DRAWING
RACK

For lifting gears comment


please kindly check page Please Mention actual wall
number opening size at HVAC Room.
Because we need to make sure
our AHU Including Damper
Installation are not touching
Architecture Scaffolding &
Rebar

CLOSE
OPEN
A O M OFF
ON

DRAWING
RACK

Please check next page to check


another comment

A O M OFF
ON

DRAWING
RACK
Please add our AHU view from side view, front view, isometric view

Example
Please mention your calculation based your
catalogue crane and marking it, so our
permit

Example
Our available Shackle are 7/8", but two from four of our lug hole for lifting
(using connector hole to join AHU Blower & AHU Evaporator part) Size are
M20. So we can't using 7/8 shackle for these two lug hole, we must borrow
from another company, we must prepare to searching this M20 shackle if
sarens team don't have it, please kindly check image below

Connector hole size, please check


another attachment in email for detail
drawing
7/8' or M22.225 hole
for shackle (AHU Lug
Hole for lifting
M20 hole for shackle (AHU
7/8' or M22.225 hole Connector lug hole)
for shackle (AHU Lug
Hole for lifting
Our Available Spreader bar size are 7.1M x 3.2M, it's very big sized
compared to our AHU size (separated to two part, each part are 2650 mm.
We prefer using smaller lifting gears (borrow from sarens), but we want to
know your comment regarding this info