Water Heaters Calculation

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 2

Project No.

Date

DESIGN CALCULATION GHENIA ###


Shair and Partners
SHEET Sheet No. Computed by

1 of 1 M A-bakry
Checked by Approved by
Subject

A-bakry

Application Type Apartment House

Qty Fixtures Selected ###


Bathtubs * 20 gph = 0 gph
Kitchen Sinks * 10 gph = 0 gph
30 Private Lavatory * 2 gph = 60 gph
Public Lavatory * 4 gph = 0 gph
15 Showers * 30 gph = 450 gph
###
###
CALCULATION RESULTS ###
###
Possible Maximum Demand: 510 gph
###
Demand Factor: 0.3 ###
###
Probable Maximum Demand: 153 gph
###
Heater Recovery Capacity: 153 gph
###
Storage Factor: 1.25 ###

Strorage Tank Capacity: 191.25 gal

Hot Water Tank Inlet / Outlet Temperatures:


T in (Deg F): 41
T out (Deg F): 140

Heater or Coil Capacity: 126225 Btu/hr


36.9944 KW

Calculations are done using the " Number of Fixtures" method as per ASHREA 1976 Systems Handbook Chap 37.
Data

Apartement Club Gymnasium Hospital Hotel Industria Office Private Schoo Y.M.C.
House l Plant Buildin Residenc l A
g e
Private lavatory 2 2 2 2 2 2 2 2 2 2
Public lavatory 4 6 8 6 8 12 6 15 8
Bathtubs 20 20 30 20 20 20 30
Dishwashers 15 100 100 100 60 15 60 60
Foot Basins 3 3 12 3 3 12 3 3 12
Kitchen Sinks 10 20 20 30 20 20 10 20 20
Laundry Tubs 20 28 28 28 20 28
Pantry Sinks 5 10 10 10 10 5 10 10
Showers 30 150 225 75 75 225 30 30 225 225
Slop Sink 20 20 20 30 20 20 15 20 20
Hydrotherapeutic
400
Showers
Hubbard Baths 600
Leg Baths 100
Arm Baths 35
Sitz Baths 30
Continous Flow
165
Baths
Circular Wash
20 20 30 20 30
Sinks
Semicircular
10 10 15 10 15
Wash Sinks
Demand Factor: 0.3 0.3 0.4 0.25 0.25 0.4 0.3 0.3 0.4 0.4
Storage Factor: 1.25 0.9 1 0.6 0.8 1 2 0.7 1 1

Apartment House 2
Club 3
Gymnasium 4
Hospital 5
Hotel 6
Industrial Plant 7
Office Building 8
Private Residence 9
School 10
Y.M.C.A 11