GENERAL NOTES: LEGEND: TABLE OF CONTENTS

1. ALL PLUMBING WORKS INCLUDED HEREIN SHALL BE EXECUTED I. WATER DISTRIBUTION SYSTEM: SHEET NUMBER SHEET CONTENT
ACCORDING TO THE PROVISIONS OF THE PHILIPPINE PLUMBING CODE
THE NATIONAL BUILDING CODE & THE RULES AND REGULATIONS OF PCWL POTABLE COLD WATER LINE
MUNTINLUPA CITY. P - 01 GEN. NOTES, MATERIAL SPECS.
NPCWL NON POTABLE COLD WATER LINE LEGEND
2. COORDINATE THE DRAWING WITH OTHER RELATED DRAWINGS AND CWR COLD WATER RISER TABLE OF CONTENTS
SPECIFICATION THE ENGINEER/ARCHITECT SHALL BE NOTIFIED
IMMEDIATELY OF ANY DECREPANCY FOUND THEREIN. CWDF COLD WATER DOWNFEED
HB HOSE BIBB P - 02 GROUND FLOOR SEWER AND VENT LAYOUT
3. ALL PIPES SHALL BE INSTALLED AS INDICATED ON PLANS. ANY RELOCA- GV (NC) GATE VALVE
TIONS REQUIREED FOR PROPER EXECUTION OF OTHER TRADES SHALL (NORMALLY CLOSE) P - 03 SECOND FLOOR SEWER AND VENT LAYOUT
BE WITH PRIOR APPROVAL OF THE ARCHITECT OR ENGINEER. GV (NO) GATE VALVE
4. PROPOSED SANITARY UTILITIES SHALL CONFORM TO THE ACTUAL (NORMALLY OPEN) P - 04 THIRD FLOOR SEWER AND VENT LAYOUT
LOCATION, DEPTH AND INVERT ELEVATION OF ALL EXISTING PIPES WM WATER METER
STRUCTURAL AS VERIFIED BY THE CONTRACTOR.
CV CHECK VALVE P - 05 FOURTH FLOOR SEWER AND VENT LAYOUT
5. ALL SLOPES FOR HORIZONTAL DRAINAGE SHALL MAINTAIN 1% UNLESS FC FLEXIBLE CONNECTION
OTHERWISE SPECIFIED. P - 06 GROUND FLOOR POTABLE AND NON POTABLE WATERLINE LAYOUT
6. SIZES OF WATER SUPPLY PIPES TO FIXTURES SHALL BE IN ACCORDANCE II. SEWER/WASTE & VENT SYSTEM:
WITH THE MANUFACTURER'S INSTRUCTIONS. P - 07 GROUND FLOOR POTABLE AND NON POTABLE WATERLINE LAYOUT
SP SOIL PIPE
7. THE CONTRACTOR SHALL VERIFY ALL EXISTING UTILITIES AT SITE.
COORDINATE THE WORKS THE SEWER LINE EFFLUENT DISPOSAL POINT SS SOIL STACK P - 08 SECOND FLOOR POTABLE AND NON POTABLE WATERLINE LAYOUT
AND WATER LINE CONNECTING POINT UNLESS OTHERWISE SPECIFIED. V/VAC VENT/VENT AT CEILING
VSTE VENT STACK THRU P - 09 FOURTH FLOOR POTABLE AND NON POTABLE WATERLINE LAYOUT
8. ALL WATER PIPE AND WATER TANKS SHALL BE THOROUGHLY FLUSHED
AND DISINFECTED WITH LIQUID CHLORINE OR HYPOCHLORITE SOLUTION. EAVES
P - 10 ROOF DECK FLOOR POTABLE AND NON POTABLE WATERLINE LAYOUT
9. ALL WATER PIPES SHALL BE HYDROSTATICALLY TESTED TO AT LEAST III. STORM DRAINAGE SYSTEM:
1-1/2 OF THE DESIGNED WORKING PRESSURE OF THE SYSTEM.
DP DRAINAGE PIPE
P - 11 MISCELLANEOUS DETAILS
10. ALL SANITARY AND STORM DRAINAGE PIPES SHALL BE HYDROSTA- DS DOWNSPOUT
TICALLY TESTED TO AT LEAST 3.0 M. HEAD TO ENSURE THAT THE SYSTEM GD/DD GUTTER DRAIN/
ARE WATER TIGHT. P - 12 MISCELLANEOUS DETAILS
DECK DRAIN
11. ALL DIMENSIONS ARE IN METERS AND ALL PIPE SIZES ARE IN MILLI- PD PARKING DRAIN
METERS UNLESS OTHERWISE SPECIFIED.
IV. FIXTURES:
12. ALL PIPES DIMENSIONS REFER TO INSIDE DIAMETER.
WC WATER CLOSET
EQUIPMENT SCHEDULE
LAV LAVATORY
URI URINAL CAPACITY APPROX. MOTOR
PUMP TYPE LOCATION VOLTS PHASE HERTZ OPERATION
SS SLOP SINK (GPM) HEAD, (FT)
SPECIFICATIONS: FD FLOOR DRAIN
(HP)

TRANSFER VERTICAL
1. POTABLE & NON POTABLE POLYPROPYLINE PIPE "AMICO" BRAND. 1-DUTY
PUMP MULTI-STAGE GROUND FLOOR 120 GPM 270 7.5 230 3 60
WATER LINES (POTABLE) 1-STANDBY
CENTRIFUGAL PUMP
2. DRAINAGE LINES V. APPURTENANCES
PVC PIPE SERIES I000 II, WITH SOLVENT JOINT AD/CB AREA DRAIN/CATCH BASIN
FITTINGS,"EMERALD" BRAND OR EQUAL. TRANSFER VERTICAL
JB JUNCTION BOX 1-DUTY
PUMP MULTI-STAGE GROUND FLOOR 60 GPM 270 5 230 3 60
OUTSIDE BUILDING SHALL BE CONCRETE SI/CB ST. INLET/CATCH BASIN (NON POTABLE) CENTRIFUGAL PUMP 1-STANDBY
DRAIN PIPE (CDP) MANHOLE
3. SEWER & WASTE LINES GT GREASE TRAP VERTICAL
& ABOVE PVC PIPES CLASS 35 WITH SOLVENT BOOSTER 1-LEAD
FCO/GCO FLOOR CLEANOUT/ MULTI-STAGE ROOF DECK
JOINT FITTINGS,"EMERALD" BRAND OR 60 GPM 120 3 230 3 60
GROUND CLEANOUT PUMP (POTABLE) CENTRIFUGAL PUMP 1-LAG
EQUAL.
4. VENT LINES PVC PIPES SERIES 600, WITH SOLVENT JOINT CCO CEILING CLEANOUT
FITTINGS,"EMERALD" BRAND OR EQUAL. VERTICAL
BOOSTER PUMP MULTI-STAGE 1-LEAD
5. WATER METER "ARAD, EVER, ASAHI" MWSS APPROVED ROOF DECK 60 GPM 120 3 230 3 60
(NON POTABLE) CENTRIFUGAL PUMP 1-LAG
6. DRAIN & CLEANOUTS BRONZE, CONFORMING ASTM B62, 1034 KPa
CLASS THREADED CONNECTION.
ELEVATOR SUBMERSIBLE
ELEVATOR PIT 10 GPM 30 1/2 230 3 60 DUTY
PUMP NON-CLOG

BY REPUBLIC ACT NO. 545, AND REPUBLIC ACT NO. 9266 DRAWN
ENGINEER PROJECT TITLE OWNER SHEET CONTENTS DATED MARCH 17, 2004: SECTION 33. OWNERSHIP OF
PROJECT I.D. NO.
PLANS, SPECIFICATIONS AND OTHER CONTRACT
GENERAL NOTES DOCUMENTS - DRAWINGS AND SPECIFICATIONS AND DATE
OTHER CONTRACT DOCUMENTS DULY SIGNED,
PRC NO.:
ALABANG MEDICAL CLINIC CLINIC SYSTEM INC. LEGENDS STAMPED OR SEALED, AS INSTRUMENTS OF SERVICE,
ARE THE INTELLECTUAL PROPERTY AND DOCUMENTS
EDITION
SHEET NO.
SHEET NO.

PTR NO.: DATE: OF THE ARCHITECT. IT SHALL BE UNLAWFUL FOR ANY


TABLE OF CONTENTS PERSON TO DUPLICATE OR TO MAKE COPIES OF SAID
DATE P
DOCUMENTS WITHOUT THE WRITTEN CONSENT OF THE
PLACE: LOCATION: APPROVAL: MR. FRANCIS MONTILLANO ARCHITECT OR AUTHOR OF DOCUMENTS. CHECKED 01