PRIORITY 1 ITEMS – Must be checked / tested during all audits as far as possible. Person
in charge of equipment to test same in the presence of the auditor.
GUIDANCE NOTES FOR TESTING OF ALARMS / INACTIVE FUNCTIONS / EMERGENCY
EQUIPMENT
PRIORITY 1 ITEMS – Must be checked / tested during all audits as far as possible. Person
in charge of equipment to test same in the presence of the auditor.
No Item Guidance Notes In
Charge
TS01 Emergency fire pump Run the emergency fire pump / Close the isolating valve on the fire line 3/E
leading to E/R to ensure freeness of valve and E/R fire pumps if operational
are not effective. / Observe flow of water from hoses. Using one hose on
foc’sle deck and one on bridge wing (throw 12 metres) / Check Pressure on
discharge line near pump (sufficient pressure on the 2 hoses, pump pressure
as per maker’s instruction) / If possible check for operation in ballast condition
(check records of 4-Monthly reporting as per format given in MTM 8.2)
Ensure vacuum pump (if fitted) is in working condition.
TS02 Oily Water separator Switch on unit / Ensure overboard discharge valve is shut / Ensure that the 2/E
pump can be run from bilge – tank/bilges / Obscure path across photo electric
cell of 15ppm with a brush etc or activate the press button for testing / Watch
for 15 ppm alarm activation, operation of 3-way valve indicating by pass to
bilge holding tank or stopping of bilge pump. / Alarm should sound and 3-way
valve should activate or pump should stop at 15ppm. It should not be more
than 15ppm on the sensor unit. (Operational test to be carried out for at least
20 mins).
TS03 Fire dampers for: THIS IS A MAJOR CAUSE FOR PSC DETENTION. All MUST be physically
tested.
Engine Room Check for operation after activation from EHQ and local operation 4/E
Funnel 4/E
Accommodation C/O
Holds C/O
TS04 Operation of Nav. and
GMDSS equip.
Radar Check operation of the radar equipment with respect to picture quality, echo 2/O
reception, and carry out a performance monitor test if fitted (If in port, Radar
to be operated only on dry cargo ships)
MF/HF DSC The Transmission and reception of DSC messages, MF/HF, etc and all the 2/O &
daily, weekly, monthly tests for SART, EPIRB etc / Operation of equipment on 3/O
emergency battery supply / DSC test with shore stations / Ship’s staff to
demonstrate operation of equipment. Carry out live test of MF/HF equipment
with a Coast station (only on dry cargo ships) / Check for acknowledgement
from shore stations / Check for relevant entries in GMDSS log book.
TS05 Emergency generator / Check for starting methods / Normally 2 different methods required. Common E/O
Battery supply methods are: Compressed Air, Hydraulic, and Battery operated. / A good
practice would be to check simulated black out condition by closing ESB tie
(To be carried out only if breaker on MSB / Check Emergency Generator starts automatically and
vessel is at anchorage and comes on load within 45 secs.
there is sufficient time to Caution :
allow gyro to settle down All Navigation / Bridge equip. power supply from ESB will need to be
and to reset all equipment). switched off prior doing this test.
Observe condition of batteries / Observe method of filling of Air receiver / (air
receiver should be pressed up at all times)
TS06 Air pipes for F.O, Ballast and (Note: - Random check: Physical check by removal of vent heads not to be 2/E &
FW tanks done on liquid cargo ships while at berth, or while carrying out cargo C/O
operations at sea.) At least 20% of all vent heads to be opened and check the
condition of floats in air pipes for ballast, FW and FO tanks. (Check record of
inspection and ask how it was done. If in doubt, randomly select vents and
have their heads removed to inspect physical condition of the float) / Check Air
pipes for wastage & holes / Check Flame arrestors in air pipes for FO tanks.
Internal Audit checklist Date: 01.06.11 Revision: 26 Prep: MR App: PKC Page 2 of 5
TS07 Lifeboat Engines, / Rudder / Check for level of fuel in tank (should be full) / Condition of battery / C/O
lights / Inventory, Lifeboat Operation of ahead -astern movement of propeller / cabin and canopy 3/O
lowering arrangements, lights/search light/torch incl. Spare batteries and bulbs. Check condition of 3/E
davits & Limit switches auto release cables, air bottles, hand pumps, sea anchor, quick release
mechanism for painter. Ensure lifeboats’ bottom drain plug secured in place
with chain.
TS08 Portable gas detection Fresh air test / O2 depletion alarm test / Calibration check.
equip.
ALL VESSELS
TS41 Earth Values on all Ask vessel to switch on all deck lights , all laundry and galley equipment C/E
Switchboard and check 440V, 220V,110V switchboard in ECR/ER and 24V in the E/O
battery room , Emergency Switchboard in the Em Gen Room.
PRIORITY 2 ITEMS - Time permitting, check / test the following items in addition to the above list.
If time is inadequate check records of maintenance of following equipment:
No Item Guidance Notes In
Charge
TS41 Navigational equipment Check for operation / Officer’s awareness of limitations of equipment
Course recorder Markings for arrival and Departure ports / Synchronization with clock and Gyro 2/O
Gyro Compare with repeaters / last annual service done etc / Error 2/O
Echo sounder Accuracy / Compare digital display and Echograph 2/O
Log Check Accuracy / Is the staff aware of inputs from log in various nav. equip. 2/O
TS42 Nav. light alarms and emer. Check if emergency supply is available / Check for awareness of NUC lights 2/O &
supply E/O
TS43 Fire detectors Detectors to randomly select and test, especially ones located in not so easily E/O
accessible locations. (Select smoke, thermal, flame detector at least 1 each).
Fire alarm Manual Call Button (randomly select 2)
TS44 Crane Check any one crane for limit switches operation./ Limit switches (5 limits) – E/O
(Any one crane randomly selected.)/ Check emer. stops and system / Check
record of renewal of crane wires (5 year interval)
TS45 Gangway Limit switch – P & S gangway. Condition of wire. E/O
C/O
TS46 Fridge room alarms. Press alarm switch in cold room / Alarm should sound in galley and bridge E/O
alleyway / Location of botton should be clearly marked.
TS47 Hospital Alarm. Check for operation E/O
TS48 Lift Alarms Check alarms working on the bridge/ship’s office. Check for emergency stops E/O
TS49 Incinerator – trips and Fire incinerator on diesel oil and operate micro switch for garbage loading 2/E &
alarms door. / Incinerator should shut down E/O
TS50 Compressor alarms . Check Logs for: C.W. high temp trip / Low lube oil pressure trip 4/E &
Confirm test for Low lube oil pressure trip is done by using hand pump and E/O
calibrated pressure gauge
TS51 Main Engine alarms Check Logs for: Low lube oil pressure trip / Other Alarms and Trips as per 2/E &
PMS / Over speed E/O
TS52 Aux. Engine alarms Check monthly alarm test record for 3 shut downs for Generators / High 3/E &
jacket temperature / Low lube oil pressure / Over speed. Confirm test for Low E/O
lube oil pressure trip is done by using hand pump and calibrated pressure
gauge,
TS53 High level Bilge Alarm: Check by physically activating float mechanism
Hold Check for records of last overhauling / inspection of non return valves C/O &
E/O
Duct Keel 4/E &
E/O
Bow Thruster room 2/E &
E/O
TS54 Lamp and Buzzer Test for Check operation of all lamps and alarm. E/O
Bridge Console, E.R.
Console, Cargo and Ballast
Console.
TS55 Auto-Pilot off-course alarm. Check operation 2/O
TS56 Sewage Plant : Check 3 way valve position for confirming sewage being directed to sewage 2/E
plant. Check compressor functioning by placing hand on suction side to feel
sucking of air.
TS57 Boiler safeties Low level alarm and trip - test by draining the float chamber. 3/E &
E/O