Ui-8 Module Install
Ui-8 Module Install
DIN 4 These modules are intended for installation within the UL Listed enclosure I/O Modules connect in the following configurations: Max. Number of I/O Modules
Number of modules is limited to 32 per CPU but may
model UL-ENCL for UL 294 and UL 1076.
2 3 Direct Connect Direct Connect Direct Connect be reduced due to the capacity of the Power Supply**
Do not remotely ground any part of the input sensor wiring. Power Supply Power Avail.
Remote grounds connected to the return terminal could make PS 120/240 AC 50-U 35 W
PS 120/240 AC 50 1 50 W
the system operate incorrectly or damage the equipment. PS 120/240 AC 85-U 70 W
Power Supply CPU I/O I/O PS 120/240 AC 85 85 W
The signal return is not true earth ground. It is an electronic PS 48 DC 50 50 W
reference point necessary to interpret the sensor properly.
For reliable operation, follow these wiring guidelines: Module Power Req.
Direct Connect Local Cable CPU (NetController) 10 W
· Never lay wires across the surface of a printed circuit board. Module I/O Bus Pin-Out UI-8-10 & UI-8-10-10V 0.7 W
· Wires should never be within 1 in. or 25 mm of any component
1 on a printed circuit board. 5 +24 VDC
DI-6 AC & DI-6 AC HV
DI-8; Digital Input Module
0.7 W
0.8 W
5 Remote Cable MI-6; MilliAmp Input Module 3.8 W
· Use shielded wire. 4 24 VDC RETURN DM-20 0.5 W *
PANEL · Terminate the shield of the wires at one end of the run 3 SHIELD I/O I/O AO-4-8 & AO-4-8-O
DO-4-R & DO-4-R-O
3.8 W
2.8 W
onlypreferably at the end where your I/O module is located. 2 COMM B
DO-6-TR 1.1 W
· Be careful when stripping wire not to drop small pieces of wire 1 COMM A LO-2 & LO-2-O 0.4 W
inside the cabinet. VT-1 1.5 W
AC-1 2.6 W *
· Dont run your wiring in the same conduit with AC power. Remote AC-1A 2.0 W *
· Dont run your input wiring in the same conduit with your I/O AC-1 Plus 2.2 W *
Connect
output wiring.
Remote Connection Line Termination 1 The PS 120/240 AC 85-U model is only to be used for
Grounding the Modules 5 UL294 applications.
RS-485 Remote configuration (outside the Continuum enclosure) requires a
4 120 W resistor across pin 1 & 2 at the begining and at the end of the remote cable. * Wattage does not include external devices
Some modules include an integral ground clip. All modules include a screw 3 ** 32 modules may require an auxiliary power source.
terminal connection for earth ground. It is important that this connection be
made as close to the module as possible. 2 Local & Remote Cable Information
1 120 W Technical Specifications Max. Cable Lengths Connectors
Caution EOL Resistor
Do not externally ground any input signal. This may damage the unit. COMM A&B Lines: Shielded, Twisted Pair RS-485 2000 ft. (610 m) Cable Connector: ACC # 01-0010-840 (20 pcs.)
Impedance= 100-120 W
I/O Installation Signal return terminals are not connected to earth ground. Low Capacitance FTT-10A 8858 ft. (2700 m) bus topology
1640 ft. (500 m) free topology
30-3001-716 Rev G.1 Power Lines: Remote hookups require Listed UL294
UL1076 power limited power supply. Calculate
f for maximum voltage drop of 2 VDC
- RET
24VDC @ .36 Amps
TO DI0-20
RET RET
10K
DM-20 to DIO-20
+ -
1 2 Power Connection LED Series-Parallel Circuits
Indicator
Digital logic I/O x I/O x UI-8-10 UI-8-10-10V *
Input
+24 VDC +24 V Return DIO-20 Max DC Voltage: 5V 10V INx INx
10 KW 10 KW
GND GND * Note: In the 10V mode the input impedance is 10 KW 10 KW
reduced to 4.4K. This may affect the performance
of the driving device. Contact Contact
Closure Closure
RET RET
IN1 IN2 RET IN3 IN4 RET IN5 IN6 RET IN7 IN8 RET
Caution: Earth ground ( ) must be
1 2 3 4 5 6 7 8 9 10 11 12 ! connected to avoid module damage
DI-6 AC / DI-6-AC-HV MI-6 DO-4-R / DO-4-R-O VT-1
AC Digital Input Module MilliAmp Input Module Relay Output Module Voice Telecom Module
Polarity
Independent
Supply LOAD
AC DC 24V
IN x Loop-Powered INx OUT x
Signal IN x Signal Sensor
Signal
LOAD
IN x OUT x Common
Device
Load LOAD
Contact OUTx V Resistance OUTx V
Closure £ 650W
Device FORM A
Load ³ 2KW OUT 2
RET Resistance
GND GND ON
IN1 IN2 RET IN3 IN4 RET IN5 IN6 RET IN7 IN8 RET Current Output: 0 - 20 mA Output Rating: 24 VAC, 0.5 A (Cannot switch DC Loads)
1 2 3 4 5 6 7 8 9 10 11 12 Voltage Output: 0 - 10V Minimum Load Current: 30 mA
LO-2 / LO-2-O
Lighting Output Module
For more information on these Andover Continuum products, see the I/O Systems
Module External Power Connections Override Switch Connections Reference, 30-3001-499, and the Power Supply Reference, 30-3001-702. For
documentation specific to Underwriters Laboratories (UL) evaluation, see the Note below.
28 VAC
Transformer Momentary Switch
PWR UL 916 Listed product for the United States and Canada, Open
24-30 VAC OFF ON
Energy Management Equipment.
RED
GND
BLK
BLK Note: Only these products mentioned in this document are evaluated by UL for UL 294
(OFF)
and UL 1076 applications:
Occupancy Sensor OVERRIDE
YEL
UI-8-10
UI -8-10-10V
DI-8 (UL294 only)
WHT DO-4
WHT
(COM)
BLU 28 VAC
RECT.
(POWER)
© 2011 Schneider Electric All Rights Reserved.
Schneider Electric § One High St. § North Andover MA USA 01845