Professional Documents
Culture Documents
EWP Code of Practice - Stairs
EWP Code of Practice - Stairs
should be designed for a minimum uniform load of (Gstair) and imposed (Qstair) point loads to be applied to the
0.22kN/m2. floor at the stair stringer positions should be determined in
accordance with the following:
The minimum partition load given above of 0.64kN/m is Gstair = (Ws x Ls)/4 x 0.41 kN …(3.1)
applicable for partitions weighing up to 27kg/m2. This load Qstair = (Ws x Ls)/4 x 1.50 kN …(3.2)
is adequate for standard timber stud partitions of 2.4m where
height comprising 38x89mm C24 wall studs at 400mm Ws is the width of the stairs
spacing with mid-height noggings and plasterboard Ls is the horizontal (plan) length of the stairs
weighing up to 10kg/m2 on each face and 75mm quilt
insulation with a density of 10kg/m3. The load is also Ws should be measured from the building drawings.
adequate for some typical proprietary metal stud partition Ls should be measured from the building drawings, and
systems. Enhanced partitions with multi-layers of should be measured as the horizontal distance from the
plasterboard and some proprietary metal stud partitions trimmer to the bottom riser as shown in Figure 3.1.
exceed this weight and in these cases the actual partition Alternatively and for simplicity, the distances Ws and Ls
weights should be calculated and used in design. may be taken as the width (Wo) and length (Lo) of the stair
opening respectively.
Note that the loads presented above are minimum loads.
Where an EWP floor system provider already adopts loads
that exceed the above minima, there is no requirement to
adopt the minimum values.
3.4.5.1 Principles
i. Wherever stairs are fixed to EWP floors the dead and Figure 3.1 Definition of Stair Width and Length.
imposed load from the stairs shall be applied to the
floor; Loads from Non-Straight Flights of Stairs
ii. The load shall be applied irrespective of whether the Where stairs are not straight flights then the load applied
top or bottom of the staircase is fixed to the floor; to the floor will not be relative to the overall stair length
iii. The applied load shall not be reduced due to the nor to the size of the stair opening. To accurately
presence of non-load bearing partitions below the determine the loads it is necessary to consider the stair
staircase; arrangement.
iv. The applied load shall not be reduced by virtue of the
stair stringer being fixed to a parallel and adjacent wall, For non-straight flights of domestic stairs the vertical dead
except where there is written confirmation from the (Gstair) and imposed (Qstair) point loads to be applied to the
Building Designer that both the wall and the method of floor at the stair stringer positions should be determined in
fixing the stringer to the wall are capable of sustaining accordance with the following:
the design load on the stairs. Gstair, i = (Ws x Lsi)/4 x 0.41 kN …(3.3)
Qstair, i = (Ws x Lsi)/4 x 1.50 kN …(3.4)
3.4.5.2 Detailed Requirements where
Basic Load Ws is the width of the stairs
i. For single occupancy domestic floors the dead load Lsi is variously the length of the stairs measured
from the stairs should be taken as a minimum of from the top to the landing/newel/winder, e.g.
0.41kN/m2 unless there is information to suggest that a Gstair, 1 = (Ws x Ls1)/4 x 0.41
higher load should be used; Gstair, 2 = (Ws x Ls2)/4 x 0.41
ii. For single occupancy domestic floors the imposed Qstair, 1 = (Ws x Ls1)/4 x 1.50
load should be 1.5kN/m2. For communal stairs in Qstair, 2 = (Ws x Ls2)/4 x 1.50
residential buildings and all other building uses refer to as shown in Figure 3.2.
BS 6399-1 or BS EN 1991-1-1 for the imposed load and
refer to the Building Designer for the dead load.