X1 WATER BOILERS
Install of package 4-pass fire tube hot water boilers complete with
all accessories. The boilers shall be complete with Microprocessor
control panel. The item shall include all necessary relief valves & 2 NO
safety operation gear. The water boilet shall be UL labelled & FM
approved.
The water boiler capacity shall be 100 BHP at 50C ambient
temperature.
X2 HEAT EXCHANGERS
Install of Water / Water heat exchangers for domestic, kitchen &
AC systems for the project . The domestic & kitchen water heat
exchangers shall be storage type with a heat coil pundle & glass
plated tank. The AC heat exchanger shall be shell & tube type. The
item shall include all necessary piping , fittings , valves , control
valves & accessories.
X3 PUMPS
X31 Primary Hot Water Pumps
Install primary hot water pumps with all standard accessories and
options. 'The pumps shall be centrifugal, end suction type, vertical
split case with mechanical seal. The pump casing shall be cast iron,
bronze impeller, stainless steel shaft & totally enclosed fan cooled
induction motor. The motor shall be 2900 rpm & shall be wound for
delta operation at 380V power supply.
PRELIMINARY
New Congress Hall COSMOS
Sharm El Sheikh MAR 30TH 2018
2018
Rate TOT
Item Description QTY Unit
(EGP) (EGP)
PRELIMINARY
New Congress Hall COSMOS
Sharm El Sheikh MAR 30TH 2018
2018
Rate TOT
Item Description QTY Unit
(EGP) (EGP)
SECTION (21 12 00) BOILER PLANT HOT WATER PIPING
X5
WORKS 0
Supply and install boiler plant hot water stainless steel 316 sch 10S
including thermal insulation, shut-off valves, valves, check valve,
drainage valve, vent valve, quick coupling valve, strainer, piping
required to be connected with the system including fittings, flange,
bolts, nuts, gaskets, supports, painting , pressure gauges and color
codes. The item shall be complete with all accessories as specified & 1 L.S
shown in the tender drawings. All valves , fittings, gauges &
accessories shall be UL/FM labelled.
0
X6 Boiler plant Electric panel & Electric works
Supply and install UL/FM labelled boiler power supply & pumps
control switch-board with an automatic and manual built-in circuit
breakers . The item shall include all cabling between the panelboard
and the boiler plant equipment including cable trays, flexible
conduits, control wiring. The panel shall include relays,
contactors,lamps, and alarms., volt, power, current meters and 1 L.S
related inherent systems and protective elements, earthing,
interlocking and connection with fire alarm and smoke system . The
works include testing, start-up and commissioning .