Prüfbericht - Produkte

Test Report - Products

Prüfbericht-Nr.: 19617564 001 Auftrags-Nr.: 166505131 Seite 1 von 19


Test report no.: Order no.: Page 1 of 19

Kunden-Referenz-Nr.: 2027764 Auftragsdatum: 2020-12-07


Client reference no.: Order date:

RR Kabel Limited
Auftraggeber: RS 201, 202/1, 202/2, 203 & 327
Client: Khanda road, At & Po. Village Waghodia
Taluka-Waghodia, Vadodara 391760, India
Prüfgegenstand: Power cables with extruded insulation and their accessories for rated voltages from 1
Test item: kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV)

Bezeichnung / Typ-Nr.: 2020 RR KABEL 1C X 400 SQ.MM 6/10 KV 2X2Y ELECTRIC CABLE REACH
Identification / Type no.: RoHS CE +0001m
Auftrags-Inhalt: Issue of test report
Order content:
Prüfgrundlage: As per Guaranted technical particular (see other), customer's requirement, and
Test specification:
IEC 60502-2:2014 Power cables with extruded insulation and their accessories for
rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV)
Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)
Wareneingangsdatum: 2021-01-24
Date of sample receipt:
Prüfmuster-Nr.: Engineering sample
Test sample no:
Prüfzeitraum: 2021-01-24 - 2021-06-28
Testing period:
Ort der Prüfung: Same as client
Place of testing:
Prüflaboratorium: TÜV Rheinland (India) Pvt.
Testing laboratory: Ltd.
Prüfergebnis*:
Pass
Test result*:

geprüft von: genehmigt von:


tested by: 2021.09.0 authorized by: 2021.09.0
Datum: 09:14:47 2 Ausstellungsdatum:
3 10:36:38
+05'30'
Date: '30'05+ Issue date:
Stellung / Position: Sr. Engineer Stellung / Position: Sr. Manager
Sonstiges / Other: Please refer Guaranted technical particular Doc. No: RRKL W/GTP/2019/0963 Revision
03 (30/01/2021) on page no. 17.

Zustand des Prüfgegenstandes bei Anlieferung: Prüfmuster vollständig und unbeschädigt


Condition of the test item at delivery: Test item complete and undamaged
* Legende: 1 = sehr gut 2 = gut 3 = befriedigend 4 = ausreichend 5 = mangelhaft
P(ass) = entspricht o.g. Prüfgrundlage(n) F(ail) = entspricht nicht o.g. Prüfgrundlage(n) N/A = nicht anwendbar N/T = nicht getestet
* Legend: 1 = very good 2 = good 3 = satisfactory 4 = sufficient 5 = poor
P(ass) = passed a.m. test specification(s) F(ail) = failed a.m. test specification(s) N/A = not applicable N/T = not tested

Dieser Prüfbericht bezieht sich nur auf das o.g. Prüfmuster und darf ohne Genehmigung der Prüfstelle nicht
auszugsweise vervielfältigt werden. Dieser Bericht berechtigt nicht zur Verwendung eines Prüfzeichens.
This test report only relates to the a. m. test sample. Without permission of the test center this test report is not permitted to be
duplicated in extracts. This test report does not entitle to carry any test mark.
TÜV Rheinland (India) Pvt. Ltd. # 27/B, 2nd Cross Road, Electronics City Phase 1, Bangalore – 560 100, INDIA.
Mail: info@ind.tuv.com ∙ Web: www.ind.tuv.com
Report No.:19617564 001 Page 2 of 19

TEST REPORT
IEC 60502-2
Power cables with extruded insulation and their accessories for rated
voltages from 1kV(Um=1,2kV) up to 30kV(Um=36kV)
Part 2: cables for rated voltages from 6kV(Um=7,2kV) up to
30kV(Um=36kV)

Report Number. .............................. : 19617564 001


Date of issue ................................... : 02.09.2021
Total number of pages ................... 19

Name of Testing Laboratory


preparing the Report...................... : TÜV Rheinland (India) Pvt. Ltd.
Applicant’s name ........................... : RR Kabel Limited
Address ........................................... : RS 201, 202/1, 202/2, 203 & 327
Khanda road, At & Po. Village Waghodia
Taluka-Waghodia, Vadodara 391760, India
Test specification:
Standard .......................................... : IEC 60502-2:2014
Test procedure ............................... : Issue of test report
Non-standard test method ............ : N/A
Test Report Form No. .................... : IEC60502_2_TUVR
Test Report Form(s) Originator .... : TÜV Rheinland (India) Pvt. Ltd.
Master TRF...................................... : 2021.07.15

General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing Testing
Laboratory.
Report No.:19617564 001 Page 3 of 19

Test item description ....................... : Power cables with extruded insulation and their accessories for
rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV)
Trade Mark ........................................ : RR KABEL
Manufacturer ..................................... : RR Kabel Limited
Model/Type reference....................... : 2020 RR KABEL 1C X 400 SQ.MM 6/10 KV 2X2Y ELECTRIC
CABLE REACH RoHS CE +0001m
Ratings............................................... : 6/10 kV (Um=12kV)

Summary of testing: This report is relates only to the particular sample 2020 RR KABEL 1C X 400
SQ.MM 6/10 KV 2X2Y ELECTRIC CABLE REACH RoHS CE +0001m received for testing from customer
with length 593m.
Tests performed (name of test and test Testing location:
clause): RR Kabel Limited
18 Type tests, electrical RS 201, 202/1, 202/2, 203 & 327
19 Type tests, non-electrical Khanda road, At & Po. Village Waghodia
Taluka-Waghodia, Vadodara 391760, India

Copy of marking plate:

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 4 of 19

IEC 60502-2
Clause Requirement + Test Result - Remark Verdict

5 Conductors
—material Copper P
Copper, aluminium or aluminium alloy
Plain or metal coated
—shape Class 2 circular compacted P
Circular or shaped
6 Insulation
—material XLPE P
PVC/B,EPR,HEPR or XLPE
7 Screening
7.2 Conductor screen
—material Extruded semi-conducting P
extruded semi-conducting compound, or extruded compound
semi-conducting compound applied on semi-
conducting tape
7.3 Insulation screen
—type Extruded semi-conducting P
semi-conducting layer in combination with a metal compound in a combination
layer with a metal layer
—material Strippable semi-conducting P
semi-conducting compound or tape compound with a layer of non-
woven water blocking tape
with copper wire + copper
tape in open helix applied
over individual cores
8 Assembly of three-core cables, inner covering and fillers
8.2 Inner covering and fillers
—type: extruded or lapped Extruded P
—material PVC-ST2 P
8.3 Cable having a collective metal layer No such element used N/A
(See Clause 9)
8.4 Cable having a metal layer over each individual No such element used N/A
core (See Clause 10)
9 Metal layer for single-core and three-core cables
—type No such element used N/A
metal screen, concentric conductor, metal sheath,
metal armour
10 Metal screen
Collective metal layer

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 5 of 19

IEC 60502-2
Clause Requirement + Test Result - Remark Verdict

—type No such element used N/A


—material No such element used N/A
Individual metal layer
—type No such element used N/A
—material No such element used N/A
11 Concentric conductor
—type No such element used N/A
—material No such element used N/A
12 Metal sheath
—material No such element used N/A
Lead, lead alloy
13 Metal armour
—types No such element used N/A
Flat wire, round wire or double tape
—wire material No such element used N/A
galvanized steel, copper or tinned
copper ,aluminium or aluminium alloy
Steel, galvanized steel, aluminium or aluminium
alloy
—tape material No such element used N/A
Steel, galvanized steel, aluminium or aluminium
alloy
13.3 Separation sheath
—material No such element used N/A
13.3.4 Lapped bedding under armour for lead sheathed cables
—material No such element used N/A
impregnated and compounded paper tapes or a
combination of two layer of impregnated and
compounded paper tapes followed by one or more
layers of compounded fibrous material
14 Oversheath
—material: ST1,ST2,ST3,ST7 or SE1 ST7 P

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 6 of 19

IEC 60502-2
Clause Requirement + Test Result - Remark Verdict

Insulation identification Single core —

18 Type tests, electrical


18.2 Cables having conductor screens and insulation screens
18.2.4 Bending test
Treatment
—number of cycles : 3 —
—diameter of mandrel (m) : 1.50 —
18.2.5 Partial discharge test
Sensitivity: 5pC or better 5pC or better —
Partial discharge test at 1,73 U0 No detectable discharge P
no detectable discharge exceeding the declared observed
sensitivity
18.2.6 Tan δmeasurement for cables of rated voltage 6/10(12)kV and above
Treatment
—temperature (C) : 95~100 —
—test voltage (kV) : 2 —
Results to be obtained: max. 7.4X10-4 P
18.2.7 Heating cycle test
Treatment
—temperature(C) : 95°C —
—heating duration and heating cycles The sample was subjected to —
The duration of the heating cycle at least 8h. The 20 heating cycles
conductor maintained within the state temperature
limits for at least 2h of each heating period and
followed by at least 3h of natural cooling.
The sample subjected to 20 heating cycles.
Followed partial discharge test at 1,73 U0 No detectable discharge P
no detectable discharge exceeding the declared observed
sensitivity
18.2.8 Impulse test followed by a voltage test
Treatment
—temperature(C) : 95~100 —
—impulse voltage,10 positive and 10 negative (kV) 75 kV —
Results to be obtained: No breakdown No breakdown P
Followed voltage test
—power frequency voltage(kV) : 21 kV —

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 7 of 19

IEC 60502-2
Clause Requirement + Test Result - Remark Verdict

—duration (min) : 15 minutes —


Results to be obtained: No breakdown No breakdown P
18.2.9 Voltage test for 4h
—power frequency voltage(kV) : 24 kV —
Results to be obtained: No breakdown No breakdown P
18.2.10 Resistivity of semi-conducting screens
—test temperature (C) : 90±2 —
For unaged samples
Conductor screen resistivity max.1000 Ω•m 1.30 P
Insulation screen resistivity max.500 Ω•m 3.82 P
For samples after additional ageing on pieces of completed cable
Treatment
—temperature(C) : 100 —
—duration(h) : 168 —
Conductor screen resistivity max.1000 Ω•m 1.56 P
Insulation screen resistivity max.500 Ω•m 5.15 P

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 8 of 19

IEC 60502-2
Clause Requirement + Test Result - Remark Verdict

18.3 Cables of rated voltage 3,6/6 (7,2)kV having unscreened insulation


18.3.2 Insulation resistance constant Ki Not applicable N/A
—at 20℃ min. M.km
18.3.3 Insulation resistance constant Ki Not applicable N/A
—at maximum conductor temperature in normal
operation ℃ min. M.km
18.3.4 Voltage test for 4h
—power frequency voltage (kV) : Not applicable —
Results to be obtained: No breakdown Not applicable N/A
18.3.5 Impulse test
—temperature (C) : Not applicable —
—impulse voltage,10 positive and 10 negative (kV): Not applicable —
Results to be obtained: No breakdown Not applicable N/A

Insulation identification Single core —

19 Type tests, non-electrical


19.2 Measurement of thickness of insulation
—average thickness: mm 3.9 —
—minimum thickness (tmin): min. 2.96 mm 3.70 P
—(tmax-tmin) / tmax : max.0.15 0.06 P
19.3 Measurement of thickness of non-metal sheaths (including extruded
separation sheaths, but excluding inner coverings)
Separation sheath
—average thickness: mm 0.6 —
—minimum thickness: min. 0.3 mm 0.51 P
Oversheath
—average thickness: mm 3.8 —
—minimum thickness: min. 1.72 mm 3.39 P
19.4 Measurement of thickness of lead sheath
—average thickness: mm Not applicable N/A
—minimum thickness: min. mm Not applicable N/A

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 9 of 19

IEC 60502-2
Clause Requirement + Test Result - Remark Verdict

19.5 Tests for determining the mechanical properties of insulation before and after
ageing
Without ageing
TS: min.12.5 N/mm2 16.24 P
EB: min. 200 % 406.6 P
After ageing in air oven
Treatment
—temperature(C) : 135±3 —
—duration(h) : 168 —
TS: min. N/mm 2 - N/A
EB: min. % - N/A
Variation
TS: max. ±25 % 15.7 P
EB: max. ±25 % 16.7 P
19.6 Tests for determining the mechanical properties of non-metal sheaths before
and after ageing
Without ageing Over sheath (PE-ST7)
TS: min. 12.5 N/mm2 29.88 P
EB: min. 300 % 826.6 P
After ageing in an air oven
Treatment

—temperature(C) : 110±2 —
—duration(h) : 240 —

TS: min. N/mm 2 - N/A


EB: min. 300 % 802.8 P
Variation
TS: max. % - N/A
EB: max. % - N/A
19.7 Additional ageing test on pieces of completed cables
Treatment
—temperature(C) : 100±2 —
—duration(h) : 168 —
Variation of insulation
TS: max. ±25 % 15.2 P
EB: max. ±25 % 6.5 P

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 10 of 19

IEC 60502-2
Clause Requirement + Test Result - Remark Verdict

Variation of sheath Over sheath (PE-ST7) —


TS: max. % - N/A
EB: max. % - N/A
19.8 Loss of mass test on PVC sheaths of type ST2
Treatment
—temperature(C) : 100 —
—duration(h) : 168 —
Sheath Over sheath (PE-ST7) —
Maximum loss of mass: max.1,5 mg/cm 2 Not applicable N/A
19.9 Pressure test at high temperature on insulations and non-metal sheaths
Insulation
Treatment
—temperature (C) : Not applicable —
—force (N) : Not applicable —
—duration (h) : Not applicable —
Indentation : max.50 % Not applicable N/A
Sheath Over sheath (PE-ST7)
Treatment
—temperature (C) : 110±2 —
—force (N) : 12.3 —
—duration (h) : 6 —
Indentation : max.50 % 5.87 P
19.10 Test on PVC insulation and sheaths at low temperature
Insulation
Cold bending test
Treatment
—temperature(C) : -5 —
—cooling time (h) : Not applicable —
—number of turns : Not applicable —
—diameter of mandrel (mm) : Not applicable —
Results to be obtained: No cracks Not applicable N/A

Cold elongation test


Treatment

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 11 of 19

IEC 60502-2
Clause Requirement + Test Result - Remark Verdict

—temperature(C) : -5 —
—cooling time (h) : Not applicable —
Elongation at break : min.20 % Not applicable N/A
Sheath
Cold bending test
Treatment
—temperature(C) : -15 —
—cooling time (h) : Not applicable —
—number of turns : Not applicable —
—diameter of mandrel (mm) : Not applicable —
Results to be obtained: No cracks Not applicable N/A
Cold elongation test Over sheath (PE-ST7)

Treatment
—temperature(C) : Not applicable —
—cooling time (h) : Not applicable —
Elongation at break: min. 20 % Not applicable N/A
Cold impact test
Treatment
—temperature(C) : Not applicable —
—cooling time (h) : Not applicable —
—mass of hammer (g) : Not applicable —
Result to be obtained: No cracks Not applicable N/A
19.11 Test for resistance of PVC insulation and sheaths to cracking
Insulation
Treatment
—temperature(C) : 150 —
—duration(h) : 1 —
—Number of turns : Not applicable —
—Diameter of mandrel (mm) : Not applicable —
Results to be obtained: No cracks Not applicable N/A
Sheath Over sheath (PE-ST7)
Treatment
—temperature(C) : 150 —

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 12 of 19

IEC 60502-2
Clause Requirement + Test Result - Remark Verdict

—duration(h) : 1 —
—Number of turns : Not applicable —
—Diameter of mandrel(mm) : Not applicable —
Results to be obtained: No cracks Not applicable N/A
19.12 Ozone resistance test for EPR and HEPR insulations
Treatment
—ozone concentration (%) : 0,025 to 0,030 —
—temperature(C) : 25 —
—duration(h) : 24 —
Result to be obtained: No cracks Not applicable N/A
19.13 Hot set test for EPR,HEPR and XLPE insulations and elastomeric sheaths
Insulation
Treatment
—temperature(C) : 200±3 —
—time under load (min) : 15 —
—mechanical stress (N/cm2) : 20 —
Elongation under load: max. 175 % 37 P
Permanent elongation after cooling: max.15 % 0.6 P
Sheath
Treatment
—temperature(C) : Not applicable —
—time under load (min) : 15 —
—mechanical stress (N/cm2) : 20 —
Elongation under load: max. 175 % Not applicable N/A
Permanent elongation after cooling: max.15 % Not applicable N/A
19.14 Oil immersion test for elastomeric sheaths
Treatment
—oil temperature(C) : 100 —
—duration(h) : 24 —
Variation
TS: max. ±40% Not applicable N/A
EB: max. ±40% Not applicable N/A
19.15 Water absorption test on insulation
PVC ( Electrical method )

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 13 of 19

IEC 60502-2
Clause Requirement + Test Result - Remark Verdict

Treatment
—temperature(C) : 70 —
—duration(h) : 240 —
—voltage(V) : Not applicable —
Results to be obtained: No breakdown Not applicable N/A
EPR,HEPR,XLPE( Gravimetric method )
Treatment
—temperature(C) : 85±2 —
—duration(h) : 336 —
Increase of mass: max. 1 mg/cm2 0.03 P
19.16 Flame spread test on single cables
—flame applied time (s) : Not applicable —
The distance between the lower edge of the top Not applicable N/A
support and the onset of charring:
great than 50 mm
Charring extends downwards to a point from the Not applicable N/A
lower edge of the top support:
not great than 540 mm
19.17 Measurement of carbon black content of black PE oversheaths
Carbon black content: 2.5±0.5% 2.67 P
19.18 Shrinkage test for XLPE insulation
Treatment
—temperature(C) : 130±3 —
—duration(h) : 1 —
Shrinkage: max. 4 % 0.36 P
19.19 Thermal stability test for PVC insulation
—temperature(C) : 200  0,5 C —
—minimum time: min.100min Not applicable N/A
19.20 Determination of hardness of HEPR insulation
IRHD: min. 80 Not applicable N/A
19.21 Determination of elastic modulus of HEPR insulation
Modulus at 150% elongation: min.4.5 N/mm 2 Not applicable N/A
19.22 Shrinkage test for PE sheaths
Treatment
—temperature(C) : 80±2 —
—duration(h) : 5 —

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 14 of 19

IEC 60502-2
Clause Requirement + Test Result - Remark Verdict

—cycles : 5 —
Shrinkage: max. 3 % 1.00 P
19.23 Strippability test for insulation screen (when the manufacturer claims that the
extruded semiconducting insulation screen is strippable)
For unaged samples
The stripping force value: 4~45 N Not less than 4 N and not P
more than 45 N
The insulation surface: No damage and No trace of P
Not damaged and no trace of the semiconducting semiconducting screen
screen remain on the insulation observed
For additional ageing samples
Treatment
—temperature(C) : 100±2 —
—duration(h) : 168 —
The stripping force value: 4~45 N Not less than 4 N and not P
more than 45 N
The insulation surface: No damage and No trace of P
Not damaged and no trace of the semiconducting semiconducting screen
screen remain on the insulation observed
19.24 Water penetration test (when the manufacturer claims that barriers to
longitudinal water penetration have been included)
—barrier —
prevent longitudinal water penetration in the region
of the metal layers or along the conductor
—water head (m) : 1 —
—temperature(C) : 95~100 —
—heating duration and heating cycles Total 10 heating cycles carried —
The duration of the heating cycle at least 8h. The out
conductor maintained within the state temperature
limits for at least 2h of each heating period and
followed by at least 3h of natural cooling.
The sample subjected to 10 heating cycles.
Results to be obtained : No water emerge from the P
During the period of testing no water emerge from end of the test piece observed
the ends of the test piece.

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 15 of 19

List of test equipment used:

Clause Measurement / Testing / measuring Range used Last Calibration


testing equipment / material Calibration due date
used, (Equipment ID) date

18.1 Type tests, Series Resonance Test 0-250kV AC 22.02.2021 22.02.2022


electrical System (EHV LAB-1)
PD Calibrator (EHV LAB-2) 4pC to 400pC 22.02.2021 22.02.2022

Impulse Voltage Test 0-9005kp 22.02.2021 22.02.2022


System (EHV LAB-3) 0-1000Vp

Test Transformer (EHV LAB- 0-250kV AC 22.02.2021 22.02.2022


4)
Standard Capacitor (EHV 100pF & 200kV 22.02.2021 22.02.2022
LAB-7)
19.2 Measurement of Profile Projector (LAB-7-C) 5,6,8,10 & 12 mm 22.09.2020 21.09.2021
thickness of
insulation
19.3 Measurement of Profile Projector (LAB-7-C) 5,6,8,10 & 12 mm 22.09.2020 21.09.2021
thickness of non-
metallic sheaths
19.5 Tests for Tensile Tester (LAB-6-A) 0 to 3 kN & 0-30 22.09.2020 21.09.2021
determining the kN
mechanical
properties of
insulation before
and after ageing
19.6 Tests for 1.Tensile Tester (LAB-6-A) 1) 0 to 3000 N & 0- 22.09.2020 21.09.2021
determining the 2.AGEING OVEN -1 & 2 30 KN 21.09.2020 20.09.2021
mechanical (LAB-17-A & B) 2) DTCS (0 to
properties of non- 200°C)
metallic sheaths & 3) Digital Timer (0
insulation before to 999 Hrs)
and after ageing 4) RotaMeter (0 to
10 LPM)
19.7 Additional ageing 1) Tensile Tester (LAB-6-A) 1) 0 to 3000 N & 0- 22.09.2020 21.09.2021
test on pieces of 2) HOT AIR OVEN (LAB- 30 KN 21.09.2020 20.09.2021
completed cables 11-A) 2) DTCS (0 to
200°C)
3) Digital Timer (0
to 999 Hrs)
4) RotaMeter (0 to
10 LPM)
19.9 Pressure test at HOT AIR OVEN (LAB-11- 0-250°C 21.09.2020 20.09.2021
high temperature A)
on non-metallic
sheaths
19.13 Hot set test for HOT SET OVEN (LAB-12- 0-300°C 22.09.2020 21.09.2021
XLPE insulations A)
19.15 Water absorption HOT AIR OVEN (LAB-11- 0-250°C 21.09.2020 20.09.2021
test on insulation A) 1 mbar & 6.6 mbar 22.09.2020 21.09.2021
Vaccum chamber LAB-10)

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 16 of 19
19.18 Shrinkage test for HOT AIR OVEN (LAB-11- 0-250°C 21.09.2020 20.09.2021
XLPE insulation A)
- Conditioning HUMIDITY Digital Temp & RH 21.09.2020 20.09.2021
CHAMBER(LAB-18) Controller
(0-50 °C and 10-
90 % RH)

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 17 of 19

Guaranted technical particular Doc. No: RRKL W/GTP/2019/0963 Revision 03 (30/01/2021)


CABLE TYPE: Copper Compacted Circular Conductor, XLPE Insulated 6/10 (12)KV ,copper wire screen , PVC
Extruded ,PE outer sheathed cable as per IEC 60502 Part 2

CABLE SIZE : 1 X 400


S.N PARAMETER UOM SPECIFICATION
o
1 Type of Cable - 2X2Y
2 Voltage Grade kV kV 6/10 (12)
3 No of cores X size in sqmm - 1 X 400
4 a) Maximum conductor temperature under °C 90°C
normal operating conditions

b) Maximum conductor temperature at the °C 250°C


termination of short circuit

5 a) Permissible Voltage Variation % ± 10%


b) Permissible Frequency Variation % ± 5%
c) Combined Voltage & Frequency variation % ± 10%
d) Minimum drum length mtr 250(±5%)
f) Approx. Overall diameter (± 2) mm 44.50
g) Min. Bending Redius mm Cable Diameter X 15
h) Packing Material Wooden Drum/Steel Drum
6 Conductor
a) Material Annealed Copper Conductor as per BS EN
60228
b) Shape of conductor Stranded Compacted Circular
c) Minimum no of strand Nos 53
d) Approx conductor diameter mm 23.31
7 Conductor Screening ( Insulation process must be with dry curing )
a) Material Extruded Semi-conducting Compound
b) Nominal thickness mm 0.3
8 Insulation ( Insulation process must be with dry curing )
a) Material XLPE as per IEC 60502-2 Specification
b) Nominal thickness mm 3.40
9 Insulation Screening ( Insulation process must be with dry curing )
a) Non - Metallic
1 Material Extruded Semi-conducting Compound
(Strippable)
2 Nominal thickness mm 0.3
b) Water Blocking Tape
1 Material Semi-conducting Non -Woven Water Blocking
Tape

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 18 of 19
2 Thickness mm 0.3
3 Overlap % 20
c) Metallic
1 Material Copper wire + Copper tape in open helix
2 Wire Size mm 1.350
3 Number of wire Nos. 48
4 Core Identification Natural
d) Water Blocking Tape
1 Material Semi-conducting Non -Woven Water Blocking
Tape
2 wit mm 0.3
3 Overlap % 20
10 Laid up
a) Lay Direction Not applicable
b) PVC Fillers Not applicable
c) Approx Diameter over laid up mm Not applicable
11 Inner Sheath
a) Material Extruded PVC as per IEC 60502-2
b) Minimum thickness mm 1.1
c) Approx Diameter over inner sheath mm 39.8
12 Armouring
a) Material Not applicable
b) Type of armouring Not applicable
c) Nominal size of armour mm Not applicable
13 Outer Sheath
a) Material (ST-7) PE as per IEC 60502-2
b) Nominal Thickness mm 2.40
C) Colour of outersheath Black
14 Printing Message By Ink Jet
"YEAR" RR KABEL 1C X 400 SQ.MM 6/10 KV 2X2Y ELECTRIC CABLE REACH RoHS CE +0001m
15 Electrical Parameters
a) Maximum d.c. resistance of conductor at 20° Ώ/Km 0.047
C
b) Max. a.c. resistance of conductor at 90° C Ώ/Km 0.0632
(ohm/km)
c) Approx. Cable Capacitance (mfd/km) µF/KM 0.480
d) Approx. Cable reactance (ohm/km) Ώ/Km 0.0900
e) Impedance of cable (ohm/km) Ώ/Km 0.065
16 Continuous Current carrying capacities :-
(a) In Ground at 30°C (A) Amps. 508

TRF No. IEC60502_2_TUVR


Report No.:19617564 001 Page 19 of 19
(b) In Air at 40°C (A) Amps. 735
17 Short Circuit rating of conductor for the K.Amp 57.23
duration of 1 sec (kA) s
Prepared By:Dhairya Parmar Revision:03(30/01/2021)

Date :19/12/2019 RRKL W/GTP/2019/0963

This is electronically generated sheet no signature is required

***END OF REPORT***