES BEDROOM SHELVES BEDROOM SHELVES BEDROOM
ALL MATERIALS TO BE USED SHALL BE NEW AND OF APPROVED TYPE
APPROPRIATE FOR BOTH LOCATION AND INTENDED USE.
800
875 600
2300
800
600
500 PLAN
500
FD
CENTER LINE PLAN OF SEPTIC COVER
OF SLOPE SCALE 1: 50 M
P-TRAP
℄ 5000 TYPICAL
WYE
MANHOLE
2300
2000
2000
2000
800 x 800
TYPICAL
SL
OP
E OP JOINT CONNECTION DETAILS
SL E 500 SCALE NTS
WYE
500
SCALE 1: 50 M
5000
2550 1150 1300
500 PLAN
2 % SLOPE
OUTLET
200
600
2 % SLOPE
2400 1000 1000
GRAVEL
100
BOULDERS
SECTION THRU AA
TYPICAL
CATCH BASIN DETAILS
SCALE NTS