Inspection Report of Electrical Installation Version No.

(En) 9
Issue Date
F-OPN-04
23/07/2023

ELECTRICAL INSTALLATION CONDITION REPORT


(The inspection and testing detailed in this report and accompanying schedules have
been carried out in accordance with Saudi Building code [401])

DECLARATION
The procedures of inspection had done on the electrical installation (as
indicated by our signatures below). The results were recorded in accordance
with the highest standards of quality and efficiency, and all information and
data contained in this report and the tables and observations contained in it,
were developed after careful evaluation of the current state of electrical
extensions (in the period of implementation of the inspection) in accordance
with the provisions of this report, We highlighted that the certificate and/or
inspection report reflects the state of wiring installation in the period of
carried out of the inspection and any modification of electrical installations
or additions to electrical loads that occur after the date of the report are not
the responsibility of the company and are not covered by the certificate
and/or inspection report.
Inspected and tested by: Reviewed and approved by:
Inspection engineer Technical Manager
Mohammed Ali
Name Name Abdulrahman Almalki
Ahmed Alshari
Mohammed Ali
Sign. Sign. Abdulrahman Almalki
Ahmed Alshari
Date 03/09/2023 Date 03/09/2023
Company: Qeraton Arabia Company
Address: Al Riyadh - Saudi Arabia
Building reference No. ZMK052(1014366)
Report Number SA23MK392
SCHEDULE(S)
8 schedules of inspection and 8 schedules of test results are part of this
document and this report is valid only when they are covered. The extent of
liability of the signatories is limited to the work described as the subject of
this report.

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
1|Page
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa
Inspection Report of Electrical Installation Version No.
(En) 9
Issue Date
F-OPN-04
23/07/2023

THE FOLLOWING JOB(S) IS/ARE APPLICABLE TO THIS REPORT


Electrical Installation
✘ Visual Inspection ✘ All Tests Determined Test(s)

DETAILS OF THE CLIENT


Name: Tawal Phone: 0555242114
Contact Person: Ali Jaradat Mobile: 0555242114
Address: Makkah – Arafat E-mail:

BUILDING ELECTRICAL DATA


Voltage type: 127/220 V ✘ 220 V L/L 230/400 V
Total Main Circuit Breaker Capacity (A) 125
No. of Electrical Meters -
Total No. of Panels to be Inspected 1

DETAILS OF THE INSTALLATION


Occupied: Unoccupied: ✘
Temperature: 40 Humidity: 17
Address: Makkah – Arafat
Description of Premises:
Domestic Commercial Industrial Other Com. Tower
Estimated age of the Electrical Installation: 5 Years
Evidence of Alterations or Additions: If “yes” estimated age: Years
Inspection Type: Initial ✘ Re-Inspection ☐
Mohammed Ali
Inspection Date: 03/09/2023 Records held by:
Ahmed Alshari
Electrical Installation Certificate No: IC1028

INFORMATION

No. Electrical INSTALLATION (risk analysis) Yes No

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
2|Page
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa
Inspection Report of Electrical Installation Version No.
(En) 9
Issue Date
F-OPN-04
23/07/2023

1 Can the work be done with the electricity dead or energized at a


☒ ☐
safe voltage or current?
2 Is it absolutely necessary for someone to be working on or near
☒ ☐
to equipment that is live at dangerous voltages or current levels?
3 Are the testers competent? Are they adequately trained and
knowledgeable, or have sufficient experience to carry out the ☒ ☐
work without risk to themselves and others?
4 Are danger notices and warnings used? ☒ ☐
5 Are the testers able to supervise the working area sufficiently
☒ ☐
and at all times, to prevent danger to others?
6 physical safeguards should be applied to the equipment under
☒ ☐
test to prevent injury, eg the use of temporary screens?
7 Do you need to set up a temporary test area around the
☒ ☐
equipment?
8 If testing is being done in a customer’s home, what special
☐ ☒
precautions are required to protect the tester and others?
9 there is much space around it to undertake the testing in a safe
☒ ☐
and unconfined manner?
10 Are all the other workshop employees competent to avoid
☒ ☐
danger?
11 Is it possible to reduce the number of available paths to earth to
reduce the likelihood of a phase-to-earth shock, e.g., by using ☒ ☐
barriers, screens and insulating mats?
12 Is there any fire alarm & protection available in the site? ☒ ☐
13 Are there wet areas or water? ☒ ☐
14 Using funnels to prevent the entry of any unauthorized
☒ ☐
individuals into the work area?
Note:

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
3|Page
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa
Inspection Report of Electrical Installation Version No.
(En) 9
Issue Date
F-OPN-04
23/07/2023

SCHEDULE (1): GENERAL INSPECTION


Conformity
Notes Description No.
NA No Yes
Circuits to be separated (no
☐ ☐ ☒ interconnections of neutral between 1
circuits).
☐ ☐ ☒ Adequate number of circuits. 2
☐ ☐ ☒ All circuit suitably identified. 3
☐ ☐ ☒ Use suitable main circuit breaker 4
Use suitable double pole switch of a
☐ ☐ ☒ 5
current rating.
Main earthing terminal provided, readily
☐ ☐ ☒ 6
accessible and identified.
☐ ☐ ☒ Conductors correctly identified. 7
☐ ☐ ☒ All connection is secure 8
Protective conductors provided to every
☐ ☐ ☒ 9
point and accessory.
All live parts are either insulated or
☐ ☐ ☒ 10
contained within enclosure
☐ ☐ ☒ Existing of earth rod 11
Ensure that there are standard
☐ ☐ ☒ specifications on the instruments and 12
equipment’s of SASO or IEC.

SCHEDULE (2): INSPECTION OF CABLES AND CORDS


Conformity
Notes Description No.
NA No Yes
Cables compliance with reference
☐ ☐ ☒ 1
standard (SASO, IEC, etc.).
☐ ☐ ☒ Cables with a correct current rating. 2
Identification of Neutral (N), Protective
☐ ☐ ☒ Earth-Neutral (PEN) and Protective Earth 3
(PE) conductors.
Connection of conductors (size of terminal
adapted to cross section area of
☐ ☐ ☒ 4
conductors) sufficient pressure contact
shall be guaranteed.

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
4|Page
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa
Inspection Report of Electrical Installation Version No.
(En) 9
Issue Date
F-OPN-04
23/07/2023

SCHEDULE (2): INSPECTION OF CABLES AND CORDS


Conformity
Notes Description No.
NA No Yes
Non sheathed cables protected by
☐ ☐ ☒ 5
enclosure in conduit, duct or trucking
☐ ☐ ☒ conduit allow suitable number of cables 6
Cables suitable for voltage drop capacity.
☐ ☐ ☒ 7
(3% lighting 5% other uses)
ducts shall be moisture resistant and
☐ ☐ ☒ corrosion and securely installed against 8
Mechanical damage.
Metal conduit connected to main earth
☐ ☐ ☒ 9
terminal.
The colors used do Use of cable insulation color conforming to
not match the the colors specified in the Saudi Building
colors specified in ☐ ☒ ☐ Code. 10
the Saudi Building
Code

SCHEDULE (3): INSPECTION OF LIGHTING FEATURES


Conformity
Notes Description No.
NA No Yes
Single pole switches connected in line
☐ ☐ ☒ 1
conductors only.
☐ ☐ ☒ Earthing of metalwork, metal switch plate. 2
Terminated in suitable accessories.
☐ ☐ ☒ 3
(use connection terminal instead of tape)

SCHEDULE (4): INSPECTION OF SOCKET OUTLETS AND JOINT BOXES


Conformity
Notes Description No.
NA No Yes
Sockets outlet Conformity with the
☒ ☐ ☐ reference standard according to (SASO, 1
VDE, etc.)
☒ ☐ ☐ Ensure that the socket is installed at a 2
suitable height above the ground
- 300 mm above the finished floor for
indoor installation
- 700 mm for Arabic Majles.

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
5|Page
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa
Inspection Report of Electrical Installation Version No.
(En) 9
Issue Date
F-OPN-04
23/07/2023

SCHEDULE (4): INSPECTION OF SOCKET OUTLETS AND JOINT BOXES


Conformity
Notes Description No.
NA No Yes
- Outside the buildings 1 meter above the
earth.
- In the kitchen 300 mm above worktop
Suitable number of socket outlets (8
☒ ☐ ☐ 3
sockets per circuit)
The protective conductor is connected
☒ ☐ ☐ directly to the earthing terminal of the 4
socket outlet
Enclosure of sockets shall be provided
protection:
- Surface sockets not less than (IP20).
☒ ☐ ☐ 5
- Floor socket not less than (IP24).
- Sockets located outside the building not less
than (IP25).
☒ ☐ ☐ Easily inspection of joint boxes 6
the joints protected safe against
☒ ☐ ☐ 7
mechanical damage

SCHEDULE (5): INSPECTION OF DISTRIBUTION PANEL BOARD


Conformity
Notes Description No.
NA No Yes
Panel boards Conformity with the
☐ ☐ ☒ reference standard according to (SASO, 1
VDE or BSI, etc.)
Ensure that all distribution panel board is
☐ ☐ ☒ 2
earthed
Ensure that each panel board achieves its
☐ ☐ ☒ 3
(IP).
☐ ☐ ☒ Panel boards located in suitable places 4
☐ ☐ ☒ Ensure full protection from direct contact 5
Use circuit breakers with rated current
☐ ☐ ☒ 6
suitable for loads
Suitable of electric panel boards for future
☐ ☐ ☒ 7
extension.
No sharp edges in cable entrances, nor
☐ ☐ ☒ 8
screw heads that damage cables

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
6|Page
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa
Inspection Report of Electrical Installation Version No.
(En) 9
Issue Date
F-OPN-04
23/07/2023

SCHEDULE (5): INSPECTION OF DISTRIBUTION PANEL BOARD


Conformity
Notes Description No.
NA No Yes
Use double poles circuit breakers when
☐ ☐ ☒ using 220 volts between two lines in the 9
new building in the existing areas.
Use three-poles circuit breakers when
The voltage used in the
☒ ☐ ☐ using voltage (400) volts for which loads 10
panel is 127/220 volts
operates on three phases

SCHEDULE (6): INSPECTION OF PROTECTION DEVICE


Conformity
Notes Description No.
NA No Yes
Inability to RCD Conformity with the reference
☒ ☐ ☐ 1
disconnect the power standards according to (SASO, IEC, etc.)
Inability to Existing RCD devices
☒ ☐ ☐ 2
disconnect the power
Inability to Discrimination between different RCD
☒ ☐ ☐ 3
disconnect the power devices

SCHEDULE (7): INSPECTION OF LABELLING AND NOTIFICATIONS


Conformity
Notes Description No.
NA No Yes
☐ ☐ ☒ Warning notice 1
☐ ☐ ☒ Danger notice 2
☐ ☐ ☒ Diagram and schedule 3
☐ ☐ ☒ Isolating, switching device 4

SCHEDULE (8): Earth Fault Loop Impedance Test


Conformity
Notes Description
NA No Yes
☐ ☐ ☒ Measured earth fault loop impedance
No. of Circuits / The earth fault loop impedance in
2.05
ohms.

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
7|Page
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa
Inspection Report of Electrical Installation Version No.
(En) 9
Issue Date
F-OPN-04
23/07/2023

SCHEDULE (9): Polarity Test


Conformity
Notes Description
NA No Yes
Connected wires properly to socket and lamps,
☒ ☐ ☐
etc..
No. of Circuits / Polarity Test Results

SCHEDULE (10): Continuity of Conductors


Conformity
Notes Description
NA No Yes
Inability to disconnect Execution continuity test on all protective
☒ ☐ ☐
the power conductors.
Inability to disconnect Execution continuity test on all conductors at
☒ ☐ ☐
the power the end of the circuit.
Continuity of Ring Final Circuit Continuity of
Circuit No.
Measured Resistance (ohm) Protective Conductors
or Details
Notes Protective Neutral Phase Measured
of
Conductor Conductor Conductor Resistance (ohm) at Equipment
outlet

SCHEDULE (11): Residual Current Device (RCD) Test


Conformity
Notes Description
NA No Yes
50% of the rated tripping current should not
☒ ☐ ☐
trip the breaker
100% of the rated tripping current should trip
☒ ☐ ☐
the breaker within the 300 mSec.
Test Results Circuit No.
Built-in test 50% rated /Designation
Opening time of
Notes button tripping
under 100% Hand Protective
(tripped current
rated tripping operation Devices
/ not (tripped
current (ms)
tripped) /not tripped)

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
8|Page
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa
Inspection Report of Electrical Installation Version No.
(En) 9
Issue Date
F-OPN-04
23/07/2023

SCHEDULE (12): Insulation Resistance Test


Conformity
Notes Description
NA No Yes
Inability to disconnect Insulation resistance between phases shall
☒ ☐ ☐
the power not be less than 1 mega Ohm
Inability to disconnect Insulation resistance between phase and
☒ ☐ ☐
the power earth shall not be less than 1 mega Ohm
Result of insulation test (Ohm) Insulation
Note resistance No. of circuit
Protective Neutral Phase value

SCHEDULE (13): Earth Electrode Resistance Test


Conformity
Notes Description
NA No Yes
Measurement of earthing electrode resistance
Inability to reach the
☒ ☐ ☐ (Ensure that the earth resistance does not
electrode
exceed 5 ohm)
Notes Earth electrode value (Ohm) No. of circuit

SCHEDULE (14): Phase Sequence Test


Conformity
Notes Description
NA No Yes
Ensuring that the sequence of the three
☐ ☐ ☒
phases was not reversed

SCHEDULE (15): Phase Balance Test


Conformity
Notes Description
NA No Yes
Measurement of each phase current to ensure
☐ ☐ ☒ that unequal current on the phases is not
exceed than 10%
Ensure that each protective devices and
☒ ☐ ☐ circuit is in normal operation using the
thermographic camera

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
9|Page
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa
Inspection Report of Electrical Installation Version No.
(En) 9
Issue Date
F-OPN-04
23/07/2023

SCHEDULE (16): INSPECTION OF fire alarm and fighting


Conformity
Notes Description No.
NA No Yes
83-2 General requirements SBC 401
a safety source shall maintain an adequate and
OUT OF SCOPE ☐ ☐ ☒ 1
continuous electrical supply;
equipment installations shall have a fire resistance
☐ ☐ ☒ of an adequate duration either by a suitable 2
selection or by an erection
83-3 Electric power supply SBC 401
The rated voltage of the auxiliary circuit and the
☐ ☐ ☒ components used in the circuit shall be compatible 3
with the supply to that circuit.
an automatic-supply, the starting of which is
☐ ☐ ☒ 4
independent of an operator.
The fire command center shall comply with NFPA 72 and shall contain the following
features (Required features) SBC 801
The emergency voice/alarm communication
☐ ☐ ☒ 5
system control unit.
The fire department (Civil Defense)
☒ ☐ ☐ communications system.
6

☐ ☐ ☒ Fire detection and alarm system annunciator. 7


Annunciator unit visually indicating the
☒ ☐ ☐ location of the elevators and whether they are 8
operational
Status indicators and controls for air
☒ ☐ ☐ distribution systems.
9
☒ ☐ ☐ The fire fighter’s control panel required by Section 10
909.16 for smoke control systems installed in the
☒ ☐ ☐ building
11
Controls for unlocking stairway doors
☒ ☐ ☐ simultaneously.
12
Sprinkler valve and water-flow detector
☒ ☐ ☐ display panels
13
Emergency and standby power status
☒ ☐ ☐ indicators.
14
A telephone for fire department (Civil
☒ ☐ ☐ Défense) use with controlled access to the 15
public telephone system.
☒ ☐ ☐ Fire pump status indicators. 16

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
10 | P a g e
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa
Inspection Report of Electrical Installation Version No.
(En) 9
Issue Date
F-OPN-04
23/07/2023

SCHEDULE (16): INSPECTION OF fire alarm and fighting


Conformity
Notes Description No.
NA No Yes
Schematic building plans indicating the
☒ ☐ ☐ typical floor plan and detailing the building core,
17
General requirements Portable fire extinguishers Extinguisher installation. The
installation of portable fire extinguishers SBC 801
Extinguisher s weighing 18 kg or less
Portable fire extinguishers having a gross weight not
☒ ☐ ☐ exceeding 18 kg shall be installed so that their tops are 18
not more than 1500 mm above the floor.
Extinguisher s weighing mor e than 18 kg
Hand-held portable fire extinguishers having a gross
☒ ☐ ☐ weight exceeding 18 kg shall be installed so that their
19
tops are not more than 1100 mm above the floor.
Floor clearance. The clearance between
☒ ☐ ☐ the floor and the bottom of installed hand-held portable 20
fire extinguishers shall be not less than 100 mm.

Result of Inspection
Not Comply ☐ Comply ☒

Non-Conformities:

1. The colors used do not match the colors specified in the Saudi Building Code.

FIGURES OF NON-CONFORMITY

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
11 | P a g e
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa
Inspection Report of Electrical Installation Version No.
(En) 9
Issue Date
F-OPN-04
23/07/2023

Non-Conformity No. (1)

Office # 4, 3571 Imam Saud Bin Abdulaziz Bin Mohamed Rd., 8514 King Fahd Dist.,
12 | P a g e
Riyadh, KSA, Tel. No. 920024402 - E-Mail Info@salim.com.sa