Mechanical Wiring Rules I/O Bus

DIN 4 These modules are intended for installation within the UL Listed enclosure I/O Modules connect in the following configurations: Max. Number of I/O Modules
Number of modules is limited to 32 per CPU but may
model UL-ENCL for UL 294 and UL 1076.
2 3 Direct Connect Direct Connect Direct Connect be reduced due to the capacity of the Power Supply**
Do not remotely ground any part of the input sensor wiring. Power Supply Power Avail.
Remote grounds connected to the return terminal could make PS 120/240 AC 50-U 35 W
PS 120/240 AC 50 1 50 W
the system operate incorrectly or damage the equipment. PS 120/240 AC 85-U 70 W
Power Supply CPU I/O I/O PS 120/240 AC 85 85 W
The signal return is not true earth ground. It is an electronic PS –48 DC 50 50 W
reference point necessary to interpret the sensor properly.

For reliable operation, follow these wiring guidelines: Module Power Req.
Direct Connect Local Cable CPU (NetController) 10 W
· Never lay wires across the surface of a printed circuit board. Module I/O Bus Pin-Out UI-8-10 & UI-8-10-10V 0.7 W
· Wires should never be within 1 in. or 25 mm of any component
1 on a printed circuit board. 5 +24 VDC
DI-6 AC & DI-6 AC HV
DI-8; Digital Input Module
0.7 W
0.8 W
5 Remote Cable MI-6; MilliAmp Input Module 3.8 W
· Use shielded wire. 4 24 VDC RETURN DM-20 0.5 W *
PANEL · Terminate the shield of the wires at one end of the run 3 SHIELD I/O I/O AO-4-8 & AO-4-8-O
DO-4-R & DO-4-R-O
3.8 W
2.8 W
only—preferably at the end where your I/O module is located. 2 COMM B
DO-6-TR 1.1 W
· Be careful when stripping wire not to drop small pieces of wire 1 COMM A LO-2 & LO-2-O 0.4 W
inside the cabinet. VT-1 1.5 W
AC-1 2.6 W *
· Don’t run your wiring in the same conduit with AC power. Remote AC-1A 2.0 W *
· Don’t run your input wiring in the same conduit with your I/O AC-1 Plus 2.2 W *
Connect
output wiring.
Remote Connection Line Termination 1 The PS 120/240 AC 85-U model is only to be used for
Grounding the Modules 5 UL294 applications.
RS-485 Remote configuration (outside the Continuum enclosure) requires a
4 120 W resistor across pin 1 & 2 at the begining and at the end of the remote cable. * Wattage does not include external devices
Some modules include an integral ground clip. All modules include a screw 3 ** 32 modules may require an auxiliary power source.
terminal connection for earth ground. It is important that this connection be
made as close to the module as possible. 2 Local & Remote Cable Information
1 120 W Technical Specifications Max. Cable Lengths Connectors
Caution EOL Resistor
Do not externally ground any input signal. This may damage the unit. COMM A&B Lines: Shielded, Twisted Pair RS-485 2000 ft. (610 m) Cable Connector: ACC # 01-0010-840 (20 pcs.)
Impedance= 100-120 W
I/O Installation Signal return terminals are not connected to earth ground. Low Capacitance FTT-10A 8858 ft. (2700 m) bus topology
1640 ft. (500 m) free topology
30-3001-716 Rev G.1 Power Lines: Remote hookups require Listed UL294
UL1076 power limited power supply. Calculate
f for maximum voltage drop of 2 VDC

DM-20 UI-8-10 / UI-8-10-10V


Digital Input/Output Module Universal Input Module Supervised Circuits Reference
Resistor = ON
DIO-20 Connections 5V
IN x
Series Circuits
General Purpose I/O Normally Open Normally Closed
IN x 10 KW 10 KW
DM-20
INx INx
Contact Reference
10K
Closure Thermistor
Resistor = ON
Contact Contact
Closure Closure
DM-20 to DIO-20 RET
Digital logic
Data Connection Signal
I/O x I/O x
RET RET
Contact
Closure

DIO-20 GND GND


Parallel Circuits
IN x INx INx
+
Reference
5V +5V
V DC Voltage Resistor = OFF Contact 10 KW Contact 10 KW
Closure Closure

- RET
24VDC @ .36 Amps
TO DI0-20
RET RET
10K

DM-20 to DIO-20
+ -
1 2 Power Connection LED Series-Parallel Circuits
Indicator
Digital logic I/O x I/O x UI-8-10 UI-8-10-10V *
Input
+24 VDC +24 V Return DIO-20 Max DC Voltage: 5V 10V INx INx

10 KW 10 KW
GND GND * Note: In the 10V mode the input impedance is 10 KW 10 KW
reduced to 4.4K. This may affect the performance
of the driving device. Contact Contact
Closure Closure
RET RET

IN1 IN2 RET IN3 IN4 RET IN5 IN6 RET IN7 IN8 RET
Caution: Earth ground ( ) must be
1 2 3 4 5 6 7 8 9 10 11 12 ! connected to avoid module damage
DI-6 AC / DI-6-AC-HV MI-6 DO-4-R / DO-4-R-O VT-1
AC Digital Input Module MilliAmp Input Module Relay Output Module Voice Telecom Module
Polarity
Independent
Supply LOAD
AC DC 24V
IN x Loop-Powered INx OUT x
Signal IN x Signal Sensor
Signal
LOAD

DI-6-AC DI-6-AC-HV Max Current: 20 mA


Voltage Range: 20-132 Vrms 90-250 Vrms Voltage Supply to Sensor: 19 - 26V
Contact Rating: 5A @ 240 VAC
5A @ 30 VDC

DI-8 AO-4-8 / AO-4-8-O DO-6-TR


RJ-11 Earth Ground
Digital Input Module Analog Output Module Triac Output Module Telephone Line
+ ON
Voltage Output Current Output
Digital logic IN x OUT 1
Signal
OUTx I OUTx I

IN x OUT x Common
Device
Load LOAD
Contact OUTx V Resistance OUTx V
Closure £ 650W
Device FORM A
Load ³ 2KW OUT 2
RET Resistance
GND GND ON

Using Two Outputs to make


FORM K

IN1 IN2 RET IN3 IN4 RET IN5 IN6 RET IN7 IN8 RET Current Output: 0 - 20 mA Output Rating: 24 VAC, 0.5 A (Cannot switch DC Loads)
1 2 3 4 5 6 7 8 9 10 11 12 Voltage Output: 0 - 10V Minimum Load Current: 30 mA

LO-2 / LO-2-O
Lighting Output Module
For more information on these Andover Continuum products, see the I/O Systems
Module External Power Connections Override Switch Connections Reference, 30-3001-499, and the Power Supply Reference, 30-3001-702. For
documentation specific to Underwriters Laboratories (UL) evaluation, see the Note below.
28 VAC
Transformer Momentary Switch

PWR UL 916 Listed product for the United States and Canada, Open
24-30 VAC OFF ON
Energy Management Equipment.
RED
GND

BLK UL 294 (Access Control System Unit Subassemblies for the


OVERRIDE
United States) and UL 1076 (Proprietary Burglar Alarm System
This ground connection must be Indicator Unit Subassemblies for the United States) and C22.2 No.
the same as the ground Output Rating: Lamp Load – 20 Amp Tungsten Filament @125 VAC
for the Continuum Power Supply
Resistive Load – 20 Amp Ballast @ 277 VAC (20 amp @347 VAC, Canada) YEL
205-M1983 (Signal Equipment for Canada)
Motor Load – 0.5 Hp @ 110-125 VAC
28 VDC (half-wave rectified AC) 0.5 HP @ 220-277 VAC (0.5 Hp @ 347 VAC, Canada)
to External Sensors WHT
28 VAC
RECT Note: Refer to the UL Listed Access Control/Proprietary Burglar Alarm System’s
installation manual (the UL294 Access Control and UL 1076 Proprietary Burglar Alarm
Systems Reference, 30-3001-504) for specific wiring, operation, and compatibility
RED (ON)
RED
information.
External Relay Assy. Connections

BLK
BLK Note: Only these products mentioned in this document are evaluated by UL for UL 294
(OFF)
and UL 1076 applications:
Occupancy Sensor OVERRIDE

YEL
UI-8-10
UI -8-10-10V
DI-8 (UL294 only)
WHT DO-4
WHT
(COM)

BLU 28 VAC
RECT.
(POWER)
© 2011 Schneider Electric All Rights Reserved.