HV/LV three phase distribution transformers

LEBANON - Reduced Losses

From 100 to 400kVA


Insulation level ≤ 24kV

General description Fittings


This range of transformers satisfies the requirements of IEC Each transformer is equipped with :
publications 60076 and 60354, together with the • 1 x five positions regulating off-circuit tap changer
specifications of EDL. The transformers comply with the • 1 x coupling off-circuit changer
following specifications: • 3 x HV porcelain bushings according to DIN 42531 with
• Outdoor installation arcing horns
• Maximum ambient temperature : 40°C • 4 x LV porcelain bushings according to DIN 42530
• Top oil temperature rise : 60°C • 2 x lifting and untanking lugs, provided each with an
• Average winding temperature rise : 65°C earthling terminal
• Cooling is implemented with natural circulation (ONAN) of • 1 x rating plate
mineral oil and air • 1 x thermometer with maxima indicator
• Hermetically sealed, totally filled • 1 x oil draining valve 3/4"
• Cover bolted on corrugated tank • 1 x pressure relief device 0.3 bar
• Color : Gray RAL 7033 • 4 x bidirectional rollers Ø=125mm
Other requirements can be provided upon request. Other fittings can be provided upon request, consult us.

ELECTRICAL CHARACTERISTICS
Rated Power (kVA) 100 160 250 400 - - - 400
Rated Voltage (kV/V) Dual primary 20-15kV/410V Dual primary 20-11kV/410V
Secondary voltage is at no-load.
High Voltage Insulation Level (kV) 24
Tappings (%) For 20kV: ±5.25 ±2.625 For 20kV: ±3.85 ±1.925
For 15kV: ±7 ±3.5 For 11kV: ±7 ±3.5
Vector Group Yzn11 Dyn11 Dyn11
(Wye; Zigzag with (Delta; Star with - (Delta; Star with
Neutral brought Neutral brought Neutral brought
out) out) out)
Frequency (Hz) 50
Impedance voltage at 75°C (%) 4 4 4 4 4
Losses (W) No-Load 210 235 315 480 470
Load (75°C) 1350 2095 2300 3100 3160
Voltage Drop at Full load(%) cosØ=1 1.36 1.32 0.92 0.78 0.79
cosØ=0.8 3.35 3.32 3.08 2.99 3
Efficiency at Full load cosØ=1 98.46 98.56 98.96 99.11 99.1
cosØ=0.8 98.09 98.21 98.71 98.89 98.88
Efficiency at 75% load cosØ=1 98.72 98.83 99.15 99.26 99.26
cosØ=0.8 98.41 98.55 98.94 99.08 99.07
The values in the table above are given for 20kV.
The losses and the impedance voltage are subject to IEC 60076 tolerances.
Other ratings, losses and impedance voltages can be provided upon request.

MATELEC GROUP
Head Office
Ghorfine - Amchit - P.O.Box: 12 Jbeil - Lebanon
Tel: (961) 9 620 920 - Fax: (961) 9 620 934 / 5
E-mail: matelec@matelecgroup.com
www.matelecgroup.com
HV/LV three phase distribution transformers
LEBANON - Reduced Losses

From 100 to 400kVA


Insulation level ≤ 24kV
8 7 3 5 6 4 11
E E

1
A
B

10
9

G G
12

Nº DESCRIPTION
C 1 Corrugated refrigeration panels
2 Rating plate
3 HV porcelain bushings
4 LV porcelain bushings
C B A
5 Regulating tap changer
6 Coupling changer
D

F F F
7 Thermometer with maxima indicator
n c b a 8 Lifting lugs
9 earthling terminals (cover and tank)
10 Oil draining valve 3/4"
11 Pressure relief device 0.3 bar
12 Bidirectional rollers

APPROXIMATE WEIGHT AND OVERALL DIMENSIONS


Power LV HV Height Cover Length Width Oil Total
Bushing Bushing Height Weight Weight
-A- -B- -C- -D- -E- -F- -G-
kVA mm mm mm mm mm mm mm Kg Kg
100 1/250 20/250
1325 940 960 750 270 130 520 135 665
15-20kV (item 12) (item 21)
160 1/250 20/250
1335 950 1170 900 270 130 520 210 1050
15-20kV (item 12) (item 21)
250 1/630 20/250
1425 1040 1140 875 270 140 520 190 1145
15-20kV (item 13) (item 21)
400 1/630 20/250
1530 1145 1260 945 270 140 670 260 1610
15-20kV (item 13) (item 21)
400 1/630 20/250
1520 1135 1245 910 270 140 670 235 1540
11-20kV (item 13) (item 21)
For bushings and cable boxes items, refer to tables 2 and 3 in our general transformers catalogue.

The values contained in this document can be changed without prior notice. Ref. PDS LEB 03 - 08/06
Exact values will be supplied upon order confirmation. All rights reserved, Matelec Group, 2006.