HAZOP Worksheet For Gas Metering (Typical)
HAZOP Worksheet For Gas Metering (Typical)
1 of 2
Node: 2. AZ5112-FMS-001 GAS EXPORT METERING SKID
Unmitigated Risk
Ranking (assuming no
safeguards) O
ve
O Overall Risk
ra
v Ranking
ll
er (considering
Mi
al recommendat
ti
l ions
Deviation Cause Consequence Current Safeguards L ga Recommendation Responsibility Comments
P E A R S implementati
te
e on)
d
v
Ri
er
sk
it
(R
y
)
R
S S S S S S L
R
BV-60010 with a potential to
cause loss of containment causing
fire/ explosion - fatalities/ asset
damage/ environmental impacts.
2.1.2. Inadvertant closure of MOV- 2.1.2.3. Compressor blocked outlet (Three 5 2 4 3 5 2. Individual Compressor B H- 6. Consider providing Vendor/ Contractor 5 A M
6201/ MOV-6202 trains - 356MMSCFD) resulting in discharge PAHH - M permissive on MOV-6201/
Compressor damage/ over 0027A/B/C trips respective 6202 such that these
pressurization up to BV-60001/ Compressor. valves cannot be closed
BV-60010 with a potential to when MOV-6211/ 6212 are
cause loss of containment causing in closed position.
fire/ explosion - fatalities/ asset
damage/ environmental impacts.