Technical Parameters: Siemens

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Technical Parameters

Rated voltage 132 kV


=E01 =E02 =E03
H H
Rated frequency 50 Hz
Rated lightning impulse withstand
-T25 650 kV
voltage
-T15
Rated switching impulse withstand

M
Busbar -T3 - kV
voltage
Rated short duration power frequency
G -QZ1 275 kV G
M QZ1
withstand voltage
M -T2 M M
QZ1 -QZ1
Rated normal current - Busbar 2000 A
-T1 -T52
Rated normal current - Feeder 2000 A
-Q0 -T51 -Q0
-Q0
-T1 -T1
Rated short - time withstand current 40 kA
-T1
F F
Rated duration of short circuit 3 s
-QZ9 M -QZ9
M
-QZ9
M Ambient indoor temperature -5…+40 °C
-Q8

-Q8 -Q8

-T5
-F1 -F1
E E
-F1

-Z1 -Z1 -Z1

LINE 1 TRAFO 1 TRAFO 2

D Symbol Designation Description D

-Q0 Circuit breaker

-QZ1 Three position switch, insulated


M

-Q1 Disconnecting switch


M

C Motor-operated work-in-progress earth C


-Q15
M switch
-Q8 High speed earthing switch, insulated
Work in progress earthing switch,
-Q8
M insulated For tender purpose only
-T1 Current transformer Project: 132 kV GIS extension at
B 8DN8 SWITCHGEAR B
-T15, -T5 Voltage transformer Kalika Steel
145 kV
-QZ9 Three position switch, non insulated Date 13.10.2023
M

Drawn SSK

Gas tight bushing Appr. ND


Single Line Diagram
Norm

A -F1 Surge arrester Sheet A

-Z1 SF6 to Air Bushing 0 First Issue 13.10.2023 SSK


SIEMENS A3_G71770_RE2391_S005_R0 1
1 Shs.
Rev. Remarks Date Name

8 7 6 5 4 3 2 1