Professional Documents
Culture Documents
MUCLecture 2023 101739236
MUCLecture 2023 101739236
Page 1 of 14
1- Open Circuit and Short Circuit
Test on Transformer
The open circuit and short circuit test are performed for determining the
parameter of the transformer like their efficiency, voltage regulation,
circuit constant etc. These tests are performed without the actual loading
and because of this reason the very less power is required for the test.
The open circuit and the short circuit test gives a very accurate result as
compared to the full load test.
Contents:
Page 2 of 14
Circuit Diagram of Open Circuit Test on Transformer
The secondary winding of the transformer is kept open, and the
voltmeter is connected to their terminal. This voltmeter measures the
secondary induced voltage. As the secondary of the transformer is
open, thus no-load current flows through the primary winding.
The value of no-load current is very small as compared to the full rated
current. The copper loss occurs only on the primary winding of the
transformer because the secondary winding is open. The reading of the
wattmeter only represents the core and iron losses. The core loss of the
transformer is the same for all types of loads.
• W0 – wattmeter reading
• V1 – voltmeter reading
• I0 – ammeter reading
Working component Iw is
Page 3 of 14
Putting the value of W0 from the equation (1) in equation (2) you will get
the value of the working component as
Page 4 of 14
Magnetizing component is
Page 5 of 14
2.2: Short Circuit Test
The short circuit test is performed for determining the below mention
parameter of the transformer.
• It determines the copper loss occur on the full load. The copper loss
is used for finding the efficiency of the transformer.
• The equivalent resistance, impedance, and leakage reactance are
known by the short circuit test.
The low voltage source is applied across the secondary winding, which
is approximately 5 to 10% of the normal rated voltage. The flux is set up
Page 6 of 14
in the core of the transformer. The magnitude of the flux is small as
compared to the normal flux.
The iron loss of the transformer depends on the flux. It is less occur in
the short circuit test because of the low value of flux. The reading of the
wattmeter only determines the copper loss occurred, in their windings.
The voltmeter measures the voltage applied to their high voltage
winding. The secondary current induces in the transformer because of
the applied voltage.
• Wc – Wattmeter reading
• V2sc – voltmeter reading
• I2sc – ammeter reading
The phasor diagram of the short circuit test of the transformer is shown
below
Page 7 of 14
Phasor Diagram of Short Circuit Test
Answer: a
Explanation: The power measured while conducting the tests is the
winding losses and the core losses.
I. core losses
II. shunt branch parameters III. turns ratio of
transformer a) I, II, III
b) I, II
c) II, III
d) I, III
Answer: a
Explanation: OC test gives the shunt branch parameters as well as the
turns ratio by connecting a voltmeter at open circuited secondary
terminals.
I. core losses
II. Shunt branch parameters
III. Series parameters
a) I, II, III
b) I, II
c) II, III
d) I, III
Page 9 of 14
Answer: b
Explanation: Series parameters are obtained by short circuit test results.
Answer: a
Explanation: Core losses are found from OC test.
Answer: a
Explanation: All the estimations asked will need results of both the tests.
Answer: a
Explanation: OC test is performed on the l.v. side of the transformer
because the l.v. winding will have lower stress on the insulation and no
damage will occur.
Page 10 of 14
7. To conduct the short circuit test, test is conducted on the
___________ a) l.v. side
b) h.v. side
c) Primary
d) secondary
Answer: b
Explanation: To circulate the rated current in the winding, we should opt
for lower value of the current so that winding will not damage.
Answer: a
Explanation: Open circuit test is conducted on l.v. side, so the measuring
instruments will be on the h.v. side.
So the current in the h.v. side will be around 3-6% of the rated.
Answer: a
Explanation: Short circuit test is conducted on h.v. side, so the measuring
instruments will be on the l.v. side.
Rated current on the h.v. will be 10A and voltage will be around 5-12%
to account for winding losses.
Page 11 of 14
10. A single phase transformer of 2200/220 V having rated l.v.
current of 150 A has to undergo open circuit test on h.v side. The
instruments used are voltmeter of 200V and ammeter of 1A. Then
the results ___________ a) Will be wrong
b) Will be accurate
c) Of ammeter will burn
d) None of the mentioned
Answer: c
Explanation: The current in the h.v. winding will be around 10 A but the
ammeter is of 1 A rating. So, it will burn off.
Answer: a
Explanation: For conducting short circuit test, l.v. winding is short
circuited and it is not performed at rated voltage.
Page 12 of 14
d) A, C
Answer: a
Explanation: For conducting short circuit test, l.v. winding is short
circuited and it is not performed at rated voltage.
Answer: a
Explanation: The feature of the high impedance is extracted in the arc
welding applications.
Answer: d
Explanation: Leakage impedance is not found from open-circuit test.
Answer: a
Explanation: Leakage impedance is not found from open-circuit test. And
it is performed on the rated voltage to account for core losses.
16. Which of the following information are not obtained from short-
circuit test?
Answer: d
Explanation: Core losses are found from OC test and the voltage
regulation is not obtained from one single test here.
Page 14 of 14