Professional Documents
Culture Documents
CH 2
CH 2
Outlines:
• Electromagnetic induction
• Working principle
• Transformer ckt
Electromagnetic induction
• When a conductor is moved through a magnetic field, a voltage is produced
across then conductor as shown in fig 4 below.
• This principle is known as electromagnetic induction, and the resulting voltage is
an induced voltage.
𝑑𝜙
• Therefore 𝑉𝑖𝑛𝑑 = 𝑁 ×
𝑑𝑡
• The principle of electromagnetic induction is widely applied in electrical circuits in
the study and operation of transformers, electric motor and generators.
Basic Theory of The Transformer
• A transformer is a static piece of equipment used either for raising or lowering the voltage of an
A.C. supply with a corresponding decrease or increase in current.
• It essentially consists of two windings, the primary and secondary, wound on a common
laminated magnetic core.
• The winding connected to the a.c. source is called primary winding (or primary) and the one
connected to load is called secondary winding (or secondary).
• Depending upon the number of turns of the primary (N1) and secondary (N2), an
alternating emf. E2 is induced in the secondary.
• This induced emf. E2 in the secondary causes a secondary current I2.
• Consequently, terminal voltage V2 will appear across the load.
• If V2 > V1, it is called a step up-transformer.
• On theother hand, if V2 < V1, it is called a step-down transformer.
Principle Operation of The Transformer
• In its simplest form, it consists of two inductive coils which are electrically separated but
magnetically linked through the path of low reluctance as shown in the fig 1 below.
• Thus when an alternating voltage V1 is applied to the primary, an alternating flux (Φ) is set up in
the core.
• This alternating flux links both the windings and induces e.m.f E1 and E2 in them according to
Faraday’s laws of electromagnetic induction.
• The e.m.f. E1 is termed as primary e.m.f and e.m.f. E2 is termed as secondary e.m.f.
Fig2: type of
transformer
Types of Transformers
2. According to Cooling System
There are two types of cooling systems of the transformer via, dry type transformer
and oil immersed transformer.
Fig 4: Winding
resistance
Fig 5: flux leakage
Core loss
Impedance transformation of the transformer
• From the voltage and current transformation ratio:
V1 I2 N1
= = =K
V2 I1 N2
Therefore :
V1 V2
𝑍1 = and 𝑍2 =
I1 I2
Now, the ratio of primary to secondary impedance becomes:
Z1 V I
= 1 × 2 = 𝐾 2 thus:
Z2 I1 V2
And also
R1 X1
= 𝐾2 and = 𝐾2
R2 X2
Shifting impedances in a transformer
• The following figure shows a transformer where resistances and reactances are
shown external to the windings before shifting or referring. However, to compute
transformer parameters in easily and simplified manner, the parameter should be
referred to one side of the core of the transformer.
𝑋2′ = 𝐾 2 × 𝑋2
𝑋𝑒𝑠 = 𝑋1 + 𝐾 2 × 𝑋2
𝑅𝑒𝑠 = 𝑅1 +𝐾 2 × 𝑅2
𝐼2 × 𝑋1′ 𝐼1 × 𝑋1
To the secondary referred × 100% = × 100%
𝑉2 𝑉1
𝑋1
𝑋1′ = 2
𝐾
𝑋2
𝑋𝑒𝑠 = 𝑋2 +𝐾2
𝑅
𝑅𝑒𝑠 = 𝑅2 +𝐾22
Fig 10:exact
traformer ckt
Exact equivalent circuit of the transformer …..
• Core loss components of the excitation current responsible for core loss (eddy-current and
hysteresis loss) of the transformer. Therefore, if 𝐸1 is the induced emf at the primary winding and
R c1 is the core loss resistance, the core loss current is given as:
E1
Ic =
R c1
• Similarly, the magnetizing components of the excitation current is responsible for the setup of
mutual flux in the core. Since the current carrying coil forms an inductor and the reactance is
magnetizing reactance Xm1 . Therefore, the magnetizing current is given as:
E1
Im =
jXm1
To make easy the calculation, the exact transformer can referred to primary or secondary side.
1
• Note: when referring to the primary side, the secondary impedance are multiplied by
K
when referring to the secondary the primary impedance are multiplied by K.
Exact equivalent circuit of the transformer …..
Equivalent circuit referred to primary:
If all the secondary quantities are referred to the primary, we get the equivalent
circuit of the transformer referred to the primary as in the figure below.
jK 2 jK 2
K2 K
K
2 K2 Fig 12: exact
K
K transformer referred
K
to secondary
Approximate equivalent circuit
• Approximate equivalent circuit referred to the • Approximate equivalent circuit referred to the
primary side of the transformer. secondary side of the transformer.
K
K
K K2 K2
K
Do this problem referred to the secondary side and sketch the circuit.
Examples …
• Example-2: A 15 KVA, 2300/230V transformer is to be tested to determine its excitation
components and its series impedance. The following test data have been taken from the
transformer : ____________________________________
open circuit test short circuit test
(low voltage side) (high voltage side)
𝑉𝑜𝑐 =230V 𝑉𝑠𝑐 =47V
𝐼𝑜𝑐 =2.1A 𝐼𝑠𝑐 =2.1A
𝑃𝑜𝑐 =50W 𝑃𝑠𝑐 =50W
________________________________________
(a) Find the approximate equivalent circuit of the transformer referred to the high-voltage side.
(b) Find the approximate equivalent circuit of this transformer referred to the low-voltage side.
(c) draw the approximate diagram and label the number.
Advantages of Transformer Tests
• Polarity test: This test used to determine the polarities of terminal of the transformer windings.
• Voltage ration test: it is used to determine the ratio of the primary and secondary winding
voltages.
• Open circuit of no load test: this test measures the power, voltage and current at the low voltage
side and these parameters are used to determine excitation resistance and excitation reactance
of the transformer.
• Short circuit test: this test is carried out at high voltage side and it measures power, voltage and
current. These measured values are used to determine:
▪ Copper loss and efficiency of the transformer
▪ equivalent impedance (𝑍𝑒𝑝 𝑜𝑟 𝑍𝑒𝑠 ) and which is used to determine equivalent resistance
and reactance.
• Back to Back test: This test is also called regenerative test or sumpner’s test and which is used
to determine the temperature rising of the transformer.
Losses in a Transformer
• The losses which occur in an actual transformer are:
▪ Iron losses or core loss
▪ Copper loss
• Core or iron losses: When AC supply is given to the primary winding of a transformer an alternating
flux is set up in the core, therefore, hysteresis and eddy current losses occur in the magnetic core.
▪ Hysteresis loss: the magnetic material subjected to reversal of magnetic flux and which creates a
reversal of molecular magnets. This effect consume electric power and dissipated in the form of
heat is called hysteresis loss. It is minimized using silicon steel to construct magnetic core.
▪ Eddy current loss: the power which carries the circulating (loop) current in the core and dissipated
in the form of heat is called eddy current loss. It is minimized by laminating of the core of the
transformer.
• Copper losses: Copper losses occur in both the primary and secondary windings due to their ohmic
resistance. If I 1, I2 are the primary and secondary currents and R1, R2 are the primary and
secondary resistances, respectively. Therefore the power loss due to this effect is:
Then, total copper losses = 𝐼12 𝑅1 + 𝐼22 𝑅2 = 𝐼12 𝑅𝑒𝑝 =𝐼22 𝑅𝑒𝑠