Professional Documents
Culture Documents
Group 5 NSCP 2015 PDF
Group 5 NSCP 2015 PDF
Structural Code
of the
Philippines 2015
GROUP 5
C A L U S T E , K H AY L I E A N N
M E N E S E S, J OA N N A J E A N
T AY H O P O N, C H E R RY R O S E
What is the National Structural Code
of the Philippines?
The National Structural Code of the Philippines
(NSCP) is used by builders to ensure that structures, such
as high-rise condominiums, can withstand the tremors of
magnitude 7 to 8.4. Only buildings, towers, and other
vertical structures such as poles and billboards are covered
by the NSCP.
Live Loads
The maximum loads anticipated by the intended usage or
occupancy are to be used as live loads, but they must never be less than the
loads specified in this section.
Wind Loads
• Is used to refer to any
pressures or forces that the wind exerts
on a building or structure. There are
actually three types of wind forces that
would be exerted on a building.
• Types of Wind Loads:
- Uplift wind loads
Other minimum loads - Shear wind loads
- Lateral wind loads
Earthquake Loads
The following earthquake provisions are
specifically designed to protect against significant
structural damage that could result in loss of life or
property. These clauses aren't meant to guarantee that
buildings won't be damaged or that they'll keep
working after a major earthquake.
Soil Lateral Loads
The foundation, basement, and retaining walls must all be built to
withstand lateral soil loads. Unless stated otherwise in a soil investigation
report approved by the building official, soil loads shall be used as the
minimum design lateral soil loads. Basement walls and other walls with
limited horizontal movement at the top must be built to withstand at-rest
strain. Active pressure can be used on retaining walls that are free to shift
and rotate at the top. The lateral earth pressure load must be increased by
the design lateral pressure from surcharge loads. If the site contains soils
with expansion potential, the design lateral pressure must be increased.
Rain Loads
Roof drainage systems must meet the requirements of the local
code. Secondary (overflow) drains or scuppers must have a flow capacity
equal to or greater than the main drains or scuppers.
Flood Loads
All new construction of buildings, structures,
and parts of buildings and structures within flood
hazard areas shall be built and constructed to withstand
the effects of flood hazards and flood loads, including
significant improvement and repair of substantial
damage to buildings and structures. The provisions
associated with the most stringent flood hazard area
shall extend to buildings located in more than one flood
hazard area.
General Requirements
This chapter sets forth requirements
for excavation, fills, footings, and
foundations for any building or structure.
Chapter 3:
Earthquake and Foundations
Excavation And Fills
General
Excavation or fills for buildings or structures
shall be constructed or protected such that they do
not endanger life or property. Reference is made
to Section 109 of this code for requirements
governing excavation, grading and earthwork
construction, including fills and embankments.
Excavation And Fills
Protection of Adjoining Property
The following provisions shall apply unless prevailing local laws are deemed more stringent from an engineering
standpoint:
• Before commencing the excavation, the person making or causing the excavation to be made shall notify in
writing the owners of adjoining building not less than 10 days before such excavation is to be made and that
adjoining building shall be protected. The condition of the adjoining building shall be documented to include
photographs prior to excavation. Technical documents pertaining to the proposed underpinning and excavation
plan shall be provided the owner of the adjacent property.
Foundation Investigation
General
Foundation investigation shall be conducted and a Professional Report
shall be submitted at each building site. For structures two storeys or higher, an
exhaustive geotechnical study shall be performed to evaluate in- situ soil parameters
for foundation design and analysis.
Expansive Soils
Soil Test
Tables 303-2 and 303-3 summarize the commonly use field and laboratory
test needed in determining the in- situ soil parameters for design and analysis.
Loads
Self-weight, applied loads, and consequences
of prestressing, earthquakes, volume shift restriction,
and different settlement are all considered loads. Loads
and seismic zones must be defined in compliance with
the general building code, or by another body with
jurisdiction in areas where no building code has been
legally implemented.
Two-way Slabs Beams
Section 418.10.1 The precast concrete industry's use of
(corresponding to ACI 318M11, open web reinforcement for torsion and shear in
Section 18.9.1) states that all slender spandrel beams as an alternative to the
flexural members with unbonded closed stirrups historically required by this Code.
pre - stressing tendons must have a Closing stirrups is advantageous because they
minimum area of bonded cause reinforcement congestion; but, because
reinforcement. The minimum pre-tensioning strand must be threaded through
unbonded reinforcement over the the closed stirrups, production costs increase
tops of columns is designed to significantly.
spread cracking caused by high
local flexural tensile stresses in
areas of peak negative moments.
However, slabs with unbonded
tendons are not the only ones with
high local flexural tensile stresses.
Diaphragms Earthquake
Subsection 418.12 of the NSCP 2015 Resistance Structures
included design and detailing criteria for There are a number
diaphragms in structures assigned to high seismicity of significant and substantive
areas (Zone 4). A new Section 412 incorporated changes to this Section.
design guidelines for diaphragms in buildings
allocated to low seismicity areas for the first time With the confinement
(Zone 2) “To the configuration of non-prestressed pressure, the ability of the
and prestressed diaphragms, from (a) through (d): concrete core of a concrete
reinforced column to
(a.) Cast-in-place slabs for diaphragms. withstand compressive strains
(b.) Diaphragms made up of precast components tends to improve. Axial load
with a cast-in-place topping slab. causes compressive strains. To
(c) Diaphragms made up of precast components ensure consistent lateral
with end strips made up of cast-in-place concrete deformation capability,
topping slabs or edge beams. confinement reinforcement
(d) Diaphragms made up of interconnected precast should be increased with axial
elements with no concrete topping cast in place. load.
Reinforcement Details
Mechanical or welded splices with strengths less than 125 percent of the
spliced reinforcing bars' yield strength are no longer allowed. The stagger conditions
that were associated with it have been removed. As a result, "complete" mechanical
or "full" welded splices are no longer needed.
Particleboard vertical diaphragms and lumber and wood structural panel horizontal and
vertical diaphragms can be used to resist horizontal forces in horizontal and vertical distributing or
resisting elements, provided the deflection in the plane of the diaphragms does not exceed the
allowable deflection of attached distributing or resisting elements, as calculated by measurements,
tests, or analogies drawn therefrom.
• General
- General Requirement
- Responsibility Of Designer To Adjust For
Conditions Of Use
Design Values for • Reference Design Values
Structural Members • Adjustment Of Reference Design Values
- Applicability Of Adjustment Factors
- Load Duration Factor
- Temperature Factor
- Fire Retardant Treatment
What is masonry?
Masonry is an individual unit of
maybe stone or brick attached by one
another with the use of mortar.
Scope
The materials, design, construction
and quality assurance of masonry shall be in
accordance with this chapter.
Mortar and Grout
Chapter 7: The mortar is used as an adhesive material,
Masonry while the grout is utilized to fill gaps in tiles or
masonry.
Selecting Portions
AGGREGA TYPE PARTS BY PARTS BY AGGREGATE MEASURED
PROPORTIONS BY VOLUME (CEMENTITIOUS TE
MATERIALS) MEASURE VOLUME VOLUMEOF IN A DAMP,
D IN OF HYDRATED LOOSE CONDITION
PORTLAN MASONRY MORTAR CEMENT HYDRATE DAMP,
D CEMENT D LIME PORTLAND LIME OR
MORTAR TYPE LOOSE
CEMENT OR LIME CONDITI CEMENT LIME FINE COARSE
OR PUTTY ON OR PUTTY
M S N M S N
BLENDED
CEMENT BLENDED
CEMENT
M 1 - - - - - - 1/4 Fine 1 0 to 1/10 2 1/4 to 3
Cement S 1 - - - - - - OVER 1/4 TO 1/2 Grout times the sum
Lime N 1 - - - - - -
OVER 1/2 TO 1 1/4 Not less of the volumes
than 2 of the
O 1 - - - - - - OVER 1 1/4 TO 2
1/2
1/4 and cementitious
not more
M 1 - - - - - 1 materials
than 3
Mortar M - - - - 1 - - Course 1 0 to 1/10 2 1/4 to 3 1 to 2 times
times the
Cement Grout times the sum sum of the
S 1/2 - - - - - 1 sum of
S - - - - - 1 - the of the volumes volumes of the
separate of the cementitious
N - - - - - - 1
volumes cementitious materials
M 1 - - 1 - - -
of materials
Masonry M - 1 - - - - - cementiti
Cement Table 703-2 Grout Proportions by Volume
ous
S 1/2 - - 1 - - - materials
S - - 1 - - - -
N - - - 1 - - -
O - - - 1 - - -
Multi-wythe Hollow-Unit
Masonry Masonry
Fine .30 20 35x50
Fine 1.50 35 35x50
Fine 2.40 35 35x50
Fine 3.60 35 45x75
Fine 7.20 50 75x75
Coarse .30 35 35x75
Coarse 1.50 50 65x75
Grout Masonry Coarse 2.40 50 75x75
Coarse 3.60 60 75x75
Coarse 7.20 75 75x100
Table 704-1 grouting Limitations
Allowable Stress (Asd) Of Masonary
707.1.5.2 Tension
EMBEDMENT LENGTH, lb, or EDGE DISTANCE, lbe (mm)
f1m(MP 50 75 100 125 150 200 250
a)
10.3 1.10 2.45 4.32 6.76 9.74 17.3 27.0
12.4 1.20 2.67 4.76 7.43 10.7 18.9 29.6
13.8 1.25 2.80 4.98 7.83 11.2 20.0 31.2
17.2 1.38 3.16 5.61 8.72 12.6 22.4 34.9
20.7 1.50 3.43 6.14 9.57 13.8 24.5 38.3
27.6 1.78 3.96 7.08 11.04 15.9 28.3 44.2
707.1.4 Embedded Anchor Bolts 34.4 1.96 4.45 7.92 12.43 17.8 31.6 49.4
41.3 2.15 4.85 8.68 13.53 19.5 34.7 54.3
Table 707-1 Allowable Tension Bt, for embedded Anchor Bolts for Clay and
Concrete Masonry. kN1,2,3
ANCHOR BOLT DIAMETER (mm) ANCHOR BOLT DIAMETER (mm)
6 10 12 16 20 22 25 28 f1m(MPa 10 12 16 20 22 25 28
1.56 3.51 6.27 9.83 14.1 19.3 25.9 31.9 )
Table 707-2 Allowable Tension Bt, for embedded Anchor Bolts for Clay and 10.3 2.14 3.78 5.92 7.92 8.45 9.12 9.7
Concrete Masonry. kN1,2, 12.4 2.14 3.78 5.92 8.28 9.35 9.57 10.1
13.8 2.14 3.78 5.92 8.45 9.17 9.79 10.4
17.2 2.14 3.78 5.92 8.45 9.70 10.4 11.0
20.7 2.14 3.78 5.92 8.45 10.1 10.9 11.5
27.6 2.14 3.78 5.92 8.45 10.9 11.7 12.4
34.4 2.14 3.78 5.92 8.45 11.5 12.3 13.1
41.3 2.14 3.78 5.92 8.45 11.6 12.9 13.7
707.1.5.3 Shear
Thank You!