Blue Prints HHER TYLER-BIDDING SET

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 103

Tyler Expansion

Tyler, Texas
13
12 9

10 11 11

12
14 14

TR
H AS
AS H
TR

20
GENERATOR

GENERATOR

5
5 5

5
5 5

C4.0
OVERALL WATER & SEWER


9/11/2020 11:15:40 AM

GENERAL NOTES CAST-IN-PLACE CONCRETE STEEL JOISTS


STRUCTURAL ABBREVIATIONS STRUCTURAL ABBREVIATIONS
1. CAST-IN-PLACE CONCRETE SHALL HAVE NORMAL WEIGHT COARSE AGGREGATES CONFORMING TO ASTM C33, 1. OPEN WEB STEEL JOISTS SHALL BE DETAILED, FABRICATED AND ERECTED IN ACCORDANCE WITH THE LATEST
ABOVE FINISH FLOOR A.F.F. LINTEL LNTL
DESIGN CODES AND LOADS NATURAL SAND FINE AGGREGATES, TYPE I PORTLAND CEMENT CONFORMING TO ASTM C150. EDITION OF THE STEEL JOIST INSTITUTE'S S.J.I. STANDARD SPECIFICATIONS AND LOAD TABLES.
ADDITIONAL ADD'L. LIVE LOAD LL
1. BUILDING CODE: 2015 INTERNATIONAL BUILDING CODE 2. FLY ASH MAY BE USED TO REPLACE A MAXIMUM OF 25% OF THE TOTAL CEMENTITIOUS CONTENT. FLY ASH SHALL 2. JOIST BRIDGING SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH S.J.I. SPECIFICATIONS AND OSHA
ALTERNATE ALT. LONGITUDINAL LONG.
2. STRUCTURAL CONCRETE: BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE CONFORM TO ASTM C618, CLASS C OR F. REGULATIONS. BRIDGING SHALL BE CONTINUOUS THROUGH JOISTS AND STRUCTURAL STEEL MEMBERS AND
ANCHOR ROD A.R. LONG LEG HORIZONTAL LLH
INSTITUTE, ACI 318. 3. CAST-IN-PLACE CONCRETE SHALL STRICTLY ADHERE TO THE PROPORTIONS ESTABLISHED IN DESIGN MIXES, SHALL BE ANCHORED TO WALL OR SPANDREL MEMBERS. PROVIDE DIAGONAL BRIDGING WITH BOLTED
AND & LONG LEG VERTICAL LLV
3. CONCRETE MASONRY: BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES, ACI 530, ASCE 5, TMS 402. CONSISTING OF THE ACTUAL MATERIALS TO BE USED DURING CONSTRUCTION. DESIGN MIXES SHALL BE CONNECTIONS WHERE REQUIRED BY S.J.I.
ANGLE L LOW POINT L.P.
4. STRUCTURAL STEEL: MANUAL OF STEEL CONSTRUCTION, AMERICAN INSTITUTE OF STEEL CONSTRUCTION. PREPARED AND SUBMITTED TO THE STRUCTURAL ENGINEER OF RECORD FOR REVIEW PRIOR TO USE. MIX 3. JOIST MANUFACTURER SHALL DESIGN AND SPECIFY BRIDGING FOR THE UPLIFT LOADING NOTED ON THE
APPROXIMATE ≈/APPROX.
5. WOOD: NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION, ALLOWABLE STRESS DESIGN. DESIGN PROPORTIONS SHALL BE IN ACCORDANCE WITH ACI 211/301/318. CONCRETE MIX DESIGNS SHALL BE IN DRAWINGS. PROVIDE ADDITIONAL BRIDGING AS REQUIRED TO BRACE BOTTOM CHORDS IN COMPRESSION.
ARCHITECTURAL ARCH'L. MANUFACTURER MANUF.
6. DESIGN WIND LOAD CRITERIA: ACCORDANCE WITH THE FOLLOWING TABLE: 4. JOIST TOP & BOTTOM CHORDS SHALL BE DOUBLE-ANGLE OR TEE SECTIONS.
AT @ MATERIAL MAT'L.
V-ULTIMATE ---------- 120 MPH 5. STEEL JOISTS SHALL BE WELDED TO SUPPORTING MEMBERS, AS DETAILED.
AIR CONDITIONER A/C MAXIMUM MAX.
AIR HANDLING UNIT AHU MECHANICAL MECH'L. V-ASD ---------- 93 MPH CONCRETE MIX DESIGN SCHEDULE 6. WHERE JOISTS ARE CENTERED ON COLUMNS OR WHERE JOIST SPANS EXCEED 40 FEET, PROVIDE SLOTTED,
RISK CATEGORY ---------- IV BOLTED JOIST SEATS FOR ERECTION WITH WELDED SEATS FOR FINAL ASSEMBLY. FOR JOISTS AT COLUMNS,
MECHANICAL, ELECTRICAL, MIN. COMPRESSIVE
EXPOSURE ---------- C MAXIMUM W/C MAX. AGGREGATE EXTEND BOTTOM CHORDS TO STABILIZER PLATES AS DETAILED.
BASE PLATE BP PLUMBING M.E.P. TYPE OF CONSTRUCTION STRENGTH @ 28 TOTAL AIR SLUMP (in.)
INTERNAL PRESS. COEFF. ---------- ±0.18 RATIO SIZE (in.) 7. ALL WELDS SHALL BE MADE ONLY BY PREQUALIFIED WELDERS AND SHALL BE PERFORMED IN ACCORD. WITH S.J.I. 09/11/2020
BEAM BM. METAL MTL. DAYS (psi)
7. DESIGN LIVE LOADS: SPECS.
BEARING BRNG. MEZZANINE MEZZ.
ROOF ---------- 25 PSF GRADE BEAMS, PLINTHS, 8. JOIST MANUFACTURER SHALL DESIGN ALL JOISTS TO SUPPORT A 150 LB. CONCENTRATED LOAD ANYWHERE
BETWEEN BTWN. MINIMUM MIN. 3000 4.5%±1.5% 0.55 3-5 1
MECHANICAL ---------- AS REQ'D. & WALLS ALONG ON THE BOTTOM CHORD AND A 150 LB. CONCENTRATED LOAD ANYWHERE ALONG ON THE TOP CHORD.
BLOCKING BLK'G. MISCELLANEOUS MISC.
RETAIL ---------- 100 PSF 9. HANGERS FOR MECHANICAL EQUIPMENT, SPRINKLER LINES, ETC. WITH REACTIONS IN EXCESS OF THOSE LISTED
BOTH WAYS B.W. MOMENT M. FOOTINGS & INTERIOR 3% MAX.
8. DESIGN SNOW LOAD: 3000 0.50 3-5 1 ABOVE SHALL BE SUPPORTED AT PANEL POINTS OR JOISTS SHALL BE REINFORCED WITH ADDITIONAL WEB
BOTTOM BOTT. MOMENT CONNECTIONS M.C. SLAB-ON-GRADE (ENTRAPPED)
GROUND SNOW ---------- 5 PSF STRUTS AS DETAILED.
BOTTOM OF B.O.
Pf ---------- 4.2 PSF 10. JOISTS SHALL BE SUPPLIED WITH A SHOP-COAT OF RUST INHIBITING PRIMER.
BOTTOM CHORD EXTENSION BCX NEAR SIDE N.S. ELEVATED SLAB ON DECK 3% MAX.
Ce ---------- 1.0 3000 0.45 4-6 3/4" 11. JOISTS DESIGNATED AS "SP" ARE JOISTS WITH SPECIAL LOADING DIAGRAMS AS INDICATED ON DRAWINGS. SUBMIT
BOTTOM OF STEEL B.O.S. NOT TO SCALE N.T.S. LTWT. CONC. (ENTRAPPED) THACKER | DAVIS ARCHITECTS
IMPORTANCE FACTOR ---------- 1.2 SIGNED AND SEALED CALCULATIONS FOR ALL "SP" JOISTS WITH THE SHOP DRAWINGS. CALCULATIONS WILL BE
BRIDGING BRDG. NUMBER NO. OR # I N C O R P O R A T E D

Ct ---------- 1.0 A. MIN. CEMENTITIOUS CONTENT = 5 SACKS PER CUBIC YARD (MAX. OF WHICH MAY BE 25% FLY ASH). RETAINED FOR SER'S RECORDS AND MAY NOT BE RETURNED WITH THE SHOP DRAWING SUBMITTAL. Member American Institute of Architects
BUILDING BLDG. ON CENTER O.C.
BUILDING LINE B.L. OPENING(S) OPNG. 9. DESIGN SEISMIC LOAD: B. USE OF CALCIUM CHLORIDE IS NOT PERMITTED .
1100 Judson Rd., Suite 620 PO Box 2723

OPPOSITE OPP. RISK CATEGORY ---------- IV 4. MIXING, TRANSPORTATION, AND PLACEMENT OF CONCRETE SHALL BE IN ACCORDANCE WITH ACI 301. COMPOSITE FLOOR DECK Longview, Texas 75606-2723

CEILING CLG. OPPOSITE HAND O.H. IMPORTANCE FACTOR ---------- 1.5 5. CONCRETE SHALL NOT BE PLACED WHEN AMBIENT AIR TEMPERATURE IS 40° OR LESS AND FALLING. 1. ELEVATED FLOOR SLAB SHALL BE 3" LIGHTWEIGHT CONCRETE OVER 2" STEEL DECK (5" TOTAL THICKNESS).
.
Phone 903.236.3771 Fax 903.753.7317

CENTER TO CENTER C/C OUTSIDE DIAMETER O.D. Ss ---------- 0.105g 6. FRESH CONCRETE SHALL BE PROTECTED FROM FREEZING WHEN CONCRETE WILL BE EXPOSED TO AMBIENT AIR CONCRETE SHALL HAVE A MIN. COMPRESSIVE STRENGTH AT 28 DAYS OF 3500 PSI. REFER TO PROJECT Email: T D A @ T - D A r c h i t e c t s . c o m
CENTER LINE CL OUTSIDE FACE O.F. S1 ---------- 0.057g TEMPERATURES LESS THAN 32° FOR MORE THAN 8 HOURS WITHIN THE FIRST 72 HOURS OF PLACEMENT. SPECIFICATIONS FOR CONCRETE MIX DESIGN CRITERIA. w w w . T - D A r c h i t e c t s . c o m
CENTERED CNTRD. SITE CLASS ---------- D 7. CONTRACTOR SHALL COORDINATE THE COMPATIBILITY OF ALL CURING COMPOUNDS WITH ARCHITECTURAL FLOOR 2. STEEL DECK SHALL BE 2 INCH, 22 GAUGE, TYPE 2VLI22, UNSHORED COMPOSITE DECK, AS MANUFACTURED BY
CHANNEL C PANEL PNL. SDs ---------- 0.112g FINISHES. VULCRAFT, DIVISION OF NUCOR CORPORATION. DECK SHALL BE CONTINUOUS OVER 3 OR MORE SUPPORTS.
CLEAR CLR. PERIMETER PERIM. SD1 ---------- 0.091g 8. REINFORCING BARS SHALL CONFORM TO ASTM A 615, GRADE 60. 3. PLUG WELD DECK TO SUPPORTING STEEL AND ADJOINING DECK SHEETS IN ACCORDANCE WITH THE AMERICAN
COLUMN COL. PERPENDICULAR PERP. SEISMIC DESIGN CATEGORY ---------- C 9. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185. FABRIC SHALL BE SUPPLIED IN FLAT SHEETS AND SHALL BE WELDING SOCIETY STANDARD D1.3. ATTACH DECK TO SUPPORTING STEEL WITH 3/4"Ø SHEAR CONNECTORS AND 3/4"Ø
COMPRESSION (C) PLATE PL SLRS ---------- STRUCTURAL STEEL SYSTEM NOT SPECIFICALLY DETAILED FOR LAPPED 2 MESHES AT SPLICES. WELDS AT 12"o.c. MAXIMUM.
CONCRETE CONC. POUNDS LBS. SEISMIC RESISTANCE 10. DETAILING OF CONCRETE REINFORCING BARS AND ACCESSORIES SHALL CONFORM TO THE RECOMMENDATIONS OF 4. STEEL DECK SHALL BE GALVANIZED.
CONCRETE MASONRY UNIT CMU POUNDS PER LINEAR FOOT PLF V ---------- 0.056 W ACI 315 "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT" AND ACI SP-66 "DETAILING MANUAL." 5. STEEL DECK SHALL BE FREE FROM OIL, DIRT AND ANY OTHER MATERIALS THAT WOULD TEND TO REDUCE THE BOND
CONDENSING UNIT CU POUNDS PER SQUARE FOOT PSF Cs ---------- 0.056 11. TIE OR STIRRUP SPACINGS SHALL BE AS INDICATED IN THE DRAWINGS, STARTING FROM THE FACE OF EACH BETWEEN THE CONCRETE AND DECK.
CONDITION COND'N. POINT PT. R ---------- 3 SUPPORT. THE FIRST STIRRUP SHALL BE PLACED AT A SPACING OF S/2 FROM THE FACE OF EACH SUPPORT, WHERE 6. REINFORCE SLAB WITH 6x6-W1.4xW1.4 WELDED WIRE FABRIC.
CONNECTION(S) CONN. POWDER ACTUATED FASTENER P.A.F. ANALYSIS METHOD ---------- EQUIVALENT LAT. FORCE "S" IS THE TYPICAL SPACING. 7. PROVIDE SUFFICIENT CHAIRS TO MAINTAIN WELDED WIRE FABRIC SPECIFIED DEPTH.
CONTINUOUS CONT. PRECAST CONCRETE P/C 12. PROVIDE CORNER BARS IN CONCRETE STEM WALLS OR GRADE BEAMS AS DETAILED. 8. TESTING LABORATORY SERVICES FOR QUALITY CONTROL OF SHEAR STUDS SHALL BE PROVIDED BY THE OWNER. STRUCTURAL ENGINEER:
CONSTRUCTION JOINT C.J. PRE-ENGINEERED METAL BUILDING PEMB 13. CONCRETE PROTECTION FOR REINFORCING BARS: TESTING SERVICES SHALL BE IN ACCORDANCE WITH PROJECT SPECIFICATIONS.
COORDINATE COORD. PROJECTION PROJ. GRADE BEAM TOP BARS ------------- 1 1/2"
MISCELLANEOUS
GRADE BEAM SIDE BARS ------------- 3"
1. SCALES INDICATED ON THE DRAWINGS ARE FOR GENERAL INFORMATION ONLY. NO DIMENSIONAL INFORMATION STEEL ROOF DECK
DETAIL DTL. RADIUS RAD. GRADE BEAM BOTTOM BARS ------------- 3"
SHALL BE OBTAINED BY DIRECT SCALING OF THE STRUCTURAL DRAWINGS. CONTRACTOR SHALL VERIFY ALL 1. STEEL ROOF DECK SHALL BE 1.5 INCH, 22 GAGE, TYPE 1.5B 22 WIDE RIB ROOF DECK, AS MANUFACTURED BY VULCRAFT,
DEAD LOAD DL REFER REF. OR RE: WALLS ------------- 1 1/2"
DIMENSIONS PRIOR TO THE START OF CONSTRUCTION AND REPORT ANY DISCREPANCIES TO THE STRUCTURAL DIVISION OF NUCOR CORPORATION.
DIAGONAL DIAG. REINFORCING REINF. SLABS ------------- AS DETAILED
ENGINEER OF RECORD. 2. STEEL ROOF DECK SHALL BE GALVANIZED WITH COATING DESIGNATION G60.
DIAGONAL BRACE D.B. REQUIRED REQ'D. FOOTING - BOTT. & SIDES ------------- 3"
2. CONTRACTOR SHALL VERIFY ALL CONDITIONS AT THE JOBSITE AND REPORT ANY DISCREPANCIES TO THE 3. PROPERTIES AND ALLOWABLE STRESSES OF STEEL ROOF DECKS SHALL BE BASED ON THE LATEST AISI SPECIFICATION
DIAMETER DIA. OR ∅ REQUIREMENTS REQ'MTS. FOOTING - TOP ------------- 2"
STRUCTURAL ENGINEER OF RECORD. FOR COLD-FORMED STRUCTURAL STEEL MEMBERS.
DIMENSION DIM. RIGID FRAME R.F. DRILLED PIERS ------------- 3"
3. ALL METHODS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION SHALL BE THE RESPONSIBILITY OF THE 4. ROOF DECK SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES:
DOUBLE DBL. ROOF TOP UNIT RTU 14. REINFORCEMENT DESIGNATED AS "CONTINUOUS" IN THE DRAWINGS SHALL BE LAP-SPLICED IN ACCORDANCE WITH
CONTRACTOR. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO INSURE AND MAINTAIN THE DESIGN THICKNESS 0.0295 IN
DOWEL DWL. ROOF DRAIN R.D. THE REINFORCING STEEL DEVELOPMENT SCHEDULE. SPLICE TOP BARS OF GRADE BEAMS AS REQUIRED AT
INTEGRITY OF THE STRUCTURE DURING ALL STAGES OF CONSTRUCTION. lp 0.155 IN ̂4
DOWN DN. MIDSPAN BETWEEN SUPPORTS. SPLICE BOTTOM BARS OF GRADE BEAMS AS REQUIRED AT CENTERLINE OF
4. THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADING CONDITIONS ONLY. THE CONTRACTOR ln 0.183 IN ̂4
DRAWING DWG. SAW CUT JOINT S.J. SUPPORTS. PROVIDE STANDARD ACI HOOKS AT ALL DISCONTINUOUS ENDS.
SHALL BE RESPONSIBLE FOR THE DESIGN AND INSTALLATION OF ALL FORM WORK AND SHORING OPERATIONS. Sp 0.186 IN ̂3 Physical: 16291 FM 849
SCHEDULE SCHED. 15. HORIZONTAL JOINTS SHALL NOT BE PERMITTED UNLESS DETAILED OTHERWISE. WHERE ALLOWED, HORIZONTAL Mail: P.O. BOX 2428
THE CONTRACTOR SHALL MAINTAIN STRUCTURE STABILITY AND SAFETY DURING ALL PHASES OF CONSTRUCTION, Sn 0.192 IN ̂3
EACH EA. SECTION SECT. IN ACCORDANCE WITH SEI/ASCE 37-01 "DESIGN LOADS ON STRUCTURES DURING CONSTRUCTION. JOINTS SHALL BE ROUGHENED TO 1/4" AMPLITUDE PRIOR TO SUBSEQUENT CONCRETE PLACEMENT OPERATIONS. Lindale, Texas 75771
Fy 33 KSI
EACH FACE E.F. SHEAR (V) VERTICAL JOINTS IN CONCRETE BEAMS SHALL OCCUR AT MIDSPAN BETWEEN SUPPORTS. Phone: 903.882.8503 / Fax 903.882.5318
5. CONSTRUCTION MATERIALS AND EQUIPMENT LOADS ON FRAME FLOORS OR ROOFS SHALL BE SPREAD OUT AND 5. ROOF DECK SHALL BE FASTENED TO ALL SUPPORT MEMBERS USING ONE OR MORE OF THE FOLLOWING OPTIONS: WWW.HOLLANDENGR.COM
EACH WAY E.W. SHEET SHT. 16. CONTRACTOR SHALL VERIFY THE PRESENCE, LOCATION, AND SIZES OF ALL OPENINGS, DEPRESSIONS, AND
SHALL NOT EXCEED THE DESIGN LIVE LOADS PER SQUARE FOOT. PROVIDE ADEQUATE SHORING AND BRACING A. HILTI X-HSN24 FOR FASTENING TO ALL K-SERIES JOISTS AND STRUCTURAL STEEL WITH STEEL THICKNESSES Texas Firm #: F-8474
ELECTRICAL ELEC'L. SIMILAR SIM. EMBEDMENTS PRIOR TO PLACING CONCRETE. NO OPENINGS SHALL BE PERMITTED THROUGH CONCRETE, UNLESS
WHERE STRUCTURE HAS NOT ATTAINED DESIGN STRENGTH. CONSTRUCTION EQUIPMENT WITH WHEEL LOADS 1/8" ≤ Tf ≤ 3/8" (WHERE Tf IS FLANGE THICKNESS). HE #: 20-019
ELEVATION EL. SLIP CONNECTION S.C. DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER OF RECORD. CONDUIT FOR ELECTRICAL OR PLUMBING
GREATER THAN 2000 POUNDS ARE NOT PERMITTED ON THE SLAB WITHOUT PRIOR WRITTEN AGREEMENT OF THE B. HILTI X-ENP-19 L15 FOR FASTENING TO STRUCTURAL STEEL WITH STEEL THICKNESSES Tf ≥ 1/4" (WHERE Tf IS
ELEVATOR ELEV. SPACE SP. LINES SHALL BE SLEEVED THROUGH GRADE BEAMS.
STRUCTURAL ENGINEER OF RECORD. FLANGE THICKNESS).
ENGINEER ENGR. SPECIFICATIONS SPEC. 17. ALL DRILLED/EPOXY SET ANCHORS OR DOWELS SHALL BE AS MANUFACTURED BY HILTI. (NO SUBSTITUTIONS
6. STRUCTURAL MEMBERS HAVE BEEN LOCATED AND DESIGNED TO ACCOMMODATE THE MECHANICAL EQUIPMENT C. #12 TEK SCREWS FOR FASTENING TO COLD-FORMED METAL FRAMING JOISTS.
EQUAL (EQUALLY) EQ. STAINLESS STEEL SS ALLOWED W/OUT WRITTEN APPROVAL OF STRUCTURAL ENGINEER.) REFER TO POST-INSTALLED ANCHORS NOTE.
AND OPENINGS, AS SPECIFIED BY THE MECHANICAL CONSULTANT. THE CONTRACTOR SHALL COORDINATE ANY D. HILTI S-SC02M HWH FOR SIDE LAP FASTENING.
EXPANSION EXP. STANDARD STD. 18. CONTRACTOR SHALL MAKE PROVISIONS FOR FINISHING EXPOSED CONCRETE. AS SOON AS FORMS ARE REMOVED,
SUBSTITUTIONS REQUIRING REVISIONS TO THE STRUCTURAL FRAMING WITH THE STRUCTURAL ENGINEER OF 6. FASTENERS FOR METAL DECK SHALL BE AS MANUFACTURED BY HILTI NORTH AMERICA.
EXPANSION JOINT E.J. STEEL STL. UNDESIRABLE FINS AND PROJECTIONS SHALL BE REMOVED, OFFSETS SHALL BE LEVELED, AND VOID OR DAMAGED
RECORD. 7. FASTENER SPACING SHALL BE IN ACCORDANCE WITH THE ROOF DECK ATTACHMENT PLAN SHOWN. ALL FASTENERS
EXISTING EX. STIFFENER STIFF. PLACES SHALL BE IMMEDIATELY SATURATED WITH WATER AND FINISHED WITH CEMENTITIOUS PASTE OR MORTAR
7. THERE SHALL BE NO DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS UNLESS APPROVED IN WRITING BY THE SHALL BE SUPPLIED AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
EXTERIOR EXT. STIRRUPS STIR. STRUCTURAL ENGINEER OF RECORD. ANY PROPOSED ADDITIONS, SUBSTITUTIONS, OR MODIFICATIONS SHALL BE OF THE SAME COMPOSITION AS USED IN THE MIX. EXPOSED SURFACES SHALL BE RUBBED WITH CARBORUNDUM
STRUCTURE STRUCT. STONE TO A SMOOTH FINISH, FREE FROM FORM MARKS OR HONEYCOMBS.
SUBMITTED IN WRITING WELL IN ADVANCE OF NEED FOR MATERIAL ON SITE. SHOP DRAWINGS DO NOT
FACE TO FACE F/F STRUCTURAL STRUCT'L. 19. OWNER SHALL PROVIDE FOR QUALITY CONTROL OF CAST-IN-PLACE CONCRETE BY EMPLOYING A QUALIFIED
CONSTITUTE "IN-WRITING" UNLESS THE PROPOSED CHANGES ARE CLEARLY AND SPECIFICALLY IDENTIFIED. THE MASONRY
FACE OF F.O. SYMMETRICAL SYMM. TESTING LABORATORY SERVICE TO PREPARE AND TEST CONCRETE COMPRESSION CYLINDERS, SLUMP, AIR
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL REVISIONS TO THE STRUCTURAL FRAMING OR 1. CONCRETE MASONRY UNITS SHALL BE HOLLOW, LIGHTWEIGHT UNITS CONFORMING TO ASTM C90, SAMPLED AND
FAR SIDE F.S. CONTENT, TEMPERATURE, ETC., IN ACCORDANCE WITH PROJECT SPECIFICATIONS, OR AS FOLLOWS:
FOUNDATION SYSTEM RESULTING FROM ACCEPTANCE OF ALTERNATES OR SUBSTITUTIONS FROM OTHER TESTED IN ACCORDANCE WITH ASTM C140.
FINISH(ED) FIN. TOP CHORD EXTENSION TCX DISCIPLINES. A. TESTING FREQUENCY: OBTAIN ONE COMPOSITE SAMPLE OF (4) CYLINDERS FOR EACH DAY'S POUR FOR EVERY
2. CONCRETE MASONRY UNITS SHALL HAVE A MIN. COMPRESSIVE STRENGTH (f'm) OF 1500 PSI ON THE NET CROSS
FINISHED FLOOR FIN. FLR. TEMPERATURE TEMP. 50 CU. YD. OR FRACTION THEREOF.
8. REPRODUCTIVE USE OF THE STRUCTURAL DRAWINGS IN PART OR IN WHOLE FOR SHOP DRAWINGS, ERECTION SECTIONAL AREA FOR INDIVIDUAL UNITS AND A MIN. NET AREA COMPRESSIVE STRENGTH OF 1900 PSI FOR UNITS
FLANGE BRACE F.B. TENSION (T) B. SLUMP TEST: ONE TEST AT POINT OF PLACEMENT FOR EACH COMPOSITE SAMPLE, BUT NOT LESS THAN ONE
DRAWINGS, OR ANY OTHER SUBMITTAL PURPOSES SHALL NOT BE ALLOWED. WITH MORTAR.
FLOOR DRAIN F.D. THICK THK. TEST FOR EACH DAY'S POUR.
9. REQUESTS FOR CAD FILES SHALL BE SUBMITTED IN WRITING TO THE STRUCTURAL ENGINEER OF RECORD AND 3. MORTAR FOR ALL MASONRY WORK SHALL CONFORM TO ASTM C270, TYPE S. MASONRY CEMENT SHALL NOT BE USED.
FOOTING FTG. THROUGH THRU C. AIR CONTENT: PRESSURE METHOD; ONE TEST FOR EACH COMPOSITE SAMPLE, BUT NOT LESS THAN ONE TEST
WILL BE CONSIDERED ON A CASE BY CASE BASIS. CAD FILES WILL NOT BE RELEASED TO CONTRACTORS OR 4. UNITS SHALL BE BONDED BY LAPPING UNITS IN SUCCESSIVE COURSES.
FOUNDATION FDN. TONGUE & GROOVE T&G. FOR EACH DAY'S POUR.
SUBCONTRACTORS WITHOUT AN EXECUTED CAD RELEASE WAIVER AND PAYMENT OF RELATED FEES. 5. POURED CONCRETE GROUT SHALL CONFORM TO ASTM C476 AND SHALL HAVE A MIN. COMPRESSIVE STRENGTH OF
TOP & BOTTOM T&B. D. CONCRETE TEMPERATURE: ONE TEST HOURLY WHEN AIR TEMPERATURE IS 40 DEGREES AND BELOW AND
10. CONTRACTOR SHALL BE RESPONSIBLE FOR FITTING NEW WORK WITH EXISTING CONSTRUCTION. CONTRACTOR 3000 PSI AT 28 DAYS. COARSE AGGREGATE FOR POURED CONCRETE GROUT SHALL BE 3/8" MAX. PEA GRAVEL.
GAGE OR GAUGE GA. TOP OF T.O. WHEN 80 DEGREES AND ABOVE, AND ONE TEST FOR EACH COMPOSITE SAMPLE.
SHALL PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY TO PROTECT EXISTING BUILDINGS, PAVING, POURED CONCRETE GROUT SHALL HAVE A SLUMP OF 8" TO 11". PLACE GROUT IN ACCORDANCE WITH ACI 530.1
GALVANIZED GALV. TOP OF BEAM T.O.B. E. COMPRESSIVE STRENGTH TESTS: TEST ONE CYLINDER AT 7 DAYS, ONE SET OF TWO (2) CYLINDERS AT 28 DAYS
AND PARKING SURFACES DURING CONSTRUCTION. WHERE ANY EXISTING CONSTRUCTION IS DAMAGED DURING SECTION 3.5.
GENERAL GEN. TOP OF FOOTING T.O.F. AND HOLD ONE (1) CYLINDER FOR TESTING WHEN REQUIRED BY ARCHITECT/ENGINEER. RESULTS SHALL
CONSTRUCTION, IT SHALL BE REPLACED AT NO ADDITIONAL COST TO THE OWNER. 6. ALL MASONRY SHALL BE LAID WITH FULL HEAD AND BED JOINTS WITH FULL MORTAR COVERAGE ON THE FACE
GLUE-LAMINATED BEAM G.L.B. TOP OF JOIST T.O.J. INDICATE THE AVERAGE COMPRESSIVE STRENGTH FOR EACH SET OBTAINED FROM THE SAME COMPOSITE
11. CONTRACTOR SHALL COORDINATE ALL MISCELLANEOUS STEEL REQUIREMENTS WITH ARCHITECTURAL AND SHELLS AND WEBS OF HOLLOW UNITS. MORTAR PROJECTIONS IN HOLLOW CAVITIES SHALL BE LIMITED TO 3/4".
GRADE GR. TOP OF METAL DECK T.M.D. MECHANICAL DRAWINGS. SAMPLE AND TESTING AT THE AGE INDICATED.
7. PROVIDE A MIN. OF (3) #5 AT EACH CORNER, (2) #5 AT EACH END OF WALL, AND (2) #5 AT EACH EDGE OF OPENING
GRADE BEAM GR.BM. TOP OF PIER T.O.P. F. ALL TEST REPORTS SHALL BE SUBMITTED TO THE PROJECT ARCHITECT AND STRUCTURAL ENGINEER FOR
12. ALL DETAILS NOTED OR LABELED AS TYPICAL (TYP.) APPLY IN A GENERAL SENSE TO THE DRAWINGS WHERE (EACH SIDE) AT EACH WALL IN CELLS FILLED SOLID WITH POURED CONCRETE GROUT, UNLESS NOTED OR DETAILED
GYPSUM BOARD GYP.BD. TOP OF PIER CAP T.O.P.C. REVIEW.
CONDITIONS ARE APPLICABLE OR SIMILAR. OTHERWISE.
TOP OF STEEL T.O.S. 20. CONCRETE SHALL BE PLACED CONTINUOUSLY, WITHOUT INTERRUPTION, IN SUCH A MANNER AS NOT TO CAUSE
8. WHERE INDICATED, HOLLOW CELLS SHALL BE FILLED WITH POURED CONCRETE GROUT. CELLS TO BE FILLED SHALL
HEADED STUD H.S. TOP OF STRUCTURAL STEEL T.O.S.S. SEGREGATION. EACH LIFT SHALL BE VIBRATED. WHERE CONCRETE DROPS ARE MORE THAN 5 FEET, CONCRETE
SUBGRADE PREPARATION BE CLEAN AND FREE OF EXCESS MORTAR AND DEBRIS.
HEIGHT HT. TOP OF STRUCT'L. CONC. T.O.S.C. SHALL BE PLACED USING A CHUTE, TREMIE, OR PUMP HOSE.
1. ALL SUBGRADE PREPARATION, EXCAVATIONS, SITEWORK, AND SELECT FILL OPERATIONS SHALL BE IN 9. CELLS SHALL BE FILLED IN VERTICAL LIFTS OF 5 FEET IN HEIGHT OR LESS. CONCRETE GROUT PLACEMENT SHALL BE
HIGH POINT H.P. TOP OF WALL T.O.W. 21. PROPER ACCESSORIES (CHAIRS, BOLSTERS, DOBIES, STANDEES OR OTHER SUPPORTS) ARE TO BE USED AND
ACCORDANCE WITH THE REFERENCED GEOTECHNICAL INVESTIGATION REPORT. STOPPED 1 1/2" FROM THE TOP OF A BLOCK COURSE. GROUT LIFT HEIGHT MAY BE INCREASED TO 6 FEET IF PROPER
HORIZONTAL HORIZ. TOTAL LOAD TL SHALL BE NOTED ON THE SHOP DRAWINGS FOR APPROVAL. DRIVING REINFORCING STEEL BARS INTO THE GROUND
2. CONTRACTOR SHALL PROVIDE COPIES OF ALL COMPACTION TESTS FOR EACH LIFT OF FILL PLACED TO HOLLAND CLEANOUTS ARE PROVIDED IN THE BOTTOM COURSE.
TRANSVERSE TRAN. SHALL NOT BE PERMITTED UNLESS SPECIFICALLY DETAILED. CLAY BRICK PRODUCTS ARE NOT ACCEPTABLE FOR
ENGINEERING, LLC. NO LIABILITY, EITHER EXPRESSED OR IMPLIED, SHALL BE ASSUMED BY HOLLAND 10. WHERE REQUIRED, VERTICAL REINFORCING SHALL BE CONTINUOUS OR LAP-SPLICED 48 BAR DIAMETERS OR 2'-8",
INFORMATION INFO. TYPICAL TYP. CHAIRING REINFORCING. ALL REINFORCING SHALL BE SECURELY AND ACCURATELY HELD IN LOCATIONS SHOWN IN
ENGINEERING, LLC FOR THE BEHAVIOR OF THE FOUNDATION SYSTEM CONSTRUCTED ON UNCONTROLLED OR WHICHEVER IS GREATER.
INSIDE DIAMETER I.D. THE DRAWINGS.
UNTESTED FILL. 11. VERTICAL REINFORCING BARS SHALL BE HELD IN PLACE AT THE TOP AND BOTTOM OF EA. LIFT WITH VERTICAL BAR
INSIDE FACE I.F. UNLESS NOTED OTHERWISE U.N.O. 22. CAST-IN-PLACE CONCRETE ON THE GROUND SHALL HAVE A THICKNESS TOLERANCE OF (-) 1/4" TO (+) 1".
3. ALL SITE PREPARATION, INCLUDING BUT NOT LIMITED TO SURFACE AND SUBSURFACE GROUNDWATER DRAINAGE, POSITIONERS. "STABBING" OF REINFORCING INTO GROUTED CELLS SHALL NOT BE PERMITTED.
INTERIOR INT. 23. REINFORCING STEEL SUBMITTALS SHALL SPECIFICALLY INCLUDE PLAN LAYOUT AND ELEVATION VIEWS OF EACH
SHALL BE AS DESIGNED AND SPECIFIED BY THE GEOTECHNICAL ENGINEER AND/OR CIVIL ENGINEER. 12. IN CONCRETE ELEMENTS SUPPORTING CONCRETE MASONRY WALLS, EMBED DOWELS TO MATCH THE SIZE,
INTERMEDIATE INTERM. VERTICAL VERT. GRADE BEAM OR WALL ASSEMBLY ALONG WITH SECTION DETAILS FOR GRADE BEAMS, PLINTHS, AND FOOTINGS.
4. CONTRACTOR AND/OR OWNER SHALL PROVIDE FOR DRAINAGE ASSESSMENTS AND OBTAIN SITE GRADING LOCATION AND SPACING OF VERTICAL MASONRY REINFORCING. DOWELS SHALL BE LAP-SPLICED 48 BAR DIAMETERS
24. CONCRETE MIX DESIGN SUBMITTALS SHALL CLEARLY INDICATE THE INTENDED USE OF EACH PROPOSED MIX.
RECOMMENDATIONS FROM A LICENSED PROFESSIONAL CIVIL ENGINEER. HOLLAND ENGINEERING, LLC SHALL NOT OR 2'-8" WITH VERTICAL REINFORCING BARS.
JOINT JT. WATERSTOP W.S. 25. AGGREGATE AND MATERIAL TEST DATA SHALL BE CURRENT (WITHIN THE PAST 6 MONTHS).
BE HELD LIABLE FOR THE SITE GRADING AND DRAINAGE. 13. HORIZ. REINFORCING IN BOND BEAMS SHALL BE LAP-SPLICED 36 BAR DIAMETERS OR 2'-8", WHICHEVER IS GREATER.
JOIST(S) JST WEIGHT WT. 26. CONCRETE MIX DESIGN AND REINFORCING STEEL SUBMITTALS FOR ITEMS DETAILED ON THE STRUCTURAL
5. WATER SHALL NOT BE ALLOWED TO COLLECT IN OR NEAR FOOTING EXCAVATIONS. 14. HORIZ. JOINT REINFORCEMENT SHALL BE PREFABRICATED TRUSS OR LADDER TYPE. HORIZ. WALL REINFORCEMENT
JOIST BEARING JST. BRNG. WELDED WIRE MESH (FABRIC) W.W.F. DRAWINGS SHALL BE SUBMITTED SEPARATE FROM ITEMS DETAILED ON THE ARCHITECTURAL OR CIVIL DRAWINGS.
6. PROPER DRAINAGE SHALL BE COORDINATED WITH THE CIVIL AND/OR GEOTECHNICAL ENGINEER DURING SHALL HAVE 16" MINIMUM SIDE ROD LAPS WHERE SPLICING IS NECESSARY. HORIZ. JOINT REINFORCEMENT SHALL BE
WIND BRACE W.B.
SUBGRADE PREPARATION. INSTALLED AT 16"o.c.
KIPS K WIND LOAD WL
15. LINTELS SHALL BEAR ON MASONRY WALLS A MIN. OF 8" AT EA. END. LINTELS AND JAMBS SHALL BE AS SCHEDULED.
KNEE BRACE K.B. WITH W/ STRUCTURAL STEEL:
FOR LINTEL SPANS IN EXCESS OF 6 FEET, PROVIDE SHORING AT MID-SPAN UNTIL MASONRY AND POURED CONCRETE
KIPS PER SQUARE INCH KSI WOOD WD. 1. STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992, GRADE 50. OTHER STEEL SHAPES,
FOUNDATIONS AND SLABS ON GRADE GROUT HAVE CURED COMPLETELY.
WORK POINT W.P. PLATES, ANGLES, AND CHANNELS SHALL CONFORM TO ASTM A36, GRADE 36.
1. FOUNDATION DESIGN IS BASED ON A GEOTECHNICAL INVESTIGATION PERFORMED BY GEO CONSULTANTS, HALLSVILLE, 16. ALL STEEL LINTELS FOR BRICK VENEER SHALL BE AS SCHEDULED. FOR LINTEL SPANS IN EXCESS OF 6 FEET, PROVIDE
LARGER THAN OR EQUAL TO >= 2. STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500, GRADE B (46 KSI) FOR SQUARE OR RECTANGULAR
TEXAS, PROJECT NO. 2015, DATED MAY, 2020, AND ALL SUPPLEMENTAL ADDENDA. SHORING AT MID-SPAN UNTIL BRICK MORTAR HAS CURED.
LEAN-TO FRAME LTF X-BRACING X.B. TUBES AND (42 KSI) FOR ROUND TUBES AND STEEL PIPE SHALL CONFORM TO ASTM A53, TYPE E, GRADE B (36 KSI).
LESS THAN OR EQUAL TO <= 2. FOUNDATION DESIGN IS BASED ON THE FOLLOWING ALLOWABLE BEARING CAPACITIES: 3. STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN ACCORDANCE WITH THE LATEST AISC
TOTAL LOAD ----------------- 8000 PSF COLD-FORMED METAL (LIGHT GAGE STEEL) FRAMING
SPECIFICATIONS, UNLESS NOTED OTHERWISE. 1. LIGHT GAGE STEEL STUDS, JOISTS AND ACCESSORIES SHALL BE OF THE TYPE, SIZE, GAGE, AND SPACING INDICATED
FOR ISOLATED SPREAD FOOTINGS AT A DEPTH OF 5 FEET BELOW FINAL ADJACENT GRADE AND 4. STRUCTURAL STEEL CONNECTIONS NOT DETAILED SHALL BE AISC STANDARD, SIMPLE, SHEAR CONNECTIONS.
TOTAL LOAD ----------------- 5500 PSF IN THE DRAWINGS. STUDS, RUNNER TRACKS, RACING & BRIDGING SHALL BE MANUF. IN ACCORDANCE W/ ASTM C955.
CONNECTIONS SHALL BE DESIGNED AND DETAILED IN ACCORDANCE WITH THE AISC MANUAL OF STEEL 2. PHYSICAL PROPERTIES AND ALLOWABLE LOAD CAPACITIES OF MEMBERS SHALL BE DEVELOPED IN ACCORDANCE WITH
FOR CONTINUOUS STRIP FOOTINGS AT A DEPTH OF 5 FEET BELOW FINAL ADJACENT GRADE. CONSTRUCTION, THIRTEENTH EDITION, TABLES 10-1 AND 10-3. BEAM REACTIONS SHALL BE AS LISTED IN THE
3. FOOTING EXCAVATIONS SHALL BE CLEANED AND HAND-TAMPED TO A UNIFORM SURFACE. THE LATEST EDITION OF THE AISI "SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS."
DRAWINGS. WHERE NO REACTIONS ARE INDICATED, CONNECTIONS SHALL BE WELDED OR BOLTED EQUAL TO ALL MEMBER AND CONNECTION DESIGN SHALL BE IN ACCORDANCE WITH THIS AISI SPECIFICATION. ALL MEMBER SIZE
4. FOOTING EXCAVATIONS SHALL BE DRY AND CLEAN WHEN CONCRETE IS PLACED.

H ospi ality
ONE-HALF THE AISC BEAM TABLE VALUE FOR THE CORRESPONDING SPAN. IN NO CASE SHALL THE BEAM END DESIGNATIONS HAVE BEEN BASED ON THE PROPERTIES AND NOMENCLATURE OF SSMA.
5. IF FOUNDATION CONDITIONS ARE NOTED DURING CONSTRUCTION THAT DIFFER FROM THE REFERENCED REACTION BE TAKEN LESS THAN 12 KIPS. THE MINIMUM NUMBER OF ROWS OF BOLTS SHALL BE THE BEAM DEPTH
GEOTECHNICAL INVESTIGATION, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT, STRUCTURAL ENGINEER, AND 3. GALVANIZED STUDS, JOISTS, AND ACCESSORIES OF 12 TO 16 GAGE (97 mil to 54 mil) THICKNESS SHALL BE FORMED
DIVIDED BY 6, WITH FRACTIONS ROUNDED UP. FROM STEEL THAT CONFORMS TO THE REQUIREMENTS OF ASTM A653 AND C955, WITH A YIELD STRESS OF 50 KSI AND
GEOTECHNICAL ENGINEER BEFORE ANY FURTHER FOUNDATION CONSTRUCTION IS ATTEMPTED. 5. ALL SHEAR PLATES SHALL BE CUT THROUGH TUBE OR PIPE COLUMNS FOR BEAM CONNECTION.

Health
AS SET FORTH IN AISI SPECIFICATION. 18 TO 20 GAGE (43 mil TO 33 mil) MEMBERS SHALL HAVE A YIELD STRESS OF 33
6. CONTRACTOR SHALL NOTIFY STRUCTURAL ENGINEER 48 HOURS PRIOR TO PLACEMENT OF CONC.
7. HOLLAND ENGINEERING, LLC, STRUCTURAL ENGINEER OF RECORD, STRONGLY RECOMMENDS CONTRACTOR ENGAGE
SERVICES OF SER FOR SITE OBSERVATION OF REINFORCING STEEL FOR FOOTINGS, GRADE BEAMS, AND SLAB
PRIOR TO CONCRETE PLACEMENT.
6. SIMPLE SHEAR CONNECTIONS FOR BEAMS SHALL BE STANDARD, DOUBLE-ANGLE CONNECTIONS, UNLESS NOTED
OR DETAILED OTHERWISE.
7. ALL BOLTS SHALL BE ASTM A325 HIGH STRENGTH BOLTS (BEARING TYPE), EXCEPT ANCHOR RODS SHALL BE ASTM
F1554, GRADE 36. PROVIDE 2 NUTS AND 1 WASHER FOR EA. ANCHOR ROD.
KSI IN ACCORDANCE WITH ASTM A653 AND C955. GALVANIZED MEMBERS SHALL HAVE A MINIMUM G-60 COATING
CONFORMING TO ASTM A653 AND C955.
4. WELDING OF LIGHT GAGE STEEL MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF AWS AND AISI. ALL WELDS
R
8. WHERE CONCRETE SLAB ON GRADE IS TO RECEIVE SENSITIVE ARCHITECTURAL FINISHES OR TO BE EXPOSED, SHALL BE MADE ONLY BY QUALIFIED WELDERS. ALL FIELD WELDS SHALL BE COATED WITH A COLD-GALVANIZING
8. GROUT FOR BASE PLATES SHALL BE NON-SHRINK, NON-METALLIC, CONFORMING TO ASTM C-1107, AND SHALL COMPOUND.
CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL JOINTS TO ALIGN WITH JOINTS IN THE FINISHED HAVE A MINIMUM COMPRESSIVE STRENGTH OF 5000 PSI AT 28 DAYS. 5. ALL STUDS SHALL HAVE FULL BEARING AT TOP AND BOTTOM TRACKS.
SURFACE. CONTRACTOR SHALL TAKE ALL PRECAUTIONS NECESSARY TO PROTECT SURFACES THAT WILL REMAIN
EXPOSED AFTER CONSTRUCTION.
9. ALL WELDS SHALL BE MADE ONLY BY PREQUALIFIED WELDERS.
10. ALL WELDING SHALL CONFORM TO RECOMMENDATIONS OF A.W.S. USING E70XX ELECTRODES, EXCEPT JOISTS
6. PROVIDE LATERAL BRACING AT 4'-0"o.c. MAX. FOR ALL LOAD BEARING WALLS. HOSPITALITY
7. PROVIDE FULL HEIGHT SHEATHING ON EA. SIDE OF ALL NON-LOAD BEARING WALLS OR PROVIDE LATERAL BRACING AS
SHALL MEET S.J.I. SPECS.
11. STRUCTURAL STEEL MEMBERS SHALL NOT BE SPLICED WITHOUT PRIOR APPROVAL OF STRUCTURAL ENGINEER
DETAILED. PROVIDE 1 ROW OF LATERAL BRACING WITHIN 1'-0" OF ALL SLIP TRACK ASSEMBLIES.
8. SPLICING OF LIGHT GAGE STEEL MEMBERS SHALL NOT BE PERMITTED, UNLESS DETAILED OTHERWISE.
HEALTH ER
OF RECORD AS TO LOCATION AND TYPE OF CONNECTION. EXISTING =
9. CUTTING OF LIGHT GAGE STEEL MEMBERS SHALL BE PERFORMED WITH A SAW. TORCH CUTTING SHALL NOT BE
HELICAL SCREW PILE SPECIFICATION
1. HELICAL PIERS SHALL BE MANUFACTURED BY ONE OF THE FOLLOWING:
12. PENETRATIONS SHALL NOT BE CUT IN STRUCTURAL STEEL MEMBERS WITHOUT PRIOR APPROVAL OF
STRUCTURAL ENGINER OF RECORD.
PERMITTED. NEW = TYLER
A. MACLEAN DIXIE, LLC. 10. HOLES THAT ARE FIELD CUT THROUGH LIGHT GAGE STEEL MEMBERS SHALL BE MADE WITHIN THE LIMITATIONS OF THE
B. HUBBELL POWER SYSTEMS, INC. (CHANCE HELICAL PIERS)
C. THE IDEAL GROUP
13. THE CONTRACTOR SHALL NOTIFY HOLLAND ENGINEERING, LLC OF ANY MISFABRICATED STEEL PRIOR TO
ERECTION OF SAME. MODIFICATION OF MEMBERS BY TORCH CUTTING WILL NOT BE ALLOWED.
PRODUCT DESIGN AND SHALL BE REINFORCED AS RECOMMENDED BY THE MANUFACTURER.
11. ALL LIGHT GAGE STEEL FRAMING STUDS SHALL HAVE 1 5/8" FLANGE WIDTHS, UNLESS NOTED OR DETAILED
EXPANSION
14. BOLT HOLES SHALL BE DRILLED OR PUNCHED. MODIFICATION OF BOLT HOLES BY TORCH CUTTING WILL NOT BE OTHERWISE. WALL STUDS SHALL BE SPACED AT 16"o.c. UNLESS NOTED OR DETAILED OTHERWISE.
D. RAM JACK SYSTEMS ALLOWED. 12. ALL CONNECTORS FOR LIGHT GAGE FRAMING SHALL BE AS DETAILED. NO SUBSTITUTIONS ALLOWED.
E. PIERTECH SYSTEMS, LLC 15. ALL STRUCTURAL STEEL MEMBERS SHALL BE SHOP-PRIMED, UNLESS NOTED OR DETAILED OTHERWISE. 13. ALL FASTENERS FOR LIGHT GAGE FRAMING NOTED AS "TEK" SCREWS SHALL BE SELF-DRILING, SELF-TAPPING SCREWS,
Tyler, Texas
2. PIERS SHALL BE INSTALLED BY AN AUTHORIZED INSTALLING CONTRACTOR WHO HAS SATIFIED THE CERTIFICATION ALL STRUCTURAL STEEL MEMBERS NOTED AS GALVANIZED IN THE PLANS AND DETAILS SHALL BE HOT-DIPPED
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

REQUIREMENTS RELATING TO THE TECHNICAL ASPECTS OF THE PRODUCT AND THE ASCRIBED INSTALLATION AS MANUFACTURED BY ITW BUILDEX OR HILTI NORTH AMERICA. ALL FASTENERS FOR LIGHT GAGE FRAMING NOTED AS
GALVANIZED WITH COATING DESIGNATION G90. ALL FIELD WELDS OF GALVANIZED MEMBERS SHALL BE COATED "POWDER ACTUATED FASTENER" OR "PAF" SHALL BE AS MANUFACTURED BY HILTI NORTH AMERICA, UNLESS NOTED OR
TECHNIQUES. PROOF OF CURRENT CERTIFICATION BY SUPPLIER MUST BE PROVIDED. WITH COLD GALVANIZING COMPOUND.
3. ALL WORK AS DESCRIBED HEREIN SHALL BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE SAFETY CODES IN DETAILED OTHERWISE.
16. TEMPORARY CONSTRUCTION BRACING OF STRUCTURAL STEEL FRAMING SHALL REMAIN IN PLACE UNTIL ALL 14. FOR WOOD SHEAR PANELS APPLIED TO LIGHT GAGE WALL STUDS, PROVIDE BLOCKING AT ALL WOOD PANEL EDGES.
EFFECT AT THE TIME OF INSTALLATION. FLOOR, ROOF AND WIND BRACING CONNECTIONS AND ATTACHMENTS ARE COMPLETED.
4. HELICAL PIERS SHALL CONFORM TO THE INTERNATIONAL BUILDING CODE LISTED HEREIN. AN OFFICIAL EVALUATION BLOCKING MAY BE PIECES OF STUD OR TRACK CUT TO FIT OR FLAT STRAP MATERIAL. FLAT STRAPPING SHALL BE A
17. STEEL SUPPLIER/ERECTOR BASE BID SHALL INCLUDE A LINE ITEM FOR AN ADDITIONAL 1 TON OF MINIMUM OF 1 1/2" WIDE WITH SAME GAGE THICKNESS AS WALL STUDS. FASTENERS SHALL BE #8x1" TEK SCREWS (FLAT
REPORT WITH ASSIGNED NUMBER SHALL BE PRESENTED UPON REQUEST TO THE OWNER AND/OR ITS DETAILED/FABRICATED STEEL TO BE SIZED AND LOCATED AT THE DIRECTION OF STRUCTURAL ENGINEER. LINE
REPRESENTATIVE. ICC-ES AC358 ESR 3032. HEAD) WITH A MINIMUM HEAD DIAMETER OF 0.292". FILE NAME:
ITEM COST OF THIS STEEL SHALL BE SPECIFICALLY LISTED ON BASE BID. IF THE ADDITIONAL STEEL IS NOT 15. ALL ROOF AND FLOOR FRAMING TRUSSES, RAFTERS, PURLINS, JOISTS, ETC. SHALL ALIGN WITH WALL STUDS BELOW.
5. THE HELICAL LEAD SECTIONS AND EXTENSION SECTIONS SHALL BE: SOLID STEEL, ROUND CORNERED, SQUARE SHAFT; NEEDED OR IS ONLY PARTIALLY NEEDED, OWNER SHALL BE GIVEN A CREDIT BASED ON THE SAME UNIT COST.
ROUND, STEEL PIPE SHAFT; OR COMPOSITE STEEL AND GROUT SHAFT, CONFIGURED WITH ONE OR MORE HELICAL ADJUST WALL STUD SPACING AS REQUIRED TO MATCH FRAMING MEMBER LAYOUTS. 20-019-STRUCTURAL
BEARINGPLATES WELDED TO THE SHAFT.
6. ALL PIERS MUST BE CORROSION PROTECTED BY HOT DIP GALVANIZATION. PROJECT NUMBER:
7. INSTALLATION UNITS SHALL CONSIST OF A ROTARY-TYPE, TORQUE MOTOR WITH FORWARD AND REVERSE
CAPABILITIES. THESE UNITS ARE TYPICALLY POWERED.
1909
8. INSTALLATION UNITS SHALL BE CAPABLE OF DEVLOPING THE MINIMUM TORQUE, AS REQUIRED.
9. INSTALLATION UNITS SHALL BE CAPABLE OF POSITIONING THE HELICAL PIER AT THE PROPER INSTALLATION ANGLE. SHEET CONTENTS:
THIS ANGLE MAY VARY BETWEEN VERTICAL AND FIVE (5) DEGREES, DEPENDING UPON APPLICATION AND TYPE OF GENERAL NOTES
LOAD TRANSFER DEVICE SPECIFIED OR REQUIRED.
10. INSTALLATION TORQUE SHALL BE MONITORED AND DOCUMENTED THROUGHOUT THE INSTALLATION PROCESS AND
COPIES OF ALL TORQUE LOGS SHALL BE PROVIDED TO SER FOR RECORD COPY.
11. HELICAL PIERS SHALL BE INSTALLED TO THE MINIMUM TORQUE VALUE REQUIRED TO PROVIDE THE LOAD CAPACITIES
REQUIRED BY THE PLANS. ENGINEERING SERVICES, IF REQUIRED, SHALL BE PROVIDED BY THE PIER
SUPPLIER/INSTALLER.
12. THE APPROPRIATE STEEL NEW CONSTRUCTION LOAD TRANSFER DEVICE SHALL BE USED.
13. APPROPRIATE HELICAL PIER SELECTION WILL CONSIDER DESIGN LOAD PLUS SAFETY FACTOR, SOIL PARAMETERS AND
THE INSTALLATION TORQUE VS. CAPACITY EQUATION, AS PER THE MANUFACTURER'S RECOMMENDATIONS.
14. TEST PIERS, WHEN REQUIRED, SHALL BE PERFORMED AT NO ADDITIONAL COST TO THE OWNER. TEST PIERS SHALL
NOT BE INCORPORATED INTO THE FINAL ASSEMBLY.

1 KEY PLAN
S0.1 SCALE: NONE

S
0.1
9/11/2020 11:15:41 AM

VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION (IBC 1705.4)


IBC 2015 SPECIAL INSPECTION REQUIREMENTS
1. IN ACCORDANCE WITH SECTION 1704, THE OWNER OR THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE (RDPiRC) ACTING AS THE OWNER'S AGENT INSPECTION REFERENCE
INSPECTION OR TEST TYPE COMMENTS
SHALL EMPLOY ONE OR MORE APPROVED AGENCIES TO PERFORM INSPECTIONS DURING CONSTRUCTION ON THE TYPES OF WORK LISTED UNDER SECTION 1705. MARK TMS 602/ACI 530.1/ASCE 6
SPECIAL INSPECTIONS ARE IN ADDITION TO THE INSPECTIONS IDENTIFIED IN SECTION 110.
VERIFY SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) AS DELIVERED TO THE ART. 1.5B.1.b.3
2. SPECIAL INSPECTION WORK AND THE FINAL LETTER OF COMPLIANCE HAVE NOT BEEN INCLUDED IN THE STRUCTURAL ENGINEER OF RECORD'S (SER) SCOPE OF PROJECT SITE FOR SELF-CONSOLIDATING GROUT
SERVICES. PERIODIC SITE OBSERVATIONS PERFORMED BY SER ARE MADE FOR GENERAL CONFORMANCE PURPOSES AND SHALL NOT BE CONSIDERED SPECIAL
INSPECTIONS. VERIFY f'm COMPLIANCE WITH CONSTRUCTION DOCUMENTS TEST EACH TYPE OF MASONRY ART. 1.4B
3. SPECIAL INSPECTORS AND TESTING TECHNICIANS SHALL NOT BE EMPLOYED BY THE GENERAL CONTRACTOR, SUBCONTRACTORS, OR MATERIAL SUPPLIERS. SPECIAL
P VERIFY COMPLIANCE WITH APPROVED SUBMITTALS WEEKLY DURING MASONRY CONSTRUCTION ART. 1.5
INSPECTOR QUALIFICATIONS SHALL BE SUBMITTED TO AND APPROVED BY THE LOCAL BUILDING OFFICIAL.
4. ARRANGEMENTS FOR SPECIAL INSPECTIONS SHALL BE MADE PRIOR TO COMMENCEMENT OF CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR NOTIFYING SPECIAL P VERIFY PROPORTIONS OF SITE PREPARED MORTAR PRIOR TO START OF EACH LIFT ART. 2.1 & 2.6A
INSPECTOR IN A TIMELY MANNER BEFORE CONSTRUCTION ACTIVITIES CONTINUE. CONTRACTOR SHALL NOT PROCEED WITH ANY WORK REQUIRING INSPECTIONS
WITHOUT THE PRESENCE OF A SPECIAL INSPECTOR. P VERIFY CONSTRUCTION OF MORTAR JOINTS PRIOR TO START OF EACH LIFT ART. 3.3B
5. SPECIAL INSPECTORS SHALL MAINTAIN RECORDS OF INSPECTIONS. REPORTS SHALL INDICATE WHETHER WORK WAS OR WAS NOT COMPLETED IN CONFORMANCE WITH P VERIFY SIZE AND LOCATION OF STRUCTURAL ELEMENTS PRIOR TO START OF EACH LIFT ART. 3.3F
THE APPROVED CONSTRUCTION DOCUMENTS. CONTRACTOR SHALL BE NOTIFIED IMMEDIATELY OF ANY DISCREPANCIES THAT REQUIRE CORRECTION. DISCREPANCIES
09/11/2020
NOT CORRECTED SHALL BE BROUGHT TO THE ATTENTION OF THE LOCAL BUILDING OFFICIAL AND THE RDPiRC PRIOR TO COMPLETION OF THAT PHASE OF WORK. P VERIFY PROPER PLACEMENT, SIZE, GRADE, TYPE, AND LOCATION OF PRIOR TO START OF EACH LIFT ART. 2.4, 3.2E, 3.4 & 3.6A
6. ALL SPECIAL INSPECTION REPORTS SHALL BE SUBMITTED TO THE LOCAL BUILDING OFFICIAL, RDPiRC, ARCHITECT, AND ENGINEER OF RECORD FOR EACH DISCIPLINE OF REINFORCEMENT, CONNECTORS, AND ANCHORAGES
WORK INSPECTED. P VERIFY PROTECTION OF MASONRY DURING COLD WEATHER (TEMPERATURE ONE EACH OCCURRENCE ART. 1.8C & 1.8D
7. CONTINUOUS SPECIAL INSPECTION SHALL BE DEFINED AS THE FULL-TIME OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL BELOW 40°F) OR HOT WEATHER (TEMPERATURE ABOVE 90°F)
INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK IS BEING PERFORMED.
8. PERIODIC SPECIAL INSPECTION SHALL BE DEFINED AS THE PART-TIME OR INTERMITTENT OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED P VERIFY PROPORTIONS OF SITE-PREPARED GROUT PRIOR TO START OF EACH LIFT ART. 2.6B & 2.4G.1.b
SPECIAL INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK HAS BEEN, OR IS BEING, PERFORMED AND AT THE COMPLETION OF THE WORK.
9. REFER TO IBC SECTIONS 1704 AND 1705 AND ANY LOCAL JURISDICTION AMENDMENTS FOR ALL SPECIAL INSPECTION REQUIREMENTS. P VERIFY PROPER GROUT SPACING AND CLEANLINESS OF CELL PRIOR TO GROUTING PRIOR TO START OF EACH LIFT ART. 3.2D & 3.2F THACKER | DAVIS ARCHITECTS
I N C O R P O R A T E D
C OBSERVE AND VERIFY GROUT PLACEMENT IS IN COMPLIANCE WITH CODE AND ART. 3.5 & 3.6C Member American Institute of Architects
THE FOLLOWING SPECIAL INSPECTIONS IN TABLE FORM ARE REQUIRED ONLY IF MARKED WITH "X", "C", OR "P".
CONSTRUCTION DOCUMENT PROVISIONS .
1100 Judson Rd., Suite 620 PO Box 2723

X - INSPECTION IS REQUIRED, ONE TIME OCCURRENCE P OBSERVE PREPARATION OF ANY REQUIRED GROUT SPECIMENS, MORTAR ART. 1.4B.2.a.3, Longview, Texas 75606-2723

SPECIMENS, OR PRISMS 1.4B.2.b.3,


.
Phone 903.236.3771 Fax 903.753.7317
C - INSPECTION IS REQUIRED AND SHALL BE CONTINUOUS
P - INSPECTION IS REQUIRED AND SHALL BE PERIODIC 1.4B.2.c.3, 1.4B.3, 1.4B.4 Email: T D A @ T - D A r c h i t e c t s . c o m
INSPECTION MARK FIELDS LEFT BLANK ARE NOT REQUIRED FOR THIS PROJECT. w w w . T - D A r c h i t e c t s . c o m

VERIFICATION AND INSPECTION OF WOOD FRAMING (IBC 1705.5)


VERIFICATION AND INSPECTION OF STRUCTURAL STEEL CONSTRUCTION (IBC 1705.2.1) INSPECTION
INSPECTION OR TEST TYPE COMMENTS REFERENCE
INSPECTION MARK
INSPECTION OR TEST TYPE COMMENTS REFERENCE
MARK P VERIFY ROOF SHEATHING OF PROPER GRADE AND THICKNESS & VERIFY
X REVIEW FABRICATOR'S FABRICATION AND QUALITY CONTROL PROCEDURES IBC 1704.2.5 SHEATHING FASTENER ATTACHMENT OF PROPER SIZE & SPACING
P TRUSS SPANS OF 60 FEET OR GREATER, VERIFY TEMPORARY
P VERIFY IDENTIFICATION MARKINGS FOR HIGH-STRENGTH BOLTS, NUTS, & APPLICABLE ASTM STD. RESTRAINT/BRACING & PERMANENT TRUSS MEMBER RESTRAINT/BRACING
WASHERS CONFORM TO ASTM STANDARDS SPECIFIED ON APPROVED & GENERATOR FOUNDATION PLAN NOTES: STRUCTURAL ENGINEER:
CONSTRUCTION DOCUMENTS AISC 360 1. REFER TO SHEET S0.1 FOR GEN. NOTES.
P VERIFICATION AND INSPECTION OF SOILS (IBC 1705.6) 2. REFERENCE FINISH SLAB ELEVATION = 0''-0". ACTUAL FINISH GRADE ELEVATION = FIELD VERIFY.
REVIEW MANUFACTURER'S CERTIFICATE OF COMPLIANCE FOR HIGH-STRENGTH ASTM
BOLTS, NUTS, AND WASHERS INSPECTION 3. CONCRETE SLAB SHALL BE 8" THICK, REINFORCED WITH #5 @ 12"o.c. EA. WAY AT MID-DEPTH OF SLAB.
INSPECTION OR TEST TYPE COMMENTS REFERENCE 4. PLACE SLAB OVER PREPARED SUBGRADE APPROVED BY A LICENSED GEOTECHNICAL ENGINEERING AGENCY.
P INSPECTION OF HIGH-STRENGTH, SNUG-TIGHTENED, BEARING-TYPE BOLTED VERIFY CONNECTED MATERIALS ARE SNUG AND AISC 360 MARK
5. COORD. EQUIPMENT LOCATION W/ OWNER AND SUPPLIER.
CONNECTIONS DRAWN TOGETHER AND VERIFY ALL BOLTS ARE P VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE REFER TO PROJECT GEOTECHNICAL REPORT 6. COORD. ALL PENETRATIONS THRU SLAB WITH EQUIPMENT SUPPLIER.
INSTALLED THE DESIGN BEARING CAPACITY 7. COORD. ANCHORAGE OF EQUIPMENT W/ EQUIPMENT SUPPLIER.
X VERIFY IDENTIFICATION MARKINGS FOR STRUCTURAL STEEL CONFORM TO ASTM APPLICABLE ASTM STD. 8. CONTRACTOR SHALL WORK GRADING TO PROVIDE POSITIVE DRAINAGE AWAY FROM NEW SLAB ON ALL SLABS.
P VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED REFER TO PROJECT GEOTECHNICAL REPORT
STANDARDS SPECIFIED ON APPROVED CONSTRUCTION DOCUMENTS &
PROPER MATERIAL
AISC 360
P PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS REFER TO PROJECT GEOTECHNICAL REPORT NOTE:
X REVIEW STRUCTURAL STEEL MILL CERTIFICATES AND TEST REPORTS ASTM A6
C VERIFY USE OF PROPER MATERIALS, DENSITIES, AND LIFT THICKNESSES DURING REFER TO PROJECT GEOTECHNICAL REPORT FOUNDATION DESIGN & LAYOUT INFORMATION
X VERIFY IDENTIFICATION MARKINGS FOR WELD FILLER MATERIAL CONFORM TO AWS / AISC 360 CONTAINED HEREIN IS BASED ON EQUIPMENT &
PLACEMENT AND COMPACTION OF FILL Physical: 16291 FM 849
AWS STANDARDS SPECIFIED ON APPROVED CONSTRUCTION DOCUMENTS SITE INFORMATION PROVIDED BY RICK WATSON, Mail: P.O. BOX 2428
P PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE SUBGRADE AND VERIFY REFER TO PROJECT GEOTECHNICAL REPORT P.E. WITH PURTLE AND ASSOCIATES, L.C.. Lindale, Texas 75771
X REVIEW MANUFACTURER'S CERTIFICATE OF COMPLIANCE FOR WELD FILLER AWS / AISC 360 THAT SITE HAS BEEN PREPARED PROPERLY Phone: 903.882.8503 / Fax 903.882.5318
MATERIAL WWW.HOLLANDENGR.COM
C INSPECTION OF COMPLETE AND PARTIAL PENETRATION GROOVE WELDS NONDESTRUCTIVE TESTING AWS D1.1/AISC 360 Texas Firm #: F-8474
8" SLAB PER NOTE #3 HE #: 20-019
C INSPECTION OF MULTIPASS FILLET WELDS NONDESTRUCTIVE TESTING AWS D1.1/AISC 360
C INSPECTION OF SINGLE-PASS FILLET WELDS > 5/16" NONDESTRUCTIVE TESTING AWS D1.1/AISC 360
13'-5 1/2"
P INSPECTION OF SINGLE-PASS FILLET WELDS < 5/16" AWS D1.1/AISC 360
P INSPECTION OF STEEL FRAME JOINT DETAILS FOR COMPLIANCE WITH APPROVED
CONSTRUCTION DOCUMENTS:
A. DETAILS SUCH AS BRACING AND STIFFENING
B. MEMBER LOCATIONS
C. APPLICATION OF JOINT DETAILS FOR EACH CONN.

VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION OTHER THAN STRUCTURAL STEEL NEW GENERATOR
15,592 LBS. 4
INSPECTION 3

5'-10"
INSPECTION OR TEST TYPE COMMENTS REFERENCE S0.2
MARK
S0.2
P VERIFY IDENTIFICATION MARKINGS FOR COLD-FORMED STEEL DECKING CONFORM APPLICABLE ASTM STD. &
TO ASTM STANDARDS SPECIFIED ON APPROVED CONSTRUCTION DOCUMENTS SDI QA/QC
P REVIEW MANUFACTURER'S CERTIFIED TEST REPORTS
P INSPECTION OF FLOOR AND ROOF DECK WELDS AWS D1.3/AISC 360
P INSPECTION OF FLOOR AND ROOF DECK MECHANICAL FASTENERS COORDINATE W/ MANUFACTURER'S PUBLISHED ANSI/SDI QA/QC-2011
LITERATURE AND ICC-ES REPORTS
P VERIFICATION OF WELDABILITY OF REINFORCING STEEL OTHER THAN ASTM A706 AWS D1.4/ACI 318
6'-8 3/4" 6'-8 3/4"

VERIFICATION AND INSPECTION OF OPEN-WEB STEEL JOISTS AND JOIST GIRDERS (IBC 1705.2.3)
INSPECTION
INSPECTION OR TEST TYPE COMMENTS REFERENCE
MARK
P VERIFY AND INSPECT END CONNECTIONS - BOLTED OR WELDED SJI SPECS. LISTED IN
1 FOUNDATION PLAN - 400KW GENERATOR
SECTION 2207.1 S0.2 SCALE: 1/2" = 1'-0"
BRIDGING - HORIZONTAL OR DIAGONAL
8" SLAB PER NOTE #3
P 1. STANDARD BRIDGING SJI SPECS. LISTED IN
SECTION 2207.1 18'-9"
P 2. BRIDGING THAT DIFFERS FROM THE SJI SPECIFICATIONS
LISTED IN SECTION 2207.1

VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION (IBC 1705.3)


INSPECTION
INSPECTION OR TEST TYPE COMMENTS REFERENCE
MARK
P INSPECTION OF REINFORCING STEEL, INCLUDING PRESTRESSING TENDONS, AND ONCE BEFORE PLACMENT OF CONCRETE FOR ACI 318: Ch. 20, 25.2,
PLACEMENT EACH POUR 25.3,
26.5.1-26.5.3
P INSPECTION OF ANCHORS CAST IN CONCRETE ONCE BEFORE PLACMENT OF CONCRETE FOR ACI 318: 17.8.2
EACH POUR
INSPECTION OF ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS

H ospi ality
C A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED ACI 318: 17.8.2.4 NEW GENERATOR 4

9'-7"
ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS 45,417 LBS.
P ACI 318: 17.8.2 S0.2
B. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN "A"
ABOVE
P VERIFYING USE OF REQUIRED DESIGN MIX EACH BATCH, EACH POUR ACI 318: Ch. 19, 26.4.3, 26.4.4 Health R
C PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH TESTS, ASTM C172 & C31 ACI
PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE 318:
OF THE CONCRETE 26.4.5, 26.12 3
C
P
INSPECTION OF CONCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES
VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES
ACI 318: 26.4.5
ACI 318: 26.4.7-26.4.9
S0.2 HOSPITALITY
P INSPECT FORMWORK FOR SHAPE, LOCATION, AND DIMENSIONS OF THE CONCRETE ACI 318: 26.10.1b HEALTH ER
MEMBER BEING FORMED
TYLER
6'-3" 6'-3" 6'-3"
EXPANSION
Tyler, Texas
FOUNDATION PLAN - 750KW GENERATOR
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

2
S0.2 SCALE: 1/2" = 1'-0"

FILE NAME:
SLAB PER PLAN NOTES SLAB PER PLAN NOTES
20-019-STRUCTURAL
NOTE: NOTE:
GENERATOR EQUIPMENT #4 SLAB DOWEL x 2'-6" GENERATOR EQUIPMENT #4 SLAB DOWEL x 2'-6" PROJECT NUMBER:
NOT SHOWN FOR CLARITY @ 18"o.c. NOT SHOWN FOR CLARITY @ 18"o.c. EA.

1'-6"

1'-6"
WAY 1909
FIN. FLR. FIN. FLR. SHEET CONTENTS:
EL. RE: PLAN EL. RE: PLAN

MAX.
GENERAL NOTES
6"

8"

8"
2'-0"

2'-0"
1'-6" MIN.

(3) #6 CONT. T&B (3) #6 CONT. T&B

#3 TIES @ 18"o.c. #3 TIES @ 18"o.c.

1'-6" 1'-6"

3 SECTION 4 SECTION
S0.2 SCALE: 3/4" = 1'-0" S0.2 SCALE: 3/4" = 1'-0"

S
0.2
9/11/2020 11:15:43 AM

EXISTING

NEW

WC1 WC2
WC2 09/11/2020

WC2
WC1 WC1 WALL COMPONENT AND CLADDING LOADING
WC1 WC2 WC2 (SERVICE LEVEL)
WALL ZONE 10 SF 100 SF 500 SF
THACKER | DAVIS ARCHITECTS
NEG. ZONE 4 -22.2PSF -19.2PSF -17.1 PSF I N C O R P O R A T E D
Member American Institute of Architects

WC3 WC3 WC3 WC3 NEG. ZONE 5 -27.3PSF -21.3 PSF -17.1 PSF .
1100 Judson Rd., Suite 620 PO Box 2723
Longview, Texas 75606-2723
POS. ZONE 4 & 5 20.5 PSF 17.5 PSF 15.4 PSF .
Phone 903.236.3771 Fax 903.753.7317

Email: T D A @ T - D A r c h i t e c t s . c o m
WC3 WC3 WC3 WC3 WC1 w w w . T - D A r c h i t e c t s . c o m

WC1 WC1 REDUCE WALL STUD SPACING AS INDICATED

WALL CORNER KEYNOTES:


• WALL CORNER 1 (WC1) - REDUCE STRUCTURAL ENGINEER:
STUD SPACING TO 12"o.c. WITHIN 5'-6"
WC1 WC1 • WALL CORNER 2 (WC2) - REDUCE
STUD SPACING TO 12"o.c. WITHIN 4'-0"
WC1 WC1 WC1
• WALL CORNER 3 (WC3) - REDUCE
STUD SPACING TO 12"o.c. IN REGION

1 WALL ZONES PLAN Physical: 16291 FM 849


Mail: P.O. BOX 2428
Lindale, Texas 75771
S0.3 SCALE: 1/16" = 1'-0" Phone: 903.882.8503 / Fax 903.882.5318
WWW.HOLLANDENGR.COM
Texas Firm #: F-8474
HE #: 20-019

1 2 3 3.5 4 4.7 5 6 6.3 6.8 7 8 9.5 9 10 11 12 13 14


EXISTING

NEW

I I ROOF DECK ATTACHMENT

2 36" WIDE ROOF DECK SHEETS SHALL BE ATTACHED AT END LAPS, END SUPPORTS, AND INTERMEDIATE
6'-0"

H H 36/4 DECK ATTACHMENT PATTERN SUPPORTS USING HILTI FASTENERS PER GENERAL NOTES, IN ACCORDANCE WITH THE FOLLOWING
PATTERNS:
G G 1 ATTACH ROOF DECK WITH 36/4 PATTERN. ATTACH SIDE LAPS TOGETHER WITH (1) SIDELAP
FASTENER AT MID-SPAN BTWN. JOIST SUPPORTS.
36/7 DECK ATTACHMENT PATTERN
F F 2 ATTACH ROOF DECK WITH 36/4 PATTERN. ATTACH SIDE LAPS TOGETHER WITH (2) SIDELAP
FASTENER AT MID-SPAN BTWN. JOIST SUPPORTS.
14'-0 5/16"

6'-11 9/16"
E E 3
ATTACH ROOF DECK WITH 36/7 PATTERN. ATTACH SIDE LAPS TOGETHER WITH (2) SIDELAP
FASTENER AT THIRD-PTS. BTWN. JOIST SUPPORTS.
6'-0"

1
D.8 D.8
D.7 2 2
D.7
D D
6'-0"

C.5 C.5
1 3
C C
2
B B
2 2
6'-0"

6'-0"
9'-4"

A A
AA 10'-4 1/2" 9'-0 3/8" 36'-0" 12'-0" 12'-7" AA

1 2 3 3.5 4 4.7 5 6 6.3 6.8 7 8 9.5 9 10 11 12 13 14


H ospi ality
2 LOW ROOF DECK ATTACHMENT PLAN
S0.3 SCALE: 1/16" = 1'-0"
Health R
1 2 3 3.5 4 4.7 5 6 6.3 6.8 7 8 9.5 9 10 11 12 1314 HOSPITALITY
EXISTING HEALTH ER
5'-2" 5'-2" NEW
ROOF NET UPLIFT COMPONENT AND CLADDING LOADING TYLER
5'-2"

3 2 3
ROOF FRAMING MEMBERS SHALL BE DESIGNED FOR THE
NET UPLIFT VALUES LISTED BELOW (SERVICE LEVEL
EXPANSION
LOADS, BASED ON 50 SQUARE FEET EFFECTIVE AREA):
2 2 ROOF ZONE WIND PRESSURE Tyler, Texas
5'-2" ZONE 1 -13.0 PSF
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

I I ZONE 2 -20.3 PSF


5'-2"

2 1 ZONE 3 -20.3 PSF


H 3 3
H
5'-2"

3 ZONE 2' N/A


G 5'-2"
G ZONE 3' N/A FILE NAME:
2 1
20-019-STRUCTURAL
F 2 F
5'-2"

3 2 3 PROJECT NUMBER:
E 2 2
E 6'-4" MECH. LIVE LOADS WHERE 7'-0" MECH. LIVE LOADS WHERE 1909
5'-2"

2 3
5'-2"

3 2 3 INDICATED ON PLAN INDICATED ON PLAN


D.8 D.8 27.2 PSF 4.2 PSF
BALANCED SNOW LOAD PLUS
37.1 PSF 4.2 PSF
BALANCED SNOW LOAD PLUS
SHEET CONTENTS:
5'-2" DECK ATTACHMENT
DRIFT AS SHOWN DRIFT AS SHOWN
D.7 3 3
D.7 PLAN/LOADS
UNIFORM SNOW = 6.0 PSF UNIFORM SNOW = 6.0 PSF
D D SEE UPLIFT WITHOUT DRIFT SEE UPLIFT WITHOUT DRIFT
5'-2"

3 2 3 LOADING PLAN LOADING PLAN

C.5 2 1 1 1 5'-2" C.5 WIND LOAD = SEE WIND NET WIND LOAD = SEE WIND NET
3 UPLIFT DIAGRAM UPLIFT DIAGRAM
C C
2 LIVE LOAD = 25 PSF LIVE LOAD = 25 PSF
B B
DEAD LOAD = 20 PSF DEAD LOAD = 20 PSF
5'-2"

2 3
A A SEE PLAN
5'-2"

3 2 3 SEE PLAN

BOTT. CHORD BEARING,


AA 5'-2" 5'-2" 5'-2" AA 10K1SP1/14K1SP1/16K3SP1/18K3SP1/ 20K5SP2 RE. PLAN

1 2 3 3.5 4 4.7 5 6 6.3 6.8 7 8 9.5 9 10 11 12 1314 20K4SP1/20K5SP1/26K5SP1/30K11SP1 S


3 LOW ROOF DECK UPLIFT LOAD PLAN 4 JOIST SP1 LOADING DIAGRAM 5 JOIST SP2 LOADING DIAGRAM 0.3
S0.3 SCALE: 1/16" = 1'-0" S0.3 SCALE: NONE S0.3 SCALE: NONE
9/11/2020 11:15:44 AM

09/11/2020

THACKER | DAVIS ARCHITECTS


I N C O R P O R A T E D
Member American Institute of Architects

.
1100 Judson Rd., Suite 620 PO Box 2723
Longview, Texas 75606-2723
.
Phone 903.236.3771 Fax 903.753.7317

Email: T D A @ T - D A r c h i t e c t s . c o m

w w w . T - D A r c h i t e c t s . c o m

STRUCTURAL ENGINEER:

Physical: 16291 FM 849


Mail: P.O. BOX 2428
Lindale, Texas 75771
Phone: 903.882.8503 / Fax 903.882.5318
WWW.HOLLANDENGR.COM
Texas Firm #: F-8474
HE #: 20-019

1 ISOMETRIC VIEW - NORTHWEST


S0.4 SCALE:

H ospi ality
Health R
HOSPITALITY
HEALTH ER
TYLER
EXPANSION
Tyler, Texas
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

FILE NAME:
20-019-STRUCTURAL

PROJECT NUMBER:
1909

SHEET CONTENTS:
ISOMETRIC

S
2 ISOMETRIC VIEW - SOUTHWEST
S0.4 SCALE: 0.4
9/11/2020 11:15:46 AM

FOUNDATION PLAN NOTES:


1. REFER TO SHEET S0.1 FOR GENERAL NOTES.
1 2 3 3.5 4 4.7 5 6 6.3 6.8 7 8 9.5 9 10 11 12 13 14 2. REFERENCE FINISH FLOOR ELEVATION = 100'-0". ACTUAL FINISH FLOOR ELEVATION = 528.0'.
3. F4, EXAMPLE, DENOTES FOOTING TYPE. (REFER TO SCHEDULE THIS SHEET.)
4. BP-1, EXAMPLE, DENOTES BASE PLATE TYPE AND ANCHOR RODS (REFER TO SHEET 1/S2.2)
5. 97'-0", EXAMPLE, DENOTES TOP OF FOOTING ELEVATION WITH RESPECT TO FINISH FLOOR.
6. REFER TO SHEET S2.1 FOR TYPICAL DETAILS NOT SPECIFICALLY SHOWN ON PLAN.
193'-3" 7. FD, EXAMPLE, DENOTES FLOOR DRAIN. COORD. LOCATION AND ELEVATION W/ ARCH'L. DRAWINGS.
8. COORD. ALL WALL LOCATIONS WITH ARCH'L. WALL LAYOUT PLANS.
10" 2'-10 15/16" 1'-6 9/16" 10"
20'-9" 10'-3" 4'-7 15/16" 9'-1 13/16" 3'-9 3/8" 25'-2 9/16" 6'-8 1/8" 13'-9 3/4" 21'-8 3/4" 16'-4 3/16" 8'-5 1/16" 2'-1" 10'-6" 6'-11 9/16" 22'-7 1/8" 4'-2 5/16"

VAPOR BARRIER NOTE:


20'-9" 11'-7 5/8" 6'-6 1/8" 38'-4" 82'-0" 29'-10" 4'-2 5/16"
FURNISH AND INSTALL 15 MIL. POLYETHYLENE MEMBRANE VAPOR BARRIER UNDER ALL INTERIOR SLABS
ON GRADE. VAPOR BARRIER SHEETS SHALL BE INSTALLED OVER LEVEL, COMPACTED, SUBGRADE WITH
4'-7 1/8" 25'-0" MINIMUM 6" JOINT LAPS. JOINT LAPS SHALL BE SEALED CONTINUOUSLY WITH MANUFACTURER'S TAPE. 09/11/2020
SEAL CAREFULLY AROUND ALL PIPES, CONDUITS, ETC., WHICH PENETRATE THE SLAB. SEAL ALL TEARS
AND PUNCTURES PRIOR TO PLACING CONCRETE.

FOOTING SCHEDULE

TYPE LENGTH WIDTH THICKNESS REINFORCING


F3 3'-0" 3'-0" 2'-0" (4) #5 BARS EA. WAY TOP & BOTT. THACKER | DAVIS ARCHITECTS
I N C O R P O R A T E D
M.J. 3 F3.5 3'-6" 3'-6" 2'-0" (4) #5 BARS EA. WAY TOP & BOTT. Member American Institute of Architects

S2.3 F4 4'-0" 4'-0" 2'-0" (5) #5 BARS EA. WAY TOP & BOTT. .
1100 Judson Rd., Suite 620 PO Box 2723
1 2

11'-9 5/8"
Longview, Texas 75606-2723
F4.5 4'-6" 4'-6" 2'-0" (5) #5 BARS EA. WAY TOP & BOTT. .
20'-0" 24'-0" 24'-0" 14'-7 5/8" S2.3 S2.3 Phone 903.236.3771 Fax 903.753.7317
F5 5'-0" 5'-0" 2'-0" (6) #5 BARS EA. WAY TOP & BOTT.
Email: T D A @ T - D A r c h i t e c t s . c o m
21'-5 13/16"

21'-5 13/16"
w w w . T - D A r c h i t e c t s . c o m
PLAN NOTE:
21'-2"

21'-2"
2 1 4 9
FIELD COORD. M.J.

25'-4 1/2"
S2.3 S2.3 S3.2 EXISTING FOUNDATION. S2.3
1
THICKENED SLAB PENDING S2.3

10'-0"
SELECTION OF WATER TANK HP-1
HSS6x6x1/4
EQUIPMENT - COORD. W/ ARCH & 11
SER PRIOR TO CONC. PLACEMENT BP-1
S2.3
I I STRUCTURAL ENGINEER:
4'-8 11/16"

4'-8 11/16"
13'-0" 20'-8 9/16" 5'-0" M.J. M.J. (3) #6 @ EA. SIDE M.J. 1'-6" FTG

5'-0"
HP-1 F3 HSS6x6x1/4
#6 VERT. FULL HT. IN (3) #6 VERT. @ EA. BM. OF M.J., TYP. EXTENSION ON (3) F3
HP-1 BP-2A
M.J. GROUT FILLED CELLS HSS6x6x1/4 SIDES AS DTL'D
H 2
@ 24"o.c., TYP. U.N.O.
BEARING LOCATION
ON 2ND FLR., TYP. BP-1B HSS6x6x1/4
4
H
RE: 4/S3.2 BP-1B (2) #4x4'-0" @ EA.
16'-8 7/8"

PLAN NOTE: S2.3 S1.1 RE-ENTRANT


12 HSS6x6x1/4 3 6
FIELD COORD. CORNER, TYP.
S2.3 S1.1 S2.3 FD
12'-3"

12'-3"
EXISTING FOUNDATION. BP-1B
TYPICAL CONCRETE SLAB NOTE:

25'-0"
10

4/S6.2
3 HSS6x6x1/4 HSS6x6x1/4 5" THICK CONCRETE SLAB ON GRADE REINFORCED WITH #3

20'-0"
1 2

20'-7 5/8"
BP-1 BP-1D EXISTING BLDG. TYP. S2.3 @ 12" o.c. EACH WAY AT MID-DEPTH OF SLAB. PLACE SLAB
S2.3
F3 F3 S2.3 S2.3 HSS6x6x1/4 ON 15 MIL. VAPOR BARRIER OVER SUBGRADE PREPARED IN
G EXISTING FTG. TYP.
BP-1B
HP-1
ACCORDANCE WITH THE PROJECT GEOTECHNICAL REPORT. 4 G
2'-8 5/8"

Physical: 16291 FM 849


F3.5 S2.3 F3

10'-8"
3'-0"

3'-0"
Mail: P.O. BOX 2428
8'-3 1/8"

F4 Lindale, Texas 75771


9
F STEP GRADE BEAM
F Phone: 903.882.8503 / Fax 903.882.5318
5'-0 5/16"

5'-0 5/16"
HSS6x6x1/4 S2.3 HSS8x8x1/4 HSS8x8x1/4 5 WWW.HOLLANDENGR.COM
HSS8x8x1/4 PER 4/S2.2 HSS8x8x1/4 HSS6x6x1/4 Texas Firm #: F-8474
F3 BP-1C (3) #6 IN GROUT FILLED F4 BP-2 F3.5 F3.5 BP-1 S2.3
7 13 HE #: 20-019

2'-0"
BP-2A BP-2 BP-2A
CELLS @ JAMB, TYP.
E S2.2 S2.3 E

1'-1 5/16"
5'-4 7/16"
5'-3 15/16"

5'-3 15/16"
M.J. M.J.
98'-7 1/2"

98'-7 1/2"
F3 5 4
HSS4x4x1/4 (5) #6 IN GROUT FILLED HSS8x8x1/4
CELLS @ CORNERS, TYP. S2.3 S2.3
PROVIDE #4 PLINTH BP-1 8 BP-1
D.8 TIES PER 9/S2.1
7
S2.3 D.8
9 7/8"

9 7/8"
S1.4 (3) #6 IN GROUT FILLED
D.7 D.7
2/S6.2

1 CELLS @ END OF WALL, TYP.


S1.4 8" SLAB REINF. W/ (2) LAYERS
OF #4 @ 12"o.c. EA. WAY
12'-9"

12'-9"
HSS8x8x1/4
F.F. EL. = 104'-1" 4 BP-1
1'-0 3/4"

1'-0 3/4"
D F4 F3.5
F4.5
HSS10x10x1/4
BP-1
HSS8x8x1/4
BP-3
HSS8x8x5/16
BP-3 S1.4 D
F4 F4 F4.5 F3.5 F3.5 8

C.5 S2.2
C.5
2'-0"
8
7 1/8"

7 1/8"
HSS8x8x1/4 HSS8x8x1/4 HSS8x8x1/4
S2.2 14 24" SQ. SLAB BLOCK-OUT
58'-0"

BP-2 BP-1 F4.5 BP-2


C HSS8x8x1/4 S2.3 HSS8x8x1/4 TYP. INT. PLINTH
DIMS. U.N.O.
2'-0" @ INT. COLS. PER 13/S2.1 EL. = 97'-0" 3 C

53'-3"
BP-2A BP-3
10'-2"

10'-2"
17'-9 7/8" TYP. U.N.O. S2.3
TYPICAL CONCRETE JOINT NOTE: F3 F3
PROVIDE SAW-CUT CONTROL JOINT AT EA. GRID
B & AT MIDSPAN BTWN., NOT TO EXCEED 15'-0"o.c.
EA. WAY PER DETAILS 01/S2.1. CUT JOINTS
B
15 FD WITHIN 8 HOURS AFTER CONCRETE PLACEMENT. HSS6x6x1/4 HSS6x6x1/4
S2.3 F.F. EL. = 100'-0" BP-1 BP-2A
2
7
S1.1 PROVIDE #4 PLINTH
S1.4 TIES PER 9/S2.1
20'-7"

20'-7"
3/S6.2
PROVIDE #4 PLINTH
TIES PER 9/S2.1
3 FD
S2.3
10'-1 1/8"

HSS8x8x1/4 HSS8x8x1/4 TYP. PERIMETER


F5 3'-0" 3'-0" PLINTH DIMS. U.N.O. 2'-0"
HSS8x8x1/4 HSS8x8x1/4 HSS6x6x1/4 BP-4A F5 BP-4A HSS8x8x1/4 HSS8x8x1/4 HSS6x6x1/4 HSS6x6x1/4
F3.5 BP-1 F4 BP-2 BP-1 F4 BP-1 F4 BP-1 BP-1 F4 F4 BP-2A
F3.5
10"

10"
9" 2'-3"

9" 2'-3"

2'-0"
A A
2'-6"

2'-6"
AA 7 6
AA
S2.3 S2.2
STEP GRADE BEAM 1/S6.2
PER 3/S2.2

159'-6" 23'-8" 10'-1"

10"
20'-9" 10'-3"
2'-10 15/16"
4'-7 15/16" 9'-1 13/16" 3'-9 3/8" 25'-2 9/16" 6'-8 1/8" 13'-9 3/4"

193'-3"
1'-6 9/16"
21'-8 3/4" 16'-4 3/16" 8'-5 1/16" 2'-1" 10'-6" 6'-11 9/16" 22'-7 1/8" 4'-2 5/16"
10" H ospi ality
Health R
1 2 3 3.5 4 4.7 5 6 6.3 6.8 7 8 9.5 9 10 11 12 13 14 HOSPITALITY
FOUNDATION PLAN HEALTH ER

NORTH
1 SCALE: 1/8" = 1'-0" TYLER
EXPANSION
6
9 1/16" 1'-8" Tyler, Texas
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

2 3
(2) #6 IN GROUT FILLED
CELLS @ JAMBS, TYP.
11
FILE NAME:
20-019-STRUCTURAL
B B
4'-8 3/8"

4'-7 5/8"

PROJECT NUMBER:
1909
#6 VERT. FULL HT. IN
GROUT FILLED CELLS

2'-11"
@ 24"o.c., TYP. U.N.O. SHEET CONTENTS:
RE: 4/S3.2 FOUNDATION PLAN
5"

@ ELEVATED FLOOR CUT G G I I


LOWEST COURSE OF CMU
4 1/16"

BLOCK TO FIT
2'-2"

2'-2"

COORD. SUMP PIT SIZE &


LOCATION W/ APPROVED
ELEVATOR SHOP DRAWINGS
1 5/8"

(3) #6 IN GROUT FILLED


CELLS @ CORNERS, TYP.
F F
5" 6'-0 13/16" 1'-9 1/4" 6 3/4" 2'-4 1/16"
4 1/16" 8 9/16"
5
2 S2.2 3 6 11

2 PARTIAL FDN. PLAN @ ELEVATOR PIT 3 FDN - HP DIM @ WALL 4 FDN - HP DIM @ EXTENSION S
S1.1 SCALE: 1/4" = 1'-0" S1.1 SCALE: 1/2" = 1'-0" S1.1 SCALE: 1/2" = 1'-0"

1.1
9/11/2020 11:15:48 AM

2ND FLOOR FRAMING PLAN NOTES:


1. REFER TO SHEET S0.1 FOR GENERAL NOTES.
2. F.F. ELEV. (T.O. CONC. SLAB) = 118'-1' WITH RESPECT TO REFERENCE F.F. ELEV. 100'-0".
3. T.O.B. SHALL BE 5" BELOW (-5") F.F. ELEV., TYP. U.N.O.
4. COMPOSITE FLOOR SYSTEM PER GENERAL NOTES & SHEET S4.1.
5. REFER TO SHEET S1.1 FOR COLUMN SIZES.
6. REFER TO SHEET S6.1 FOR TYPICAL STEEL FRAMING DETAILS NOT SPECIFICALLY SHOWN ON PLAN.
7. SHEAR PLATES SHALL BE CUT THROUGH TUBE OR PIPE COLUMNS FOR BEAM CONNECTIONS,
UNLESS NOTED OR DETAILED OTHERWISE.
8. ALL COLUMNS SHALL HAVE A MIN. 1/4" THICK CAP PLATE, UNLESS NOTED OR DETAILED OTHERWISE.
9. HDR, EXAMPLE, DENOTES LT. GAGE STEEL HEADER AT FIRST FLOOR. REFER TO SHEET S3.1 FOR
SCHEDULE & DETAILS.
10. [4], EXAMPLE, DENOTES NUMBER OF 3/4"Øx3 1/2" LONG HEADED STUD SHEAR CONNECTORS.
11. REFERENCE S4.1 FOR COMPOSITE DETAILS NOT SPECIFICALLY SHOWN ON PLAN.
12. LNTL, EXAMPLE, DENOTES CMU LINTEL. REFER TO SHEET S3.2 FOR SCHED. & DETAILS. 09/11/2020
13. ► , INDICATES WELDED MOMENT CONNECTION. REFER TO SHEET S6.1

THACKER | DAVIS ARCHITECTS


1 2 3 3.5 4 4.7 5 6 6.3 6.8 7 8 9.5 9 10 11 12 13 14 I N C O
Member American
R P O R
Institute of
A T E D
Architects

.
1100 Judson Rd., Suite 620 PO Box 2723
Longview, Texas 75606-2723
.
Phone 903.236.3771 Fax 903.753.7317

Email: T D A @ T - D A r c h i t e c t s . c o m

w w w . T - D A r c h i t e c t s . c o m

REINF. EXISTING
JOIST PER 11/S5.1

REINF. EXISTING
JOIST PER 11/S5.1
RTU-3
3400 LBS.

EXISTING RTU
(TYP.) STRUCTURAL ENGINEER:

EXISTING JOIST
(TYP.)

RTU-2 EXISTING BM.


3600 LBS. (TYP.)
RTU-1 NOTE:
EXISTING COL. 4800 LBS. CANOPY & CONNECTIONS
(TYP.) TO BE BY OTHERS (TYP.)

EXISTING RTU EXISTING


(TYP.) BUILDING 2 Physical: 16291 FM 849
Mail: P.O. BOX 2428
S5.2 Lindale, Texas 75771
Phone: 903.882.8503 / Fax 903.882.5318
WWW.HOLLANDENGR.COM
EXISTING RTU Texas Firm #: F-8474
(TYP.) HE #: 20-019

29'-6 11/16"

LNTL.
REINF. EXISTING
6'-0" 6'-0" 6'-0" 6'-0" 2'-4 1/8"
JOIST PER 11/S5.1

W14x30 (+2 1/2")


1
REINF. EXISTING
JOIST PER 11/S5.1 S5.2
RTU-8
3200 LBS.
10
RTU-6 4 3 4 5
16K2 SP1 S5.2
2200 LBS. S4.2 S3.2 S4.2
S3.2

P.
P.

TY
TY
HSS6x6x1/4 MOMENT CONN.
STUB COL. 117'-6 11/16" PER 3 / S6.1 , TYP.
HSS8x6x1/4 (LLV)
W24x68
I 3 I

3'-11 7/8"

4'-8 11/16"
L6x4x5/16 LNTL.
S5.2
W14x68 [12] W10x12 [4] HI
W10x12 (+2 1/2")
H W10x12 [4] HI H

W16x36 [16]

W16x31 [16]
W16x36 [16]

W16x36 [18]

W16x36 [16]

W16x36 [16]

W16x36 [18]

W16x36 [16]

W18x35 [18]

W18x35 [18]

W16x36 [16]
HSS4x4x1/4

W21x48 LOW
6'-0"
STUB COL.

W18x40 [28]
W14x34 [12] 20K5 SP2

W16x67 [18]

W16x40 (+2 1/2")

12'-3"
FD FD FD

W10x22 (+2 1/2")


L6x4x5/16
2 2 3 FD FD FD
HDR-3

4/S6.2
6'-0"
HSS8x6x1/4 (LLV)
S4.2 MOMENT CONN. S1.4 S4.2 W12x26 DIAG. BRACE.
PER 3 / S6.1 , TYP. WHERE INDICATED, 11 W10x12 [4] HI

HDR-3
W14x34 [12]
G G

HDR-4
W12x26

LNTL
TYP. RE: 7/S4.1
W14x22 [3]

W14x22 [3]

W14x22 [3]

W14x22 [3]

S4.2

3'-11 7/8"
W10x12 [3]
HI

HDR-5

3'-0"
5 6
4 W10x12 [8] W10x12 [4] W24x84
F W18x35 [10] HDR-6
10
S4.2
S4.2 W10x12 [4] S4.2 F

5'-0 5/16"
S4.2 HI
PROPOSED

6'-3 1/2"
FLR. OPENING HSS6x6x1/4
8 W21x50 [8] W21x48 [16] W24x55 [18] STUB COL. HSS6x6x1/4
E HSS6x6x1/4 8 E

2'-11 1/4"
S1.4 W16x26 [6] W14x34 [12]
STUB COL.

5'-3 15/16"
L6x4x5/16 W12x14 [6] HANGER

4'-9 1/2"
DECK SPAN 7 S5.2
HSS4x4x1/4 DIRECTION W10x12 [4]
S4.2
W21x44 [18]

W16x36 [10] HI W18x35 116'-11 11/16"


HDR-2

6'-6"
D.8 D.8

W14x22 [4]

W14x22 [4]
W14x30 [16]

W16x36 [16]

W16x36 [18]

W16x36 [16]

4'-10 1/2"

W18x35 [28]
9

9 7/8"
W14x34 [12]
W12x26 [10]

W21x48 LOW
W10x12 [6] S4.2

W14x30 [16]
W14x22 [14]
W16x36 [14]

W16x36 [16]

W16x36 [16]

W16x36 [16]

W16x36 [32]

W16x36 [16]

W16x36 [16]

W16x36 [16]

W14x22 [16]

W16x36 [16]
2/S6.2

W16x36 [16]

W16x36 [14]

W16x36 [16]

W16x36 [16]

W16x36 [16]

W16x26 [16]
D.7 W16x36 [10] W10x12 [4]
HI
D.7

6'-6"
7'-0" 1'-8" 9

W16x36 [16]

12'-9"
W10x12 [8]

S5.2

W16x36 [10]
W14x34 [12]
OPENING, COORD. FD W10x12 [4]
D D

1'-0 3/4"
MOMENT CONN. HI

6'-3 1/2"
W/ ARCH'L. HSS6x6x1/4
PER 3 / S6.1 , TYP.
W10x12 [6] STUB COL.
C.5 W24x55 [14] W21x44 [14] W24x62 [18] W24x55 [16] W24x55 [16] W24x76 [18] W14x22 [8] W21x44 [2] C.5
H ospi ality
W10x12 [8]

7 1/8"
4'-4 1/2" 6'-0" 6'-0" 4'-4 1/2" 5'-1 1/2" 5'-1 1/2" 4'-3" 6'-0" 6'-0" 4'-3" 6'-1 5/16" 6'-6" 6'-6" 6'-1 11/16" 6'-0" 6'-0" 5'-0 3/16" 4'-10 3/8" 6'-0" 6'-0" 4'-10 3/8" 7'-0" 6'-6" 7'-0" 6'-4 1/4" 5'-3" 5'-3"
3 MOMENT CONN.
C PER 3 / S6.1 , TYP. C

W10x12 [8]
W10x12 [8]

W12x26 [8]
HDR-2
4'-11 13/16" S4.2
Health R

10'-2"
12 2'-2"
8 1/4" 11 1/2" PROPOSED
S4.2 DIAG. BRACE. FLR. OPENING
W10x12 [6] WHERE INDICATED, DECK SPAN DIRECTION W16x36 [4]
TYP. RE: 7/S4.1

4'-1" 1'-4"
W10x12 [6]
W16x26 [14]

B B

W16x36 [3]
4 1/2"

HOSPITALITY
W16x31 [10]

W21x68 [16]

W21x68 [16]

W21x55 [12]

W21x48 [12]

W21x68 [16]

W21x68 [18]

W21x68 [16]

W18x40 [16]

W21x68 [18]

W21x68 [20]

W21x68 [18]

W21x68 [16]

W21x68 [18]

W21x68 [16]

W18x40 [16]

W21x68 [16]

W21x68 [18]

W21x68 [16]

W21x44 [18]

W21x68 [20]

W21x68 [20]

W21x68 [20]
W21x68 [16]

W16x36 [4] HEALTH ER


TYLER

W12x26 [12]
7'-7" 5'-6"
4 1/2"

FD

W12x35
13

20'-7"
3/S6.2
PROPOSED
FLR. OPENING W16x36 [6]
S4.2 FD FD FD FD FD FD EXPANSION
W16x36 [2]

W16x36 [2]

W10x12 [6]
2'-9 3/4"

W10x12 [8]

W16x36 [6] MOMENT CONN. Tyler, Texas


PER 3 / S6.1 , TYP.
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

1 W10x12 [6]
4'-8"

S4.2
W21x44 [18] W21x44 [18] W18x35 [12] W21x57 [12] W21x44 [10] W21x44 [10] W24x55 [12] W12x26
A A
W14x22 [3]

W14x22 [3]

W14x22 [3]

W14x22 [3]

W14x22 [3]

W14x22 [3]

W16x26 [3]
W16x26 [3]

W16x26 [3]

3'-4"
HDR-1 HDR-1 HDR-1 HDR-1 HDR-1 HDR-1

AA AA FILE NAME:

M.
M.

SI
HSS5x5x1/4 HSS5x5x1/4

SI
MOMENT CONN. 1 3 4
PER 3 / S6.1 , TYP. STUB COL. STUB COL. S4.2 S4.2 S1.4 20-019-STRUCTURAL
1/S6.2
2 PROJECT NUMBER:
8
S4.2
S4.2 1909

2'-10 15/16" 1'-6 9/16" SHEET CONTENTS:


20'-9" 10'-3" 4'-7 15/16" 9'-1 13/16" 3'-9 3/8" 25'-2 9/16" 6'-8 1/8" 13'-9 3/4" 21'-8 3/4" 16'-4 3/16" 8'-5 1/16" 2'-1" 10'-6" 6'-11 9/16" 22'-7 1/8" 4'-2 5/16" SECOND FLOOR FRAMING
PLAN

1 2 3 3.5 4 4.7 5 6 6.3 6.8 7 8 9.5 9 10 11 12 13 14

LEVEL 2 PLAN

NORTH
1 SCALE: 1/8" = 1'-0"

S
1.2
9/11/2020 11:15:50 AM

ROOF FRAMING PLAN NOTE:


1. REFER TO SHEET S0.1 FOR GENERAL NOTES.
2. (137'-10 1/4"), EXAMPLE, DENOTES JOIST BEARING ELEVATION WITH RESPECT TO FINISH FLOOR.
3. (+2 1/2"), EXAMPLE, INDICATES TOP OF BEAM IS TOP OF JOIST ELEVATION.
4. REFER TO SHEET S1.1 FOR COLUMN SIZES.
1 2 3 3.5 4 4.7 5 6 6.3 6.8 7 8 9.5 9 10 11 12 13 14 5. ALL COLUMNS SHALL HAVE 1/4" CAP PLATE, UNLESS NOTED OR DETAILED OTHERWISE.ALL
6. SHEAR PLATES SHALL BE CUT THROUGH TUBE COLUMNS FOR BEAM CONNECTIONS, UNLESS NOTED
OR DETAILED OTHERWISE.
7. PROVIDE L3x3x5/16 FRAME AT ALL ROOF OPENINGS 12" WIDE AND GREATER. PROVIDE L4x4x5/16
FRAME UNDER EACH ROOF TOP MECHANICAL UNIT. COORDINATE AND VERIFY ALL RTU FRAME SIZES
AND LOCATIONS WITH MECHANICAL DRAWINGS.
2'-10 15/16" 1'-6 9/16" 8. REINFORCE JOISTS W/ (2) L2x2x3/16 STRUTS TO NEAREST PANEL POINT AT OPPOSITE CHORD FROM
20'-9" 10'-3" 4'-7 15/16" 9'-1 13/16" 3'-9 3/8" 25'-2 9/16" 6'-8 1/8" 13'-9 3/4" 21'-8 3/4" 16'-4 3/16" 8'-5 1/16" 2'-1" 10'-6" 6'-11 9/16" 22'-7 1/8" 4'-2 5/16" ALL CONCENTRATED LADS ON JOISTS.
9. JOIST SEATS SHALL BE "CANTED" OR "SLOPED" WHEN NECESSARY TO PROVIDE A LEVEL BEARING
4 4 SURFACE. 09/11/2020
10. JOIST MANUFACTURER SHALL DESIGN ALL JOISTS/BRIDGING FOR A NET UPLIFT PER S0.2. JOIST
S5.3 S3.2
MANUFACTURER SHALL SPECIFY BRIDGING.
11. HDR, EXAMPLE, DENOTES LIGHT GAGE STEEL HEADER. REFER TO SHEET S3.1
12. 26K5SPM, EXAMPLE, DENOTES JOIST W/ MECHANICAL LOADING REQUIREMENTS. JOIST
HDR-1 HDR-1 HDR-1 HDR-1 HDR-1 W10x12 MANUFACTURER SHALL COORDINATE ROOF TOP EQUIPMENT LOADS W/ MECHANICAL SUPPLIER.
I I 13. , INDICATES BOLTED JOIST SEAT. STEEL DETAILER SHALL COORDINATE W/ JOIST SUPPLIER.

4'-8 11/16"
C12x20.7 HDR-1
14. , INDICATES WELDED MOMENT CONNECTION. REFER TO SHEET S6.1

"R1" TYPE JOIST EXT. THACKER | DAVIS ARCHITECTS


H @ WALL BUMP OUT H I N C O
Member American
R P O R
Institute of
A T E D
Architects

W10x22 (+2 1/2")

W12x26 (+2 1/2")


1100 Judson Rd., Suite 620 PO Box 2723

M.

14K1 SP1
Longview, Texas 75606-2723

SI 3 7 6 7 2 .
Phone 903.236.3771 Fax 903.753.7317

12'-3"
S5.4 S5.2 S5.2 S5.3 S5.3 26K5 SP1 30K11 SP1

L6x4x5/16
Email: T D A @ T - D A r c h i t e c t s . c o m

4/S6.2
w w w . T - D A r c h i t e c t s . c o m

HSS6x6x1/4 137'-10 1/4" RTU-13


STUB COL. 137'-10 1/4" 4800 LBS.
G W12x26
3
1 G
HSS6x6x1/4 S5.3

W12x26 (+2 1/2")

3'-0"
S5.3
STUB COL. W14x30 W10x12
F F

30K11 SPM

30K11 SPM

30K11 SPM

30K11 SPM
134'-4" 134'-4"

5'-0 5/16"
4
134'-2 3/4"
S5.4 HDR-1

HDR-2
W12x14 C12x20.7 C12x20.7 STRUCTURAL ENGINEER:
E E

5'-3 15/16"
20K4 SP1
HSS6x6x1/4 HSS6x6x1/4

W14x30 (+2 1/2")


W12x45 (+2 1/2")

STUB COL. STUB COL. 134'-1 7/16" 134'-1 7/16"


W21x44

W12x35 (+2 1/2")

W12x35 (+2 1/2")


D.8 W14x22 D.8

18K3 SP1
W21x44 (+2 1/2")

9 7/8"
HSS6x6x1/4 HSS6x6x1/4
2.5K1 SP1
2/S6.2

D.7 20K4 SP1 16K3 SP1 STUB COL. STUB COL. D.7

W14x30 (+2 1/2")


W10x22 (+2 1/2")

W14x30 (+2 1/2")


1

W16x26 (+2 1/2")

W14x22 (+2 1/2")

W14x22 (+2 1/2")


S5.4

12K1 SP1
RTU-10

12'-9"
4800 LBS. 6'-0" 4'-6" 3'-1" 3'-5 3/4" 3'-5 7/8"
DIAG. BRACE.
WHERE INDICATED,
133'-10 1/16" TYP. RE: 6/S5.1 5 12

1'-0 3/4"
D 133'-10 1/16" HSS6x6x1/4 HSS6x6x1/4 HSS6x6x1/4
STUB COL.
HSS6x6x1/4 S1.4 S5.3 D Physical: 16291 FM 849
STUB COL. STUB COL. STUB COL. Mail: P.O. BOX 2428
133'-9 11/16" 133'-9 11/16" Lindale, Texas 75771
C.5 W18x35 W10x22 W18x35 W21x44 W18x35 W21x44 W24x55 W10x12 W12x16 C.5 Phone: 903.882.8503 / Fax 903.882.5318
10K1 SP1

7 1/8"
WWW.HOLLANDENGR.COM
Texas Firm #: F-8474

W10x12 (+2 1/2")


C 4'-4 1/2" 6'-0" 6'-0" 4'-4 1/2" 5'-1 1/2" 5'-1 1/2" 2'-6" 6'-0" 6'-0" 6'-0" 5'-3" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 3'-6" C HE #: 20-019

HDR-2
W12x26

10'-2"
RTU-11
5
2 4800 LBS.
COORD. HOIST BEAM S5.3 RTU-14
S5.4
LOCATION W/ ELEV. SUPPLIER 4800 LBS.
W10x12
B DIAG. BRACE.
B
W18x35 (+2 1/2")

W18x35 (+2 1/2")

WHERE INDICATED,
W8x18

26K5 SPM

26K5 SPM

26K5 SPM

26K5 SPM
TYP. RE: 9/S5.1
W16x36 (+2 1/2")

10K1 SP1

26K5 SP1
26K5 SP1

6'-11 7/8"

26K5 SPM 26K5 SP1 26K5 SP1

W12x26 (+2 1/2")


11 8

W12x40

20'-7"
5 S5.3 S5.3

3/S6.2
S5.2
RTU-15
RTU-12
4000 LBS.
3000 LBS.
10K1 SPM

133'-2" 133'-2"
W16x26 (+2 1/2")

W14x30 W16x26 W10x12 W16x26 W16x26 W16x26 W21x48 W12x26


A A
3'-4"

3'-4"
HSS6x6x1/4 HDR-1 HDR-1 HDR-1 HDR-1 HDR-1 HSS6x4x1/4 HDR-1
STUB COL. STUB COL.
AA AA
HSS6x6x1/4
STUB COL.

P.
"R1" TYPE JOIST EXT. MOMENT CONN.

TY
1/S6.2 10 4 10 9
@ WALL BUMP OUT PER 3 / S6.1 , TYP.
S5.1 S5.2 S5.3 S5.3
M.

3 6
SI

7
S5.4 S5.2 S5.3

1 2 3 3.5 4 4.7 5 6 6.3 6.8 7 8 9.5 9 10 11 12 13 14

LOW ROOF FRAMING PLAN

NORTH
1 SCALE: 1/8" = 1'-0"

3 3.5 4 4.7 5 6 6.3 6.8 7 9.5 9 10 11 12

2'-10 15/16"
4'-7 15/16" 9'-1 13/16" 3'-9 3/8" 25'-2 9/16" 6'-8 1/8" 13'-9 3/4"
1'-6 9/16"
38'-1" 8'-5 1/16" 2'-1" 10'-6" 6'-11 9/16"
H ospi ality
2
S5.4
2
S5.4
Health R
D.8 D.8 HOSPITALITY

9 7/8"
HSS6x6x1/4 HSS6x6x1/4
D.7 1 1 D.7 HEALTH ER
S5.4 S5.4
TYLER
HSS6x6x1/4

HSS6x6x1/4

HSS6x6x1/4

HSS6x6x1/4

12'-9"
12

800S162-54 JOISTS @ 800S162-54 JOISTS @


S5.3 EXPANSION

1'-0 3/4"
D 2'-0"o.c. MAX. W/
BRIDGING @ MID-PTS.
2'-0"o.c. MAX. W/ D
BRIDGING @ MID-PTS.
Tyler, Texas
C.5 W10x12
C.5
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

146'-5" 146'-5"

7 1/8"
HSS6x6x1/4 HSS6x6x1/4

HDR-6
W10x12 (+2 1/2")

W12x26 (+2 1/2")


C C

10'-2"
MOMENT CONN. MOMENT CONN.
PER 3 / S6.1 , TYP. PER 3 / S6.1 , TYP.
FILE NAME:
20-019-STRUCTURAL
B B
MOMENT CONN.
PROJECT NUMBER:
PER 3 / S6.1 , TYP. 1909

24K5 SHEET CONTENTS:


11 8
LOW & HIGH ROOF

20'-7"
S5.3 S5.3
W10x22 (+2 1/2")

W12x26 (+2 1/2")


FRAMING PLAN

HSS12x6x1/4 (LLH) W12x26


A 145'-7" 145'-7"
A
AA 3'-4" AA
10 9
1/S6.2 S5.3 S5.3

3 3.5 4 4.7 5 6 6.3 6.8 7 9.5 9 10 11 12

S
2 HIGH ROOF FRAMING PLAN
NORTH

S1.3 SCALE: 1/8" = 1'-0" 1.3


9/11/2020 11:15:53 AM

2 3
3 3 G E D.8 D
S1.4
2 S1.4 9'-4" 3
C12x20.7
C12x20.7 EDGE BEAM
G G
3" CONC. OVER
G G EQ. EQ. EQ. EQ. EQ.
10 GA. PAN, TYP. COMPOSITE DECK
PER PLAN FIN. FLR.

C12x20.7

C12x20.7
L2x2x1/4

L2x2x1/4

L2x2x1/4

L2x2x1/4
EL. RE: PLAN

F F C12x20.7 HEADER

MC8x18.7 C12x20.7 09/11/2020


EDGE BEAM L2x2x1/4 STIFF.
@ 2'-0"o.c., MAX.
3" CONC. OVER
10 GA. PAN, TYP. MC8x18.7 HEADER BM. PER PLAN
8

C12x20.7
C12x20.7
E S1.4 E C12x20.7 STRINGER T.O. LANDING

P.
E E

TY
EL. = 114'-0"

THACKER | DAVIS ARCHITECTS


I N C O R P O R A T E D
MC8x18.7 Member American Institute of Architects

MC8x18.7 HEADER .
1100 Judson Rd., Suite 620 PO Box 2723
EQ. EQ. EQ. NOTE: Longview, Texas 75606-2723

L2x2x1/4 STIFF. C12x20.7 STRINGER ALL STEEL INTERSECTIONS .


Phone 903.236.3771 Fax 903.753.7317

C12x20.7

C12x20.7

C12x20.7
C12x20.7

L2x2x1/4

L2x2x1/4
@ 2'-0"o.c., MAX. SHALL BE WELDED W/ 3/16"
2" CONC. OVER FILLET WELDS ALL AROUND, Email: T D A @ T - D A r c h i t e c t s . c o m
C12x20.7

C12x20.7 w w w . T - D A r c h i t e c t s . c o m
12 GA. PAN, TYP. TYP. U.N.O.

RE: ARCH'L.
RE: ARCH'L.

TYP.
W10x12 TYP.
COL. PER PLAN

C12x20.7 HEADER

TY "
P.
2
C12x20.7

C12x20.7

C12x20.7
EDGE BEAM STRUCTURAL ENGINEER:
3" CONC. OVER
MC8x18.7 10 GA. PAN, TYP.
EQ EQ. EQ. EQ. EQ
C12x20.7

C12x20.7

T.O. LANDING
L2x2x1/4

L2x2x1/4

L2x2x1/4

L2x2x1/4

EL. = 102'-11"
C12x20.7 STRINGER

C12x20.7
D D 7
MC8x18.7 HEADER
S1.4
D D
L2x2x1/4 STIFF.
@ 2'-0"o.c., MAX. FIN. FLR. Physical: 16291 FM 849

2 3 EL. RE: PLAN Mail: P.O. BOX 2428


Lindale, Texas 75771

2 COORD. ALL STAIR 3 COORD. ALL STAIR


Phone: 903.882.8503 / Fax 903.882.5318
WWW.HOLLANDENGR.COM
DIMS. W/ ARCH'L. DIMS. W/ ARCH'L. Texas Firm #: F-8474
HE #: 20-019

1 SCHEMATIC NE STAIR FRAMING PLAN @ FOUNDATION LEVEL 2 SCHEMATIC NE STAIR FRAMING PLAN @ 2ND FLOOR 3 NE STAIR ELEVATION
S1.4 SCALE: 1/4" = 1'-0" S1.4 SCALE: 1/4" = 1'-0" S1.4 SCALE: 3/8" = 1'-0"

10 6 11
S1.4
10 6
11 C B A
S1.4

MC8x18.7 HEADER
C12x30
C C C C 3" CONC. OVER
10 GA. PAN, TYP.
T.O. LANDING
EQ EQ EQ EQ EQ EQ
EL. = 135'-7"

L3x3x1/4 STIFF.

L3x3x1/4

L3x3x1/4

L3x3x1/4

L3x3x1/4

L3x3x1/4
@ 2'-0"o.c., MAX.

C12x30

C12x30
C12x30
EDGE BEAM
C12x30 HEADER

BM. PER PLAN BM. PER PLAN

MC8x18.7
W10x12
L2x2x1/4

L2x2x1/4

B B B B
C12x30

C12x30

C12x30 STRINGER
L4x4x1/4
L2x2x1/4

L2x2x1/4
C12x30

C12x30

C12x30 HEADER

C12x30
EQ. EQ. EQ. EDGE BEAM
NOTE:
ALL STEEL INTERSECTIONS 3" CONC. OVER
MC8x18.7 SHALL BE WELDED W/ 3/16" 10 GA. PAN, TYP.
FILLET WELDS ALL AROUND,
TYP. U.N.O. T.O. LANDING
C12x30
C12x30

EL. = 125'-1"
C12x30
C12x30

C12x30

C12x30 STRINGER
MC8x18.7 HEADER MC8x18.7 HEADER
C12x30

C12x30
C12x30

C12x30 L2x2x1/4 STIFF.


EDGE BEAM @ 2'-0"o.c., MAX.

3" CONC. OVER


10 GA. PAN, TYP.

L2x2x1/4 STIFF.
H ospi ality
MC8x18.7 MC8x18.7 @ 2'-0"o.c., MAX.
Health R
L4x4x1/4 HEADER
COMPOSITE DECK
FIN. FLR.
C12x30
C12x30
C12x30

L2x2x1/4

L2x2x1/4

L2x2x1/4

L2x2x1/4

L2x2x1/4
L2x2x1/4

L2x2x1/4

L2x2x1/4

L2x2x1/4

L2x2x1/4
C12x30

PER PLAN
EL. RE: PLAN HOSPITALITY
EQ. EQ. EQ. EQ. EQ. EQ. EQ EQ EQ EQ EQ EQ
HEALTH ER
C12x30 C12x30
A A A A BM. PER PLAN TYLER
BM. PER PLAN
EXPANSION
10 COORD. ALL STAIR 11 10 COORD. ALL STAIR 11 Tyler, Texas
DIMS. W/ ARCH'L. DIMS. W/ ARCH'L. C12x30 STRINGER
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

C12x30 HEADER

4 SCHEMATIC SW STAIR FRAMING PLAN @ 2ND FLOOR 5 SCHEMATIC SW STAIR FRAMING PLAN @ LOW ROOF C12x30
EDGE BEAM
S1.4 SCALE: 1/4" = 1'-0" S1.4 SCALE: 1/4" = 1'-0" 3" CONC. OVER FILE NAME:
10 GA. PAN, TYP.
20-019-STRUCTURAL
T.O. LANDING
PROJECT NUMBER:
1909
C12x30 STRINGER MC8x18.7 HEADER
SHEET CONTENTS:
2" CONC. OVER L2x2x1/4 STIFF.
STAIR TREADS AND RISERS ARE
12 GA. PAN, TYP. @ 2'-0"o.c., MAX. STAIR FRAMING PLANS
SHOWN FOR GENERAL ARRANGEMENT
ONLY - COORDINATE TREAD AND RISER

RE: ARCH'L.
QTY. & DIMS. W/ ARCH'L. DWGS. RE: ARCH'L.

TYP.
TYP.

L3x3x1/4 x 9" LONG W/ (2) COL. PER PLAN COL. PER PLAN
1/2"Ø HILTI KWIK BOLTS (6"

2" .
TY
EMBEDMENT)

P
COL. PER PLAN
1/4 7
S1.4
TYP. STRINGER FIN. FLR. 00 FOUNDATION LEVEL
FIN. FLR. EL. RE: PLAN EL. = 100'-0"
EL. RE: PLAN
1'-0"

L6x6x5/16 EA. SIDE STRINGER AS DTL'D.


(2) #5 CONT. W/ #5
CROSS BARS @
12"o.c.
S
1'-0"

1.4
7 TYP. SECTION @ STRINGER LANDING 8 TYPICAL C-CHANNEL TO COLUMN CONN. 6 SCHEMATIC SW STAIR ELEVATION
S1.4 SCALE: 3/4" = 1'-0" S1.4 SCALE: 3/4" = 1'-0" S1.4 SCALE: 3/8" = 1'-0"
9/11/2020 11:15:55 AM

NOTE:
SAWED JOINTS SHALL BE CUT WITHIN 8 HOURS OF
09/11/2020
1/4" CONCRETE PLACEMENT

T/3
PROVIDE POURED JOINT SEALANT
@ EXPOSED CONCRETE
(@ OWNER'S DESCRETION)

PER PLAN
SLAB
VARIES
T
THACKER | DAVIS ARCHITECTS

PER PLAN
SLAB
I N C O R P O R A T E D
Member American Institute of Architects
FIN. FLR.
.
1100 Judson Rd., Suite 620 PO Box 2723
EL. RE: PLAN W SLEEVE DIAMETER 2" GRADE BEAM REINF. Longview, Texas 75606-2723
GRANULAR FILL
JOINT KEY SHALL BE 1 1/2" LARGER THAN PIPING LINE AS DETAILED .
Phone 903.236.3771 Fax 903.753.7317
W/3 RE: MEP FOR PIPE SIZE
DEEP Email: T D A @ T - D A r c h i t e c t s . c o m
6"
FIN. PAVING w w w . T - D A r c h i t e c t s . c o m
PREPARED SUBGRADE OR 8"
EL. RE: CIVIL

D/4
TYPICAL SLAB SAWCUT CONTROL JOINT TYPICAL SLAB DEPRESSION <3"

D
1 3
S2.1 S2.1

D/4
SCALE: NONE SCALE: NONE
. . .

CVR. (MIN.)
SPACE A MINIMUM (3) SLEEVE STRUCTURAL ENGINEER:

6" CLR.
NOTE: 4 CONDUITS DIAMETERS
EL. RE: CIVIL
PROPOSED CONSTRUCTION JOINT

T/3
LOCATIONS SHALL BE SUBMITTED TO
ARCH./ENGR. FOR APPROVAL PRIOR TO

T
CONCRETE PLACEMENT STEP B.O. G.B./T.O.
PROVIDE #4 DOWELS x 2'-0" LONG FTG. AS REQ'D.
@ 18"o.c. TOP & BOTT. BARS SHALL
PREFORMED WOOD OR
T/3

BE CONT. THRU JOINT SLEEVE


METAL KEY JOINT NOTES:
EL. RE: CIVIL
1. CONDUITS SHALL NOT BE LARGER IN OUTSIDE DIAMETER THAN 1/3 THE OVERALL

T
THICKNESS OF THE SLAB IN WHICH THEY ARE EMBEDDED. NOTES:
2. CONDUITS SHALL NOT BE SPACED CLOSER THAN THREE DIAMETERS OR WIDTHS 1. CONSTRUCTION JOINTS SHALL BE LOCATED WITHIN 1'-0" OF THE MIDSPAN 2'-0" 2'-0"
T/3

ON CENTER. BETWEEN INTERIOR SUPPORTS. Physical: 16291 FM 849


3. CONDUITS AND PIPES OF ALUMINUM SHALL NOT BE EMBEDDED IN STRUCTURAL 2. JOINT SHALL NOT BE PLACED IN A SPAN CONTAINING A TOP BAR SPLICE. Mail: P.O. BOX 2428
6" 4'-0" 6"
GRANULAR FILL CONCRETE. 3. JOINT SHALL NOT BE PLACED IN THE FIRST SPAN FROM A CORNER OR Lindale, Texas 75771
4. CONDUITS SHALL BE PLACED BETWEEN TOP AND BOTTOM REINFORCEMENT AND INTERSECTION. Phone: 903.882.8503 / Fax 903.882.5318
SHALL BE LOCATED AS CLOSE AS POSSIBLE TO THE MID-DEPTH OF SLAB. 4. JOINT SHALL NOT BE PLACED IN A CLEAR SPAN OF 10'-0" OR LESS. 5'-0" WWW.HOLLANDENGR.COM
Texas Firm #: F-8474
5. MINIMUM CONCRETE COVER FOR CONDUITS SHALL BE THE SAME AS THAT OF THE
PREPARED SUBGRADE SLAB MAIN REINFORCEMENT.
HE #: 20-019

6. LIMIT CONDUIT CROSSING.

2 TYPICAL SLAB KEYED CONST. JOINT 4 TYPICAL EMBEDDED CONDUITS DETAIL 5 TYPICAL GRADE BEAM KEYED CONST. JOINT 6 TYPICAL SLEEVE THRU GRADE BEAM/STEM WALL
S2.1 SCALE: NONE S2.1 SCALE: NONE S2.1 SCALE: NONE S2.1 SCALE: NONE

BAR LEG
4" 4" BEAM REINFORCING - SEE SIZE LENGTH
DETAILS
GRADE BEAM
#4 2'-0"
REINFORCING - SEE #5 2'-6"
DETAILS W2 W2
#6 3'-0"
#7 3'-6" PERIMETER TIE
B/3
GRADE BEAM

GRADE BEAM

#8 4'-0"
DEEPTH
WIDTH

(2) #5 ADD'L. HORIZ. BEAM REINF.,


#9 4'-6"
B/3

BOTH SIDES OF BEAM CENTERED TIES TIES


ON SLEEVE EXTEND 2'-0" MIN. EA. INSIDE FACE OF ROOM
WHERE MORE THAN (3) BARS
WAY PAST SLEEVE OCCUR ON A SINGLE PLINTH
B/3

WALL STUDS AS DTL'D.


3" CLR. FACE, EVERY OTHER BAR W/ CONT. BOTT. TRACK
CORNER BARS TYP. U.N.O. SHALL HAVE AN INTERIOR TO MATCH GAGE
CORNER BARS TOP & BOTT. HAIRPIN TIE AT EACH TIE LEVEL
TOP & BOTT. PLUMBING LINE
GRADE BEAM RE: MEP DWGS.
CL.OF
PROVIDE ONE SET OF ADD'L. STIRRUPS ON SLEEVE GRADE BEAM WIDTH 1 1/2" 1 1/2" 10" FIN. FLR.
TOP OF PLINTH
SCHED. LEG LENGTH

SCHED. LEG LENGTH


MACTH BEAM STEEL

MATCH BEAM STEEL


EA. SIDE OF SLEEVE (NOT SCHED.) TOP OR BOTT.

1 1/2"
1 1/2"

MAX.
STEEL PLAN VIEW MAX. EL. RE: PLAN

2"
TIE @ 1/2 THE SPACING

1'-0"
PLAN SECTION
TIES @ 10"o.c. (MAX.)

2/3 x W1
NOTES: COL. & SLAB NOT

2/3 x W1
1. REQUIRED BEAM SLEEVES ARE TO BE COORDINATED WITH MEP CONTRACTORS. REQUIRED SLEEVES MAY OR SHOWN FOR CLARITY

W1

W1
MAY NOT BE SHOWN ON THE STRUCTURAL DWGS. GENERAL CONTRACTOR SHALL SUBMIT PLAN SHOWING PLINTH AS DETAILED

MAX.
10"
LAYOUT OF ALL SLEEVES.
NOTES: VERT. BARS @ 10"o.c.
2. SLEEVES SHALL BE LOCATED ON THE BEAM CENTERLINE, OR AT LEAST WITHIN THE MIDDLE THIRD OF THE
1. PLINTH TIES SHOWN HERE MUST (MAX.) ALONG EA. (2) #5 CONT.
GRADE BEAM WIDTH.
BE INSTALLED ABOVE THE FTG. PLINTH FACE W/ STD. 1'-4"
3. CONT. BEAM REINFORCING MAY BE SLIGHTLY DISPLACED (3" MAXIMUM) OR ADJACENT BARS BUNDLED (2 BAR
SCHED. LEG LENGTH 2/3 x W2 2. PROVIDE A MIN. OF (4) SETS OF HOOK INTO FTG.
BUNDLE MAX.) TO FACILITATE SLEEVE INSTALLATION. DO NOT CUT, OFFSET, OR BEND REINFORCING. 1 1/2"
TOP OR BOTT. TIES AT ALL PLINTHS.
4. SLEEVES OCCURRING ON OPPOSITE SIDES OF A PIER MUST BE IN LINE. MATCH BEAM STEEL STEEL
5. THE OUTSIDE DIAMETER OF A SLEEVE MAY NOT EXCEED 15% OF THE WIDTH OF THE GRADE BEAM THRU SCHED. LEG LENGTH PROVIDE ADD'L. TIES
WHICH IT MUST PASS. THE CONTRACTOR SHALL CONTACT THE STRUCTURAL ENGINEER OF RECORD FOR IN FTG. AS REQ'D. FOR
DIRECTIONS WHEN A SLEEVE SIZE OR LOCATION DOES NOT MEET THE CONDITIONS ESTABLISHED ABOVE. MATCH BEAM STEEL SECTION VIEW ALIGNMENT
PLAN AT INTERSECTION PLAN AT CORNER

7 TYPICAL VERTICAL PENETRATION, CONCRETE GRADE BEAM 8 TYPICAL GRADE BEAM CORNER BAR DETAIL 9 TYPICAL PLINTH REINF. PLAN VIEW 10 SECTION
S2.1 SCALE: NONE S2.1 SCALE: NONE S2.1 SCALE: NONE S2.1 SCALE: NONE

H ospi ality
Idh Idh HOOK
DETAILING A OR G
db
CRITICAL SECTION

CRITICAL SECTION

DIMENSION
db

A OR G
HOOK

12db FOR #6,#7,#8


FOR #8 BARS Health R
D

6db FOR #3,#4,#5


J

NOTE:
A OR G

AND SMALLER ADJUST SLAB BLOCKOUT


12db
D

4db OR 4db #3-#8 DIMENSION AS REQ'D. TO


6d

2 1/2" min. ACCOMMODATE BASE PLATE SIZE


B

5db #9-#11
HOSPITALITY
H

6db #14-#18
DIMENSION
DIMENSION

DETAILING
DETAILING

db
90° HOOK 180° HOOK D
D
CL. CONSTRUCTION
REINFORCEMENT DEVELOPMENT HEALTH ER
D

RECOMMENDED END HOOKS, ALL GRADES OR CONTROL JOINT


SCHEDULE
180° HOOK 90° HOOK HOOK DEVELOPMENT LENGTH
A OR G
24" SQUARE
f 'c = 3000 psi, LAP CLASS B
TYLER
BAR FINISHED BEND BLOCK-OUT
SIZE DIAMETER D. (IN.) A OR G (IN.) J (IN.) A OR G (IN.) Idh (IN.) 90° HOOK 135° HOOK
BAR
DEVELOPMENT
DEVELOPMENT
LAP SPLICE LAP SPLICE LENGTH
TENSION
EXPANSION
1'-6" LENGTH LENGTH
#3 2 1/4 5 3 6 9
STIRRUP AND TIE HOOKS, ALL TYP.
SIZE COMPRESSION
LENGTH TENSION
COMPRESSION TOP BARS OTHER BARS
Tyler, Texas
#4 3 6 4 8 11 #3 0'-9" 1'-5" 1'-0" 2'-4" 1'-10"
GRADES
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

#4 0'-11" 1'-10" 1'-3" 3'-1" 2'-5"


#5 3 3/4 7 5 10 14 90° HOOK 135° HOOK
BAR D #5 1'-2" 2'-4" 1'-7" 3'-11" 3'-0"
#6 4 1/2 8 6 12 17 SIZE (IN.) H
A OR G (IN.) A OR G (IN.)
#6 1'-5" 2'-9" 1'-11" 4'-8" 3'-7"
#7 5 1/4 10 7 14 19 #7 1'-7" 4'-0" 2'-3" 6'-9" 5'-3"
#3 1 1/2 4 4 2 1/2 SEE PLAN FOR FILE NAME:
#8 6 11 8 16 22 COLUMN #8 1'-10" 4'-7" 2'-6" 7'-9" 6'-0"
#4 2 4 1/2 4 1/2 3 (1) #4 @ EA. 20-019-STRUCTURAL
SIDE (TYP.) #9 2'-1" 5'-2" 2'-10" 8'-9" 6'-9"
#9 9 1/2 15 11 3/4 19 25
#5 2 1/2 6 5 1/2 3 3/4
#10 2'-4" 5'-10" 3'-2" 11'-10" 7'-7"
PROJECT NUMBER:
(1) #4 PLACED @ EA.
#10 10 3/4 17 13 1/4 22 28
#6 4 1/2 12 8 4 1/2 SIDE OF BLOCK-OUT 1909
#11 12 19 14 3/4 24 31
#7 5 1/4 14 9 5 1/4 SHEET CONTENTS:
#14 18 1/4 27 21 3/4 31 37
#8 6 16 10 1/2 6
TYPICAL FOUNDATION
DETAILS
#18 24 36 28 1/2 41 50

11 TYPICAL END HOOKS 12 TYPICAL STIRRUP AND TIE HOOKS 13 TYPICAL COLUMN BLOCK-OUT DETAIL (PLAN VIEW) 14 REINFORCEMENT DEVELOPEMENT SCHEDULE
S2.1 SCALE: NONE S2.1 SCALE: NONE S2.1 SCALE: 3/4" = 1'-0" S2.1 SCALE: NONE

S
2.1
9/11/2020 11:15:56 AM

CONT. TOP REINF. PROVIDE (3) TIES MIN.


@ EA. LAP
PROVIDE 90° BEND OF
REF. FIN. FLR.
TOP REINF. @ STEP

SEE PLAN
"H"

AS DETAILED
09/11/2020

AS DETAILED
L L
L L PROVIDE NUT
X B LINE OF X X LINE OF & WASHER
REF. FIN. FLR. THACKER | DAVIS ARCHITECTS
X X CONC. CONC. X X
ANCHOR ROD SCHEDULE

PROJ.
I N C O R P O R A T E D
Y

(B)
Y

Y
Member American Institute of Architects

.
1100 Judson Rd., Suite 620 PO Box 2723

B
EQ

EQ

EQ
Longview, Texas 75606-2723

TYPE A B C D
& PL.

& PL.
COL.

COL.
"H" .
CL.

CL.
Phone 903.236.3771 Fax 903.753.7317

COL.

COL.
W

W
CL.

CL.
(A) Ø HILTI
EQ

EQ

EQ
AR-4 5/8" Ø 2 1/2" 5 5/8" N/A Email: T D A @ T - D A r c h i t e c t s . c o m
HAS-E ROD w w w . T - D A r c h i t e c t s . c o m

TYPICAL GRADE BEAM STEP DETAIL

(C)
A A 3

Y
Y

Y
EQ EQ A
1/4 1/4 7/8"Ø DRILLED
HOLD S2.2 SCALE: 3/4" = 1'-0"
CL. COL. 1/4 1/4 CL. COL. NOTES:
CL. COL. CL. COL.
& PL. & PL. 1. ALL ANCHOR RODS SHALL HILTI HAS-E THREADED ROD.
& AR & AR PROVIDE (3) TIES MIN. LINE OF BRICK LEDGE
2. THREAD LENGTH SHALL MATCH PROJECTION HEIGHT.
3. INSTALL HAS-E RODS INTO HILTI HIT-RE 500 V3 EPOXY PER @ EA. LAP
BP-1/BP-2/BP-2A/BP-3/BP-4A BP-1B BP-1C BP-1D AR-4
MANUF. INSTRUCTIONS.
CONT. TOP REINF. LINE OF
CONTRACTOR NOTE: PLINTH FIN. FLR. STRUCTURAL ENGINEER:
PLATE WASHERS SHALL BE INSTALLED AT EACH
EL. RE: PLAN
BASE PLATE SCHEDULE PROVIDE NUT
& WASHER
BASE PLATE SPECIFICALLY NOTED IN BASE PLATE
SCHEDULE. PLATE WASHERS SHALL BE SHIPPED
LOOSE (1 WASHER PER BOLT). PLATE WASHERS
DIMENSIONS ANCHOR
SHALL BE FIELD WELDED W/ 1/4" x 2" FILLET WELDS

PROJ.

GROUT
ALL AROUND. (TYP. EACH PLATE WASHER)
ANCHOR ROD SCHEDULE

(B)

(D)
MARK L W X Y A B THICK RODS NOTES LEVELING NUT TYPE A B C D
3/8"x3"x3"
WASHER W/
HSS4x4 BP-1 10" 10" 1 1/2" 1 1/2" 3/4" (4) AR-1 STD. HOLE

SEE PLAN
HSS6x6 BP-1 12" 12" 1 1/2" 1 1/2" 3/4" (4) AR-1 (A) Ø ASTM AR-1 3/4" Ø 4" 9" 1 1/2"

"H"
CONT. BOTT. REINF.

& PL.
COL.
HSS6x6 BP-1B 12" 12" 1 1/2" 1 1/2" 4 1/4" 4 1/2" 3/4" (4) AR-4 EPOXY BOLTS F1554 GR. 36 A.R.

(C)

CL.
AR-2 1" Ø 5" 12" 1 1/2" Physical: 16291 FM 849
HSS6x6 BP-1C 12" 12" 1 1/2" 1 1/2" 3 1/2" 3/4" (4) AR-1 Mail: P.O. BOX 2428
PROVIDE BOLT Lindale, Texas 75771
HSS6x6 BP-1D 12" 12" 1 1/2" 1 1/2" 3 1/2" 3 1/2" 3/4" (4) AR-1 AR-3 1 1/4" Ø 5 1/2" 15" 1 1/2"
Phone: 903.882.8503 / Fax 903.882.5318
HEAD OR NUT
HSS6x6 BP-2A 14" 14" 2" 2" 1 1/2" (4) AR-2 PL WASHERS PER 2A/S2.2 EDGE OF CONC. FTG. WWW.HOLLANDENGR.COM
W/ DAMAGED NOTES:
HSS8x8 BP-1 14" 14" 1 1/2" 1 1/2" 3/4" (4) AR-1 Texas Firm #: F-8474
THREADS 1. ALL ANCHOR RODS SHALL BE ASTM F1554, GRADE 36.
HSS8x8 BP-2 16" 16" 2" 2" 1" (4) AR-2 CL. COL. 1/4 HE #: 20-019
2. THREAD LENGTH SHALL MATCH PROJECTION HEIGHT.
HSS8x8 BP-2A 16" 16" 2" 2" 1" (4) AR-2 PL WASHERS PER 2A/S2.2 IF NUT IS USED, & PL.
3. GROUT SHALL BE NON-SHRINK NON-METALLIC GROUT WITH A
HSS8x8 BP-3 16" 16" 2" 2" 2" (4) AR-2 EXTEND ROD 1" NOTE:
HSS8x8 BP-4A 16" 16" 2" 2" 2" (4) AR-3 PL WASHERS PER 2A/S2.2 AR-1/AR-2/AR-3 PAST NUT
MINIMUM COMPRESSIVE STRENGTH OF 5000 PSI AT 28 DAYS.
2A - PL. WASHER DETAIL PLINTH & SPREAD FOOTING REINF. NOT
SHOWN FOR CLARITY
"H" PROVIDE DOWEL TO MATCH BOTT.
REINF. LAP 2'-0" W/ BOTT. BARS
HSS10x10 BP-1 18" 18" 2" 2" 2" (4) AR-2

1 BASEPLATE SCHEDULE 2 ANCHOR ROD DETAILS AND SCHEDULE 4 TYPICAL GRADE BEAM STEP
S2.2 SCALE: 3/4" = 1'-0" S2.2 SCALE: 3/4" = 1'-0" S2.2 SCALE: 3/4" = 1'-0"

1'-0" PLAN DIM. - COORD. W/ ELEVATOR SUPPLIER DRAWINGS 1'-0"

FIN. FLR.
EL. RE: PLAN

A
PROVIDE PIT LADDER CMU WALLS NOT SHOWN
PER ELEVATOR SUPPLIER FOR CLARITY
SPECIFICATIONS 3 3/8" 6 5/8"

WALL STUD AS DTL'D


W/ CONT. BOTT. TRACK
TO MATCH GAGE

VARIES
10"

L4x4x3/8 x SILL OPENING W/ 1/2"Ø x 4


1/2" LONG HILTI KWIK BOLT 3 10"
#4 HORIZ. @ 12"o.c. EA FACE
NOTE:
ANCHORS @ 24"o.c. (VERIFY SIZE W/ WALL STUD NOT COL. PER PLAN
MANUF.) FIN. FLR. SHOWN FOR CLARITY
8'-1"

#5 VERT. @ 16"o.c. EA FACE


EL. RE: PLAN
CONT. 2x KEY W/ SYNKO-FLEX FINISH ANCHOR RODS
COORDINATE ELEV. PIT #4 @ 16"o.c. PER 2/S2.2
WATERSTOP PER ARCH'L
DIMS W/SUPPLIER EA. WAY
EA. FACE WATERPROOFING #3 SLAB DOWEL x 2'-6"
LINE OF SLAB
MEMBRANE W/ @ 24"o.c. 2 BLOCK-OUT

2'-6"
(2) #4 CONT.
PROTECTION BOARD
FOR ALL CONCRETE FIN. FLR.
FINISH GRADE FIN. FLR.
BELOW FIN. GRADE EL. RE: PLAN 5 1/2"
EL. RE: PLAN

MAX.
8"

6"
4'-0"

8"
COMPACTED #5 @ 12"o.c. (2) #4 CONT.
2'-6"

SELECT FILL EA. WAY #4 DWLS x SLAB PER PLAN HSS COL. PER PLAN
1'-0" 4"Ø PERFORATED PIPE IN 1'-2"
@ 16"o.c. EA. CONT. 2x KEY W/ SYNKO-FLEX #3 TIES @ 10"o.c.
PROVIDE WATERPROOFING FILTER FABRIC SLEEVE WATERSTOP LINE OF SLAB ANCHOR RODS PER 2/S2.2
WAY EA. FACE PER 9/S2.1, U.N.O.
W/ 1/4" PEA GRAVEL

3'-0"
MEMBRANE & BLOCK-OUT G.B. REINF. SHALL BE

3'-0"
SLOPE PIT

2'-6" MIN.
PROTECTION BOARD WRAPPED IN GEOFABRIC #5 SLAB DOWEL x 1'-0" CONT. THRU PLINTH
1'-6" SQ. TO DRAIN FIN. FLR. #5 VERT.

H ospi ality
@ 24"o.c. PER 9/S2.1

4'-0"
SUMP PIT EL. RE: PLAN
CONT. 2x KEY

8"
CONT. 2x KEY W/ SYNKO-FLEX W/ SYNKO-FLEX
WATERSTOP LINE OF GR. BM.
CONT. 2x KEY
WATERSTOP
BEYOND
Health R
1'-0"

W/SYNKO-FLEX
1'-6"

WATERSTOP

2'-0"
(3) #6 CONT. T&B
#5 @ 12"o.c.
HOSPITALITY

2'-0"

SCHD.
SEE
EA. WAY BOTTOM
#6 @ 10"o.c.
CONT. 2x KEY
HEALTH ER
1'-0"

W/SYNKO-FLEX
WATERSTOP #5 DOWELS x
SCHED. FTG., CL. COL.
1'-6" 1'-6"
@ 12"o.c.
N.T.S. & FTG. TYLER
3" CONC.

2'-4" 11"
COVER

PER PLAN CL. COL. SCHED. FTG.


6"
3'-3" & FTG. N.T.S. EXPANSION
Tyler, Texas
5 SECTION AT ELEVATOR PIT 6 SECTION 7 SECTION 8 SECTION
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

S2.2 SCALE: 3/4" = 1'-0" S2.2 SCALE: 3/4" = 1'-0" S2.2 SCALE: 3/4" = 1'-0" S2.2 SCALE: 3/4" = 1'-0"

MAT PER PLAN NOTE:


REINF. NOT SHOWN
FOR CLARITY FILE NAME:
FIN. FLR.
20-019-STRUCTURAL
EL. RE: PLAN PROJECT NUMBER:
SEE
T.O. PL.

1909
1'-4"

SCHED.
GALVANIZED 3/4"x8"x8" 1/4
BEARING PL. SHEET CONTENTS:
2'-8"

FOUNDATION DETAILS
NOTE:
6"

COAT ALL WELDS W/


COLD GALVANIZING
COMPOUND

HELICAL PIER SCHEDULE


HELICAL SCREW PILE,
HELICAL PIER AS HOLE FOR BOLT FOR INSTALL TO MINIMUM
INDICATED ON PLAN UPLIFT - COORD. W/ DEPTH AND DESIGN
TYPE WORKING LOAD ULTIMATE LOAD CAP PL.
SUPPLIER TORQUE TO ACHIEVE HP-1 15 kips 30 kips 8"x8"
SCHEDULED DESIGN LOAD
SEE SCHED.

NOTES:
MULTI HELIX PIER
SEE SCHED.

1. WORKING LOAD DENOTES THE ALLOWABLE STRESS LOAD DOWNWARD REACTION


HELICAL PIER LEAD AS REQ'D.
2. UPLIFT LOAD DENOTES THE ALLOWABLE STRESS LOAD UPWARD REACTION.
SECTION W/ 3. TEST PIERS, IF REQ'D., SHALL NOT BE A PART OF THE PERMANENT ASSEMBLY.
BEARING PLATE(S)

CL. HELICAL
4. ADD'L. GEOTECHNICAL TESTING, IF REQ'D., SHALL BE COORDINATED W/ THE OWNER.
5. REFER TO HELICAL PIER GENERAL NOTES FOR ADDITIONAL INFORMATION. S
ANCHOR & GR. BM.

2.2
9 TYPICAL HELICAL PIER DETAIL & SCHEDULE
S2.2 SCALE: 3/4" = 1'-0"
9/11/2020 11:15:59 AM

CONTRACTOR NOTE: CONTRACTOR NOTE:


EXISTING INFORMATION EXISTING INFORMATION 3 3/8" 6 5/8"
SHOWN HERE IS FOR 1" EXP. JT. 3 3/8"
SHOWN HERE IS FOR 1" EXP. JT.
ILLUSTRATION ONLY - 8" CMU WALL W/ VERT. ILLUSTRATION ONLY - 8" CMU WALL W/ VERT.
FIELD VERIFY REINF. PER 4/S3.2 FIELD VERIFY REINF. PER 4/S3.2 FINISH 3 3/8" 6 5/8"
PER ARCH'L FINISH
DOWEL TO MATCH HORIZ. LADDER TYPE DOWEL TO MATCH HORIZ. LADDER TYPE FINISH WALL STUD AS DTL'D WALL STUD AS DTL'D PER ARCH'L WALL STUD AS DTL'D
WALL REINF. @ EA. JOINT REINF. @16"o.c. PER ARCH'L W/ CONT. BOTT. TRACK 1/2" ASPHALTIC W/ CONT. BOTT. TRACK W/ CONT. BOTT. TRACK
WALL REINF. @ EA. JOINT REINF. @16"o.c. 1/2" ASPHALTIC
VERT. BAR LOCATION TO MATCH GAGE BOARD CAPPED W/
VERT. BAR LOCATION TO MATCH GAGE BOARD CAPPED W/ TO MATCH GAGE
COMPRESSIBLE
SEALANT COMPRESSIBLE
SEALANT
(2) #4 CONT. #3 SLAB DOWEL x 2'-6" (2) #4 CONT. #3 SLAB DOWEL x 2'-6" (2) #4 CONT. #3 SLAB DOWEL x 2'-6" #4 DWLS. x 3'-0" LG. #3 SLAB DOWEL x 2'-6" #3 SLAB DOWEL x 2'-6" #3 SLAB DOWEL x 2'-6"
#4 DWLS. x 3'-0" LG.
@ 24"o.c. @ 24"o.c. @ 24"o.c. @ 16"o.c. AT DOOR @ 24"o.c. @ 24"o.c. @ 24"o.c. 09/11/2020

2'-6"

2'-6"

2'-6"

2'-6"

2'-6"
2'-6"
@ 16"o.c. AT DOOR
EA. WAY
EXISTING BLDG. EXISTING BLDG. FINISH GRADE PAVEMENT PAVEMENT
FIN. FLR. FIN. FLR. FIN. FLR. BY OTHERS FIN. FLR. BY OTHERS FIN. FLR. FIN. FLR.
EL. RE: PLAN EL. RE: PLAN EL. RE: PLAN EL. RE: PLAN EL. RE: PLAN EL. RE: PLAN

MAX.
6"
8"

8"

8"

8"

8"
8"
(2) LAYERS OF 1/2" (2) #4 CONT. THACKER | DAVIS ARCHITECTS
(2) LAYERS OF 1/2" (2) #5 CONT. T&B ASPHALTIC BOARD (2) #5 CONT. (2) #5 CONT. T&B (2) #5 CONT. T&B (2) #4 CONT. (2) #5 CONT. T&B (2) #5 CONT. T&B I N C O R P O R A T E D
3" CONC. 3" CONC. Member American Institute of Architects
ASPHALTIC BOARD T&B COVER TYP. COVER TYP. .

3'-0"

3'-0"

3'-0"

3'-0"

3'-0"
1100 Judson Rd., Suite 620 PO Box 2723
#3 TIES @ 24"o.c.

2'-6" MIN.
Longview, Texas 75606-2723
#3 TIES @ 24"o.c. #3 TIES @ 24"o.c. #3 TIES @ 24"o.c. 3" CONC. #3 TIES @ 24"o.c. .
Phone 903.236.3771 Fax 903.753.7317
3" CONC. #3 TIES @ 24"o.c.
COVER TYP.
3" CONC. COVER TYP. (2) #5 CONT. MID. Email: T D A @ T - D A r c h i t e c t s . c o m
(2) #5 CONT. MID. (2) #5 CONT. MID. (2) #5 CONT. MID. (2) #5 CONT. MID.
COVER TYP. w w w . T - D A r c h i t e c t s . c o m

5'-0"
#5 CONT. @
LINE OF G.B.

MIN.
12"o.c. EA. FACE

6"
BETOND
1'-2"
1'-2" 1'-2" 1'-2"
1'-2"

1" CEMENTITIOUS
RETAINER BOARD
STRUCTURAL ENGINEER:

1'-2"

1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 SECTION 6 SECTION


S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0"

CONTRACTOR NOTE:
A CONTRACTOR NOTE:
EXISTING INFORMATION
6 EXISTING INFORMATION 6 11
10" 1" EXP. JT. SHOWN HERE IS FOR 1" EXP. JT. Physical: 16291 FM 849
SHOWN HERE IS FOR 8" CMU WALL W/ VERT. 8" CMU WALL W/ VERT. 8" CMU WALL W/ VERT. Mail: P.O. BOX 2428
ILLUSTRATION ONLY -
ILLUSTRATION ONLY - REINF. PER 4/S3.2 REINF. PER 4/S3.2 REINF. PER 4/S3.2 Lindale, Texas 75771
FORM CURB WALL FIELD VERIFY Phone: 903.882.8503 / Fax 903.882.5318
FIELD VERIFY
AROUND COL. DOWEL TO MATCH DOWEL TO MATCH DOWEL TO MATCH WWW.HOLLANDENGR.COM
WALL REINF. @ EA. WALL REINF. @ EA. WALL REINF. @ EA. Texas Firm #: F-8474
#4 HORIZ. @ 12"o.c. EA FACE CONTRACTOR NOTE: HE #: 20-019
NOTE: NEW HSS6x6x1/4 VERT. BAR LOCATION NEW HSS6x6x1/4 VERT. BAR LOCATION VERT. BAR LOCATION
COL. PER PLAN COL. PER PLAN EXISTING INFORMATION
WALL STUD NOT
HORIZ. LADDER TYPE HORIZ. LADDER TYPE HORIZ. LADDER TYPE SHOWN HERE IS FOR
SHOWN FOR CLARITY
#5 VERT. @ 16"o.c. EA FACE JOINT REINF. @16"o.c. JOINT REINF. @16"o.c. JOINT REINF. @16"o.c. ILLUSTRATION ONLY -
CONT. 2x KEY W/ SYNKO-FLEX FIELD VERIFY
FINISH ANCHOR RODS
EXISTING WALL (2) #4 CONT. EXISTING WALL (2) #4 CONT. (2) #4 CONT.
PER ARCH'L WATERSTOP PER 2/S2.2
ANCHOR RODS #3 SLAB DOWEL
PER 2/S2.2 LINE OF SLAB ANCHOR RODS #3 SLAB DOWEL x 2'-6" ANCHOR RODS #3 SLAB DOWEL x 2'-6" 2'-6" x @ 24"o.c. EXISTING WALL
(2) #4 CONT. LINE OF SLAB BLOCK-OUT PER 2/S2.2 @ 24"o.c. PER 2/S2.2 @ 24"o.c.

2'-6"
2'-6"

2'-6"
BLOCK-OUT
FINISH GRADE FIN. FLR. FIN. FLR. FIN. FLR. FIN. FLR. FIN. FLR.
EL. RE: PLAN EL. RE: PLAN EL. RE: PLAN EL. RE: PLAN EL. RE: PLAN
MAX.
6"

8"

8"

8"

8"

8"
(2) LAYERS OF 1/2"
EXISTING FDN. ASPHALTIC BOARD & (2) #5 CONT. T&B
#3 TIES @ 10"o.c. #3 TIES @ 10"o.c. (2) #5 CONT. T&B
CAP W/ COMPRESSIBLE (2) #5 CONT. T&B 1" EXP. JT. W/ (2)
#3 TIES @ 24"o.c.

3'-0"
PER 9/S2.1, U.N.O. 3" CONC. PER 9/S2.1, U.N.O. #3 TIES @ 24"o.c. SEALANT @ DOORS LAYERS OF 1/2"
G.B. REINF. SHALL BE
3'-0"

3'-0"

3'-0"
COVER TYP. (2) LAYERS OF 1/2" DRILL & EPOXY SET #3 TIES @ 24"o.c. ASPHALTIC BOARD
2'-6" MIN.

CONT. THRU PLINTH #5 VERT. #5 VERT. DRILL & EPOXY SET 1/2"Ø SMOOTH DOWELS
ASPHALTIC BOARD &
PER 9/S2.1 PER 9/S2.1 CAP W/ COMPRESSIBLE 1/2"Ø SMOOTH DOWELS x 1'-4" LONG @ 16"o.c.
(2) #5 CONT. MID.
CONT. 2x KEY SEALANT @ DOORS x 1'-4" LONG @ 16"o.c. EMBED 4 1/2" INTO
W/ SYNKO-FLEX EMBED 4 1/2" INTO EXIST. W/ HILTI HIT-RE DRILL & EPOXY SET #5
LINE OF GR. BM. CONC. PLINTH PER PLAN

5'-0"
WATERSTOP EXIST. W/ HILTI HIT-RE 500 V3 ADHESIVE PER DOWELS T&B x
BEYOND 500 V3 ADHESIVE PER MANUF. INSTRUCTIONS @12"o.c. EMBED 5 1/2" 1'-6" EXISTING FDN.
MANUF. INSTRUCTIONS EXISTING FDN. @ DOORS INTO EXIST. W/ HILTI HIT-
BRACKET & CONN. @ DOORS RE 500V3 ADHESIVE PER
(2) #5 CONT. MID. MANUF. INSTRUCTIONS 1'-2"
BY HELICAL PIER 1'-2"
SUPPLIER #5 CONT. @ 12"o.c. BRACKET & CONN.
SEE SCHED.

EA. FACE BY HELICAL PIER (3) #5 CONT.


SCHED.

SUPPLIER
SEE

2'-0"
HP BY HELICAL
PIER SUPPLIER
1'-2"
BRACKET & CONN.
CONT. FTG. BY HELICAL PIER
BEYOND HP BY HELICAL SUPPLIER
PIER SUPPLIER
WALL FTG. REINF.
CL. COL. SCHED. FTG. CL. COL. SCHED. FTG. HP BY HELICAL
SHALL BE CONT.
& FTG. N.T.S. & FTG. N.T.S. PIER SUPPLIER
THRU COLUMN
FOOTING

7 SECTION 8 SECTION 9 SECTION 10 SECTION 11 SECTION


S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0"

G
3 3/8" 6 5/8"

FINISH
PER ARCH'L
WALL STUD AS DTL'D
W/ CONT. BOTT. TRACK
TO MATCH GAGE 9 3/8"
3 H ospi ality
2
(2) #4 CONT. #4 SLAB DOWEL x 2'-6"
FINISH
PER ARCH'L
COL. PER PLAN
(2) #4 CONT. #4 SLAB DOWEL x 2'-6"
Health R
@ 24"o.c. 2'-6" @ 24"o.c.

2'-6"
2'-6"

LINE OF SLAB #4 SLAB DOWEL x


BLOCK-OUT @ 24"o.c.

2'-6"
(2) #4 CONT. #3 x 2'-6" 2'-6

FIN. FLR.
(2) #4 CONT.
FIN. FLR. FIN. FLR. FIN. FLR.
@ 12"o.c.
"
HOSPITALITY
ANCHOR RODS
EL. RE: PLAN
PER 2/S2.2
EL. RE: PLAN EL. RE: PLAN EL. RE: PLAN CONT. 2x KEY W/ NOTE: STAIR TREADS AND RISERS ARE
HEALTH ER
8"

8"

SYNKO-FLEX DOWEL REINF. TO SHOWN FOR GENERAL ARRANGEMENT

1'-0"
WATERSTOP CHEEK WALLS EA. END ONLY - COORDINATE TREAD AND RISER

#5 @ 12" o.c.
#5 @ 12" o.c.
QTY. & DIMS. W/ ARCH'L. DWGS. TYLER
EA. FACE
EA. FACE
STEM WALL REINF.
#3 TIES @ 10"o.c.
PER 9/S2.1, U.N.O.
CONT. 2x KEY W/
SYNKO-FLEX #6 VERT. @ 12"o.c.
#3 SLAB DOWEL x
@ 18"o.c.
11"
EXPANSION
SHALL BE CONT.

5.5"
#6 VERT. @ 12"o.c. #5 HORIZ. (1) #3 EA.
THRU PLINTH WATERSTOP EA. FACE
EA. FACE
#6 VERT. WATERPROOFING
@ 12"o.c.
EA. FACE
NOSING Tyler, Texas
PER 9/S2.1
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

4"
MEMBRANE W/ #3 @ 12"o.c.
3'-5"

2"Ø PVC WEEPS @ CONTINUOUS GRAVEL


EA. WAY

3'-1"
8'-0"o.c. W/ MESH DRAIN (3/4" MIN. ROCK PROTECTION BOARD
SCREENS - OWNER SIZE) CENTERED @ FOR ALL CONCRETE
SHALL MAKE PERIODIC WEEP HOLE - WRAP W/
1'-0" BELOW FIN. GRADE #6 VERT. 2'-6"
INSPECTIONS TO FILTER FABRIC SLAB REINF. @ 12"o.c. 1" TYP. #3 x
ENSURE DRAINS ARE PER PLAN, #3 SLAB DOWEL x 2'-6" @ 12"o.c.
EA. FACE
7'-1"

7'-1"

FREE FROM CLOGS & TYP. @ 24"o.c. 1'-0" FILE NAME:


2'-6"

DEBRIS
FIN. FLR. FIN. FLR. 20-019-STRUCTURAL
FINISH GRADE EL. RE: PLAN EL. RE: PLAN
FINISH GRADE PROJECT NUMBER:
9'-1"

1'-0"
WATERPROOFING #3 SLAB DOWEL x 2'-6" CEMENT STABILIZED 1909
MEMBRANE W/ @ 24"o.c. SAND

2'-6"
PROTECTION BOARD 1'-2"
WATERPROOFING 1'-0" WATERPROOFING 4"Ø PERFORATED PIPE IN FOR ALL CONCRETE SHEET CONTENTS:
MEMBRANE W/ MEMBRANE W/ FILTER FABRIC SLEEVE (2) #5 CONT. W/ #5 1'-0"
BELOW FIN. GRADE FOUNDATION DETAILS

3'-0"
3'-0"

PROTECTION BOARD PROTECTION BOARD W/ 1/4" PEA GRAVEL CROSS BARS @


FOR ALL CONCRETE FOR ALL CONCRETE WRAPPED IN GEOFABRIC 12"o.c.
#3 SLAB DOWEL x 0'-6"
BELOW FIN. GRADE BELOW FIN. GRADE
@ 24"o.c.
4'-6"

CONT. 2x KEY 4"Ø PERFORATED PIPE IN CONT. 2x KEY


CONT. 2x KEY #5 @ 12"o.c. T&B W/ SYNKO-FLEX FILTER FABRIC SLEEVE W/ SYNKO-FLEX
1'-2"
W/ SYNKO-FLEX WATERSTOP W/ 1/4" PEA GRAVEL WATERSTOP
WATERSTOP WRAPPED IN GEOFABRIC
#5 @ 12"o.c. T&B 1'-0"
#5 SLAB DOWEL x
(3) #5 CONT. T&B CONT. 2x KEY W/ #5 SLAB DOWEL x 1'-0" @ 24"o.c.

4'-2"
SYNKO-FLEX @ 24"o.c.

2'-0"
2'-0"

2'-0"

2'-0"

4'-2"

WATERSTOP
(3) #5 CONT. T&B (3) #5 CONT. T&B

2'-6" CL. COL. 2'-0"


& FTG. 2'-0"

3'-0"

S
12 SECTION 13 SECTION 14 SECTION 15 SECTION
S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0" S2.3 SCALE: 3/4" = 1'-0" 2.3
9/11/2020 11:16:00 AM

NON-LOAD BEARING LIGHT GAGE STEEL HEADER SCHEDULE #10 TEK SCREWS
@ 10"o.c. EA. SIDE
TRACK
HEADER TO FULL HEIGHT JAMB STUD HEAD CONN. BASE CONN. SILL TO JAMB STUD @ EA. END SILL TO JAMB
CLEAR HEADER MEMBER SIZE HEADER
JAMB CONN. EACH END OF HEADER @ JAMB @ JAMB
SILL MEMBER SIZE
JAMB CONN. (OR SUPPORT
09/11/2020
SPAN [1] ORIENTATION [6] OF HEADER - [3]
[2] [3] [4] [5] [7] STUD) CONN. - [7]
SILL - [6]
HEAD CONN. A JAMB - [4]
(1) EasyClip™ S545
HDR-1 (1) EasyClip™ S545 (1) Fast Top™ FTC5 (1) EasyClip™ S545
(2) 600S162-43 VERT. VERT. (1) 600S200-54 W/ (5) #10 TEK (1) 600T125-43 PROVIDE SECTION OF TRACK JAMB STUD @ EA.
4'-0" WINDOW T&B EA. END W/ (5) #10 TEK W/ (2) HILTI EA. END W/ (5) #10 TEK (2) ROWS #12 TEK
(2) 600T125-43 HORIZ. SCREWS & (4) & ATTACH TO HEADER & JAMB W/ END OF HEADER - [3]
INFILL SCREWS EA. LEG X-S16P8TH SCREWS EA. LEG SCREWS @ 12"o.c.
HILTI X-C22P8TH #10 TEK SCREWS @ 2"o.c.
(1) EasyClip™ S545 THACKER | DAVIS ARCHITECTS
HDR-2 (1) EasyClip™ S545 (1) Fast Top™ FTC5 BASE CONN. I N C O R P O R A T E D
(2) 600S162-43 VERT. VERT. (1) 600S200-68 W/ (5) #10 TEK N/A N/A @ JAMB - [5] Member American Institute of Architects
6'-4" DOOR T&B EA. END W/ (5) #10 TEK W/ (2) HILTI
(2) 600T125-43 HORIZ. SCREWS & (4) .
INFILL SCREWS EA. LEG X-S16P8TH 1100 Judson Rd., Suite 620 PO Box 2723
HILTI X-C22P8TH Longview, Texas 75606-2723
OPENING STUD .
Phone 903.236.3771 Fax 903.753.7317
(1) EasyClip™ S545
HDR-3 (1) EasyClip™ S545 (1) Fast Top™ FTC5
(2) 600S162-43 VERT. VERT. (1) 600S200-68 W/ (5) #10 TEK N/A N/A Email: T D A @ T - D A r c h i t e c t s . c o m
3'-4" DOOR T&B EA. END W/ (5) #10 TEK W/ (2) HILTI SCREWS & (4)
(2) 600T125-43 HORIZ.
BUILT-UP JAMB
w w w . T - D A r c h i t e c t s . c o m
INFILL SCREWS EA. LEG X-S16P8TH HILTI X-C22P8TH

(1) EasyClip™ S545


HDR-4 (1) EasyClip™ S545 (1) Fast Top™ FTC5
(2) 600S162-43 VERT. VERT. (2) 600S200-54 W/ (5) #10 TEK N/A N/A
6'-4" DOOR T&B EA. END W/ (5) #10 TEK W/ (2) HILTI STRUCT'L. FRAMING
(2) 600T125-43 HORIZ. (1) 600T125-54 SCREWS & (4)
INFILL SCREWS EA. LEG X-S16P8TH BY OTHERS
HILTI X-C22P8TH

HDR-5 (1) EasyClip™ S545 (1) Fast Top™ FTC5


(2) EasyClip™ S545
COMBINED
HEADER
TOP TRACK
HEAD CONN.
NESTED SILL
(2) 600S200-54 VERT. VERT. (2) 600S250-54 W/ (5) #10 TEK N/A N/A @ JAMB - [4]
10'-8" DOOR T&B EA. END W/ (5) #10 TEK W/ (2) HILTI
(2) 600T125-54 HORIZ. (1) 600T125-54 SCREWS & (4)
INFILL SCREWS EA. LEG X-S16P8TH HILTI X-C22P8TH SILL TO JAMB
STRUCTURAL ENGINEER:
PROVIDE SECTION OF (OR SUPPORT
(1) EasyClip™ S545
HDR-6 (1) EasyClip™ S545 (1) Fast Top™ FTC5 TRACK & ATTACH TO SILL - [6] STUD) CONN. - [7]
(2) 600S162-43 VERT. VERT. (1) 600S200-54 W/ (5) #10 TEK N/A N/A
4'-4" DOOR T&B EA. END W/ (5) #10 TEK W/ (2) HILTI WALL STUD HEADER & JAMB W/ #10
(2) 600T125-43 HORIZ. SCREWS & (2)
INFILL SCREWS EA. LEG X-S16P8TH TEK SCREWS @ 2"o.c.
HILTI X-S16P8TH COMBINED JAMB STUD @ EA.
HEADER END OF HEADER - [3]
HEADER TO JAMB
CONN. - [2]
HEADER - [1] BASE CONN.
@ JAMB - [5]
HEADER TO JAMB
HORIZONTAL
VERTICAL BOXED CONN. - [2]
HEADER
NOTES: HEADER JAMB STUD @ EA.
1. HEADER SHALL BE INSTALLED AT WINDOW/DOOR HEAD - COORDINATE ELEVATION WITH ARCHITECTURAL DRAWINGS. END OF HEADER - [3] Physical: 16291 FM 849
HEADER - [1] Mail: P.O. BOX 2428
2. FOR HEADER SPANS NOT LISTED, USE NEXT LARGER SIZE.
Lindale, Texas 75771
3. FILL HEADERS WITH INSULATION PRIOR TO ERECTION. HORIZTONTAL VERTICAL Phone: 903.882.8503 / Fax 903.882.5318
4. REFER TO 02/S3.1 & 11/S3.1 FOR HEADER DETAIL. HEADER BOXED HEADER WWW.HOLLANDENGR.COM
5. ALL CONNECTIONS OF HEADER, SILL, OR BASE TO JAMB SHALL BE FASTENED WITH (4) #12 TEK SCREWS OR (5) #10 TEK SCREWS TO EACH MEMBER. Texas Firm #: F-8474
6. ATTACH HEADER, JAMB & SILL COMPONENTS TOGETHER W/ #12 TEK SCREWS @ 12"o.c. EA. SIDE OR #10 TEK SCREWS @ 10"o.c. EA. SIDE. HE #: 20-019
7. HEADER, JAMB, & SILL COMPONENTS SHALL BE INSTALLED FULL LENGTH - SPLICING OF MEMBERS SHALL NOT BE PERMITTED.
8. FASTEN ALL DEFLECTION CLIPS TO METAL STUDS W/ MANUFACTURER'S RECOMMENDED FASTENERS IN ALL HOLES.

BYPASS JAMB CONDITION INFILL JAMB CONDITION SINGLE TRACK SILL

1 NON-LOAD BEARING LIGHT GAGE HEADER SCHEDULE 2 ISOMETRIC NON-LOAD BEARING LIGHT GAGE HEADER & SILL DETAIL
S3.1 SCALE: NONE S3.1 SCALE: NONE

REFER TO SECTIONS
TYPICAL JAMB STUD OR POST FOR TRACK SIZE
ALL SLIP TRACKS
WHERE BRACING TERMINATES @ BUILT-UP JAMB OR SHALL BE 50 ksi
MIN. 43mil RUNNER TRACK SOLID U.N.O IN DETAIL, ATTACH TO STEEL STRUCTURE
POST, EXTEND CHANNEL INTO PUNCH-OUT. USE (1)
BLOCKING @ 10'-0"o.c. MAX. MAKE W/ (1) ROW OF HILTI X-S16P8TH PAF @ 16"o.c.
RUNNER TRACK 8" LONGER THAN 1 1/2"x1 1/2"x54mil CLIP ANGLE 1 1/4" LESS THAN STUD
TOP TRACK BLOCKING NOTE: WIDTH. ATTACH USING (4) #7 TEK SCREWS.
STUD INSIDE SPACING. CLIP

1"
PLACE SOLID BLOCKING @ INSTALLER NOTE
FLANGES ENDS OF WALL SYSTEM, 150U50-54 COLD ROLLED CHANNEL WHERE WALL STUD SPACING IS
OF TRACK 4" FROM EA. END. BEND ADJACENT TO ALL OPENINGS (1 1/2"x54mil CRC), AS DETAILED REDUCED, FASTENER SPACING
TRACK @ CLIPPED FLANGES. SLIP TRACK

MAX.
AND @ 10'-0"o.c. MAX

1'-0"
SHALL BE REDUCED ACCORDINGLY
(1) #8 TEK SCREW EA. ATTACH BLOCKING TO INSTALL STUDS W/ SAME
FLANGE PER STUD DIMENSION (1'-0" MIN.) LATERAL
WALL STUDS W/ (2) WALL STUD BRIDGING
" #10 TEK SCREWS IN EA. FOR BRIDGING ALIGNMENT WALL STUD
1'-4
FLANGE AS SHOWN.

MIN.
1'-0"
WALL STUD PROVIDE (1) ADD'L. PAF
1 1/2"x1 1/2"x54mil CLIP ANGLE EA. SIDE OF EA. TRACK " WALL STUD
1/4" LESS THAN STUD WIDTH. BOTT. TRACK 1'-4
Q. JOINT.
8" ATTACH USING (4) #7 TEK
.E
INSTALLER NOTE: EQ SCREWS. PLACE CLIP ANGLE
Q. WALL STUD " (1) #8 TEK SCREW
WHERE WALL STUD SPACING IS . E @ EA. STUD. 1'-4
REDUCED, FASTENER SPACING . EQ EA. FLANGE PER STUD
SHALL BE REDUCED ACCORDINGLY EQ
USE (6) #10 TEK SCREWS STUDS SHALL BE CUT ACCURATELY
FOR A TIGHT FIT W/ TRACK (-1/8") LATERAL BRIDGING PER
ON EA. SIDE OF BLOCKING
MAX. GAP BETWEEN END OF STUD TYPICAL BRIDGING DETAIL
U.N.O IN DETAIL, ATTACH TO STEEL STRUCTURE W/
1 1/2" x 33mil STRAPPING ON EA. SIDE OF & TOP OR BOTT. TRACK NOT
(1) ROW OF HILTI X-S16P8TH PAF @ 16"o.c. 8"
WALL STUDS @ MID-POINT, U.N.O. (STRAPPING TO MORE THAN 12" FROM TOP OF
(FASTENER LENGTH SHALL BE STL. THICKNESS +3/8") TYP. LATERAL BRACING SPLICE USE
START, END & SPLICE @ SOLID BLOCKING) STUD
-OR- (1) 12" LONG CRC INVERTED OVER U.N.O IN DETAIL, ATTACH TO STEEL STRUCTURE W/ (1) JAMB AS
ATTACH TRACK TO CONCRETE STRUCTURE W/ CENTER OF SPLICE W/ (3) #10 TEK ROW OF HILTI X-S16P8TH PAF @ 16"o.c. REQUIRED
(2) ROWS OF HILTI X-C22P8TH PAF @ 16"o.c. (STAGGER 8") (1) #10 TEK SCREW WALL STUD
SCREWS ON EA. SIDE OF SPLICE -OR-
IN EA. STUD FLANGE
INSTALLER NOTE: ATTACH TRACK TO CONCRETE STRUCTURE W/ (2) INSTALLER NOTE:
WHERE TRACK IS CONNECTED TO ROWS WHERE STUD SPACING IS
FLAT STRAP BRIDGING CRC BRIDGING 22 GA ROOF DECK, PROVIDE (3)
#8 TEK SCREWS PER STUD
OF HILTI X-C22P8TH PAF @ 16"o.c. (STAGGER 8") REDUCED, FASTENER SPACING
SHALL BE REDUCED ACCORDINGLY

3 TYPICAL TOP TRACK DETAIL 4 TYPICAL WALL BRIDGING DETAIL 5 TYPICAL BOTTOM TRACK DETAIL 6 TYPICAL EXTERIOR STUD TOP SLIP TRACK DETAIL H ospi ality
S3.1 SCALE: NONE S3.1 SCALE: NONE S3.1 SCALE: NONE S3.1 SCALE: NONE Health R
HOSPITALITY
HEALTH ER
TYLER
EXPANSION
Tyler, Texas
1 1/2"x33mil STRAP BRIDGING WHERE
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

SHOWN ON PLAN. ATTACH TO B.O.


JOIST W/ #8 TEK SCREWS.
STRAPPING TO START & END ON
SOLID BLOCKING

FILE NAME:
ATTACH TO EA. STUD W/ (3) FastClip™
FastClip™ DEFLECTION SCREWS SUPPLIED W/ CLIP. 20-019-STRUCTURAL
NOTE: U.N.O. IN DETAIL, ATTACH TO STEEL ATTACH TO COLD-FORMED MTL.
FLOOR DECK NOT SERIES CLIP ATTACH TO STEEL STRUCTURE W/ ATTACH TO EA. STUD W/ (8) #10
STRUCTURE W/ (2) HILTI X-S16P8TH PAF FRAMING W/ #10 TEK SCREWS PROJECT NUMBER:
SHOWN FOR CLARITY (3) HILTI X-S16P8TH PAF SCREWS ATTACH TO STEEL
-OR- (FILL ALL HOLES)
(FASTENER LENGTH SHALL BE STL. STRUCTURE W/ (3) HILTI X-S16P8TH
ATTACH TO CMU W/ (2) HILTI KWIK-CON II+
THICKNESS +3/8")
1909
1 1/2"

316-134 THWH (EMBED 1" MIN.) PAF T.O. STL. W/ 3/4" EDGE DISTANCE
LENGTH AND GAGE PER
-OR- (FASTENER LENGTH SHALL BE STL.
CALLOUT EXAMPLE,
THICKNESS + 3/8")
SHEET CONTENTS:
ATTACH TO ROOF DECK W/ (4) #10 TECK S543 (54mil. & 3" LONG)
LIGHT GAGE TYPICAL LIGHT GAGE
SCREWS S545 (54mil. & 5" LONG) NOTE:
STEEL FLOOR
S547 (54mil. & 7" LONG) WHERE INDICATED ATTACH CLIP TO WEB DETAILS
JOISTS OF BEAM W/ (3) HILTI X-S16P8TH PAF.
S549 (54mil. & 9" LONG)
S541 (54mil. & 11" LONG) ATTACH CLIP TO PIECE OF STUD STRUT TO
43mil SOLID UniClip ™
SCHED. 1 1/2" MATCH WALL STUD SIZE & GAGE W/
BLOCKING @ 4'-0"o.c. SERIES CLIP
WIDTH SCREWS PROVIDED W/ CLIP. ATTACH
STRUT TO STUD W/ (4) #12 TEK SCREWS.
STRUCT'L. FRAMING UniClip ™ SERIES CLIP AS
CLIP L2x2x54mil W/(4) #8 BY OTHERS
EasyClip ™ SERIES CLIP AS WALL STUD MANUFACTURED BY DIETRICH
TEK SCREWS EA. CLIP
MANUFACTURED BY ClarkDietrich Metal STRUCT'L. FRAMING METAL MANUFACTURING
Framing (1-888-437-3244) BY OTHERS WALL STUD (1-800-873-2443)
FastClip™
SERIES CLIP AS
MANUFACTURED BY DIETRICH METAL
MANUFACTURING (1-800-873-2443)

7 TYPICAL JOIST BRIDGING DETAIL 8 ClarkDietrich EasyClip™ S-SERIES DETAIL 9 DIETRICH FastClip DETAIL 10 DIETRICH UniClip™ DETAIL
S3.1 SCALE: 3/4" = 1'-0" S3.1 SCALE: 3/4" = 1'-0" S3.1 SCALE: 3/4" = 1'-0" S3.1 SCALE: 3/4" = 1'-0"

S
3.1
9/11/2020 11:16:01 AM

FILL ALL CELLS IN LINTEL HEIGHT W/


POURED CONCRETE GROUT
(MONOLITHIC WITH BOND BEAM)

5"

09/11/2020
CMU LINTEL SCHEDULE I
3/16" 4"
T.O.B.
CMU LINTEL FOR 8" BLOCK WALL FILL POCKET W/ PROVIDE HSS STUB CONT. 8" BOND BEAM EL. = 137'-4"
NON-SHRINK GROUT AS REQ'D. FOR REINF. W/ (1) #6 T&B
CLEAR LINTEL LINTEL REINF. TOP BEARING HEIGHT (TYP.)
SPAN LENGTH HEIGHT and BOTT.
THACKER | DAVIS ARCHITECTS
FILLER BLOCK

8"
B.O. DECK I N C O R P O R A T E D

FIELD VERIFY
7'-4" 8'-8" 16" (1) #6 Member American Institute of Architects

3"
KNOCK OUT WEB OF EL. RE: PLAN
LINTEL BLOCK TO .
1100 Judson Rd., Suite 620 PO Box 2723

LINTEL LENGTH ALLOW VERT. REINF. T.O.B. Longview, Texas 75606-2723


.
Phone 903.236.3771 Fax 903.753.7317
TO PASS THRU (TYP.) EL. = 134'-8"
Email: T D A @ T - D A r c h i t e c t s . c o m

SCHED. LINTEL REINF. w w w . T - D A r c h i t e c t s . c o m

2"
HSS5x5x1/4 W/ 3/8" CAP
PL x 5" x7 1/2" - FIELD
BOND BEAM WELD TO EMBED PL 3/8" THICK EMBED PL

4"
NOTE:
1. LINTELS SHALL BE INSTALLED AT HEAD OF ALL DOORS AND WINDOWS OF - AT CONTRACTOR'S 6" PL x
ALL WALLS. OPTION CUT BLOCK TO W/ (2) 1/2"Ø x 5" LONG
VERT. REINF. SHALL BE

2"
2. PROVIDE BOND BREAKER (2 LAYERS OF BLDG. PAPER) AT LINTEL FIT EMBED PL @ BEAM HEADED STUD ANCHORS 2" 4"
CONT. THRU BOND BRNG. ELEVATION
BEAM BEARINGS THAT CROSS MASONRY C.J.'S.
3. FOR OPENINGS NOT SHOWN, USE SIZE & REINFORCING FOR NEXT
LARGER SIZE.
VERT. REINF. PER PLAN 4. CMU BLOCK LINTELS SHALL BE FILLED WITH POURED CONCRETE GROUT STRUCTURAL ENGINEER:
(SEE GENERAL NOTES).
5. STEEL AND BLOCK LINTELS SHALL BEAR A MINIMUM OF 8" ON MASONRY
EACH END.
6. COORDINATE ALL LINTEL ELEVATIONS WITH ARCHITECTURAL DRAWINGS.
CLEAR SPAN
T.O.B.
EL. = 128'-8"

1 TYPICAL CMU LINTEL DETAIL 2 TYPICAL CMU LINTEL SCHEDULE 3 BEAM PERPENDICULAR TO CMU
S3.2 SCALE: 3/4" = 1'-0" S3.2 SCALE: 3/4" = 1'-0" S3.2 SCALE: 3/4" = 1'-0"

Physical: 16291 FM 849


Mail: P.O. BOX 2428
Lindale, Texas 75771
Phone: 903.882.8503 / Fax 903.882.5318
WWW.HOLLANDENGR.COM
Texas Firm #: F-8474
HE #: 20-019

T.O.B.
EL. = 123'-4"

FILL ALL CELLS SOLID W/


POURED CONC. GROUT FIN. FLR.
EL. RE: PLAN
VERT. BAR SPA. PER PLAN VERT. BAR SPA. PER PLAN
T.O.B.
EL. = 118'-0"

FILL JOINT W/ PROVIDE DUR-O-WALL RAPID CONTROL JOINT


COMPRESSIBL (REGULAR SIZE, RUBBER COMPOUND) @ CMU
E SEALANT CONTROL JOINTS
ADD'L. BAR EA. SIDE ADD'L. BAR EA.
VERT. BAR SPA. PER PLAN

OF CORNER SIDE OF CORNER

HORIZONTAL LADDER TYPE


HORIZONTAL LADDER TYPE JOINT REINF. @ 16"o.c.
JOINT REINF. @ 16"o.c.

WALL CORNER WALL END OR JAMB

NOTE: PROVIDE (1) VERTICAL ALL CMU CONTROL JOINTS SHALL HAVE DUR-
REINFORCING TYPICAL FOR REINFORCING BAR EA. O-WALL RAPID CONTROL JOINT INSTALLED
T.O.B.
INTERIOR AND EXTERIOR CMU WALL SIDE OF CONTROL FULL HEIGHT OF JOINT. INSTALL CMU JOINTS
JOINT WHERE SHOWN ON ARCH'L. ELEVATIONS. EL. = 111'-4"

5 TYPICAL 8" CMU WALL REINFORCING DETAIL 6 TYPICAL CMU CONTROL JOINT DETAIL (PLAN VIEW)
S3.2 SCALE: 3/4" = 1'-0" S3.2 SCALE: 3/4" = 1'-0"

H ospi ality
T.O.B.
Health R
EL. = 106'-0"
NOTE:
HOSPITALITY

LAP 2'-8" TYP.


NEW 8" CMU
COORDINATE REQUIRED
ALL VERTICAL REINFORCING EDGE REINFORCING
SHALL BE HELD SECURELY IN
PLACE W/ VERTICAL BAR
(INTERIOR OR EXTERIOR
FACE) W/ DETAILS
FIN. FLR.
EL. RE: PLAN
HEALTH ER
POSITIONERS
HORIZ. TRUSS TYPE
JOINT REINF. @ 16"o.c.
TYLER
#5 VERT. DWLS. EXPANSION
EQ.

TO FDN. @ 16"o.c.
2 1/2" CLEAR

LAP 2'-8" TYP.


COVER

VERT. REINF. PER


PLAN (CENTERED IN Tyler, Texas
WALL U.N.O.)
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

EQ.

EXISTING CMU
FIN. FLR.
EL. RE: PLAN

1'-6" MIN.
FILE NAME:
REINF. @ CENTER REINF. @ EDGE EXISTING FND
20-019-STRUCTURAL

PROJECT NUMBER:
WHERE INDICATED ON PLAN OR SECTIONS, CELLS SHALL BE REINFORCED AND FILLED WITH POURED ACI STD.
CONCRETE GROUT (FULL HEIGHT). REFER TO PLAN OR SECTIONS FOR REINFORCING SIZE AND HOOK 1909
SPACING. REFER TO MASONRY SECTION OF GENERAL NOTES FOR CONCRETE PLACEMENT
PROCEDURE. SHEET CONTENTS:
TYPICAL CMU DETAILS

7 TYPICAL VERT. BAR POSITIONER DETAIL (PLAN VIEW) 4 TYPICAL FULL HT. 8" CMU VERT. REINF.
S3.2 SCALE: 3/4" = 1'-0" S3.2 SCALE: 1/2" = 1'-0"

S
3.2
9/11/2020 11:16:02 AM

09/11/2020
SPAN "L1" SPAN "L2"
L1/4 L1/4 L2/4

MAXIMUM OF 1 STUD PER MAXIMUM OF 1 STUD PER


VALLEY RIB FOR DECK VALLEY RIB FOR DECK
#4 @ 12"o.c. PERPENDICULAR TO BEAM PERPENDICULAR TO BEAM
#4 x 10'-0" AT THACKER | DAVIS ARCHITECTS

SLAB TOTAL
THICKNESS
@ GIRDERS 1'-0"o.c. W.W.F. (SEE NOTES) 3/4" DIA. HEADED FIELD WELD SHEAR STUDS I N C O R P O R A T E D
Member American Institute of Architects
SHEAR STUD (SEE THROUGH DECK TO WF BEAM

CONC.
.

SLAB
FINISH STRUCTURAL PLAN FOR TOTAL IN VALLEY OF DECK (SEE 1100 Judson Rd., Suite 620 PO Box 2723
W.W.F. (SEE NOTES) NUMBER S.C.) STUD SPACING DETAIL) Longview, Texas 75606-2723
SLAB .

3/4" CLEAR
2 1/2" 2 1/2" Phone 903.236.3771 Fax 903.753.7317

1" CLEAR
MESH
FINISH STRUCTURAL

BARS
SLAB Email: T D A @ T - D A r c h i t e c t s . c o m

w w w . T - D A r c h i t e c t s . c o m

COMPOSITE
DECK
COMPOSITE TYPE
STEEL DECK

COMPOSITE TYPE CENTERLINE OF 3/4" DIA.


STEEL DECK HEADED SHEAR STUD IS
(2) #4 CONT. CENTERLINE OF BEAM (SEE
@ COLS. EA. CENTER DECK VALLEY PLAN FOR TOTAL NUMBER WF BEAM
WAY OVER BEAM USE OF S.C.) STRUCTURAL ENGINEER:
SPACER SHEET AS
REQUIRED - SPLIT DECK BEAM PER PLAN
TO FORM A 5" WIDE (MIN.)
CONCRETE HAUNCH AT BEAM
SECTION ELEVATION

1 TYPICAL ADD'L. REINF. AT COLS/GIRDERS 2 TYPICAL COMPOSITE BEAM PARALLEL TO DECK FLUTES 3 TYPCIAL COMPOSITE BEAM PERPENDICULAR TO FLUTES
S4.1 SCALE: 3/4" = 1'-0" S4.1 SCALE: 3/4" = 1'-0" S4.1 SCALE: 3/4" = 1'-0"

Physical: 16291 FM 849


Mail: P.O. BOX 2428
Lindale, Texas 75771
Phone: 903.882.8503 / Fax 903.882.5318
WWW.HOLLANDENGR.COM
Texas Firm #: F-8474
HE #: 20-019

TOTAL # OF SHEAR STUDS SHOWN ON PLAN (SC)

1/2 OF TOTAL # SHEAR STUDS 1/2 OF TOTAL # SHEAR STUDS

SHEAR STUDS COMPOSITE TYPE


DECK

1'-0" MIN. BEAMS PERPENDICULAR


TO DECK SPAN
6" MIN. SEE PLAN
BEAMS OR GIRDERS BEAM SUPPORT MID SPAN OF BEAM
PARALLEL TO DECK SPAN BEGIN SPACING
2'-0" MAX. BEAM SUPPORT
BEAMS PERPENDICULAR 2" FILLET WELDS
BEGIN SPACING
TO DECK SPAN @ 12"o.c.

DEPTH
SLAB
2'-0" MAX. BEAMS OR GIRDERS NOTES:
PARALLEL TO DECK SPAN 1. 1/2 OF TOTAL NUMBER OF SHEAR STUDS MUST BE SPACED EA. SIDE OF MID-SPAN OF BEAM (UNLESS
NOTED OTHERWISE ON PLAN).
2. BEGIN SPACING AT BEAM SUPPORTS AND DISTRIBUTE ALL SHEAR STUDS UNIFORMLY ACROSS BEAM
LENGTH.
3. DETERMINE WHERE ALL SHEAR STUDS ARE TO BE LOCATED BEFORE WELDING TO BEAM (SEE TYPICAL
COMPOSITE BEAM AND COMPOSITE DECK DETAIL).
4. WHERE ADDITIONAL STUDS ARE REQUIRED, INSTALL IN PAIRS STARTING FROM END OF BEAM.
5. DESIGN ALL BEAM REACTIONS FOR 80% OF TABULATED ALLOWABLE LOAD SPECIFIED IN AISC STEEL UP TO 1'-3", USE
CONSTRUCTION MANUAL, 14TH EDITION. 1/4" BENT PL. 5"
x OR 1/4" ANGLE
CENTERLINE OF BEAM FIELD WELD SHEAR STUDS
THROUGH DECK TO WF BEAM
IN VALLEY OF DECK (SEE
STUD SPACING DETAIL)

4 TYPICAL SHEAR STUD LAYOUT - PLAN VIEW 5 TYPICAL SHEAR STUD SPACING DETAIL 6 TYPICAL SLAB EDGE DETAIL - STRUCT'L. STEEL ANGLE/PLATE
S4.1 SCALE: 3/4" = 1'-0" S4.1 SCALE: 3/4" = 1'-0" S4.1 SCALE: 3/4" = 1'-0"

H ospi ality
Health R
HOSPITALITY
HEALTH ER
FLOOR DECK
PER GEN. NOTES TYLER
FIN. FLR.
EXPANSION
EL. RE: PLAN
Tyler, Texas
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

FILE NAME:
20-019-STRUCTURAL
WHERE SHOWN ON PLAN, PROVIDE L2 1/2x2 PROJECT NUMBER:
1/2x1/4 X-BRACE FROM BEAM TO BEAM WHERE
SPECIFIED ON PLAN - INSTALL AFTER FLOOR 1909
DEAD LOAD IS IN PLACE
SHEET CONTENTS:
TYPICAL FLOOR FRAMING
DETAILS
7 SECTION
S4.1 SCALE: 3/4" = 1'-0"

S
4.1
9/11/2020 11:16:04 AM

6 5/8"
600S162-43
@ 16"o.c.
6 5/8" W/ BRIDGING
@ MID-PT.
600S162-43
PER 4/S3.1
@ 16"o.c.
W/ BRIDGING 6 5/8"
ALIGN STUD W/
@ MID-PT. Z-FURRING
600S200-43 1" EXP. JT.
PER 4/S3.1
@ 16"o.c. BOTT. TRACK 1" EXP. JT.
W/ BRIDGING 600T125-43
@ THIRD-PT. PER 5/S3.1 8" CMU WALL W/ 09/11/2020
BOTT. TRACK
PER 4/S3.1 1" Z-FURRING 20GA. @ 16"o.c. W/ VERT. REINF.
600T125-43 8" CMU WALL W/
PER 5/S3.1 (2) #12 TEK SCREWS INTO BOTT. PER 4/S3.2
VERT. REINF. COMPOSITE SLAB
MOMENT CONN. TRACK & (2) X-S16P8TH INTO
PER 4/S3.2 PER GEN. NOTES FIN. FLR.
SLAB EDGE COMPOSITE SLAB ClarkDietrich PER 3/S6.1, TYP. COMPOSITE SLAB STL., TYP. T.O.S. COMPOSITE SLAB T.O. BOND BM.
PER 6/S4.1 PER GEN. NOTES FIN. FLR. Uni-Clip™ UCEC PER GEN. NOTES FIN. FLR. PER GEN. NOTES FIN. FLR. EL. = 118'-0" EL. RE: PLAN

5"
EL. = 123'-10" T.O. BOND BM.
EL. RE: PLAN PER 10/S3.1 EL. RE: PLAN CONT. 1/4" PL. EL. RE: PLAN
EL. = 118'-0"

5"
EL. - 117'-8" @ SIM.
BEAM PER PLAN CONT. DBL. BOND BEAM PER PLAN THACKER | DAVIS ARCHITECTS
1" Z-FURRING 20GA. @ 12"o.c. CONT. DBL. BOND CONT. L6x4x5/16 (LLV) W/ BM. REINF. W/ (1) I N C O R P O R A T E D
Member American Institute of Architects

BEAM PER PLAN TOP TRACK 362T125-43 W/ (2) #12 TEK SCREWS INTO BM. REINF. W/ (1) 1/2"Ø HAS-E RODS @ 16"o.c. - #6 T&B EA.
PER 3/S3.1 (SEGMENT TOP TRACK & (2) X-S16P8TH #6 T&B EA. SET RODS W/ HILTI HIT-HY 270
CONT. L6x4x5/16 (LLV) W/ .
1100 Judson Rd., Suite 620 PO Box 2723

INTO STL. BM., TYP. EXISTING 1/2"Ø HAS-E RODS @ 16"o.c. - Longview, Texas 75606-2723
BTWN. BEAMS) ADHESIVE (EMBED 4 1/2" MIN.) .
1" Z-FURRING 20GA. @ 12"o.c. CONC. WALL SET RODS W/ HILTI HIT-HY 270 Phone 903.236.3771 Fax 903.753.7317
W/ (2) #12 TEK SCREWS INTO TOP SLIP TRACK EXISTING ADHESIVE (EMBED 4 1/2" MIN.)
TOP TRACK & (2) X-S16P8TH 600T200-68 CONC. WALL Email: T D A @ T - D A r c h i t e c t s . c o m
BEAM PER PLAN
INTO STL. BM., TYP. SOFFIT JOIST BEAM PER PLAN PER 6/S3.1 BEAM PER PLAN
w w w . T - D A r c h i t e c t s . c o m

LANDING ELEV.

1 1/2"
362S162-43
TOP SLIP TRACK EL. RE: ELEV. CONN. BM. TO CMU
CL. BM. @ 16"o.c. 1" Z-FURRING 20GA. @ 12"o.c.
600T200-68 PER 3/S3.2
W/ (2) #12 TEK SCREWS INTO
PER 6/S3.1 T.O. BOND BM. CONT. BOND BM.

3"
TOP TRACK & (2) X-S16P8TH
(4) #10 TEK INTO STL. BM., TYP. REINF. W/ (1) #5
B.O. SOFFIT EL. = 110'-0"
600S162-43 SCREWS, TYP. T&B
TOP SLIP TRACK EL. RE: PLAN ClarkDietrich
@ 16"o.c. CONT. PL. 1/2" x 1'-0" T.O. DOOR OPENING
600T200-68 FastClip FCSC8
W/ BRIDGING W/ 1/2"Ø HAS-E RODS
PER 6/S3.1 PER 9/S3.1 EL. = 109'-4"
@ MID-PT. @ 24"o.c.HILTI HIT-HY
PER 4/S3.1 600S162-43 270 ADHESIVE STRUCTURAL ENGINEER:
600S162-43
@ 16"o.c. (EMBED 4 1/2" MIN.)
@ 16"o.c.
W/ BRIDGING
W/ BRIDGING
@ MID-PT. HSS8x6x1/4 BM.
@ MID-PT.
PER 4/S3.1 (LLV)
6 5/8" PER 4/S3.1

1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 SECTION


S4.2 SCALE: 3/4" = 1'-0" S4.2 SCALE: 3/4" = 1'-0" S4.2 SCALE: 3/4" = 1'-0" S4.2 SCALE: 3/4" = 1'-0" S4.2 SCALE: 3/4" = 1'-0"

Physical: 16291 FM 849


Mail: P.O. BOX 2428
12 11 Lindale, Texas 75771
Phone: 903.882.8503 / Fax 903.882.5318
6 5/8" WWW.HOLLANDENGR.COM
600S162-43 Texas Firm #: F-8474
HE #: 20-019
@ 16"o.c.
W/ BRIDGING
12 @ MID-PT.
6 5/8" AA A PER 4/S3.1

2 5/8"
NOTE: 12 11 600S162-43
@ 16"o.c.
MOMENT CONN.
PER 3/S6.1, TYP.
SLAB EDGE
PER 6/S4.1
WALL STUD NOT W/ BRIDGING BOTT. TRACK
6 5/8" WINDOW COMPOSITE SLAB BOTT. TRACK
SHOWN FOR CLARITY @ MID-PT. 600T125-43
COL. PER PLAN PER ARCH'L. PER GEN. NOTES 600T125-43
PER 4/S3.1 PER 5/S3.1 PER 5/S3.1 4'-0" MAX.
ClarkDietrich COMPOSITE SLAB
TOP TRACK
SLAB EDGE COMPOSITE SLAB SLAB EDGE COMPOSITE SLAB EasyClip S545 PER GEN. NOTES
362T125-43
FIN. FLR. PER 6/S4.1 PER GEN. NOTES FIN. FLR. PER 6/S4.1 PER GEN. NOTES SLAB EDGE PER 8/S3.1 FIN. FLR. FIN. FLR.
PER 3/S3.1
EL. RE: PLAN EL. RE: PLAN PER 6/S4.1
EL. RE: PLAN EL. RE: PLAN
5"

5"
5"
ROOF DECK PER
GEN. NOTES TOP TRACK
B.O. DECK 600T125-43
B.O. DECK
2'-4 15/16"

EL. VARIES PER 3/S3.1 - TOP TRACK


EL. VARIES SEGMENT 362T125-43
ROOF DECK PER L3x3x1/4 x 18" LONG W/ (2)
BTWN. BEAMS PER 3/S3.1 1/4 6
GEN. NOTES 1/2"Ø HILTI KWIK HUS-EZ
ANCHORS (EMBED 3") BEAM PER PLAN
JOIST PER PLAN
CONT. L4x4x1/4 BEAM PER PLAN 600S162-43 BEAM PER PLAN BEAM PER PLAN BEAM PER PLAN
BEAM PER PLAN BRACE
STRAP W/ FLANGES DOWN 362S162-43 3/8" THK. STIFF. PL @ EA. BEAM
BEAM L2x2x1/4 BRACE (4) #10 TEK 600S162-43 1" Z-FURRING 20GA. @ 12"o.c.
362S162-43 ATTACH TO STUD @ 16"o.c. (TYP.)
PER PLAN SCREWS, TYP. @ 16"o.c. W/ (2) #12 TEK SCREWS INTO
JOIST PER PLAN HSS6x6x1/4 HANGER COL. TOP TRACK & (2) X-S16P8TH W/ (2) #10 TEK SCREWS
SOFFIT JOIST 1" Z-FURRING 20GA. @ 12"o.c.
INTO STL. BM., TYP. ATTACH TO BEAM W/ (2) HILTI
B.O. SOFFIT 362S162-43 W/ (2) #12 TEK SCREWS INTO
BEAM PER PLAN X-S16P8TH PAF PER STRAP
SHOP WELD ANGLE TO @ 16"o.c. TOP TRACK & (2) X-S16P8TH
TOP TRACK EL. RE: PLAN
HSS HANGER W/ 1/4" INTO STL. BM., TYP.
SOFFIT JOIST 600T125-43
FILLET WELDS DOWN 600S162-43 B.O. SOFFIT
LENGTH OF ANGLE PER 3/S3.1
@ 16"o.c.
(4) #10 TEK TOP SLIP TRACK EL. RE: PLAN
SCREWS, TYP. 600T200-68
WINDOW GLASS MANUF. SHALL PROVIDE PER 6/S3.1
PER ARCH'L. FOR VERT. DEFLECTION @
HEAD OF GLASS
600S162-43
@ 16"o.c.
W/ BRIDGING
@ MID-PT.
PER 4/S3.1
6'-11 3/16" 3/8" 6 5/8"

6 SECTION 7 SECTION 8 SECTION 9 SECTION


S4.2 SCALE: 3/4" = 1'-0" S4.2 SCALE: 3/4" = 1'-0" S4.2 SCALE: 3/4" = 1'-0" S4.2 SCALE: 3/4" = 1'-0"

12 11 9
3 5/16"
6 5/8"
H ospi ality
600S162-43
@ 16"o.c.
W/ BRIDGING
BOTT. TRACK
600T125-43
NOTE:
VERT. REINF. SHALL
CL.
"X" = RE: PLAN Health R
600S162-43 @ MID-PT. PER 5/S3.1 BE CONT. THROUGH
@ 16"o.c. PER 4/S3.1 CONT. L5x5x5/16 W/ 1/2"Ø
1/4 6 BOND BEAMS
COMPOSITE SLAB HSA @ 16"o.c. INTO CMU
BOTT. TRACK
600T125-43
COMPOSITE SLAB
PER GEN. NOTES FIN. FLR. FIN. FLR.
SLAB EDGE
PER 6/S4.1
PER GEN. NOTES
FIN. FLR.
COMPOSITE SLAB
PER GEN. NOTES
HOSPITALITY
GROUT FILL SOLID COURSE
PER 5/S3.1 EL. RE: PLAN EL. RE: PLAN EL. RE: PLAN ABOVE BOND BEAM HEALTH ER
5"

5"

SLAB EDGE
PER 6/S4.1 BEAM PER PLAN
B.O. DECK
EL. VARIES BEAM PER PLAN
T.O. BOND BM.
EL. = 117'-4"
TYLER
BEAM PER PLAN

TOP SLIP TRACK 1" Z-FURRING 20GA. @ 12"o.c.


TOP SLIP TRACK
600T200-68
CONT. L4x4x1/4
CONT. BOND BM. EXPANSION
PER 6/S3.1 5/16x5x"X" BENT PL. W/ 2" REINF. W/ (1) #6 T&B
600T200-68 W/ (2) #12 TEK SCREWS INTO LONG VERT. SLOTTED HOLES
PER 6/S3.1 TOP TRACK & (2) X-S16P8TH 1" Z-FURRING 20GA. @ 12"o.c. KNOCK OUT WEB OF LINTEL Tyler, Texas
INTO STL. BM., TYP. BEAM PER PLAN W/ (2) #12 TEK SCREWS INTO NOTE: 1/2"Ø HILTI-E-ROD @ 16"o.c. W/ BLOCK FOR REINF., TYP.
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

TOP TRACK & (2) X-S16P8TH INSTALL HILTI BOLT HILTI HIT-HY270 (EMBED 4 1/2") -
JOIST PER PLAN BEAM
INTO STL. BM., TYP. AFTER CONCRETE HAND TIGHTEN, BACK OFF 1/2 8" CMU WALL W/
PER PLAN IS PLACED TURN & TACK WELD NUT TO VERT. REINF. PER
TOP SLIP TRACK ROD ONLY PLAN & 4/S3.2
600T200-68
PER 6/S3.1
600S162-43 3/8" THK. STIFF.
BRACE @ 16"o.c. PL @ EA. BEAM FILE NAME:
12 SECTION @ SECOND FLOOR ELEVATOR NORTH WALL 20-019-STRUCTURAL
PROVIDE BLOCKING AS PROJECT NUMBER:
REQ'D FOR CANOPY
S4.2 SCALE: 3/4" = 1'-0"
CONN. COORD. W/ SOFFIT JOIST 1909
CANOPY SUPPLIER AS DTL'D NOTE:
VERT. REINF. SHALL SHEET CONTENTS:
BE CONT. THROUGH
BOND BEAMS SECOND FLOOR FRAMING
"X" = RE: PLAN
DETAILS
SLAB EDGE
600S162-43 BOX HDR. PER 6/S4.1 8" CMU WALL W/
@ 16"o.c. (2) 600S162-43 VERT. COMPOSITE SLAB VERT. REINF. PER
(2) 600T125-43 HORIZ. FIN. FLR. PER GEN. NOTES PLAN & 4/S3.2
W/ EasyClip™ S545 600S162-43
600S162-43 EL. RE: PLAN
T&B EA. END @ 16"o.c.
@ 16"o.c. W/
ATTACH TO CMU WALL AND W/ BRIDGING
BRIDGING
STRL. STEEL COLUMN PER 8/S3.1 @ THIRD-PT. T.O. BOND BM.
@ MID-PT.
PER 4/S3.1
PER 4/S3.1 BEAM PER PLAN EL. = 117'-4"
ClarkDietrich CONT. BOND BM.
EasyClip™ S543 HDR-2 6 5/8" REINF. W/ (1) #6 T&B
PER 8/S3.1 SEE SCHD. NOTE:
PER 1/S3.1 HDR-5 INSTALL HILTI BOLT KNOCK OUT WEB
SEE SCHD. AFTER CONCRETE OF LINTEL BLOCK
B.O. SOFFIT PER 1/S3.1 FOR REINF., TYP.
IS PLACED
EL. = 109'-2" GLASS MANUF. CL.
SOFFIT JOIST CONT. 5/16x5x"X" (LLH) BENT PL. W/ 2" LONG
SHALL PROVIDE FOR
362S162-43 VERT. SLOTTED HOLES FOR 1/2"Ø HILTI-E-ROD
VERT. DEFLECTION
@ 16"o.c. @ 16"o.c. W/ HILTI HIT-HY270 (EMBED 4 1/2") -
@ HEAD OF GLASS
HAND TIGHTEN, BACK OFF 1/2 TURN & TACK
GLASS MANUF. SHALL PROVIDE
FOR VERT. DEFLECTION @
WINDOW
PER ARCH'L.
WINDOW
PER ARCH'L.
WELD NUT TO ROD ONLY, USE SCREEN TUBES
WHERE NECESSARY @ HOLLOW CELLS - ANGLE
S
LENGTH SHALL MATCH CMU WALL LENGTH
HEAD OF GLASS

10 SECTION 11 SECTION 13 SECTION @ SECOND FLOOR ELEVATOR WEST WALL


4.2
S4.2 SCALE: 3/4" = 1'-0" S4.2 SCALE: 3/4" = 1'-0" S4.2 SCALE: 3/4" = 1'-0"
9/11/2020 11:16:05 AM

NOTE:
"A" DIM. IS BASED ON 4" STD.
BEARING LENGTH. ACTUAL HEIGHT
"A1" WILL ADJUST WITH SLOPE AND
ACTUAL BEARING LENGTH. AS DTL'D.
CONT. BENT PL
OR ANGLE AS 4"
ROOF SLOPE DIM "A"
DTL'D. STD.
AS DTL'D.
0.25:12 2 1/ " RIGID X-BRACING - BOLTED OR WELDED
1/8 2 2
CONT. BENT PL 4" @ INTERSECTION PER JOIST SUPPLIER
0.375:12 3 1/ " 1/8 2
2 OR ANGLE AS STD.
ROOF DECK

"A1"
0.5:12 3 1/ " DTL'D.

"A"
EL. RE: PLAN 2 SEE PLAN
JOIST BRNG. 1:12 3 1/ "
2

2 1/2"
JOIST BRNG. 09/11/2020
2 1/2" 1.5:12 4"
TYPE S TOP MIN. EL. RE: PLAN EL. RE: PLAN
2:12 4"
CHORD EXTENSION JOIST BRNG.
2.5:12 4"
2 1/2" HORIZ. BRIDGING
3:12 4 1/ " TYPE S TOP MIN. WELDED TO BEAM &
CONT. BENT PL AS DTL'D. 2
CHORD JOIST BY JOIST MANUF.
OR ANGLE AS 3.5:12 4 1/ "
2 EXTENSION
DTL'D. THACKER | DAVIS ARCHITECTS
4" 4:12 4 1/ "
2 I N C O
Member American
R P O R
Institute of
A T E D
Architects
STD. 4.5:12 5"

2 1/2"
AS DTL'D. STL. BM. .
1100 Judson Rd., Suite 620 PO Box 2723

1/8 2 5:12 5" SEE PLAN WHERE END BAY DIMENSION IS LESS Longview, Texas 75606-2723
.
Phone 903.236.3771 Fax 903.753.7317
5.5:12 5 1/ " CONT. BENT PL 4" THAN DEPTH OF JOIST MOVE X-BRIDGING BACK ONE BAY STL. JOIST
2 1/8 2 SEE PLAN
"A"
EL. RE: PLAN OR ANGLE AS STD. Email: T D A @ T - D A r c h i t e c t s . c o m
6:12 5 1/ " DTL'D. w w w . T - D A r c h i t e c t s . c o m
JOIST BRNG. 2 FACE OF
>6:12 SEE NOTE SUPPPORT
2 1/2"

3"
2 1/2"
TYPE R TOP MIN.
CHORD NOTE:
EXTENSION FOR SLOPES IN EXCESS OF 6:12,
COORDINATE JOIST SEAT DEPTH
DIMENSION "A" W/ STEEL JOIST
MANUFACTURER. 2 1/2"
TYPE R TOP MIN.
CHORD EXTENSION
STRUCTURAL ENGINEER:

1 KCS OR K SERIES JOIST BEARING ON PERIMETER BEAM (HI END) 2 KCS OR K SERIES JOIST BEARING ON PERIMETER BEAM (LO END) 3 TYPICAL CROSS-BRIDGING AT END BAY FOR K & KCS JOISTS
S5.1 SCALE: 3/4" = 1'-0" S5.1 SCALE: 3/4" = 1'-0" S5.1 SCALE: NONE

L3x3
STRIP FLANGE
AND WELD TO
L3x3x5/16 JOIST TOP
EA. SIDE OF OPNG. CHORD Physical: 16291 FM 849
Mail: P.O. BOX 2428
Lindale, Texas 75771
Phone: 903.882.8503 / Fax 903.882.5318
RE: PLAN FOR WWW.HOLLANDENGR.COM

B
JOIST SIZE Texas Firm #: F-8474
3/16 2-12 HE #: 20-019

JOIST BRNG.
EL. RE: PLAN

ROOFTOP UNITS PROVIDE L4x4x5/16 FRAME AT


WHERE SHOWN EA. ROOT TOP MECHANICAL L4x4x5/16
ON PLAN UNIT CURB - VERIFY & UNDER CURB
L3X3x5/16
COORDINATE FRAME SIZES &
LOCATIONS W/ MEP
SECTION "A"
2 1/2" MIN. PROVIDE BOLTED 2 1/2" MIN.
1/2" 1/2"
BEARING SEATS WHERE BEARING
INDICATED

A
ROOF DECK PER ROOF DECK PER
PLANOR GEN. PLANOR GEN.
NOTES NOTES

2 1/2"

2 1/2"
JOIST BRNG.
EL. RE: PLAN
WHEN NEW POINT LOADS ARE LOCATED JOIST BRNG. JOIST BRNG.
BETWEEN TOP CHORD PANEL POINTS,
WHEN NEW POINT LOADS ARE LOCATED EL. RE: PLAN EL. RE: PLAN
FIELD INSTALL L2x2x3/16 STRUT EA. SIDE
BETWEEN BOTT. CHORD PANEL POINTS,
TO NEAREST BOTT. CHORD PANEL POINT L4x4x5/16
FIELD INSTALL L2x2x3/16 STRUT EA. SIDE
TO NEAREST BOTT. CHORD PANEL POINT OPENING DIM. UNDER CURB

3" JOIST SPACING MINUS 6" 3" RE: PLAN FOR


JOIST SIZE

SECTION "B"
NOTES: L3x3x1/4 BRACES L3x3x1/4 BRACES
1. DETAIL SIM. FOR OPENINGS BETWEEN BEAMS. WHERE WHERE
2. APPLIES TO ALL OPNG.'S WITH A DIM GREATER THAN 12" INDICATED ON INDICATED ON
PLAN PLAN

4 TYPICAL JOIST REINF. DETAIL 5 TYPICAL FRAMING AT ROOF OPENING 6 SECTION 7 SECTION
S5.1 SCALE: NONE S5.1 SCALE: 3/4" = 1'-0" S5.1 SCALE: NONE S5.1 SCALE: 3/4" = 1'-0"

EX. TOP CHORD ANGLES

TYP. @ EA. PANEL NEW TOP CHORD REINF.


PT. & MIDSPAN (L2 1/2x2 1/2x3/16) EA. SIDE
STEEL DETAILER NOTE: BETWEEN PANEL 3/16 2
COORDINATE ALL BOLTED PTS.
JOIST CONNECTIONS W/ JOIST NEW WEB REINF. (L1 1/2x1
T.O.S. 1/2x3/16) EA. SIDE WELD TO
SUPPLIER PRIOR TO PROVIDE HOLES EA.
SUBMITTAL OF SHOP SIDE FOR BOLTED EL. RE: PLAN TOP AND BOTT. CHORDS
1/2" ROOF DECK PER
DRAWINGS JOIST SEAT. COORD.
GEN. NOTES

H ospi ality
1/2" THK. CAP PL. BOLT HOLE W/ TOP RAIL AS DTL'D TYP. @ EA. PANEL
JOIST SUPPLIER. NOTE: PT. & MIDSPAN
WALL STUD NOT BETWEEN PANEL NEW BOTT. CHORD REINF.
3/16 2
2 1/2"

SHOWN FOR CLARITY PTS. (L2 1/2x2 1/2x3/16) EA. SIDE

JOIST BRNG.
2 1/2"
Health R
EL. RE: PLAN C6x8.2 CHANNEL
JOIST BRNG.
EL. RE: PLAN
@ 6'-0"o.c. MAX.
11 TYPICAL DETAIL AT K SERIES JOIST REINFORCING
1 1/2"
1 1/2" S5.1 SCALE: 3/4" = 1'-0"
HOSPITALITY
1 1/2"
1 1/2" HEALTH ER
CONT. L4x4x1/4 SPLICE @ PANEL PT. IN JOIST
ROOF DECK PER TYLER
GEN. NOTES
HORIZONTAL BRIDGING AT
LOCATIONS AS SPECIFIED
EXPANSION
STD. SJI HORIZ.
T.O.S.
BY JOIST MANUF. BRIDGING
EL. RE: PLAN Tyler, Texas

4"
L1 1/4x1 1/4x 1/8 X-BRIDGING 1/4"x4x4 STL. PL. @ SPLICE IN
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

BEAM PER PLAN AS REQ'D. BY JOIST MANUF. BEAM ANGLES - WELD TO EA. ANGLE
TYP. PER PLAN
3/16 2
WHERE SHOWN ON PLAN, PROVIDE L2 1/2x2
1/2x1/4 BRACE TO JOIST TOP CHORD PANEL JOIST PER PLAN
POINT @ EA. JOIST - SPLAY OR SKEW AS REQ'D.
& WELD TO JOIST TOP CHORD ONLY - INSTALL FILE NAME:
AFTER ROOF DEAD LOAD IS IN PLACE 20-019-STRUCTURAL

PROJECT NUMBER:
8 JOIST @ COL. W/ BOLTED SEAT 9 JOIST PARALLEL TO BEAM 10 TYPICAL PARAPET STEEL 12 TYPICAL DETAIL AT JOIST REINFORCING SPLICE 1909
S5.1 SCALE: 3/4" = 1'-0" S5.1 SCALE: 3/4" = 1'-0" S5.1 SCALE: 3/4" = 1'-0" S5.1 SCALE: 3/4" = 1'-0"
SHEET CONTENTS:
CONTRACTOR NOTE: TYPICAL ROOF FRAMING
ALL EXISTING FRAMING MEMBERS, BUILDING DIMENSIONS, ELEVATIONS, AND DETAILS
DETAILS SHOWN SHALL BE FIELD VERIFIED BY GENERAL CONTRACTOR PRIOR
TO SHOP DRAWING SUBMITTAL. NO FABRICATION OR CONSTRUCTION SHALL
BE STARTED UNTIL VERIFICATION IS COMPLETE. CONTRACTOR SHALL 11
NEW CONT. TOP CHORD REINF. EA. SIDE NEW WEB REINF. EA. SIDE
PROVIDE WRITTEN DOCUMENTATION OF ANY AND ALL DISCREPENCIES TO S5.1
THE STRUCTURAL ENGINEER OF RECORD FOR REVIEW.

6" 6"

NOTE: NEW CONT. BOTT. CHORD REINF. EA. SIDE INSTALL NEW CHORD REINF. FULL LENGTH
1. FIELD VERIFY EXISTING CONFIGURATION, DIMENSIONS, AND QUANTITIES. WHERE SPLICING IS ABSOLUTELY
2. REMOVE BRIDGING AS REQUIRED FOR NEW REINFORCING INSTALLATION
& REPLACE ALL BRIDGING UPON COMPLETION OF NEW REINFORCING.
3. REFER TO 4/S5.1 FOR ADD'L. WEB REINFORCING WHERE UNIT CURBS
CONTRACTOR NOTE:
REINFORCING SHOWN IS FOR PRICING ONLY.CONTACT HOLLAND
ENGINEERING WHEN JOISTS ARE ACCESSIBLE FOR VERIFICATION OF JOIST
NECESSARY, REFER TO 12/S5.1
S
DO NOT ALIGN WITH TOP CHORD PANEL POINTS. REINFORCING REQUIREMENTS

5.1
13 TYPICAL JOIST REINFORCING ELEVATION
S5.1 SCALE: 3/4" = 1'-0"
9/11/2020 11:16:07 AM

EXISTING
CONC. WALL
NOTE: 13 NOTE:
VERIFY PARAPET REFER TO 10/S5.1
CL.
DIMENSIONS W/ ARCH'L FOR PARAPET STEEL
BM.
TOP TRACK
11 600T125-43 1'-6" 11 3/8" 5 5/8" 1"
1" EXP. JT. PER 3/S3.1 T.O.S.
HSS8x6x1/4 (LLH) EL. = 121'-11 1/2"
T.O. BOND BM. T.O. BOND BM. ClarkDietrich

1'-4"
EL. = 121'-4" EasyClip™ S543 TOP TRACK
EL. = 121'-4"
PER 8/S3.1 1000T125-43
600S162-43 CONT. BOND BM. PER 3/S3.1
CONT. BOND BM. 09/11/2020
REINF. W/ (1) #6 @ 16"o.c. W/ #6 T&B
T&B 362S162-43 (6) #10 TEK SCREWS TYP.

1'-0"
@ 16"o.c. (TYP.)

INFILL BTWN. CHANNELS


CONT. L4x4x1/4 1000S162-43 @ 16"o.c.
SOFFIT JOIST
BOTT. TRACK ROOF DECK PER 362S162-43 ROOF DECK PER
600T125-43 @ 16"o.c. (TYP.) GEN. NOTES THACKER | DAVIS ARCHITECTS
ROOF DECK PER GEN. NOTES I N C O R P O R A T E D
PER 5/S3.1 Member American Institute of Architects

GEN. NOTES
.
1100 Judson Rd., Suite 620 PO Box 2723

T.O. BOND BM. B.O. DECK T.O. BOND BM. JOIST BRNG. BOTT. TRACK Longview, Texas 75606-2723

1000T125-43 .
Phone 903.236.3771 Fax 903.753.7317
EL. = 118'-0" EL. = VARIES EL. = 118'-0" EL. = 117'-11 7/8" B.O. DECK
PER 5/S3.1
Email: T D A @ T - D A r c h i t e c t s . c o m
EL. = VARIES w w w . T - D A r c h i t e c t s . c o m
CONT. DBL. BOND CONT. BENT PL.
BM. REINF. W/ (1) 1/4"x7"x1 1/2"
#6 T&B CONT. DBL.
BOND BM. REINF. JOIST PER PLAN BEAM PER PLAN L3x3x1/4 BRACE
W/ (1) #6 T&B @ 6'-0"o.c. MAX. -
JOIST PER PLAN
EXISTING CONT. C12x20.7 W/ (2) ROWS OF 1/2"Ø WELD TO JOIST
TOP SLIP TRACK
CONC. WALL CONT. L6x4x5/16 (LLV) W/ HAS-E RODS @ 16"o.c. (STAGGER 8") @ TOP CHORD
600T200-68
1/2"Ø HAS-E RODS @ 24"o.c. - - SET ROD W/ HILTI HIT-HY 270 PANEL POINT
PER 6/S3.1
SET RODS W/ HILTI HIT-HY 270 ADHESIVE (EMBED 4 1/2" MIN.)
ADHESIVE (EMBED 4 1/2" MIN.) EXISTING
8" CMU WALL W/ CONC. WALL 1" Z-FURRING 20GA. @ 12"o.c. STRUCTURAL ENGINEER:
W/ (2) #12 TEK SCREWS INTO JOIST PER PLAN
VERT. REINF.
8" CMU WALL W/ TOP TRACK & (2) X-S16P8TH
PER 4/S3.2
VERT. REINF. INTO STL. BM., TYP.
1" EXP. JT. PER 4/S3.2
600S162-43
@ 16"o.c.
W/ BRIDGING
@ MID-PT.
PER 4/S3.1

1 SECTION 2 SECTION 3 SECTION Physical: 16291 FM 849


Mail: P.O. BOX 2428
S5.2 SCALE: 3/4" = 1'-0" S5.2 SCALE: 3/4" = 1'-0" S5.2 SCALE: 3/4" = 1'-0" Lindale, Texas 75771
Phone: 903.882.8503 / Fax 903.882.5318

AA A WWW.HOLLANDENGR.COM
Texas Firm #: F-8474
HE #: 20-019
NOTE: 1 NOTE: G G F
NOTE:
VERIFY PARAPET
A NOTE:
REFER TO 10/S5.1
VERIFY PARAPET
DIMENSIONS W/ ARCH'L
REFER TO 10/S5.1
FOR PARAPET STEEL
NOTE:
VERIFY PARAPET
NOTE:
REFER TO 10/S5.1
NOTE:
VERIFY PARAPET
DIMENSIONS W/ ARCH'L FOR PARAPET STEEL DIMENSIONS W/ ARCH'L FOR PARAPET STEEL DIMENSIONS W/ ARCH'L

1'-6" 1'-2 7/8" 6 5/8" 1'-6" 9" 6 5/8" 1'-6" 1'-6" 9 1/8" 6 5/8"
HSS6x6x1/4 (LLH)
T.O.S. T.O.S. T.O.S. T.O. PARAPET
HSS8x6x1/4 (LLH) EL. = 137'-10 1/4" EL. = 137'-10 1/4" TOP TRACK EL. = 137'-10 1/4" EL. = 137'-10 1/4"
1000T125-43
HSS8x6x1/4 (LLH) ClarkDietrich PER 3/S3.1
ClarkDietrich
1'-5"

1'-5"

1'-5"
1'-5"

(4) #10 TEK TOP TRACK EasyClip™ S543


SCREWS TYP. 1000T125-43 EasyClip™ S543 TOP TRACK INFILL BTWN. CHANNELS
PER 8/S3.1 362S162-43
PER 3/S3.1 PER 8/S3.1 1000T125-43 1000S162-43 @ 16"o.c. @ 16"o.c. (TYP.)
PER 3/S3.1
ClarkDietrich ALIGN STUD W/
Z-FURRING (4) #10 TEK
EasyClip™ S543 (6) #10 TEK 362S162-43 SCREWS TYP.
362S162-43 PER 8/S3.1 @ 16"o.c. (TYP.)
1'-0"

1'-0"

1'-0"
1'-0"

362S162-43 SCREWS TYP. CONT. L4x4x1/4


@ 16"o.c. (TYP.) (4) #10 TEK CONT. L4x4x1/4
INFILL BTWN. CHANNELS @ 16"o.c. (TYP.) ROOF DECK PER
1000S162-43 @ 16"o.c. INFILL BTWN. CHANNELS SCREWS TYP.
1000S162-43 @ 16"o.c. GEN. NOTES ROOF DECK PER
362S162-43 362S162-43 SOFFIT GEN. NOTES
SOFFIT JOISTS SOFFIT JOIST JOISTS @ 16"o.c. (TYP.) JOIST PER PLAN 362S162-43
CONT. L4x4x1/4
@ 16"o.c. (TYP.) 362S162-43 BOTT. TRACK 1000T125-43 SOFFIT JOISTS
@ 16"o.c. (TYP.) PER 5/S3.1 - SEGMENT JOIST BRNG. @ 16"o.c. (TYP.)
ALIGN STUD W/ ROOF DECK PER JOIST BRNG.
Z-FURRING GEN. NOTES ROOF DECK PER BTEN. JOISTS EL. RE: PLAN
BOTT. TRACK EL. RE: PLAN
GEN. NOTES 1" Z-FURRING 20GA. @ 16"o.c. ClarkDietrich
BOTT. TRACK 1000T125-43 JOIST PER PLAN 1000T125-43
PER 5/S3.1 W/ (2) #12 TEK SCREWS INTO FastClip™ FCSC "R1" TYPE JOIST EXT.
PER 5/S3.1 - SEGMENT B.O. DECK
BOTT. TRACK & (2) X-S16P8TH PER 9/S3.1 @ WALL BUMP OUT
BTWN. JOISTS EL. = VARIES
CONT. BENT. PL. INTO STL., TYP.
JOIST BRNG.
1" Z-FURRING 20GA. @ 16"o.c. 1/4"x7"x1 1/2" BEAM PER PLAN
EL. RE: PLAN
W/ (2) #12 TEK SCREWS INTO WALL STUD AS DTL'D
BEAM PER PLAN
BOTT. TRACK & (2) X-S16P8TH TOP SLIP TRACK L3x3x1/4 BRACE @ EA.JOIST SPLAY OR
BEAM PER PLAN 600T200-68
INTO STL., TYP. SKEW AS REQ'D. & WELD TO JOIST @ JOIST PER PLAN
PER 6/S3.1 TOP CHORD ONLY @ PANEL POINT
L3x3x1/4 BRACE @ 6'-0"o.c. MAX. - WELD
BEAM PER PLAN TOP SLIP TRACK TO JOIST @ TOP CHORD PANEL POINT 1" Z-FURRING 20GA. @ 12"o.c.
600T200-68 WALL STUD AS DTL'D
W/ (2) #12 TEK SCREWS INTO
TOP SLIP TRACK PER 6/S3.1 1" Z-FURRING 20GA. @ 12"o.c. TOP TRACK & (2) X-S16P8TH
600T200-68 W/ (2) #12 TEK SCREWS INTO INTO STL. BM., TYP.
PER 6/S3.1 L3x3x1/4 BRACE @ EA.JOIST SPLAY OR WALL STUD AS DTL'D TOP TRACK & (2) X-S16P8TH
SKEW AS REQ'D. & WELD TO JOIST @ INTO STL. BM., TYP.
600S162-43 TOP CHORD ONLY @ PANEL POINT
@ 16"o.c. 1" Z-FURRING 20GA. @ 12"o.c. W/ (2)
#12 TEK SCREWS INTO TOP TRACK

4 SECTION & (2) X-S16P8TH INTO STL. BM., TYP.


5 SECTION 6 SECTION 7 SECTION
S5.2 SCALE: 3/4" = 1'-0" S5.2 SCALE: 3/4" = 1'-0" S5.2 SCALE: 3/4" = 1'-0" S5.2 SCALE: 3/4" = 1'-0"

D.7 D.8 E F
13
NOTE:
VERIFY PARAPET
DIMENSIONS W/ ARCH'L
NOTE:
VERIFY PARAPET
DIMENSIONS W/ ARCH'L CL.
NOTE:
REFER TO 10/S5.1
FOR PARAPET STEEL
H ospi ality
2 5/8" 2'-8 1/2" 1'-6" 11 3/8"
BM.
5 5/8" 1"
HSS8x6x1/4 (LLH)
Health R
T.O. PARAPET T.O.S.
EL. = 121'-11 1/2" TOP TRACK EL. = 121'-11 1/2"
600S162-43 ClarkDietrich 1000T125-43
HOSPITALITY
1'-4"

1'-4"
@ 16"o.c. (TYP.) EasyClip™ S543 PER 3/S3.1
PER 8/S3.1
INFILL BTWN. CHANNELS
1000S162-43 @ 16"o.c. HEALTH ER
(6) #10 TEK
362S162-43 TYLER
1'-0"

1'-0"
600S162-43 ClarkDietrich SCREWS TYP.
@ 16"o.c. (TYP.)
KICKER EasyClip S545
PER 8/S3.1
EXPANSION
362S162-43
362S162-43 MC6x12 SOFFIT JOIST ROOF DECK PER
@ 16"o.c. (TYP.) WELD THRU @ 16"o.c. (TYP.) GEN. NOTES Tyler, Texas
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

DECK TO EA.
BOTT. TRACK
(4) #10 TEK JOIST
3 7/16" 1000T125-43
SCREWS TYP. ROOF DECK PER JOIST PER PLAN
PER 5/S3.1
GEN. NOTES
F ClarkDietrich
CONT. CONT. BENT PL. B.O. DECK
L4x4x1/4 1/4"x7"x1 1/2" EL. = VARIES
FastClip™ FCSC
PER 9/S3.1 BEAM PER PLAN FILE NAME:
TOP TRACK 600T125-43 20-019-STRUCTURAL
JOIST BRNG. PER 3/S3.1
BEAM PER PLAN EL. RE: PLAN
600S162-43 @ 16"o.c. PROJECT NUMBER:
INFILL BTWN. CHANNELS L3x3x1/4 BRACE @ 6'-0"o.c. MAX. - WELD 1909
HSS4x4x1/4 STUB COL BOTT. TRACK 600T125-43 TO JOIST @ TOP CHORD PANEL POINT
PER 11/S6.1 PER 5/S3.1
T.O.S.
1" Z-FURRING 20GA. @ 12"o.c. W/ (2) SHEET CONTENTS:
BEAM OVER COL. JOIST PER PLAN #12 TEK SCREWS INTO TOP TRACK
PER 10/S6.1 JOIST BRNG. TOP TRACK GLASS MANUF. ROOF FRAMING DETAILS
EL. = 115'-8 1/16" SHALL PROVIDE FOR & (2) X-S16P8TH INTO STL. BM., TYP.
600T125-43 TOP SLIP TRACK
CL. EL. = 115'-8 1/16" VERT. DEFLECTION
BEAM PER PLAN PER 3/S3.1 600T200-68 L3x3x1/4 @ EA. CHANNEL - WELD TO
BM. @ HEAD OF GLASS
PER 6/S3.1 JOIST @ TOP CHORD PANEL POINT
ClarkDietrich SHIM JOIST AS REQ'D 600S162-43
WINDOW 2 1/2" C6x8.2 @ 6'-0"o.c.
EasyClip™ S543 FOR FULL BOTT. @ 16"o.c.
SOFFIT JOIST PER ARCH'L.
PER 8/S3.1 CHORD JSTS. BRNG. HSS8x2x1/4 (LLH)
600S162-43 (4) #10 TEK
ON STEEL BEEM TOP TRACK
@ 16"o.c. SCREWS TYP.
600S162-43 362T125-43
BEAM PER PLAN @ 16"o.c. PER 3/S3.1
B.O. SOFFIT W/ BRIDGING
CANOPY & CONN. 5"
@ MID-PT.
PER 4/S3.1 BY OTHERS
CL. BEAM 362S162-43 T.O.S.
@ 16"o.c. HSS8x6x3/16 EL. = 110'-9"
11 1/16"
ClarkDietrich
EasyClip™ S543
PER 8/S3.1

BOTT. TRACK (4) #10 TEK SCREWS TYP.


362T125-43
250S162-43
PER 5/S3.1

WINDOW
PER ARCH'L.
@ 16"o.c. (T&B)
ClarkDietrich
EasyClip™ S543
S
PER 8/S3.1 (T&B)

5.2
8 SECTION 9 SECTION 10 SECTION
S5.2 SCALE: 3/4" = 1'-0" S5.2 SCALE: 3/4" = 1'-0" S5.2 SCALE: 3/4" = 1'-0"
9/11/2020 11:16:10 AM

NOTE: NOTE: NOTE:


VERIFY PARAPET VERIFY PARAPET
12
VERIFY PARAPET
DIMENSIONS W/ ARCH'L E DIMENSIONS W/ ARCH'L 6 DIMENSIONS W/ ARCH'L I
NOTE: NOTE: 1'-6" 1'-1 3/16" 1'-6" 1'-0 7/8"
VERIFY PARAPET REFER TO 10/S5.1 1'-6" 1'-0 7/8"
CL.
DIMENSIONS W/ ARCH'L BM. FOR PARAPET STEEL ClarkDietrich 362S162-43 ClarkDietrich 362S162-43
ClarkDietrich 362S162-43 EasyClip™ S543 @ 16"o.c. EasyClip™ S543 @ 16"o.c.
1'-6" 8 3/16" 5 5/8" 1" EasyClip™ S543 @ 16"o.c. T.O. PARAPET T.O. PARAPET T.O. PARAPET
PER 8/S3.1 PER 8/S3.1
T.O.S. PER 8/S3.1
EL. = 137'-10 1/4" EL. = 137'-10 1/4" EL. = 137'-10 1/4"
HSS8x6x1/4 (LLH) EL. = 137'-10 1/4"
T.O. BOND BM. T.O. BOND BM. T.O. BOND BM.

1'-3 1/4"

1'-3 1/4"
1'-3 1/4"
ClarkDietrich

1'-4 1/2"
TOP TRACK (4) #10 TEK (4) #10 TEK
EasyClip™ S543 1000T125-43 (4) #10 TEK EL. = 137'-4" CONT. 8" BOND BEAM REINF. EL. = 137'-4" EL. = 137'-4"
SCREWS TYP. SCREWS TYP.
PER 8/S3.1 PER 3/S3.1 SCREWS TYP. W/ (1) #6 T&B
INFILL BTWN. CHANNELS CONT. 8" BOND BEAM CONT. 8" BOND BEAM 09/11/2020
1000S162-43 @ 16"o.c. REINF. W/ (1) #6 T&B 8" CMU WALL W/ VERT. REINF. REINF. W/ (1) #6 T&B
362S162-43 362S162-43
362S162-43 PER 4/S3.2

1'-0"

1'-0"
1'-0"

362S162-43 SOFFIT JOISTS SOFFIT JOISTS

1'-0"
(6) #10 TEK SOFFIT JOISTS CONT. L4x4x1/4
@ 16"o.c. (TYP.) @ 16"o.c. (TYP.) @ 16"o.c. (TYP.)
SCREWS TYP. @ 16"o.c. (TYP.) ROOF DECK PER
362S162-43 GEN. NOTES
362S162-43 362S162-43 362S162-43 ROOF DECK PER
CONT. L4x4x1/4 @ 16"o.c. (TYP.) GEN. NOTES @ 16"o.c. (TYP.)
SOFFIT JOISTS ROOF DECK PER @ 16"o.c. (TYP.)
@ 16"o.c. (TYP.) GEN. NOTES ROOF DECK PER ClarkDietrich THACKER | DAVIS ARCHITECTS
ClarkDietrich ClarkDietrich I N C O R P O R A T E D
B.O. DECK GEN. NOTES B.O. DECK EasyClip™ S543
BOTT. TRACK EasyClip™ S543 EasyClip™ S543
Member American Institute of Architects

PER 8/S3.1
1000T125-43
EL. = VARIES PER 8/S3.1 PER 8/S3.1 EL. = VARIES .
1100 Judson Rd., Suite 620 PO Box 2723
JOIST PER PLAN Longview, Texas 75606-2723
PER 5/S3.1 T.O. BOND BM. T.O. BOND BM. T.O.S. .
Phone 903.236.3771 Fax 903.753.7317

CONT. BENT PL. JOIST PER PLAN EL. = 134'-8 15/16"


L3x3x1/4 BRACE @ 6'-0"o.c. MAX. - WELD EL. = 134'-8" EL. = 134'-8" CONT. L6x4x1/4 (LLV) W/ 1/2"Ø Email: T D A @ T - D A r c h i t e c t s . c o m
1/4"x7"x1 1/2" TO JOIST @ TOP CHORD PANEL PT. HAS-E RODS @ 24"o.c. - SET T.O. BOND BM. JOIST PER PLAN w w w . T - D A r c h i t e c t s . c o m
BEAM PER PLAN T.O.S. CONT. C12x20.7 W/ (2) ROWS OF 1/2"Ø ROD W/ HILTI HIT-HY 270
TOP SLIP TRACK HAS-E RODS @ 16"o.c. (STAGGER 8") 1" EXP. JT. EL. = 134'-8"
ADHESIVE (EMBED 4 1/2" MIN.)
600T200-68 EL. = 134'-2 11/16" - SET ROD W/ HILTI HIT-HY 270
PER 6/S3.1 1" Z-FURRING 20GA. @ 12"o.c. ADHESIVE (EMBED 4 1/2" MIN.)
8" DOUBLE BOND BEAM EX. CONC. WALL 8" DOUBLE BOND BEAM 8" DOUBLE BOND BEAM CONT. C12x20.7 W/ (2) ROWS OF 1/2"Ø
W/ (2) #12 TEK SCREWS INTO REINF. W/ (1) #6 T&B
WALL STUD AS DTL'D REINF. W/ (1) #6 T&B REINF. W/ (1) #6 T&B HAS-E RODS @ 16"o.c. (STAGGER 8")
TOP TRACK & (2) X-S16P8TH 8" CMU WALL W/ VERT. REINF.
PER 4/S3.2 - SET ROD W/ HILTI HIT-HY 270
INTO STL. BM., TYP. 8" CMU WALL W/ VERT. ADHESIVE (EMBED 4 1/2" MIN.)
REINF. PER 4/S3.2

1 SECTION 2 SECTION 3 SECTION STRUCTURAL ENGINEER:


S5.3 SCALE: 3/4" = 1'-0" S5.3 SCALE: 3/4" = 1'-0" S5.3 SCALE: 3/4" = 1'-0"
4 SECTION
S5.3 SCALE: 3/4" = 1'-0"

NOTE:
AA A
NOTE:
VERIFY PARAPET E NOTE:
REFER TO 10/S5.1
VERIFY PARAPET
DIMENSIONS W/ ARCH'L FOR PARAPET STEEL
DIMENSIONS W/ ARCH'L
3 5/16" ClarkDietrich
1'-6" 9" 6 5/8" 1'-6" 9 1/2" EasyClip™ S543
T.O. PARAPET PER 8/S3.1 T.O.S.
EL. = 137'-10 1/4" EL. = 137'-10 1/4"
HSS6x6x1/4 Physical: 16291 FM 849
Mail: P.O. BOX 2428

1'-4 1/2"
Lindale, Texas 75771

1'-5"
TOP TRACK Phone: 903.882.8503 / Fax 903.882.5318
600T125-43 WWW.HOLLANDENGR.COM
PER 3/S3.1 Texas Firm #: F-8474
HE #: 20-019
INFILL BTWN. CHANNELS
362S162-43 362S162-43
600S162-43 @ 16"o.c.

1'-0"
1'-0"
@ 16"o.c. (TYP.) (4) #10 TEK @ 16"o.c. (TYP.)
SCREWS TYP.
CONT. L4x4x1/4
EQ. EQ. EQ. EQ.
(4) #10 TEK
ROOF DECK PER
B SCREWS TYP.
2"

2"
3/8" THK. EMBED PL. x 3/8" THK. EMBED PL. x 3 5/16" GEN. NOTES
@ EA. JOIST W/ (2) @ EA. JOIST W/ (2) 362S162-43 CONT. L4x4x1/4 362S162-43
6"

6"
1/2"Øx5" LONG ROOF DECK PER 1/2"Øx5" LONG SOFFIT JOISTS SOFFIT JOISTS
@ 16"o.c. (TYP.) T.O.S.
2"

2"
2 1/2" BRNG. HEADED STUD GEN. NOTES 2 1/2" BRNG. HEADED STUD ROOF DECK PER @ 16"o.c. (TYP.)
MIN. ANCHORS 7 5/8" MIN. ANCHORS 7 5/8" GEN. NOTES EL. = 134'-2 3/4"
BOTT. TRACK
T.O. BOND BM. 600T125-43
EL. = 133'-7" T.O. BOND BM. ClarkDietrich PER 5/S3.1 BEAM PER PLAN
FastClip™ FCSC JOIST BRNG.
EL. = 133'-3 7/8" 1" Z-FURRING 20GA. @ 16"o.c.
PER 9/S3.1 EL. RE: PLAN W/ (2) #12 TEK SCREWS INTO
CONT. 8" BOND BEAM BOTT. TRACK & (2) X-S16P8TH 1" Z-FURRING 20GA. @ 12"o.c.
REINF. W/ (1) #6 T&B INTO STL., TYP. W/ (2) #12 TEK SCREWS INTO
CONT. 8" BOND BEAM
600S200-43 "R1" TYPE JOIST EXT. TOP TRACK & (2) X-S16P8TH
REINF. W/ (1) #6 T&B
CUT CMU BLOCK @ 16"o.c. @ WALL BUMP OUT TOP TRACK INTO STL. BM., TYP.
AS NEEDED COORD. W/ ELEVATOR SUPPLIER JOIST PER PLAN 600T125-43
PER 3/S3.1
CUT CMU BLOCK ALIGN STUD W/
8" CMU WALL W/ VERT.
AS NEEDED Z-FURRING BEAM PER PLAN JOIST PER PLAN
REINF. PER 4/S3.2

B.O.S. 8" CMU WALL W/ VERT.


BOTT. TRACK 600S162-43
REINF. PER 4/S3.2 1" Z-FURRING 20GA. @ 16"o.c.
NOTE: CL. EL. = 130'-9" 600T125-43 @ 16"o.c.
PER 5/S3.1 W/ (2) #12 TEK SCREWS INTO
VERIFY HOIST BEAM LOCATION BOTT. TRACK & (2) X-S16P8TH
& ELEVATION W/ APPROVED HOIST BEAM INTO STL., TYP.
ELEVATOR SHOP DRAWINGS PER PLAN CONT. 1/4" PL.
T.O.S.
EL. = 128'-3 1/8" BOTT. TRACK 1" Z-FURRING 20GA. @ 16"o.c.
GLASS MANUF. 600T125-43 W/ (2) #12 TEK SCREWS INTO
SHALL PROVIDE FOR PER 5/S3.1 BOTT. TRACK & (2) X-S16P8TH
HSS7x5x1/4 (LLV)
VERT. DEFLECTION INTO STL., TYP.
@ HEAD OF GLASS
5/8"
WINDOW CL. HSS8x6x1/4 (LLV)
PER ARCH'L. BM.
GLASS MANUF. T.O. WINDOW
SHALL PROVIDE FOR
VERT. DEFLECTION EL. = 127'-8 1/8"
@ HEAD OF GLASS WINDOW
PER ARCH'L.

5 SECTION 6 SECTION 7 SECTION


S5.3 SCALE: 3/4" = 1'-0" S5.3 SCALE: 3/4" = 1'-0" S5.3 SCALE: 3/4" = 1'-0"

NOTE:
H ospi ality
NOTE:
VERIFY PARAPET 11 HSS6x6x1/4
NOTE:
REFER TO 10/S5.1
FOR PARAPET STEEL
NOTE:
VERIFY PARAPET
A NOTE:
REFER TO 10/S5.1
NOTE:
VERIFY PARAPET A NOTE:
VERIFY PARAPET 10
REFER TO 10/S5.1
FOR PARAPET STEEL
NOTE:
VERIFY PARAPET C NOTE:
REFER TO 10/S5.1
Health R
DIMENSIONS W/ ARCH'L DIMENSIONS W/ ARCH'L FOR PARAPET STEEL DIMENSIONS W/ ARCH'L DIMENSIONS W/ ARCH'L HSS6x6x1/4 DIMENSIONS W/ ARCH'L FOR PARAPET STEEL
TOP TRACK HSS12x6x1/4 (LLH)
1'-6" 9" 6 5/8" 1000T125-43 HSS6x6x1/4 TOP TRACK 1'-6" 1'-0 1/4" 6 5/8" HSS8x6x1/4 (LLH)
1'-6" 5 3/4" 6 5/8" 1'-6" 1'-0 3/8" 1'-0 3/8" 1'-6" 1'-6" 9" 6 5/8"
PER 3/S3.1 1000T125-43

1000S162-43
T.O. PARAPET
EL. = 147'-11"
TOP TRACK
1000T125-43
T.O. PARAPET
EL. = 147'-11"
T.O. PARAPET
EL. = 147'-11"
PER 3/S3.1
1000S162-43
T.O. PARAPET
EL. = 147'-11"
TOP TRACK
1000T125-43
T.O. PARAPET
EL. = 147'-11"
HOSPITALITY
PER 3/S3.1 PER 3/S3.1
ClarkDietrich @ 16"o.c. ClarkDietrich
(4) #10 TEK
TOP TRACK ClarkDietrich @ 16"o.c. ClarkDietrich
1000S162-43 ROOF DECK HEALTH ER

1'-4"
1'-4"

1'-4"

1'-4"

1'-4"
EasyClip™ S543 BOTT. TRACK EasyClip™ S543 1000S162-43 600T125-43 EasyClip™ S543 BOTT. TRACK EasyClip™ S543
@ 16"o.c. SCREWS TYP. PER 8/S3.1 @ 16"o.c. PER GEN. NOTES
PER 8/S3.1 1000T125-43
PER 5/S3.1
PER 8/S3.1
CONT. L4x4x1/4 JOIST
PER 3/S3.1 1000T125-43
PER 5/S3.1
PER 8/S3.1
CONT. L4x4x1/4 TYLER
ROOF DECK PER ROOF DECK PER JOIST BRNG.
(4) #10 TEK GEN. NOTES ROOF DECK PER PER PLAN (4) #10 TEK GEN. NOTES (4) #10 TEK EXPANSION

11 3/16"
362S162-43 362S162-43 EL. RE: PLAN
11 1/2"

SCREWS TYP. B.O. DECK GEN. NOTES 600S162-43 SCREWS TYP. B.O. DECK SCREWS TYP.
1'-0"

1'-0"

1'-0"
SOFFIT JOISTS SOFFIT JOISTS @ 16"o.c.
362S162-43 EL. = VARIES 362S162-43 EL. = VARIES 362S162-43
@ 16"o.c. (TYP.) @ 16"o.c. (TYP.)
@ 16"o.c. (TYP.) JOIST BRNG. T.O.S. @ 16"o.c. (TYP.) @ 16"o.c. (TYP.) Tyler, Texas
362S162-43 EL. = 145'-7"
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

CONT. BENT PL. EL. RE: PLAN CONT. BENT PL. L3x3x1/4 BRACE @ 6'-0"o.c. BOTT. TRACK BEAM
L3x3x1/4 BRACE @ 6'-0"o.c. MAX. - WELD @ 16"o.c. (TYP.) 362S162-43 ClarkDietrich L3x3x1/4 BRACE @ EA. JOIST SPLAY OR
1/4"x7"x1 1/2" 1/4"x7"x1 1/2" MAX. - WELD TO JOIST @ 1000T125-43 PER PLAN
TO JOIST @ TOP CHORD PANEL PT. @ 16"o.c. (TYP.) EasyClip™ S543 SKEW AS REQ'D & WELD TO JOIST TOP
(4) #10 TEK BEAM PER PLAN TOP CHORD PANEL PT. PER 5/S3.1 -
362S162-43 BEAM PER PLAN PER 8/S3.1 362S162-43 ClarkDietrich CHORD ONLY @ PANEL POINT
SCREWS TYP. SEGMENT BTWN.
SOFFIT JOISTS SOFFIT JOISTS
BOTT. TRACK 6 5/8" 6 5/8" 1" Z-FURRING 20GA. @ 12"o.c. JOISTS EasyClip™ S543
@ 16"o.c. (TYP.) 1" Z-FURRING 20GA. @ 12"o.c. BOTT. TRACK HSS12x6x1/4 (LLH) @ 16"o.c. (TYP.)
L3x3x1/4 BRACE @ EA. JOIST SPLAY OR 600T125-43 W/ (2) #12 TEK SCREWS INTO PER 8/S3.1
W/ (2) #12 TEK SCREWS INTO 1000T125-43 1" Z-FURRING
ClarkDietrich SKEW AS REQ'D & WELD TO JOIST TOP PER 5/S3.1 ClarkDietrich TOP TRACK & (2) X-S16P8TH FILE NAME:
TOP TRACK & (2) X-S16P8TH PER 5/S3.1 - TOP SLIP TRACK 20GA. @ 16"o.c. 1" Z-FURRING 20GA. @ 12"o.c. W/ (2)
EasyClip™ S543 BEAM CHORD ONLY @ PANEL POINT EasyClip™ S543 INTO STL. BM., TYP.
INTO STL. BM., TYP. SEGMENT BTWN. 600T200-68 W/ (2) #12 TEK #12 TEK SCREWS INTO TOP TRACK &
PER 8/S3.1 JOISTS PER PLAN PER 8/S3.1
(2) X-S16P8TH INTO STL. BM., TYP.
20-019-STRUCTURAL
TOP SLIP TRACK PER 6/S3.1 TOP TRACK SCREWS INTO
600T200-68 1" Z-FURRING 20GA. @ 12"o.c. 600T200-68 BOTT. TRACK & TOP SLIP TRACK
PER 6/S3.1
1" Z-FURRING 600S162-43 PER 6/S3.1 (2) X-S16P8TH
PROJECT NUMBER:
20GA. @ 16"o.c. W/ (2) #12 TEK SCREWS INTO @ 16"o.c. 600T200-68
W/ (2) #12 TEK TOP TRACK & (2) X-S16P8TH W/ BRIDGING 600S162-43 INTO STL., TYP. PER 6/S3.1 1909
SCREWS INTO INTO STL. BM., TYP. @ MID-PT. @ 16"o.c. 362S162-43 600S162-43
600S162-43
BOTT. TRACK & PER 4/S3.1 W/ BRIDGING SOFFIT JOISTS @ 16"o.c. SHEET CONTENTS:
@ 16"o.c. TOP SLIP TRACK
(2) X-S16P8TH @ MID-PT. @ 16"o.c. (TYP.) W/ BRIDGING
W/ BRIDGING 600T200-68 ROOF FRAMING DETAILS
INTO STL., TYP. CONT. HSS6x4x1/4 (LLH) PER 4/S3.1 @ MID-PT.
@ MID-PT. PER 6/S3.1
PER 4/S3.1 CONT. L4x4x1/4 PER 4/S3.1
BOTT. TRACK
600T125-43 CONT. MC6x12 BOTT. TRACK
ROOF DECK PER WELD THRU DECK 600T125-43
BOTT. TRACK 1" Z-FURRING 20GA. @ 16"o.c. PER 5/S3.1 CONT. C6x8.2 WELD TO BOTT. TRACK
600S162-43 1" Z-FURRING 20GA. @ 16"o.c. GEN. NOTES TO BEAM/DECK PER 5/S3.1
600T125-43 W/ (2) #12 TEK SCREWS INTO CHANNEL 600T125-43
@ 16"o.c. W/ (2) #12 TEK SCREWS INTO 4"
PER 5/3.1 BOTT. TRACK & (2) X-S16P8TH PER 5/S3.1
W/ BRIDGING BOTT. TRACK & (2) X-S16P8TH 1" Z-FURRING ROOF DECK PER CONT. L4x4x1/4
INTO STL., TYP. T.O.S. ROOF DECK PER
@ MID-PT. INTO STL., TYP. 20GA. @ 16"o.c. JOIST BRNG. GEN. NOTES
EL. RE: PLAN T.O.S. W/ (2) #12 TEK GEN. NOTES CONT. L4x4x1/4
PER 4/S3.1 EL. RE: PLAN
EL. = 133'-2" SCREWS INTO T.O.S.
1" Z-FURRING 20GA. @ 12"o.c. BOTT. TRACK & B.O. DECK JOIST EL. = 133'-9 11/16"
CONT. 1/4" PL. BOTT. TRACK
W/ (2) #12 TEK SCREWS INTO (2) X-S16P8TH PER PLAN
600T125-43 EL. RE: PLAN
TOP TRACK & (2) X-S16P8TH INTO STL., TYP.
PER 5/S3.1
INTO STL. BM., TYP. BEAM PER PLAN BEAM PER PLAN
TOP SLIP TRACK CONT. MC6x12 WELD THRU BEAM PER PLAN
BEAM PER PLAN TOP SLIP TRACK CONT. 1/4" PL. L3x3x1/4 BRACE @ EA. JOIST SPLAY OR DECK TO BEAM/DECK
1" Z-FURRING 20GA. @ 12"o.c. 600T200-68 SKEW AS REQ'D & WELD TO JOIST TOP
600T200-68 3"
W/ (2) #12 TEK SCREWS INTO PER 6/S3.1 CHORD ONLY @ PANEL POINT
PER 6/S3.1 TOP SLIP TRACK JOIST PER PLAN
TOP TRACK & (2) X-S16P8TH
WALL STUD AS DTL'D 600T200-68 INTO STL. BM., TYP. BEAM PER PLAN 3"
PER 6/S3.1
WALL STUD AS DTL'D
1" Z-FURRING 20GA. @ 12"o.c.
W/ (2) #12 TEK SCREWS INTO
TOP TRACK & (2) X-S16P8TH
INTO STL. BM., TYP.
S
8 SECTION 9 SECTION 10 SECTION 11 SECTION 12 SECTION 5.3
S5.3 SCALE: 3/4" = 1'-0" S5.3 SCALE: 3/4" = 1'-0" S5.3 SCALE: 3/4" = 1'-0" S5.3 SCALE: 3/4" = 1'-0" S5.3 SCALE: 3/4" = 1'-0"
9/11/2020 11:16:11 AM

NOTE: ClarkDietrich NOTE:


NOTE:
VERIFY PARAPET
3.5 4.7 NOTE:
VERIFY PARAPET VERIFY PARAPET D.7 EasyClip™ E543 C.5 VERIFY PARAPET
DIMENSIONS W/ ARCH'L PER 8/S3.1 DIMENSIONS W/ ARCH'L
DIMENSIONS W/ ARCH'L DIMENSIONS W/ ARCH'L
1'-4" 9" 9" 1'-4" 1'-4" 9" 9" 1'-4"

T.O. PARAPET T.O. PARAPET


09/11/2020
600S162-43 EL. = 144'-1 1/16" 600S162-43 600S162-43 EL. = 144'-1 1/16" 600S162-43
@ 16"o.c. @ 16"o.c. @ 16"o.c. @ 16"o.c.

1'-4 1/8"

1'-4 1/8"
1'-4 1/8"

1'-4 1/8"
(4) #10 TEK (4) #10 TEK (4) #10 TEK (4) #10 TEK
SCREWS TYP. 600S162-43 ClarkDietrich 600S162-43 SCREWS TYP. SCREWS TYP. 600S162-43 ClarkDietrich 600S162-43 SCREWS TYP.
BRACE @ EasyClip™ E545 BRACE @ BRACE @ EasyClip™ E545 BRACE @
EA. STUD PER 8/S3.1 EA. STUD EA. STUD PER 8/S3.1 EA. STUD

362S162-43 362S162-43 362S162-43


362S162-43 SOFFIT JOISTS THACKER | DAVIS ARCHITECTS
ROOF DECK PER SOFFIT JOISTS SOFFIT JOISTS I N C O R P O R A T E D
SOFFIT JOISTS @ 16"o.c. (TYP.) ROOF DECK PER
@ 16"o.c. (TYP.) @ 16"o.c. (TYP.) Member American Institute of Architects

1'-6"
1'-6"

1'-6"

1'-6"
@ 16"o.c. (TYP.) GEN. NOTES GEN. NOTES
600S162-43 600S162-43 .
1100 Judson Rd., Suite 620 PO Box 2723

362S162-43 B.O. DECK 362S162-43 @ 16"o.c. (TYP.) @ 16"o.c. (TYP.)


Longview, Texas 75606-2723

@ 16"o.c. (TYP.) .
Phone 903.236.3771 Fax 903.753.7317
@ 16"o.c. (TYP.) EL. = VARIES 362S162-43 362S162-43
CONT. L4x4x1/4 @ 16"o.c. (TYP.)
CONT. L4x4x1/4 CONT. L4x4x1/4 ClarkDietrich @ 16"o.c. (TYP.) Email: T D A @ T - D A r c h i t e c t s . c o m

ClarkDietrich w w w . T - D A r c h i t e c t s . c o m
EasyClip™ S545 CONT. L4x4x1/4
EasyClip™ S545 ClarkDietrich ROOF JOIST
PER 8/S3.1 BEAM PER PLAN PER 8/S3.1
T.O. WINDOW EasyClip™ S543 PER PLAN T.O. WINDOW
JOIST BLOCKING TOP TRACK
TOP TRACK @ 16"o.c. PER 8/S3.1
RE: ARCH'L. 600T200-43 RE: ARCH'L.
600T200-43 TOP TRACK ClarkDietrich ROOF JOIST
PER 3/S3.1
PER 3/S3.1 600T200-43 EasyClip™ S545 PER PLAN
ClarkDietrich BEAM PER PLAN ROOF JOIST ClarkDietrich PER 3/S3.1 PER 8/S3.1
Uni-Clip™ UCEC PER PLAN Uni-Clip™ UCEC
600S162-43 ClarkDietrich
ClarkDietrich
EasyClip™ S545
AA A
PER 10/S3.1 PER 10/S3.1
@ 16"o.c. Uni-Clip™ UCEC PER 8/S3.1
600S162-43 WINDOW 600S162-43
BOTT. TRACK
PER 10/S3.1 G F
@ 16"o.c. PER ARCH'L. @ 16"o.c. BEAM PER STRUCTURAL ENGINEER:
600T125-43 BEAM PER
PLAN PLAN
BOTT. TRACK BOTT. TRACK PER 5/S3.1 CL. HSS8x6x1/4
600T125-43 600T125-43
AS DTL'D
PER 5/S3.1 PER 5/S3.1 GLASS MANUF. GLASS MANUF. T.O. PARAPET
SHALL PROVIDE FOR SHALL PROVIDE FOR
GLASS MANUF. GLASS MANUF. VERT. DEFLECTION EL. = 137'-10 1/4"
SHALL PROVIDE FOR SHALL PROVIDE FOR VERT. DEFLECTION
@ HEAD OF GLASS @ HEAD OF GLASS
VERT. DEFLECTION VERT. DEFLECTION
@ HEAD OF GLASS @ HEAD OF GLASS
TOP TRACK 600T125-43 WINDOW WINDOW TOP TRACK 600T125-43 PER
PER 3/S3.1 PER ARCH'L. PER ARCH'L. 3/S3.1 TOP OF COL.
TOP TRACK TOP TRACK
TO BM. CONN.
ROOF DECK PER 600T200-43 600T200-43 ROOF DECK PER 600S162-43 @16"o.c. B.O. WINDOW 600S162-43 @16"o.c. PER 10 / S6.1
GEN. NOTES PER 3/S3.1 B.O. WINDOW PER 3/S3.1 GEN. NOTES Physical: 16291 FM 849
RE: ARCH'L. STUB COL. Mail: P.O. BOX 2428
ClarkDietrich 600S162-43 RE: ARCH'L. 600S162-43 ClarkDietrich BOTT. TRACK 600T125-43 BOTT. TRACK 600T125-43
PER PLAN Lindale, Texas 75771
PER 5/S3.1 ClarkDietrich PER 5/S3.1 C6x8.2 AS DTL'D
Uni-Clip™ UCEC @ 16"o.c. @ 16"o.c. Uni-Clip™ UCEC Phone: 903.882.8503 / Fax 903.882.5318
PER 10/S3.1 PER 10/S3.1 Uni-Clip™ UCEC ClarkDietrich WWW.HOLLANDENGR.COM
BOTT. TRACK BOTT. TRACK CONT. MC6x12 WELD THRU PER 10/S3.1 CONT. MC6x12 WELD THRU Texas Firm #: F-8474
Uni-Clip™ UCEC
600T125-43 600T125-43 CONT. MC6x12 WELD TO DECK TO BEAM/DECK DECK TO BEAM/DECK HE #: 20-019
CONT. MC6x12 WELD TO PER 10/S3.1
PER 5/S3.1 PER 5/S3.1 C-CHANNEL
C-CHANNEL CONT. L4x4x1/4
CONT. L4x4x1/4
T.O.S.
T.O.S. STUB COL. BASE
CONT. BENT PL. EL. = 134'-2 3/4" CONT. BENT PL. CONT. C6x8.2 WELD THRU TO BM. CONN.
EL. = 134'-1 1/4" T.O.S. PER 11 / S6.1
1/4"x4"x1 1/2" (LLH) 1/4"x4"x1 1/2" (LLH) DECK TO BEAM/JOIST
CONT. C6x8.2 WELD THRU EL. = 133'-9 11/16"
DECK TO BEAM/JOIST JOIST BEAM PER PLAN
JOIST PER PLAN JOIST BRNG.
PER PLAN
EXTEND JOIST TO JOIST EL. RE: PLAN
BEAM PER PLAN
BEAM PER PLAN CATCH WALL STUD PER PLAN

BEAM PER PLAN

BEAM 1/2" THK. WEB


PER PLAN STIFF. PL. EA. SIDE
ALIGNED W/ COL.
FLANGES BELOW

COL. PER PLAN TOP OF COL.


TO BM. CONN.
6 1/2" PER 10 / S6.1
3'-4 5/8"
3'-0 5/8" @ SIM
COORD CANTILEVER
DIMENSIONS W/ ARCH'L
CL.

1 SECTION 2 SECTION 3 SECTION


S5.4 SCALE: 3/4" = 1'-0" S5.4 SCALE: 3/4" = 1'-0" S5.4 SCALE: 3/4" = 1'-0"

4 3

H ospi ality
CFMF WALL
Health R
CMU WALL

8" HOSPITALITY
HEALTH ER
TYLER
EXPANSION
3" 3" HSS BEAM PER 7/S5.3
1/2" THK. PL. W/ Tyler, Texas
2"

(2) 3/4"Øx4" LONG


WINDOW BY
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

HEADED STUD
OTHERS
6"

ANCHORS
x
2"

FILE NAME:
20-019-STRUCTURAL

PROJECT NUMBER:
1909

SHEET CONTENTS:
4 SECTION ROOF FRAMING DETAILS
S5.4 SCALE: 3/4" = 1'-0"

S
5.4
9/11/2020 11:16:12 AM

BEAM CONNECTION 09/11/2020


SCHEDULE
BEAM SIZE ANGLE LENGTH NO. OF BOLTS
(L) (EA. LEG)
THACKER | DAVIS ARCHITECTS
I N C O R P O R A T E D
W8/W10 6" (2) 3/4" Ø Member American Institute of Architects
1/4" THICK
CAP PL. .
1100 Judson Rd., Suite 620 PO Box 2723

W12/W14 9" (3) 3/4" Ø AISC STD. THRU PL. U.N.O. Longview, Texas 75606-2723

W BEAM TO HSS COLUMN .


Phone 903.236.3771 Fax 903.753.7317
SHEAR CONNECTION
W16/W18 1'-0" (4) 3/4" Ø U.N.O.
3/16 CONNECTION Email: T D A @ T - D A r c h i t e c t s . c o m

w w w . T - D A r c h i t e c t s . c o m

COPE AS REQ'D. @ BEAM TO


W21 1'-3" (5) 3/4" Ø
BEAM BEAM
PLATE SCHEDULE
BEAM CONNECTION (6" MAX.)
W24 1'-6" (6) 3/4" Ø BEAM PLATE
N0. OF BOLTS
DEPTH SIZE

W27 1'-9" (7) 3/4" Ø W8/W10 3/8"x4"x0'-6" (2) 3/4"Ø


SEE PLAN FOR BEAM SIZE W12/W14 3/8"x4"x0'-9" (3) 3/4"Ø
W30 2'-0" (8) 3/4" Ø STRAP PL 5/16"x4"x10"
W16/W18 3/8"x4"x1'-0" (4) 3/4"Ø
1/4" END PL. EA. END
W33 2'-3" (9) 3/4" Ø W21 3/8"x4"x1'-3" (5) 3/4"Ø
STRUCTURAL ENGINEER:

COL.
ROOF AND FLOOR W24 3/8"x4"x1'-6" (6) 3/4"Ø
W36 2'-6" (10) 3/4" Ø FRAMING NOT SHOWN 1/4 HSS BEAM PER
FOR CLARITY W27 3/8"x4"x1'-9" (7) 3/4"Ø 1/4" CAP PL 1/4 PLAN
STRAP PL 5/16"x4"x10" 1/4
NOTES: W30 3/8"x4"x2'-0" (8) 3/4"Ø TYP. T&B
A. RIGHT ANGLE CONNECTIONS SHALL BE DOUBLE ANGLE AS W33 3/8"x4"x2'-3" (9) 3/4"Ø ASIC STD.
SCHEDULED. SKEWED CONNECTIONS SHALL BE DOUBLE ANGLES OR AISC STD.
SHEAR SHEAR CONN.
BENT PLATES PER ??/S?.? W36 3/8"x4"x2'-6" (10) 3/4"Ø
ANGLE EA. SIDE B. REFER TO STRUCTURAL STEEL GENERAL NOTES ON SHEET S0.1 FOR CONNECTION
3/16
ADDITIONAL INFORMATION
C. MINIMUM CONNECTION ANGLE THICKNESS IS 3/8" TYPICAL AND 7/16" HSS WHERE
AT W33 AND DEEPER "HEAVY" CONNECTIONS. INDICATED
L4x4x5/16 x 5" LONG TOP & BOTT. - SHOP
D. MINIMUM LEG LENGTH IS 4". WELD BOTT. ANGLE SEAT TO COL. Physical: 16291 FM 849
BEAM BEAM Mail: P.O. BOX 2428
E. BOLTS ARE 3/4"Ø TYPICAL AND 7/8"Ø AT W40, AND W44 "HEAVY" L4x4x5/16 x COL. WIDTH HSS BEAM PER Lindale, Texas 75771
ASIC STD. DBL. ANGLE
CONNECTIONS. BOLTS ARE A325N. SHOP WELD TO COL. PLAN Phone: 903.882.8503 / Fax 903.882.5318
SHEAR CONN.
F. BEAM CONNECTIONS ARE "STANDARD" U.N.O. ON PLAN WWW.HOLLANDENGR.COM

COL.
G. CONTRACTOR SHALL CHECK DESIGN OF ALL BEAMS REQUIRING COL. PER PLAN Texas Firm #: F-8474
COPES GREATER THAN SHOWN IN DETAIL BASED ON REACTIONS HE #: 20-019
SHOWN IN TABLE. CONNECTION ANGLES, BOLTS AND WELDS SHALL
NOT BE LESS THAN THAT SHOWN.
BM. TO BM. BM. TO COL.
1 TYPICAL BOLTED BEAM TO BEAM CONNECTION 2 TYPICAL W BEAM TO HSS COLUMN CONNECTION 3 TYP. MOMENT CONN. DTLS. 4 TYPICAL HSS BEAM TO COLUMN CONNECTION
S6.1 SCALE: NONE S6.1 SCALE: NONE S6.1 SCALE: 3/4" = 1'-0" S6.1 SCALE: NONE

3/4" Ø ERECTION
WORK POINT BOLT (TYP.)
DOUBLE ANGLE
CONNECTION SEE NOTE 3
A
1/4 3 3/8" THK. STIFF PL. WORK POINT

"A"
EA. SIDE FINISH FLOOR
WORK POINT
1/2" STRAP PL. CL. OF BEAM
BEAM
1/4
HSS BEAM
PER PLAN
CL. OF
3/4" Ø ERECTION BOLT BEAM

NON-SHRINK GROUT
HS
S

SEE NOTE 5
COL.
PER PLAN
SCHED. ANCHOR
3/4"Ø ERECTION
1/4" END PL. EA. END RODS
BOLT (TYP.)
GUSSET PL. 3/8"
THK. CL. COL.

HS
S
HSS BEAM PER L4x4x5/16 x 5" LONG TOP & BOTT. - SHOP

HS

S
PLAN WELD BOTT. ANGLE SEAT TO COL. NOTES:
CL. OF COLUMN
1. SEE COLUMN SCHEDULE, PLANS, OR DETAILS FOR ELEVATION OF BASE PLATE.
1/4 3 2. MINIMUM FILLET WELD ACCORDING TO AISC SPECIFICATIONS (1/4" MIN.).
GUSSET PL. 3. REFER TO BRACE ELEVATIONS AND BRACE NOTES FOR ADDITIONAL
HSS COL. PER PLAN NOTES: 3/8" THK. CONNECTION DESIGN CRITERIA.
1. AT ROOF, SLOPE CAP PLATE ACCORDINGLY. 4. GUSSET PLATE AT CENTER OF COLUMN, U.N.O., 3/8" THICK MIN.
2. REFER TO BRACE ELEVATIONS AND BRACE NOTES FOR ADD'L. NOTES: 5. MINIMUM GROUT IS 1 1/2" U.N.O. ON PLANS, DETAILS, OR IN ANCHOR ROD
CONNECTION DESIGN CRITERIA. 1. GUSSET PLATE TO BE AT THE CENTER OF BEAM. SCHEDULE.

5 TYPICAL HSS BEAM TO COLUMN CONNECTION 6 TYPCIAL WIND BRACE CONNECTION 7 TYPICAL WIND BRACE CONNECTION 8 TYPICAL WIND BRACE CONNECTION
S6.1 S6.1 S6.1 S6.1
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
H ospi ality
Health R
HOSPITALITY
HEALTH ER
TYLER
1/4 3 EXPANSION
T.O.S.
EL. RE: PLAN Tyler, Texas
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

HSS COL.
S
HS

GUSSET PL. 3/8" THK.


1/2" BASE PL W/ (4)
ASTM A325 BOLTS
FILE NAME:
COL. PER PLAN

BEAM
BM. 20-019-STRUCTURAL
CL. OF BEAM (2) 3/8" STIFFENER GA.
EA. SIDE PROJECT NUMBER:
1909
3/4" CAP PL. W/
3/4"Ø ERECTION BOLT, TYP. (4) 3/4"Ø A325 BOLTS SHEET CONTENTS:
TYPICAL STEEL FRAMING
WORK POINT
DETAILS
BEAM PER PLAN 1/2" THK. STIFF PL EA.
NOTES: SIDE ALIGNED W/
1. GUSSET PLATE TO BE AT THE CENTER OF BEAM. COL. FLANGES ABOVE

9 TYP. WIND BRACE CONNECTION 10 TYPICAL BEAM OVER COLUMN 11 TYPICAL HSS STUB COL. DETAIL
S6.1 SCALE: 3/4" = 1'-0" S6.1 SCALE: 3/4" = 1'-0" S6.1 SCALE: 3/4" = 1'-0"

S
6.1
9/11/2020 11:16:13 AM

BRACED FRAME NOTES:

1. CENTER OF GRAVITY OF MEMBERS SHALL INTERSECT AT ALL JOINTS.


2. ALL WELDED CONNECTIONS (GUSSET PLATES TO BEAMS OR COLUMNS) SHALL BE DETAILED USING
1/4" FILLET WELDS ALL AROUND.
3. ALL GUSSET AND STIFFENER PLATES SHALL BE 3/8" THICK MINIMUM.
4. ALL WEB MEMBERS SHALL BE FIELD WELDED TO GUSSET PLATES W/ 1/4" FILLET WELDS x 3" LONG @
5 6 F C EA. STEEL INTERSECTION (4 TYP. AT EA. WEB HSS TO GUSSET PLATE).
5. JOISTS, ROOF DECK, FLOOR DECK AND FINISHES ARE NOT SHOWN FOR CLARITY.
T.O.S. SEE PLAN T.O.S. SEE PLAN 6. VERIFY COLUMN SIZES WITH FOUNDATION PLAN.
EL. = 137'-10 1/4" EL. = 137'-10 1/4" 7. VERIFY BEAM SIZES WITH FLOOR AND ROOF FRAMING PLANS.
HSS8x6x1/4 HSS8x6x1/4
T.O.S.
T.O.S.
EL. = 134'-6 1/2" EL. = 137'-10 1/4"
09/11/2020

HSS6x6x1/4

C6x8.2

C6x8.2

C6x8.2

C6x8.2
C6x8.2

C6x8.2

C6x8.2

C6x8.2
W12x45 (+2 1/2")
T.O.S.
W16x26 EL. = 134'-0 1/4"
T.O.S.
EL. = 133'-2"
THACKER | DAVIS ARCHITECTS
7 I N C O
Member American
R P O R
Institute of
A T E D
Architects

S6.1
.
1100 Judson Rd., Suite 620 PO Box 2723
Longview, Texas 75606-2723
.
Phone 903.236.3771 Fax 903.753.7317

Email: T D A @ T - D A r c h i t e c t s . c o m

w w w . T - D A r c h i t e c t s . c o m

HSS8x8x1/4

HSS8x8x1/4
1/4

HS
4x

S
HS
1/4

4x
x
S4

4
S5
5x

x1
HS
5x

x5

/4
S

x1
HS

/4
HSS8x8x1/4

HSS8x8x1/4
7 7 STRUCTURAL ENGINEER:
9
9 S6.1 S6.1

51°

53°
51°
S6.1

53°
S6.1
W21x57 W14x30
T.O.S. T.O.S.
EL. = 117'-8" EL. = 117'-8"

Physical: 16291 FM 849


Mail: P.O. BOX 2428

1/4

HS
Lindale, Texas 75771

4x

S
4x
Phone: 903.882.8503 / Fax 903.882.5318

4x

4x
S
WWW.HOLLANDENGR.COM

1/4
HS
Texas Firm #: F-8474

/4

HS
HE #: 20-019

x1

S
x5

5x
S5

5x
1/ 4
HS
8
S6.1

45°

45°
FIN. FLR.
8 EL. RE: PLAN
S6.1

53°
53°

FIN. FLR.
EL. RE: PLAN

1 SECTION @ GRID LINE "A" 2 SECTION @ GRID LINE "1"


S6.2 SCALE: 1/4" = 1'-0" S6.2 SCALE: 1/4" = 1'-0"

A B
SEE PLAN

HSS6x6x1/4 T.O.S.
T.O.S. EL. = 147'-11"
C6x8.2
C6x8.2
C6x8.2

EL. = 145'-9 9/16"

W12x26 (+2 1/2")


T.O.S.
EL. = 146'-4 1/8"

T.O.S.
T.O.S. 7 EL. = 133'-7 1/16"
EL. = 133'-2 1/16" S6.1

W12x40

H ospi ality
Health R
HOSPITALITY
HS
4

HEALTH ER
x1/

S4

F H
4x4

x4x
S
HSS6x6x1/4

HSS6x6x1/4
1/4
HS

SEE PLAN
TYLER
HSS8x6x1/4 T.O.S. EXPANSION
EL. = 121'-11 1/2"
9 Tyler, Texas

C6x8.2
C6x8.2
C6x8.2
S6.1 7
T.O.S.
F:\HE Projects\2020\20-019 Hospitality Health ER - New Addition\Structural (Revit 2020)\20-019 Hospitality Health ER New Addition - Structural_JMHHE.rvt

57°

57°

S6.1 EL. = 117'-4 3/16" T.O.S.


EL. = 117'-7 1/16"
W12x35 T.O.S. W16x40 (+2 1/2")
EL. = 117'-8"

FILE NAME:
20-019-STRUCTURAL
7
S6.1 PROJECT NUMBER:
1909
HSS6x6x1/4

HSS6x6x1/4
SHEET CONTENTS:
FRAME ELEVATIONS
4

HS

HSS
1/4
x 1/

S4
x4

x
4x4
x4

4
S4

x4x
x 1/
HS

HS S

1/ 4
4

8 8
S6.1 S6.1
65°
66°
59°
59°

FIN. FLR. FIN. FLR.


EL. RE: PLAN EL. RE: PLAN

3 SECTION @ GRID LINE "11" 4 SECTION @ GRID LINE "14"


S6.2 S6.2
SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0"
S
6.2
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
X X X X X X X X X

X
X X X X X X X X X X X X X X X X X X X X X

X
X X X X X X X X X X X X

X X X X X

X
X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X

X X X X X
XX

X XX

X
X X X X X X
XX

X
X X XX

X
X
X X X X

X
XX
X
XX XX XX XX

X
X

X
X X
X

X
X X X X X X X X X
X
X

X X X X X X X X X
X X X X X
X

X X X
X X X X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

X
X
XX X X X X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X X

X
XX XX XX

X
X

X
X X X

X
X X
X X X X

X X X
X X X

X
X X X
X X X

X X

X X X
XX
XX

X
X X
XX
XX

X
X

X
X X X X X X
X

X
X
X
X X X X X X
X

X X X X X X

X
X X X X

X X X
X X X
X

X
X X X X X X X X X X X X X X X X X X X X X X X X X X X

X X X
X X X X X X X X X X X X X X X X X

X
X X X X X X X X

X X X
X
X
X

X
X X X X

X
X
X X

X X X X X X

X
X

X
X X X
X

XX
XX

X X XX
X X X X X X

X
X
X

X
X
X X

X
X X

XX
X X X X X X X

X
X
X
X X X X X X

X X
X X X X X X X X

X X X X X X X
X X X X X X X X X X X X

X X
X
X X X X X X X X X X X X X X X X X X X X X X X X X X

X
X X X X X X
X XX X
X

X X X X
X X X
X X X X X X

XX
X X

X X X
X X X
X X
XX

X
X X X X X X

X X
X
X XX X X

X
X
X X X X X X X X X

X
X X X X X X X X

X
X

X
X X X X X X
X

X
COPYRIGHT
X X X X X X X X X X

X
X
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
X X X X X X X X X

X X X X X X X X X X
X X COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY

X X X X X X X X X

X X X X X
X X X X X X X X X X
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE

X X X X X X X X X
X X X
X

X X X X X
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT

XX
X X X X X X X X X THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

X
X
X X PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE

X X
X
XX
X X X X X X

X
X DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE

XX XX X X

X
X

X X X X

X
X

X X

X X X X X XX XX
X X X X X X X
X X X
X X AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS

X
X
X

X
X X X
X X X

X X X X
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.

X X X
XX

X X X X

X
XX

X
X X X X X X X
X X X X X X X X
X X X X X X X
X X X X
X X X X X X X

X
X

X
X X X XX X
X

X
X X X X X X X
X

X X X X X X
X X X

XX
X X X X X X X X

X X X X X X
X X X
XX

X
X X X X

X
X

X X X

X X X
X

XX

XX
X
X

X
XX

X
X

X
X X X X X X X X
X

X
X X X X X X X X X X X

X
XX
X X X X X X X X X X X X X X
XX

X
XX

X
X X

X
X X X X X X X X X X

XX
X

X X X X X X X X X X X X X X X X X X X X X X X

X X

X
XX
XX

X
X
X X X X X X X X X X X X X X X X X X X X

X X

X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X
X X X
X
X X

X
X X
X X
X X
X X
X X
X
XX
X

X
X
X X
X X XX

X X X

X X
X

XX X X

X X X X X X X X
X XX
X
X X X X X X
XX X XXX X
X
X
X X

X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X

X X X
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
X X
X X X
XX

X X X X X
X
X

X X X X
X

X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X

X X X X X X X X X X X X

X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

X
X

X
X
X
X X

X
X
X X X
X
X X X X X X
X
X XX

X
X X

X X X X X
X X X X X X X X X

X X X

X
X X COPYRIGHT
X THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY

X
X FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
X

X
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT

X
X X X X X X X X X X THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

X X X
X X X X X X X X X PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE

X X X X X X X X X X

X
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.

X X X X

X X X X X
X

X
X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

X X X X
X X X X X X X X

X
X

X
X X X X X X X X

X
X
X
XXX
X

X X X

X X X X X
X
X X X X X X X X X X
X XX X X X X
X
X X X X X
X

X X X X X
X

X
X
X X X X X X X
X X
X

X
X X X XX X X X X X
X
X X

X
XX
X
X
X
X

X
X X X X
XX X XX XX
X X X X X
X X X X X X X X X X

X X X X X X
X

X X X X

X X X
X X

X
X
XX
X

X
X X X X XX XX
X X

X X X
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.

1. CLOSE VALVES #1 AND #3


2. OPEN VALVE #4 AND #5
3. OPEN VENT VALVE #6 TO
PROVIDE VENT
4. TURN ON AUXILIARY WATER PUMP
5. REVERSE SEQUENCE TO PROVIDE
FOR CITY WATER
RICKEY L. WATSON

X X X X X X X

X X X
X X

X
XX
X

X X X
X X
X

X
X X X
X X X X

X X

X X
X X

X X
XX X
X

COPYRIGHT

X
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES

X
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
X X X THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

X
X

X
X
X X PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE

X XX
X X
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE

X X
X

X X
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS

X X

X
X
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.

X
X X X X X X

X
X

X
X
X X
X

X
X

X
X
X XX
X

X
X X X X X X X

X
X
X X

X X

X X

X X

X X

X X
X X

X X

X X

X X

X X

X X
XX X X X

X
XX
X X

X
X X

X
X

X
X
XX X X X X X X
X
X X

X
X X
X X X X
X X X X
X X

X X X

X
X

X X
X
X

X X

X X
X X

X
X
X

X
X X X
X

X X
X X
X
X
X

X
X
X
X
X
X

X X X
X X X X X X X X
X

X
X

X X X X
X X
X
X X X X
X

X
X X

X X X X
X X X X
X

X
X

X
X
X

X
X X

X X X
RICKEY L. WATSON

X X X

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.
RICKEY L. WATSON

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

X X X X X X X X X X
X X X X X X X X X X
COPYRIGHT
THESE DOCUMENTS ARE PROTECTED BY UNITED STATES
COPYRIGHT LAW. THEY HAVE BEEN PREPARED SPECIFICALLY
FOR THE PROJECT IDENTIFIED AND ARE NOT SUITABLE FOR USE
ON ANY OTHER PROJECT OR AT ANY OTHER LOCATION WITHOUT
THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
PURTLE AND ASSOCIATES, L.C. REPRODUCTION OF THESE
DOCUMENTS OR ANY PART, PARTS, DETAILS, ETC., MUST BE
AUTHORIZED BY PURTLE AND ASSOCIATES, L.C. ALL RIGHTS
ARE RESERVED TO PURTLE AND ASSOCIATES, L.C.

X X
X
X X