Professional Documents
Culture Documents
2.2 - Prototypes-SPEC (DIV21-33) - 2022.07.19
2.2 - Prototypes-SPEC (DIV21-33) - 2022.07.19
(NEIGHBOURHOOD – PROTOTYPE)
TECHNICAL SPECIFICATIONS
Document 5.2, Volume 2.2: DIV. 21 - 33
January 2022
DOCUMENT 5
TECHNICAL SPECIFICATION
INDEX
VOLUME 1
VOLUME 2.1
DIVISION 03 CONCRETE
DIVISION 04 MASONRY
DIVISION 05 METALS
DIVISION 08 OPENINGS
DIVISION 09 FINISHES
DIVISION 10 SPECIALTIES
DIVISION 11 EQUIPMENT
DIVISION 12 FURNISHINGS
VOLUME 2.2
KEO/19-3262-0000 /3 Index
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
DIVISION 21 FIRE SUPPRESSION
DIVISION 22 PLUMBING
DIVISION 26 ELECTRICAL
DIVISION 27 COMMUNICATIONS
KEO/19-3262-0000 /5 Index
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
SECTION 27 1000 ANALOGUE TELEPHONE SYSTEM
27 1100 COMMUNICATION CABLING SYSTEM
27 1116 COMMUNICATIONS RACKS FRAMES AND ENCLOSURES
27 1323 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING
27 1513 COMMUNICATIONS COPPER HORIZONTAL CABLING
27 2133 WIFI SYSTEM
27 2223 IP DATA AND COMPUTER SYSTEM
27 4116 AV SYSTEM
27 4133 SMATV, IPTV AND DIGITAL INFORMATION DISPLAY SYSTEM
27 4220 QUEUE MANAGEMENT STSTEM
27 5116 MASJID SOUND SYSTEM
27 5117 PUBLIC ADDRESS SYSTEM
27 5223 EMERGENCY CALL SYSTEM FOR SPECIAL NEED PERSON
DIVISION 31 EARTHWORK
DIVISION 33 UTILITIES
END OF INDEX
KEO/19-3262-0000 /7 Index
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
SECTION 21 0500
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 DEFINITIONS
A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred
spaces, pipe chases, unheated spaces immediately below roof, spaces above ceilings,
unexcavated spaces, crawlspaces, and tunnels.
D. Concealed, Interior Installations: Concealed from view and protected from physical
contact by building occupants. Examples include above ceilings and in chases.
E. Concealed, Exterior Installations: Concealed from view and protected from weather
conditions and physical contact by building occupants but subject to outdoor ambient
temperatures. Examples include installations within unheated shelters.
1.03 SUBMITTALS
A. Steel Support Welding: Qualify processes and operators according to AWS D1.1,
"Structural Welding Code--Steel."
B. Steel Pipe Welding: Qualify processes and operators according to ASME Boiler and
Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications."
a) Comply with provisions in ASME B31 Series, "Code for Pressure Piping."
b) Certify that each welder has passed AWS qualification tests for welding
processes involved and that certification is current.
A. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through
shipping, storage, and handling to prevent pipe end damage and to prevent entrance of
dirt, debris, and moisture.
B. Store plastic pipes protected from direct sunlight. Support to prevent sagging and
bending.
1.06 COORDINATION
A. Arrange for pipe spaces, chases, slots, and openings in building structure during
progress of construction, to allow for fire-suppression installations.
C. Coordinate requirements for access panels and doors for fire-suppression items
requiring access that are concealed behind finished surfaces. Access panels and doors
are specified in Division 08 Section "Access Doors and Frames."
a) Sprinkler system will be provided in the basement of all buildings (where exists).
b) Duration of operation will differ based on the protection of the building
c) For buildings protected by maximum 2 fire hose reel, the flow of the fire pump
shall be not less than 36 GPM with a fire tank minimum capacity 500 US gallon
(1.9 m3)
Ground Total
Floor Built Required
Building Building
No. Name
Floors Foot Up Type of
Print Area Protection
m2 m2
sprinkler
LBF + LGF + L01 + hose reel
C1 Supermarket 7781.7 26817.1
LLRF + LURF landing
valve
Society
sprinkler
C2 Development LGF+L01+LLRF+LURF 2359.8 4114
+hose reel
Center
Social Unit LGF + L01 + LLRF +
C3 756.1 1384.5 hose reel
Building LURF
Citizen LGF + L01 + LLRF +
C4 1013 1609.4 hose reel
Services LURF
KEO/19-3262-0000 21 0500/3 Common Work Results for Fire Suppression
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
LGF + L01 + LLRF + Sprinkler +
C5 Police station 1528.4 3152.7
LURF Hose reel
sprinkler (in
Municipality LBF + LGF +
C6 720 720 basement)
Building LLRF+LURF
+hose reel
Masjid,
Ablution,
LGF + L01 + LLRF +
C7 Imam & 2787.3 3834.5 hose reel
LURF
Called
Building
LGF + L01 + LLRF + sprinkler
C8 Post Office 1176.4 2433.2
LURF +hose reel
Health Care sprinkler
LGF + L01 + LLRF +
C9 & Ambulance 3746.3 7241.3 +hose reel
LURF
Center + LV
Trade
Control & sprinkler (in
LBF + LGF + L01 +
C10 Consumer 552.6 1995.8 basement)
L02+ LLRF+LURF
Protection +hose reel
Center
LGF + L01 + LLRF + sprinkler
C11 Library 1799.4 2921
LURF +hose reel
sprinkler
LBF+LGF + L01 + +hose reel +
C12 Children Club 2359.8 4114
LLRF + LURF Landing
Valve
Building
No. Name Fire Requirements
C1 Supermarket At Basement:
1- Conceret Tank (230 m3).
2- Conventenioal (1000 gpm) Fire Pumps
(1W+1S + 1J).
Building
No. Name Fire Requirements
C5 Police station At Roof (Fire):
1- Tank: Separate GRP Tank (60 m3)
(Selection: 6x4x3).
2- Pumps: Horizontal Split Case Pumps
(1W+1S+ 1J). (500 gpm)
C6 Municipality 1- Fire Tank:
Separate GRP Tank (11 m3)
Building
No. Name Fire Requirements
C8 Post Office At Roof (Fire):
1- Tank: Separate GRP Tank (45 m3)
2- Pumps: End Suction Pumps (1W) + 1 jocky
pump. 1000 L/MIN (265 gpm )
Building Name
No.
Fire Requirements
KEO/19-3262-0000 21 0500/5 Common Work Results for Fire Suppression
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C11 Library At Roof (Fire):
1- Tank: Separate GRP Tank (60 m3)
(Selection: 6x4x3).
2- Pumps: Horizontal Split Case Pumps
(1W+1S+ 1J). (500 gpm)
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. In other Part 2 articles where subparagraph titles below introduce lists, the following
requirements apply for product selection:
a) Subject to approved manufacturers list by PAHW.
b) The product or manufacturers listed are included for the purpose of establishing
minimum quality standards. Products of equal quality or better might be
considered if produced by a specialized manufacturer whose products are equal
in every respect and have been in similar service for not less than five years.
The products must also have a local distributor and must be backed with a
professional service centre. The decision of acceptability shall rest with the
Engineer’s representative.
c) Products to be provided shall be from the manufacturer approved from KFSD &
civil Defense.
2.02 Products to be provided shall be from the manufacturer approved from KFSD & civil
DefensePIPE, TUBE, AND FITTINGS
A. Refer to individual Division 21 piping Sections for pipe, tube, and fitting materials and
joining methods.
B. Pipe Threads: ASME B1.20.1 for factory-threaded pipe and pipe fittings.
A. Refer to individual Division 21 piping Sections for special joining materials not listed
below.
B. Pipe-Flange Gasket Materials: Suitable for chemical and thermal conditions of piping
system contents.
a) ASME B16.21, nonmetallic, flat, asbestos-free, 1/8-inch (3.2-mm) maximum
thickness unless thickness or specific material is indicated.
a. Full-Face Type: For flat-face, Class 125, cast-iron and cast-bronze
flanges.
b. Narrow-Face Type: For raised-face, Class 250, cast-iron and steel
flanges.
b) AWWA C110, rubber, flat face, 1/8 inch (3.2 mm) thick, unless otherwise
indicated; and full-face or ring type, unless otherwise indicated.
C. Flange Bolts and Nuts: ASME B18.2.1, carbon steel, unless otherwise indicated.
E. Brazing Filler Metals: AWS A5.8, BCuP Series, copper-phosphorus alloys for general-
duty brazing, unless otherwise indicated; and AWS A5.8, BAg1, silver alloy for
refrigerant piping, unless otherwise indicated.
F. Welding Filler Metals: Comply with AWS D10.12 for welding materials appropriate for
wall thickness and chemical analysis of steel pipe being welded.
A. Description: Modular sealing element unit, designed for field assembly, to fill annular
space between pipe and sleeve.
a) Sealing Elements: EPDM/NBR interlocking links shaped to fit surface of pipe.
Include type and number required for pipe material and size of pipe.
b) Pressure Plates: Carbon steel. Include two for each sealing element.
c) Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of
length required to secure pressure plates to sealing elements. Include one for
each sealing element.
2.05 SLEEVES
B. Steel Pipe: ASTM A 53, Type E, Grade B, Schedule 40, galvanized, plain ends.
C. Cast Iron: Cast or fabricated "wall pipe" equivalent to ductile-iron pressure pipe, with
plain ends and integral waterstop, unless otherwise indicated.
D. Stack Sleeve Fittings: Manufactured, cast-iron sleeve with integral clamping flange.
Include clamping ring and bolts and nuts for membrane flashing.
a) Underdeck Clamp: Clamping ring with set screws.
E. Molded PVC: Permanent, with nailing flange for attaching to wooden forms.
G. Molded PE: Reusable, PE, tapered-cup shaped, and smooth-outer surface with nailing
flange for attaching to wooden forms.
2.06 ESCUTCHEONS
A. Description: Manufactured wall and ceiling escutcheons and floor plates, with an ID to
closely fit around pipe, tube, and insulation of insulated piping and an OD that
completely covers opening.
E. One-Piece, Stamped-Steel Type: With set screw or spring clips and chrome-plated
finish.
H. Split-Casting, Floor-Plate Type: Cast brass with concealed hinge and set screw.
2.07 GROUT
PART 3 - EXECUTION
B. Drawing plans, schematics, and diagrams indicate general location and arrangement of
piping systems. Indicated locations and arrangements were used to size pipe and
calculate friction loss, expansion, pump sizing, and other design considerations. Install
piping as indicated unless deviations to layout are approved on Coordination Drawings.
D. Install piping indicated to be exposed and piping in equipment rooms and service areas
at right angles or parallel to building walls. Diagonal runs are prohibited unless
specifically indicated otherwise.
E. Install piping above accessible ceilings to allow sufficient space for ceiling panel
removal.
L. Install escutcheons for penetrations of walls, ceilings, and floors according to the
following:
a) New Piping:
a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep-
pattern type.
b. Chrome-Plated Piping: One-piece, cast-brass type with polished chrome-
plated finish.
c. Insulated Piping: One-piece, stamped-steel type with spring clips.
d. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-
piece, cast-brass type with polished chrome-plated finish.
e. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-
piece, stamped-steel type.
f. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece or
split-casting, cast-brass type with polished chrome-plated finish.
g. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece,
stamped-steel type or split-plate, stamped-steel type with concealed hinge
and set screw.
h. Bare Piping in Unfinished Service Spaces: One-piece, cast-brass type
with polished chrome-plated finish.
i. Bare Piping in Unfinished Service Spaces: One-piece, stamped-steel
type with concealed or exposed-rivet hinge and set screw or spring clips.
j. Bare Piping in Equipment Rooms: One-piece, cast-brass type.
k. Bare Piping in Equipment Rooms: One-piece, stamped-steel type with set
screw or spring clips.
l. Bare Piping at Floor Penetrations in Equipment Rooms: One-piece, floor-
plate type.
N. Permanent sleeves are not required for holes formed by removable PE sleeves.
O. Install sleeves for pipes passing through concrete and masonry walls and concrete floor
and roof slabs.
P. Install sleeves for pipes passing through concrete and masonry walls, gypsum-board
partitions, and concrete floor and roof slabs.
a) Cut sleeves to length for mounting flush with both surfaces.
a. Exception: Extend sleeves installed in floors of mechanical equipment
areas or other wet areas 2 inches (50 mm) above finished floor level.
Extend cast-iron sleeve fittings below floor slab as required to secure
clamping ring if ring is specified.
b) Install sleeves in new walls and slabs as new walls and slabs are constructed.
c) Install sleeves that are large enough to provide 1/4-inch (6.4-mm) annular clear
space between sleeve and pipe or pipe insulation. Use the following sleeve
materials:
a. Steel Pipe Sleeves: For pipes smaller than NPS 6 (DN 150).
b. Steel Sheet Sleeves: For pipes NPS 6 (DN 150) and larger, penetrating
gypsum-board partitions.
c. Stack Sleeve Fittings: For pipes penetrating floors with membrane
waterproofing. Secure flashing between clamping flanges. Install section
of cast-iron soil pipe to extend sleeve to 2 inches (50 mm) above finished
KEO/19-3262-0000 21 0500/10 Common Work Results for Fire Suppression
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
floor level. Refer to Division 07 Section "Sheet Metal Flashing and Trim"
for flashing.
1) Seal space outside of sleeve fittings with grout.
d) Except for underground wall penetrations, seal annular space between sleeve
and pipe or pipe insulation, using joint sealants appropriate for size, depth, and
location of joint. Refer to Division 07 Section "Joint Sealants" for materials and
installation.
R. Underground, Exterior-Wall Pipe Penetrations: Install cast-iron "wall pipes" for sleeves.
Seal pipe penetrations using mechanical sleeve seals. Select sleeve size to allow for
1-inch (25-mm) annular clear space between pipe and sleeve for installing mechanical
sleeve seals.
a) Mechanical Sleeve Seal Installation: Select type and number of sealing
elements required for pipe material and size. Position pipe in center of sleeve.
Assemble mechanical sleeve seals and install in annular space between pipe
and sleeve. Tighten bolts against pressure plates that cause sealing elements to
expand and make watertight seal.
S. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and
floors at pipe penetrations. Seal pipe penetrations with firestop materials. Refer to
Division 07 Section "Penetration Firestopping" for materials.
A. Join pipe and fittings according to the following requirements and Division 21 Sections
specifying piping systems.
B. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
C. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before
assembly.
D. Soldered Joints: Apply ASTM B 813, water-flushable flux, unless otherwise indicated, to
tube end. Construct joints according to ASTM B 828 or CDA's "Copper Tube
Handbook," using lead-free solder alloy complying with ASTM B 32.
F. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1.
Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs
and restore full ID. Join pipe fittings and valves as follows:
a) Apply appropriate tape or thread compound to external pipe threads unless dry
seal threading is specified.
b) Damaged Threads: Do not use pipe or pipe fittings with threads that are
corroded or damaged. Do not use pipe sections that have cracked or open
welds.
G. Welded Joints: Construct joints according to AWS D10.12, using qualified processes
and welding operators according to Part 1 "Quality Assurance" Article.
H. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service
application. Install gasket concentrically positioned. Use suitable lubricants on bolt
threads.
I. Plastic Piping Solvent-Cement Joints: Clean and dry joining surfaces. Join pipe and
fittings according to the following:
a) Comply with ASTM F 402 for safe-handling practice of cleaners, primers, and
solvent cements.
b) CPVC Piping: Join according to ASTM D 2846/D 2846M Appendix.
3.03 PAINTING
B. Damage and Touchup: Repair marred and damaged factory-painted finishes with
materials and procedures to match original factory finish.
B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and
elevation to support and anchor fire-suppression materials and equipment.
A. Cut, fit, and place wood grounds, nailers, blocking, and anchorages to support, and
anchor fire-suppression materials and equipment.
B. Select fastener sizes that will not penetrate members if opposite side will be exposed to
view or will receive finish materials. Tighten connections between members. Install
fasteners without splitting wood members.
3.07 GROUTING
A. Mix and install grout for fire-suppression equipment base bearing surfaces, pump and
other equipment base plates, and anchors.
F. Place grout on concrete bases and provide smooth bearing surface for equipment.
A. Provide a written monthly report to the employer, detailing the maintenance work
performed, including dates, parts replaced etc.
B. Provide all necessary maintenance staff experienced in fire protection works such as
engineers, supervisors, operators, technicians, helpers etc. for effective maintenance
and operations of all systems. Submit to the engineer for approval the qualification
details of all maintenance staff.
D. Provide all spare parts for replacements made necessary due to wear and tear of
equipment, provide all consumable parts, short life parts, oil, grease, filters, chemicals,
etc. and all tools and maintenance equipment required for proper operation and
complete maintenance of the work.
F. Include for complete routine maintenance and corrective and preventive maintenance
with the requirement of the contract document as follow:
a) Defect liability / breakdown maintenance, inclusive of replacement parts.
b) Preventive maintenance as scheduled, inclusive of replacement parts and
consumables.
c) Submit the schedule of routine operational and preventive maintenance for all
equipment for the employer’s/engineer approval.
d) Attending to emergencies, which may damage property or endanger lives, even
outside normal working hours.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 COORDINATION
PART 2 - PRODUCTS
A. Comply with requirements in this Section except when stricter requirements are
specified in fire suppression equipment schedules or Sections.
A. Duty: Continuous duty at ambient temperature of 40 deg C and at altitude of 3300 feet
(1000 m) above sea level.
G. Bearings: Regreasable, shielded, antifriction ball bearings suitable for radial and thrust
loading.
I. Insulation: Class F.
K. Enclosure Material: Cast iron for motor frame sizes 324T and larger; rolled steel for
motor frame sizes smaller than 324T.
B. Motors Used with Variable Frequency Controllers: Ratings, characteristics, and features
coordinated with and approved by controller manufacturer.
1. Windings: Copper magnet wire with moisture-resistant insulation varnish,
designed and tested to resist transient spikes, high frequencies, and short time
rise pulses produced by pulse-width modulated inverters.
2. Energy- and Premium-Efficient Motors: Class B temperature rise; Class F
insulation.
3. Inverter-Duty Motors: Class F temperature rise; Class H insulation.
4. Thermal Protection: Comply with NEMA MG 1 requirements for thermally
protected motors.
C. Severe-Duty Motors: Comply with IEEE 841, with 1.15 minimum service factor.
A. Motors larger than 1/20 hp shall be one of the following, to suit starting torque and
requirements of specific motor application:
1. Permanent-split capacitor.
KEO/19-3262-0000 21 0513/2 Common Motor Requirements for Fire Suppression Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Split phase.
3. Capacitor start, inductor run.
4. Capacitor start, capacitor run.
C. Bearings: Prelubricated, antifriction ball bearings or sleeve bearings suitable for radial
and thrust loading.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
E. Fire stopping.
A. Division 21 Section "Water-Based Fire-Suppression Systems" for pipe hangers for fire-
suppression piping.
B. Division 21 Section "Vibration and Noise Controls for Fire Suppression Piping and
Equipment" for vibration isolation devices.
1.03 REFERENCES
A. General:
1. The following documents form part of the Specifications to the extent stated.
Where differences exist between codes and standards, the one affording the
greatest protection shall apply.
2. Unless otherwise noted, the referenced standard edition is the current one at the
time of commencement of the Work.
3. Refer to Division 21 Section "Common Results for Fire Suppression" for codes
and standards, and other general requirements.
1.04 SUBMITTALS
A. Submit under provisions of Division 21 Section "Common Results for Fire Suppression –
Quality Assurance."
B. Submit shop drawing of hanger and support spacing, framing and attachment methods.
D. Do not use black steel devices, components, fasteners, etc. within the Clean Room
interstitial space or in any related airflow path. Steel items shall be plated, galvanized,
painted, or coated.
PART 2 - PRODUCTS
A. Hangers for Pipe Sizes ½ (12.7 mm) to 1-1/2 Inch (38 mm): electro-galvanized,
adjustable swivel ring, UL listed.
B. Hangers for Pipe Sizes 2 Inches (50.8 mm) and Cold Pipe Sizes 6 Inches (152.4 mm)
and Over: electro- galvanized, adjustable, clevis, UL listed.
C. Hangers for Hot Pipe Sizes 6 Inches (152.4 mm) and Over: electro-galvanized
Adjustable steel yoke, cast iron roll, double hanger.
F. Floor Support for Pipe Sizes to 4 Inches (101.6 mm): electro-galvanized adjustable pipe
saddle, locknut nipple, floor flange, and concrete pier or steel support.
KEO/19-3262-0000 21 0529/2 Hangers and Supports for Fire Suppression Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2.03 HANGER RODS
A. Inserts for new formed concrete construction: Malleable iron case of galvanized steel
shell and expander plug for threaded connection with lateral adjustment, top slot for
reinforcing rods, lugs for attaching to forms; size inserts to suit threaded hanger rods.
A. Miscellaneous Steel: Angles, channels, brackets, rods, clamps, etc., of new materials
conforming to ASTM A36. electro-galvanize all steel parts after fabrication where used
outdoors or inside the penthouse.
B. Fasteners: All bolts and nuts, except as otherwise specified, shall conform to ASTM
Standard Specifications for Low Carbon Steel Externally and Internally Threaded
Standard Fasteners, Designation A307. Bolts shall have heavy hexagon heads, and
nuts shall be of the hexagon heavy series. All bolts, washers, nuts, anchor bolts,
screws and other hardware used outdoors or inside the penthouse shall be galvanized,
and all galvanized nuts shall have a free running fit. Provide bolts of ample size and
strength for the purpose intended. All ferrous metal components below grade shall be
stainless steel.
A. See Arch. and Structural Drawings for the design detail of the equipment curb.
2.08 SLEEVES
A. Materials and installation shall comply with U.L. "Fire Resistance Directory", for
Through-Penetration for Fire stop Devices, latest edition.
KEO/19-3262-0000 21 0529/3 Hangers and Supports for Fire Suppression Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2.010 FABRICATION
A. Size sleeves large enough to allow for movement due to expansion and contraction.
Provide for continuous insulation wrapping.
2.011 FINISHES
A. Prime-paint exposed steel hangers and supports. Hangers and supports located in
crawl spaces, pipe shafts, and suspended ceiling spaces are not considered exposed.
1. Steel in the Clean Room interstitial space is considered exposed.
PART 3 - EXECUTION
A. Concrete Structure: Locate anchors from any edge condition and at a spacing to obtain
maximum working loads specified in the applicable ICC report.
1. See structural drawings for additional restrictions for locating anchors.
B. Steel Structure: Attach at beam axis. Avoid eccentric loads wherever possible.
D. Submit for structural review all pipe hanger locations, point loads and structural
attachment details for pipes 6 inches (152.4 mm) and larger.
A. Set all machines and devices dead level, except where pitch or slope is specified or
shown. Securely fasten to the structure unless shown otherwise. Use dry pack cement
grout to obtain complete contact between structure and equipment.
B. This Section is responsible for the concrete work for the support of equipment provided
by this Section. Coordinate locations with anchor bolts before concrete is placed.
2. Install hangers to provide at least 1/2 inch (13 mm) space between finished
covering and adjacent work.
3. Place a hanger within 12 inches (300 mm) of each horizontal elbow.
4. Use hangers with at least 1-1/2 inch (38 mm) vertical adjustment.
5. Support horizontal cast iron pipe adjacent to each hub, with 5 feet (1.5 m)
maximum spacing between hangers.
6. Support vertical piping at every floor. Support vertical cast iron pipe at each floor
at hub.
7. Where several pipes can be installed in parallel and at same elevation, provide
multiple or trapeze hangers. Use specified pipe shields (if applicable). Trapeze
size, and support size and spacing shall be governed by the cumulative weight of
the supported piping. Maximum trapeze deflection shall be 1/240th of the span
on a maximum stress of 15,000 psi (103.5 MPa), whichever is more stringent.
8. Support riser piping independently of connected horizontal piping.
9. Brace piping longitudinally and transversely as specified and indicated on the
drawings.
10. Support all pipe from the building structure so that there is no apparent deflection
in pipe runs. Fit piping with steel sway braces and anchors to prevent vibration
and/or horizontal displacement under load when required. Do not support from,
or brace to, ducts, other pipes, conduit, or any materials except building
structure. Piping or equipment shall be immobile and shall not be supported or
hung by wire, rope, plumber's tape, plastic ties, or blocking of any kind. Vertical
piping running between floors shall be additionally supported at mid points in a
rigid and immobile fashion. Any exposed or concealed piping which can be
physically moved, and which is not properly supported will not be accepted, and
additional support or bracing will be required.
11. Install and secure all equipment with anchors and braces to floors, structural
members and walls with sufficient backing, to prevent vibration and/or horizontal
displacement under load and seismic force as hereinbefore specified. Follow
manufacturer's recommendations for the installation of vibration isolators where
required for all equipment requiring such.
E. Sleeves:
1. Set sleeves in position in formwork. Provide reinforcing around sleeves.
2. Extend sleeves through floors 1 inch (25 mm) above finished floor level. Caulk
sleeves full depth and provide floor plate.
3. Where piping or ductwork penetrates floor, ceiling, or wall, close-off space
between pipe or duct and adjacent work with fire-stopping insulation and caulk
airtight. Provide close-fitting metal collar or escutcheon covers at both sides of
penetration.
4. Install chrome-plated steel escutcheons at finished surfaces.
KEO/19-3262-0000 21 0529/5 Hangers and Supports for Fire Suppression Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
END OF SECTION
KEO/19-3262-0000 21 0529/6 Hangers and Supports for Fire Suppression Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
SECTION 21 0548
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Inertia bases.
B. Vibration isolation.
1.02 REFERENCES
C. Do not exceed the allowable noise level, 70 dBA measured at a distance of 1200 mm (4
feet) from source, by proper engineering of equipment assemblies.
A. Fans and other rotating mechanical equipment shall not operate at speeds in excess of
80 % of their true critical speed.
B. Vertical vibration of rotating equipment shall not be greater than the levels indicated.
The vibration shall be measured on the equipment or steel frame equipment base when
the equipment is mounted on its vibration isolation mounts. If the equipment has an
inertia base, the allowable vibration level is reduced by the ratio of the equipment weight
alone to the equipment weight plus the inertia base weight.
KEO/19-3262-0000 21 0548/1 Vibration and Noise Controls for Fire Suppression Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1.05 SUBMITTALS
B. Include data for each equipment and size of unit showing isolation type, efficiency,
stiffness, natural frequency, and transmissibility at lowest operating speed of equipment,
actual load, static deflection under actual load etc.
D. Indicate vibration isolator locations, on general layout and plant room detail drawings.
E. Flexible pipe connector shop drawings data to include maximum allowable temperature
and pressure rating, overall face to face length, live length, hose wall thickness, and
fundamental frequency of assembly.
F. Submit manufacturer's certificates that the vibration isolators are properly selected and
installed in equipment assemblies, to meet with, or to exceed the Contract requirements.
PART 2 - PRODUCTS
2.01 GENERAL
C. Products to be provided shall be from the manufacturer approved from KFSD & civil
DefenseAll metal parts of vibration isolation units installed out of doors shall be hot dip
galvanised, cadmium plated, or neoprene coated after fabrication. Galvanising shall
meet ASTM salt spray test standards and Federal test standard No. 14.
E. Static deflection of isolators shall be as shown on the schedule. All static deflections
stated are the minimum acceptable deflection for the mounts under actual load. Isolators
selected on the basis of rated deflection are not acceptable.
2.02 BASES
A. Type "A" - INTEGRAL BASES: This type is generally applicable for packaged chillers,
pumps, Air Handling Units, Air conditioning Units etc. which are supplied with factory
fabricated rigid base which can be mounted directly on vibration isolators. Equipment
manufacturer's recommendations should be sought for the number, locations and
weight distribution to select and install vibration isolators.
B. Type "B" - STEEL STRUCTURAL BASES: This type is generally subdivided into closed
frame type (Type B1) and rails type (Type B2). These are steel bases fabricated either
as per the approved shop drawing or as per the equipment manufacturer's
recommendation. These are used for equipment not having a rigid base. The type B1
shall be used where the vibration isolators are located within the equipment base and
type B2 shall be used when the vibration isolators are outside the equipment and the
type B2 base acts as a cradle. The minimum depth shall be 4 inches.
C. TYPE "C" CONCRETE INTERTIAL BASES: This type generally consists of structural
steel, fabricated pouring form with reinforcing bars. The concrete shall be poured on
site. The minimum depth shall be 6 inches.
D. TYPE "D" - ROOF CURBS: This type is generally used for Roof top Air Handling Units
with direct cutting through roof slab under the units. These roof curbs shall be supplied
by the unit manufacturer. The manufacturer's recommendations should be sought for
the number, locations and weight distribution to select and install vibration isolators.
E. TYPE "E" - HOUSE KEEPING PADS: These are concrete bases used for all equipment
with or without moving parts and shall be suitable for taking up the static and dynamic
loads (if any). Size base to extend 10 cms beyond equipment base in all directions and
minimum10 cms above finished floor level. Roughen floor slab beneath base for bond
and or provide rebar dowels in floor slab. Locate anchor bolts (welded on to a rebar
framework to maintain spacing) with templates supplied by the equipment manufacturer.
Provide steel angle frame with anchorage lugs at the corners. Also see table 3.03 for
exact heights.
F. TYPE "F" - FLOATING CONCRETE BASE: This is similar to Type "E" (House keeping
pads) but isolated at the bottom and all the side by either pre-compressed glass fiber
pads or Heavy density seasoned cork. The thickness of isolating pads vary from 25 to
100 mm (1 to 4 inch) depending on the application.
D. TYPE "1C" - CORK PADS: The cork pads shall be constructed from natural cork
granules compressed and steam baked to form slabs and shall have a density of 96 to
106 kg/cu.M (6 to 6.6 lbs/cu.ft). The cork pads shall be treated with hot Bitumen Asphalt
coating for protection of cork.
E. TYPE "2" - MOLDED NEOPRENE RUBBER MOUNTS: These shall be used where a
greater deflection is required than that for pads. The maximum deflection allowable is 12
mm (0.5 inch) on these rubber mounts. The normal shape of mount is conical with a
captive insert for attaching to equipment base.
F. TYPE "3" - FREE STANDING SPRING ISOLATORS: These shall be constructed with
open type stable spring and load plates at top and bottom with an adjustable bolt for
levelling. Neoprene rubber acoustical treatment shall be provided to prevent
transmission of very high frequency vibration and noise. The spring shall be so designed
that the horizontal stiffness is more than 75 % of vertical stiffness. The rated loads and
deflections for these springs shall allow additional 50 % travel to that of the rated
deflection before the springs are compressed solid, to accommodate any errors in actual
load distribution.
G. TYPE "4" - RESTRAINED SPRING ISOLATORS: These are similar to type "3", but with
additional restraints in the vertical direction. These isolators shall have hold down bolts
to limit vertical movement. The restraints should have adequate clearance so that they
are activated only when a temporary restraint is needed.
H. TYPE "5" - HOUSED SPRING ISOLATORS: These isolators are similar to type "4"
except that they consist of two telescoping houses. The contact surfaces of houses are
separated by resilient inserts such as Neoprene Sponge or equivalent material.
I. TYPE "6" - RUBBER HANGERS: These are similar to type "2" except that the conical
rubber mold is housed in a steel casing and have a through hole for the hanger rod. The
assembly should allow for 20 to 35 degrees angular movement for the hanging rod
without metal to metal contact.
J. TYPE "7" - SPRING HANGERS: These are similar to type "3" except that the spring is
mounted in a steel casing and used for suspension only. The assembly shall allow for
20 to 25 degrees angular movement for the hanging rod without metal to metal contact.
L. TYPE "9" - THRUST RESTRAINTS: These are similar to type "7", but installed in pairs
to counteract the thrust caused by air pressure.
KEO/19-3262-0000 21 0548/4 Vibration and Noise Controls for Fire Suppression Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
M. TYPE "10" - AIR SPRINGS: These shall consist of constant dry air supplying equipment
and air bellows. These shall be used where 150 mm (6 inch) or greater deflection is
required and natural frequencies do not exceed 80 Hz.
A. This shall consist of a sleeve 25 mm (1-inch) larger all round than that of the penetrating
element and fabricated out of steel pipe or sheet metal as the condition warrants. The
sleeve length shall be 25 mm (1 inch) extra on both sides of the penetrated construction.
The annular space is filled with resilient material such as Neoprene sponge or type 1B
material and ends sealed with approved sealant compatible with the resilient material.
A. Flexible pipe connections shall be fabricated of multiple plies of nylon cord, fabric, and
neoprene, vulcanised so as to become inseparable and homogeneous. Straight
connections shall be formed in a double sphere shape. Elbow connections shall have a
single sphere shape at the curve of the unit. Flexible connections shall be able to accept
compressive, elongative, transverse, and angular movements.
B. The flexible connections shall be selected and specially fitted, if necessary, to suit the
system temperature, pressure, and fluid type.
C. Use bellow type metal flexible connectors with braided steel wire armour when they are
located in outdoor areas where the type described above will be damaged due to sun
radiation.
D. Connectors for pipe sizes 50 mm (2 inch) nom. dia. or smaller shall have threaded
female union couplings, made up of compatible material like cast iron for steel and
bronze for copper piping, on each end. Larger sizes shall be fitted with metallic flange
couplings.
PART 3 - EXECUTION
3.01 APPLICATION
A. GENERAL
1. Refer to PART 2 - PRODUCTS of this specification for vibration isolation devices
identified on the schedule or specified herein.
B. MAJOR EQUIPMENT
1. Unless otherwise shown or specified, all floor mounted major equipment shall be
set on concrete housekeeping pads as per recommendations of the
manufacturer. See schedule of mounting pads in this section.
2. Types and minimum static deflections of vibration isolation devices for major
equipment items shall be as scheduled on the drawings or specified here under.
3. Flexible duct connections shall be installed at all fan unit intakes, fan unit
discharges, and wherever else shown on the drawings.
4. Flexible pipe connections shall be installed at all pipe connections to vibration
isolated equipment in the positions shown on the drawings.
5. Electrical connections to vibration isolated equipment shall be flexible, as called
for in the electrical portion of the specification.
KEO/19-3262-0000 21 0548/5 Vibration and Noise Controls for Fire Suppression Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
6. Snubbers or thrust restraints shall be installed on equipment as called for in the
schedule on the drawings or specified here under.
D. PIPING
1. Provide flexible pipe connections in piping connected to vibration isolated
equipment, as called for and shown on drawings.
2. Anchor piping at the system side of the flexible connector.
3. Inlet and outlet piping of all pumps should have flexible connections.
4. All piping within mechanical rooms should be supported with spring isolated
hangers. Piping should not rigidly contact structural elements.
5. All pipe/conduit penetrations of portions, floors/ceiling slabs must be sealed
airtight with acoustic sealant or mineral fiber and fire code compound.
A. General
1. Locations of all vibration isolation equipment shall be selected for ease of
inspection and adjustment as well as for proper operation.
2. Installation of vibration isolation equipment shall be in accordance with the
manufacturer's instructions.
B. Isolation Mounts
1. All vibration isolators shall be aligned squarely above or below mounting points of
the supported equipment.
2. Isolators for equipment with bases shall be located on the sides of the bases,
which are parallel to the equipment shaft unless this is not possible because of
physical constraints.
3. If a housekeeping pad is provided, the isolators shall bear on the housekeeping
pad and the isolator base plate shall rest entirely on the pad.
4. Hanger rods for vibration isolated support shall be connected to structural beams
or joists, not from the floor slab between beams and joists. Provide intermediate
support members as necessary.
5. Vibration isolation hanger elements shall be positioned as high as possible in the
hanger rod assembly, but not in contact with the building structure, and so that
the hanger housing may rotate a full 360 degrees about the rod axis without
contacting any object.
6. Parallel running pipes may be hung together on a trapeze, which is isolated from
the building. Isolator deflections must be the largest determined by the provisions
for pipe isolation. Do not mix isolated and non-isolated pipes on the same
trapeze.
7. No pipes or equipment shall be supported from other pipes or equipment.
8. Resiliently isolated pipes shall not contact the building construction or other
equipment.
9. The installed and operating heights of vibration isolators supporting any
equipment shall be identical. Limit stops shall be out of contact during normal
operation.
KEO/19-3262-0000 21 0548/6 Vibration and Noise Controls for Fire Suppression Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
10. Adjust all levelling bolts and hanger rod bolts so that the isolated equipment is
level and in proper alignment with connecting ducts or pipes.
C. Bases
1. No equipment unit shall bear directly on vibration isolators unless its own frame
is suitably rigid to span between isolators and such direct support is approved by
the equipment manufacturer. This provision shall apply whether or not a base
frame is called for on the schedule. In the case that a base frame is required for
the unit because of the equipment manufacturer's requirements and is not
specifically called for on the equipment schedule, a base frame recommended by
the equipment manufacturer shall be provided.
2. Unless otherwise indicated, there is to be a minimum operating clearance of 38-
mm (1 1/2 inch) between inertia bases or steel frame bases and the floor
beneath the equipment. Position isolator mounting brackets and adjust isolators
so that the required clearance is maintained. The clearance space shall be
checked by the Contractor to ensure that no construction debris has been left to
short circuit or restrict the proper operation of the vibration isolation system.
E. Thrust Restraints
1. Snubbers shall be adjusted to clear the equipment base and to provide lateral
restraint during on / off cycling, but be out of contact during normal operation of
the equipment.
2. Thrust restraints shall be attached at the centreline of thrust and symmetrically
on each of the units. Adjust the restraints to limit equipment movement to the
specified limit.
END OF SECTION
KEO/19-3262-0000 21 0548/7 Vibration and Noise Controls for Fire Suppression Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
SECTION 21 1000
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the following fire-suppression piping inside the building:
1. Wet-pipe sprinkler systems.
2. Wet standpipe system.
3. Deluge sprinkler systems.
4. First aid hose reel systems.
5. External fire hydrants.
1.2 DEFINITIONS
B. First aid fire hose reel system: Includes NPS 1 (DN 25) hose stations. Has open water-
supply valve with pressure maintained and is capable of supplying water demand.
D. Deluge Sprinkler System: Open sprinklers are attached to piping connected to water
supply through deluge valve. Fire-detection system in same area as sprinklers opens
KEO/19-3262-0000 21 1000/1 Water Based Fire Suppression Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
valve. Water flows into piping system and discharges from attached sprinklers when
valve opens.
A. Standard Piping System Component Working Pressure: Listed for at least 175 psig
(1200 kPa).
B. High-Pressure Piping System Component Working Pressure: Listed for 250 psig (1725
kPa) minimum or 300 psig (2070 kPa).
1.5 SUBMITTALS
C. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA 13,
that have been approved by authorities having jurisdiction, including hydraulic
calculations.
1. Sprinklers shall be referred to on drawings and shall be specifically identified by
the listed manufacturer’s style or series designation. Trade names and
abbreviations are not permitted.
D. Field Test Reports and Certificates: Indicate and interpret test results for compliance
with performance requirements and as described in NFPA 13 and NFPA 14. Include
"Contractor's Material and Test Certificate for Aboveground Piping" and "Contractor's
Material and Test Certificate for Underground Piping."
E. Welding certificates.
H. Manufacturer's printed brochures and catalogs (one original and three copies) with
relevant information highlighted (or irrelevant information struck out), along with write up
of selection criteria.
J. Equipment installation and piping layout double line drawings of plant rooms, water
storage tanks, etc. clearly indicating all fittings, supports, valves and control gear to a
scale of 1:20. Submit sections and elevations as required by the Construction Engineer.
K. Typical floor plans indicating shafts, riser locations etc. to a scale of 1:50.
L. Builders work layout plans to a scale of 1:100/1:50 as above, along with shaft detail
plans to 1:10.
R. Submit three (3) hard bound copies of "operation and maintenance manual", with
complete data for each piece of equipment installed, as detailed below:
1. The cover shall contain:
a. The title - Fire protection system operation and maintenance manual.
b. Names:
1) The Owner.
2) The Engineer.
3) The Contractor/subcontractor.
2. The Manual shall contain:
a. Table of contents.
b. Fire protection materials submittal with the AE approval.
c. Manufacturer's installation instructions.
d. Manufacturer's internal wiring diagrams.
e. Manufacturer's assembly details.
f. Replacements parts / materials, number listing and description.
g. Preventive maintenance schedules listing frequency of service and or
replacement
h. Lubricants, commercial equivalents and schedules of use.
i. Name and address of manufacturer's sales and service agencies and
local representative / distributor including telephone and telex numbers.
A. Installer Qualifications:
1. Installer's responsibilities include designing, fabricating, and installing fire-
suppression systems and providing professional engineering services needed to
assume engineering responsibility.
a. Engineering Responsibility: Preparation of working plans, calculations.
B. Welding: Qualify processes and operators according to ASME Boiler and Pressure
Vessel Code: Section IX.
D. All grooved joint couplings, fittings, valves, and specialties shall be the products of a
single manufacturer. Grooving tools shall be of the same manufacturer as the grooved
components.
1. All castings used for coupling housings, fittings, valve bodies, etc., shall be date
stamped for quality assurance and traceability.
G. The works covered by this Section shall be executed by contractors, engaged in the
installation of fire protection systems as primary business for at least five (5)
immediately preceding years and having Class I registration as Fire Protection
contractors with the Local Civil Defense Department. Employ specialist subcontractors,
with local representation, for the execution of the special fire protection systems.
H. Use only those products specifically listed / approved for Fire protection services by
Underwriters Laboratories Incorporated USA, Factory Mutual Testing Laboratories USA,
and KFD.
I. Materials incorporated in the work covered by this Section shall be unused, new
products in good condition. Materials spoiled due to improper storage or mishandling
shall be rejected.
L. All copper alloys used in the construction of valves, pipe fittings, fire protection
specialties etc., which comes in contact with water, shall be dezincification resistant
type.
M. Confirm to AWS code in respect of welding materials and procedures and employ
welders certified in accordance with ASME Section 9.
N. Test certificates for materials used in the work covered by this Section, from approved
independent laboratories or testing agencies, shall be furnished at no extra cost if
required by the Engineer.
1.7 WARRANTY
1.8 COORDINATION
A. Coordinate layout and installation of sprinklers with other construction that penetrates
ceilings, including light fixtures, HVAC equipment, and partition assemblies.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
1. Sprinkler Cabinets: Finished, wall-mounting, steel cabinet with hinged cover,
with space for minimum of six spare sprinklers plus sprinkler wrench. Include
number of sprinklers required by NFPA 13 and sprinkler wrench. Include
separate cabinet with sprinklers and wrench for each type of sprinkler on Project.
PART 2 - PRODUCTS
C. Products to be provided shall be from the manufacturer approved from KFSD & civil
Defense.
A. Assembly shall be copper alloy, ferrous, and insulating materials with ends matching
piping system.
D. Dielectric Flange Insulation Kits: Components for field assembly shall include CR or
phenolic gasket, PE or phenolic bolt sleeves, phenolic washers, and steel backing
washers.
E. Dielectric Couplings: Galvanized steel with inert and noncorrosive thermoplastic lining
and threaded ends and 300-psig (2070-kPa) working-pressure rating at 225 deg F
(107 deg C).
F. Dielectric Nipples: Electroplated steel with inert and noncorrosive thermoplastic lining,
with combination of plain, threaded, or grooved ends and 300-psig (2070-kPa) working-
pressure rating at 225 deg F (107 deg C).
G. Dielectric Waterway: Copper silicon casting conforming to UNS C87850 with grooved
and/or threaded ends.
A. Flexible connectors shall have materials suitable for system fluid. Include 250-psig
(1725-kPa) minimum working-pressure rating and ends according to the following:
1. NPS 2 (DN 50) and Smaller: Threaded.
2. NPS 2-1/2 (DN 65) and Larger: Flanged.
3. Option for NPS 2-1/2 (DN 65) and Larger: Grooved for use with grooved-end-
pipe couplings.
E. Three flexible type grooved joint couplings may be used in lieu of flexible connectors at
equipment connections in applicable piping systems. The couplings shall be placed in
close proximity to the vibration source.
C. Sprinkler Drain and Alarm Test Fittings: Cast- or ductile-iron body; with threaded or
locking-lug inlet and outlet, test valve, and orifice and sight glass.
D. Sprinkler Branch-Line Test Fittings: Brass body with threaded inlet, capped drain outlet,
and threaded outlet for sprinkler.
E. Sprinkler Inspector's Test Fitting: Cast- or ductile-iron housing with threaded inlet and
drain outlet and sight glass.
F. Drop-Nipple Fittings: UL 1474, adjustable with threaded inlet and outlet, and seals.
A. Valves shall be UL listed / FM approved, with 175-psig (1200 kPa) minimum pressure
rating.
C. Ball Valves: Comply with UL 1091, except with ball instead of disc.
1. NPS 1-1/2 (DN 40) and Smaller: Bronze body with threaded ends.
2. NPS 2 and NPS 2-1/2 (DN 50 and DN 65): Bronze body with threaded ends or
ductile-iron body with grooved ends.
3. NPS 3 (DN 80): Ductile-iron body with grooved ends.
E. Check Valves NPS 2 (DN 50) and Larger: UL 312, spring-assisted swing type for
vertical or horizontal installation, cast ductile-iron body with flanged or grooved ends.
B. Pressure-Regulating Valves: UL 1468, brass or bronze, NPS 1-1/2 and NPS 2-1/2
(DN 40 and DN 65) 400-psig (2760-kPa) minimum rating. Include female NPS inlet and
outlet, adjustable setting feature, and straight or 90-degree-angle pattern design as
indicated.
1. Finish: Rough Chrome-plated.
C. Automatic Drain Valves: UL 1726, NPS 3/4 (DN 20), ball-check device with threaded
ends.
2.10 SPRINKLERS
A. Sprinklers shall be glass bulb type, with wrench boss integrally cast into the sprinkler
body to reduce the risk of damage during installation. (Wrenches shall be provided by
the sprinkler manufacturer that directly engage the cast wrench boss).
C. Sprinkler Types and Categories: Nominal 1/2-inch (12.7-mm) orifice for "Ordinary"
temperature classification rating, unless otherwise indicated or required by application.
1. Open Sprinklers: UL 199, without heat-responsive element.
a. Orifice: 1/2 inch (12.7 mm), with discharge coefficient K between 5.3 and
5.8.
b. Orifice: 17/32 inch (13.5 mm), with discharge coefficient K between 7.4
and 8.2.
G. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler
mounting applications. Escutcheons for concealed, flush, and recessed-type sprinklers
are specified with sprinklers.
1. Ceiling Mounting Chrome-plated steel, 2 piece, with 1-inch (25-mm) vertical
adjustment.
2. Sidewall Mounting: Chrome-plated steel one piece, flat.
H. Sprinkler Guards: Wire-cage type, including fastening device for attaching to sprinkler.
I. Escutcheons and guards shall be listed, and supplied for use with the sprinkler by the
sprinkler manufacturer.
J. The Connection to Sprinkler head from Main/Branch Fire Pipe line can be flexible hose
pipe suitable for use with pendant or sidewall sprinkler heads. These connections shall
be FM/UL and compatible to be installed in concrete wall or ceiling penetrations.
1. The hose assembly includes 28 mm diameter braided, annular corrugated
stainless steel - 304 flexible pipe with zinc-plated steel male adapter nipple for
connection to branch line piping
2. The Flexible Pipe connection shall be braided of annular corrugation construction
and to have various sizes of lengths to suit the site conditions in order to avoid
unnecessary bends.
3. The braided hose shall be UL listed; braided hose with a bend radius to 2” to
allow for proper installation in confined spaces
a. The hose shall be listed for [(4) bends at 31” length] [(5) bends at 36”
length] [(8) bends at 48” length] [(10) bends at 60” length] [(12) bends at
72” length]
4. Each Flexible Sprinkler Connection shall be with complete package assembly
comes with suspended ceiling rail support brackets with special Inlet/Outlet
fittings. Flexible drop assembly components must be supplied from a single
source to comply with UL requirements
5. The mounting open-gate bracket system locates and secures the sprinkler in the
required position within the ceiling system with special outlet fittings provide a
reasonable amount of adjustment both laterally and vertically for flush and
precise sprinkler installation. The bracket shall allow installation before the ceiling
tile is in place
6. Flexible Sprinkler connections shall be FM-approved and UL-listed for rigorous
tests for hydrostatic pressure, vibration, friction loss, corrosion and water
hammer. Every hose shall be leak-checked at the factory
7. Flexible Sprinkler connection Test Pressure shall be minimum 28 bar and the
Working Pressure shall not be less than 12 bar. The Temperature rating shall be
compatible with FM/UL sprinkler heads.
8. Union joints shall be provided for ease of installation. The bracket shall allow
installation before the ceiling tile is in place.
A. All fire hydrants shall be manufactured and tested in accordance with latest BS 750,
“Type 2”, and its amendments.
1. Fire hydrants shall be screw down type with captive stopper.
2. Fire hydrants shall be medium, fixed type stopper. Simple drain plug with needle
hole.
3. Fire hydrants shall be installed as shown on the drawing and as directed by the
Engineer and Fire Department.
4. Fire hydrant shall be pillar type supplied by an approved supplier of Fire
Department.
A. Description: UL 47, semiautomatic hose stations. Include brass rack nipple, hose rack,
and the following:
1. Valve: UL 668, brass or bronze, 300-psig (2070-kPa) minimum pressure rating,
90-degree-angle-pattern hose valve with female NPS inlet and outlet, unless
otherwise indicated.
a. Valve Operation: Nonadjustable type, unless pressure-regulating type is
indicated.
2. Threads and Gaskets: NFPA 1963 and matching local fire department threads.
3. Flow-Restricting Devices: NPS 2-1/2 (DN 65), brass, adjustable for NPS 2-1/2
(DN 65) fire hose inlet.
4. Fire Hose: NFPA 1961 and UL 219, lined fire hose with couplings, gaskets, and
nozzle. Include the following fire hose materials:
a. Jacket: Natural, synthetic, or combination of natural and synthetic threads
b. Lining: Rubber, plastic, or combination of rubber and plastic compounds
c. Cover: Rubber, plastic, or combination of rubber and plastic compounds.
5. Nozzles: UL 401.
6. Drain Valves: UL 1726.
7. Mountings: Pipe clamp or wall bracket for freestanding and escutcheon for
cabinet-mounted units.
B. NPS 2-1/2 (DN 65) Hose Station: NPS 2-1/2 (DN 65) hose valve with male threaded
outlet, cap, and chain and NPS 2-1/2 (DN 65) hose valve; hose reel with water-retention
device and pins for folded, NPS 2-1/2 (DN 65) lined hose; and NPS 2-1/2 (DN 65) lined
hose with swivel inlet coupling and nozzle.
1. Hose-Reel Finish: Red enamel
2. Hose Valve and Trim Finish: Polished chrome-plated.
3. Fire Hose: Lined, 100-foot (30-m) length.
4. Nozzle: Polished brass, adjustable from shutoff to fog spray or straight stream.
2.14 MONITORS
C. At the low point near each fire department connection, provide a 90-degree elbow with
drain connection to allow for localized system drainage.
A. Description: UL 393, 90- to 115-mm (3-1/2- to 4-1/2-inch) diameter, dial pressure gauge
with range of 0 to 250 psig (0 to 1725 kPa) minimum.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine roughing-in for hose connections and stations to verify actual locations of
piping connections before installation.
B. Examine walls and partitions for suitable thicknesses, fire- and smoke-rated
construction, framing for hose-station cabinets, and other conditions where hose
connections and stations are to be installed.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
C. Flanges, flanged fittings, unions, nipples, and transition and special fittings with finish
and pressure ratings same as or higher than system's pressure rating may be used in
aboveground applications, unless otherwise indicated.
E. Pipes
KEO/19-3262-0000 21 1000/15 Water Based Fire Suppression Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
SERVICE LOCATION TYPE
Sprinkler system piping All Galvanized carbon /steel
up to 80 mm nom. dia sch. 40, seamless.
Sprinkler system piping All Black, carbon steel Sch.
100mm nom dia. And 40, seamless.
larger
Hose Reel System piping All Galvanised wrought
upto 50mm nom.dia. steel, schedule 40
seamless
A. Drawings indicate valve types to be used. Where specific valve types are not indicated,
the following requirements apply:
1. Listed Fire-Protection Valves: UL listed and FM approved for applications where
required by NFPA 13 and NFPA 14.
a. Shutoff Duty: Use ball, butterfly, or gate valves.
A. Refer to Division 21 Section "Common Work Results for Fire Suppression" for basic
piping joint construction.
B. Threaded Joints: Comply with NFPA 13 for pipe thickness and threads. Do not thread
pipe larger than NPS 3 (DN 80) with wall thickness less than Schedule 40 unless
approved by authorities having jurisdiction and threads are checked by a ring gauge and
comply with ASME B1.20.1.
C. Twist-Locked Joints: Insert plain-end piping into locking-lug fitting and rotate retainer
lug one-quarter turn.
D. Pressure-Sealed Joints: Use UL-listed tool and procedure. Include use of specific
equipment, pressure-sealing tool, and accessories.
F. Grooved Joints: Assemble joints with listed coupling and gasket, lubricant, and bolts.
1. Ductile-Iron Pipe: Radius-cut-groove ends of piping. Use grooved-end fittings
and grooved-end-pipe couplings.
2. Steel Pipe: Square-cut or roll-groove piping as indicated. Use grooved-end
fittings and rigid, grooved-end-pipe couplings, unless otherwise indicated.
3. Copper Tube: Roll-groove tubing. Use grooved-end fittings and grooved-end-
tube couplings.
4. Dry-Pipe Systems: Use fittings and gaskets listed for dry-pipe service.
5. Install in accordance with the manufacturer’s latest published installation
instructions.
6. Pipe ends shall be clean and free from indentations, projections and roll marks in
the area from pipe end to (and including) groove.
G. Dissimilar-Metal Piping Joints: Construct joints using dielectric fittings compatible with
both piping materials.
1. NPS 2 (DN 50) and Smaller: Use dielectric unions, couplings, or nipples.
2. NPS 2-1/2 to NPS 4 (DN 65 to DN 100): Use dielectric flanges.
3. NPS 6 (DN 150) and Larger: Use dielectric flange insulation kits.
A. Refer to Division 21 Section "Common Work Results for Fire Suppression" for basic
piping installation.
D. Use approved fittings to make changes in direction, branch takeoffs from mains, and
reductions in pipe sizes.
E. Install unions adjacent to each valve in pipes NPS 2 (DN 50) and smaller. Unions are
not required on flanged devices or in piping installations using grooved joints.
F. Install flanges or flange adapters on valves, apparatus, and equipment having NPS 2-
1/2 (DN 65) and larger connections.
G. Install "Inspector's Test Connections" in sprinkler system piping, complete with shutoff
valve, sized and located according to NFPA 13.
I. Install sprinkler zone control valves, test assemblies, and drain risers adjacent to
standpipes when sprinkler piping is connected to standpipes.
K. Install ball drip valves to drain piping between fire department connections and check
valves. Drain to floor drain or outside building.
O. Install pressure gauges on riser or feed main, at each sprinkler test connection, and at
top of each standpipe. Include pressure gauges with connection not less than NPS 1/4
(DN 8) and with soft metal seated globe valve, arranged for draining pipe between
gauge and valve. Install gauges to permit removal, and install where they will not be
subject to freezing.
P. Pressurize and check dry-pipe sprinkler system piping and air-pressure maintenance
devices and air compressors.
A. Install listed fire-protection valves, specialty valves and trim, controls, and specialties
according to NFPA 13 and NFPA 14 and authorities having jurisdiction.
C. Install check valve in each water-supply connection. Install backflow preventers instead
of check valves in potable-water supply sources.
D. Specialty Valves:
1. Alarm Check Valves: Install in vertical position for proper direction of flow,
including bypass check valve and retarding chamber drain-line connection.
2. Deluge Valves: Install in vertical position, in proper direction of flow, in main
supply to deluge system.
A. Drawings indicate sprinkler types to be used. Where specific types are not indicated,
use the following sprinkler types:
1. Rooms without Ceilings: Upright sprinklers
2. Rooms with Suspended Ceilings: Pendent, concealed sprinklers, as indicated.
3. Wall Mounting: Sidewall sprinklers.
4. Spaces Subject to Freezing: Upright, pendent, dry sprinklers; and sidewall, dry
sprinklers as indicated.
5. Deluge-Sprinkler Systems: Upright and pendent open sprinklers.
6. Special Applications: Extended-coverage, flow-control, and quick-response
sprinklers where indicated
a. Sprinkler Finishes:
b. Upright and Sidewall Sprinklers: Chrome plated in finished spaces
exposed to view; rough bronze in unfinished spaces not exposed to view;
wax coated where exposed to acids, chemicals, or other corrosive fumes.
c. Concealed Sprinklers: Rough brass, with factory-painted cover plate
(color to match ceiling color).
KEO/19-3262-0000 21 1000/18 Water Based Fire Suppression Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
d. Residential Sprinklers: Dull chrome.
B. Do not install pendent or sidewall, wet-type sprinklers in areas subject to freezing. Use
dry-type sprinklers.
C. Do not install sprinklers that have been dropped, damaged, or show a visible loss of
fluid. Never install sprinklers with cracked bulbs.
D. Sprinkler bulb protector shall be removed by hand after installation. Do not use tools or
any other device(s) to remove the protector that could damage the bulb in any way.
E. The Connection to sprinkler head from Main/Branch Fire Pipe line can be flexible hose
pipe suitable for use with pendant or sidewall sprinkler heads. Failure to follow
manufacturer installation instructions is not accepted to avoid compromising assembly
listing.
C. Install freestanding hose connections for access and minimum passage restriction.
D. Install NPS 1 (DN 25) hose-connection valves with flow-restricting device, unless
otherwise indicated.
E. Install NPS 2-1/2 (DN 65) hose connections with quick-disconnect NPS 2-1/2(DN 65)
and flow- restricting device, unless otherwise indicated.
C. Install ball drip valve at each check valve for fire department connection.
D. Install ball drip valves at each check valve for fire department connection. Drain to floor
drain or outside building.
A. Install labeling and pipe markers on equipment and piping according to requirements in
NFPA 13 and NFPA 14.
A. Perform the following field tests and inspections and prepare test reports:
1. Leak Test: After installation, charge system and test for leaks. Repair leaks and
retest until no leaks exist.
2. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
3. Energize circuits to electrical equipment and devices.
4. Flush, test, and inspect sprinkler systems according to NFPA 13, "Systems
Acceptance" Chapter.
5. Flush, test, and inspect standpipe systems according to NFPA 14, "System
Acceptance" Chapter.
6. Coordinate with fire alarm tests. Operate as required.
7. Verify that equipment hose threads are same as local fire department equipment.
B. Report test results promptly and in writing to the Architect and Engineer.
B. The piping shall be tested for line, gradient and water tightness. Furnish all
C. Labor and necessary testing instruments such as gauges. as directed by the Engineer.
A minimum of 2 nos. identical pressure gauges shall be installed at extremities of the
piping circuit to be tested.
D. Fill the piping with clean fresh water, leaving all high points open to allow for purging of
air. Allow a soaking period of at least 24 hours for cement lined pipes.
E. Pressure test the system using manual pumps in increments of 25 percent of the test
pressure. Allow a standing period of 10 minutes after each pressure increment.
Pressure testing using motor driven pump is not permitted.
F. Do not over pressurise the system under any circumstance. If the test pressure is close
to the maximum permissible working pressure of any of the system components, install
calibrated pressure relief valves in the tested circuit.
G. Prior to testing keep all valves and control devices in open position. After completion of
pressure test, close each valve one at a time starting from the pressure release end, so
as to ensure tightness of the valve.
H. The piping shall be hydrostatically tested to a pressure of 200psi (1380 Kpa) or 50psi
(350 Kpa) above the system working pressure, whichever is greater. The pressure shall
be maintained for at least 2 hours. Allow for pressure fluctuations due to ambient
temperature variations. Record the circuit temperature along with the pressure readings.
I. Check for leaks by swabbing with a dry tissue. Drop in pressure to the order of 10 Kpa
per hour, but without any visible leaks, shall be considered as acceptable.
1. Do not subject sprinklers to the test pressure.
2. Test the piping in segments during the progress of the work. Maintain an official
log book for recording the tests carried out on sections of piping, including test
pressure, date of test and approval signature of Engineer's representative
witnessing the test.
A. Drain the complete piping after completion of all tests and flush with fresh water
intended for fire protection services. Do not leave any segment of the piping partially
filled with water at any time, to prevent the occurrence of internal corrosion.
B. Leave all air release outlets open to purge the air in the system and fill the system
gradually using the manual pump.
3.17 PROTECTION
A. Give the following protective coatings / wrappings to piping, on completion of the works.
All piping above louvered ceilings shall be painted red as further described in
architectural finish schedule.
B. Remove and replace sprinklers with paint other than factory finish.
3.20 DEMONSTRATION
B. KFD / CD Compliance: Comply to latest KFD / CD regulations and requirements, and obtain
approval from them
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 DEFINITIONS
1.05 SUBMITTALS
B. Shop Drawings:
1. Include plans, elevations, sections, details, and attachments to other work.
Indicate dimensions, weights, loads, required clearances, method of field
assembly, components, and location and size of each field connection.
2. Wiring Diagrams: Power, signal, and control wiring.
3. Design Calculations: For amount of foam concentrate required for each hazard
area.
4. Plans: Show the following:
a. Foam-solution proportioning tanks and devices, piping, discharge devices,
monitoring and alarm devices, and accessories.
b. Method of attaching hangers to building structure.
c. Fire alarm panel.
d. Equipment and furnishings.
C. Permit-Approved Drawings: Working plans, prepared according to NFPA 16, that have
been approved by authorities having jurisdiction. Include design calculations.
D. Welding certificates.
G. Operation and Maintenance Data: For foam fire extinguishing to include in emergency,
operation, and maintenance manuals. In addition to items specified in Division 01
Section "Operation and Maintenance Data," include the following:
1. Valves and specialties.
2. Proportioning tanks and proportioning devices.
3. Foam concentrate.
4. Discharge devices. Include flow characteristics.
KEO/19-3262-0000 21 1339/2 Foam Water Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
5. Monitoring and alarm devices.
A. Welding: Qualify processes and operators according to ASME Boiler and Pressure
Vessel Code: Section IX.
C. FMG Compliance: Provide components that are FMG approved and that are listed in
FMG's "Fire Protection Approval Guide."
1.07 WARRANTY
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
1. Discharge Devices: Not less than 20 percent of amount of each type installed.
2. Foam Concentrate: Not less than 20 percent of amount installed.
PART 2 - PRODUCTS
B. The product or manufacturers listed are included for the purpose of establishing
minimum quality standards. Products of equal quality or better might be considered if
produced by a specialized manufacturer whose products are equal in every respect and
have been in similar service for not less than five years. The products must also have a
local distributor and must be backed with a professional service centre. The decision of
acceptability shall rest with the Engineer’s representative.
A. Steel Pipe: ASTM A 53/A 53M, ASTM A 135, ASTM A 106, or ASTM A 795, Type E or
S, Grade A or B, Schedule 40, with factory- or field-formed threaded ends.
1. Cast-Iron Threaded Flanges: ASME B16.1.
2. Malleable-Iron Threaded Fittings: ASME B16.3.
3. Gray-Iron Threaded Fittings: ASME B16.4.
4. Butt-Weld Fittings: ASTM A 234/A 234M, Grade WPB, Schedule 40, carbon-
steel butt-weld fittings.
5. Steel Threaded Pipe Nipples: ASTM A 733, made of ASTM A 53/A 53M or
ASTM A 106, Schedule 40, seamless steel pipe. Include ends matching joining
method.
6. Steel Threaded Couplings: ASTM A 865.
B. Stainless Steel: ASTM A 312/A 312M, Schedule 40, with factory-formed threaded or
beveled ends; ASTM A 376/A 376M for seamless pipe; or ASTM A 213/A 213M,
ASTM A 249/A 249M, and ASTM A 269 for seamless and welded tubing.
1. Class 150 Threaded Fittings: ASME B16.3 and MSS SP 114.
2. Butt-Weld Fittings: ASTM A 403/A 403M.
3. Flanges, Forged Fittings and Flanges, and Socket-Weld Fittings:
ASTM A 182/A 182M.
4. Bar Stock and Compression Fittings: ASTM A 276 and ASTM A 479/A 479M.
C. Red Brass Pipe: ASTM B 43, Schedule 40, with factory- or field-formed threaded ends.
1. Threaded Flanges and Fittings: ASTM B 584.
D. Refer to Division 21 Section "Common Work Results for Fire Suppression" for basic
joining materials.
2.03 VALVES
A. Ball Valves: Bronze body with threaded or flanged ends. Comply with UL 1091, except
with stainless-steel ball instead of disc.
2.04 SPECIALTIES
C. Proportioning Controller: Venturi type complying with UL 162 and of capacity to match
design at minimum and maximum flow.
D. Concentrate Control Valve: Water-operated ball or deluge valve designed to open with
flow through the proportioning controller.
F. Provide devices that comply with NFPA 16, are compatible with the foam concentrate,
and are designed to be drained and cleaned.
A. Description: AFFF liquid concentrate, complying with NFPA 11 and UL 162, for making
foam-water fire-extinguishing foam solution.
A. Description: Comply with UL 393, with 3-1/2-inch- (90-mm-) minimum diameter dial, 0-
to 300-psig (0- to 2070-kPa) dial range, and caption "WATER" or "CONCENTRATE" on
dial face.
D. Spray Nozzles: Foam-water spray nozzles including foam generator and distributing
deflector complying with UL 162 and designed to distribute foam or water in the absence
of foam solution in a special pattern peculiar to a particular head.
A. Valve Supervisory Switches: UL 753, electrical, single pole, double throw, with normally
closed contacts. Include design that signals controlled valve is in other than fully open
position.
A. Description: UL listed or FMG approved, low voltage, and surface mounting. Alarm and
monitoring devices are specified in Division 28 Section "Fire Detection and Alarm."
PART 3 - EXECUTION
A. Flanged pipe and fittings and flanged joints may be used to connect to specialties and
accessories and where required for maintenance.
B. AFFF-Concentrate Piping: Steel pipe, malleable iron threaded fittings, and threaded
joints.
B. Refer to Division 21 Section "Common Work Results for Fire Suppression " for basic
pipe installation and joint construction.
D. Install pipe and fittings, valves, and discharge devices according to requirements listed
in NFPA 16, "Installation of Deluge Foam-Water Sprinkler and Foam-Water Spray
Systems."
1. Support piping using supports and methods according to NFPA 13.
2. Install seismic restraints for proportioning tanks and piping systems.
3. Install monitoring and alarm devices according to NFPA 16 and NFPA 72.
3.04 CONNECTIONS
C. Provide concentrate control, maintenance service, and drain valves with piping to permit
maintenance of the foam concentrate with continuous sprinkler system service.
3.05 LABELING
A. Fill proportioning tanks with foam concentrate after field quality-control testing is
complete and satisfactory results have been achieved.
B. Comply with operating instructions and procedures in NFPA 16, "Acceptance Tests"
Chapter. Include the following tests and inspections to demonstrate compliance with
requirements:
1. Check mechanical items.
2. Inspect equipment and fire-extinguishing foam concentrate, and check mountings
for adequate anchoring to substrate.
3. Check electrical systems.
4. Flush piping.
5. Perform acceptance test.
6. Perform pressure test.
7. Perform operating test.
8. Perform discharge test.
9. Correct malfunctioning equipment, then retest to demonstrate compliance.
Replace equipment that cannot be satisfactorily corrected or does not perform as
specified and indicated, then retest to demonstrate compliance. Repeat
procedure until satisfactory results are obtained.
C. Report test results promptly and in writing to the Architect and Engineer.
D. Perform the following field tests and inspections and prepare test reports:
1. After installing foam fire-extinguishing piping system and after electrical circuitry
has been energized, test for compliance with requirements.
2. Perform each electrical test and visual and mechanical inspection stated in
NETA ATS, "Inspection and Test Procedures" and "System Function Tests."
Certify compliance with test parameters.
3. Leak Test: After installation, charge system and test for leaks. Repair leaks and
retest until no leaks exist.
4. Operational Test: After electrical circuitry has been energized, start systems to
confirm proper unit operation.
5. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 DEFINITIONS
C. Performance Requirements: Discharge IG-541 within 120 seconds and maintains 38.5
percent concentration by volume at 21 deg C for 10 minute holding time in hazard
areas.
1. IG-541 concentration in hazard areas greater than 40 percent immediately after
discharge or less than 32 percent throughout holding time will not be accepted.
2. System Capabilities: Minimum 15-MPa calculated working pressure upstream
from orifice union, minimum 6895 kPa calculated working pressure downstream
from orifice union, and 15 MPa initial charging pressure.
E. Verified Detection: Devices located in single zone. Sound alarm on activating single-
detection device, and discharge extinguishing agent on actuating second-detection
device.
I. Operating abort switches will delay extinguishing-agent discharge while being activated,
and switches must be reset to prevent agent discharge. Release of hand pressure on
the switch will cause agent discharge if the time delay has expired.
K. Low-Agent Pressure Switch: Initiate trouble alarm if sensing less than set pressure.
1.05 SUBMITTALS
1.07 WARRANTY
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents. Deliver extra materials to Owner.
1. Detection Devices: Not less than 20 percent of amount of each type installed.
2. Container Valves: Not less than 10 percent of amount of each size and type
installed.
3. Nozzles: Not less than 20 percent of amount of each type installed.
PART 2 - PRODUCTS
B. The product or manufacturers listed are included for the purpose of establishing
minimum quality standards. Products of equal quality or better might be considered if
produced by a specialized manufacturer whose products are equal in every respect and
have been in similar service for not less than five years. The products must also have a
local distributor and must be backed with a professional service centre. The decision of
acceptability shall rest with the Engineer’s representative.
C. Products to be provided shall be from the manufacturer approved from KFSD & civil
Defense.
A. Refer to Part 3 piping applications Article retained for applications of pipe, tube, fitting,
and joining materials.
B. Piping, Valves, and Discharge Nozzles: Comply with types and standards listed in
NFPA 2001, Section "Distribution," for charging pressure of system.
A. Steel Pipe: ASTM A 53/A 53M, Type S, Grade B or ASTM A 106, Grade B;
Schedule 40, seamless steel pipe.
1. Threaded Fittings:
a. Malleable-Iron Fittings: ASME B16.3, Class 300.
b. Flanges and Flanged Fittings: ASME B16.5, Class 300, unless Class 600
is indicated.
2. Forged-Steel Welding Fittings: ASME B16.11, Class 3000, socket pattern.
3. Grooved-End Fittings: FMG approved and NRTL listed, ASTM A 47/A 47M
malleable iron or ASTM A 536 ductile iron, with dimensions matching steel pipe
and ends factory grooved according to AWWA C606.
B. Pipe-Flange Gasket Materials: Suitable for chemical and thermal conditions of piping
system contents.
1. ASME B16.21, non-metallic, flat, asbestos-free, 3.2 mm maximum thickness,
unless thickness or specific material is indicated.
D. Brazing Filler Metals: AWS A5.8, BCuP Series, copper-phosphorus alloys for general-
duty brazing.
KEO/19-3262-0000 21 2200/5 Clean Agent Fire Extinguishing System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
E. Welding Filler Metals: Comply with AWS D10.12 for welding materials appropriate for
wall thickness and chemical analysis of steel pipe being welded.
2.04 VALVES
B. Container Valves: With rupture disc or solenoid and manual-release lever, capable of
immediate and total agent discharge and suitable for intended flow capacity.
D. Valves in Manifolds: Check valve; installed to prevent loss of extinguishing agent when
container is removed from manifold.
A. Description: Steel tanks complying with ASME Boiler and Pressure Vessel Code:
Section VIII, for unfired pressure vessels. Include minimum working-pressure rating that
matches system charging pressure, valve, pressure switch, and pressure gage.
1. Finish: Manufacturer's standard color, enamel or epoxy paint.
2. Manifold: Fabricate with valves, pressure switches, and connections for multiple
storage containers, as indicated.
3. Manifold: Fabricate with valves, pressure switches, selector switch, and
connections for main- and reserve-supply banks of multiple storage containers.
4. Storage-Tank Brackets: Factory- or field-fabricated retaining brackets consisting
of steel straps and channels; suitable for container support, maintenance, and
tank refilling or replacement.
A. Description: NRTL-listed device with minimum 15 MPa pressure rating, to control flow
and reduce pressure of IG-541 gas in piping.
1. DN 50 and Smaller: Piping assembly with orifice sized for system design
requirements.
2. DN 65 and Larger: Piping assembly with nipple sized for system design
requirements.
B. Power Requirements: 240-V ac; with electrical contacts for connection to system
components and fire alarm system, and transformer or rectifier as needed to produce
power at voltage required for accessories and alarm devices.
F. Annunciator Panel: Graphic type showing protected hazard-area plans and locations of
detectors, abort, EPO, and manual stations. Include lamps to indicate device-initiating
alarm, electrical contacts for connection to control panel, and stainless-steel or
aluminum enclosure.
A. Description: Comply with NFPA 2001 and NFPA 72, and include the following types:
1. Ionization Detectors: Comply with UL 268, dual-chamber type, having sampling
and referencing chambers, with smoke-sensing element.
2. Photoelectric Detectors: Comply with UL 268, consisting of LED light source and
silicon photodiode receiving element.
3. Remote Air-Sampling Detector System: Includes air-sampling pipe network, a
laser-based photoelectric detector, a sample transport fan, and a control unit.
4. Comply with UL 268 and NRTL listed, operating at 24-V dc, nominal.
5. Pipe Network: CPVC tubing connects control unit with calibrated sampling holes.
6. Smoke Detector: Particle-counting type with continuous laser beam. Sensitivity
adjustable to a minimum of four preset values.
7. Sample Transport Fan: Centrifugal type, creating a minimum static pressure of
12.5 Pa at all sampling ports.
KEO/19-3262-0000 21 2200/7 Clean Agent Fire Extinguishing System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
8. Control Unit: Multi-zone unit as indicated on Drawings. Provides same system
power supply, supervision, and alarm features as specified for the control panel
plus separate trouble indication for airflow and detector problems.
9. Signals to the Central Fire Alarm Control Panel: Any type of local system trouble
is reported to the central fire alarm control panel as a composite "trouble" signal.
Alarms on each system zone are individually reported to the central fire alarm
control panel as separately identified zones.
B. Manual Release: "MANUAL RELEASE" caption, and red finish. Unit can manually
discharge extinguishing agent with operating device that remains engaged until
unlocked.
1.12 SWITCHES
A. Description: FMG approved or NRTL listed, where available, 240-V ac or low voltage
compatible with controls. Include contacts for connection to control panel.
1. Low-Agent Pressure Switches: Pneumatic operation.
2. Power Transfer Switches: Key-operation selector, for transfer of release circuit
signal from main supply to reserve supply.
3. Door Closers: Magnetic retaining and release device or electrical interlock to
cause the door operator to drive the door closed.
A. Description: FMG approved or NRTL listed, low voltage, and surface mounting, unless
otherwise indicated.
C. Horns: 90 to 94 dBA.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Flanged pipe and fittings and flanged joints may be used to connect to specialties and
accessories and where required for maintenance.
D. DN 50 and Smaller: Schedule 40, steel pipe; malleable-iron threaded fittings; and
threaded joints.
E. DN 65 and DN 80: Schedule 40, steel pipe; steel, grooved-end fittings; steel, keyed
couplings; and grooved joints.
F. DN 100 and Larger: Schedule 40, steel pipe; steel, grooved-end fittings; steel, keyed
couplings; and grooved joints.
A. Install clean-agent extinguishing piping and other components level and plumb and
according to manufacturers' written instructions.
B. Refer to Division 21 Section "Common Work Results For Fire Suppression" for basic
pipe installation and joint construction.
C. Grooved Piping Joints: Groove pipe ends according to AWWA C606 dimensions.
Assemble grooved-end steel pipe and steel, grooved-end fittings with steel, keyed
couplings and lubricant according to manufacturer's written instructions.
3.04 CONNECTIONS
C. Connect electrical devices to control panel and to building's fire alarm system. Electrical
power, wiring, and devices are specified in Division 28 Section "Fire Detection and
Alarm."
3.05 LABELING
B. Install signs at entry doors for protected areas to warn occupants that they are entering
a room protected with a clean-agent fire extinguishing system.
C. Install signs at entry doors to advise persons outside the room the meaning of the
horn(s), bell(s), and strobe light(s) outside the protected space.
A. Comply with operating instructions and procedures of NFPA 2001, Section "Approval of
Installations." Include the following tests and inspections to demonstrate compliance
with requirements:
1. Check mechanical items.
2. Inspect extinguishing-agent containers and extinguishing agent, and check
mountings for adequate anchoring to substrate.
3. Check electrical systems.
4. Check enclosure integrity. Comply with NFPA 2001, Section "Enclosure
Inspection," and Appendix C, "Enclosure Integrity Procedure."
5. Perform functional pre-discharge test.
6. Perform system functional operational test including, EPO, abort, and manual
release.
7. Check remote monitoring operations.
8. Check control-panel primary power source.
9. Perform "puff" test on piping system, using nitrogen.
D. Perform the following field tests and inspections and prepare test reports:
1. After installing clean-agent extinguishing piping system and after electrical
circuitry has been energized, test for compliance with requirements.
2. Perform each electrical test and visual and mechanical inspection stated in
NETA ATS, Sections "Inspection and Test Procedures" and "System Function
Tests." Certify compliance with test parameters.
3. Leak Test: After installation, charge system and test for leaks. Repair leaks and
retest until no leaks exist.
4. Operational Test: After electrical circuitry has been energized, start units to
confirm proper motor rotation and unit operation. Remove malfunctioning units,
replace with new units, and retest.
5. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
6. The contractor shall be responsible for sealing and securing the protected
spaces against loss and or leakage during the 10 minutes “Hold Period”.
3.07 CLEANING
A. Each pipe section shall be cleaned internally after preparation and before assembly by
means of swabbing, using a suitable nonflammable cleaner. Pipe network shall be free
of particulate matter and oil residue before installing nozzles or discharge devices.
A. Preparation:
1. Verify that piping system installation is completed and cleaned.
2. Check for complete enclosure integrity.
3. Check operation of ventilation and exhaust systems.
B. Filling Procedures:
1. Fill extinguishing-agent containers with extinguishing agent and pressurize to the
indicated charging pressure.
2. Install filled extinguishing-agent containers.
3. Energize circuits.
KEO/19-3262-0000 21 2200/11 Clean Agent Fire Extinguishing System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4. Adjust operating controls.
3.09 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes electric and diesel driven, split-case, vertical turbine, end section
and jockey pumps centrifugal fire pumps and the following:
1. Fire-pump controllers and automatic transfer switches.
2. Fire-pump accessories and specialties.
3. Pressure-maintenance pumps, controllers, accessories, and specialties.
4. Alarm panels.
5. Flow meter systems.
A. Pump Equipment, Accessory, Specialty, and Piping Pressure Rating: 175 psi (1200 -
kPa) maximum working-pressure rating, unless otherwise indicated.
1.03 SUBMITTALS
A. Product Data: For each type of product indicated include rated capacities, certified
pump performance curves with each selection point indicated, operating characteristics,
and furnished accessories and specialties for each fire pump and pressure-maintenance
pump.
B. Shop Drawings: For fire pumps and drivers, fire-pump controllers, fire-pump
accessories and specialties, pressure-maintenance pumps, pressure-maintenance-
pump controllers, and pressure-maintenance-pump accessories and specialties.
Include plans, elevations, sections, details, and attachments to other work.
1. For installed products indicated to comply with design loads, include structural
analysis data signed and sealed by the qualified professional engineer
responsible for their preparation.
2. Wiring Diagrams: Power, signal, and control wiring.
D. Product Certificates: For each type of fire pump and fire-pump controller, signed by
product manufacturer.
G. Operation and Maintenance Data: For fire pumps and drivers, pressure-maintenance
pumps, controllers, accessories and specialties, alarm panels, and flow meter systems
to include in emergency, operation, and maintenance manuals.
B. Product Options: Drawings indicate size, profiles, and dimensional requirements of fire
pumps, pressure-maintenance pumps, and controllers and are based on specific
systems indicated. Refer to Division 01 Section "Product Requirements."
E. Comply with NFPA 20, "Stationary Pumps for Fire Protection," for fire pumps, drivers,
controllers, accessories, and their installation.
A. Retain shipping flange protective covers and protective coatings during storage.
1.06 WARRANTY
A. Provide complete spare parts and maintenance equipment for two (2) years
maintenance of all the equipment furnished under this section. Spare parts in a
location designated by the Engineer or the Employer.
B. All spare parts and maintenance equipment shall be provided in original packing,
clearly identified and labelled. Provide complete schedules of spare parts and
maintenance equipment clearly cross-referenced with the “Record Drawings” and
maintenance instructions and manuals.
D. Spare parts and maintenance equipment provided shall, as a minimum, equal the
items used during the two (2) years maintenance period. The Contractor shall
carefully log all spare parts utilized during maintenance period.
E. Provide spare parts and maintenance equipment for all pumps, control panel etc.
requiring maintenance and replacement.
F. Provide two new complete sets of tools for the proper operation, routine maintenance
and adjustment of all components and equipment.
1.08 COORDINATION
PART 2 - PRODUCTS
2.02 FIRE PUMP (Horizontal Split Case) (FM, UL, approved by AHJ)
A. Type: Single stage, non-self-priming, long-coupled, centrifugal volute pump with axial
suction port, radial discharge port and horizontal shaft. The pump shall be of back pull-
KEO/19-3262-0000 21 3000/3 Fire Pumps and Controllers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
out design that enables the removal and dismantling of the motor, couplings, bearing
bracket and impeller without disturbing the pump housing and pipework. The pump
speed shall not exceed 2900 rpm.
B. Materials of construction:
1. Impeller Bronze.
2. Shaft Stainless steel.
3. Coupling Guard Stainless steel.
4. Casing Cast iron.
5. Bearing Bracket Cast iron
6. Case wearing ring Bronze.
7. Seal Mechanical.
8. O Ring EPDM.
C. Capacity: See schedules on drawings for nominal flow and pressure ratings. Pumps
shall have name-plate stating these parameters, permanently attached to the casing.
E. Motor power rating: See schedules on drawings for motor power ratings. The motor
shall be rated for continuous operation at 150 % of the pump nominal flow. Additional
capacity available from motor service factors exceeding unity may be used in working
out the motor power ratings in limiting cases. The motor acceleration period (star to
delta change over) shall not exceed 10 seconds.
B. Materials of construction:
1. Impeller - Bronze
2. Shaft - Stainless steel
3. Casing - Cast iron
4. Case wearing ring - Bronze
5. Seal - Mechanical
6. Base plate - Cast iron / fabricated steel
D. Working pressure: Pump casing and flanges shall be suitable for a working water
pressure of 1379 Kpa (200 psig) working water pressure at 121 deg.C (250 deg.F)
E. Capacity: See schedules on drawings for nominal flow and pressure ratings.
Pumps shall have name plates stating these parameters, permanently attached to
the casing.
KEO/19-3262-0000 21 3000/4 Fire Pumps and Controllers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
F. Electrical motor: Refer to and comply with the requirements of Section 15245.
Type and construction shall be as follows:
1. Type - Squirrel cage induction, Delta Wound.
2. Enclosure - TEFC (IP 55).
3. Service factor - 1.0.
4. Power factor - 0.85 Minimum at full load
5. Insulation - Class F
6. Temperature rise - Class B
7. Electrical supply - 415 v / 3 ph / 50 Hz.
Motor power rating: See schedules on drawings for motor power ratings. The motor
shall be rated for continuous operation at 150% of the pump nominal flow. Additional
capacity available from motor service factors exceeding unity may be used in working
out the motor power ratings in limiting cases. the motor acceleration period (star to delta
change over) shall not exceed 10 seconds
A. The controller shall be of the combined manual and automatic type suitable for star
(Wye) - delta starting at 415 v / 3 ph / 50 Hz supply. Refer to schedules on drawings for
power ratings. The panel components / functions shall be as listed below.
1. Mains isolator switch (4 pole) and circuit breaker combination, mechanically
interlocked to operate with a single, flange mounted, external handle. The
interlocking shall be such that the circuit breaker (with minimum 22 kAmps
rupturing capacity) will engage or break the load current. Both of the above shall
be suitable for padlocking in ON or OFF position and shall be interlocked with the
panel door; restricting access to the controller with the switch in `ON' position,
except by a hidden tool operator defeater. Provide external emergency release
for the circuit breaker.
2. Audio visual earth leakage alarm
3. Power on (supply healthy) indicator wired through normally closed contacts of the
power available relays to give true indication. Loss of power in any one phase
shall cause the light to go off.
4. Control circuit healthy indicator.
5. Pump on demand indicator.
6. Pump run indicator.
7. Manual, pump start and stop push buttons.
8. Emergency start lever with latch.
9. Adjustable star to delta change over timer (consult motor manufacturer for
change over timing.)
10. Adjustable, 10-300 psi, combination pressure gauge switch, mounted on the
enclosure flange. Extend piping to outside of the panel with union. Pressure
switch shall be wired for automatic start only.
11. Starter contactor with auxiliary relays.
12. Fused control power circuit, with voltage not exceeding 240 v / 1 ph / 50 Hz. Use
transformers where appropriate.
13. Terminal block for interlocking wiring.
14. Earthing bar for equipotential bonding.
15. Set of terminals / relays with volt free contacts for connecting to building
automation system and remote alarm panel
A. Description: Factory-assembled and -wired remote panel complying with UL 508 and
requirements in NFPA 20. Include audible and visible alarms matching controller type.
1. Enclosure: NEMA 250, Type 2, remote wall-mounting type.
a. Finish: Manufacturer's standard red paint applied to factory-assembled
and -tested unit before shipping.
2. Features: Include manufacturer's standard features and the following:
a. Motor-operating condition.
b. Loss-of-line power.
c. Phase reversal.
d. Low-water alarm.
A. Description: Fire-pump flow meter system that indicates flow to not less than 175
percent of fire-pump rated capacity. Include sensor of size to match pipe, tubing, flow
meter, and fittings.
1. Pressure Rating: 1200-kPa minimum.
2. Sensor: Venturi, annubar probe, or orifice plate, unless otherwise indicated.
3. Flow meter: Compatible with flow sensor with dial not less than 115 mm in
diameter or manufacturer's equivalent size.
4. Permanently Mounted Flow meter: Suitable for wall mounting with copper tubing
to connect to flow sensor.
5. Portable Flow meter: With two 3.7-m hoses, in carrying case.
2.010 GROUT
A. Test and inspect fire pumps with their controllers according to NFPA 20 for certified
shop tests.
A. EXECUTION
2.011 EXAMINATION
C. Proceed with installation only after unsatisfactory conditions have been corrected.
2.013 INSTALLATION
A. Install and align fire pump, pressure-maintenance pump, and controller according to
NFPA 20.
B. Install pumps and controllers to provide access for periodic maintenance including
removal of motors, impellers, couplings, and accessories.
D. Install suction and discharge piping equal to or greater than diameter of fire-pump
nozzles.
E. Install valves that are same size as piping connecting fire pumps, bypasses, test
headers, and other piping systems.
G. Support pumps and piping separately so weight of piping does not rest on pumps.
H. Refer to Division 21 Section "Common Work Results for Fire Suppression" for basic
piping installation and joint construction.
I. Install piping accessories, hangers and supports, anchors, valves, meters and gages,
and equipment supports.
KEO/19-3262-0000 21 3000/8 Fire Pumps and Controllers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
J. Install flow meters and sensors where indicated. Install flow meter-system components
and make connections according to manufacturer's written instructions.
2.014 ALIGNMENT
A. Align fire-pump and driver shafts after complete unit has been leveled on concrete base,
grout has set, and anchor bolts have been tightened.
B. After alignment is correct, tighten anchor bolts evenly. Fill base plate completely with
grout, with metal blocks and shims or wedges in place. Tighten anchor bolts after grout
has hardened. Check alignment and make required corrections.
D. Align pump and driver shafts for angular and parallel alignment according to HI 1.4 and
to tolerances specified by manufacturer.
2.015 CONNECTIONS
B. Install piping adjacent to pumps and equipment to allow service and maintenance.
C. Connect water supply and discharge piping to fire pumps with flexible connectors.
Connect water supply and discharge piping to pressure-maintenance pumps with
flexible connectors. Refer to Division 21 Section "Water-Based Fire-Suppression
Systems" for flexible connectors.
C. Perform the following field tests and inspections and prepare test reports:
1. Leak Test: After installation, charge system and test for leaks. Repair leaks and
retest until no leaks exist.
2. Final Checks before Start-up: Perform the following preventive-maintenance
operations and checks:
a. Lubricate oil-lubrication-type bearings.
b. Remove grease-lubrication-type bearing covers, flush bearings with
kerosene, and clean thoroughly. Fill with new lubricant according to
manufacturer's written instructions.
c. Disconnect coupling and check electric motor for proper rotation.
Rotation shall match direction of rotation marked on pump casing.
d. Verify that pump is free to rotate by hand. If pump is bound or if it drags
even slightly, do not operate until cause of trouble is determined and
corrected.
3. Starting procedure for pumps is as follows:
a. Prime pump by opening suction valve and closing drains, and prepare
pump for operation.
b. Open sealing-liquid supply valves if pump is so fitted.
c. Start motor.
d. Open discharge valve slowly.
e. Observe leakage from stuffing boxes and adjust sealing-liquid valve for
proper flow to ensure lubrication of packing. Do not tighten gland
immediately, but let packing run in before reducing leakage through
stuffing boxes.
f. Check general mechanical operation of pump and motor.
4. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
2.017 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 DEFINITIONS
A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred
spaces, pipe chases, unheated spaces immediately below roof, spaces above ceilings,
unexcavated spaces, crawlspaces, and tunnels.
D. Concealed, Interior Installations: Concealed from view and protected from physical
contact by building occupants. Examples include above ceilings and in chases.
E. Concealed, Exterior Installations: Concealed from view and protected from weather
conditions and physical contact by building occupants but subject to outdoor ambient
temperatures. Examples include installations within unheated shelters.
1.03 SUBMITTALS
B. Welding certificates.
A. Steel Support Welding: Qualify processes and operators according to AWS D1.1,
"Structural Welding Code--Steel."
B. Steel Pipe Welding: Qualify processes and operators according to ASME Boiler and
Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications."
1. Comply with provisions in ASME B31 Series, "Code for Pressure Piping."
2. Certify that each welder has passed AWS qualification tests for welding
processes involved and that certification is current.
A. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through
shipping, storage, and handling to prevent pipe end damage and to prevent entrance of
dirt, debris, and moisture.
B. Store plastic pipes protected from direct sunlight. Support to prevent sagging and
bending.
1.06 COORDINATION
A. Arrange for pipe spaces, chases, slots, and openings in building structure during
progress of construction, to allow for plumbing installations.
A. Plumbing Systems
Connection/s from the city freshwater mains with meter shall be piped to a
common pressure break water tank at basement for the building. Domestic
transfer set will be used to draw water from the pressure break tank and transfer it
to GRP tank at roof level, Water will be supplied to the users’ points in the upper
floors by booster pump
The capacities of water tanks will vary depending on the number of the occupants
in the building.
Electrical Unit water heaters will be provided in the wet areas (in the ceiling void)
to produce the required hot water.
Connection/s from the city freshwater mains with meter shall be piped to the GRP
tank at roof level, Water will be supplied to the users’ points in all floors by booster
pump
The capacity of the stored water shall be size on two days storage in the elevated
roof tank.
Electrical Unit water heaters will be provided in the wet areas (in the ceiling void)
to produce the required hot water.
Building
No. Name Domestic Requirements
C1 Supermarket Basement:
1-Tanks Volume: 60 m3
2- Pumps: Transfer Pumps
(1W+1S).
Roof:
1- Tanks Volume: 20 m3 (selection
4x4x1.5).
2- Pumps: Booster Pumps (2W +
1S).
C2 Society Center At Roof (Domestic):
1- Tanks Volume Domestic (85m3)
(6.5x10x1.5)
2- Pumps: Booster Pumps (2W +
1S).
C6 Municipality At Roof:
1- Tank: Separate GRP Tank (4
m3) (Selection: 2x2x1.5)
2- Domestic Pumps: Vertical
Booster Inline (1W+1S).
2- Pumps: .
a. Ablution= Booster Pumps (1W
+ 1S)
b. Masjed= Booster Pumps (1W +
1S)
c. Imam Residential= Booster
Pumps (1W + 1S)
C8 Post Office At Roof (Domestic):
1- Tanks Volume Domestic
(5.5m3) (3x2x1.5)
2- Pumps: Booster Pumps (1W +
1S).
C9 Health Care At Roof (Domestic):
1- Tanks Volume Domestic
(20.5m3) (4x4x1.5)
2- Pumps: Booster Pumps (2W +
1S).
Combined vented drainage and wastewater risers will be provided to serve the
buildings
Drainage of all fixtures, drains and equipment are of gravity drainage type. All
stacks will be full size extend through roofs and connected to the city mains
through inspection chambers.
Double sealed cover will be designed for all inspection chambers
3. Storm Drainage System
All roof drains and area drains will be collected through a gravity storm water
drainage system and free discharged to grade levels.
PART 2 - PRODUCTS
A. Refer to individual Division 22 piping Sections for pipe, tube, and fitting materials and
joining methods.
B. Pipe Threads: ASME B1.20.1 for factory-threaded pipe and pipe fittings.
A. Refer to individual Division 22 piping Sections for special joining materials not listed
below.
B. Pipe-Flange Gasket Materials: Suitable for chemical and thermal conditions of piping
system contents.
1. ASME B16.21, nonmetallic, flat, asbestos-free, 1/8-inch (3.2-mm) maximum
thickness unless thickness or specific material is indicated.
a. Full-Face Type: For flat-face, Class 125, cast-iron and cast-bronze
flanges.
b. Narrow-Face Type: For raised-face, Class 250, cast-iron and steel
flanges.
2. AWWA C110, rubber, flat face, 1/8 inch (3.2 mm) thick, unless otherwise
indicated; and full-face or ring type, unless otherwise indicated.
C. Flange Bolts and Nuts: ASME B18.2.1, carbon steel, unless otherwise indicated.
D. Plastic, Pipe-Flange Gasket, Bolts, and Nuts: Type and material recommended by
piping system manufacturer, unless otherwise indicated.
E. Solder Filler Metals: ASTM B 32, lead-free alloys. Include water-flushable flux
according to ASTM B 813.
F. Brazing Filler Metals: AWS A5.8, BCuP Series, copper-phosphorus alloys for general-
duty brazing, unless otherwise indicated; and AWS A5.8, BAg1, silver alloy for
refrigerant piping, unless otherwise indicated.
G. Welding Filler Metals: Comply with AWS D10.12 for welding materials appropriate for
wall thickness and chemical analysis of steel pipe being welded.
I. Multilayer (PE & Aluminum): Screw joints, press fitting, composite compression and
clamp as appropriate.
A. AWWA Transition Couplings: Same size as, and with pressure rating at least equal to
and with ends compatible with, piping to be joined.
1. Approved Manufacturers: Subject to approved manufacturers list by PAHW.
2. Underground Piping NPS 1-1/2 (DN 40) and Smaller: Manufactured fitting or
coupling.
3. Underground Piping NPS 2 (DN 50) and Larger: AWWA C219, metal sleeve-
type coupling.
4. Aboveground Pressure Piping: Pipe fitting.
D. Plastic-to-Metal Transition Unions: MSS SP-107, [CPVC] [PVC] [CPVC and PVC] four-
part union. Include brass end, solvent-cement-joint end, rubber O-ring, and union nut.
1. Approved Manufacturers: Subject to approved manufacturers list by PAHW.
A. Description: Combination fitting of copper alloy and ferrous materials with threaded,
solder-joint, plain, or weld-neck end connections that match piping system materials.
G. Dielectric Nipples: Electroplated steel nipple with inert and noncorrosive, thermoplastic
lining; plain, threaded, or grooved ends; and 300-psig (2070-kPa) minimum working
pressure at 225 deg F (107 deg C).
1. Approved Manufacturers: Subject to approved manufacturers list by PAHW.
2.07 SLEEVES
B. Steel Pipe: ASTM A 53, Type E, Grade B, Schedule 40, galvanized, plain ends.
C. Cast Iron: Cast or fabricated "wall pipe" equivalent to ductile-iron pressure pipe, with
plain ends and integral waterstop, unless otherwise indicated.
D. Stack Sleeve Fittings: Manufactured, cast-iron sleeve with integral clamping flange.
Include clamping ring and bolts and nuts for membrane flashing.
1. Underdeck Clamp: Clamping ring with set screws.
E. Molded PVC: Permanent, with nailing flange for attaching to wooden forms.
G. Molded PE: Reusable, PE, tapered-cup shaped, and smooth-outer surface with nailing
flange for attaching to wooden forms.
2.08 ESCUTCHEONS
A. Description: Manufactured wall and ceiling escutcheons and floor plates, with an ID to
closely fit around pipe, tube, and insulation of insulated piping and an OD that
completely covers opening.
E. One-Piece, Stamped-Steel Type: With set screw or spring clips and chrome-plated
finish.
F. Split-Plate, Stamped-Steel Type: With concealed hinge, set screw or spring clips, and
chrome-plated finish.
2.09 GROUT
PART 3 - EXECUTION
B. Drawing plans, schematics, and diagrams indicate general location and arrangement of
piping systems. Indicated locations and arrangements were used to size pipe and
calculate friction loss, expansion, pump sizing, and other design considerations. Install
piping as indicated unless deviations to layout are approved on Coordination Drawings.
D. Install piping indicated to be exposed and piping in equipment rooms and service areas
at right angles or parallel to building walls. Diagonal runs are prohibited unless
specifically indicated otherwise.
E. Install piping above accessible ceilings to allow sufficient space for ceiling panel
removal.
K. Select system components with pressure rating equal to or greater than system
operating pressure.
L. Install escutcheons for penetrations of walls, ceilings, and floors according to the
following:
1. New Piping:
a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep-
pattern type.
b. Chrome-Plated Piping: One-piece, cast-brass type with polished chrome-
plated finish.
KEO/19-3262-0000 22 0500/9 Common Work Results for Plumbing
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
c. Insulated Piping: One-piece, stamped-steel type with spring clips.
d. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-
piece, cast-brass type with polished chrome-plated finish.
e. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-
piece, stamped-steel type.
f. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece or
split-casting, cast-brass type with polished chrome-plated finish.
g. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece,
stamped-steel type or split-plate, stamped-steel type with concealed hinge
and set screw.
h. Bare Piping in Unfinished Service Spaces: One-piece, cast-brass type
with polished chrome-plated finish.
i. Bare Piping in Unfinished Service Spaces: One-piece, stamped-steel
type with concealed or exposed-rivet hinge and set screw or spring clips.
j. Bare Piping in Equipment Rooms: One-piece, cast-brass type.
k. Bare Piping in Equipment Rooms: One-piece, stamped-steel type with set
screw or spring clips.
l. Bare Piping at Floor Penetrations in Equipment Rooms: One-piece, floor-
plate type.
N. Permanent sleeves are not required for holes formed by removable PE sleeves.
O. Install sleeves for pipes passing through concrete and masonry walls and concrete floor
and roof slabs.
P. Install sleeves for pipes passing through concrete and masonry walls, gypsum-board
partitions, and concrete floor and roof slabs.
1. Cut sleeves to length for mounting flush with both surfaces.
a. Exception: Extend sleeves installed in floors of mechanical equipment
areas or other wet areas 2 inches (50 mm) above finished floor level.
Extend cast-iron sleeve fittings below floor slab as required to secure
clamping ring if ring is specified.
2. Install sleeves in new walls and slabs as new walls and slabs are constructed.
3. Install sleeves that are large enough to provide 1/4-inch (6.4-mm) annular clear
space between sleeve and pipe or pipe insulation. Use the following sleeve
materials:
a. PVC/Steel Pipe Sleeves: For pipes smaller than NPS 6 (DN 150).
b. Steel Sheet Sleeves: For pipes NPS 6 (DN 150) and larger, penetrating
gypsum-board partitions.
c. Stack Sleeve Fittings: For pipes penetrating floors with membrane
waterproofing. Secure flashing between clamping flanges. Install section
of cast-iron soil pipe to extend sleeve to 2 inches (50 mm) above finished
floor level. Refer to Division 07 Section "Sheet Metal Flashing and Trim"
for flashing.
1) Seal space outside of sleeve fittings with grout.
4. Except for underground wall penetrations, seal annular space between sleeve
and pipe or pipe insulation, using joint sealants appropriate for size, depth, and
location of joint. Refer to Division 07 Section "Joint Sealants" for materials and
installation.
R. Underground, Exterior-Wall Pipe Penetrations: Install cast-iron "wall pipes" for sleeves.
Seal pipe penetrations using mechanical sleeve seals. Select sleeve size to allow for
1-inch (25-mm) annular clear space between pipe and sleeve for installing mechanical
sleeve seals.
1. Mechanical Sleeve Seal Installation: Select type and number of sealing
elements required for pipe material and size. Position pipe in center of sleeve.
Assemble mechanical sleeve seals and install in annular space between pipe
and sleeve. Tighten bolts against pressure plates that cause sealing elements to
expand and make watertight seal.
S. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and
floors at pipe penetrations. Seal pipe penetrations with firestop materials. Refer to
Division 07 Section "Penetration Firestopping" for materials.
A. Join pipe and fittings according to the following requirements and Division 22 Sections
specifying piping systems.
B. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
C. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before
assembly.
D. Soldered Joints: Apply ASTM B 813, water-flushable flux, unless otherwise indicated, to
tube end. Construct joints according to ASTM B 828 or CDA's "Copper Tube
Handbook," using lead-free solder alloy complying with ASTM B 32.
E. Brazed Joints: Construct joints according to AWS's "Brazing Handbook," "Pipe and
Tube" Chapter, using copper-phosphorus brazing filler metal complying with AWS A5.8.
F. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1.
Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs
and restore full ID. Join pipe fittings and valves as follows:
1. Apply appropriate tape or thread compound to external pipe threads unless dry
seal threading is specified.
G. Welded Joints: Construct joints according to AWS D10.12, using qualified processes
and welding operators according to Part 1 "Quality Assurance" Article.
H. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service
application. Install gasket concentrically positioned. Use suitable lubricants on bolt
threads.
I. Plastic Piping Solvent-Cement Joints: Clean and dry joining surfaces. Join pipe and
fittings according to the following:
1. Comply with ASTM F 402 for safe-handling practice of cleaners, primers, and
solvent cements.
2. ABS Piping: Join according to ASTM D 2235 and ASTM D 2661 Appendixes.
3. CPVC Piping: Join according to ASTM D 2846/D 2846M Appendix.
4. PVC Pressure Piping: Join schedule number ASTM D 1785, PVC pipe and PVC
socket fittings according to ASTM D 2672. Join other-than-schedule-number
PVC pipe and socket fittings according to ASTM D 2855.
5. PVC Nonpressure Piping: Join according to ASTM D 2855.
6. PVC to ABS Nonpressure Transition Fittings: Join according to ASTM D 3138
Appendix.
L. PE Piping Heat-Fusion Joints: Clean and dry joining surfaces by wiping with clean cloth
or paper towels. Join according to ASTM D 2657.
1. Plain-End Pipe and Fittings: Use butt fusion.
2. Plain-End Pipe and Socket Fittings: Use socket fusion.
M. Fiberglass Bonded Joints: Prepare pipe ends and fittings, apply adhesive, and join
according to pipe manufacturer's written instructions.
D. Install equipment to allow right of way for piping installed at required slope.
3.05 PAINTING
B. Damage and Touchup: Repair marred and damaged factory-painted finishes with
materials and procedures to match original factory finish.
B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and
elevation to support and anchor plumbing materials and equipment.
B. Select fastener sizes that will not penetrate members if opposite side will be exposed to
view or will receive finish materials. Tighten connections between members. Install
fasteners without splitting wood members.
3.09 GROUTING
A. Mix and install grout for plumbing equipment base bearing surfaces, pump and other
equipment base plates, and anchors.
F. Place grout on concrete bases and provide smooth bearing surface for equipment.
A. Provide a written monthly report to the employer, detailing the maintenance work
performed, including dates, parts replaced etc.
C. The contractor shall keep permanently on the site sufficient number of operation and
maintenance staff to fulfil the obligation of the contract. Contractor shall provide the
following minimum staff:
1. One engineer for all Services 20% of time.
2. One supervisors 100% of time.
D. Provide all spare parts for replacements made necessary due to wear and tear of
equipment, provide all consumable parts, short life parts, oil, grease, filters, chemicals,
etc. and all tools and maintenance equipment required for proper operation and
complete maintenance of the work.
F. Include for complete routine maintenance and corrective and preventive maintenance
with the requirement of the contract document as follow:
KEO/19-3262-0000 22 0500/14 Common Work Results for Plumbing
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Defect liability / breakdown maintenance, inclusive of replacement parts.
2. Preventive maintenance as scheduled, inclusive of replacement parts and
consumables.
3. Submit the schedule of routine operational and preventive maintenance for all
equipment for the employer’s/engineer approval.
4. Attending to emergencies, which may damage property or endanger lives, even
outside normal working hours.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 COORDINATION
PART 2 - PRODUCTS
A. Comply with requirements in this Section except when stricter requirements are
specified in plumbing equipment schedules or Sections.
A. Duty: Continuous duty at ambient temperature of 40 deg C and at altitude of 3300 feet
(1000 m) above sea level.
G. Bearings: Regreasable, shielded, antifriction ball bearings suitable for radial and thrust
loading.
I. Insulation: Class F.
K. Enclosure Material: Cast iron for motor frame sizes 324T and larger; rolled steel for
motor frame sizes smaller than 324T.
B. Motors Used with Variable Frequency Controllers: Ratings, characteristics, and features
coordinated with and approved by controller manufacturer.
1. Windings: Copper magnet wire with moisture-resistant insulation varnish,
designed and tested to resist transient spikes, high frequencies, and short time
rise pulses produced by pulse-width modulated inverters.
2. Energy- and Premium-Efficient Motors: Class B temperature rise; Class F
insulation.
3. Inverter-Duty Motors: Class F temperature rise; Class H insulation.
4. Thermal Protection: Comply with NEMA MG 1 requirements for thermally
protected motors.
C. Severe-Duty Motors: Comply with IEEE 841, with 1.15 minimum service factor.
A. Motors larger than 1/20 hp shall be one of the following, to suit starting torque and
requirements of specific motor application:
1. Permanent-split capacitor.
KEO/19-3262-0000 22 0513/2 Common Motor Requirements for Plumbing Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Split phase.
3. Capacitor start, inductor run.
4. Capacitor start, capacitor run.
C. Bearings: Pre-lubricated, antifriction ball bearings or sleeve bearings suitable for radial
and thrust loading.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Section Includes:
1. Metal-bellows expansion joints.
2. Rubber expansion joints.
3. Flexible-hose expansion joints.
4. Pipe bends and loops.
5. Alignment guides and anchors.
1.02 DEFINITIONS
A. Compatibility: Products shall be suitable for piping system fluids, materials, working
pressures, and temperatures.
B. Capability: Products shall absorb 200 percent of maximum axial movement between
anchors.
1.04 SUBMITTALS
B. Delegated-Design Submittal: For each anchor and alignment guide indicated to comply
with performance requirements and design criteria, including analysis data signed and
sealed by the qualified professional engineer responsible for their preparation.
1. Design Calculations: Calculate requirements for thermal expansion of piping
systems and for selecting and designing expansion joints, loops, and bends.
C. Welding certificates.
D. Product Certificates: For each type of pipe expansion joint, signed by product
manufacturer.
PART 2 - PRODUCTS
B. Rubber Expansion Joints: ASTM F 1123, fabric-reinforced rubber with external control
rods and complying with FSA's "Technical Handbook: Non-Metallic Expansion Joints
and Flexible Pipe Connectors."
1. Manufacturers: Subject to compliance with requirements, provide products by
one of the following:
2. Arch Type: Single or multiple arches.
3. Spherical Type: Single or multiple spheres.
a. Minimum Pressure and Temperature Ratings for NPS 1-1/2 to NPS 4
(DN 40 to DN 100): 150 psig (1035 kPa) at 220 deg F (104 deg C).
b. Minimum Pressure and Temperature Ratings for NPS 5 and NPS 6
(DN 125 and DN 150): 140 psig (966 kPa) at 200 deg F (93 deg C).
c. Minimum Pressure and Temperature Ratings for NPS 8 to NPS 12
(DN 200 to DN 300): 140 psig (966 kPa) at 180 deg F (82 deg C).
4. Material: EPDM.
5. End Connections: Full-faced, integral, steel flanges with steel retaining rings.
A. Description: Steel, factory fabricated, with bolted two-section outer cylinder and base
for alignment of piping and two-section guiding spider for bolting to pipe.
B. Bolts and Nuts: ASME B18.10 or ASTM A 183, steel, hex head.
D. Mechanical Fasteners: Insert-wedge-type stud with expansion plug anchor for use in
hardened portland cement concrete, and tension and shear capacities appropriate for
application.
1. Stud: Threaded, zinc-coated carbon steel.
2. Expansion Plug: Zinc-coated steel.
3. Washer and Nut: Zinc-coated steel.
E. Chemical Fasteners: Insert-type-stud bonding system anchor for use with hardened
portland cement concrete, and tension and shear capacities appropriate for application.
1. Bonding Material: ASTM C 881, Type IV, Grade 3, 2-component epoxy resin
suitable for surface temperature of hardened concrete where fastener is to be
installed.
2. Stud: ASTM A 307, zinc-coated carbon steel with continuous thread on stud,
unless otherwise indicated.
3. Washer and Nut: Zinc-coated steel.
F. Concrete: Portland cement mix, 3000 psi (20.7 MPa) minimum. Comply with
requirements in Division 03 Section "Cast-in-Place Concrete" for formwork,
reinforcement, and concrete.
PART 3 - EXECUTION
B. Install expansion joints of sizes matching size of piping in which they are installed.
C. Install alignment guides to allow expansion and to avoid end-loading and torsional
stress.
A. Install pipe bends and loops cold-sprung in tension or compression as required to partly
absorb tension or compression produced during anticipated change in temperature.
A. Connect risers and branch connections to mains with at least five pipe fittings, including
tee in main.
B. Connect risers and branch connections to terminal units with at least four pipe fittings,
including tee in riser.
C. Connect mains and branch connections to terminal units with at least four pipe fittings,
including tee in main.
B. Fabricate and install steel anchors by welding steel shapes, plates, and bars to piping
and to structure. Comply with ASME B31.9 and AWS D1.1.
E. Use grout to form flat bearing surfaces for expansion fittings, guides, and anchors
installed on or in concrete.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Section Includes:
1. Thermometers.
2. Gages.
3. Test plugs.
4. Water Meter
B. Related Sections:
1. Division 22 Section "Facility Water Distribution Piping" for domestic and fire-
protection water service meters outside the building.
2. Division 22 Section "Domestic Water Piping" for domestic and fire-protection
water service meters inside the building.
3. Division 23 Section "Liquefied Petroleum Gas" for gas meters.
1.02 DEFINITIONS
1.03 SUBMITTALS
A. Product Data and Sample: For each type of product indicated; include performance
curves.
C. Product Certificates: For each type of thermometer and gage, signed by product
manufacturer.
PART 2 - PRODUCTS
E. Window: Glass.
F. Connector: Adjustable type, 180 degrees in vertical plane, 360 degrees in horizontal
plane, with locking device.
G. Stem: Copper-plated steel, aluminum, or brass for thermowell installation and of length
to suit installation.
C. Tube: Red or blue reading, mercury or organic-liquid filled, with magnifying lens.
F. Connector: Adjustable type, 180 degrees in vertical plane, 360 degrees in horizontal
plane, with locking device.
G. Window: Glass.
I. Connector: Adjustable type, 180 degrees in vertical plane, 360 degrees in horizontal
plane, with locking device.
B. Case: Dry type, drawn steel or cast aluminum4-1/2-inch (114-mm) diameter with holes
for panel mounting.
G. Window: Glass.
G. Window: Glass.
2.06 THERMOWELLS
B. Description: Pressure-tight, socket-type metal fitting made for insertion into piping and
of type, diameter, and length required to hold thermometer.
D. Pressure-Gage Fittings:
1. Subject to approved manufacturers list by PAHW
2. Valves: NPS 1/4 (DN 8) brass or stainless-steel needle type.
3. Snubbers: ASME B40.5, NPS 1/4 (DN 8) brass bushing with corrosion-resistant,
porous-metal disc of material suitable for system fluid and working pressure.
C. Minimum Pressure and Temperature Rating: 500 psig at 200 deg F (3450 kPa at 93
deg C.
E. Test Kit: Furnish one test kit(s) containing one pressure gage and adaptor, [one] [two]
thermometer(s), and carrying case. Pressure gage, adapter probes, and thermometer
sensing elements shall be of diameter to fit test plugs and of length to project into piping.
1. Pressure Gage: Small bourdon-tube insertion type with [2- to 3-inch- (51- to 76-
mm-)] diameter dial and probe. Dial range shall be [0 to 200 psig (0 to 1380
kPa)].
2. Low-Range Thermometer: Small bimetallic insertion type with [1- to 2-inch- (25-
to 51-mm-)] <Insert other> diameter dial and tapered-end sensing element. Dial
ranges shall be 25 to 125 deg F (minus 4 to plus 52 deg C).
3. High-Range Thermometer: Small bimetallic insertion type with [1- to 2-inch- (25-
to 51-mm-)] diameter dial and tapered-end sensing element. Dial ranges shall be
[0 to 220 deg F (minus 18 to plus 104 deg C)].
4. Carrying case shall have formed instrument padding.
C. Meters shall be Automatic Meter Reading (AMR) enabled while retaining the facility to
provide visual readings at an integral LCD display.
E. Operating Specification:
1. Max. water temperature + 60 deg.C
2. Working pressure 16 bar
3. Maximum pressure rating 20 bar
4. Pressure loss at qs <1 bar
F. Display:
1. LCD max. 99,999 m3
2. LCD min. 1 m3 (1.000 litre)
3. Meter reading LCD display + remote via
AMR.
G. Environmental:
1. Ingress protection IP68 / EN 60529
2. Storage temp. - 10 to + 60 deg.C
3. Ambient temp. range -10 to + 85 deg.C
4. Battery life > 10 years.
I. Approvals:
1. Meters shall be approved by an internationally recognized authority for use
with potable water.
2. Meters shall be manufactured under accredited BS EN ISO 9001 quality
conditions
3. Meters shall be manufactured under accredited BS EN ISO 14001
environmental conditions.
PART 3 - EXECUTION
3.03 INSTALLATIONS
B. Install remote-mounting dial thermometers on panel, with tubing connecting panel and
thermometer bulb supported to prevent kinks. Use minimum tubing length.
C. Install direct-mounting pressure gages in piping tees with pressure gage located on pipe
at most readable position.
E. Install needle-valve and snubber fitting in piping for each pressure gage.
H. Install thermometers and gages adjacent to machines and equipment to allow service
and maintenance for thermometers, gages, machines, and equipment.
I. Install water meters as indicated on the drawings and connect to BMS for automatic
billing issuance.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 DEFINITIONS
1.03 SUBMITTALS
A. Product Data and Sample: For each type of valve indicated. Include body, seating, and
trim materials; valve design; pressure and temperature classifications; end connections;
arrangement; dimensions; and required clearances. Include list indicating valve and its
application. Include rated capacities; shipping, installed, and operating weights;
furnished specialties; and accessories.
A. ASME Compliance for Ferrous Valves: ASME B16.10 and ASME B16.34 for dimension
and design criteria.
C. Use sling to handle large valves; rig sling to avoid damage to exposed parts. Do not
use handwheels or stems as lifting or rigging points.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
B. Bronze Valves: NPS 2 (DN 50) and smaller with threaded ends, unless otherwise
indicated.
C. Ferrous Valves: NPS 2-1/2 (DN 65) and larger with flanged ends, unless otherwise
indicated.
D. Valve Pressure and Temperature Ratings: Not less than indicated and as required for
system pressures and temperatures.
F. Valve Actuators:
1. Gear Drive: For quarter-turn valves NPS 8 (DN 200) and larger.
2. Handwheel: For valves other than quarter-turn types.
3. Lever Handle: For quarter-turn valves NPS 6 (DN 150) and smaller, except plug
valves.
4. Wrench: For plug valves with square heads. Furnish Owner with 1 wrench for
every 10 plug valves, for each size square plug head.
H. Valve Flanges: ASME B16.1 for cast-iron valves, ASME B16.5 for steel valves, and
ASME B16.24 for bronze valves.
B. Type 2, Class 125, Bronze Angle Valves: Bronze body with PTFE or TFE disc and
union-ring bonnet.
B. Class 125, Cast-Iron Angle Valves: Bronze mounted with gray-iron body and bronze
seats.
B. Type 2, Class 125, Bronze, Horizontal Lift Check Valves: Bronze body with nonmetallic
disc and bronze seat.
C. Type 2, Class 125, Bronze, Vertical Lift Check Valves: Bronze body with nonmetallic
disc and bronze seat.
D. Type 3, Class 125, Bronze, Swing Check Valves: Bronze body with bronze disc and
seat.
E. Type 4, Class 125, Bronze, Swing Check Valves: Bronze body with nonmetallic disc
and bronze seat.
B. Type I, Class 125, gray-iron, swing check valves with metal seats.
C. Type II, Class 125, gray-iron, swing check valves with composition to metal seats.
A. Lift-Disc Check Valves, General: FCI 74-1, with spring-loaded bronze or alloy disc and
bronze or alloy seat.
B. Type I, Class 125, Wafer Lift-Disc Check Valves: Wafer style with cast-iron shell with
diameter matching companion flanges.
C. Type II, Class 125, Compact-Wafer, Lift-Disc Check Valves: Compact-wafer style with
cast-iron shell with diameter made to fit within bolt circle.
E. Type IV, Class 125, Threaded Lift-Disc Check Valves: Threaded style with bronze shell
and threaded ends.
B. Type 1, Class 125, Bronze Gate Valves: Bronze body with nonrising stem and bronze
solid wedge and union-ring bonnet.
C. Type 2, Class 125, Bronze Gate Valves: Bronze body with rising stem and bronze solid
wedge and union-ring bonnet.
B. Class 125, NRS, Bronze-Mounted, Cast-Iron Gate Valves: Cast-iron body with bronze
trim, nonrising stem, and solid-wedge disc.
C. Class 125, OS&Y, Bronze-Mounted, Cast-Iron Gate Valves: Cast-iron body with bronze
trim, rising stem, and solid-wedge disc.
D. Class 125, NRS, All-Iron, Cast-Iron Gate Valves: Cast-iron body with cast-iron trim,
nonrising stem, and solid-wedge disc.
E. Class 125, OS&Y, All-Iron, Cast-Iron Gate Valves: Cast-iron body with cast-iron trim,
rising stem, and solid-wedge disc.
B. Type 1, Class 125, Bronze Globe Valves: Bronze body with bronze disc and union-ring
bonnet.
C. Type 2, Class 125, Bronze Globe Valves: Bronze body with PTFE or TFE disc and
union-ring bonnet.
B. Type I, Class 125, Cast-Iron Globe Valves: Gray-iron body with bronze seats.
PART 3 - EXECUTION
3.01 EXAMINATION
KEO/19-3262-0000 22 0523/4 General Duty Valves for Plumbing Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
A. Examine piping system for compliance with requirements for installation tolerances and
other conditions affecting performance.
1. Proceed with installation only after unsatisfactory conditions have been
corrected.
B. Examine valve interior for cleanliness, freedom from foreign matter, and corrosion.
Remove special packing materials, such as blocks, used to prevent disc movement
during shipping and handling.
C. Operate valves in positions from fully open to fully closed. Examine guides and seats
made accessible by such operations.
D. Examine threads on valve and mating pipe for form and cleanliness.
E. Examine mating flange faces for conditions that might cause leakage. Check bolting for
proper size, length, and material. Verify that gasket is of proper size, that its material
composition is suitable for service, and that it is free from defects and damage.
A. Refer to piping Sections for specific valve applications. If valve applications are not
indicated, use the following:
1. Shutoff Service: Ball, butterfly, or gate valves.
2. Throttling Service: Angle, ball, butterfly, or globe valves.
3. Pump Discharge: Spring-loaded, lift-disc check valves.
B. If valves with specified CWP ratings are not available, the same types of valves with
higher CWP ratings may be substituted.
B. Install valves with unions or flanges at each piece of equipment arranged to allow
service, maintenance, and equipment removal without system shutdown.
C. Locate valves for easy access and provide separate support where necessary.
KEO/19-3262-0000 22 0523/5 General Duty Valves for Plumbing Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
D. Install valves in horizontal piping with stem at or above center of pipe.
3.04 ADJUSTING
A. Adjust or replace valve packing after piping systems have been tested and put into
service but before final adjusting and balancing. Replace valves if persistent leaking
occurs.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the following hangers and supports for plumbing system piping
and equipment:
1. Steel pipe hangers and supports.
2. Trapeze pipe hangers.
3. Metal framing systems.
4. Thermal-hanger shield inserts.
5. Fastener systems.
6. Pipe stands.
7. Pipe positioning systems.
8. Equipment supports.
1.02 DEFINITIONS
A. MSS: Manufacturers Standardization Society for the Valve and Fittings Industry Inc.
A. Design supports for multiple pipes, including pipe stands, capable of supporting
combined weight of supported systems, system contents, and test water.
KEO/19-3262-0000 22 0529/1 Hangers and Supports and Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1.04 SUBMITTALS
C. Welding certificates.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
G. Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion for
support of bearing surface of piping.
C. Coatings: Manufacturer's standard finish unless bare metal surfaces are indicated.
C. Insulation-Insert Material for Hot Piping: Water-repellent treated, ASTM C 533, Type I
calcium silicate.
D. For Trapeze or Clamped Systems: Insert and shield shall cover entire circumference of
pipe.
E. For Clevis or Band Hangers: Insert and shield shall cover lower 180 degrees of pipe.
F. Insert Length: Extend 2 inches (50 mm) beyond sheet metal shield for piping operating
below ambient air temperature.
B. Compact Pipe Stand: One-piece plastic unit with integral-rod-roller, pipe clamps, or V-
shaped cradle to support pipe, for roof installation without membrane penetration.
1. Subject to approved manufacturers list by PAHW.
KEO/19-3262-0000 22 0529/3 Hangers and Supports and Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Approved alternatives/substitutions under provision of the General Conditions of
Contract.
C. Low-Type, Single-Pipe Stand: One-piece stainless-steel base unit with plastic roller, for
roof installation without membrane penetration.
a. Subject to approved manufacturers list by PAHW.
b. Approved alternatives/substitutions under provision of the General
Conditions of Contract.
D. High-Type, Single-Pipe Stand: Assembly of base, vertical and horizontal members, and
pipe support, for roof installation without membrane penetration.
a. Subject to approved manufacturers list by PAHW.
b. Approved alternatives/substitutions under provision of the General
Conditions of Contract.
2. Base: Stainless steel.
3. Vertical Members: Two or more cadmium-plated-steel or stainless-steel,
continuous-thread rods.
4. Horizontal Member: Cadmium-plated-steel or stainless-steel rod with plastic or
stainless-steel, roller-type pipe support.
A. Description: IAPMO PS 42, system of metal brackets, clips, and straps for positioning
piping in pipe spaces for plumbing fixtures for commercial applications.
1. Subject to approved manufacturers list by PAHW.
2. Approved alternatives/substitutions under provision of the General Conditions of
Contract.
A. Structural Steel: ASTM A 36/A 36M, steel plates, shapes, and bars; black and
galvanized.
KEO/19-3262-0000 22 0529/4 Hangers and Supports and Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. Grout: ASTM C 1107, factory-mixed and -packaged, dry, hydraulic-cement, nonshrink
and nonmetallic grout; suitable for interior and exterior applications.
1. Properties: Nonstaining, noncorrosive, and nongaseous.
2. Design Mix: 5000-psi (34.5-MPa), 28-day compressive strength.
PART 3 - EXECUTION
A. Specific hanger and support requirements are specified in Sections specifying piping
systems and equipment.
B. Comply with MSS SP-69 for pipe hanger selections and applications that are not
specified in piping system Sections.
C. Use hangers and supports with galvanized, metallic coatings for piping and equipment
that will not have field-applied finish.
KEO/19-3262-0000 22 0529/6 Hangers and Supports and Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Side-Beam or Channel Clamps (MSS Type 20): For attaching to bottom flange
of beams, channels, or angles.
4. Center-Beam Clamps (MSS Type 21): For attaching to center of bottom flange
of beams.
5. Welded Beam Attachments (MSS Type 22): For attaching to bottom of beams if
loads are considerable and rod sizes are large.
6. C-Clamps (MSS Type 23): For structural shapes.
7. Top-Beam Clamps (MSS Type 25): For top of beams if hanger rod is required
tangent to flange edge.
8. Side-Beam Clamps (MSS Type 27): For bottom of steel I-beams.
9. Steel-Beam Clamps with Eye Nuts (MSS Type 28): For attaching to bottom of
steel I-beams for heavy loads.
10. Linked-Steel Clamps with Eye Nuts (MSS Type 29): For attaching to bottom of
steel I-beams for heavy loads, with link extensions.
11. Malleable Beam Clamps with Extension Pieces (MSS Type 30): For attaching to
structural steel.
12. Welded-Steel Brackets: For support of pipes from below, or for suspending from
above by using clip and rod. Use one of the following for indicated loads:
a. Light (MSS Type 31): 750 lb (340 kg).
b. Medium (MSS Type 32): 1500 lb (680 kg).
c. Heavy (MSS Type 33): 3000 lb (1360 kg).
13. Side-Beam Brackets (MSS Type 34): For sides of steel or wooden beams.
14. Plate Lugs (MSS Type 57): For attaching to steel beams if flexibility at beam is
required.
15. Horizontal Travelers (MSS Type 58): For supporting piping systems subject to
linear horizontal movement where headroom is limited.
J. Saddles and Shields: Unless otherwise indicated and except as specified in piping
system Sections, install the following types:
1. Steel Pipe-Covering Protection Saddles (MSS Type 39): To fill interior voids with
insulation that matches adjoining insulation.
2. Protection Shields (MSS Type 40): Of length recommended in writing by
manufacturer to prevent crushing insulation.
3. Thermal-Hanger Shield Inserts: For supporting insulated pipe.
K. Spring Hangers and Supports: Unless otherwise indicated and except as specified in
piping system Sections, install the following types:
1. Restraint-Control Devices (MSS Type 47): Where indicated to control piping
movement.
2. Spring Cushions (MSS Type 48): For light loads if vertical movement does not
exceed 1-1/4 inches (32 mm).
3. Spring-Cushion Roll Hangers (MSS Type 49): For equipping Type 41 roll hanger
with springs.
4. Spring Sway Braces (MSS Type 50): To retard sway, shock, vibration, or
thermal expansion in piping systems.
5. Variable-Spring Hangers (MSS Type 51): Preset to indicated load and limit
variability factor to 25 percent to absorb expansion and contraction of piping
system from hanger.
6. Variable-Spring Base Supports (MSS Type 52): Preset to indicated load and
limit variability factor to 25 percent to absorb expansion and contraction of piping
system from base support.
7. Variable-Spring Trapeze Hangers (MSS Type 53): Preset to indicated load and
limit variability factor to 25 percent to absorb expansion and contraction of piping
system from trapeze support.
KEO/19-3262-0000 22 0529/7 Hangers and Supports and Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
8. Constant Supports: For critical piping stress and if necessary to avoid transfer of
stress from one support to another support, critical terminal, or connected
equipment. Include auxiliary stops for erection, hydrostatic test, and load-
adjustment capability. These supports include the following types:
a. Horizontal (MSS Type 54): Mounted horizontally.
b. Vertical (MSS Type 55): Mounted vertically.
c. Trapeze (MSS Type 56): Two vertical-type supports and one trapeze
member.
L. Comply with MSS SP-69 for trapeze pipe hanger selections and applications that are
not specified in piping system Sections.
M. Comply with MFMA-102 for metal framing system selections and applications that are
not specified in piping system Sections.
O. Use pipe positioning systems in pipe spaces behind plumbing fixtures to support supply
and waste piping for plumbing fixtures.
A. Steel Pipe Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Install
hangers, supports, clamps, and attachments as required to properly support piping from
building structure.
B. Trapeze Pipe Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Arrange
for grouping of parallel runs of horizontal piping and support together on field-fabricated
trapeze pipe hangers.
1. Pipes of Various Sizes: Support together and space trapezes for smallest pipe
size or install intermediate supports for smaller diameter pipes as specified
above for individual pipe hangers.
2. Field fabricate from ASTM A 36/A 36M, steel shapes selected for loads being
supported. Weld steel according to AWS D1.1.
C. Fiberglass Pipe Hanger Installation: Comply with applicable portions of MSS SP-69 and
MSS SP-89. Install hangers and attachments as required to properly support piping
from building structure.
D. Metal Framing System Installation: Arrange for grouping of parallel runs of piping and
support together on field-assembled metal framing systems.
E. Fiberglass Strut System Installation: Arrange for grouping of parallel runs of piping and
support together on field-assembled fiberglass struts.
F. Thermal-Hanger Shield Installation: Install in pipe hanger or shield for insulated piping.
KEO/19-3262-0000 22 0529/8 Hangers and Supports and Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Install mechanical-expansion anchors in concrete after concrete is placed and
completely cured. Install fasteners according to manufacturer's written
instructions.
I. Pipe Positioning System Installation: Install support devices to make rigid supply and
waste piping connections to each plumbing fixture. Refer to Division 22 Section
"Plumbing Fixtures" for plumbing fixtures.
J. Install hangers and supports complete with necessary inserts, bolts, rods, nuts,
washers, and other accessories.
L. Install hangers and supports to allow controlled thermal and seismic movement of piping
systems, to permit freedom of movement between pipe anchors, and to facilitate action
of expansion joints, expansion loops, expansion bends, and similar units.
M. Install lateral bracing with pipe hangers and supports to prevent swaying.
N. Install building attachments within concrete slabs or attach to structural steel. Install
additional attachments at concentrated loads, including valves, flanges, and strainers,
NPS 2-1/2 (DN 65) and larger and at changes in direction of piping. Install concrete
inserts before concrete is placed; fasten inserts to forms and install reinforcing bars
through openings at top of inserts.
O. Load Distribution: Install hangers and supports so piping live and dead loads and
stresses from movement will not be transmitted to connected equipment.
P. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and so
maximum pipe deflections allowed by ASME B31.9 (for building services piping) are not
exceeded.
KEO/19-3262-0000 22 0529/9 Hangers and Supports and Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
a. Option: Thermal-hanger shield inserts may be used. Include steel
weight-distribution plate for pipe NPS 4 (DN 100) and larger if pipe is
installed on rollers.
4. Shield Dimensions for Pipe: Not less than the following:
a. NPS 1/4 to NPS 3-1/2 (DN 8 to DN 90): 12 inches (305 mm) long and
0.048 inch (1.22 mm) thick.
b. NPS 4 (DN 100): 12 inches (305 mm) long and 0.06 inch (1.52 mm) thick.
c. NPS 5 and NPS 6 (DN 125 and DN 150): 18 inches (457 mm) long and
0.06 inch (1.52 mm) thick.
d. NPS 8 to NPS 14 (DN 200 to DN 350): 24 inches (610 mm) long and
0.075 inch (1.91 mm) thick.
e. NPS 16 to NPS 24 (DN 400 to DN 600): 24 inches (610 mm) long and
0.105 inch (2.67 mm) thick.
5. Pipes NPS 8 (DN 200) and Larger: Include wood inserts.
6. Insert Material: Length at least as long as protective shield.
7. Thermal-Hanger Shields: Install with insulation same thickness as piping
insulation.
B. Grouting: Place grout under supports for equipment and make smooth bearing surface.
A. Cut, drill, and fit miscellaneous metal fabrications for trapeze pipe hangers and
equipment supports.
B. Fit exposed connections together to form hairline joints. Field weld connections that
cannot be shop welded because of shipping size limitations.
C. Field Welding: Comply with AWS D1.1 procedures for shielded metal arc welding,
appearance and quality of welds, and methods used in correcting welding work, and
with the following:
1. Use materials and methods that minimize distortion and develop strength and
corrosion resistance of base metals.
2. Obtain fusion without undercut or overlap.
3. Remove welding flux immediately.
4. Finish welds at exposed connections so no roughness shows after finishing and
contours of welded surfaces match adjacent contours.
3.05 ADJUSTING
B. Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches (40
mm).
KEO/19-3262-0000 22 0529/10 Hangers and Supports and Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3.06 PAINTING
A. Touch Up: Clean field welds and abraded areas of shop paint. Paint exposed areas
immediately after erecting hangers and supports. Use same materials as used for shop
painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.
1. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils
(0.05 mm).
B. Touch Up: Cleaning and touchup painting of field welds, bolted connections, and
abraded areas of shop paint on miscellaneous metal are specified in Division 09
painting Sections. Section "High-Performance Coatings."
C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply
galvanizing-repair paint to comply with ASTM A 780.
END OF SECTION
KEO/19-3262-0000 22 0529/11 Hangers and Supports and Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
SECTION 22 0548
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Inertia bases.
B. Vibration isolation.
B. Do not exceed the allowable noise level, 70 dBA measured at a distance of 1200 mm (4
feet) from source, by proper engineering of equipment assemblies.
A. Fans and other rotating mechanical equipment shall not operate at speeds in excess of
80 % of their true critical speed.
B. Vertical vibration of rotating equipment shall not be greater than the levels indicated.
The vibration shall be measured on the equipment or steel frame equipment base when
the equipment is mounted on its vibration isolation mounts. If the equipment has an
inertia base, the allowable vibration level is reduced by the ratio of the equipment weight
alone to the equipment weight plus the inertia base weight.
1.04 SUBMITTALS
B. Include data for each equipment and size of unit showing isolation type, efficiency,
stiffness, natural frequency, and transmissibility at lowest operating speed of equipment,
actual load, static deflection under actual load etc.
KEO/19-3262-0000 22 0548/1 Vibration and Noise Controls for Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. Submit manufacturer's certificates in respect of static and dynamic loading, fundamental
frequency, average noise level at full load conditions etc. of all equipment.
D. Indicate vibration isolator locations, on general layout and plant room detail drawings.
E. Flexible pipe connector shop drawings data to include maximum allowable temperature
and pressure rating, overall face to face length, live length, hose wall thickness, and
fundamental frequency of assembly.
F. Submit manufacturer's certificates that the vibration isolators are properly selected and
installed in equipment assemblies, to meet with, or to exceed the Contract requirements.
PART 2 - PRODUCTS
B. TYPE "1" - ISOLATING PADS: This type of vibration isolators shall be generally used
where the vibrating force is transmitted directly to ground or the vibrating force is very
small compared to the absorption capacity of the structural slab at higher levels.
E. TYPE "1C" - CORK PADS: The cork pads shall be constructed from natural cork
granules compressed and steam baked to form slabs and shall have a density of 96 to
106 kg/cu.M (6 to 6.6 lbs/cu.ft). The cork pads shall be treated with hot Bitumen Asphalt
coating for protection of cork.
F. TYPE "2" - MOLDED NEOPRENE RUBBER MOUNTS: These shall be used where a
greater deflection is required than that for pads. The maximum deflection allowable is 12
mm (0.5 inch) on these rubber mounts. The normal shape of mount is conical with a
captive insert for attaching to equipment base.
G. TYPE "3" - FREE STANDING SPRING ISOLATORS: These shall be constructed with
open type stable spring and load plates at top and bottom with an adjustable bolt for
levelling. Neoprene rubber acoustical treatment shall be provided to prevent
transmission of very high frequency vibration and noise. The spring shall be so designed
that the horizontal stiffness is more than 75 % of vertical stiffness. The rated loads and
deflections for these springs shall allow additional 50 % travel to that of the rated
deflection before the springs are compressed solid, to accommodate any errors in actual
load distribution.
KEO/19-3262-0000 22 0548/2 Vibration and Noise Controls for Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
H. TYPE "4" - RESTRAINED SPRING ISOLATORS: These are similar to type "3", but with
additional restraints in the vertical direction. These isolators shall have hold down bolts
to limit vertical movement. The restraints should have adequate clearance so that they
are activated only when a temporary restraint is needed.
I. TYPE "5" - HOUSED SPRING ISOLATORS: These isolators are similar to type "4"
except that they consist of two telescoping houses. The contact surfaces of houses are
separated by resilient inserts such as Neoprene Sponge or equivalent material.
J. TYPE "6" - RUBBER HANGERS: These are similar to type "2" except that the conical
rubber mold is housed in a steel casing and have a through hole for the hanger rod. The
assembly should allow for 20 to 35 degrees angular movement for the hanging rod
without metal to metal contact.
K. TYPE "7" - SPRING HANGERS: These are similar to type "3" except that the spring is
mounted in a steel casing and used for suspension only. The assembly shall allow for
20 to 25 degrees angular movement for the hanging rod without metal to metal contact.
M. TYPE "9" - THRUST RESTRAINTS: These are similar to type "7", but installed in pairs
to counteract the thrust caused by air pressure.
N. TYPE "10" - AIR SPRINGS: These shall consist of constant dry air supplying equipment
and air bellows. These shall be used where 150 mm (6 inch) or greater deflection is
required and natural frequencies do not exceed 80 Hz.
C. Approved Manufacturers:
1. Isolation Technology, Inc.
2. Mason Industries.
3. Vibration Mountings & Controls, Inc.
4. Approved alternatives/substitutions under provisions of General Conditions of
Contract.
D. Type "A" - INTEGRAL BASES: This type is generally applicable for packaged chillers,
pumps, Air Handling Units, Air conditioning Units etc. which are supplied with factory
fabricated rigid base which can be mounted directly on vibration isolators. Equipment
manufacturer's recommendations should be sought for the number, locations and
weight distribution to select and install vibration isolators.
E. Type "B" - STEEL STRUCTURAL BASES: This type is generally subdivided into closed
frame type (Type B1) and rails type (Type B2). These are steel bases fabricated either
as per the approved shop drawing or as per the equipment manufacturer's
recommendation. These are used for equipment not having a rigid base. The type B1
shall be used where the vibration isolators are located within the equipment base and
KEO/19-3262-0000 22 0548/3 Vibration and Noise Controls for Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
type B2 shall be used when the vibration isolators are outside the equipment and the
type B2 base acts as a cradle. The minimum depth shall be 4 inches.
F. TYPE "C" CONCRETE INTERTIAL BASES: This type generally consists of structural
steel, fabricated pouring form with reinforcing bars. The concrete shall be poured on
site. The minimum depth shall be 6 inches.
G. TYPE "D" - ROOF CURBS: This type is generally used for Roof top Air Handling Units
with direct cutting through roof slab under the units. These roof curbs shall be supplied
by the unit manufacturer. The manufacturer's recommendations should be sought for
the number, locations and weight distribution to select and install vibration isolators.
H. TYPE "E" - HOUSE KEEPING PADS: These are concrete bases used for all equipment
with or without moving parts and shall be suitable for taking up the static and dynamic
loads (if any). Size base to extend 10 cms beyond equipment base in all directions and
minimum10 cms above finished floor level. Roughen floor slab beneath base for bond
and or provide rebar dowels in floor slab. Locate anchor bolts (welded on to a rebar
framework to maintain spacing) with templates supplied by the equipment manufacturer.
Provide steel angle frame with anchorage lugs at the corners. Also see table 3.03 for
exact heights.
I. TYPE "F" - FLOATING CONCRETE BASE: This is similar to Type "E" (House keeping
pads) but isolated at the bottom and all the side by either pre-compressed glass fiber
pads or Heavy density seasoned cork. The thickness of isolating pads vary from 25 to
100 mm (1 to 4 inch) depending on the application.
PART 3 - EXECUTION
3.01 APPLICATION
A. General
1. Refer to PART 2 - PRODUCTS of this specification for vibration isolation devices
identified on the schedule or specified herein.
B. Major Equipment
KEO/19-3262-0000 22 0548/4 Vibration and Noise Controls for Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Unless otherwise shown or specified, all floor mounted major equipment shall be
set on concrete housekeeping pads as per recommendations of the
manufacturer. See schedule of mounting pads in this section.
2. Types and minimum static deflections of vibration isolation devices for major
equipment items shall be as scheduled on the drawings or specified here under.
3. Flexible duct connections shall be installed at all fan unit intakes, fan unit
discharges, and wherever else shown on the drawings.
4. Flexible pipe connections shall be installed at all pipe connections to vibration
isolated equipment in the positions shown on the drawings.
5. Electrical connections to vibration isolated equipment shall be flexible, as called
for in the electrical portion of the specification.
6. Snubbers or thrust restraints shall be installed on equipment as called for in the
schedule on the drawings or specified here under.
D. Piping
1. Provide flexible pipe connections in piping connected to vibration isolated
equipment, as called for and shown on drawings.
2. Anchor piping at the system side of the flexible connector.
A. General
1. Locations of all vibration isolation equipment shall be selected for ease of
inspection and adjustment as well as for proper operation.
2. Installation of vibration isolation equipment shall be in accordance with the
manufacturer's instructions.
B. Isolation Mounts
1. All vibration isolators shall be aligned squarely above or below mounting points of
the supported equipment.
2. Isolators for equipment with bases shall be located on the sides of the bases,
which are parallel to the equipment shaft unless this is not possible because of
physical constraints.
3. If a housekeeping pad is provided, the isolators shall bear on the housekeeping
pad and the isolator base plate shall rest entirely on the pad.
4. Hanger rods for vibration isolated support shall be connected to structural beams
or joists, not from the floor slab between beams and joists. Provide intermediate
support members as necessary.
5. Vibration isolation hanger elements shall be positioned as high as possible in the
hanger rod assembly, but not in contact with the building structure, and so that
the hanger housing may rotate a full 360 degrees about the rod axis without
contacting any object.
6. Parallel running pipes may be hung together on a trapeze, which is isolated from
the building. Isolator deflections must be the largest determined by the provisions
for pipe isolation. Do not mix isolated and non-isolated pipes on the same
trapeze.
7. No pipes or equipment shall be supported from other pipes or equipment.
KEO/19-3262-0000 22 0548/5 Vibration and Noise Controls for Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
8. Resiliently isolated pipes shall not contact the building construction or other
equipment.
9. The installed and operating heights of vibration isolators supporting any
equipment shall be identical. Limit stops shall be out of contact during normal
operation.
10. Adjust all leveling bolts and hanger rod bolts so that the isolated equipment is
level and in proper alignment with connecting ducts or pipes.
C. Bases
1. No equipment unit shall bear directly on vibration isolators unless its own frame
is suitably rigid to span between isolators and such direct support is approved by
the equipment manufacturer. This provision shall apply whether or not a base
frame is called for on the schedule. In the case that a base frame is required for
the unit because of the equipment manufacturer's requirements and is not
specifically called for on the equipment schedule, a base frame recommended by
the equipment manufacturer shall be provided.
2. Unless otherwise indicated, there is to be a minimum operating clearance of 38-
mm (1 1/2 inch) between inertia bases or steel frame bases and the floor
beneath the equipment. Position isolator mounting brackets and adjust isolators
so that the required clearance is maintained. The clearance space shall be
checked by the Contractor to ensure that no construction debris has been left to
short circuit or restrict the proper operation of the vibration isolation system.
E. Thrust Restraints
1. Snubbers shall be adjusted to clear the equipment base and to provide lateral
restraint during on / off cycling, but be out of contact during normal operation of
the equipment.
2. Thrust restraints shall be attached at the center line of thrust and symmetrically
on each of the units. Adjust the restraints to limit equipment movement to the
specified limit.
3.04 ADJUSTING
B. Adjust limit stops on restrained spring isolators to mount equipment at normal operating
height. After equipment installation is complete, adjust limit stops so they are out of
contact during normal operation.
END OF SECTION
KEO/19-3262-0000 22 0548/7 Vibration and Noise Controls for Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
SECTION 22 0553
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Section Includes:
1. Equipment labels.
2. Warning signs and labels.
3. Pipe labels.
4. Stencils.
5. Valve tags.
6. Warning tags.
1.02 SUBMITTALS
B. Samples: For color, letter style, and graphic representation required for each
identification material and device.
C. Equipment Label Schedule: Include a listing of all equipment to be labeled with the
proposed content for each label.
1.03 COORDINATION
B. Coordinate installation of identifying devices with locations of access panels and doors.
C. Install identifying devices before installing acoustical ceilings and similar concealment.
PART 2 - PRODUCTS
A. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving,
1/8 inch (3.2 mm) thick, and having predrilled holes for attachment hardware.
D. Maximum Temperature: Able to withstand temperatures up to 160 deg F (71 deg C).
E. Minimum Label Size: Length and width vary for required label content, but not less than
2-1/2 by 3/4 inch (64 by 19 mm).
F. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less
than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances up to 72 inches (1830
mm), and proportionately larger lettering for greater viewing distances. Include
secondary lettering two-thirds to three-fourths the size of principal lettering.
H. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
I. Label Content: Include caution and warning information, plus emergency notification
instructions.
B. Pretensioned Pipe Labels: Precoiled, semirigid plastic formed to [partially cover] [cover
full] circumference of pipe and to attach to pipe without fasteners or adhesive.
D. Pipe Label Contents: Include identification of piping service using same designations or
abbreviations as used on Drawings, pipe size, and an arrow indicating flow direction.
1. Flow-Direction Arrows: Integral with piping system service lettering to
accommodate both directions, or as separate unit on each pipe label to indicate
flow direction.
2. Lettering Size: At least 1-1/2 inches (38 mm) high.
2.05 STENCILS
A. Stencils: Prepared with letter sizes according to ASME A13.1 for piping; and minimum
letter height of 3/4 inch (19 mm) for access panel and door labels, equipment labels,
and similar operational instructions.
1. Stencil Material: Aluminum.
2. Stencil Paint: Exterior, gloss, acrylic enamel black unless otherwise indicated.
Paint may be in pressurized spray-can form.
3. Identification Paint: Exterior, acrylic enamel in colors according to ASME A13.1
unless otherwise indicated.
A. Valve Tags: Stamped or engraved with 1/4-inch (6.4-mm) letters for piping system
abbreviation and 1/2-inch (13-mm) numbers.
B. Valve Schedules: For each piping system, on 8-1/2-by-11-inch (A4) bond paper.
Tabulate valve number, piping system, system abbreviation (as shown on valve tag),
location of valve (room or space), normal-operating position (open, closed, or
modulating), and variations for identification. Mark valves for emergency shutoff and
similar special uses.
1. Valve-tag schedule shall be included in operation and maintenance data.
PART 3 - EXECUTION
3.01 PREPARATION
A. Clean piping and equipment surfaces of substances that could impair bond of
identification devices, including dirt, oil, grease, release agents, and incompatible
primers, paints, and encapsulants.
B. Stenciled Pipe Label Option: Stenciled labels may be provided instead of manufactured
pipe labels, at Installer's option. Install stenciled pipe labels complying with
ASME A13.1, on each piping system.
1. Identification Paint: Use for contrasting background.
2. Stencil Paint: Use for pipe marking.
C. Locate pipe labels where piping is exposed or above accessible ceilings in finished
spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and
plenums; and exterior exposed locations as follows:
1. Near each valve and control device.
2. Near each branch connection, excluding short takeoffs for fixtures and terminal
units. Where flow pattern is not obvious, mark each pipe at branch.
KEO/19-3262-0000 22 0553/4 Identification for Plumbing Piping and Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Near penetrations through walls, floors, ceilings, and inaccessible enclosures.
4. At access doors, manholes, and similar access points that permit view of
concealed piping.
5. Near major equipment items and other points of origination and termination.
6. Spaced at maximum intervals of 50 feet (15 m) along each run. Reduce intervals
to 25 feet (7.6 m) in areas of congested piping and equipment.
7. On piping above removable acoustical ceilings. Omit intermediately spaced
labels.
A. Install tags on valves and control devices in piping systems, except check valves; valves
within factory-fabricated equipment units; shutoff valves; faucets; convenience and
lawn-watering hose connections; and similar roughing-in connections of end-use fixtures
and units. List tagged valves in a valve schedule.
B. Valve-Tag Application Schedule: Tag valves according to size, shape, and color
scheme and with captions similar to those indicated in the following subparagraphs:
1. Valve-Tag Size and Shape:
a. Cold Water: 2 inches (50 mm), round.
b. Hot Water: 2 inches (50 mm), round.
2. Valve-Tag Color:
a. Cold Water: Natural.
b. Hot Water: Natural.
3. Letter Color:
a. Cold Water: Black.
b. Hot Water: Black.
A. Write required message on, and attach warning tags to, equipment and other items
where required.
END OF SECTION
PLUMBING INSULATION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Piping insulation.
A. Division 22
1.03 REFERENCES
A. The work under this section shall include all labor, services, materials and equipment as
required for the proper installation of the piping and equipment insulation as hereinafter
specified and subject to the terms and conditions of the contract.
B. Applicator: Company specialized in piping and equipment insulation application with ten
(10) years minimum experience.
E. All insulation materials and accessories for piping and equipment shall meet the
requirements of The National Building Code, Section 200 and The National Fire Code,
Section, 220. Ratings shall be determined by Underwriters' Laboratories, Inc., "Method
of Test of Surface Burning Characteristics of Building Materials". All accessories and
materials such as coatings, adhesive and sealer are to be shipped to the job in
unopened containers as received from the manufacturer. These accessory materials are
to be applied at can consistency and are not to be diluted in any form.
1. All insulating materials shall have composite fire and fuel contributed and smoke
hazard ratings for insulation, jacket or facing, and adhesive used to adhere the
facing or jacket to the insulation. Rating as tested in accordance with ASTM E-
84 shall be less than:
a. Flame Spread - 25
b. Fuel Contributed & smoke developed - 50
2. All accessories, including adhesives, mastics, tapes, cements, etc., shall have
the same component ratings as listed above.
1.05 SUBMITTALS
B. Submit schedule listing product description, list of materials and thickness for each
service, and locations.
C. Submit maintenance data and replacement material lists for each type of insulation.
Include this data in the maintenance manual.
D. Submit for The Engineer’s representative review, one sample of each type of insulation
with jackets and finishes representing the finished application of the particular insulating
material. Each sample shall be coded in a manner that will facilitate matching of the
respective sample with the schedule list and job application.
PART 2 - PRODUCTS
A. Insulation Material
1. Type A: Pre-formed glass fiber sectional insulation; `ksi' value of 0.032 at 24
deg.C (`K' value of 0.23 at 77 deg.F), non-combustible; density 64 kg/cu.M (4
C. Protective Jackets
1. All vapor barrier material on top of insulation shall be polyester membrane
(synthetic fibre composition) with waterproof anti fungicidal vapor barrier mastic
fire resistive to NFPA 255. The polyester membrane shall have a mesh size of 9
x 8 (openings per square inch) with a maximum service temperature of 250°F.
Average weight of polyester cloth shall be 0.9 oz/sq. yard
2. Aluminum jackets: 0.70mm thick with corrugated finish.
D. Accessories
1. Insulation bands: Kraft reinforced aluminum foil tapes of minimum 50 mm (2 inch)
width, with self sealing adhesive.
2. Metal jacket bands: 10 mm (3/8 inch) wide; 0.38 mm (0.015 inch) thick aluminum.
3. Polyester membrane adhesive coating: Compatible with insulation, non-
flammable type, tough, vapour barrier, antifungicidal, abrasion resistant, applied
by brush or spray.
PART 3 - EXECUTION
3.01 PREPARATION
A. Install materials after piping has been tested and approved and painted with two coats
of approved primer paint, where applicable.
3.02 INSTALLATION
D. On insulated piping with vapour barrier, insulate fittings, valves, unions, flanges,
strainers, flexible connections, and expansion joints.
E. On insulated piping without vapour barrier and piping conveying fluids 60 °C (140 °F) or
less, do not insulate flanges and unions at equipment, but bevel and seal ends of
insulation at such locations.
G. Where glass fiber rigid sectional insulation is specified, insulate fittings flanges and
valves by applying mineral wool cement, maintaining thickness of insulation same as for
adjoining pipe. Finish with jacketing as specified.
I. Provide mitered bends on insulation shells at pipe fittings and finish neatly.
L. Insulation on all pipe strainers shall have removable cover for cleaning.
------------------------------------------------------------------------------------------------------------------------
PIPING TYPE PIPE SIZE THICKNESS
(Section 2.02A) mm (inch) mm (inch)
------------------------------------------------------------------------------------------------------------
A. Domestic hot water supply, return and piping in plant areas: Canvas jacketing with
adhesive coating shall be applied.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes domestic water piping and water meters inside the building.
1.02 DEFINITIONS
1.04 SUBMITTALS
A. Product Data and Samples: For pipe, tube, fittings, and couplings and water meters.
A. Piping materials shall bear label, stamp, or other markings of specified testing agency.
B. Comply with NSF 14, "Plastics Piping System Components and Related Materials," for
plastic, potable domestic water piping and components. Include marking "NSF-pw" on
piping.
C. Comply with NSF 61, "Drinking Water System Components - Health Effects; Sections 1
through 9," for potable domestic water piping and components.
2.02 REFERENCES
B. ANSI B 16.3 - Malleable iron threaded fittings class 150 and 300.
I. DIN 16962ff Pipe Joint assemblies and fittings for polypropylene pressure pipes.
L. API 600 - General design specifications for gate, globe and check valves.
N. ANSI B 16.10- Face to face dimensions of cast iron gate, globe and check valves.
2.04 PIPES
2.05 JOINTS
A. Type of joints.
1. Polypropylene (PP-R): Socket fusion, electro fusion or compression as
appropriate.
B. Pressure ratings of joints. All figures stated are working water / air pressures (WOG) at
121 deg.C (250 deg.F).
1. PP-R pipe : 2000 Kpa (290 psig).
C. All flanges, unions and couplings shall be pressure rated as the pipe joints.
2.07 VALVES
A. Bronze and cast-iron, general-duty valves are specified in Division 22 Section "General-
Duty Valves for Plumbing Piping."
PART 3 - EXECUTION
KEO/19-3262-0000 22 1116/3 Facility Water Distribution Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3.01 EXCAVATION
A. Transition and special fittings with pressure ratings at least equal to piping rating may be
used in applications below, unless otherwise indicated.
A. Drawings indicate valve types to be used. Where specific valve types are not indicated,
the following requirements apply:
1. Shutoff Duty: Use bronze ball or gate valves for piping NPS 2 (DN 50) and
smaller. Use cast-iron butterfly or gate valves with flanged ends for piping
NPS 2-1/2 (DN 65) and larger.
2. Throttling Duty: Use bronze ball or globe valves for piping NPS 2 (DN 50) and
smaller. Use cast-iron butterfly valves with flanged ends for piping NPS 2-1/2
(DN 65) and larger.
3. Drain Duty: Hose-end drain valves.
C. Install shutoff valve close to water main on each branch and riser serving plumbing
fixtures or equipment, on each water supply to equipment, and on each water supply to
plumbing fixtures that do not have supply stops. Use ball or gate valves for piping
NPS 2 (DN 50) and smaller. Use butterfly or gate valves for piping NPS 2-1/2 (DN 65)
and larger.
D. Install drain valves for equipment at base of each water riser, at low points in horizontal
piping, and where required to drain water piping.
1. Install hose-end drain valves at low points in water mains, risers, and branches.
2. Install stop-and-waste drain valves where indicated.
A. Install cast-iron sleeve with water stop and mechanical sleeve seal at each service pipe
penetration through foundation wall. Select number of interlocking rubber links required
to make installation watertight.
B. Install wall penetration system at each service pipe penetration through foundation wall.
Make installation watertight.
C. Install shutoff valve, hose-end drain valve, strainer, pressure gage, and test tee with
valve, inside the building at each domestic water service entrance.
KEO/19-3262-0000 22 1116/4 Facility Water Distribution Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
D. Install domestic water piping level with 0.25 percent slope downward toward drain and
plumb.
A. Soldered Joints: Use ASTM B 813, water-flushable, lead-free flux; ASTM B 32, lead-
free-alloy solder; and ASTM B 828 procedure, unless otherwise indicated.
A. Rough-in domestic water piping for water meter installation according to utility
company's requirements.
3.07 CONNECTIONS
B. Install piping adjacent to equipment and machines to allow service and maintenance.
C. Connect domestic water piping to exterior water-service piping. Use transition fitting to
join dissimilar piping materials.
D. Connect domestic water piping to water-service piping with shutoff valve, and extend
and connect to the following:
1. Booster Pumps: Cold-water suction and discharge piping.
2. Water Heaters: Cold-water supply and hot-water outlet piping in sizes indicated,
but not smaller than sizes of water heater connections.
3.09 ADJUSTING
3.10 CLEANING
B. Clean interior of domestic water piping system. Remove dirt and debris as work
progresses.
3.11 PROTECTION: Give the following protective coating / wrapping to piping. All piping
above louvered ceilings shall be painted black.
E. Insulated plastic piping in technical areas and below grade pipe trenches.
1. Heavy canvas jacketing with Benjamin Foster finish.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Minimum Working Pressure for Domestic Water Piping Specialties: 125 psig (860 kPa),
unless otherwise indicated.
1.03 SUBMITTALS
D. Operation and Maintenance Data: For domestic water piping specialties to include in
emergency, operation, and maintenance manuals.
B. NSF Compliance:
1. Comply with NSF 14, "Plastics Piping Components and Related Materials," for
plastic domestic water piping components.
2. Comply with NSF 61, "Drinking Water System Components - Health Effects;
Sections 1 through 9."
KEO/19-3262-0000 22 1119/1 Facility Water Piping Specialties
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
PART 2 - PRODUCTS
A. Y-Pattern Strainers
1. Pressure Rating: 125 psig (860 kPa) minimum, unless otherwise indicated.
2. Body: Bronze for NPS 2 (DN 50) and smaller; cast iron with interior lining
complying with AWWA C550 or FDA-approved, epoxy coating and] for NPS 2-1/2
(DN 65) and larger.
3. End Connections: Threaded for NPS 2 (DN 50) and smaller; flanged for NPS 2-
1/2 (DN 65) and larger.
4. Screen: Stainless steel with round perforations, unless otherwise indicated.
5. Perforation Size:
a. Strainers NPS 2 (DN 50) and Smaller: 0.020 inch (0.51 mm).
b. Strainers NPS 2-1/2 to NPS 4 (DN 65 to DN 100): 0.045 inch (1.14 mm).
c. Strainers NPS 5 (DN 125) and Larger: 0.10 inch (2.54 mm).
6. Drain: Factory-installed, hose-end drain valve.
A. Hose Bibbs:
1. Standard: ASME A112.18.1 for sediment faucets.
2. Body Material: Bronze.
3. Seat: Bronze, replaceable.
4. Supply Connections: NPS 1/2 or NPS 3/4 (DN 15 or DN 20) threaded or solder-
joint inlet.
5. Outlet Connection: Garden-hose thread complying with ASME B1.20.7.
KEO/19-3262-0000 22 1119/2 Facility Water Piping Specialties
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
6. Pressure Rating: 125 psig (860 kPa).
7. Vacuum Breaker: Integral or field-installation, nonremovable, drainable, hose-
connection vacuum breaker complying with ASSE 1011.
8. Finish for Equipment Rooms: Rough bronze, or chrome or nickel plated.
9. Finish for Service Areas: Rough bronze.
10. Finish for Finished Rooms: Chrome or nickel plated.
11. Operation for Equipment Rooms: Wheel handle or operating key.
12. Operation for Service Areas: Operating key.
13. Operation for Finished Rooms: Operating key.
14. Include operating key with each operating-key hose bib.
15. Include integral wall flange with each chrome- or nickel-plated hose bib.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Refer to Division 22 Section “Common Work Results for Plumbing” for piping joining
materials, joint construction, and basic installation requirements.
B. Install backflow preventers in each water supply to mechanical equipment and systems
and to other equipment and water systems that may be sources of contamination.
Comply with authorities having jurisdiction.
1. Locate backflow preventers in same room as connected equipment or system.
2. Install drain for backflow preventers with atmospheric-vent drain connection with
air-gap fitting, fixed air-gap fitting, or equivalent positive pipe separation of at
least two pipe diameters in drain piping and pipe to floor drain. Locate air-gap
device attached to or under backflow preventer. Simple air breaks are not
acceptable for this application.
3. Do not install bypass piping around backflow preventers.
C. Install water regulators with inlet and outlet shutoff valves and bypass with memory-stop
balancing valve. Install pressure gages on inlet and outlet.
D. Install water control valves with inlet and outlet shutoff valves and bypass with globe
valve. Install pressure gages on inlet and outlet.
F. Install temperature-actuated water mixing valves with check stops or shutoff valves on
inlets and with shutoff valve on outlet.
1. Install thermometers and water regulators if specified.
2. Install cabinet-type units recessed in or surface mounted on wall as specified.
G. Install Y-pattern strainers for water on supply side of each control valve, water pressure-
reducing valve, solenoid valve, and pump.
H. Install air vents at high points of water piping. Install drain piping and discharge onto
floor drain.
I. Install supply-type, trap-seal primer valves with outlet piping pitched down toward drain
trap a minimum of 1 percent, and connect to floor-drain body, trap, or inlet fitting. Adjust
valve for proper flow.
J. Install drainage-type, trap-seal primer valves as lavatory trap with outlet piping pitched
down toward drain trap a minimum of 1 percent, and connect to floor-drain body, trap, or
inlet fitting.
3.02 CONNECTIONS
B. Remove and replace malfunctioning domestic water piping specialties and retest as
specified above.
3.05 ADJUSTING
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes constant and variable speed, multiplex, packaged booster
pumps for domestic water piping systems.
1.02 DEFINITIONS
1.03 SUBMITTALS
A. Product Data: For each packaged booster pump specified. Include certified
performance curves with operating points plotted on curves; and rated capacities of
selected models, furnished specialties, and accessories.
B. Shop Drawings: For packaged booster pumps and accessories. Include plans,
elevations, sections, details, and attachments to other work. .
1. For installed products indicated to comply with design loads, include structural
analysis data signed and sealed by the qualified professional engineer
responsible for their preparation.
2. Design Calculations: Calculate requirements for selecting vibration isolators
and seismic restraints and for designing vibration isolation bases.
3. Vibration Isolation Base Details: Detail fabrication including anchorages and
attachments to structure and to supported equipment. Include auxiliary motor
slides and rails and equipment mounting frames.
4. Wiring Diagrams: Detail power, signal, and control wiring.
D. Operation and Maintenance Data: For each packaged booster pump to include in
emergency, operation, and maintenance manuals.
D. Regulatory Requirements
a. Name of manufacturer.
c. Certified ratings.
E. Packaged booster pumps shall be listed and labeled as pumping systems by testing
agency acceptable to authorities having jurisdiction.
A. Retain shipping flange protective covers and protective coatings during storage.
1.06 WARRANTY
A. Provide complete spare parts and maintenance equipment for two (2) years
maintenance of all the equipment furnished under this section. Spare parts in a
location designated by the Engineer or the Employer.
B. All spare parts and maintenance equipment shall be provided in original packing,
clearly identified and labelled. Provide complete schedules of spare parts and
maintenance equipment clearly cross-referenced with the “Record Drawings” and
maintenance instructions and manuals.
D. Spare parts and maintenance equipment provided shall, as a minimum, equal the
items used during the two (2) years maintenance period. The Contractor shall carefully
log all spare parts utilized during maintenance period.
E. Provide spare parts and maintenance equipment for all pumps, control panel etc.
requiring maintenance and replacement.
F. Provide two new complete sets of tools for the proper operation, routine maintenance
and adjustment of all components and equipment.
1.08 COORDINATION
PART 2 - PRODUCTS
2.01 MANUFACTURER
2.02 QUALIFICATIONS
KEO/19-3262-0000 22 1123.13/3 Domestic Water Packaged Booster Pumps
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
A. The manufacturer shall have a minimum of twenty years’ experience in the design,
manufacture and testing of pumps.
B. Pumps: Vertical multistage, centrifugal type of 2900 rpm speed. All wetted areas shall
be of stainless steel 316. Booster sets shall be of variable speed nature, with individual
VFD controller for each pump on the set, maintaining a constant discharge pressure
by continuously matching the pump speed relative to the actual water consumption in
the network. Transfer pump sets and A/C make up pump sets shall work on pressure
networks (similar to booster pump sets but without VFD controllers) with delayed
action float valves in the fed tanks controlling their operation. Pumps materials of
construction shall be as follows:
1. Pump body Stainless steel AISI 316.
2. Lower support (where applicable) Stainless steel AISI 316.
3. Impeller Stainless steel AISI 316.
4. Diffuser Stainless steel AISI 316L.
5. Upper spacer (where applicable) Stainless steel AISI 316L.
6. Outer sleeve Stainless steel AISI 316L.
7. Shaft Stainless steel AISI 316 (min.)
8. Adapter Cast iron.
9. Base (where applicable) Aluminum.
10. Wear ring (where applicable) Technopolymer PPS
11. Coupling Aluminium on pumps up to 4 KW Cast
iron (for all sizes)
12. Upper head (where applicable) Stainless steel AISI 316.
13. Seal housing Stainless steel AISI 316.
14. Mechanical seal Silicon carbide/carbon/EPDM.
15. Elastomers EPDM.
16. Coupling protection Stainless steel AISI 304.
17. Shaft sleeve Tungsten carbide
18. Bushing Ceramic (pumps up to 20m3/hr)
19. Tungsten carbide (other pumps)
20. Bushing for diffuser (where applicable) Carbon
21. Fill/Drain Plugs: Stainless steel AISI 316.
22. Tie Rods Stainless steel AISI 431.
23. Pumps shall be suitable for handling potable water (WRAS certified).
C. System piping shall be type “K” copper with brazed joints. Manifold ends shall be
flanged.
D. Valves:
Pumps with suction and discharge connection 2” and smaller shall each be fitted with
bronze PN 25 gate valves at the suction and discharge sides and brass spring loaded
self closing check valve at the discharge side.
Pumps with suction and discharge connections 2 1/2” or bigger shall each be fitted
with internally and externally epoxy coated ductile iron valves in PN 16 or PN 25 flange
pressure ratings (according to pump closed valve head) at the suction and discharge
sides and wafer style self closing check valve at the discharge side.
F. Pressure vessel (for pressure controlled sets only): Welded steel construction with
butyl rubber diaphragm, hooded charging valve, suitable for 10 bars, or 25 bar
pressure rating (based on pump closed valve head), pre-charged with nitrogen.
Pressure tanks in pressure ratings of PN 16 and above must have flanged
connections.
The pressure tank capacity shall be suitable for limiting the number of pump starts to
15 per hour.
G. Relief Valve: Provide suitable bypass pressure relief valve from discharge to suction
manifolds to prevent pump operation at shutoff head.
I. Pump Motor:
Pump motor shall fall within the range normally referred to as efficiency Class 1.
Pump motors shall be standard and easily found on the market. On pumps with higher
heads, this shall be achieved through an axial load compensation system.
J. Finishing: The assembly shall be given two (2) coats of primer and one coat of gloss
enamel at the factory.
K. VFD Controllers:
The microprocessor based variable speed pump set controller shall have the following
features:
The controller shall also be able to flow a system curve i.e. it shall be able to achieve
automatic motor speed regulation in order to compensate for increased friction losses
in the system during periods of high water demand.
The controller shall include one VFD for every pump in the pumping system. The
controller can be pump mounted or stand mounted. In this case the controller shall
consist of multiple VFD (depending on the number of pumps) fixed in one control
panel.
The controller shall have an IP 55 enclosure with thermal resistor for mounting inside
the motor terminal box.
It shall be possible to mount the controller on any fan cooled standard 240/415 volt,
three phase TEFC motor with Class F insulation where the motor fan will provide the
necessary cooling for the controller.
The controller shall prevent motor noise from occurring by generating, through the
frequency converter in the controller a sinus evaluated pulse with modulated output
KEO/19-3262-0000 22 1123.13/5 Domestic Water Packaged Booster Pumps
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
voltage with a switching frequency, selectable between 2.5 kHz and 8 kHz.
The controller shall have an internal protection against overload and short circuit. It
shall work controlled with sinusoidal current synthesis and dynamic over current
limitation.
The controller shall have a control unit incorporated in it containing foil covered push
buttons and a two line display to show the set value, the operational status, the hours
of operation, the output frequency, the control and fault signs in plain text, programmed
in different languages up to the client’s choice.
The Controller shall have dry contacts for “pump running” and a summarized “pump
fault” for communication with an external Building Automation System (BAS).
The controller shall have RS 485 interface for communication between multiple pumps
in a multi pump system.
The Controller has three color LEDs for signalling “Power On”, “Pump Run”, and
“Pump Fault”.
In a multi pump system the controller built-in microprocessor shall ensure the following
features:
It shall also be possible to program separate “conveyor limit” whereby the unit will stop
KEO/19-3262-0000 22 1123.13/6 Domestic Water Packaged Booster Pumps
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
and indicate an error in case the pump does not reach this limit within a programmable
time. This feature shall be used for the dry run protection of the pump set.
It shall be possible to use the included power supply to supply the external pressure
or flow sensor, which will give a 4-20 mA signal to the controller.
The controller shall be supplied with anti-condensation heaters that shall switch on
when the units are in the standby mode.
Each controller shall be supplied with a pressure transducer (wherever the system is
a constant pressure system), transducer connection cable and transducer mounting
hardware as standard. The pressure transducer shall be of stainless steel AISI 316
with a viton gasket and shall be designed for a pressure of 10 bar or 25 bar depending
on the application. If constant flow is required then an orifice plate with a differential
pressure transducer is available. The measured differential pressure shall then be
converted into flow and shall be used to adjust the pump running speed.
2.01 MOTORS
A. Comply with NEMA designation, temperature rating, service factor, enclosure type,
and efficiency requirements for motors.
1. Motor Sixes: Minimum size as indicated. If not indicated, large enough so
driven load will not require motor to operate in service factor range above 1.0.
2. Controllers, Electrical Devices, and Wiring: Comply with requirements for
electrical devices and connections specified in NFPA 70.
A. Description: Corrugated, bronze inner tubing covered with bronze wire braid. Include
copper-tube ends or bronze flanged ends, braze-welded to tubing. Include 175-psig
(1200-kPa) minimum working-pressure rating and ends according to the following:
1. NPS 2 (DN 50) and Smaller: Threaded. Provide flanged ends if pump has
flanged connections.
2. NPS 2-1/2 (DN 65) and Larger: Flanged.
PART 3 - EXECUTION
3.01 EXAMINATION
B. Install concrete bases of dimensions indicated for packaged booster pumps. Refer to
Division 22 Section "Common Work Results for Plumbing."
1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise
indicated, install dowel rods on 18-inch (450-mm) centers around full perimeter
of base.
2. For supported equipment, install epoxy-coated anchor bolts that extend through
concrete base and anchor into structural concrete floor.
3. Place and secure anchorage devices. Use setting drawings, templates,
diagrams, instructions, and directions furnished with items to be imbedded.
4. Install anchor bolts to elevation required for proper attachment to supported
equipment.
3.03 SELECTION
A. Pump motors shall be selected for the maximum loading of the selected impeller.
B. Pumps shall be selected with the operating points within 20 % on either side of the
maximum efficiency point.
C. The maximum and minimum impeller sizes shall not be selected for unit pumps, as far
as possible.
3.04 COORDINATION
A. The size of door ways and other accesses to technical areas shall be coordinated to
ensure that these are amply sized to allow for the movement of equipment.
B. Hooks, rails or other provisions shall be provided to allow for hoisting or movement of
equipment in technical areas.
C. Data on heat loss to surroundings from equipment located in air conditioned areas
shall be furnished to the HVAC trade.
D. Data on the required power supplies shall be furnished to the Electrical trade.
3.05 INSTALLATION
3.01 CONNECTIONS
C. Connect domestic water piping to packaged booster pumps. Install suction and
discharge pipe equal to or greater than size of unit suction and discharge headers.
1. Install flexible connectors on piping connections to unit suction and discharge
piping. Install flexible connectors same size as piping.
2. Install shutoff valves on piping connections to each booster pump suction and
discharge piping. Install ball, butterfly, or gate valves same size as suction and
discharge piping. General-duty valves are specified in Division 22 Section
"General-Duty Valves for Plumbing Piping."
3. Install union or flanged connections on pump suction and discharge piping at
connection to domestic water piping.
4. Install piping adjacent to packaged booster pumps to allow service and
maintenance.
C. Perform the following startup checks for each pump of packaged booster pump unit
before starting:
1. Verify bearing lubrication.
2. Prime pumps by opening suction valves and closing discharge valves, and
prepare pumps for operation.
3. Start motors.
4. Open discharge valves slowly.
5. Adjust settings.
3.04 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes RCC reservoirs for storage of domestic and fire-suppression
water.
1.02 DEFINITIONS
1.04 SUBMITTALS
C. Comply with NFPA 22, "Water Tanks for Private Fire Protection," for surface water-
storage tanks for fire-suppression water supply.
D. Comply with NSF 61, "Drinking Water System Components--Health Effects, Sections 1
to 9," for potable-water storage tanks. Include appropriate NSF marking.
1.06 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Section 03 1000.
PART 2 - PRODUCTS
2.01 MANUFACTURER
A. Puddle flanges shall be used for all connections to RCC water storage tanks. Details on
the Drawings shall be referred to for minimum dimensions.
KEO/19-3262-0000 22 1200/2 Facility RCC Potable-Water Tanks
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. Puddle flanges fabricated from schedule 80 wrot steel pipes and welding neck steel
flanges shall be used for connections to ferrous piping. The assembly shall be hot dip
galvanized after fabrication. For potable water tanks use stainless steel 316 pipes and
welding neck flanges.
C. Integral flanges with studs / cap nuts at wall face and loose, split flanges shall be used
to flash tanking membranes at the puddle flange.
A. Modulating Type: Angle pattern, single seated, hydraulically operated, pilot controlled,
diaphragm type, normally closed valves of cast iron construction with flanged ends
complete with pilot assembly, type `K' copper capillary lines, mounting plate, plastic float
and operating rod, adjustable stops etc. complete.
B. Delayed Action Float Valves: Angle / globe pattern, single seated, hydraulically
operated, pilot controlled, diaphragm type, normally closed valve of cast iron
construction with flanged ends complete with pilot assembly, type 'K' copper capillary
lines, mounting plate, plastic float and operating rod, adjustable stops etc. complete.
A. For potable water: Shall be fabricated from line size stainless steel 316. Minimum total
area of perforations (6 mm size) shall be four (4) times the sectional area of the pipe.
B. For Non-potable water: Food grade epoxy coated cast iron body with integral flange and
12 mm perforations Fasteners shall be of corrosion resistant material like stainless steel
or high tensile brass.
A. L-shaped pipe (schedule 80 wrot steel) with integral puddles at the water storage tank
wall, hot dip galvanized after fabrication; fitted with coated cast iron vandal proof hooded
vent cap with counter flashing collar, deep protective hood and recessed securing
screws
B. Air passages shall be covered with fine copper or plastic wire mesh to prevent the entry
of flies and pests into the tank.
A. Conduiting: Heavy duty galvanized iron conduits (surface mounted) and painted sheet
steel trunking shall be used for wiring.
B. Wiring: Stranded copper 1.5 mm2, PVC insulated wires with crimped on, sheathed
terminal lugs shall be used for all interconnecting wiring. Joints shall not be allowed in a
single wire length. Terminals shall be numbered using slip-on ferrules for quick
identification.
PART 3 - EXECUTION
A. Tank Wall: Construct tank wall and install accessories and appurtenances according to
AWWA D110 and the following:
1. Construct cast-in-place core wall with steel diaphragm. Install solid neoprene
bearing pad and (225-mm-) wide waterstop between wall and wall footing.
2. Install steel diaphragm. Apply shotcrete to interior of diaphragm to form core
wall.
a. Seal vertical joints in diaphragm with polysulfide, polyurethane, or epoxy
sealant; or double-fold with a mechanical seamer.
B. Tank Wall: Construct tank wall and install accessories and appurtenances according to
AWWA D115 and the following:
1. Install vertical prestressed wall with threadbars and screw nut anchors.
2. Sand blast exterior of core wall to provide well-pitted surface free from curing
compounds, laitance, and form oils. Use (7.3 kg) of silica sand (No. 16 grit) per
square (meter) of surface area.
3. Apply at least 3 coats of wet-mix shotcrete to exterior of tank wall in layers of at
least (10 mm) thick for a minimum total thickness of (38 mm). Apply shotcrete
when temperature range is at least (2 deg C) and rising to a maximum
temperature of (35 deg C). Do not apply shotcrete if temperature is (5 deg C) and
falling.
C. Floor: Reinforced, cast-in-place concrete. Slope floor 1.0 to 1.5 percent from highest
point to water outlet pipe. Pour monolithically without cold joints and provide
mechanical float finish.
E. Flat Slab Roof: Install reinforced, cast-in-place concrete with drop panels and support
having reinforced, cast-in-place concrete columns. Place solid neoprene bearing pads
and (150-mm) waterstop between roof and wall. If voids are present between wall and
roof after use of solid bearing pads, fill voids with closed-cell CR pads and soft mastic.
1. Install curb on roof perimeter with at least 6 downspouts spaced 60 degrees and
no more than (15 m) apart.
A. Puddle flanges shall be erected in the form work perpendicular to the wall face and
rigidly to resist displacement during pouring of concrete.
B. Verticality of the flange faces and alignment of bolt holes with connecting equipment
(valves etc.) shall be checked and ensured.
KEO/19-3262-0000 22 1200/5 Facility RCC Potable-Water Tanks
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. The openings in the form work, around puddle flanges, shall be sealed so as to avoid
leakage (and resultant honey combing) and undesirable formation of concrete.
A. Suction strainers shall be installed on all supply connections from water storage tanks,
with bend down elbows in low level connections.
C. Prime-Coat Touchup: Apply primer to cleaned areas and where shop finish has been
damaged during shipping, handling, and erection. Apply prime coat to a dry film
thickness of (0.08 to 0.13 mm) for tank interior and to a dry film thickness of (0.05 to
0.08 mm) for exterior tank and support surfaces.
D. Tank Shell Interior Finish Coats: Apply 2 coats of interior finish paint above bottom ring
to a dry film thickness of (0.1 to 0.13 mm). Apply interior finish paint to surfaces below
bottom ring to a dry film thickness of (0.2 to 0.25 mm).
E. Tank Shell and Steel Support Exterior Coats: Apply intermediate paint to a dry film
thickness of (0.05 to 0.08 mm). Apply finish paint to a dry film thickness of (0.05 to 0.08
mm).
H. Tank Exterior Lettering and Logo: Apply one coat or two coats of urethane paint to a dry
film thickness of (0.05 to 0.08 mm) for each application.
I. Overflow Pipe: Paint pipe exterior that is outside tank and structure as indicated for tank
exterior.
K. Do not paint if ambient temperature is less than (10 deg C) or is expected to drop below
(5 deg C) in the next 18 hours. Do not paint if temperature of steel surface is higher
than (52 deg C). Do not apply paint if surfaces are wet or damp, if precipitation is
expected, or if relative humidity will exceed 85 percent. Do not spray paint when wind
velocity exceeds (24 km/h). Maintain at least a 24-hour waiting period between coats.
Provide adequate ventilation in tank during painting to maintain clear atmosphere and
provide explosion-proof flood lighting and spot lighting.
L. Complete daily painting to allow time for paint to dry before condensation is expected.
A. Inserts shall be installed in the form work for tank walls in a manner similar to that of
puddle flanges and good alignment shall be attained.
B. Fasteners and cap nuts of corrosion resistant material shall be used for fixing the ladder
to the tank walls.
A. The power supply requirements to the system shall be coordinated with the Electrical
works. Conduiting and wiring to the source shall be included in this Section.
A. Blank flanges / plugs shall be temporarily installed on the piping connections to enable
the civil works contractor to test the water tightness of concrete tanks.
B. The inside of the tank shall be thoroughly cleaned of all dirt, washed down with water
and drained.
A. The Employer shall be furnished with guarantee and warranty certificates, duly
registered with the manufacturer.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes potable and non-potable water storage tanks and related
accessories for indoor installation.
1.02 DEFINITIONS
1.03 SUBMITTALS
B. ASME Compliance for Steel Tanks: Fabricate and label steel, potable-water storage
tanks to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1,
where indicated.
C. ASME Compliance for GRP Tanks: Fabricate and label GRP, potable-water storage
tanks to comply with ASME Boiler and Pressure Vessel Code: Section X, where
indicated.
D. Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic
potable-water storage tanks and components. Include appropriate NSF marking.
E. Comply with NSF 61, "Drinking Water System Components--Health Effects, Sections 1
to 9," for potable-water storage tanks. Include appropriate NSF marking.
1.05 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 QUALIFICATIONS
The manufacturer shall have a minimum of twenty years’ experience in the design,
manufacture and testing of pumps
B. Tanks should be suitable for storage at atmospheric pressure, of potable cold drinking
water at 50 deg. C.
C. Supplier shall take necessary measures to satisfy relevant authority that potable water
tanks supplied for use within its domain meets all requirements detailed here forth.
This shall be repeatedly done every five years or as and when called for by the
authority having jurisdiction. Whenever the raw ingredient, composition or process of
manufacture of a particular component part is changed or modified, the affected
KEO/19-3262-0000 22 1223/2 Indoor Potable Water Storage Tanks
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
component part shall have to be tested and certified as to its fitness for use and
compliance with articles detailed here forth. All testing and inspection costs shall be
borne by the Contractor.
D. No fiber shall project out of any tank panel. The internal surface of the shell or panel
shall be smoothly finished and free of defects such as crazing, delaminating, blister,
wrinkles, crevice and pinholes to prevent sticking of foreign matters such as dust,
moss, algae, bacteria, scale formation and rust. If necessary, tank interior should be
coated with an approved material for algae resistance.
E. The use of in-situ G.R.P. lamination inside the tank for whatever purpose it may be,
shall not be permitted.
F. Flexible connectors shall be used – wherever necessary – to avoid stress and vibration
transfer to the water tank.
H. Tanks shall be erected, tested and commissioned for use only by the manufacturer or
by an installer approved by him.
I. Upon completion of erection, tank shall be tested as per the manufacturer’s guideline
and then cleaned and disinfected be the erector or under his direct supervision. Water
shall be sampled and tested.
J. Supplier shall maintain and preserve a record of every tank sale, until the expiry of the
tank guarantee, updating, it upon completion of every stage of work to reflect the
required information detailed below.
A record shall be kept ready for inspection – along with relevant certificates – by the
relevant ministry authorized personnel and shall contain the following information:
1. Tank type, size, capacity, serial number and other specific details.
2. Client name & address.
3. Location of point of use (Plot & Sector).
4. Name of tank assembler.
5. Date of sale.
6. Date of erection completion.
7. Date of successful testing.
8. Ministry approval date.
K. A name plate (stamp may be acceptable) of size not less than 20 x 15 cm should be
securely imposed to tank exterior in a clearly visible and accessible location preferably
on tank side, by stainless steel 316 bolts and nuts or similar approved arrangement.
Plate shall be made of material not affected by weather conditions. The following data
should be engraved on the plate with lettering color different to that of the plate. Color
shall not be affected by weather conditions:
M. Sides, bottom, and roof panels shall have uniform mass per unit area. Unless
otherwise specified, 6 mm minimum thickness and 17.5 kg/m2 minimum mass should
be used.
N. Refer to the related drawings for details such as mass, dimensions, nominal and
effective capacity, tank type, location etc.
O. The centre of the panels to be curved/ pressed to evenly distribute the stress applied
to it.
P. The roof panels shall be embossed for ultraviolet resistance and slip resistance (for
workman).
Q. The tank panel joints shall be completely sealed with a special gasket which must not
deteriorate under repeated changes of temperature for a long time.
R. The manhole panel shall have a 600mm diameter hinged type manhole hatch.
S. All domestic water tanks used for drinking purpose shall be protected from excessive
heat, direct sun and ultra-violet rays. Tanks exterior shell/panel fasteners, supports,
etc. shall be protected against weather conditions for the duration of the Guarantee
Period. Tanks shall either be insulated, kept in-doors or under a protective structural
shed.
2.07 TRANSPARENCY:
KEO/19-3262-0000 22 1223/4 Indoor Potable Water Storage Tanks
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
A. Tank should be opaque to help reduce evaporation of disinfectant and inhibit Algae
growth. Maximum measured light transmission value inside a closed cover; ready for
use thank shall not exceed 0.1%.
2.28 REFERENCES:
Unless elsewhere specified, latest of these standards shall apply:
A. Conduiting: Heavy duty galvanized iron conduits (surface mounted) and painted sheet
steel trunking shall be used for wiring.
B. Wiring: Stranded copper (1.5 mm2), PVC insulated wires with crimped on, sheathed
terminal lugs shall be used for all interconnecting wiring. Joints shall not be allowed in
a single wire length. Terminals shall be numbered using slip-on ferrules for quick
identification.
A. Test and inspect potable-water storage tanks according to the following tests and
inspections and prepare test reports:
1. Non-pressure Testing for Potable-Water Storage Tanks: Fill tanks to water
operating level to ensure structural integrity and freedom from leaks. Hold
water level for two hours with no drop in water level. Repair or replace tanks
that fail test with new tanks, and repeat until test is satisfactory.
PART 3 - EXECUTION
A. Install concrete bases of dimensions indicated for tanks. Refer to Division 22 Section
"Common Work Results for Plumbing."
3.02 INSTALLATION
A. Install water storage tanks on concrete bases, level and plumb, firmly anchored.
Arrange so devices needing servicing are accessible.
1. Install horizontal tanks on concrete piers and factory-fabricated or fabricated
steel supports and saddles.
F. After installing tanks with factory finish, inspect finishes and repair damages to
finishes.
3.03 CONNECTIONS
C. Connect water piping to water storage tanks with unions or flanges and with shutoff
valves. Connect tank drains with shutoff valves and discharge over closest floor
drains.
1. General-duty valves are specified in Division 22 Section "General-Duty Valves
for Plumbing Piping."
a. Valves (DN 50) and Smaller: Gate or ball.
b. Valves (DN 65) and Larger: Gate or butterfly.
c. Drain Valves: (DN 20) gate or ball valve. Include outlet with, or nipple
in outlet with, ASME B1.20.7, 3/4-11.5NH thread for garden-hose
service, threaded cap, and chain.
2. Water Piping Connections: Make connections to dissimilar metals with
dielectric fittings. Dielectric fittings are specified in Division 22 Section
"Common Work Results for Plumbing."
B. Filling Procedures: Follow manufacturer's written procedures. Fill tanks with water to
operating level.
3.05 CLEANING
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the following for storm, soil, waste, and vent piping inside the
building:
1. Pipe, tube, and fittings.
2. Special pipe fittings.
3. Encasement for underground piping.
1.02 DEFINITIONS
1.04 SUBMITTALS
A. Product Data and Samples: For pipe, tube, fittings, and couplings.
B. Shop Drawings:
KEO/19-3262-0000 22 1300/1 Sanitary Waste and Vent Piping & Storm Water Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Design Calculations.
2. Controlled – Flow Storm Drainage System: Include calculation, plans and
details.
A. Piping materials shall bear label, stamp, or other markings of specified testing agency.
B. Comply with NSF 14, "Plastics Piping Systems Components and Related Materials," for
plastic piping components. Include marking with "NSF-dwv" for plastic drain, waste, and
vent piping; "NSF-drain" for plastic drain piping; "NSF-tubular" for plastic continuous
waste piping; and "NSF-sewer" for plastic sewer piping.
PART 2 - PRODUCTS
A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and
joining materials.
A. UPVC pipes and fittings: DIN 1953 & 8062 / 1986 class 6 bar.
2.04 JOINTS
A. Type of joints.
1. UPVC: Solvent welded joints. Use flanged spigots / sockets where required.
B. Pressure ratings of joints. All figures stated are working water / air pressures (WOG) at
121 deg.C (250 deg.F).
1. UPVC: 1034 Kpa (150 psig)
C. Dielectric connections: Use dielectric unions with one end malleable iron threaded and
the other end copper solder for pipe sizes 50 mm (2 inch) nom. dia. and under. Use
KEO/19-3262-0000 22 1300/2 Sanitary Waste and Vent Piping & Storm Water Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
dielectric flanged fittings for pipe sizes 65 mm (2 1/2 inch) nom. dia. and above. Both
unions and flanges shall have water impervious isolation barrier certified to withstand a
minimum 600 volts on a dry line with no flashover.
D. All flanges, unions and couplings shall be pressure rated as the pipe joints.
D. Wall-Penetration Fittings: Compound, ductile-iron coupling fitting with sleeve and flexing
sections for up to 20-degree deflection, gaskets, and restrained-joint ends complying
with AWWA C110 or AWWA C153. Include AWWA C111, ductile-iron glands, rubber
gaskets, and steel bolts.
A. All concrete elements of any class for drainage works, whether precast or in-situ, shall
be carried out in accordance with other Section.
1. Plain cement concrete: This work shall include, but not by way of limitation,
supply and casting of sulphate resisting concrete as shown on Drawings and
shall be of the following classes (unless specified elsewhere to the contrary):
a. Class C 140 for bed or haunch or encasement to pipes.
b. Class C 140 for benching including 2 cm thick, smooth hard finish.
c. Class C140 for blinding
2. Reinforced cement concrete: This work shall include, but not by way of
limitation, supply and casting of all class C 300 Ordinary Portland Cement
reinforced concrete elements, whether precast or in-situ, incorporated in the
storm water works as shown in the drawings.
B. Reinforced concrete elements shall be measured by number and the rate shall include
for; but not by way of limitation; temporary work, formwork, moulds, reinforcement
during testing, expansion and construction joints and all other things necessary to
accomplish the work in accordance with the Drawings and Specifications and the
instruction of the Engineer.
B. Step irons shall be of galvanized cast iron conforming to BS 1247. The weight of the
step iron shall not be less than 3.20 lbs. and shall be 10 inch long and 6 inch wide.
C. The sanitary house connection shall be carried out with the external inspection chamber
using the Vitrified Clay pipes conforming to B.S.65.
2.10 STEELWORK
A. Structural steel shall comply with the requirements of BS 15. Dimensions and
properties of beams, T-bars etc. shall comply with the requirements of BS 4.
B. Bolts, nuts, etc. shall comply with the requirements of BS 916 or BS 1768 whichever is
applicable.
C. Welding shall be carried out by approved welders in accordance with the requirements
of BS 1856 or BS 2642, whichever shall be applicable and BS 2645. Electrodes shall
fulfill the requirements of BS 639.
Unless otherwise specified, structural steel work shall be rust protected in general
conformance with BS 5493 and as follows. After erection all rust and scale and loose
paint shall be removed by means of sand blasting or by steel wire brush or other
approved means. All surfaces shall immediately thereafter be coated with two coats of
bituminous paint, thick Inertol 49 or similar approved product. The coating shall be
applied in dry weather. Prior to the second coating, the first coating shall be absolutely
dry.
PART 3 - EXECUTION
3.01 EXCAVATION
A. Refer to Division 31 Section "Earth Moving" for excavating, trenching, and backfilling.
A. Installations exposed to sunlight shall remain of cast iron conforming to the British
standard (B.S 416) and shall be connected to UPVC pipes using special fitting made of
UPVC and rubber.
--------------------------------------------------------------------------------------------------
A. Install cleanouts at grade and extend to where building sanitary drains connect to
building sanitary sewers.
B. Install wall-penetration fitting at each service pipe penetration through foundation wall.
Make installation watertight.
C. Make changes in direction for soil, storms and waste drainage and vent piping using
appropriate branches, bends, and long-sweep bends. Sanitary tees and short-sweep
1/4 bends may be used on vertical stacks if change in direction of flow is from horizontal
to vertical. Use long-turn, double Y-branch and 1/8-bend fittings if 2 fixtures are
installed back to back or side by side with common drain pipe. Straight tees, elbows,
and crosses may be used on vent lines. Do not change direction of flow more than 90
degrees. Use proper size of standard increasers and reducers if pipes of different sizes
are connected. Reducing size of drainage piping in direction of flow is prohibited.
D. Lay buried building drainage piping beginning at low point of each system. Install true to
grades and alignment indicated, with unbroken continuity of invert. Place hub ends of
piping upstream. Install required gaskets according to manufacturer's written
instructions for use of lubricants, cements, and other installation requirements. Maintain
swab in piping and pull past each joint as completed.
E. Install soil, storm and waste drainage and vent piping at the following minimum slopes,
unless otherwise indicated:
1. Building Sanitary Drain: 2 percent downward in direction of flow for piping NPS 3
(DN 80) and smaller; 1 percent downward in direction of flow for piping NPS 4
(DN 100) and larger.
2. Horizontal Sanitary/storm Drainage Piping: 1 percent downward in direction of
flow.
3. Vent Piping: 1 percent down toward vertical fixture vent or toward vent stack.
F. Install UPVC soil and waste drainage and vent piping according to ASTM D 2665.
G. Do not enclose, cover, or put piping into operation until it is inspected and approved by
authorities having jurisdiction.
B. Soldered Joints: Use ASTM B 813, water-flushable, lead-free flux; ASTM B 32, lead-
free-alloy solder; and ASTM B 828 procedure, unless otherwise indicated.
KEO/19-3262-0000 22 1300/5 Sanitary Waste and Vent Piping & Storm Water Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. UPVC Nonpressure Piping Joints: Join piping according to ASTM D 2665.
3.05 CONNECTIONS
B. Connect soil and waste piping to exterior sanitary sewerage piping. Use transition fitting
to join dissimilar piping materials.
B. Re-inspection: If authorities having jurisdiction find that piping will not pass test or
inspection, make required corrections and arrange for re-inspection.
C. Reports: Prepare inspection reports and have them signed by authorities having
jurisdiction.
D. Test sanitary, storm drainage and vent piping according to procedures of authorities
having jurisdiction or, in absence of published procedures, as follows:
1. Test for leaks and defects in new piping and parts of existing piping that have
been altered, extended, or repaired. If testing is performed in segments, submit
separate report for each test, complete with diagram of portion of piping tested.
2. Leave uncovered and unconcealed new, altered, extended, or replaced drainage
and vent piping until it has been tested and approved. Expose work that was
covered or concealed before it was tested.
3. Roughing-in Plumbing Test Procedure: Test drainage and vent piping, except
outside leaders, on completion of roughing-in. Close openings in piping system
and fill with water to point of overflow, but not less than 10-foot head of water (30
kPa). From 15 minutes before inspection starts to completion of inspection,
water level must not drop. Inspect joints for leaks.
KEO/19-3262-0000 22 1300/6 Sanitary Waste and Vent Piping & Storm Water Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4. Finished Plumbing Test Procedure: After plumbing fixtures have been set and
traps filled with water, test connections and prove they are gastight and
watertight. Plug vent-stack openings on roof and building drains where they
leave building. Introduce air into piping system equal to pressure of 1-inch wg
(250 Pa). Use U-tube or manometer inserted in trap of water closet to measure
this pressure. Air pressure must remain constant without introducing additional
air throughout period of inspection. Inspect plumbing fixture connections for gas
and water leaks.
5. Repair leaks and defects with new materials and retest piping, or portion thereof,
until satisfactory results are obtained.
6. Test Procedure: Test storm drainage piping, exceptout leaders, on completion of
roughing-in. Close openings in piping system and fill with water to point of
overflow, but not less than 10 foot head of water (30 kPa). From 15 minutes
before inspection starts to completion of inspection, water level must not drop.
Inspect joints for leaks.
7. Prepare reports for tests and required corrective action.
3.07 CLEANING
B. Protect drains during remainder of construction period to avoid clogging with dirt and
debris and to prevent damage from traffic and construction work.
C. Place plugs in ends of uncompleted piping at end of day and when work stops.
3.08 SETTING OUT AND EXCAVATION OF TRENCHES FOR BELOW GRADE MAINS
A. Trenches shall be excavated only after completion of site development work like
backfilling, if any. Care shall be taken to ensure that no heavy equipment shall be
worked or moved over piping, which is not designed to take up such loads.
B. Clear the existing ground levels along the line of all mains, particularly at all manholes,
building connections etc.
C. Where long lengths of piping mains are to be laid in trenches at slight slope, sight rails
should be fixed across the trench at intervals of at least 5 meters at a height equal to the
length of the boning rod to be used above the required invert level of the drain or sewer
at the point where the sight rail is fixed. There shall be not less than two sight rails in
position on each length of the main under construction.
KEO/19-3262-0000 22 1300/7 Sanitary Waste and Vent Piping & Storm Water Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
D. The trench shall be excavated to the actual required depth such that the pipe shall bear
uniformly on undisturbed ground at every point between joint holes.
E. The Contractor shall examine any unfitting or weak ground material which may be found
below the pipe laying level and report the same in writing to the Engineer, before laying
any pipe. In such cases, the unsuitable material shall be removed and made up by
backfilling, at additional cost to the Owner.
A. Handle pipes with utmost care so as not to subject the pipes to shocks which may crack
or break the internal lining, if any. Cement lined pipes which are cut to length on site
shall be tapered at their spigot ends by a grinder and a fast drying coal tar coat applied
at the uncoated areas.
B. The pipes shall be laid directly on the undisturbed bottom of the trench with special
recesses made for the joints or placed on a concrete bed. The pipes must be aligned
carefully both in line and level. Wooden supports must not be placed under the pipes.
Precautions shall be taken to prevent dirt from entering the pipe.
C. Ductile iron pipes shall be wrapped up with polyethylene sleeving before laying.
Adhesive tapes shall be used to secure the sleeving at socket and spigot ends. Plastic
coated wire shall be used to secure the encasement at every one third length of the
pipe. After jointing is done and testing completed, encasement shall be pulled to close
the whole joint and be secured with plastic coated wire strapping. The pipes shall be laid
with the folded part of the polyethylene encasement on the crown of the piping.
D. Piping shall be protected against the ingress of foreign material before the pipe is placed
in the trench. If the case is such that the pipe can not be laid, in the trench and in place,
without getting earth into it; each end shall be covered with a heavy, tightly woven
canvas bag of suitable size before lowering the pipe into the trench. The bag shall be
left there until the connection is to be made to the adjacent pipe.
E. When jointing pipes, a mark shall be made to check the position of the end of the barrel.
Leave a gap of 5 to 10mm between the ends of the pipes, for piping with flexible joints.
F. The joints shall be left exposed until the line is pressure tested and approved by the
Engineer.
G. Deviations from given levels may not be greater than + or - 1 cm at any point and
gradients not greater than 1/20 of the given value.
A. All surplus, suitable and approved excavation material shall be used for backfilling the
trenches.
B. All backfill material shall be free of cinders, ashes, refuse, vegetable or organic matter,
boulders, stones or other material which are unsuitable for the purpose, in the opinion of
the Engineer.
C. Excavations shall be backfilled without unnecessary delay, but not before completion of
testing of the piping. The first 30 cm fill shall only be compacted by hand tamping;
KEO/19-3262-0000 22 1300/8 Sanitary Waste and Vent Piping & Storm Water Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
subsequent layers being compacted by power tampers as approved by the Engineer.
No heavy mechanical equipment shall be used for backfilling or compaction.
A. Frame of manhole cover shall not be cast in together with roof slab of manhole.
B. Covers and frames shall be fixed in such a way to match adjacent surface levels with
tolerance not exceeding + or -3mm. Before the Defects Liability Period expires, check
all manhole covers and readjust them if they are in excess of above mentioned
tolerance.
C. Fix all cast iron accessories to concrete manholes using cement and sand mortar (1:3)
3.12 PROTECTION: Give the following protective coating / wrapping to piping. All piping
above louvered ceilings shall be painted black.
A. Buried plastic piping under grade slabs within or outside building lines and in areas
subjected to traffic loading:
1. Encasement with minimum 10cm thick, class K 140, plain concrete, 20mm (3/4
inch) thick bitumen emulsion impregnated fiber board and other suitable material
shall be provided across the encasement at flexible joints to maintain flexibility of
the piping.
2. Coloured, metal coated, plastic foil warning grids.
E. Exposed UPVC Piping: Protect plumbing vents exposed to sunlight with two coats of
water based latex paint.
END OF SECTION
KEO/19-3262-0000 22 1300/9 Sanitary Waste and Vent Piping & Storm Water Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
SECTION 22 1319
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 DEFINITIONS
1.03 SUBMITTALS
C. Shop Drawings: Show fabrication and installation details for frost-resistant vent
terminals.
1. Wiring Diagrams: Power, signal, and control wiring.
A. Drainage piping specialties shall bear label, stamp, or other markings of specified
testing agency.
C. Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic
sanitary piping specialty components.
1.05 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
PART 2 - PRODUCTS
2.02 CLEANOUTS
A. Floor Cleanouts:
1. Floor cleanouts shall be made of UPVC with chrome plated or stainless steel
closure cover.
B. Ground Cleanouts:
1. Ground cleanouts shall be made of UPVC with 300 x 300 mm light duty,
single seal cast iron cover and frame. CLEANOUT to be written in Arabic and
English.
2. Ground cleanouts to be installed as per the tiles levels.
A. Open Drains:
1. Description: Shop or field fabricate from ASTM A 74, Service class, hub-and-
spigot, cast-iron, soil-pipe fittings. Include P-trap, hub-and-spigot riser section;
and where required, increaser fitting joined with ASTM C 564, rubber gaskets.
2. Size: Same as connected waste piping with increaser fitting of size indicated.
D. Vent Caps:
1. Description: Cast-iron body with threaded or hub inlet and vandal-proof design.
Include vented hood and setscrews to secure to vent pipe.
2. Size: Same as connected stack vent or vent stack.
E. Expansion Joints:
1. Standard: ASME A112.21.2M.
2. Body: Cast iron with bronze sleeve, packing, and gland.
3. End Connections: Matching connected piping.
4. Size: Same as connected soil, waste, or vent piping.
B. Copper Sheet: ASTM B 152/B 152M, of the following minimum weights and
thicknesses, unless otherwise indicated:
1. General Applications: 12 oz./sq. ft. (3.7 kg/sq. m or 0.41-mm thickness).
2. Vent Pipe Flashing: 8 oz./sq. ft. (2.5 kg/sq. m or 0.27-mm thickness).
C. Zinc-Coated Steel Sheet: ASTM A 653/A 653M, with 0.20 percent copper content and
0.04-inch (1.01-mm) minimum thickness, unless otherwise indicated. Include G90
(Z275) hot-dip galvanized, mill-phosphatized finish for painting if indicated.
F. Metal Accessories: Sheet metal strips, clamps, anchoring devices, and similar
accessory units required for installation; matching or compatible with material being
installed.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Refer to Division 22 Section "Common Work Results for Plumbing" for piping joining
materials, joint construction, and basic installation requirements.
B. Install cleanouts in aboveground piping and building drain piping according to the
following, unless otherwise indicated:
1. Size same as drainage piping up to NPS 4 (DN 100). Use NPS 4 (DN 100) for
larger drainage piping unless larger cleanout is indicated.
2. Locate at each change in direction of piping greater than 45 degrees.
3. Locate at minimum intervals of 50 feet (15 m) for piping NPS 4 (DN 100) and
smaller and 100 feet (30 m) for larger piping.
4. Locate at base of each vertical soil and waste stack.
KEO/19-3262-0000 22 1319/4 Sanitary, Storm and Waste Piping Specialties
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. For floor cleanouts for piping below floors, install cleanout deck plates with top flush with
finished floor.
D. For cleanouts located in concealed piping, install cleanout wall access covers, of types
indicated, with frame and cover flush with finished wall.
E. Install floor drains at low points of surface areas to be drained. Set grates of drains
flush with finished floor, unless otherwise indicated.
1. Position floor drains for easy access and maintenance.
2. Set floor drains below elevation of surrounding finished floor to allow floor
drainage. Set with grates depressed according to the following drainage area
radii:
a. Radius, 30 Inches (750 mm) or Less: Equivalent to 1 percent slope, but
not less than 1/4-inch (6.35-mm) total depression.
b. Radius, 30 to 60 Inches (750 to 1500 mm): Equivalent to 1 percent slope.
c. Radius, 60 Inches (1500 mm) or Larger: Equivalent to 1 percent slope,
but not greater than 1-inch (25-mm) total depression.
3. Install floor-drain flashing collar or flange so no leakage occurs between drain
and adjoining flooring. Maintain integrity of waterproof membranes where
penetrated.
4. Install individual traps for floor drains connected to sanitary building drain, unless
otherwise indicated.
F. Install roof flashing assemblies on sanitary stack vents and vent stacks that extend
through roof.
G. Install flashing fittings on sanitary stack vents and vent stacks that extend through roof.
I. Assemble open drain fittings and install with top of hub 1 inch (25 mm) above floor.
J. Install sleeve flashing device with each riser and stack passing through floors with
waterproof membrane.
L. Install expansion joints on vertical stacks and conductors. Position expansion joints for
easy access and maintenance.
N. Install traps on plumbing specialty drain outlets. Omit traps on indirect wastes unless
trap is indicated.
O. Install escutcheons at wall, floor, and ceiling penetrations in exposed finished locations
and within cabinets and millwork. Use deep-pattern escutcheons if required to conceal
protruding pipe fittings.
P. Install roof drains at low points of roof areas according to roof membrane manufacturer's
written installation instructions. Roofing materials are specified in Division 07.
1. Install roof-drain flashing collar or flange so that there will be no leakage between
drain and adjoining roofing. Maintain integrity of waterproof membranes where
penetrated.
2. Position roof drains for easy access and maintenance.
KEO/19-3262-0000 22 1319/5 Sanitary, Storm and Waste Piping Specialties
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
Q. Install manufactured, gray-iron downspout boots at grade with top 6 inches (152 mm)
above grade. Secure to building wall.
3.02 CONNECTIONS
A. Fabricate flashing from single piece unless large pans, sumps, or other drainage shapes
are required. Join flashing according to the following if required:
1. Lead Sheets: Burn joints of lead sheets 6.0-lb/sq. ft. (30-kg/sq. m), 0.0938-inch
(2.4-mm) thickness or thicker. Solder joints of lead sheets 4.0-lb/sq. ft. (20-
kg/sq. m), 0.0625-inch (1.6-mm) thickness or thinner.
2. Copper Sheets: Solder joints of copper sheets.
B. Install sheet flashing on pipes, sleeves, and specialties passing through or embedded in
floors and roofs with waterproof membrane.
1. Pipe Flashing: Sleeve type, matching pipe size, with minimum length of 10
inches (250 mm), and skirt or flange extending at least 8 inches (200 mm)
around pipe.
2. Sleeve Flashing: Flat sheet, with skirt or flange extending at least 8 inches (200
mm) around sleeve.
3. Embedded Specialty Flashing: Flat sheet, with skirt or flange extending at least
8 inches (200 mm) around specialty.
E. Install flashing for piping passing through roofs with counterflashing or commercially
made flashing fittings, according to Division 07 Section "Sheet Metal Flashing and Trim."
F. Extend flashing up vent pipe passing through roofs and turn down into pipe, or secure
flashing into cast-iron sleeve having calking recess.
G. Fabricate and install flashing and pans, sumps, and other drainage shapes.
3.04 PROTECTION
A. Protect drains during remainder of construction period to avoid clogging with dirt or
debris and to prevent damage from traffic or construction work.
B. Place plugs in ends of uncompleted piping at end of each day or when work stops.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the following types of interceptors outside the building:
1. Grease interceptors.
2. Oil interceptors.
3. Sand interceptors.
4. Sediment interceptors.
1.02 DEFINITIONS
1.03 SUBMITTALS
A. Product Data: For each type of metal and plastic interceptor indicated. Include materials
of fabrication, dimensions, rated capacities, retention capacities, operating
characteristics, size and location of each pipe connection and accessories for the
following:
1. FOG disposal systems.
2. Grease interceptors.
3. Grease removal devices.
4. Oil interceptors.
B. Shop Drawings: For each type and size of cast-in-place-concrete interceptor indicated.
1. Include materials of construction, dimensions, rated capacities, retention
capacities, location and size of each pipe connection, furnished specialties, and
accessories.
2. Include reports and calculations for design mixes of concrete.
C. Shop Drawings: For each type and size of precast concrete interceptor indicated.
1. Include materials of construction, dimensions, rated capacities, retention
capacities, location and size of each pipe connection, furnished specialties, and
accessories.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
1. Cultures: Provide 3.8-L bottles of bacteria culture recommended by
manufacturer of FOG disposal systems equal to 200 percent of amount installed,
but no fewer than 3.8-L bottles.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Grease Interceptors:
1. Standard: ASME A112.14.3 and PDI-G101, for intercepting and retaining fats,
oils, and greases from food preparation wastewater.
2. Plumbing and Drainage Institute Seal: Required.
3. Body Material: Cast iron.
4. Interior Lining: Corrosion-resistant enamel.
5. Exterior Coating: Corrosion-resistant enamel.
6. Body Extension: Required.
7. End Connections: Flanged.
8. Cleanout: Integral or field installed on outlet.
9. Mounting: Recessed, flush with floor.
10. Flow-Control Fitting: Required.
11. Operation: Automatic recovery.
B. Oil Interceptors: Construct bottom, sidewalls, and top of reinforced, cast- in-place
concrete. Include waste oil and vent connections, manholes and piping or openings to
draw off oil and to permit wastewater flow.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Install precast concrete interceptors according to ASTM C 891. Set level and plumb.
B. Clean and prepare concrete surfaces to be field painted. Remove loose efflorescence,
chalk, dust, dirt, grease, oils, and release agents. Roughen surface as required to
remove glaze. Paint the following concrete surfaces as recommended by paint
manufacturer:
1. Cast-in-Place-Concrete Interceptors: All exterior, except bottom and all interior.
2. Precast Concrete Interceptors: All exterior and interior.
D. Clean and prepare metal surfaces to be field painted according to SSPC- PA 1. Paint
the following metal surfaces according to SSPC-PA 1 and SSPC-Paint 16:
1. Metal Interceptors: All surfaces except baskets, screens, and strainers.
2. Plastic Interceptors: All metal surfaces except baskets, screens, and strainers.
KEO/19-3262-0000 22 1323/3 Sanitary Waste Interceptors
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Metal Manhole Frames and Covers Including Grates all surfaces.
4. Do not paint metal surfaces with factory-applied, corrosion-resistant coating.
F. Prepare and paint metal components, to be field painted, according to SSPC-Paint 16.
3.02 CONNECTIONS
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the following sewage pumps and accessories for sanitary
drainage piping systems in buildings:
1. Submersible sewage pumps.
2. Packaged, submersible sewage pump units.
3. Packaged, wastewater pump units.
1.02 SUBMITTALS
A. Product Data: For each type and size of sewage pump specified. Include certified
performance curves with operating points plotted on curves; and rated capacities of
selected models, furnished specialties, and accessories.
C. Operation and Maintenance Data: For each sewage pump to include in emergency,
operation, and maintenance manuals.
a. Name of manufacturer.
c. Certified ratings.
A. Retain shipping flange protective covers and protective coatings during storage.
1.05 WARRANTY
A. When warranties are required, verify with Owner's counsel that special warranties stated
in this Article are not less than remedies available to Owner under prevailing local laws.
1.06 COORDINATION
A. Provide complete spare parts and maintenance equipment for two (2) years
maintenance of all the equipment furnished under this section. Spare parts in a location
designated by the Engineer or the Employer.
B. All spare parts and maintenance equipment shall be provided in original packing, clearly
identified and labelled. Provide complete schedules of spare parts and maintenance
equipment clearly cross-referenced with the “Record Drawings” and maintenance
instructions and manuals.
C. All spare parts and maintenance equipment shall be as recommended by the equipment
manufacturer and shall be subject to the final approval of the Engineer.
D. Spare parts and maintenance equipment provided shall, as a minimum, equal the items
used during the two (2) years maintenance period. The Contractor shall carefully log all
spare parts utilized during maintenance period.
E. Provide spare parts and maintenance equipment for all pumps, control panel etc.
requiring maintenance and replacement.
F. Provide two new complete sets of tools for the proper operation, routine maintenance
and adjustment of all components and equipment.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
C. Pump Discharge Piping: Factory or field fabricated, UPVC pipes, schedules 40 / PN16 ,
ASTM D 1785.
D. Controls: NEMA 250, Type 1enclosure, pedestal mounted unless wall mounting is
indicated; with three mechanical- or mercury-float or micropressure switches in
NEMA 250, Type 6 enclosures; mounting rod; and electric cables. Include automatic
alternator to alternate operation of pump units on successive cycles and to operate
multiple units if one pump cannot handle load.
KEO/19-3262-0000 22 1329/4 Sanitary Sewerage Pumps
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Float Guide: Pipe or other restraint for floats and rods in basins of depth greater
than 60 inches (1500 mm).
2. High-Water Alarm: Rod-mounted, NEMA 250, Type 6 enclosure with
mechanical- or mercury-float or micropressure -switch alarm matching control
and electric bell; 120-V ac, with transformer and contacts for remote alarm bell.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine roughing-in for plumbing piping to verify actual locations of sanitary drainage
and vent piping connections before sewage pump installation.
3.02 CONCRETE
A. Install concrete bases of dimensions indicated for pumps and controllers. Refer to
Division 22 Section "Common Work Results for Plumbing."
1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise
indicated, install dowel rods on 18-inch (450-mm) centers around full perimeter of
base.
2. For supported equipment, install epoxy-coated anchor bolts that extend through
concrete base and anchor into structural concrete floor.
3. Place and secure anchorage devices. Use setting drawings, templates,
diagrams, instructions, and directions furnished with items to be embedded.
4. Install anchor bolts to elevations required for proper attachment to supported
equipment.
3.03 INSTALLATION
C. Suspend wet-pit-mounted, vertical sewage pumps from basin and pit covers. Make
direct connections to sanitary drainage piping.
D. Set submersible sewage pumps on basin and pit floors. Make direct connections to
sanitary drainage piping.
1. Anchor guide-rail supports to basin and pit bottoms and sidewalls or covers.
Install pumps so pump and discharge pipe disconnecting flanges make positive
seals when pumps are lowered into place.
E. Install sewage pump basins and connect to drainage and vent piping. Brace interior of
basins according to manufacturer's written instructions to prevent distortion or collapse
during concrete placement. Set basin cover and fasten to basin top flange. Install cover
so top surface is flush with finished floor.
F. Construct sewage pump pits and connect to drainage and vent piping. Set pit curb
frame recessed in and anchored to concrete. Fasten pit cover to pit curb flange. Install
cover so top surface is flush with finished floor.
G. Install packaged, wastewater pump unit basins on floor or concrete base unless
recessed installation is indicated. Make direct connections to drainage and vent piping.
3.04 CONNECTIONS
A. Piping installation requirements are specified in Division 22 Section "Sanitary Waste and
Vent Piping." Drawings indicate general arrangement of piping, fittings, and specialties.
C. Connect sanitary drainage and vent piping to pumps. Install discharge piping equal to
or greater than size of pump discharge piping. Install vent piping equal to or greater
than size of pump basin vent connection. Refer to Division 22 Section "Sanitary
Drainage and Vent Piping."
1. Install check and shutoff valves on discharge piping from each pump. Install
unions on pumps having threaded pipe connections. Install valves same size as
connected piping. Refer to Division 22 Section "General-Duty Valves for
Plumbing Piping" for general-duty valves for sanitary waste piping.
3.06 DEMONSTRATION
END OF SECTION
SUMP PUMPS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the following sump pumps and accessories, inside the building, for
building storm drainage systems:
1. Submersible sump pumps.
2. Sump pump basins and pits.
1.02 SUBMITTALS
A. Product Data: For each type and size of sump pump specified. Include certified
performance curves with operating points plotted on curves, and rated capacities of
selected models, furnished specialties, and accessories.
C. Operation and Maintenance Data: For each sump pump to include in emergency,
operation, and maintenance manuals.
C. Regulatory Requirements
a. Name of manufacturer.
c. Certified ratings.
A. Retain shipping flange protective covers and protective coatings during storage.
1.05 COORDINATION
1.06 WARRANTY
A. When warranties are required, verify with Owner's counsel that special warranties stated
in this Article are not less than remedies available to Owner under prevailing local laws.
A. Provide complete spare parts and maintenance equipment for two (2) years
maintenance of all the equipment furnished under this section. Spare parts in a location
designated by the Engineer or the Employer.
C. All spare parts and maintenance equipment shall be as recommended by the equipment
manufacturer and shall be subject to the final approval of the Engineer.
D. Spare parts and maintenance equipment provided shall, as a minimum, equal the items
used during the two (2) years maintenance period. The Contractor shall carefully log all
spare parts utilized during maintenance period.
E. Provide spare parts and maintenance equipment for all pumps, control panel etc.
requiring maintenance and replacement.
F. Provide two new complete sets of tools for the proper operation, routine maintenance
and adjustment of all components and equipment.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
B. Casing: Cast iron; with cast-iron inlet strainer, legs that elevate pump to permit flow into
impeller, and vertical discharge with companion flange for piping connection.
C. Impeller: ASTM B 584, cast bronze or stainless steel; statically and dynamically
balanced, semi open non clog design, overhung, single suction, keyed and secured to
shaft.
D. Pump and Motor Shaft: Stainless steel, with factory-sealed, grease-lubricated ball
bearings and double-mechanical seals.
E. Motor: Hermetically sealed, capacitor-start type, with built-in overload protection; three-
conductor waterproof power cable of length required, and with grounding plug and
cable-sealing assembly for connection at pump. Comply with requirements in
Division 22 Section "Common Motor Requirements for Plumbing Equipment."
1. Moisture-Sensing Probe: Internal moisture sensor with moisture alarm.
F. Pump Discharge Piping: Factory or field fabricated, PVC pipes, schedules 40 / PN 16.
G. Basin Pit Cover: Cast iron or steel with bituminous coating and strong enough to
support controls.
H. Controls: NEMA 250, Type 1 enclosure, pedestal mounted unless wall mounting is
indicated; with three mechanical- or mercury-float or micro pressure mechanical-float
KEO/19-3262-0000 22 1429/3 Sump Pumps
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
mercury-float micro pressure switches in NEMA 250, Type 6
enclosures; mounting rod; and electric cables. Include automatic alternator to alternate
operation of pump units on successive cycles and to operate multiple units if one pump
cannot handle load.
1. Float Guide: Pipe or other restraint for floats and rods in basins of depth greater
than 60 inches (1500 mm).
2. High-Water Alarm: Cover-mounted, compression-probe alarm, with electric bell;
120-V ac, with transformer and contacts for remote alarm bell.
3. High-Water Alarm: Rod-mounted, NEMA 250, Type 6 enclosure with
mechanical- or mercury-float or micro pressure mechanical-float mercury-float
micro pressure-switch alarm matching control and electric bell; 120-V ac, with
transformer and contacts for remote alarm bell.
PART 3 - EXECUTION
3.01 EXAMINATION
3.02 CONCRETE
A. Install concrete bases of dimensions indicated for pumps and controllers. Refer to
Division 22 Section "Common Work Results for Plumbing."
B. Install pumps and arrange to provide access for maintenance including removal of
motors, impellers, couplings, and accessories.
C. Set submersible sump pumps on basin or pit floor. Make direct connections to storm
drainage piping.
D. Construct sump pump pits and connect to drainage piping. Set pit curb frame recessed
in and anchored to concrete. Fasten pit cover to pit curb flange. Install cover so top
surface is flush with finished floor.
E. Install packaged, pedestal, drainage pump units and make direct connection to storm
drainage piping.
3.04 CONNECTIONS
C. Connect storm drainage piping to pumps. Install discharge piping equal to or greater
than size of pump discharge piping. Refer to Division 22 Section "Facility Storm
Drainage Piping."
1. Install flexible connectors adjacent to pumps in discharge piping.
2. Install check and shutoff valves on discharge piping from each pump. Install
unions on pumps having threaded pipe connections. Install valves same size as
connected piping. Refer to Division 22 Section "General-Duty Valves for
Plumbing Piping" for general-duty valves for drainage piping.
3.06 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
A. This Section includes the following types of water filtration equipment for water systems
in buildings:
1. Multimedia sand filters.
2. In-line water filter.
3. Irrigation screen filter.
4. Water Purification System (Reverse Osmosis).
1.02 DEFINITIONS
1.03 SUBMITTALS
B. Shop Drawings: Detail water filtration equipment assemblies and indicate dimensions,
weights, loads, required clearances, method of field assembly, components, and
location and size of each field connection.
1. Wiring Diagrams: Power, signal, and control wiring.
C. Certificates of Shop Inspections and Data Reports: For products required to have
ASME label, signed by product manufacturer.
A. Source Limitations: Obtain each type of water filtration equipment through one source
from a single manufacturer.
C. Welding: Qualify processes and operators according to ASME Boiler and Pressure
Vessel Code: Section IX.
E. Comply with NSF 61, "Drinking Water System Components - Health Effects; Sections 1
through 9," for all components that will be in contact with potable water.
1.06 COORDINATION
A. Coordinate size and location of concrete bases with Architectural and Structural
Drawings.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
1.08 WARRANTEE
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Type: Inline water filter with automatic backwash with 20 micron (900 mesh
approximate), the connections shall be NPT threaded tailpieces with union on inlet and
outlet. Materials of construction shall be as follows:
Body and Sump Brass
Screen Stainless Steel
Internal Construction Acetal Copolymer
Seals NBR
Ball Valve Brass with PTFE Seals
D. Automatic Backwash Control: Bayonet mounted shaft of 24 Vac motor and timer
replaces ball valve manual control for automatic backwash at programmed intervals
complete with 24V transformer with the following specifications:
Power: 4 VA
Current: 170 mA
Voltage: 24 Vac
Cycle Time: 20 Seconds (approximate)
Timer: Variable.
C. Construction: Rated (150 psig), internally and externally epoxy coated stainless steel
(type 316) housing, with quick release covers and integral supports, welded inlet and
outlet pipes with flanged/grooved ends. Ports for air release valve, clean and dirty water
KEO/19-3262-0000 22 3200/4 Domestic Water Filtration Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
sampling cocks and pressure gauges at inlet and outlet and stainless steel (type 316)
screen.
D. Accessories: Air bleed valve, sampling cocks, pressure gauges, ball type valves on the
flushing lines.
B. Manufacturer shall have been engaged in the manufacture of reverse osmosis systems
as a primary product for at least ten years. The ten year requirement supersedes any
conflicting requirement in other parts of the project specification.
C. Project Conditions:
1. Influent Water Analysis:
a. The system shall be fed by potable water (MEW), below are guidelines of
potable water quality:
1) pH 6–8
2) Maximum Free Chlorine 0.5 ppm
3) Conductivity <600 μs/cm
4) TDS <400 ppm
5) Total Hardness <200 ppm
b. The Contractor should confirm the analysis with current samples and
tests.
2. Design Parameters:
a. Product Water Capacity: 75 liter per minute
b. Product Water Quality
1) pH 6–8
2) TDS <20 ppm
3) Total Hardness Nil
c. Daily Hours of Water Demand: 24 Hours
d. Operating Temperature Range: <50 oC
3. Reference Standards
a. American Society of Mechanical Engineers (ASME).
1) B40.100-1998 – Pressure Gages and Gage Attachments.
b. ASTM International (ASTM):
1) A269-04 Seamless and Welded Austenitic Stainless Steel
Tubing for General Service.
2) D1785-06 Poly (Vinyl Chloride) (PVC) Plastic Pipe, Schedules
40, 80 and 120.
c. American Water Works Association (AWWA):
1) B300-04 Hypochlorites.
2) B301-04 Liquid Chlorine.
3) C651-99 Disinfecting Chlorine.
d. National Electrical Manufacturers Association (NEMA):
1) ICS-6-1993 (R2001) – Industrial Control and System Enclosures.
e. National Fire Protection Association (NFPA):
1) 70-50 National Electrical Code.
F. Softener
H. UV Disinfection Unit
1. UV disinfection unit should be installed inline after the RO plant to ensure
microbiological free water supply. The performance rating shall be greater than
99% destruction if bacteria and viruses at rated flow.
2. Chamber Material: Stainless Steel 316.
3. Dosage shall be greater than 30 mj/cm2 @254 nm.
I. Pressure Gages:
1. ASME B40.100, Grade A, 1% accuracy, 110 mm (4-1/2 inches) diameter, all
metal case, bottom connected. White dials, black hands graduated from 0 to 700
kPa (0 to 100 psi) and identity labeled.
K. Tests:
1. Operating: Tests shall be run in presence of consultant engineer.
2. Procedure:
a. Operate RO system at constant maximum required capacity for one hour
after RO product water is produced. When necessary, waste product
water to sewer to maintain above flow rate. Product water production
A. Hydrostatically test before shipment to minimum of one and one-half times pressure
rating.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine areas and conditions, with Installer present, for compliance with requirements
for installation tolerances and other conditions affecting performance of filters and
separators.
B. Examine roughing-in for piping systems to verify actual locations of piping connections
before equipment installation.
C. Examine walls and floors for suitable conditions where filters and separators will be
installed.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
B. Install seismic restraints for sand-filter tanks and accessories and anchor to building
structure.
KEO/19-3262-0000 22 3200/9 Domestic Water Filtration Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3.04 CONNECTIONS
C. Make piping connections between water filtration equipment and dissimilar-metal water
piping with dielectric fittings. Dielectric fittings are specified in Division 22 Section
"Common Work Results for Plumbing."
D. Install shutoff valves on feed water-inlet and filtrate-outlet piping of each water filtration
equipment filter and separator, and on inlet and outlet headers.
1. Metal general-duty valves are specified in Division 22 Section "General-Duty
Valves for Plumbing Piping."
E. Install pressure gages on feedwater-inlet and filtrate-outlet piping of each water filtration
equipment filter and separator. Pressure gages are specified in Division 22 Section
"Meters and Gages for Plumbing Piping."
F. Install valved bypass water piping around each water filtration equipment filter and
separator.
1. Metal general-duty valves are specified in Division 22 Section "General-Duty
Valves for Plumbing Piping."
2. Water piping is specified in Division 22 Section "Domestic Water Piping."
G. Install drains as indirect wastes to spill into open drains or over floor drains.
B. Perform the following field tests and inspections and prepare test reports:
1. Leak Test: After installation, charge system and test for leaks. Repair leaks and
retest until no leaks exist.
2. Operational Test: After electrical circuitry has been energized, start units to
confirm proper unit operation.
3. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
C. Remove and replace water filtration equipment that does not pass tests and inspections
and retest as specified above.
B. Sample water after startup and at three consecutive seven-day intervals (total of four
samples), and prepare certified test reports for required water performance
characteristics.
3.07 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
1.03 SUBMITTALS
A. Product Data: For each type and size of water heater indicated. Include rated
capacities, operating characteristics, furnished specialties, and accessories.
C. Product Certificates: For each type of commercial and instantaneous electric water
heater, signed by product manufacturer.
G. Operation and Maintenance Data: For electric water heaters to include in emergency,
operation, and maintenance manuals.
A. Source Limitations: Obtain same type of electric water heaters through one source
from a single manufacturer.
D. ASME Compliance: Where indicated, fabricate and label commercial water heater
storage tanks to comply with ASME Boiler and Pressure Vessel Code: Section VIII,
Division 1.
E. Comply with NSF 61, "Drinking Water System Components - Health Effects;
Sections 1 through 9," for all components that will be in contact with potable water.
1.05 COORDINATION
A. Coordinate size and location of concrete bases with Architectural and Structural
Drawings.
1.06 WARRANTY
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 QUALIFICATIONS
The manufacturer shall have a minimum of twenty years’ experience in the design,
manufacture and testing of pumps
B. Storage section: ASTM rated and certified (150 psi), Duplex Stainless Steel shell
insulated with 90 mm removable cfc free foam insulation in an aluminum casing.
C. Connections: Bronze nipples for cold water inlets, hot water outlet, threaded T&P relief
valve and drain valve ports, flanged connection for element plate.
E. Recovery section: Immersion ceramic core type element assembly with screw in type,
removable without draining tank. The elements housed in removable IP-54 Stainless
Steel housings/barrels multiple stages, with individual overheating protection 110°C
and built-in 2- pole Thermostat with temperature adjustment 30°C - 90°C for each
heating stage.
G. Control Panel: IP55 protection (dust, spray), mounted and fully wired with power on
lamp, test buttons and heater indicator lamps for all stages. Power cut-off when
opening control panel door. Off-peak control timer include element protection circuit
against over heating due and manual override switches. Heater indicator LED for each
heating stage. Power-on LED, auto-off-manual switch for each of the 3 stages, electronic
temperature sensor, off-peak control timer with programmable stage cascading control
and LCD digital display. Individual fault indication (blinking heater indictor) of short circuit
or safety cut-out tripping for each heating stage and volt free output contacts for Building
Management System "HEATING FAULT STAGE TO BMS". Integrated 230V power
H. Capacity: Schedule on drawing shall be referred to for details of selection and capacity
ratings.
B. Storage Section: ASME rated and certified (125 psi), glass lined steel shell insulated
with 25mm (1 inch) thick high density fibreglass or polyurethane foam, enclosed in
square ware sheet metal jaketing, with wall mounting brackets fixed on the shell.
C. Connections for cold water inlet with diffuser and hot water outlet with upstand pipe.
E. Recovery section: Immersion type elements assembly with screw in type, copper
faced heat resistant plastic base. Heating element shall be made of nickel chromium
wire embedded in magnesium oxide and sheathed in copper incolloy tubes. Watt
density shall not exceed 7.75 / 11.63 per sq. cm. (50 / 75 per sq. inch) for copper
incolloy.
F. Thermostats: Immersion type with an operating range of 20 to 82.2 deg. C and built-
in over-temperature limiter with manual reset.
A. Combination Temperature and Pressure Relief Valves: ASME rated and stamped and
complying with ASME PTC 25.3. Include relieving capacity at least as great as heat
input, and include pressure setting less than water heater working-pressure rating.
Select relief valves with sensing element that extends into storage tank.
B. Pressure Relief Valves: ASME rated and stamped and complying with
ASME PTC 25.3. Include pressure setting less than water heater working-pressure
rating.
D. Water Heater Stands: Water heater manufacturer's factory-fabricated steel stand for
floor mounting and capable of supporting water heater. Include dimension that will
support bottom of water heater a minimum of 18 inches (457 mm) above the floor.
F. Drain Pans: Corrosion-resistant metal with raised edge. Include dimensions not less
than base of water heater and include drain outlet not less than NPS 3/4 (DN 20).
G. Piping Manifold Kits: Water heater manufacturer's factory-fabricated inlet and outlet
piping arrangement for multiple-unit installation. Include piping and valves for field
assembly that are capable of isolating each water heater and of providing balanced
flow through each water heater.
J. Thermal Expansion Tank: Thermal expansion tanks shall be sized in accordance with
the tank manufacturer's instructions.
A. Type: In-line centrifugal type of 2900 rpm speed, single/twin units. Materials of
construction shall be as follows:
1. Impeller …………. Bronze/Stainless Steel.
2. Shaft …………….. Stainless Steel.
3. Casing …………… Bronze/Stainless Steel.
4. Seal ……………… Mechanical.
C. Accessories: Pressure gauges at inlet and outlet, dielectric flanges where required,
bronze gate valves at inlet and outlet bronze non-slam check valve at outlet.
A. Test and inspect water heater storage tanks, specified to be ASME-code construction,
according to ASME Boiler and Pressure Vessel Code.
B. Hydrostatically test water heater storage tanks before shipment to minimum of one
and one-half times pressure rating.
PART 3 - EXECUTION
B. Install water heaters level and plumb, according to layout drawings, original design,
and referenced standards. Maintain manufacturer's recommended clearances.
Arrange units so controls and devices needing service are accessible.
C. Install seismic restraints for light-commercial and commercial water heaters. Anchor
to substrate.
D. Install combination temperature and pressure relief valves in top portion of storage
tanks. Use relief valves with sensing elements that extend into tanks. Extend
commercial-water-heater relief-valve outlet, with drain piping same as domestic water
piping in continuous downward pitch, and discharge by positive air gap onto closest
floor drain.
E. Install combination temperature and pressure relief valves in water piping for water
heaters without storage. Extend commercial-water-heater relief-valve outlet, with
drain piping same as domestic water piping in continuous downward pitch, and
discharge by positive air gap onto closest floor drain.
F. Install water-heater drain piping as indirect waste to spill by positive air gap into open
drains or over floor drains. Install hose-end drain valves at low points in water piping
for water heaters that do not have tank drains. Refer to Division 22 Section "Domestic
Water Piping Specialties" for hose-end drain valves.
I. Install pressure gage(s) on inlet and outlet of commercial electric water- heater piping.
Refer to Division 22 Section "Meters and Gages for Plumbing Piping" for pressure
gages.
J. Install expansion (compression) tank on cold water supply to commercial water heater.
K. Assemble and install inlet and outlet piping manifold kits for multiple water heaters.
Fabricate, modify, or arrange manifolds for balanced water flow through each water
heater. Include shutoff valve, thermometer in each water heater inlet and outlet, and
throttling valve in each water heater outlet. Refer to Division 22 Section "General-Duty
Valves for Plumbing Piping" for general-duty valves and to Division 22 Section "Meters
and Gages for Plumbing Piping" for thermometers.
L. Install water regulator, with integral bypass relief valve, in booster-heater inlet piping
and water hammer arrester in booster-heater outlet piping.
M. Install piping-type heat traps on inlet and outlet piping of water heater storage tanks
without integral or fitting-type heat traps.
KEO/19-3262-0000 22 3300/6 Electric Domestic Water Heaters
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
N. Fill water heaters with water.
3.02 CONNECTIONS
B. Install piping adjacent to water heaters to allow service and maintenance. Arrange
piping for easy removal of water heaters.
B. Perform the following field tests and inspections and prepare test reports:
1. Leak Test: After installation, test for leaks. Repair leaks and retest until no
leaks exist.
2. Operational Test: After electrical circuitry has been energized, confirm proper
operation.
3. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
C. Remove and replace water heaters that do not pass tests and inspections and retest
as specified above.
3.04 DEMONSTRATION
END OF SECTION
PLUMBING FIXTURES
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the following conventional plumbing fixtures and related
components:
1. Faucets for lavatories, bathtubs, bathtub/showers, showers, and, sinks.
2. Laminar-flow faucet-spout outlets.
3. Toilet seats.
4. Protective shielding guards.
5. Fixture supports.
6. Dishwasher air-gap fittings.
7. Hot-water dispensers.
8. Water closets.
9. Lavatories.
10. Bathtubs.
11. Individual showers.
12. Kitchen sinks.
1.02 DEFINITIONS
B. Accessible Fixture: Plumbing fixture that can be approached, entered, and used by
people with disabilities.
E. Fitting: Device that controls the flow of water into or out of the plumbing fixture. Fittings
specified in this Section include supplies and stops, faucets and spouts, shower heads
and tub spouts, drains and tailpieces, and traps and waste pipes. Piping and general-
duty valves are included where indicated.
1.03 SUBMITTALS
A. Product Data: For each type of plumbing fixture indicated. Include selected fixture and
trim, fittings, accessories, appliances, appurtenances, equipment, and supports.
Indicate materials and finishes, dimensions, construction details, and flow-control rates.
A. Source Limitations: Obtain plumbing fixtures, faucets, and other components of each
category through one source from a single manufacturer.
1. Exception: If fixtures, faucets, or other components are not available from a
single manufacturer, obtain similar products from other manufacturers specified
for that category.
E. NSF Standard: Comply with NSF 61, "Drinking Water System Components--Health
Effects," for fixture materials that will be in contact with potable water.
F. Select combinations of fixtures and trim, faucets, fittings, and other components that are
compatible.
G. Comply with the following applicable standards and other requirements specified for
plumbing fixtures:
1. Enameled, Cast-Iron Fixtures: ASME A112.19.1M.
2. Slip-Resistant Bathing Surfaces: ASTM F 462.
3. Solid-Surface-Material Lavatories and Sinks: ANSI/ICPA SS-1.
4. Stainless-Steel Residential Sinks: ASME A112.19.3.
5. Vitreous-China Fixtures: ASME A112.19.2M.
6. Water-Closet, Flush Valve, Tank Trim: ASME A112.19.5.
KEO/19-3262-0000 22 4000/2 Plumbing Fixtures
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
7. Water-Closet, Flushometer Tank Trim: ASSE 1037.
H. Comply with the following applicable standards and other requirements specified for
lavatory and sink faucets:
1. Backflow Protection Devices for Faucets with Side Spray: ASME A112.18.3M.
2. Backflow Protection Devices for Faucets with Hose-Thread Outlet:
ASME A112.18.3M.
3. Diverter Valves for Faucets with Hose Spray: ASSE 1025.
4. Faucets: ASME A112.18.1.
5. Hose-Connection Vacuum Breakers: ASSE 1011.
6. Hose-Coupling Threads: ASME B1.20.7.
7. Integral, Atmospheric Vacuum Breakers: ASSE 1001.
8. NSF Potable-Water Materials: NSF 61.
9. Pipe Threads: ASME B1.20.1.
10. Sensor-Actuated Faucets and Electrical Devices: UL 1951.
11. Supply Fittings: ASME A112.18.1.
12. Brass Waste Fittings: ASME A112.18.2.
I. Comply with the following applicable standards and other requirements specified for
bathtub and shower faucets:
1. Backflow Protection Devices for Hand-Held Showers: ASME A112.18.3M.
2. Combination, Pressure-Equalizing and Thermostatic-Control Antiscald Faucets:
ASSE 1016.
3. Deck-Mounted Bath/Shower Transfer Valves: ASME 18.7.
4. Faucets: ASME A112.18.1.
5. Hand-Held Showers: ASSE 1014.
6. High-Temperature-Limit Controls for Thermal-Shock-Preventing Devices:
ASTM F 445.
7. Hose-Coupling Threads: ASME B1.20.7.
8. Manual-Control Antiscald Faucets: ASTM F 444.
9. Pipe Threads: ASME B1.20.1.
10. Pressure-Equalizing-Control Antiscald Faucets: ASTM F 444 and ASSE 1016.
11. Sensor-Actuated Faucets and Electrical Devices: UL 1951.
12. Thermostatic-Control Antiscald Faucets: ASTM F 444 and ASSE 1016.
J. Comply with the following applicable standards and other requirements specified for
miscellaneous fittings:
1. Atmospheric Vacuum Breakers: ASSE 1001.
2. Brass and Copper Supplies: ASME A112.18.1.
3. Dishwasher Air-Gap Fittings: ASSE 1021.
4. Manual-Operation Flushometers: ASSE 1037.
5. Plastic Tubular Fittings: ASTM F 409.
6. Brass Waste Fittings: ASME A112.18.2.
7. Sensor-Operation Flushometers: ASSE 1037 and UL 1951.
K. Comply with the following applicable standards and other requirements specified for
miscellaneous components:
1. Disposers: ASSE 1008 and UL 430.
2. Dishwasher Air-Gap Fittings: ASSE 1021.
3. Flexible Water Connectors: ASME A112.18.6.
4. Floor Drains: ASME A112.6.3.
5. Grab Bars: ASTM F 446.
6. Hose-Coupling Threads: ASME B1.20.7.
7. Hot-Water Dispensers: ASSE 1023 and UL 499.
KEO/19-3262-0000 22 4000/3 Plumbing Fixtures
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
8. Off-Floor Fixture Supports: ASME A112.6.1M.
9. Pipe Threads: ASME B1.20.1.
10. Plastic Shower Receptors: ANSI Z124.2.
11. Plastic Toilet Seats: ANSI Z124.5.
12. Supply and Drain Protective Shielding Guards: ICC A117.1.
1.05 WARRANTY
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
1. Faucet Washers and O-Rings: Equal to 10 percent of amount of each type and
size installed.
2. Faucet Cartridges and O-Rings: Equal to 5 percent of amount of each type and
size installed.
3. Provide hinged-top wood or metal box, or individual metal boxes, with separate
compartments for each type and size of extra materials listed above.
4. Water-Closet Tank, Repair Kits: Equal to 5 percent of amount of each type
installed.
5. Toilet Seats: Equal to 5 percent of amount of each type installed.
PART 2 - PRODUCTS
B. When coloured sanitary fixtures are specified, the colour shall be finalised in co-
ordination with other finishing elements in the wet areas.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine roughing-in of water supply and sanitary drainage and vent piping systems to
verify actual locations of piping connections before plumbing fixture installation.
B. Examine cabinets, counters, floors, and walls for suitable conditions where fixtures will
be installed.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 INSTALLATION
C. Install back-outlet, wall-mounting fixtures onto waste fitting seals and attach to supports.
F. Install floor-mounting, back-outlet water closets attached to building floor substrate and
wall bracket and onto waste fitting seals.
I. Install water-supply piping with stop on each supply to each fixture to be connected to
water distribution piping. Attach supplies to supports or substrate within pipe spaces
behind fixtures. Install stops in locations where they can be easily reached for
operation.
1. Exception: Use ball, gate, or globe valves if supply stops are not specified with
fixture. Valves are specified in Division 22 Section "General-Duty Valves for
Plumbing Piping."
J. Install trap and tubular waste piping on drain outlet of each fixture to be directly
connected to sanitary drainage system.
K. Install tubular waste piping on drain outlet of each fixture to be indirectly connected to
drainage system.
N. Install faucet-spout fittings with specified flow rates and patterns in faucet spouts if
faucets are not available with required rates and patterns. Include adapters if required.
O. Install water-supply flow-control fittings with specified flow rates in fixture supplies at
stop valves.
P. Install faucet flow-control fittings with specified flow rates and patterns in faucet spouts if
faucets are not available with required rates and patterns. Include adapters if required.
Q. Install shower flow-control fittings with specified maximum flow rates in shower arms.
S. Install disposer in outlet of each sink indicated to have disposer. Install switch where
indicated or in wall adjacent to sink if location is not indicated.
T. Install dishwasher air-gap fitting at each sink indicated to have air-gap fitting. Install in
sink deck. Connect inlet hose to dishwasher and outlet hose to disposer.
U. Install hot-water dispensers in back top surface of sink or in countertop with spout over
sink.
V. Install escutcheons at piping wall ceiling penetrations in exposed, finished locations and
within cabinets and millwork. Use deep-pattern escutcheons if required to conceal
protruding fittings. Escutcheons are specified in Division 22 Section "Common Work
Results for Plumbing."
X. Seal joints between fixtures and walls, floors, and countertops using sanitary-type, one-
part, mildew-resistant silicone sealant. Match sealant color to fixture color. Sealants
are specified in Division 07 Section "Joint Sealants."
3.03 CONNECTIONS
B. Connect fixtures with water supplies, stops, and risers, and with traps, soil, waste, and
vent piping. Use size fittings required to match fixtures.
A. Verify that installed plumbing fixtures are categories and types specified for locations
where installed.
C. Inspect installed plumbing fixtures for damage. Replace damaged fixtures and
components.
D. Test installed fixtures after water systems are pressurized for proper operation. Replace
malfunctioning fixtures and components, then retest. Repeat procedure until units
operate properly.
3.05 ADJUSTING
A. Operate and adjust faucets and controls. Replace damaged and malfunctioning
fixtures, fittings, and controls.
B. Operate and adjust hot-water dispensers and controls. Replace damaged and
malfunctioning units and controls.
C. Replace washers and seals of leaking and dripping faucets and stops.
3.06 CLEANING
A. Clean fixtures, faucets, and other fittings with manufacturers' recommended cleaning
methods and materials. Do the following:
1. Remove faucet spouts and strainers, remove sediment and debris, and reinstall
strainers and spouts.
2. Remove sediment and debris from drains.
3.07 PROTECTION
B. Do not allow use of plumbing fixtures for temporary facilities unless approved in writing
by Owner.
END OF SECTION
PART 1 - GENERAL
E. Control Panels
1.2 REFERENCES:
1.3 SUBMITTALS
C. Coordination Drawings and Piping Diagrams: For laboratory air and vacuum piping
and specialties, including relationship to other services that serve same work areas.
Show connections to laboratory fume hoods and casework.
E. Inspection and Test Reports: Specified in "Field Quality Control" Article in Part 3 of
this Section.
A. Testing Agency Services: Employer will provide independent testing agency services
under separate contract to inspect, test, and certify medical gas piping and
components, except for inspections and tests specified in "Field Quality Control"
Article in Part 3 of this Section.
D. Source Limitations: Obtain laboratory air and vacuum specialties through one source
from a single manufacturer.
E. Source Limitations: Provide laboratory air and vacuum specialties compatible with
existing systems.
F. Source Limitations: Provide laboratory air and vacuum specialties from manufacturer
of existing specialties, compatible with existing systems.
A. Deliver and store large laboratory air and vacuum piping specialties on shipping
skids, small specialties in containers, and piping with end protection.
B. Store precleared and sealed pipe, fittings, valves, and specialties with sealing plugs
and sealing packaging intact.
A. All electrical works starting from the outgoing terminals of switch fuses/submain
switchboards onwards, for laboratory and medical gas equipment are included in this
Section.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
B. Components such as fuses, contractors, indicators, timers… etc. which may require
replacement in future, shall be products of the same standard / manufacture as that
of the electrical works of the Project.
C. Pumps, compressors and control panels shall be from those manufacturers who
have local agents certified to check, test adjust and commission this equipment.
A. General
1. The compressor air system package composed of two compressors, two air
reservoirs, valves, connections, sequence control panel shall be provided to
regulate the function of the compressors, air intake with filter and after
Refrigeration Air Dryer.
4. The compressor package are completely wired and equipped with all
interconnecting pipes and fittings, include a belt driven compressor element
totally enclosed fan - cooled electric motor together with lubrication, cooling
and regulating system with control panel for start / stop switch and the
emergency stop button.
5. Total integration of refrigerant dryer, compressed air filters, air tank, stop start
system with piston type inlet check valve, (all as one component) results in a
complete compressed air system including all connections and outlets valves.
8. The compressor shall be combined with low noise levels, down to 63 Db. The
unit shall be tank mounted type with air receiver capacity of 500 lit.
B. Compressors
1. Reciprocating or Screw type, two stage, air cooled, belt driven by electric
motor, adequately guarded, or direct driven as appropriate.
C. Air Intake
1. b
D. Aftercoolers
1. Air blast operation with motor driven fan. Each aftercooler is fitted with
thermometers giving inlet and outlet temperatures and has automatic drain
with manual bypass.
E. Compressor Motor
F. Air Receiver
1. Air leaving the receive is passed through twin pre-filters, two oil removal filters
to a double twin column dryer assembly with its own control box and timer.
H. Filter/Pressure Control
I. Delivered Air
1. Each litre of air at STP will not contain more than 0.0005 mg of oil mist,
particulate 0.5mg/m3, or more than 5.5mg/m3 (5ppm) of carbon monoxide, or
900mg/m3 (500 ppm) of carbon dioxide. Other substances will not exceed
the limits permitted in BS 4275. Dew point will be at atmospheric pressure.
Minus 40° (C or F), or better.
J. Control Panel
2. The upper compartment has two control pressure switches and an alarm
pressure switch, hand/auto switches, run on timers (to limit the number of
starts), pneumatic solenoid valves and various indication and control circuitry.
2. Type: Diaphragm-operated
1. Corrosion-resistant metal body and internal parts, rated for 1380 kPa (200
psig) minimum working pressure, capable of automatic discharge of collected.
M. Air Dryer:
1. The compressed air dryer shall be of the refrigerated type designed for
operating at the rated system pressure (13 bar). The dryer shall be capable
of delivering air at a dew point of 3°C as Mark or equal and approved.
N. Air Filters:
1. High efficiency oil removal filter particle removal down to 0.01 micron including
water and oil aerosols providing a maximum remaining oil aerosol content of
0.01 mg/m3 at 21°C all as Mark or equal and approved.
A. General
1. Composed of two sets, each has one Pump, separator, and individual control
for each set and sequence control panel to regulate the performance of the
two sets as per load requirements. A condensation water separator shall be
installed at lowest point before connection to the pumps. Exhaust pipe shall
be filtered via bacteria filter with separation rate 99.997% subject to a part
size of 0.3 ppm.
2. The installation will consist of simplex dental (Wet Suction) vacuum pumps,
complete with starter/control panel, air liquid separator, amalgam separator
and buffer tank. These assemblies should be installed in the incoming main
distribution pipe. Pump exhausts should be run to atmosphere, to discharge
well clear of windows or air intake. A transparent flask and valve is provided
for each exhaust. These are used to provide condense traps close to the
pump outlets.
B. Vacuum Pumps
2. The main vacuum line is passed through a combined filter, drainage trap and
sight tube assembly before entering the receiver.
KEO/19-3262-0000 22 6113/6 Compressed Air & Vacuum Equipment for Dental
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. The exhaust of the vacuum pumps are taken out through muffler assembly
and discharged on the roof.
4. Type: Single stage, air cooled rotary type with close coupled motor mounted
on a horizontal / vertical cylindrical receiver.
C. Separator/Receiver:
1. The waste water flows on through the secretion tank down into the buffer tank
via the pre-separator and the amalgam separator. Due to the position of the
ball check valve and an evacuation pipe that evens out the pressure between
the buffer tank and the secretion tank, the same level of under-pressure is
achieved in the entire system to guarantee a steady flow between the
separators. A power-operated, overflow safety device shuts down the suction
motor when the system is full. When the suction motor stops, negative
pressure levels are reversed causing the ball check valve to open and the
buffer tank is emptied.
E. Vacuum Conditions
F. Control Panel
1. Equipment has to be supplied with 3-phase and zero voltage and grounded as
described here. When installing, kae sure to check that the motor circuit
switch complies with the suction motor’s rated output current. Check that the
short-circuiting terminal is correctly fitted to the junction box in the suction
motor. When installing the suction motor and the start-up box, the box is
KEO/19-3262-0000 22 6113/7 Compressed Air & Vacuum Equipment for Dental
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
connected to the power supply through a 5x2.5 mm2 cable using a multipole
safety switch, which must be shut down when servicing the equipment. 16-
amp delay action fuse. The powered wires are connected at “1”. “2”, “3”, and
the neutral wire to “4” in the connection terminal in the start-up box. The
suction motor is connected to the start-up box via a 4x1.5 mm2 cable.
2. The time-relay, is set to 10-20 seconds to allow the suction motor to shut
down 10 to 20 seconds after the suction system has not been in use. The
power-operated overflow safety device in the secretion tank is linked in series
with the chair control unit, so that the suction motor is shut down when the
tank is full.
G. Operation
PART 3 - EXECUTION
A. Air inlet point location should be agreed with the medical officer.
B. The air inlets shall not be effected by rain, dust, fumes and noxious vapours.
A Exhaust gases should be discharged outdoors above roof level of the pump house
and away from windows and other air intakes.
B. Install flexible connection at suction and discharge to prevent carry out pump
vibration to system piping. Anchor piping immediately after the flexible connections.
A. Panels shall be fabricated from minimum mm thick sheet steel and have
continuously welded butt joints. Apply two (2 coats) of red oxide primer and two (2
coats) of baked on enamel. All required holes and cuts shall be done at the factory.
B. All internal wiring shall be done in a neat and professional manner, using cable ties,
slip-on spiral plastic bundle sheaths etc. Provide ample free length to allow full
swing of doors.
C. Provide suitable legs, drilled for bolting down to house keeping pads.
D. Wall mounted panels shall be stiffened with profiled sections welded to the back
plate, as required. Top of wall mounted panels shall be at 180 cms above F.F.L.
KEO/19-3262-0000 22 6113/8 Compressed Air & Vacuum Equipment for Dental
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
E. All panels shall have enclosure to IP-44 as minimum requirement and anti-
condensation heater within.
1. Prior to Start-up
2. Start-up
iii. Check the motor full load current by manipulating the floor.
iv. Check the pressure relief valve for proper operation by gradually
closing the test valve.
3.5 WARRANTY
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.1 SUMMARY
A. This Section includes piping and related specialties aboveground and inside the building
for the following systems:
1. Compressed air, designated "Dental air."
2. Vacuum System , designated "Dental Vacuum."
1.2 DEFINITIONS
A. PTFE: Polytetrafluoroethylene.
B. TFE: Tetrafluoroethylene.
1.3 SUBMITTALS
B. Coordination Drawings and Piping Diagrams: For Dental air & Dental vacuum piping
and specialties, including relationship to other services that serve same work areas.
Show connections to Dental fume hoods and casework.
D. Inspection and Test Reports: Specified in "Field Quality Control" Article in Part 3 of this
Section.
A. Testing Agency Services: Employer will provide independent testing agency services
under separate contract to inspect, test, and certify medical gas piping and components,
except for inspections and tests specified in "Field Quality Control" Article in Part 3 of
this Section.
C. Source Limitations: Obtain dental air & dental vacuum specialties through one source
from a single manufacturer.
D. Source Limitations: Provide dental air & dental vacuum specialties compatible with
existing systems.
G. Source Limitations: Provide dental air & dental vacuum specialties from manufacturer of
existing specialties, compatible with existing systems.
H. Listing and Labeling: Provide electrically operated specialties specified in this Section
that are listed and labeled.
1. Terms "Listed" and "Labeled": As defined in NFPA 70, Article 100.
A. Deliver and store large dental air & dental vacuum piping specialties on shipping skids,
small specialties in containers, and piping with end protection.
B. Store precleared and sealed pipe, fittings, valves, and specialties with sealing plugs and
sealing packaging intact.
C. Label pipe, fittings, valves, and specialties that have not been precleaned, and that have
been precleaned but have seal or packaging that is not intact, with temporary labels
indicating that cleaning is required before installation.
2.1 MANUFACTURERS
A. General: Applications of the following pipe and tube materials are indicated in Part 3
"Piping Applications" Article.
B. Copper Tube: EN 13348 Type X, seamless, drawn temper. for dental air.
C. PVC Type I, Grade I, with a cell classification of 12454 and shall meet, or exceed, the r
equirements of ASTM D1784 for dental vacuum.
A. General: Applications of the following pipe and tube fitting materials are indicated in Part
3 "Piping Applications" Article.
D. Bronze-Tube Flanges
E. Flexible Pipe Connectors: Bronze hose, covered with bronze wire braid with copper-tube
or bronze-flanged ends brazed to hose.
F. All materials shall be PVC Type I, Grade I, with a cell classification of 12454 and shall
meet, or exceed, the requirements of ASTM D1784. All compound components shall be
listed with NSF and meet the requirements of NSF Standard 61 as suitable for potable
water
G. Socket : All PVC Schedule 80 fittings shall meet, or exceed, the dimensional and
tolerance requirements of ASTM D2467
H. Threaded : All PVC Schedule 80 threaded fittings shall meet, or exceed, the
dimensional and tolerance requirements of ASTM D2464
A. General: Applications of the following piping joining materials are indicated in Part 3
"Piping Applications" Article.
E. All PVC Schedule 80 fittings/sockets shall meet, or exceed, the dimensional and toleran
ce requirements of ASTM D2467.
F. All PVC Schedule 80 threaded fittings shall meet, or exceed, the dimensional and toler
ance requirements of ASTM D2464.
Note : Contractor shall ensure the use of proper pipe cutters, beveling and deburring
tools before making the joints.
P-70 Primer : Professional grade, industrial strength primer essential for proper
softening and preparation of PVC and CPVC pipe and fitting surfaces. Specially
recommended for use on Schedule 80 (PN 10 and higher) and large size pipe. Meets
and exceeds :ASTM F 656 NSF/ANSI 14 NSF/ANSI 61
711 cement : Heavy bodied, medium setting gray Low VOC PVC cement for all classes
and schedules with interference fit through 12" diameter. Meets and exceeds: ASTM D
2564 NSF/ANSI 14 NSF/ANSI 61 CSA B137.3 CSA B181.2
A. Dental Air Valves: Pre-cleaned for oxygen service and factory sealed.
B. Ball Valves,: BSEN 13485 3-piece, brass valves bolted-body construction; chrome-
plated brass ball, full port; blowout proof; bronze or brass stem; PTFE or TFE seats and
seals; threaded or solder-joint end connections; and vinyl-covered steel lever handle
with locking device.
E. Shutoff Valves:
1. Copper Tubing: Copper-alloy ball valve with manufacturer-installed ASTM B 819,
copper-tube extensions.
2. PVC Piping:
a. NPS 4 (DN 100) and Smaller: [Copper-alloy ball valve with manufacturer-
installed ASTM B 819, copper-tube extensions] [PVC ball valve].
b. NPS 5 (DN 125) and Larger: PVC butterfly valve.
B. Components: Designed for continuous service and operation on power supplied from
220-V, ac power source to alarm panels. Include connections for 24- or 12-V, ac low-
voltage wiring to remote sensing devices. Include step-down transformers where
required.
C. Dew-Point Monitors: Continuous line monitors having panel with gage or digital display.
Include pipeline sensing element, electrical connections for alarm system, factory- or
field-installed valved bypass, and a visual and cancelable audio signal for dryer site and
master alarm panels. Activate alarm when pressure dew point rises above 3.9 deg C (39
deg F) at 380 kPa (55 psig).
D. Alarm Panels: Factory-wired, audible, and color-coded visual signals that indicate
specified functions.
1. Mounting: Recess.
2. Enclosure: Fabricated from minimum 1.2-mm thick steel or minimum 1.25-mm
thick aluminum, and with knockouts for electrical and piping connections.
A. Nitrogen for Pressure Testing: CGA G-10.1, oil free, dry, and at least Grade D.
B. Nitrogen for Flow Testing: CGA P-9, oil free and dry.
PART 3 - EXECUTION
3.1 PREPARATION
PVC Type I, Grade I, with a cell classification of 12454 and shall meet, or exceed, t
he requirements of ASTM D1784 for dental vacuum.
A. Refer to Division 22 Section "Basic Mechanical Materials and Methods" for basic piping
installation and joint construction.
B. Install piping next to equipment, accessories, and specialties to allow service and
maintenance.
C. Transition and special fittings with pressure ratings at least equal to piping pressure
rating may be used, unless otherwise indicated.
E. Install supports and anchors according to Division 22 Section "Hangers and Supports."
1. Spacing between Hangers: As described in NFPA 99 and NFPA 99C.
G. Valve Applications: Use ball valves specified in this Section for main shutoff and zone
valve duties.
H. Purge Dental air piping using oil-free, dry nitrogen after installing piping but before
connecting to service-outlet valves, alarms, and gages.
J. Install unions in PVC vacuum piping NPS 2 (DN 50) and smaller adjacent to each
valve and at final connection to each machine, specialty, and piece of equipment.
K. Install flanges in PVC vacuum piping NPS 2-1/2 (DN 65) and larger adjacent to flanged
valves and at final connection to each machine, specialty, and piece of equipment.
L. PVC-to-Copper Joints: Join transition fitting PVC socket end as solvent-cemented joint
to PVC pipe and join fitting end with insert to copper tube as threaded joint.
M. Flanged Joints:
1. Copper Tubing: Install flange on copper tubes. Use pipe-flange gasket between
flanges. Join flanges with gasket and bolts according to HTM-02-01 for bolting
procedure.
2. PVC Piping: Install PVC flange on PVC pipes. Use pipe-flange gasket between
flanges. Join flanges with gasket and bolts according to HTM-02-01 for bolting
procedure.
A. Connect Dental air piping to equipment, accessories, and specialties with unions. Install
with ball valve on both sides, and strainer at inlet connection.
1. Install flexible piping connectors on air piping to Dental air compressors piping to
Dental chairs.
2. Install thermometers on l Dental air-compressor discharge and air-receiver tanks.
3. Install pressure gages on Dental air-compressor discharge piping.
4. Install pressure regulators downstream from Dental air compressors, dryers,
purification units, and filter assemblies.
C. Arrange for electric-power connections to specialties and devices that require power.
Electric power, wiring, and disconnect switches are specified in Division.
A. Install labeling on piping, valves, valve-box covers, air manifolds, and alarm panels
according to NFPA 99 and NFPA 99C. Use the following or similar captions and color-
coding for specialties:
1. Dental Air: Black or white letters on yellow background.
2. Label Dental air piping to indicate system operating pressure.
3. Install continuous underground warning tape during backfilling of trench for
underground Dental air piping.
C. Certify that systems comply with specified requirements, that tests were properly
performed, and that test results were satisfactory.
D. Inspect outlets and inlets, gages, alarms, and zone valves for proper labeling for service
and function.
E. Inspect manifold supply systems for installation and operation according to NFPA 99,
Chapter 4 and NFPA 99C.
F. Phase I Tests: Perform the following tests using dry nitrogen after installing Dental air
system but before connecting new systems to existing gas sources:
1. Outlet and Inlet Cross-Connection Test: Pressurize 1 gas system to 345 kPa (50
psig), with other systems at atmospheric pressure, and access each outlet with
an appropriate adapter and test gage. Repeat procedure for each system.
2. Outlet and Inlet Cross-Connection Test: Pressurize each system in 69-kPa (10-
psig) increments and access each outlet with an appropriate adapter and test
gage.
3. Alarm System Test: Test for operation of functions specified in "Alarm System"
Article, within limits required.
4. Pressure Test: Test systems at operational pressure with system components
installed. No leaks are allowed. Conduct tests by zone.
5. Particulate Sampling: Test positive-pressure terminal outlets, using a 0.45-micron
filter, for evidence of solid particulate contamination. Allowable limit is 2 mg/cu.
m.
6. Systems Purity: Test terminal outlets and gas source for contaminant levels as
defined below. Excessive contaminant levels will require additional purging of
outlets within a specific zone until levels are within the following limits:
KEO/19-3262-0000 22 6219/8 Dental Air & Dental Vacuum Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
G. Phase II Tests: After Phase I testing has been completed, test completed Dental air
system using applicable gas for each system. Completed systems have outlets and
inlets, alarms, and gages installed; and gas supply systems installed and ready for
operation.
1. Final Purging: Introduce applicable gas for each system into respective piping
systems. Purge installed outlet valves to remove nitrogen test gas present from
Phase I testing.
2. Outflow Analysis: Analyze gas at positive-pressure outlets to confirm delivery of
proper gas at proper concentration level. Minimum allowable concentration levels
are defined by USP-NF, "U.S. Pharmacopeia 23--National Formulary 18" and the
following CGA Commodity Specifications:
3. System Delivery Pressures: Test pressure piping systems to confirm supply
sources are set to deliver gas at the following nominal pressure levels:
a. Dental Air Systems, except High-Pressure Air: 345 to 380 kPa (50 to 55
psig) at maximum flow.
H. Certification: Certify that specified inspections, tests, and procedures have been
performed and report results in writing to Engineer. Include the following:
1. Inspections performed.
2. Procedures, materials, and gases used.
3. Test methods used.
4. Results of tests.
3.8 COMMISSIONING
D. Operate and adjust operating and safety controls. Replace damaged and malfunctioning
controls and equipment discovered by service representative.
3.9 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes general description of Heating, Ventilation and Air Conditioning
systems.
U. Section 23 7313 - Modular Indoor And Outdoor Air Handling Units / fresh Air Handling
Units
A. HVAC Contractor executing this work shall be having minimum 10 years of experience
in the installation of similar HVAC system and shall meet all requirement by PAHW
quality control department.
1.04 SUBMITTALS
C. Submit 4 copies of the product data and shop drawings. Allow for (4) weeks for review
and approval, before placing order or commencing work.
1. Manufacturers printed brochures and catalogues (one original and three copies)
with relevant information highlighted, along with write up of selection criteria.
2. General piping and ducting layout drawings to a scale not smaller than 1:50.
3. Equipment installation and piping layout, double line drawings clearly indicating
all fittings, supports, valves etc. to a scale of 1:20. Submit sections and wall
elevations as appropriate.
4. Typical floor plans indicating shafts, risers locations etc. to a scale of 1:50.
5. Builder's work layout plans to a scale of 1:100/1:50 as above.
6. Electrical & control wiring diagrams (NTS) and panel installation details (1:20).
7. Calculations/details to substantiate the shop drawings.
8. Test and performance certificates of equipment, where required.
9. Provide composite shop drawings and sections.
E. Submit three (3) copies of “Operation & Maintenance Manual” with complete data for
each piece of equipment installed and as detailed below:
1. The cover shall contain:
KEO/19-3262-0000 23 0100/2 Hvac Systems – General Description
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
a. The title: Operation & Maintenance Manual – HVAC Services
b. The name of:
1) The Employer
2) The Consultant
3) The Contractor
2. The Manual shall contain:
a. Table of Contents – Submit sample for approval.
b. HVAC material submittals with the Engineer’s and or local authorities’ s
approval.
c. Manufacturer’s installation, Operation & Maintenance instructions.
d. Manufacturer’s internal wiring diagrams.
e. Manufacturer’s assembly details.
f. Replacements, parts number listings and description.
g. Lubrication materials, equivalents and schedules.
h. Name and addresses of Manufacturer, Sales and Service Agency and
Local Representative/Distributor.
i. Name and address of Contractor’s Maintenance Department, including
emergency contact telephone number.
j. Equipment Warranties.
k. Testing, Adjusting and Balancing Report.
l. Equipment start-up and test report.
1.06 SCOPE
A. The work covered by this Section consists of manufacture, supply, installation and
maintenance of the heating, ventilation and air-condition installation of the project and
includes the design, manufacture, Inspection and testing at manufacturer’s premises,
packing for export shipments, insurance, delivery to site, erection, setting to work,
adjusting, testing, balancing and handing over in perfect operating and running condition
B. All HVAC equipment shall be in compliance with local codes and international codes &
standards as specified in clause no. 1.05 D.
1.07 DESCRIPTION
A. The drawings, specifications, schedules of equipment and bill of quantities and all other
contract documents are complementary to each other and any material, equipment,
plant or works called for either part shall be furnished by the contractor and included in
the contract as if called for by all parts. Should the tenderer discover any conflict,
discrepancy, error or omission.
B. The employer shall issue his instructions to all tenderers by supplement notices and
each tenderer shall comply with and allow in his rates for complying with such
instruction before submitting his tender on the prescribed date.
C. The contractor shall take into consideration that the drawings are meant to shown the
general picture and layout without much details and shall not reflect the final execution
of the works. The contractor shall furnish all drawings, sketches and all details required,
and all items, parts and material necessary to make the installation complete and ready
to operate without any additional cost in price whether such items are particularly
specified or not.
D. The contract drawings shall indicate the extent and general arrangement of the specified
systems. If any deviations from the contract documents are deemed necessary by the
contractor, details of such deviations and reason therefore shall be submitted as soon
as practicable to the engineer for approval. No such deviations shall be made without
the prior written approval of the engineer.
E. The works covered by this specification in general shall be sized, located and performed
as indicated on the drawings and in the specifications. They shall be installed and
adjusted in accordance with the manufacturer’s instructions and these specifications to
ensure that they fulfill the design condition. However, the contractor shall be responsible
for checking and making sure that the system design, drawings and schedule of all
equipment satisfy the design requirements. The design, drawings and schedules shall
not relieve the contractor of his obligation towards proper selection and functioning of all
specified equipment. If, after the systems are in operation, any equipment and any work
should appear inconvenient, abnormal, or give unsatisfactory operation after
adjustment, the contractor shall replace them with a type selected by the engineer and
shall make any other changes that may be necessary without any additional charges to
the employer.
F. The contractor shall install the works as closely as possible to the layout shown and the
layout shall be checked and exact locations shall be determined by the dimensions of
the equipment approved. The contractor shall be responsible for co-ordination of his
drawings for space clearance with the works of other trades and services affecting his
works and shall consult the architectural and structural drawings for all dimensions,
openings, clearances, partitions, false ceilings, beams, expansions joints, structural
supports, foundation details, etc. before submitting the working drawing for approval.
A. The Ministry of Public Works Particular Specifications shall be applied unless otherwise
mentioned in the technical specifications.
A. The tendered shall enclose with his offer the original engineering technical catalogues
for all air conditioning equipment and machines.
A. The contractor shall be deemed to have included for all materials, labor etc. for the
complete installation of the plant whether detailed under contract documents or not.
B. Should the Tenderer discover discrepancy in the tender documents, he shall notify the
Employer in writing in reasonable time during the tendering stage period.
C. The Contractor shall be obliged towards proper selection of all specified equipment. If,
any work give unsatisfactory operation, the Contractor shall replace them with a type
selected by the Engineer and shall make any other changes that may be necessary
without any additional charges to the Employer.
D. The Contractor shall install the works as closely as possible to tender drawings layout,
but shall make without additional cost any changes in routing to meet job condition.
A. Electrical works scope starts from outgoing terminals of the isolator/ switch-fuses / sub-
main switchboards provided by Electrical Contractor.
1.13 MANUFACTURERS
A. Air quality should comply with ASHRAE Standard 55-2004 Thermal Environmental
Condition for Human Occupancy.
A. The fresh air is introduced via infiltration in compliance with ASHRAE standard 62.1,
and IMC.
A. Ministry of Electricity and Water (MEW Kuwait) Energy Conservation program code of
practice MEW/R-6 (2018) & R-7 (2010) will be applied in all design aspects. The
contractor must comply and implement any revised or new regulation from MEW without
any extra cost or time.
B. External Walls and slab: Refer to architecture specification for wall and slab construction
details. Overall, U value shall not exceed 2018 MEW regulation.
C. Walls between air conditioned and non-conditioned space ( partitions) shall have U –
Value not to exceed 2.6 W/m². C for shafts , lifts and stair case
D. Roof: Refer to architecture specification for roof construction details. Overall, U value
shall not exceed 2018 MEW regulation.
A. Smoke Control system shall be based on the KFF (Kuwait Fire Force) requirement at
that time of construction. The contractor shall be responsible for the implementation of
any above-mentioned requirement from KFF.
A. Building Management System shall be provided to manage, monitor and control HVAC
system.
B. Stand-alone control system shall be based on thermostat and local switches wherever
BMS is not applicable.
C. Follow latest regulation of MEW while selecting thermostat for A/C units.
PART 3 - EXECUTION
3.01 COORDINATION
A. Study all drawings and specifications and familiarize with the Structural and
Architectural details.
B. Ensure that the works under this section are compatible with the Architectural finishes,
prior to placing orders, fabrication and installation.
C. Co-ordinate with the Electrical works for the exact power requirements and location and
type of the interface. Furnish all information as required by the local authority having
jurisdiction for obtaining approvals.
D. Where work is installed in close proximity, to or will interfere with other works, take
necessary measures for satisfactory space arrangements. Prepare composite shop
drawings to a suitable scale, showing how the work is installed in relation to other work.
E. Ensure the sufficiency of dimensions of the plant areas, doors etc. and the suitability of
slabs and other structural members for placement, operation and maintenance of
equipment.
F. Resolve conflicts in requirements with other works. Refer to the owner representative
only those that cannot be solved, without changes to structure or those, which involve
major changes to system design.
G. Contractor shall prepare coordinated working drawings with all required information,
submit to the relevant trades and obtain their approval.
A. Submit factory testing certificates for all A/C units before shipment. Include in these
certificates the machine capacity, power consumption, noise and vibration performance
when tested in operation conditions with specified capacity. Submit all calculations to
derate the capacity for the design conditions compared to the test conditions.
B. At this performance test, measure electrical data during start up period including starting
current, starting power factor and voltage dip (if any).
C. Examine areas and conditions under which VRF cooling units are to be installed. Do not
proceed with the work until unsatisfactory conditions have been corrected.
D. The Contractor shall provide all testing instruments and accessories complete with valid
calibration certificate to the presence of the Engineer as directed below or elsewhere
for approval.
E. Carry out the testing, adjusting and balancing of the HVAC Equipment and systems
under provisions of section 23 0593.
3.03 START – UP
A. Start-up VRF cooling units, in accordance with manufacturer's start-up instructions. Test
controls and demonstrate compliance with requirements. Replace damaged or
malfunctioning controls and equipment.
B. Balance VRF systems to verify its capacity and balanced delivery of air for each space.
A. Contractor shall not make any claims/variation due to re-routing of HVAC ducts, pipe
etc. to meet site requirements. In case of any disparity in schedule parameters and
capacities, always provide higher capacity resulting from all design parameters as
scheduled. Contractor shall not claim any variation while submitting any equipment,
which consumes less or more electrical power than shown on schedule during any
stage of the project.
A. Contractor shall be completely responsible for repairing, replacing with new to the
satisfaction of Owner, all and any HVAC installed system found defective or not
satisfactorily operating, for a period specified in division 01, without any extra cost to the
Owner.
KEO/19-3262-0000 23 0100/9 Hvac Systems – General Description
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. Defects liability period shall be two years from substantial completion.
A. Contractor shall include in his offer for complete operation and maintenance of the
installed HVAC plant for a period specified in division 01. This offer shall include all man
power, material, parts, labor etc, (all inclusive).
B. Extra man power shall be provided as required to accomplish the maintenance work.
B. The contractor shall make sure that HVAC system shall be capable to operate on
temporary power without affecting the warranty and defects period of the equipment, as
specified in division 01.
D. Warranty shall include complete regular maintenance for all HVAC equipment.
A. All HVAC equipment installed shall meet all MEW regulations including watts/sqr mtr,
KW/TON. All HVAC equipment shall be procured and installed only after obtaining
MEW approval. HVAC contractor shall submit all calculations to Engineer for approval.
B. Furnish all information as required by the authorities to obtain approvals without the
assistance of designer. The designer may provide design cooling load zonal
calculations, at his discretion, if such calculations are required by authority.
C. Contractor shall take necessary approval from KFD if any smoke ventilation system is
required by KFD during the time of construction.
A. In addition to the spare parts, tools and maintenance equipment provided by the
Contractor at the Maintenance Period, the Contractor shall supply spare parts, tools and
maintenance equipment specified herein for use after the expiry of such Maintenance
Period, and store the same in a location in the building designated by the owner. Such
specified spare parts, tools and maintenance equipment shall not be used by the
Contractor during the period of maintenance unless in an emergency and as expressly
authorized by the Engineer.
C. All spare parts, tools and maintenance equipment shall be provided in original packing,
clearly labeled and referenced. Provide complete schedules of spare parts and
maintenance equipment clearly cross referenced with the “as-built” record drawings and
with operation and maintenance instructions manuals.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
B. Sections of this Services Specification which relate to other Divisions are not intended to
supersede the specifications of these divisions, but to guide the Contractor in tendering
and performance. In no event shall a quality less than that indicated here be acceptable.
D. The scope of works includes the supply, delivery to site, installation, testing,
commissioning, demonstrating and staff training of the various complete systems
outlined in this specification and on the drawings and documentation including liaison
with the Main Contractor, Authorities, Master Plan Developer and their representatives
and Consultants as necessary for the duration of the works and the defects liability
period
E. The contractor will be responsible for reaching an agreement on their Program with the
Main Contractor and coordinating every aspect of their design, submissions, approvals
as well as installation, testing, commissioning and handover works with them
F. Wherever the term authorities is indicated, it shall mean statutory authorities, the master
plan developer or their representatives and services provider.
G. The contractor shall Check issued drawings and accept responsibility for proper
performance of all mechanical and plumbing systems in accordance with relevant
standards and codes and design parameters listed hereinafter
H. The contractor shall provide all items, articles, materials, samples, operations, sundries,
labour, supervision, guarantees, allowances for overhead and profit, etc., to achieve a
fully functionable and acceptable system
I. The contractor shall consider the specifications as an integral part of the work together
with the drawings. Consider any item or subject omitted from one but mentioned or
reasonably implied on the other as properly and sufficiently indicated and provide the
same under the work of this division.
A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred
spaces, pipe and duct chases, unheated spaces immediately below roof, spaces above
ceilings, unexcavated spaces, crawlspaces, and tunnels.
D. Concealed, Interior Installations: Concealed from view and protected from physical
contact by building occupants. Examples include above ceilings and chases.
E. Concealed, Exterior Installations: Concealed from view and protected from weather
conditions and physical contact by building occupants but subject to outdoor ambient
temperatures. Examples include installations within unheated shelters.
A. HVAC Contractor executing this work shall be having minimum 10 years’ experience in
the installation of similar HVAC system and having required registration as Mechanical
Contractor with Central Tender Committee.
B. Contractor shall appoint one Graduate Mechanical HVAC Engineer for site work,
(Society of Engineers approved) with minimum 10 years’ experience in similar HVAC
installations and one foreman of 10 years of experience in similar HVAC installations.
The name, qualification and experience of the nominated engineer / foreman shall be
submitted to Engineer for approval.
A. Visit the site of the proposed works and obtain all information as to existing conditions
and limitations and all proposed works on adjacent sites and in adjacent areas which
might affect the works on this site, whether by Private Individuals or by Government
Authorities or others.
B. Examine the documents including the Specifications and Drawings of all other Divisions
before bidding and again before commencing any portion of the works.
C. Neither the Owner nor the Consultant will be responsible for any claim for extra work or
expense resulting from the failure of the Contractor to be fully aware of Site Conditions,
Drawing implications, etc.
KEO/19-3262-0000 23 0500/3 Common Work Results For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1.06 PERMITS, FEES AND INSPECTIONS
A. Arrange for inspection of all work by the Authorities having jurisdiction over the works.
This is to occur on an on-going basis throughout construction to avoid delays at the
termination of the project. On completion of the work present to the Consultant, for the
Owner, final unconditional approval certificates of the Inspecting Authorities and the
master plan developer or their representatives.
C. Before commencing any work on site, submit the required number of copies to the
relevant Authorities for checking and approval. Follow the progress of such drawings to
permit the timely approval of them by the Authorities. Comply with any changes
requested by the Authorities but notify the Consultant immediately of any such change
for proper processing of these requirements. The Contractor, working on a regular basis
with the Authorities is expected to know which changes are likely at the time he bids the
job, and no extra cost will be allowed for such changes.
A. The drawings for services works are performance drawings, diagrammatic, and intended
to convey the scope of work and indicate general arrangement and approximate
locations of apparatus, fixtures, pipe and duct runs, etc. The drawings do not intend to
indicate architectural or structural details, nor do they show any fabrication or installation
details.
B. Do not scale drawings. Obtain accurate dimensions to structure and architectural items
from drawings of those trades. Confirm by site measurement. Verify location and
elevation of all services (Water, Electrical, Telephone, Sanitary, Storm Drainage, Gas,
etc.) before proceeding with the work.
E. Install all ceiling mounted components (Diffusers, grilles, etc.) in accordance with the
reflected ceiling drawings which are to be prepared by the Contractor and coordinated
with all trades. These must be submitted for approval and be approved before any work
commences on site.
F. Leave space clear and install all work to accommodate future materials and/or
equipment as indicated and/or supplied by another division of work of the contract.
Install all pipe runs, conduit runs, cable trays, etc., to maintain maximum headroom and
clearances, and to conserve space in shafts and ceiling spaces and under floors, and to
provide adequate space for service and maintenance.
A. Prepare fully coordinated drawings in conjunction with all trades concerned, showing
sleeves and openings for all passages through structure and all insert sizes and
locations.
C. The location of final fix items such as supply / return air diffusers and sprinkler heads
shown in the contract drawings are indicative only. Contractor shall co-ordinate with the
reflected ceiling plans and Interior design drawings and agree the actual location in
relation to other items such as light fittings, smoke detectors, speakers etc. Final
location should be based on the approved reflected ceiling plans prepared by Contractor
and obtain approval from the Architect / Engineer.
D. Prepare drawings of equipment bases, pump pits, anchors, inertia slabs, floor and roof
curbs, wall openings, trenches, pertaining to mechanical work.
E. Prepare all drawings to scale as agreed with the Consultant. Forward these drawings,
approved by all trades concerned to the Consultant for his records. Provide soft copies
and provide printed copies in a number as specified elsewhere in the Contract but not
less than four sets.
F. Bind one complete set of construction drawings showing "as built" conditions in each
operating and maintenance instruction manual. The extent of these drawings will be
indicated to the Contractor in advance by the Consultant.
E. Submit three (3) copies of “Operation & Maintenance Manual” with complete data for
each piece of equipment installed and as detailed below:
1. The cover shall contain:
a. The title: Operation & Maintenance Manual – HVAC Services
b. The name of:
1) The Employer
2) The Consultant
3) The Contractor
2. The Manual shall contain:
a. Table of Contents – Submit sample for approval.
1) HVAC material submittals with the Engineer’s and or local
authority’s approval.
2) Manufacturer’s installation, Operation & Maintenance instructions.
3) Manufacturer’s internal wiring diagrams.
4) Manufacturer’s assembly details.
5) Replacements, parts number listings and description.
6) Lubrication materials, equivalents and schedules.
7) Name and addresses of Manufacturer, Sales and Service Agency
and Local Representative/Distributor.
8) Name and address of Contractor’s Maintenance Department,
including emergency contact telephone number.
9) Equipment Warranties.
10) Testing, Adjusting and Balancing Report.
11) Equipment start-up and test report.
G. Welding certificates.
H. Submit shop drawings and samples for materials and equipment as listed in this and in
each subsequent section.
J. Present a schedule of shop drawings and material submittal after award of the contract
and not later than what is specified in the contract documents, indicating the anticipated
date when the drawings will be submitted for review. Assume full responsibility for timely
submission of all drawings. Allow a minimum of two weeks for the Consultant's review
K. Drawings production and presentation is a Contractual matter and any delay on the
Contractor's behalf in making these submissions will be considered a Contractual delay
and may be subject to Contractual penalties and other remedies as determined by the
Consultant.
L. The Consultant will only consider shop drawings bearing the stamp of the Contractor
and all Subcontractors involved. Check for all pertinent information such as physical
dimensions, make, performance, electrical characteristics and indicate the intended use
and location before submitting these drawings. Use reference symbols or enumeration
to correspond to the design drawings.
N. The submission of samples will be subject to the same procedure as that of shop
drawings. One set of such samples shall be required to be brought to site and kept there
after approval till substantial completion.
O. Prepare drawings in conjunction with all trades concerned, showing sleeves and
openings for all passages through structure and all insert sizes and locations.
Q. Base equipment drawings upon shop drawings and include but do not necessarily limit
to, all details pertaining to access, cleanouts, tappings, sleeves, electrical connections,
drains, location and elevation of pipes, ducts, conduits, etc., obtained from consultation
with, and agreement of, all trades involved.
R. Prepare drawings of equipment bases, pump pits, anchors, inertia slabs, floor and roof
curbs, wall openings, trenches, pertaining to mechanical work.
S. The Consultant is not responsible for any delays caused by the inadequacy of the
Contractor's drawings or his failure to obtain initial or subsequent approval. Any time
taken by the Contractor to obtain approval after the originally scheduled date will be
considered as a delay to the contract caused by the Contractor.
T. When drawings are marked "resubmit specified item", the Contractor is to resubmit the
item as originally specified or as may be determined to be equivalent by the Consultant.
The Consultant is the sole arbiter of whether any item is satisfactory or equivalent.
U. When drawings are marked "rejected" a complete resubmission of the particular drawing
is necessary, subject to the same conditions as outlined above.
W. Furnish prints of the reviewed details to all other parties who may require them for
proper coordination of their work and furnish all information necessary for the work as a
whole.
X. Obtain Manufacturers' installation directions to aid in the proper execution of the work.
Submit two copies of such directions to the Consultant prior to installation, for use in
inspecting the work.
Y. Bind one complete set of checked shop drawings into each operating and maintenance
manual.
A. As the job progresses, mark on one set of prints to accurately indicate the status of
installed work. Have the white prints available for inspection at the site at all times and
present them for scrutiny at all job meetings. Obtain the Contractor's approval before
forwarding these to the Consultant. Submit two sets of white prints to the Consultant for
checking and approval.
B. Upon approval, submit one set of soft copy and five sets of white prints to the consultant
for onward transmission to the client.
C. Show on the record drawings the installed inverts of all services entering and leaving the
building and the property. Dimension underground services at key points of every run in
relation to structure and building. Record all elevations for underground services in
relation to floor level of the building and give reference datums to Municipal
benchmarks.
D. Indicate exact location of all services left for future work. Show and dimension all work
embedded in the structure.
A. Do not use any of the permanent service facilities during construction, unless specific
written approval is obtained from the Consultant and the Owner or where specifically
allowed elsewhere in the Contract Documents.
B. The use of permanent facilities for temporary services will not affect, in any way, the
commencement day of the period in which the correction after completion is the
Contractor's responsibility. Such period will commence only when the overall project is
completed, and certificates of acceptance are issued.
D. Any generator must have full safety features and must be maintained regularly to ensure
site power at all times.
A. Before this Contractor undertakes work in any area he must prepare a list of deficiencies
in that area which affect his works, or which could possibly be construed as being
caused by himself if not noted. In the event that such deficiency list is not prepared, then
he shall be deemed responsible for such deficiencies. Any list shall be brought to the
attention of the Consultant forthwith.
1.013 SUPERVISION
A. The Subcontractor will maintain at site, as necessary for the performance of the
Contract, qualified personnel and supporting staff, with proven experience in erecting,
testing, and adjusting projects of comparable nature and complexity.
B. Before commencing work the Contractor will submit details of the proposed Engineers
and Supervisors, including copies of their Certificates. If in the Consultant's opinion the
proposed Engineers or Supervisors are not adequately qualified or are otherwise
unacceptable, the onus is on the Contractor to submit alternates until such approval is
given.
E. In the event of any negligent or severely detrimental behavior the Consultant has the
right to order the removal from site of any Engineer, Supervisor, or worker on a
"forthwith" basis.
F. The Contractor will remedy the situation on a similar forthwith basis and in any event will
not be allowed to proceed with any area of work which as a result is left without proper
supervision or technical backup until such time as the Consultant is again satisfied by
the measures taken.
A. Unless specifically instructed otherwise by the Consultant the works are to continue to
completion in the most expeditious manner.
B. Obtain approval of shop drawings / Asbuilt drawings from all Authorities having
jurisdiction. All costs towards such approvals to be borne by the contractor.
A. All refrigerant piping assembled at site shall consist of copper tubing to ASTM
specification B -88 type “k” hard drawn and soldered joints. Joints fittings shall be of
wrought copper or cast brass. Where required for gauges etc. tubing not larger than
3/8” may be of type “k” soft ( annealed) with flared tube or double ferrule
compression fitting suitable for high pressure . flux and solder, recommended by
the manufactures of tubing and fittings and, shall only be used during
installation.
B. Steel Support Welding: Qualify processes and operators according to AWS D1.1,
"Structural Welding Code--Steel."
C. Steel Pipe Welding: Qualify processes and operators according to ASME Boiler and
Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications."
1. Comply with provisions in ASME B31 Series, "Code for Pressure Piping."
2. Certify that each welder has passed AWS qualification tests for welding
processes involved and that certification is current.
A. Protect all mechanical, plumbing & electrical works from damage. Keep all equipment
dry and clean at all times.
B. Cover all openings in equipment and materials. Cover all temporary openings in ducts
and pipes with polyethylene sheets or caps until final connection is made. The quality of
such cover must be determined with due regard to how long it may be until final
connection
C. Be responsible for and make good any damages caused directly or indirectly to any
walls, floors, ceilings, woodwork, brickwork, finishes, services, roads, gardens, etc.
D. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through
shipping, storage, and handling to prevent pipe end damage and to prevent entrance of
dirt, debris, and moisture.
E. Store plastic pipes protected from direct sunlight. Support to prevent sagging and
bending.
C. Coordinate requirements for access panels and doors for HVAC items requiring access
that are concealed behind finished surfaces. Access panels and doors are specified in
Division 08 Section "Access Doors and Frames."
D. Confer with all trades installing equipment which may affect the work of this division and
arrange equipment in proper relation with that equipment installed under all Divisions of
the Contract.
E. Furnish all items to be built in by others, in time, complete with all pertinent information,
commensurate with the progress of the work.
F. Store materials neatly and out of the way and clean up all refuse caused by the work
daily.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Refer to individual Division 23 Refrigerant piping Section for pipe, tube, and fitting
materials and joining methods.
A. Refer to individual Division 23 piping Sections for special joining materials not listed
below.
B. Pipe-Flange Gasket Materials: Suitable for chemical and thermal conditions of piping
system contents.
1. ASME B16.21, nonmetallic, flat, asbestos-free, 1/8-inch (3.2-mm) maximum
thickness unless thickness or specific material is indicated.
a. Full-Face Type: For flat-face, Class 125, cast-iron and cast-bronze
flanges.
b. Narrow-Face Type: For raised-face, Class 250, cast-iron and steel
flanges.
2. AWWA C110, rubber, flat face, 1/8 inch (3.2 mm) thick, unless otherwise
indicated; and full-face or ring type, unless otherwise indicated.
C. Flange Bolts and Nuts: ASME B18.2.1(hot dip galvanized), carbon steel, unless
otherwise indicated.
E. Solder Filler Metals: ASTM B 32, lead-free alloys. Include water-flushable flux
according to ASTM B 813.
F. Brazing Filler Metals: AWS A5.8, BCuP Series, copper-phosphorus alloys for general-
duty brazing, unless otherwise indicated; and AWS A5.8, BAg1, silver alloy for
refrigerant piping, unless otherwise indicated.
G. Welding Filler Metals: Comply with AWS D10.12 for welding materials appropriate for
wall thickness and chemical analysis of steel pipe being welded.
C. Plastic-to-Metal Transition Unions: MSS SP-107, CPVC and PVC four-part union.
Include brass end, solvent-cement-joint end, rubber O-ring, and union nut.
A. Description: Combination fitting of copper alloy and ferrous materials with threaded,
solder-joint, plain, or weld-neck end connections that match piping system materials.
G. Dielectric Nipples: Electroplated steel nipple with inert and noncorrosive, thermoplastic
lining; plain, threaded, or grooved ends; and 300-psig (2070-kPa) minimum working
pressure at 225 deg F (107 deg C).
A. Description: Modular sealing element unit, designed for field assembly, to fill annular
space between pipe and sleeve.
1. Sealing Elements: EPDM interlocking links shaped to fit surface of pipe. Include
type and number required for pipe material and size of pipe.
2. Pressure Plates: Carbon steel. Include two for each sealing element.
3. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of
length required to secure pressure plates to sealing elements. Include one for
each sealing element.
2.07 SLEEVES
B. Steel Pipe: ASTM A 53, Type E, Grade B, Schedule 40, galvanized, plain ends.
C. Cast Iron: Cast or fabricated "wall pipe" equivalent to ductile-iron pressure pipe, with
plain ends and integral water stop, unless otherwise indicated.
D. Stack Sleeve Fittings: Manufactured, cast-iron sleeve with integral clamping flange.
Include clamping ring and bolts and nuts for membrane flashing.
1. Under deck Clamp: Clamping ring with set screws.
E. Molded PE: Reusable, PE, tapered-cup shaped, and smooth-outer surface with nailing
flange for attaching to wooden forms.
2.08 ESCUTCHEONS
A. Description: Manufactured wall and ceiling escutcheons and floor plates, with an ID to
closely fit around pipe, tube, and insulation of insulated piping and an OD that
completely covers opening.
E. One-Piece, Stamped-Steel Type: With set screw or spring clips and chrome-plated
finish.
KEO/19-3262-0000 23 0500/13 Common Work Results For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
F. Split-Plate, Stamped-Steel Type: With concealed hinge, set screw or spring clips, and
chrome-plated finish.
H. Split-Casting, Floor-Plate Type: Cast brass with concealed hinge and set screw.
2.09 GROUT
PART 3 - EXECUTION
3.01 WORKMANSHIP
D. Install control valves to guarantee proper sensing. Shield elements from direct radiation
and avoid placing them behind obstructions.
G. Replace all work unsatisfactory to the Consultant without extra cost and to the standard
required by the Consultant. This applies to any item which is found to be defective in
service during the maintenance period, or extended maintenance period as appropriate.
H. Where height dimensions are given, the installation shall be reasonably expected to be
within 1/8" (3mm) of the design dimensions. Where room centre or proportion
dimensions are not shown these shall be reasonably expected to be located on site to
within 1/2" (13mm) of actual position.
I. Items displaying a horizontal dimension or edge must be plumbed with a level and must
be to the Consultant's satisfaction. Any apparent discrepancy between "level" electrical
items and adjacent items MUST be reported immediately to the Consultant.
B. "New" is defined as newly manufactured, "state of the arts," tested and proven item of
equipment. Items which have been held in stock for any extended period of time by
either the Manufacturer or the Supplier will be rejected.
C. All materials used on this project shall bear the third-party quality assurance stamp like
British Standard Kitemark, UL, FM, NFPA, WRAS, DVGW and/or other quality
assurance authority as stated herein elsewhere.
3.03 CLEANING
A. Each day as the work proceeds and on completion, clean up, vacuum, wipe down,
remove labels and markings from equipment and remove from the premises all rubbish,
surplus material, equipment, machinery, tools, scaffolds, and other items used in the
performance of the work. Clean out dirt and debris and leave the buildings clear and
free from rubbish, waste, dust, dirt, debris and sand. Equipment is to be spotless and in
‘Brand New’ condition at handover complete with new or thoroughly cleaned filters and
in a condition acceptable to the Consultant.
B. Where electrical items form part of the visible finish in the rooms, protect from over-
painting, etc. and give all items a final cleaning before handing over of the project.
3.04 ACCESSIBILITY
A. Inform all other Divisions in time concerning required openings. Obtain the approval of
the Consultant before doing any cutting.
B. Obtain the approval of the Consultant before doing any cutting. Supporting members of
any floor, wall or the building structure shall only be cut and in such a manner as
approved by the Consultant. All reinstatement work must be done to the same standard
as the original work.
A. Under this section supply necessary sleeves and other inserts to other trades.
C. Use factory made expansion shields where inserts cannot be placed, but only where
approved by the Consultant and for light weights.
D. Do not use powder activated tools except with the written permission of the Consultant.
E. Supply and locate all inserts, holes, anchor bolts, and sleeves in good time when walls,
floors, and roof are erected.
F. Pass insulation unbroken where pipe or duct is insulated. Size sleeves to provide
adequate clearance all around and in accordance with specialist supplier’s
recommendations.
H. Pack all sleeves between the insulated pipe and the sleeve or where un-insulated
between the pipe and the sleeve with loose fibreglass insulation. Seal the annular space
as follows:
1. For all horizontal sleeves in exposed areas, use a seal equal or better fire rated
than the wall to be sealed.
2. For all vertical sleeves through roofs, janitor's closets, equipment rooms, use
permanently resilient silicone-based sealing compound, non-inflammable and
waterproof (fire sealant). Ensure that the seal is compatible with floor and ceiling
finishes. Check the room finishing schedules for further details and clarify if
necessary with the Consultant.
3. Cover exposed floor and wall pipe sleeves in finished areas with satin finish
chrome or nickel-plated solid brass or with satin finished stainless steel
escutcheons with non-ferrous set screws. Split cast plates of the screw locking
type may not be used. Do not use stamped steel friction type split plates Through
roofs, provide curbs and sleeves as shown on drawings and to suit flashing
requirements.
J. After ducts are installed, pack the opening and seal the packing as follows:
1. Use fibreglass insulation for packing except through curbed concrete floors
where asbestos braid must be used.
2. Seal the asbestos braid packing in openings through floors with permanently
resilient silicone base non-inflammable waterproof compound. Press duct
supports firmly down into caulking before bolting it down to curb.
3. Through all vertical walls seal the fibreglass packing using permanently resilient
silicone-based water proof sealant.
K. Brace duct sleeves and box-outs to retain their position and shape during the pouring of
concrete and other work.
L. Provide bracing for each duct at every passage through structure to prevent sagging.
M. Cover exposed pipework, gullies, duct sleeves and openings in exposed areas. Use 100
mm galvanized steel escutcheons in the form of a duct collar or screw fixed pipework
cap or similar approved protection. Over curbs extend the collar 30 mm down the side of
the curb, similar to counter flashing Fix collar in ace with Cadmium plated screws.
B. Provide the respective Division of work with panels, doors or frames, complete with all
pertinent information for installation.
C. Ensure that access doors are installed in a manner to match the building grids where
applicable
D. Prepare detail drawings showing location and type of all access doors in coordination
with other trades before proceeding with installation and hand these to the Contractor to
obtain approval.
E. Size all access doors to provide adequate access and commensurate with the type of
structure and Architectural finish. Should it be necessary for persons to enter, provide a
minimum opening of 600 x 450 mm.
H. Provide panels in glazed tile walls of 2.6mm thick 304 alloy stainless steel, no. 4 finish,
with recessed frame secured with stainless steel, countersunk, flush-headed screws.
I. Provide panels in plaster surfaces with dish shaped door and welded metal lath, ready
to take plaster. Provide a plastic grommet for door key access.
J. Provide other access doors of welded 2.6 mm thick steel, flush type with concealed
hinges, lock and anchor straps, complete with factory prime coat. Submit details to
Consultant for approval.
3.08 FLASHING
A. Flash all mechanical and electrical parts passing through or built into a roof, an outside
wall, or a waterproof floor.
B. Provide uPVC or GI sleeves (depending on pipe material) with puddle flanges for
services crossing water proofed walls in basement.
D. All flashing shall suit roof angle and shall extend a minimum of 400 mm on all sides.
Leave the flashing as directed by the Contractor for him to build into the roofing system
to render a completely watertight connection.
E. Provide counter flashing on all stacks, ducts, and pipes passing through roofs to fit over
flashing or curb.
G. Provide pipes and sleeves passing through outside walls with lead or copper flashings
and as directed by the Consultant. All visual aspects of such sleeves to be approved by
the Consultant.
H. Pay special attention to the waterproofing conditions of basements and walls and floors
that may exist. Cooperate at all times with the waterproofing trade and do not cut or
destroy any waterproofing seal without the consent of the waterproofing trade.
I. Provide piping sleeves passing through waterproof walls with asphalt roofing felt
wrapped around so as to leave a 25 x 50 mm recess on both sides of the wall. These
recesses and the space between pipe and sleeve will be caulked by the General
Contract, Moisture protection, or Waterproofing, Division.
A. The Contractor shall guarantee all material and workmanship for at least 2 years after
the issue of final completion certificate and take over by the Engineer and Owner.
Extended warranty for particular items/ equipment shall be as specified in related
specification sections.
C. Guarantees will be full guarantees and will include all Parts, Labor, overhead, profit,
incidental charges and sundries.
D. Where damage is caused to any other item by any failure of the item guaranteed, then
the guarantee shall also include the costs incurred in rectifying that damage.
E. Contractor shall be completely responsible for repairing, replacing with new to the
satisfaction of Owner, all and any HVAC installed system found defective or not
satisfactorily operating, for a period of two year from the date of handing over
completion certificate to the client, without any extra cost to the Owner.
F. Warranty shall include complete regular maintenance for all HVAC equipment.
A. Install piping according to the following requirements and Division 23 Section 23 2300
B. Drawing plans, schematics, and diagrams indicate general location and arrangement of
piping systems. Indicated locations and arrangements were used to size pipe and
calculate friction loss, expansion, pump sizing, and other design considerations. Install
piping as indicated unless deviations to layout are approved on Coordination Drawings.
D. Install piping indicated to be exposed and piping in equipment rooms and service areas
at right angles or parallel to building walls. Diagonal runs are prohibited unless
specifically indicated otherwise.
E. Install piping above accessible ceilings to allow sufficient space for ceiling panel
removal.
K. Select system components with pressure rating equal to or greater than system
operating pressure.
KEO/19-3262-0000 23 0500/19 Common Work Results For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
L. Install escutcheons for penetrations of walls, ceilings, and floors according to the
following:
1. New Piping:
a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep-
pattern type.
b. Chrome-Plated Piping: One-piece, cast-brass type with polished chrome-
plated finish.
c. Insulated Piping: One-piece, stamped-steel type with spring clips.
d. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-
piece, cast-brass type with polished chrome-plated finish.
e. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece or
split-casting, cast-brass type with polished chrome-plated finish.
f. Bare Piping in Unfinished Service Spaces: One-piece, cast-brass type
with polished chrome-plated finish.
g. Bare Piping in Equipment Rooms: One-piece, stamped-steel type with set
screw or spring clips.
h. Bare Piping at Floor Penetrations in Equipment Rooms: One-piece, floor-
plate type.
2. Existing Piping: Use the following: (If Applicable)
a. Chrome-Plated Piping: Split-casting, cast-brass type with chrome-plated
finish.
b. Insulated Piping: Split-plate, stamped-steel type with concealed or
exposed-rivet hinge and spring clips.
c. Bare Piping at Wall and Floor Penetrations in Finished Spaces: Split-
casting, cast-brass type with chrome-plated finish.
d. Bare Piping at Ceiling Penetrations in Finished Spaces: Split-casting,
cast-brass type with chrome-plated finish.
e. Bare Piping in Unfinished Service Spaces: Split-casting, cast-brass type
with polished chrome-plated finish.
f. Bare Piping in Equipment Rooms: Split-plate, stamped-steel type with set
screw or spring clips.
g. Bare Piping at Floor Penetrations in Equipment Rooms: Split-casting,
floor-plate type.
M. Install sleeves for pipes passing through concrete and masonry walls and concrete floor
and roof slabs.
1. Cut sleeves to length for mounting flush with both surfaces.
a. Exception: Extend sleeves installed in floors of mechanical equipment
areas or other wet areas 2 inches (50 mm) above finished floor level.
Extend cast-iron sleeve fittings below floor slab as required to secure
clamping ring if ring is specified.
2. Install sleeves in new walls and slabs as new walls and slabs are constructed.
3. Install sleeves that are large enough to provide 1/4-inch (6.4-mm) annular clear
space between sleeve and pipe or pipe insulation. Use the following sleeve
materials:
a. Steel Pipe Sleeves: For pipes smaller than NPS 6 (DN 150).
b. Steel Sheet Sleeves: For pipes NPS 6 (DN 150) and larger, penetrating
gypsum-board partitions.
c. Stack Sleeve Fittings: For pipes penetrating floors with membrane
waterproofing. Secure flashing between clamping flanges. Install section
of cast-iron soil pipe to extend sleeve to 2 inches (50 mm) above finished
floor level. Refer to Division 07 Section 07 6200 - Sheet Metal Flashing
and Trim for flashing.
1) Seal space outside of sleeve fittings with grout.
KEO/19-3262-0000 23 0500/20 Common Work Results For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4. Except for underground wall penetrations, seal annular space between sleeve
and pipe or pipe insulation, using joint sealants appropriate for size, depth, and
location of joint. Refer to Division 07 Section 07 9200 - Joint Sealants for
materials and installation.
P. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and
floors at pipe penetrations. Seal pipe penetrations with fire stop materials. Refer to
Division 07 Section 07 8400 - Fire Stopping for materials.
A. Join pipe and fittings according to the following requirements and Division 23 Sections
specifying piping systems.
B. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
C. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before
assembly.
D. Soldered Joints: Apply ASTM B 813, water-flushable flux, unless otherwise indicated, to
tube end. Construct joints according to ASTM B 828 or CDA's "Copper Tube
Handbook," using lead-free solder alloy complying with ASTM B 32.
E. Brazed Joints: Construct joints according to AWS's "Brazing Handbook," "Pipe and
Tube" Chapter, using copper-phosphorus brazing filler metal complying with AWS A5.8.
G. Welded Joints: Construct joints according to AWS D10.12, using qualified processes
and welding operators according to Part 1 "Quality Assurance" Article.
H. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service
application. Install gasket concentrically positioned. Use suitable lubricants on bolt
threads.
I. Plastic Piping Solvent-Cement Joints: Clean and dry joining surfaces. Join pipe and
fittings according to the following:
1. Comply with ASTM F 402 for safe-handling practice of cleaners, primers, and
solvent cements.
2. CPVC Piping: Join according to ASTM D 2846/D 2846M.
3. PVC Pressure Piping: Join schedule number ASTM D 1785, PVC pipe and PVC
socket fittings according to ASTM D 2672. Join other-than-schedule-number
PVC pipe and socket fittings according to ASTM D 2855.
4. PVC Nonpressure Piping: Join according to ASTM D 2855.
L. PE Piping Heat-Fusion Joints: Clean and dry joining surfaces by wiping with clean cloth
or paper towels. Join according to ASTM D 2657.
1. Plain-End Pipe and Fittings: Use butt fusion.
2. Plain-End Pipe and Socket Fittings: Use socket fusion.
M. Fiberglass Bonded Joints: Prepare pipe ends and fittings, apply adhesive, and join
according to pipe manufacturer's written instructions.
D. Install equipment to allow right of way for piping installed at required slope.
3.015 PAINTING
B. Damage and Touchup: Repair marred and damaged factory-painted finishes with
materials and procedures to match original factory finish.
A. Construct suitable concrete bases for the elevated support of all floor mounted
equipment. Furnish, for the Engineer's approval, scaled layouts of all required bases,
with dimensions and location to column center lines, and templates, anchors bolts and
accessories, necessary for base construction.
B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and
elevation to support and anchor HVAC materials and equipment.
A. Cut, fit, and place wood grounds, nailers, blocking, and anchorages to support, and
anchor HVAC materials and equipment.
B. Select fastener sizes that will not penetrate members if opposite side will be exposed to
view or will receive finish materials. Tighten connections between members. Install
fasteners without splitting wood members.
3.019 GROUTING
A. Mix and install grout for HVAC equipment base bearing surfaces, pump and other
equipment base plates, and anchors.
F. Place grout on concrete bases and provide smooth bearing surface for equipment.
A. Contractor shall not make any claims/variation due to re-routing of HVAC ducts, pipe
etc. to meet site requirements. In case of any disparity in schedule parameters and
capacities, always provide higher capacity resulting from all design parameters as
scheduled. Contractor shall not claim any variation while submitting any equipment,
which consumes less or more electrical power than shown on schedule during any
stage of the project.
A. All HVAC equipment installed shall meet all local regulations including watts/sqr mtr,
KW/TON. All HVAC equipment shall be procured and installed only after obtaining
authorities approval. HVAC contractor shall submit all calculations to Engineer for
approval.
B. Furnish all information as required by the authorities to obtain approvals without the
assistance of designer. The designer may provide design cooling load zonal
calculations, at his discretion, if such calculations are required by local authority.
C. All smoke ventilation system and location of fire dampers and smoke dampers shall
meet KFF requirement. This system shall be installed only after getting KFF approval
on drawing.
A. In addition to the spare parts, tools and maintenance equipment provided by the
Contractor during the Maintenance Period, the Contractor shall supply spare parts, tools
and maintenance equipment specified herein for use after the expiry of such
Maintenance Period and store the same in a location in the building designated by the
owner. Such specified spare parts, tools and maintenance equipment shall not be used
by the Contractor during the period of maintenance unless in an emergency and as
expressly authorized by the Engineer.
B. Contractor shall supply spare parts as listed in the respective specification section for all
the equipment and other required items to two years operation as minimum. Service
including but not limited to the following:
1. Refrigerants .
2. Fan belts, filters, bearings etc. for each type for unit, fans etc.
3. Spare filter dryers.
4. Spare motor type for each fan, and unit.
KEO/19-3262-0000 23 0500/24 Common Work Results For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
All spare parts, tools and maintenance equipment shall be provided in original packing, clearly
labeled and referenced. Provide complete schedules of spare parts and maintenance
equipment clearly cross referenced with the “as-built” record drawings and with operation and
maintenance instructions manuals
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 COORDINATION
PART 2 - PRODUCTS
A. Comply with requirements in this Section except when stricter requirements are
specified in HVAC equipment schedules or Sections.
G. Bearings: Re-greasable, shielded, antifriction ball bearings suitable for radial and thrust
loading.
I. Insulation: Class F.
K. Enclosure Material: Cast iron for motor frame sizes 324T and larger; rolled steel for
motor frame sizes smaller than 324T.
B. Motors Used with Variable Frequency Controllers: Ratings, characteristics, and features
coordinated with and approved by controller manufacturer.
1. Windings: Copper magnet wire with moisture-resistant insulation varnish,
designed and tested to resist transient spikes, high frequencies, and short time
rise pulses produced by pulse-width modulated inverters.
C. Severe-Duty Motors: Comply with IEEE 841, with 1.15 minimum service factor.
A. Motors larger than 1/20 hp shall be one of the following, to suit starting torque and
requirements of specific motor application:
1. Permanent-split capacitor.
2. Split phase.
3. Capacitor start, inductor run.
4. Capacitor start, capacitor run.
C. Bearings: Prelubricated, antifriction ball bearings or sleeve bearings suitable for radial
and thrust loading.
2.07 EC MOTORS
C. Motor shall maintain a minimum of 70% efficiency over its entire operating range.
D. Bearings: PR lubricated, antifriction ball bearings or sleeve bearings suitable for radial
and thrust loading.
PART 3 - EXECUTION
C. Cable tray hangers shall be attached to ceilings with expansion anchors and studs.
Support vertical cable trays by bolting to steel angles, extending from floor to ceiling.
D. The general arrangement of power distribution in the plumbing and fire protection plant
rooms shall be as follows:
1. Rise from electrical panel to cable trays. Drop to wall mounted/free standing
panels, in cable trays.
2. Rise from panels to another layer of horizontal network of cable trays. Drop to
motors in cable trays.
E. Use flexible PVC conduits with termination bushes for connecting valve monitor
switches to ceiling roses. Attach the conduit to pipe work with cable ties/metallic straps,
where required.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Choose the applicable clauses from this section and carryout the testing, adjusting and
balancing procedure.
B. This Section includes Testing, Adjusting & Balancing (TAB) to produce design
objectives for the following:
1. Air Systems: All Air Systems and associated equipment and apparatus of
mechanical work of Constant-volume air systems.
2. Space pressurization testing and adjusting. (If applicable)
3. Vibration measuring.
4. Sound level measuring.
5. Smoke-control systems testing and adjusting. (If applicable)
6. Indoor-air quality measuring.
7. Verifying that automatic control devices are functioning properly.
8. Reporting results of activities and procedures specified in this Section.
9. Commercial Refrigeration Systems and associated equipment and apparatus of
mechanical work.
1.02 DEFINITIONS
A. Adjust: To regulate fluid flow rate and air patterns at the terminal equipment, such as to
reduce fan speed or adjust a damper.
D. Draft: A current of air, when referring to localized effect caused by one or more factors
of high air velocity, low ambient temperature, or direction of airflow, whereby more heat
is withdrawn from a person's skin than is normally dissipated.
I. Smoke-Control System: An engineered system that uses fans to produce airflow and
pressure differences across barriers to limit smoke movement.
J. Smoke-Control Zone: A space within a building that is enclosed by smoke barriers and
is a part of a zoned smoke-control system.
L. Static Head: The pressure due to the weight of the fluid above the point of
measurement. In a closed system, static head is equal on both sides of the pump.
M. Suction Head: The height of fluid surface above the centerline of the pump on the
suction side.
N. System Effect: A phenomenon that can create undesired or unpredicted conditions that
cause reduced capacities in all or part of a system.
Q. Terminal: A point where the controlled medium, such as fluid or energy, enters or
leaves the distribution system.
S. Testing, Adjusting, and Balancing (TAB) Firm: The entity responsible for performing and
reporting TAB procedures.
1.03 RELATED SECTIONS: Related work to be coordinated and used in conjunction with
this specification includes but is not restricted to:
1.04 REFERENCES
A. ASHRAE 111, Practices for Measurement, Testing, Adjusting, and Balancing of Building
Heating, Ventilation, Air-conditioning, and Refrigeration Systems.
J. BSRlA- Pre Commissioning of Pipe work Systems, 2nd Edition; Application Guide
112001.1
L. BSRlA- Achieving minimum outdoor air- commissioning and test procedures; application
Guide 1712000.
M. BSRlA- Guidance to the standard Specification for vibration testing of building services
installations; Facilities Management Specification 7.
1.05 SUBMITTALS
B. Qualification Data: , Submit 3 copies of evidence that TAB firm and this Project's TAB
team members meet the qualifications specified in "Quality Assurance" Article.
D. Strategies and Procedures Plan: Submit 3 copies of TAB strategies and step-by-step
procedures as specified in Part 3 "Preparation" Article. Include a complete set of report
forms intended for use on this Project.
E. Submit test sheet formats, drawings, schemes etc. for approval prior to commencement
of work
F. Certified TAB Reports: Submit two copies of reports prepared, as specified in this
Section, on approved forms certified by TAB firm.
G. Sample Report Forms: Submit two sets of sample TAB report forms.
H. Include identification and types of instruments used and their most recent calibration
date with submission of final test report
D. Certification of TAB Reports: Certify TAB field data reports. This certification includes
the following:
1. Review field data reports to validate accuracy of data and to prepare certified
TAB reports.
2. Certify that TAB team complied with approved TAB plan and the procedures
specified and referenced in this Specification.
E. TAB Report Forms: Use standard TAB firm's forms approved by a Commissioning
Authority.
A. Do not proceed with testing, adjusting, and balancing work until work has been
completed and is operable. Ensure that there is no latent residual work still to be
completed, and the system has started-up. Start-up shall include the following :
1. All equipment operable in safe and normal condition.
2. Temperature control systems installed complete and operable.
3. Proper thermal overload protection in place for electrical equipment.
4. Air Systems
a. Final filters clean and in place. If conditions warrant, the Contractor shall
install temporary media in addition to the final filters.
b. Duct systems clean of debris.
c. Correct fan rotation.
d. Volume dampers in place and open.
e. Coil fins cleaned and combed.
f. Access doors closed, duct, and caps in place.
g. All outlets installed and connected.
KEO/19-3262-0000 23 0593/4 Testing, Adjusting And Balancing For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
h. Duct systems leakage shall not exceed the rate specified.
1.08 COORDINATION
A. Notice: Provide seven days' advance notice for each test. Include scheduled test dates
and times.
B. Perform TAB after leakage and pressure tests on air and water distribution systems
have been satisfactorily completed.
1.09 WARRANTY
A. National Project Performance Guarantee: Provide a guarantee forms stating that TAB
firm comply and guarantee the following provisions:
1. The certified TAB firm has tested and balanced systems according to the
Contract Documents.
2. Systems are balanced to optimum performance capabilities within design and
installation limits.
PART 2 - PRODUCTS
A. Utilize test instruments and equipment for TAB work required, of type, precision, and
capacity as recommended by the Commissioning Authority.
B. All equipment shall be properly calibrated with certification providing that recent
calibration has taken place.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine installed work and conditions under which testing is to be done to ensure that
work has been completed, cleaned and is operable. Do not proceed with TAB work
until unsatisfactory conditions have been corrected in manner acceptable to Tester
B. Examine the Contract Documents to become familiar with Project requirements and to
discover conditions in systems' designs that may preclude proper TAB of systems and
equipment.
1. Contract Documents are defined in the General and Supplementary Conditions
of Contract.
2. Verify that balancing devices, such as test ports, gage cocks, thermometer wells,
flow-control devices, balancing valves and fittings, and manual volume dampers,
are required by the Contract Documents. Verify that quantities and locations of
these balancing devices are accessible and appropriate for effective balancing
and for efficient system and equipment operation.
F. Examine equipment performance data including fan and pump curves. Relate
performance data to Project conditions and requirements, including system effects that
can create undesired or unpredicted conditions that cause reduced capacities in all or
part of a system. Calculate system effect factors to reduce performance ratings of
HVAC equipment when installed under conditions different from those presented when
the equipment was performance tested at the factory. To calculate system effects for air
systems, use tables and charts found in AMCA 201, "Fans and Systems," Sections 7
through 10; or in SMACNA's "HVAC Systems--Duct Design," Sections 5 and 6.
Compare this data with the design data and installed conditions.
G. Examine system and equipment installations to verify that they are complete and that
testing, cleaning, adjusting, and commissioning specified in individual Sections have
been performed.
I. Examine HVAC system and equipment installations to verify that indicated balancing
devices, such as test ports, gage cocks, thermometer wells, flow-control devices,
balancing valves and fittings, and manual volume dampers, are properly installed, and
that their locations are accessible and appropriate for effective balancing and for
efficient system and equipment operation.
J. Examine systems for functional deficiencies that cannot be corrected by adjusting and
balancing.
K. Examine HVAC equipment to ensure that clean filters have been installed, bearings are
greased, belts are aligned and tight, and equipment with functioning controls is ready for
operation.
L. Examine terminal units, such as variable-air-volume boxes, to verify that they are
accessible and their controls are connected and functioning.
M. Examine plenum ceilings used for supply air to verify that they are airtight. Verify that
pipe penetrations and other holes are sealed.
N. Examine heat-transfer coils for correct piping connections and for clean and straight
fins.
O. Examine equipment for installation and for properly operating safety interlocks and
controls.
3.02 PREPARATION
B. Provide instruments required for testing, adjusting, and balancing operations. Make
instruments available to Engineers Representative to facilitate spot checks during
testing. Retain possession of instruments and remove at completion of services.
C. Complete system readiness checks and prepare system readiness reports. Verify the
following:
1. Permanent electrical power wiring is complete.
2. Automatic temperature-control systems are operational.
3. Equipment and duct access doors are securely closed.
4. Balance, smoke, and fire dampers are open (If available)
5. Isolating and balancing valves are open and control valves are operational.
6. Ceilings are installed in critical areas where air-pattern adjustments are required
and access to balancing devices is provided.
7. Windows and doors can be closed so indicated conditions for system operations
can be met.
A. Perform testing and balancing procedures on each system according to the procedures
contained in ASHRAE 111 and this Section.
B. Cut insulation, ducts, pipes, and equipment cabinets for installation of test probes to the
minimum extent necessary to allow adequate performance of procedures. After testing
and balancing, close probe holes and patch insulation with new materials identical to
those removed. Restore vapor barrier and finish according to insulation Specifications
for this Project. Obtain prior engineer approval for the use of plastic plugs with retainers
may be used to patch drilled holes in ductwork and housings.
C. Mark equipment and balancing device settings with paint or other suitable, permanent
identification material, including damper-control positions, valve position indicators, fan-
speed-control levers, and similar controls and devices, to show final settings.
A. Prepare test reports for both fans and outlets. Obtain manufacturer's outlet factors and
recommended testing procedures. Crosscheck the summation of required outlet
volumes with required fan volumes.
D. Determine the best locations in main and branch ducts for accurate duct airflow
measurements.
E. Check airflow patterns from the outside-air louvers and dampers and the return- and
exhaust-air dampers, through the supply-fan discharge and mixing dampers.
F. Locate start-stop and disconnect switches, electrical interlocks, and motor starters.
G. Verify that motor starters are equipped with properly sized thermal protection.
A. After completion of the works, the contractor shall and as directed by the engineer
demonstrate to the engineer that the installation is adjusted and regulated correctly to
fulfill the function for which it has been designed the contractor shall test adjust balance
and regulate the section concerned as necessary until the required conditions are
obtained. Include for continuity and insulation tests on all electrical works and tests all
interlocks safety cutouts and other protective device to ensure correct functioning. All
such tests shall be carried out in the presence of the engineer and full records of the
values obtained shall be prepared along with the final settings.
A. After finishing the initial trial tests to the satisfaction of the engineer, the contractor will
be responsible for running reliability tests of all plants and equipments.
B. The reliability tests shall be made under the full responsibility of the contractor and he
shall provide full - time skilled operators for running the plants during the whole test
period
C. Each reliability test shall last for a period of 31 consecutive days during which time the
whole of the plant under test shall operate continuously without adjustment or repair to
the satisfaction of the engineer. In the event of any repair to the adjustment having to be
made other than normal running adjustment, The test shall void and the installation shall
KEO/19-3262-0000 23 0593/8 Testing, Adjusting And Balancing For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
be re - tested after the re-adjustments or repairs have been completed a test shall not
be void due to circumstances outside the control of the contract.
D. The whole reliability tests of the refrigeration and cooling plants shall take place during
the period between 30th of may and 15th of September, and for the heating plants
during the period between 1st December, and 15th of February meanwhile the following
tests and readings shall be made by the contractor in the presence of the engineer and
results shall be recorded and submitted in a tabulated form .
A. Air quantities shall be obtained by anemometer and velocimeter readings and all
necessary adjustments shall be made to obtain the specified quantities of air indicated
at each inlet and outlet.
B. Following readings shall be made, one on the suction side of the fan and one on the
discharge side of the fan:
1. Total C.F.M. supplied by each supply fan.
2. Total C.F.M. exhausted by each exhausted fan.
3. Total C.F.M. return air to each supply fan.
4. Total static pressure of each fan.
5. Motor speed, fan speed and input ampere reading for each fan.
6. Average velocity on intake side of each fan.
7. Noise level.
C. Cooling Coils:
1. For any conditioner the following tests shall be performed and submitted in
tabulated form to the engineer.
a. Average velocity over intake - side of each coil face
b. Entering air temperature (D.B. & W.B.)
c. Discharge air temperature (D.B. & W.B.)
D. Electric Motors
1. For each motor
a. Speed in R.P.M.
b. Amperes for each phase
c. Power input in K.W.
A. Adjust fans to deliver total indicated airflows within the maximum allowable fan speed
listed by fan manufacturer.
1. Measure fan static pressures to determine actual static pressure as follows:
a. Measure outlet static pressure as far downstream from the fan as
practicable and upstream from restrictions in ducts such as elbows and
transitions.
B. Measure static pressure across each component that makes up an air-handling unit,
rooftop unit, and other air-handling and -treating equipment.
1. Simulate dirty filter operation and record the point at which maintenance
personnel must change filters.
C. Measure static pressures entering and leaving other devices such as sound traps, heat
recovery equipment, and air washers, under final balanced conditions.
D. Compare design data with installed conditions to determine variations in design static
pressures versus actual static pressures. Compare actual system effect factors with
calculated system effect factors to identify where variations occur. Recommend
corrective action to align design and actual conditions.
E. Obtain approval from Architect for adjustment of fan speed higher or lower than
indicated speed. Make required adjustments to pulley sizes, motor sizes, and electrical
connections to accommodate fan-speed changes.
F. Do not make fan-speed adjustments that result in motor overload. Consult equipment
manufacturers about fan-speed safety factors. Modulate dampers and measure fan-
motor amperage to ensure that no overload will occur. Measure amperage in full
cooling, full heating, economizer, and any other operating modes to determine the
maximum required brake horsepower.
G. Adjust volume dampers for main duct, submain ducts, and major branch ducts to
indicated airflows within specified tolerances.
1. Measure static pressure at a point downstream from the balancing damper and
adjust volume dampers until the proper static pressure is achieved.
a. Where sufficient space in submain and branch ducts is unavailable for
Pitot-tube traverse measurements, measure airflow at terminal outlets and
inlets and calculate the total airflow for that zone.
2. Remeasure each submain and branch duct after all have been adjusted.
Continue to adjust submain and branch ducts to indicated airflows within
specified tolerances.
I. Adjust terminal outlets and inlets for each space to indicated airflows within specified
tolerances of indicated values. Make adjustments using volume dampers rather than
extractors and the dampers at air terminals.
1. Adjust each outlet in same room or space to within specified tolerances of
indicated quantities without generating noise levels above the limitations
prescribed by the Contract Documents.
2. Adjust patterns of adjustable outlets for proper distribution without drafts.
A. Motors, 1/2 HP and Larger: Test at final balanced conditions and record the following
data:
1. Manufacturer, model, and serial numbers.
2. Motor horsepower rating.
3. Motor rpm.
4. Efficiency rating.
5. Nameplate and measured voltage, each phase.
6. Nameplate and measured amperage, each phase.
7. Starter thermal-protection-element rating.
A. During TAB, report the need for adjustment in temperature regulation within the
automatic temperature-control system.
B. Measure indoor wet- and dry-bulb temperatures every other hour for a period of two
successive eight-hour days, in each separately controlled zone, to prove correctness of
final temperature settings. Measure when the building or zone is occupied.
C. Perform vibration measurements when other building and outdoor vibration sources are
at a minimum level and will not influence measurements of equipment being tested.
1. Turn off equipment in the building that might interfere with testing.
2. Clear the space of people.
D. Perform vibration measurements after air and water balancing and equipment testing is
complete.
H. Measure and record equipment vibration, bearing vibration, equipment base vibration,
and building structure vibration. Record velocity and displacement readings in the
horizontal, vertical, and axial planes.
1. Fans and HVAC Equipment with Fans:
a. Fan Bearing: Drive end and opposite end.
b. Motor Bearing: Drive end and opposite end.
c. Equipment Casing: Top and side.
d. Equipment Base: Top and side.
e. Building: Floor.
f. Ductwork: To and from equipment after flexible connections.
g. Piping: To and from equipment after flexible connections.
2. HVAC Equipment with Compressors:
a. Compressor Bearing: Drive end and opposite end.
b. Motor Bearing: Drive end and opposite end.
c. Equipment Casing: Top and side.
d. Equipment Base: Top and side.
e. Building: Floor.
f. Piping: To and from equipment after flexible connections.
I. For equipment with vibration isolation, take floor measurements with the vibration
isolation blocked solid to the floor and with the vibration isolation floating. Calculate and
report the differences.
B. Calibrate sound meters before each day of testing. Use a calibrator provided with the
sound meter complying with ANSI S1.40 and that has NIST certification.
C. Use a microphone that is suitable for the type of sound levels measured. For areas
where air velocities exceed 100 fpm (0.51 m/s), use a windscreen on the microphone.
D. Perform sound-level testing after air and water balancing and equipment testing are
complete.
F. Perform measurements when the space is not occupied and when the occupant noise
level from other spaces in the building and outside are at a minimum.
G. Clear the space of temporary sound sources so unrelated disturbances will not be
measured. Position testing personnel during measurements to achieve a direct line-of-
sight between the sound source and the sound-level meter.
H. Take sound measurements at a height approximately 48 inches (1200 mm) above the
floor and at least 36 inches (900 mm) from a wall, column, and other large surface
capable of altering the measurements.
I. Take sound measurements in dBA and in each of the 8 unweighted octave bands in the
frequency range of 63 to 8000 Hz.
J. Take sound measurements with the HVAC systems off to establish the background
sound levels and take sound measurements with the HVAC systems operating.
1. Calculate the difference between measurements. Apply a correction factor
depending on the difference and adjust measurements.
K. Perform sound testing at critical locations on Project for each of the space types; offices,
bedrooms, auditorium, classrooms, conference, spaces with NC 25 or lower,
mechanical rooms, etc. If testing multiple locations for each space type, select at least
one location that is near and at least one location that is remote from the predominant
sound source.
K.L. Refer to acoustic report for internal and external noise levels.
B. Before testing smoke-control systems, verify that construction is complete and verify the
integrity of each smoke-control zone boundary. Verify that windows and doors are
closed and that applicable safing, gasket, and sealants are installed. Report
deficiencies and postpone testing until after the reported deficiencies are corrected.
C. Measure and record wind speed and direction, outside-air temperature, and relative
humidity on each test day.
D. Measure, adjust, and record airflow of each smoke-control system with all fans that are
a part of the system operating as intended by the design.
E. Measure, adjust, and record the airflow of each fan. For ducted systems, measure the
fan airflow by duct Pitot-tube traverse.
F. After air balancing is complete, perform the following pressurization testing for each
smoke-control zone in the system:
1. Verify the boundaries of each smoke-control zone.
2. With the HVAC systems in their normal mode of operation and smoke control not
operating, measure and record the pressure difference across each smoke-
control zone. Make measurements after closing doors that separate the zones.
Make one measurement across each door. Clearly indicate the high and low
pressure side of each door.
3. With the system operating in the smoke-control mode and with each zone in the
smoke-control system activated, perform the following:
a. Measure and record the pressure difference across each door that
separates the smoke zone from adjacent zones. Make measurements
with doors that separate the smoke zone from the other zones closed.
Clearly indicate the high and low pressure side of the door. Doors that
have a tendency to open slightly due to the pressure difference should
have one pressure measurement made while held closed and another
measurement made with the door open.
b. Continue to activate each separate zoned smoke-control system and
make pressure difference measurements.
c. After testing a smoke zone's smoke-control system, deactivate the HVAC
systems involved and return them to their normal operating mode before
activating another zone's smoke-control system.
d. Verify that controls necessary to prevent excessive pressure differences
are functional.
G. Operational Tests:
1. Check the proper activation of each zoned smoke-control system in response to
all means of activation, both automatic and manual.
2. Check automatic activation in response to fire alarm signals received from the
building's fire alarm and detection system. Initiate a separate alarm for each
means of activation to ensure that the proper operation of the correct zoned
smoke-control system occurs.
3. Check and record the proper operation of fans, dampers, and related equipment
as outlined below for each separate zone of the smoke-control system.
a. Fire zone in which a smoke-control system automatically activates.
b. Type of signal that activates a smoke-control system, such as pull station,
sprinkler water flow, or smoke detector.
c. Smoke zone(s) where maximum mechanical exhaust to the outside is
implemented and no supply air is provided.
KEO/19-3262-0000 23 0593/14 Testing, Adjusting And Balancing For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
d. Positive pressure smoke-control zone(s) where maximum air supply is
implemented and no exhaust to the outside is provided.
e. Fan(s) "ON" as required to implement the smoke-control system.
Multiple- or variable-speed fans should be further noted as "MAX.
VOLUME" to verify that the intended control configuration is achieved.
f. Fan(s) "OFF" as required to implement the smoke-control system.
g. Damper(s) "OPEN" where maximum airflow must be achieved.
h. Damper(s) "CLOSED" where no airflow should take place.
i. Auxiliary functions to achieve the smoke-control system configuration
such as changes or override of normal operating pressure and
temperature-control set points.
j. If standby power is provided for the smoke-control system, test to verify
that the system functions while operating under both normal and standby
power.
J. Contractor shall be responsible for providing a completely operational, design & built,
smoke exhaust system approved by local civil defense authority without additional cost.
A. After air balancing is complete and with HVAC systems operating at indicated
conditions, perform indoor-air quality testing.
B. Observe and record the following conditions for each HVAC system:
1. The distance between the outside-air intake and the closest exhaust fan
discharge,, flue termination, or vent termination.
2. Specified filters are installed. Check for leakage around filters.
3. Cooling coil drain pans have a positive slope to drain.
4. Cooling coil condensate drain trap maintains an air seal.
5. Evidence of water damage.
6. Insulation in contact with the supply, return, and outside air is dry and clean.
C. Measure and record indoor conditions served by each HVAC system. Make
measurements at multiple locations served by the system if required to satisfy the
following:
1. Bed rooms
2. Living roomsand Diwania
3. Each and every appartments.
D. Measure and record the following indoor conditions for each location two times at two-
hour intervals, and in accordance with ASHRAE 113:
1. Temperature.
2. Relative humidity.
3. Air velocity.
4. Concentration of carbon dioxide (ppm).
5. Concentration of carbon monoxide (ppm).
6. Nitrogen oxides (ppm).
7. Formaldehyde (ppm).
KEO/19-3262-0000 23 0593/15 Testing, Adjusting And Balancing For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3.18 TEMPERATURE-CONTROL VERIFICATION
B. Check transmitter and controller locations and note conditions that would adversely
affect control functions.
C. Record controller settings and note variances between set points and actual
measurements.
D. Check the operation of limiting controllers (i.e., high- and low-temperature controllers).
E. Check free travel and proper operation of control devices such as damper and valve
operators.
F. Check the sequence of operation of control devices. Note air pressures and device
positions and correlate with airflow and water flow measurements. Note the speed of
response to input changes.
I. Check main control supply-air pressure and observe compressor and dryer operations.
J. Record voltages of power supply and controller output. Determine whether the system
operates on a grounded or nongrounded power supply.
K. Note operation of electric actuators using spring return for proper fail-safe operations.
3.19 TOLERANCES
A. Set HVAC system airflow and water flow rates within the following tolerances:
1. Supply, Return, and Exhaust Fans and Equipment with Fans: Plus 5 to plus 10
percent.
2. Air Outlets and Inlets: 0 to minus 10 percent.
3. Heating-Water Flow Rate: 0 to minus 10 percent.
4. Cooling-Water Flow Rate: 0 to minus 5 percent.
3.20 REPORTING
B. Include a certification sheet in front of binder signed and sealed by the certified testing
and balancing engineer.
1. Include a list of instruments used for procedures, along with proof of calibration.
C. Final Report Contents: In addition to certified field report data, include the following:
1. Fan curves.
2. Manufacturers' test data.
3. Field test reports prepared by system and equipment installers.
4. Other information relative to equipment performance, but do not include Shop
Drawings and Product Data.
D. General Report Data: In addition to form titles and entries, include the following data in
the final report, as applicable:
1. Title page.
2. Name and address of TAB firm.
3. Project name.
4. Project location.
5. Architect's name and address.
6. Engineer's name and address.
7. Contractor's name and address.
8. Report date.
9. Signature of TAB firm who certifies the report.
10. Table of Contents with the total number of pages defined for each section of the
report. Number each page in the report.
11. Summary of contents including the following:
a. Indicated versus final performance.
b. Notable characteristics of systems.
c. Description of system operation sequence if it varies from the Contract
Documents.
12. Nomenclature sheets for each item of equipment.
13. Data for terminal units, including manufacturer, type size, and fittings.
14. Notes to explain why certain final data in the body of reports varies from
indicated values.
15. Test conditions for fans and pump performance forms including the following:
a. Settings for outside-, return-, and exhaust-air dampers.
b. Conditions of filters.
c. Cooling coil, wet- and dry-bulb conditions.
d. Face and bypass damper settings at coils.
e. Fan drive settings including settings and percentage of maximum pitch
diameter.
f. Inlet vane settings for variable-air-volume systems.
g. Settings for supply-air, static-pressure controller.
h. Other system operating conditions that affect performance.
E. System Diagrams: Include schematic layouts of air and hydronic distribution systems.
Present each system with single-line diagram and include the following:
1. Quantities of outside, supply, return, and exhaust airflows.
KEO/19-3262-0000 23 0593/17 Testing, Adjusting And Balancing For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Water flow rates.
3. Duct, outlet, and inlet sizes.
4. Pipe and valve sizes and locations.
5. Terminal units.
6. Balancing stations.
7. Position of balancing devices.
F. Air-Handling Unit Test Reports: For air-handling units with coils, include the following:
1. Unit Data: Include the following:
a. Unit identification.
b. Location.
c. Make and type.
d. Model number and unit size.
e. Manufacturer's serial number.
f. Unit arrangement and class.
g. Discharge arrangement.
h. Sheave make, size in inches (mm), and bore.
i. Sheave dimensions, center-to-center, and amount of adjustments in
inches (mm).
j. Number of belts, make, and size.
k. Number of filters, type, and size.
2. Motor Data:
a. Make and frame type and size.
b. Horsepower and rpm.
c. Volts, phase, and hertz.
d. Full-load amperage and service factor.
e. Sheave make, size in inches (mm), and bore.
f. Sheave dimensions, center-to-center, and amount of adjustments in
inches (mm).
3. Test Data (Indicated and Actual Values):
a. Total airflow rate in cfm (L/s).
b. Total system static pressure in inches wg (Pa).
c. Fan rpm.
d. Discharge static pressure in inches wg (Pa).
e. Filter static-pressure differential in inches wg (Pa).
f. Preheat coil static-pressure differential in inches wg (Pa).
g. Cooling coil static-pressure differential in inches wg (Pa).
h. Heating coil static-pressure differential in inches wg (Pa).
i. Outside airflow in cfm (L/s).
j. Return airflow in cfm (L/s).
k. Outside-air damper position.
l. Return-air damper position.
m. Damper position.
H. Electric-Coil Test Reports: For electric furnaces, duct coils, and electric coils installed in
central-station air-handling units, include the following:
1. Unit Data:
a. System identification.
b. Location.
c. Coil identification.
d. Capacity in Btuh (kW).
e. Number of stages.
f. Connected volts, phase, and hertz.
g. Rated amperage.
h. Airflow rate in cfm (L/s).
i. Face area in sq. ft. (sq. m).
j. Minimum face velocity in fpm (m/s).
2. Test Data (Indicated and Actual Values):
a. Heat output in Btuh (kW).
b. Airflow rate in cfm (L/s).
c. Air velocity in fpm (m/s).
d. Entering-air temperature in deg F (deg C).
e. Leaving-air temperature in deg F (deg C).
f. Voltage at each connection.
g. Amperage for each phase.
I. Fan Test Reports: For supply, return, and exhaust fans, include the following:
1. Fan Data:
a. System identification.
b. Location.
c. Make and type.
d. Model number and size.
e. Manufacturer's serial number.
f. Arrangement and class.
g. Sheave make, size in inches (mm), and bore.
h. Sheave dimensions, center-to-center, and amount of adjustments in
inches (mm).
2. Motor Data:
a. Make and frame type and size.
b. Horsepower and rpm.
KEO/19-3262-0000 23 0593/19 Testing, Adjusting And Balancing For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
c. Volts, phase, and hertz.
d. Full-load amperage and service factor.
e. Sheave make, size in inches (mm), and bore.
f. Sheave dimensions, center-to-center, and amount of adjustments in
inches (mm).
g. Number of belts, make, and size.
3. Test Data (Indicated and Actual Values):
a. Total airflow rate in cfm (L/s).
b. Total system static pressure in inches wg (Pa).
c. Fan rpm.
d. Discharge static pressure in inches wg (Pa).
e. Suction static pressure in inches wg (Pa).
J. Round, Flat-Oval, and Rectangular Duct Traverse Reports: Include a diagram with a
grid representing the duct cross-section and record the following:
1. Report Data:
a. System and air-handling unit number.
b. Location and zone.
c. Traverse air temperature in deg F (deg C).
d. Duct static pressure in inches wg (Pa).
e. Duct size in inches (mm).
f. Duct area in sq. ft. (sq. m).
g. Indicated airflow rate in cfm (L/s).
h. Indicated velocity in fpm (m/s).
i. Actual airflow rate in cfm (L/s).
j. Actual average velocity in fpm (m/s).
k. Barometric pressure in psig (Pa).
K. Compressor and Condenser Reports: For refrigerant side of unitary systems, stand-
alone refrigerant compressors, air-cooled condensing units, or water-cooled condensing
units, include the following:
1. Unit Data:
a. Unit identification.
b. Location.
c. Unit make and model number.
d. Compressor make.
e. Compressor model and serial numbers.
f. Refrigerant weight in lb (kg).
g. Low ambient temperature cutoff in deg F (deg C).
2. Test Data (Indicated and Actual Values):
a. Inlet-duct static pressure in inches wg (Pa).
b. Outlet-duct static pressure in inches wg (Pa).
c. Entering-air, dry-bulb temperature in deg F (deg C).
d. Leaving-air, dry-bulb temperature in deg F (deg C).
e. Condenser entering-water temperature in deg F (deg C).
f. Condenser leaving-water temperature in deg F (deg C).
g. Condenser-water temperature differential in deg F (deg C).
h. Condenser entering-water pressure in feet of head or psig (kPa).
i. Condenser leaving-water pressure in feet of head or psig (kPa).
j. Condenser-water pressure differential in feet of head or psig (kPa).
k. Control settings.
l. Unloader set points.
m. Low-pressure-cutout set point in psig (kPa).
n. High-pressure-cutout set point in psig (kPa).
KEO/19-3262-0000 23 0593/20 Testing, Adjusting And Balancing For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
o. Suction pressure in psig (kPa).
p. Suction temperature in deg F (deg C).
q. Condenser refrigerant pressure in psig (kPa).
r. Condenser refrigerant temperature in deg F (deg C).
s. Oil pressure in psig (kPa).
t. Oil temperature in deg F (deg C).
u. Voltage at each connection.
v. Amperage for each phase.
w. Kilowatt input.
x. Crankcase heater kilowatt.
y. Number of fans.
z. Condenser fan rpm.
aa. Condenser fan airflow rate in cfm (L/s).
bb. Condenser fan motor make, frame size, rpm, and horsepower.
cc. Condenser fan motor voltage at each connection.
dd. Condenser fan motor amperage for each phase.
M. Sound Measurement Reports: Record sound measurements on octave band and dBA
test forms and on an NC or RC chart indicating the decibel level measured in each
frequency band for both "background" and "HVAC system operating" readings. Record
each tested location on a separate NC or RC chart. Record the following on the forms:
1. Date and time of test. Record each tested location on its own NC curve.
2. Sound meter manufacturer, model number, and serial number.
3. Space location within the building including floor level and room number.
4. Diagram or color photograph of the space showing the measurement location.
5. Time weighting of measurements, either fast or slow.
6. Description of the measured sound: steady, transient, or tonal.
7. Description of predominant sound source.
3.22 INSPECTIONS
A. Initial Inspection:
1. After testing and balancing are complete, operate each system and randomly
check measurements to verify that the system is operating according to the final
test and balance readings documented in the Final Report.
2. Randomly check the following for each system:
a. Measure airflow of at least 10 percent of air outlets.
b. Measure water flow of at least 5 percent of terminals.
c. Measure room temperature at each thermostat/temperature sensor.
Compare the reading to the set point.
d. Measure sound levels at two locations.
e. Measure space pressure of at least 10 percent of locations.
f. Verify that balancing devices are marked with final balance position.
g. Note deviations to the Contract Documents in the Final Report.
B. Final Inspection:
1. After initial inspection is complete request that a final inspection be made. TAB
firm test and balance engineer shall conduct the inspection in the presence of
[Owner] / engineer.
2. [Owner] / Engineer can randomly select measurements documented in the final
report to be rechecked. The rechecking shall be limited to either minimum 15
percent of the total measurements recorded, or the extent of measurements that
can be accomplished in a normal 2 business days.
3. If the rechecks yield measurements that differ from the measurements
documented in the final report by more than the tolerances allowed, the
measurements shall be noted as "FAILED."
4. If the number of "FAILED" measurements is greater than 10 percent of the total
measurements checked during the final inspection, the testing and balancing
shall be considered incomplete and shall be rejected.
5. TAB firm shall recheck all measurements and make adjustments. Revise the
final report and balancing device settings to include all changes and resubmit the
final report.
6. Request a second final inspection. If the second final inspection also fails,
Owner shall contract the services of another TAB firm to complete the testing and
balancing in accordance with the Contract Documents and deduct the cost of the
services from the final payment.
END OF SECTION
HVAC INSULATION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. The whole of the insulation work shall be carried out by an approved specialist insulation
Contractor. All allowances shall be included for arranging a specialist subcontract
accordingly and for informing the specialist Sub-contractor of all conditions relating to
the Contract and for coordinating his works with the remainder of the works.
B. All allowances shall be included for informing the specialist Sub-contractor of all details
of the building structure, program arrangements, and other relevant details at the time of
tender and for all necessary visits to site by the Sub-contractor or his workers.
D. In addition to complying with the relevant standards, all insulating material shall be free
from Asbestos and with low VOC.
E. Insulating materials shall be acceptable only if they are equal to or better than the
grades or classes of fire resistance as follows:
1. B.S. 476 Part 5 Class P, (Not easily ignitable.)
2. B.S. 476, Part 6, (Fire Propagation Index a maximum of 12.6.)
3. B.S. 476, Part 7, Class 1, (Surface spread of flame.)
4. B.S. 476 Part 9, (Production of emitted smoke shall not give more than 35%
obscuration of the light beam.)
F. All insulation finishes, and coverings shall be classified as Class 0 surface spread when
tested in accordance with B.S. 476, Part 6 & Part 7. (OR) insulation should have Flame
Spread Index (FSI) of less than 25 and Smoke Developed Index (SDI) less than 50
when tested in accordance with ASTM E84 and also complying to FM4924
G. All adhesives, mastics, coatings, sealers and primers shall be classified as Class 1
surface spread when tested in accordance with B.S. 476, part 7, and shall have low
VOC content. They shall not in any way attack the insulation or the surface to which the
insulation is being applied and shall be suitable for the working temperatures.
A. Section Includes:
1. Insulation Materials:
a. Cellular glass / Fibre Glass
b. Flexible elastomeric / Elastomeric rubber
c. Mineral fiber / Mineral wool
KEO/19-3262-0000 23 0700/1 Hvac Insulation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
d. Polystyrene.
e. Closed Cell.
f. Physically crosslinked Polyolefin insulation
g. Polyurethane
h. Styrofoam
2. Fire-rated insulation systems.
3. Insulating cements.
4. Adhesives.
5. Mastics.
6. Lagging adhesives.
7. Sealants.
8. Factory-applied jackets.
9. Field-applied jackets.
10. Tapes.
11. Securements.
12. Corner angles.
1.03 SUBMITTALS
A. Product Data: For each type of product indicated. Include thermal conductivity,
thickness, and jackets (both factory and field applied, if any).
B. Shop Drawings:
1. Detail application of protective shields, saddles, and inserts at hangers for each
type of insulation and hanger.
2. Detail attachment and covering of heat tracing inside insulation.
3. Detail insulation application at pipe expansion joints for each type of insulation.
4. Detail insulation application at elbows, fittings, flanges, valves, and specialties for
each type of insulation.
5. Detail removable insulation at piping specialties, equipment connections, and
access panels.
6. Detail application of field-applied jackets.
7. Detail application at linkages of control devices.
8. Detail field application for each equipment type.
B. Samples: For each type of insulation and jacket indicated. Identify each Sample,
describing product and intended use.
1. Sample Sizes:
a. Submit samples of all types of insulation for approval. Submit pipe
insulation samples 300 mm long x 25 mm inside x 125 mm outside
diameter, and flat samples 300 mm x 300 mm x 25 mm, minimum size.
b. Submit with samples, the full technical brochures.
c. Where the specification calls for additional treatments, such as wrapping
and waterproofing, submit also a completed sample of similar size.
d. All samples after approval are to be retained on site to be a reference for
future work.
D. Material Test Reports: From a qualified testing agency acceptable to authorities having
jurisdiction indicating, interpreting, and certifying test results for compliance of insulation
materials, sealers, attachments, cements, and jackets, with requirements indicated.
Include dates of tests and test methods employed.
A. Installer Qualifications: Skilled mechanics who have successfully completed three (3)
years minimum experience.
C. Mockups: Before installing insulation, build mockups for each type of insulation and
finish listed below to demonstrate quality of insulation application and finishes. Build
mockups in the location indicated or, if not indicated, as directed by Architect. Use
materials indicated for the completed Work.
D. Insulation material shall comply with the following British Standard (OR) equivalent
American Standards:
1. BS 476 (Part 4,5, 6, 7,9)
2. BS 874
3. BS2972
4. BS3958 (Part 4,5)
5. BS 5422
6. BS6676 (Part 1)
B. Protect insulation from moisture and dirt by inside storage and enclosure and polythene
wrapping in accordance with the manufacturer’s recommendation.
1.06 COORDINATION
A. Coordinate size and location of supports, hangers, and insulation shields specified in
Division 23 Section "Hangers and Supports for HVAC Piping and Equipment."
B. Coordinate clearance requirements with piping Installer for piping insulation application,
duct Installer for duct insulation application, and equipment Installer for equipment
insulation application. Before preparing piping and ductwork Shop Drawings, establish
and maintain clearance requirements for installation of insulation and field-applied
jackets and finishes and for space required for maintenance.
A. Submit maintenance data for each type of mechanical insulation. Include this data,
product data and certifications in the maintenance manual.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 GENERAL:
A. Thermal insulation shall be of an approved material with thermal conductivity not higher
than 0.042 w/m °C (0.29 Btu/hr. Ft. sq. °F Inch) measured at an average temperature of
35°C (95°F). The thermal insulation shall be non-corrosive to the metal, water repellent,
fire retardant, sustenance to vermin and easily cut and fitted to shape during application.
B. The insulation (fiberglass) shall be provided with an approved fire retardant vapor barrier
jacket to prevent moisture penetration to the insulation. Vapor barrier shall also be
applied to all joints and edges.
C. The insulation shall be fixed into the material surface by means of an approved
adhesive compound that has no corrosion effect on the metal and thoroughly applied to
the metal surface and insulation.
D. The insulation and finishing shall be carried out by skilled labor, and before thermal
insulation is applied, all metal surfaces shall be thoroughly cleaned and treated with an
approved corrosion inhibitor.
E. Insulation shall be applied in such a manner that air circulation within the insulation or
between the insulation and pipe, duct or equipment is completely prevented. Pipe
insulation shall fit snugly on the pipe and duct insulation shall be adhered to the duct
surface with special adhesive.
F. All insulation joints shall be firmly butted together, made absolutely tight and finished
smooth. Vapor barrier jackets shall have 50mm minimum overlaps. Longitudinal
overlaps on exposed works shall be made towards ceiling or wall.
G. All insulation shall be made continuous through sleeves, openings and pipe hangers.
The hanger shall be of size to fit around the insulation and jacketing.
I. Openings made in the insulation shall be provided with metal frames to protect the
edges of the insulation, and vapor sealed.
A. Insulating materials shall have thermal conductivity values not more than those listed as
follows:
---------------------------------------------------------------------------------------------------
MATERIAL TYPE THERMAL CONDUCTIVITY.
W/M/DEG.C
--------------------------------------------------------------------------------------------------
Mineral wool Sectional 0.04
Mineral wool Slabs 0.04
Fibre Glass All 0.034
Closed Cell All 0.035
(elastomeric foam)
Polyurethane Sectional 0.025
Styrofoam Rigid 0.026
Polyolefin All 0.032
---------------------------------------------------------------------------------------------------
All conductivity figures are rated at an average temperature of 23 deg C.or mean
temperature of 35 deg C.
B. The insulation thickness for pipes and ducts shall be verified by the specialist supplier/
manufacturer to confirm no condensation.
D. Products that come in contact with stainless steel shall have a leachable chloride
content of less than 50 ppm when tested according to ASTM C 871.
E. Insulation materials for use on austenitic stainless steel shall be qualified as acceptable
according to ASTM C 795.
F. Foam insulation materials shall not use CFC or HCFC blowing agents in the
manufacturing process.
H. Calcium Silicate:
1. Preformed Pipe Sections: Flat-, curved-, and grooved-block sections of
noncombustible, inorganic, hydrous calcium silicate with a non-asbestos fibrous
reinforcement. Comply with ASTM C 533, Type I.
2. Flat-, curved-, and grooved-block sections of noncombustible, inorganic, hydrous
calcium silicate with a non-asbestos fibrous reinforcement. Comply with ASTM C
533, Type I.
3. Prefabricated Fitting Covers: Comply with ASTM C 450 and ASTM C 585 for
dimensions used in preforming insulation to cover valves, elbows, tees, and
flanges.
KEO/19-3262-0000 23 0700/5 Hvac Insulation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
I. Cellular Glass: Inorganic, incombustible, foamed or cellulated glass with annealed,
rigid, hermetically sealed cells. Factory-applied jacket requirements are specified in
"Factory-Applied Jackets" Article.
1. Block Insulation: ASTM C 552, Type I.
2. Special-Shaped Insulation: ASTM C 552, Type III.
3. Board Insulation: ASTM C 552, Type IV.
4. Preformed Pipe Insulation without Jacket: Comply with ASTM C 552, Type II,
Class 1.
5. Preformed Pipe Insulation with Factory-Applied [ASJ] [ASJ-SSL]: Comply with
ASTM C 552, Type II, Class 2.
6. Factory fabricate shapes according to ASTM C 450 and ASTM C 585.
K. The closed cell elastomeric rubber insulation shall have following characteristics in
addition to clause 1.05 above:
1. Water vapour permeability - 0.09 ugm/Nh, BS 4370/2
(= 7000 to DIN 52615) (OR) < 0.05
Perm-inch
2. Density - 50 ±10 kg / m3 or 2.54Lb / ft3 to 3.75Lb /
ft3
3. Closed cell content - > 90%.
4. Corrosion risk assessment - Din 1988 / 7 Certified.
5. Noise reduction - Din 4109 up to 32 dB (A).
6. Thermal conductivity of 0.035 w/mk at 35°C mean temperature to BS 874 PART
2 – 86 (DIN 52613, 52612). or ASTM C518
The insulation thickness for pipes and ducts shall be verified by the specialist
supplier/ manufacturer to confirm no condensation.
L. Mineral Fiber Insulation: Mineral or glass fibers bonded with a thermosetting resin.
1. Mineral-Fiber Blanket Insulation: Comply with ASTM C 553, Type II and ASTM C
1290, Type III with factory-applied FSK jacket. Factory-applied jacket
requirements are specified in "Factory-Applied Jackets" Article.
3. Mineral-Fiber Board Insulation: Comply with ASTM C 612, Type IA or Type IB.
For duct and plenum applications, provide insulation with factory-applied FSK
jacket. For equipment applications, provide insulation with factory-applied FSK
jacket. Factory-applied jacket requirements are specified in "Factory-Applied
Jackets" Article.
M. Mineral-Fiber, Pipe and Tank Insulation: Semirigid board material with factory-applied
FSK jacket complying with ASTM C 1393, Type II or Type IIIA Category 2, or with
properties similar to ASTM C 612, Type IB. Nominal density is 2.5 lb/cu. ft. (40 kg/cu.
m) or more. Thermal conductivity (k-value) at 100 deg F (55 deg C) is 0.29 Btu x in./h x
sq. ft. x deg F (0.042 W/m x K) or less. Factory-applied jacket requirements are
specified in "Factory-Applied Jackets" Article.
O. Fire Classification: Fire classification ‘A1’ as per EN 13501; when tested as per BS EN
ISO 1182 & EN ISO 1176 for Base fibers. And Fire classification of B-s1-d0 as per EN
13501 for Faced products
P. Mineral Fiber Insulation to have moisture absorption: <1.00 % by volume when tested in
accordance with ASTM C1104
Q. Mineral Fiber Insulation to have Water vapor permeance: Water vapor barrier
Aluminium facing shall achieve water vapor permeance of not more than 0.02 perm
when tested as per ASTM E96
S. Insulation Products shall not contain asbestos, lead, mercury, or mercury compounds.
Glass fibers shall be EUCEB certified or equivalent.
T. Phenolic:
1. Preformed pipe insulation of rigid, expanded, closed-cell structure. Comply with
ASTM C 1126, Type III, Grade 1.
2. Block insulation of rigid, expanded, closed-cell structure. Comply with ASTM C
1126, Type II, Grade 1.
3. Factory fabricate shapes according to ASTM C 450 and ASTM C 585.
4. Factory-Applied Jacket: Requirements are specified in "Factory-Applied Jackets"
Article.
a. Preformed Pipe Insulation: ASJ.
b. Board for Duct and Plenum Applications: ASJ.
c. Board for Equipment Applications: ASJ.
U. Physically cross-linked polyolefin foam with factory applied reinforced aluminium foil.
Insulation shall have the following specifications:
1. Physically cross-linked, closed cell polyolefin foam with factory applied reinforced
aluminium foil and factory applied acrylic adhesive backing.
2. Exceed the minimum thickness to prevent condensation.
3. Density: 25 kg/m3 (foam core only).
4. Thermal Conductivity (ASTM C518): Maximum 0.032 W/m.°K at mean
temperature 23°C.
KEO/19-3262-0000 23 0700/7 Hvac Insulation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
5. Water absorption: <0.2 % v/v.
6. Water Vapour permeability (ASTM E96): Maximum 2.3 x 10-15 kg/Pa.s.m,
(µ>80,000).
7. Service Temperature Range: - 80°C ~ +80°C (adhesive backing).
8. Zero mould growth when tested to ASTM G21.
9. Fire Rating:
a. Class 0 to BS476 Parts 6 and 7.
b. Euroclass B-S2,d0 classification according to EN 13501Part 1.
c. Complies with NFPA 90A and B (ASTM E84 25/50 rating).
d. Complies with FM 4924 fire performance criteria and “FM Approved” by
FM Approvals certification body.
10. Smoke Density and Toxicity:
a. Complies with the requirements of International Maritime Organization
Resolution MSC 61(67) Part 2.
b. Dm<200 (ISO 5659 Part 2 gas analysis); combustion gases CO, HCl, HF,
NOx, HBr, HCN and SO2 to be within the maximum allowable
concentrations of International Maritime Organization Resolution MSC
61(67) Part 2.
B. Fire-Rated Blanket: High-temperature, flexible, blanket insulation with FSK jacket that is
tested and certified to provide a 2-hour fire rating by a NRTL acceptable to authority
having jurisdiction.
2.06 ADHESIVES
A. Materials shall be compatible with insulation materials, jackets, and substrates and for
bonding insulation to itself and to surfaces to be insulated, unless otherwise indicated.
D. Flexible Elastomeric and Polyolefin Adhesive: Comply with MIL-A-24179A, Type II,
Class I. Insulation Adhesive & tape: As per manufacturer’s recommendation
KEO/19-3262-0000 23 0700/8 Hvac Insulation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
E. Mineral-Fiber Adhesive: Comply with MIL-A-3316C, Class 2, Grade A.
G. ASJ Adhesive, and FSK and PVDC Jacket Adhesive: Comply with MIL-A-3316C,
Class 2, Grade A for bonding insulation jacket lap seams and joints.
I. Physically crosslinked adhesive: shall be suitable for indoor and outdoor use in high
humidity envinronments and shall meet Class 0 requirements when tested for fire
performance to BS 476 Part 6 and Part 7.
A. Adhesive shall be a flexible, fire resistive compound suitable for vapour sealing
insulated ducts and pipes.
B. Adhesive shall be suitable for indoor and outdoor use and in high humidity
environments.
C. Water vapour permeance shall not exceed 0.05 perms at 0.030-inch dry film thickness
when tested in compliance with ASTMF 1249.
D. When tested for surface burning characteristics in compliance with ASTM E84, flame
spread index shall be less than 25 and smoke developed index less than 50.
E. Adhesive shall be UL classified and shall meet or exceed the requirements of NFPA
90A and 90 B 25/50.
A. Fungicidal protective coatings shall be applied over external surfaces of chilled water
pipes and interior and exterior surfaces of ductwork.
B. Coating shall be a polyacrylate copolymer emulsion specially formulated for long term
fungicidal activity with no loss of activity on aging. It shall prevent the spread of molds
and odour causing bacteria on the applied surface.
2.09 MASTICS
A. Materials shall be compatible with insulation materials, jackets, and substrates; comply
with MIL-C-19565C, Type II.
B. Vapor-Barrier Mastic: Water based; suitable for indoor and outdoor use on below
ambient services.
1. Water-Vapor Permeance: ASTM E 96, Procedure B, 0.013 perm (0.009 metric
perm) at 43-mil (1.09-mm) dry film thickness.
2. Service Temperature Range: Minus 20 to plus 180 deg F (Minus 29 to plus 82
deg C).
KEO/19-3262-0000 23 0700/9 Hvac Insulation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Solids Content: ASTM D 1644, 59 percent by volume and 71 percent by weight.
4. Color: White.
C. Vapor-Barrier Mastic: Solvent based; suitable for indoor use on below ambient services.
1. Water-Vapor Permeance: ASTM F 1249, 0.05 perm (0.03 metric perm) at 35-mil
(0.9-mm) dry film thickness.
2. Service Temperature Range: 0 to 180 deg F (Minus 18 to plus 82 deg C).
3. Solids Content: ASTM D 1644, 44 percent by volume and 62 percent by weight.
4. Color: White.
D. Vapor-Barrier Mastic: Solvent based; suitable for outdoor use on below ambient
services.
1. Water-Vapor Permeance: ASTM F 1249, 0.05 perm (0.033 metric perm) at 30-
mil (0.8-mm) dry film thickness.
2. Service Temperature Range: Minus 50 to plus 220 deg F (Minus 46 to plus 104
deg C).
3. Solids Content: ASTM D 1644, 33 percent by volume and 46 percent by weight.
4. Color: White.
E. Breather Mastic: Water based; suitable for indoor and outdoor use on above ambient
services.
1. Water-Vapor Permeance: ASTM F 1249, 3 perms (2 metric perms) at 0.0625-
inch (1.6-mm) dry film thickness.
2. Service Temperature Range: Minus 20 to plus 200 deg F (Minus 29 to plus 93
deg C).
3. Solids Content: 63 percent by volume and 73 percent by weight.
4. Color: White.
2.10 SEALANTS
A. Joint Sealants:
1. Materials shall be compatible with insulation materials, jackets, and substrates.
2. Permanently flexible, elastomeric sealant.
3. Service Temperature Range: Minus 100 to plus 300 deg F (Minus 73 to plus 149
deg C).
4. Color: White or gray.
C. ASJ Flashing Sealants, and Vinyl, PVDC, and PVC Jacket Flashing Sealants:
1. Materials shall be compatible with insulation materials, jackets, and substrates.
2. Fire- and water-resistant, flexible, elastomeric sealant.
3. Service Temperature Range: Minus 40 to plus 250 deg F (Minus 40 to plus 121
deg C).
4. Color: White.
A. Woven Glass-Fiber Fabric for Pipe Insulation: Approximately 2 oz./sq. yd. (68 g/sq. m)
with a thread count of 10 strands by 10 strands/sq. inch (4 strands by 4 strands/sq. mm)
for covering pipe and pipe fittings.
B. Woven Glass-Fiber Fabric for Duct and Equipment Insulation: Approximately 6 oz./sq.
yd. (203 g/sq. m) with a thread count of 5 strands by 5 strands/sq. inch (2 strands by 2
strands/sq. mm) for covering equipment.
C. Woven Polyester Fabric: Approximately 1 oz./sq. yd. (34 g/sq. m) with a thread count of
10 strands by 10 strands/sq. inch (4 strands by 4 strands/sq. mm), in a Leno weave, for
duct, equipment, and pipe.
A. Woven Glass-Fiber Fabric: Comply with MIL-C-20079H, Type I, plain weave, and
presized a minimum of 8 oz./sq. yd. (271 g/sq. m).
A. Field-applied jackets shall comply with ASTM C 921, Type I, unless otherwise indicated.
D. Aluminum Jacket:
1. Aluminum Jacket: Comply with ASTM B 209 (ASTM B 209M), Alloy 3003, 3005,
3105 or 5005, Temper H-14.
a. Sheet and roll stock ready for shop or field sizing.
b. Finish and thickness are indicated in field-applied jacket schedules.
c. Moisture Barrier for Indoor Applications: 3-mil- (0.075-mm-) thick, heat-
bonded polyethylene and kraft paper.
d. Moisture Barrier for Outdoor Applications: 3-mil- (0.075-mm-) thick, heat-
bonded polyethylene and kraft paper.
e. Factory-Fabricated Fitting Covers:
a) Same material, finish, and thickness as jacket.
b) Preformed 2-piece or gore, 45- and 90-degree, short- and long-
radius elbows.
c) Tee covers.
d) Flange and union covers.
e) End caps.
f) Beveled collars.
g) Valve covers.
h) Field fabricate fitting covers only if factory-fabricated fitting covers
are not available.
2.15 TAPES
A. ASJ Tape: White vapor-retarder tape matching factory-applied jacket with acrylic
adhesive, complying with ASTM C 1136.
1. Width: 3 inches (75 mm).
2. Thickness: 11.5 mils (0.29 mm).
3. Adhesion: 90 ounces force/inch (1.0 N/mm) in width.
4. Elongation: 2 percent.
5. Tensile Strength: 40 lbf/inch (7.2 N/mm) in width.
6. ASJ Tape Disks and Squares: Precut disks or squares of ASJ tape.
B. FSK Tape: Foil-face, vapor-retarder tape matching factory-applied jacket with acrylic
adhesive; complying with ASTM C 1136.
1. Width: 3 inches (75 mm).
2. Thickness: 6.5 mils (0.16 mm).
3. Adhesion: 90 ounces force/inch (1.0 N/mm) in width.
4. Elongation: 2 percent.
5. Tensile Strength: 40 lbf/inch (7.2 N/mm) in width.
6. FSK Tape Disks and Squares: Precut disks or squares of FSK tape.
D. Aluminum-FSK Tapes: Aluminum FSK Tapes to be used with glass wool insulation
having FSK/FRK facing. Plain Aluminum Foil Tape should be used with FSK/FRK faced
glasswool insulation. The adhesive used shall be acrylic adhesive and thickness
excluding substrate shall not be less than 195 micron. Temperature resistance to be
from 30 deg F to 250 deg F and peel adhesion not to be lower than 83 oz/inch width.
Tensile strength not be lower than 22 lbs/inch width and rolling tack to be 7-7/8” or
better with a 7/16” ball. Tapes used should not be lower than 3 inch (72 mm) width.
Confirms BS 476 Part 6, Part 7 with fire propagation Index, I=1.5. Water Vapor
Transmission value 0.304 g/h/m2 as per ASTM E 96 standards. Average Tensile
Strength of 16.17 N/mm2 and Elongation 11.49% as per ASTM D 638:03 standards.
Global Warming Potential value 0 and Ozone Depletion Potential value 5.
E. Alum Glass Cloth Tape: Alum glass Cloth Tape to be used with Glass wool insulation
having a similar facing. Aluminum Foil Thickness to be minimum of 7 micron and Alum-
Glass Cloth backing to be a minimum of 120 micron. Peel Adhesion to be 25 N/25 mm
or better, and rolling tack to be 20 cm for a 11 mm ball or better. Service temperature to
be 20 deg C or better. Confirms BS 476 Part 6 and Part 7, Class O. Fungal Resistance
rating of 2 as per ASTM G 21-96. Average Tensile Strength of 47 kgf/25mm width as
per ASTM D 638 standards. Global Warming Potential value 0 and Ozone Depletion
Potential value 5.
2.16 SECUREMENTS
A. Bands:
1. Stainless Steel: ASTM A 167 or ASTM A 240/A 240M, Type 304 or Type 316;
0.015 inch (0.38 mm) thick, 3/4 inch (19 mm) wide with wing or closed seal.
2. Springs: Twin spring set constructed of stainless steel with ends flat and slotted
to accept metal bands. Spring size determined by manufacturer for application.
A. Stainless-Steel Corner Angles: 0.024 inch (0.61 mm) thick, minimum 1 by 1 inch (25 by
25 mm), stainless steel according to ASTM A 167 or ASTM A 240/A 240M, Type 304 or
316.
2.18 APPLICATION
A. Ductwork Insulation
1. Concealed supply, return, fresh air and extract air ducts- Fibre Glass
a. Unless otherwise indicated insulate all ductwork with 25 mm thick, 24
Kg/M3 density aluminium foil faced fibreglass duct insulation. Fasten the
insulation with adhesive on 200 to 250 mm centres. Butt all joints tightly
and seal all breaks and joints by adhering Aluminium foil vapour barrier
tape or sheet with a fire-retardant adhesive.
b. Insulate flexible connections and connections to diffusers with 25 mm
thick, 24 Kg/M3 density reinforced aluminium foil faced, flame resistant
KEO/19-3262-0000 23 0700/14 Hvac Insulation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
flexible fiberglass insulation. Overlap onto adjacent insulation and seal
with adhesive duct tape to give good closure.
c. Where ductwork is installed in ceiling voids and masonry shafts, which are
not used as return air plenums insulate with 50mm thick, 48 Kg/M3
density aluminium foil faced rigid fibreglass duct insulation.
d. Finish all duct insulation with a 20x20 (thread/inch) woven glass cloth
cover adhered between two coats of fire resistant fungicidal protective
lagging adhesive.
3. Concealed Supply, Return, Fresh Air and Extract air ducts- Closed Cell
Elastomeric rubber
a. Insulate all GI rectangular supply, return, fresh air and extract air ductwork
within air-conditioned areas with 13mm thick closed cell elastomeric foam
sheets with a density of 50±10kg/m3 .
b. The ductwork within non-air-conditioned areas shall be insulated with 25
mm thick, 50±10kg/m3 density closed cell elastomeric rubber insulation.
c. Insulate flexible connections and connections to diffusers with 25 mm
thick, 24 Kg/M3 density reinforced aluminum foil faced, flame resistant
flexible fiberglass insulation. Overlap onto adjacent insulation and seal
with adhesive duct tape to give good closure.
d. Extract duct from commercial kitchen hoods shall be insulated with 50mm
thick, 48 Kg/m3rockwool insulation with aluminium foil finish.
4. Exposed supply, return, fresh air and extract air ducts- Closed Cell Elastomeric
rubber
a. For ductwork exposed in non-air-conditioned areas, insulate using 25 mm
closed cell elastomeric foam sheets .
b. For ductwork exposed directly to sun light, insulate with 32 mm thick,
50±10kg/m3 closed cell elastomeric rubber insulation sheets withUV
resistant cladding.
KEO/19-3262-0000 23 0700/15 Hvac Insulation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
c. All ductwork in exposed areas (at roof, in car parking areas and
mechanical rooms) shall be clad with aluminium plain sheet of 0.7 mm
thickness. The cladding in mechanical rooms shall be up to 2.5 m from
finish floor level.
d. Where ducts penetrate the building shell, the duct shall be flashed and
waterproofed before any insulation is applied.
B. Concealed Supply, Return, Fresh Air and Extract air ducts - Physically crosslinked
polyolefin foam:
1. Building Internal Areas
Supply, return and extract air ducts for all ductwork shall be insulated with
physically cross-linked polyolefin foam with factory applied reinforced aluminium
foil. Insulation shall have the following specifications:
a. Physically cross-linked, closed cell polyolefin foam with factory applied
reinforced aluminium foil and factory applied acrylic adhesive backing.
b. Exceed the minimum thickness to prevent condensation.
c. Density: 25 kg/m3 (foam core only).
d. Thermal Conductivity (ASTM C518): Maximum 0.032 W/m.°K at mean
temperature 23°C.
e. Water absorption: <0.2 % v/v.
f. Water Vapour permeability (ASTM E96): Maximum 2.3 x 10-15 kg/Pa.s.m,
(µ>80,000).
g. Service Temperature Range: - 80°C ~ +80°C (adhesive backing).
h. Zero mould growth when tested to ASTM G21.
i. Fire Rating:
1) Class 0 to BS476 Parts 6 and 7.
2) Euroclass B-S2,d0 classification according to EN 13501Part 1.
3) Complies with NFPA 90A and B (ASTM E84 25/50 rating).
4) Complies with FM 4924 fire performance criteria and “FM Approved”
by FM Approvals certification body.
j. Smoke Density and Toxicity:
1) Complies with the requirements of International Maritime
Organization Resolution MSC 61(67) Part 2.
2) Dm<200 (ISO 5659 Part 2 gas analysis); combustion gases CO, HCl,
HF, NOx, HBr, HCN and SO2 to be within the maximum allowable
concentrations of International Maritime Organization Resolution
MSC 61(67) Part 2.
k. Schedule of thicknesses (must exceed minimum thickness to prevent
condensation):
1) Conditioned spaces: minimum 12mm.
2) Unconditioned spaces, shafts: minimum 15mm.
3) Plant rooms: minimum 20mm.
l. Refer to manufacturer’s instructions for installing insulation around
ductwork and fittings.
2. Exposed supply, return, fresh air and extract ducts- Physically Crosslinked
Polyolefin Foam.
3. Supply, return and extract air ducts for all ductwork shall be insulated with
physically cross-linked polyolefin foam with factory applied reinforced UV and
puncture resistant aluminium foil. Insulation shall have the following
specifications:
D. Chilled Water Pipework insulation- Closed Cell Elastomeric Rubber (If Applicable)
1. The following pipes shall be insulated with closed cell elastomeric rubber
insulation with following thickness:
a. Chilled Water Pipes in Conditioned Areas:
1) Insulate with closed cell elastomeric foam sheet. Thickness of
insulation shall be 19mm with 50±10kg/m3 density for pipes up to
50mm dia.
KEO/19-3262-0000 23 0700/17 Hvac Insulation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2) Pipes 65mm dia & bigger., thickness of insulation shall be 25mm.
b. Chilled Water pipes at Roof, Riser shafts and in Plant Room Areas:
1) Insulate with closed cell elastomeric foam rubber sheet. Thickness of
insulation shall be 32mm with 50±10 kg/m3 density for pipes up to
50mm.
2) Apply 0.7mm aluminium cladding plain sheet on top of insulation.
Roof insulation shall be UV resistant.
3) Pipes 65mm dia and above, thickness of insulation shall be 32mm.
4) Apply 0.7mm aluminium cladding plain sheet on top of insulation.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine substrates and conditions for compliance with requirements for installation and
other conditions affecting performance of insulation application.
1. Verify that systems and equipment to be insulated have been tested and are free
of defects.
2. Verify that surfaces to be insulated are clean and dry.
3. Proceed with installation only after unsatisfactory conditions have been
corrected.
3.02 PREPARATION
A. Surface Preparation: Clean and dry surfaces to receive insulation. Remove materials
that will adversely affect insulation application.
B. Mix insulating cements with clean potable water; if insulating cements are to be in
contact with stainless-steel surfaces, use demineralized water.
C. All material delivered to site shall be new and fully dried out and so maintained
throughout the progress of the works.
D. All insulating materials shall be stored in storage sheds, and in accordance with the
Manufacturer's recommendations.
E. In order to ensure that the insulation applied is in all respects in accordance with the
specification, sections shall, as required by the Consultant, be cut from the finished
insulation.
F. The Contractor is to allow in his price for the removal and replacement of two sections of
each type of insulation.
G. If, however, defects are revealed, further sections shall be cut out for inspection, and all
cutout sections shall be replaced at no cost to the Contract.
H. If further defects are revealed then the Consultant shall have the right, when in his
opinion it is necessary, to issue instructions for any part or the whole of the insulation to
be removed and replaced. The replacement with new insulation shall be to the
satisfaction of the Consultant and the cutting out and replacing shall be at no cost to the
Contract.
I. Particular attention shall be paid to the finished appearance of all thermal insulation
which must present a neat and symmetrical appearance running true in line with pipe
layouts, etc.
J. Any rough, irregular and badly finished surfaces shall be stripped down and re-insulated
to the Consultant's satisfaction.
KEO/19-3262-0000 23 0700/20 Hvac Insulation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
K. In certain cases, the type of insulation specified will require a painted finish, in addition
to identifying bands and any signs which are to be applied.
L. All systems are to have been tested and approved by the Consultant prior to installation
of insulation.
M. Manufacturer shall have production process control in accordance with ISO 9002 / UNI
EN 29002 or any other equivalent standard.
N. In case of heavy ducts and pipes wherein the supports are fixed directly on ducts / pipes
the supports shall be also insulated with a thermal break / barrier.
O. The insulation thickness for pipes and ducts shall be verified by the specialist supplier/
manufacturer to confirm no condensation and temperature loss.
A. Install insulation materials, accessories, and finishes with smooth, straight, and even
surfaces; free of voids throughout the length of equipment, ducts and fittings, and piping
including fittings, valves, and specialties.
B. Install insulation materials, forms, vapor barriers or retarders, jackets, and thicknesses
required for each item of equipment, duct system, and pipe system as specified in
insulation system schedules.
C. Install accessories compatible with insulation materials and suitable for the service.
Install accessories that do not corrode, soften, or otherwise attack insulation or jacket in
either wet or dry state.
D. Install insulation with longitudinal seams at top and bottom of horizontal runs.
E. Install multiple layers of insulation with longitudinal and end seams staggered.
F. Do not weld brackets, clips, or other attachment devices to piping, fittings, and
specialties.
H. Install insulation with tight longitudinal seams and end joints. Bond seams and joints
with adhesive recommended by insulation material manufacturer.
J. Where vapor barrier is indicated, seal joints, seams, and penetrations in insulation at
hangers, supports, anchors, and other projections with vapor-barrier mastic.
1. Install insulation continuously through hangers and around anchor attachments.
2. For insulation application where vapor barriers are indicated, extend insulation on
anchor legs from point of attachment to supported item to point of attachment to
structure. Taper and seal ends at attachment to structure with vapor-barrier
mastic.
3. Install insert materials and install insulation to tightly join the insert. Seal
insulation to insulation inserts with adhesive or sealing compound recommended
by insulation material manufacturer.
M. Cut insulation in a manner to avoid compressing insulation more than 75 percent of its
nominal thickness.
N. Finish installation with systems at operating conditions. Repair joint separations and
cracking due to thermal movement.
O. Repair damaged insulation facings by applying same facing material over damaged
areas. Extend patches at least 4 inches (100 mm) beyond damaged areas. Adhere,
staple, and seal patches similar to butt joints.
3.04 PENETRATIONS
D. Insulation Installation at Interior Wall and Partition Penetrations (That Are Not Fire
Rated): Install insulation continuously through walls and partitions.
A. Seal longitudinal seams and end joints with manufacturer's recommended adhesive to
eliminate openings in insulation that allow passage of air to surface being insulated.
H. Board Insulation Installation on Ducts and Plenums: Secure with adhesive and
insulation pins.
1. Apply adhesives according to manufacturer's recommended coverage rates per
unit area, for 100 percent coverage of duct and plenum surfaces.
A. Where glass-cloth jackets are indicated, install directly over bare insulation or insulation
with factory-applied jackets.
1. Draw jacket smooth and tight to surface with 2-inch (50-mm) overlap at seams
and joints.
2. Embed glass cloth between two 0.062-inch- (1.6-mm-) thick coats of lagging
adhesive.
3. Completely encapsulate insulation with coating, leaving no exposed insulation.
C. Where metal jackets are indicated, install with 2-inch (50-mm) overlap at longitudinal
seams and end joints. Overlap longitudinal seams arranged to shed water. Seal end
joints with weatherproof sealant recommended by insulation manufacturer. Secure
jacket with stainless-steel bands 12 inches (300 mm) o.c. and at end joints.
A. Where fire-rated insulation system is indicated, secure system to ducts and duct
hangers and supports to maintain a continuous fire rating.
B. Insulate duct access panels and doors to achieve same fire rating as duct.
3.11 FINISHES
A. Duct, Equipment, and Pipe Insulation with ASJ, Glass-Cloth, or Other Paintable Jacket
Material: Paint jacket with paint system identified below and as specified in Division 09
painting Sections.
1. Flat Acrylic Finish: Two finish coats over a primer that is compatible with jacket
material and finish coat paint. Add fungicidal agent to render fabric mildew proof.
a. Finish Coat Material: Interior, flat, latex-emulsion size.
C. Color: Final color as selected by Architect. Vary first and second coats to allow visual
inspection of the completed Work.
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
D. All insulation applications will be considered defective Work if sample inspection reveals
noncompliance with requirements.
B. The density of insulation shall be minimum 24 Kg/cubic meter for flexible blanket type
and 48 Kg/cubic meter for rigid type and thickness shall be as below:
1. Supply air duct in non-air conditioned areas - 50mm
2. Supply air duct in air conditioned areas - 25mm
3. Return air duct in non-air-conditioned areas - 25mm
4. Return air duct in air-conditioned areas - NIL
5. Fresh air duct in air-conditioned areas - 25mm
6. Supply and Return air ducts exposed to outside ambient temperature -75mm
C. Insulation shall be secured to duct work with 50x50mm G.I sheet metal strips of 22
gauge fixed to corners and tightened with wire at 150mm intervals. The strips may be
suitably grooved to take the wire fasteners. Transverse duct connections such as pocket
joints and flanges shall be additionally insulated with 100mm wide, 25mm thick
insulation and covered with 20mm wide, 8 oz. canvas equally overlapped on either side
and finally coated with 2 coats of approved paint.
D. All duct work exposed to outside, shall be covered with 0.7mm thick aluminium metal
jacketing (smooth finish) and shall be treated for waterproofing prior to cladding i.e. wrap
the insulation with 0.5mm thick polyethylene sheet and secure with adhesive. All duct
work insulation exposed to view shall be finished with 227 gm canvas finished with 2
coats of fire retardant and waterproof paint.
E. Internal duct lining for acoustic insulation where applicable shall not be less than 25mm
thick fiberglass mat faced, flexible blanket of fine fibers with securely bonded surface
mat coated with black neoprene or approved equal. Lining shall be applied with 100%
coverage of fire resistive approved adhesive compound and mechanical fastenings
according to the manufacturer's instructions. Acoustic lining shall be cleared 20cm on
each side of the duct heater where applicable. Duct lining density shall be 24 Kg/cubic
meter. Acoustic lining shall be treated against fungus growth. Increase duct sizes where
acoustic lining is used. Duct sizes shown on the drawings are inside clear dimensions.
C. Clean and dry ductwork prior to insulating. Butt insulation joints firmly together to ensure
complete and tight fit over surfaces to be covered.
E. Extend ductwork insulation without interruption through walls, floors and similar
ductwork penetrations, except where otherwise indicated.
B. Replace damaged insulation which cannot be repaired satisfactorily, including units with
vapour barrier damage and moisture saturated units.
END OF SECTION
COMMISSIONING OF HVAC
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes requirements for commissioning the HVAC system and its
subsystems and equipment.
1.02 DEFINITIONS
A. Architect: Includes Architect identified in the Contract for Construction between Owner
and Contractor, plus consultant/design professionals responsible for design of HVAC,
electrical, communications, controls for HVAC systems, and other related systems.
B. Test Checklists: Contractor shall develop test checklists for HVAC systems,
subsystems, and equipment, including interfaces and interlocks with other systems.
Contractor shall prepare separate checklists for each mode of operation and provide
space to indicate whether the mode under test responded as required. In addition to the
requirements specified in Division 01 Section "General Commissioning Requirements,"
checklists shall include, but not be limited to, the following:
1. Calibration of sensors and sensor function.
2. Testing conditions under which test was conducted, including (as applicable)
ambient conditions, set points, override conditions, and status and operating
conditions that impact the results of test.
3. Control sequences for HVAC systems.
4. Strength of control signal for each set point at specified conditions.
5. Responses to control signals at specified conditions.
6. Sequence of response(s) to control signals at specified conditions.
7. Electrical demand or power input at specified conditions.
8. Power quality and related measurements.
9. Expected performance of systems, and equipment at each step of test.
10. Narrative description of observed performance of systems, and equipment.
Notation to indicate whether the observed performance at each step meets the
expected results.
11. Interaction of auxiliary equipment.
12. Issues log.
1.05 SUBMITTALS
B. Testing Procedures: Contractor shall submit detailed testing plan, procedures, and
checklists for each series of tests. Submittals shall include samples of data reporting
sheets that will be part of the reports.
F. Test and Inspection Reports: Contractor shall compile and submit test and inspection
reports and certificates, and shall include them in systems manual and commissioning
report.
H. Certified TAB Reports: Contractor shall submit verified, certified TAB reports.
PART 3 - EXECUTION
A. TAB Preparation:
1. Contractor shall provide data required for "Pre-Field TAB Engineering Reports"
specified in Division 23 Section "Testing, Adjusting, and Balancing for HVAC."
a. Contractor shall use this data to certify that prestart and startup activities
have been completed for systems and equipment installation.
D. If deficiencies are identified during verification testing, Contractor shall take action to
remedy the deficiency. The Engineer shall review final tabulated checklists and data
sheets to determine if verification is complete and that system is operating according to
the Contract Documents.
E. The Engineer shall certify that TAB Work has been successfully completed.
B. Test systems and intersystem performance after test checklists for systems,
subsystems, and equipment have been approved.
E. Detailed Testing Procedures: The Engineer with HVAC Contractor shall prepare
detailed testing plans, procedures, and checklists for HVAC systems and equipment.
J. HVAC Distribution System Testing: Contractor shall prepare a testing plan to verify
performance of air, steam, and hydronic distribution systems; special exhaust; and other
distribution systems. Include HVAC terminal equipment and unitary equipment. Plan
shall include the following:
1. Sequence of testing and testing procedures for each item of equipment and
section of pipe to be tested, identified by identification marker. Markers shall be
keyed to Drawings showing the physical location of each item of equipment and
pipe test section. Drawings shall be formatted to allow each item of equipment
and section of piping to be physically located and identified when referred to in
the system testing plan.
2. Tracking checklist for managing and ensuring that all pipe sections have been
tested.
K. Vibration and Sound Tests: Contractor shall prepare testing plans to verify performance
of vibration isolation and seismic controls.
L. Deferred Testing:
1. If tests cannot be completed because of a deficiency outside the scope of the
HVAC system, the deficiency shall be documented and reported to Engineer.
Deficiencies shall be resolved and corrected by appropriate parties and test
rescheduled.
2. If the testing plan indicates specific seasonal testing, appropriate initial
performance tests shall be completed and documented and additional tests
scheduled.
M. Testing Reports:
KEO/19-3262-0000 23 0800/6 Commissioning Of Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Reports shall include measured data, data sheets, and a comprehensive
summary describing the operation of systems at the time of testing.
2. Include data sheets for each controller to verify proper operation of the control
system, the system it serves, the service it provides, and its location. For each
controller, provide space for recording its readout, the reading at the controller's
sensor(s), plus comments. Provide space for testing personnel to sign off on
each data sheet.
3. Prepare a preliminary test report. Deficiencies will be evaluated by Engineer to
determine corrective action. Deficiencies shall be corrected and test repeated.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes control equipment for HVAC systems and components, including
control components for terminal heating and cooling units not supplied with factory-wired
controls.
1.02 DISCRIPTION
A. Scope
1. The control system stated herein is intended to define functional requirements of
an acceptable system. Contractor shall, in his tender, highlight and allow for
alterations / modifications to the system or the system components; which in his
opinion are necessary to accomplish the purpose of maintaining predetermined
environmental conditions and other requirements at no additional cost.
Contractor shall not make any system modifications, including operating
parameters, control settings, etc. without prior written approval of the Client.
2. Supply and install a complete, state of the art, open architecture control system
based on true BACNET for the control, operation and monitoring of mechanical
and electrical systems in the Building. Provide all required services, materials
and equipment necessary for the successful operation of the entire control
system.
3. Provide the engineering, installation supervision and labor, calibration, software,
programming etc. necessary for a complete and fully operational control system.
4. Control system shall consist of, but not limited to the followings, sensors,
indicators, actuators, final control elements, interface equipment, other
apparatus, accessories, and software connected to distributed controllers
operating in multiuser, multitasking environment
5. Refer only to the applicable clauses as per the project requirement.
1.03 DEFINITIONS
B. I/O: Input/output.
C. Lon Works: A control network technology platform for designing and implementing
interoperable control devices and networks.
1.05 SUBMITTALS
A. Product Data: Include manufacturer’s technical literature for each control device.
Indicate dimensions, capacities, performance characteristics, electrical characteristics,
finishes for materials, and installation and startup instructions for each type of product
indicated.
1. DDC System Hardware: Bill of materials of equipment indicating quantity,
manufacturer, and model number. Include technical data for interface
equipment, control units, transducers/transmitters, sensors, actuators, valves,
relays/switches and control panels.
2. Controlled Systems: Instrumentation list with element name, type of device,
manufacturer, model number, and product data. Include written description of
sequence of operation including schematic diagram.
B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads,
required clearances, method of field assembly, components, and location and size of
each field connection.
1. Bill of materials of equipment indicating quantity, manufacturer, and model
number.
2. Schematic flow diagrams showing fans, pumps, coils, dampers, valves, and
control devices.
3. Wiring Diagrams: Power, signal, and control wiring.
4. Details of control panel faces, including controls, instruments, and labeling.
5. Written description of sequence of operation.
6. Schedule of dampers including size, leakage, and flow characteristics.
7. Schedule of valves including flow characteristics.
8. DDC System Hardware:
a. Wiring diagrams for control units with termination numbers.
b. Schematic diagrams and floor plans for field sensors and control
hardware.
c. Schematic diagrams for control, communication, and power wiring.
9. Control System Software: List of data (connected and calculated) point
addresses, output schedule, and operator notations.
10. Controlled Systems:
a. Schematic diagrams of each controlled system with control points labeled
and control elements graphically shown, with wiring.
b. Scaled drawings showing mounting, routing, and wiring of elements
including bases and special construction.
c. Written description of sequence of operation including schematic diagram.
d. Points list.
C. Data Communications Protocol Certificates: Certify that each proposed DDC system
component complies with ASHRAE 135.
D. Data Communications Protocol Certificates: Certify that each proposed DDC system
component complies with LonWorks.
E. Samples for Verification: For each color required, of each type of thermostat or sensor
cover.
KEO/19-3262-0000 23 0900/3 Instrumentation And Control For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
F. Software and Firmware Operational Documentation: Include the following:
1. Software operating and upgrade manuals.
2. Program Software Backup: On a magnetic media or compact disc, complete with
data files.
3. Device address list.
4. Printout of software application and graphic screens.
5. Software license required by and installed for DDC control systems.
G. Software Upgrade Kit: For Owner to use in modifying software to suit future systems
revisions or monitoring and control revisions.
I. Operation and Maintenance Data: For HVAC instrumentation and control system to
include in emergency, operation, and maintenance manuals. In addition to items
specified in Division 01 Section “Operation and Maintenance Data,” include the
following:
1. Interconnection wiring diagrams with identified and numbered system
components and devices.
2. Keyboard illustrations and step-by-step procedures indexed for each operator
function.
3. Inspection period, cleaning methods, cleaning materials recommended, and
calibration tolerances.
4. Calibration records and list of set points.
1.08 COORDINATION
A. Coordinate location for ease and maintenance of thermostats, humidistat and other
exposed control sensors with plans and room details before installation.
G. Coordinate equipment with Division 28 Section “Fire Detection and Alarm” to achieve
compatibility with equipment that interfaces with that system.
K. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03
Section “Cast-in-Place Concrete.”
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare Parts furnished under this clause shall not be used during the maintenance
period without the written permission of the owner (Contractor shall procure spare parts,
tools etc., fulfill his obligations to operate and maintain the system in the contract
period).
C. Spare parts as recommended by the manufacturer, including but not limited to the
following shall be furnished to the owner.
1. 1 no. Back-up Battery for Laptop Computer.
2. 1 no. DDC Controller of each type
3. 2 nos. of each type of thermostats and humidistat
4. 2 nos. of each type of two way and 3 way control valve motors
5. 2 nos. of each type of damper motors
6. 1 no. Kilowatt Transmitter
7. 3 nos. Pressure Transmitter
8. 3 nos. Temperature Sensors
9. 6 nos. Differential Pressure Switches
10. 10 nos. VAV Space Sensors
11. 2nos. Ordinary Space Sensors
12. 1no. Outdoor Air Temperature Sensor
2.01 MANUFACTURERS
D. I/O Interface: Hardwired inputs and outputs may tie into system through controllers.
Protect points so that shorting will cause no damage to controllers.
1. Binary Inputs: Allow monitoring of on-off signals without external power.
2. Pulse Accumulation Inputs: Accept up to 10 pulses per second.
3. Analog Inputs: Allow monitoring of low-voltage (0- to 10-V dc), current (4 to 20
mA), or resistance signals.
4. Binary Outputs: Provide on-off or pulsed low-voltage signal, selectable for
normally open or normally closed operation with three-position (on-off-auto)
override switches and status lights.
5. Analog Outputs: Provide modulating signal, either low voltage (0- to 10-V dc) or
current (4 to 20 mA) with status lights, two-position (auto-manual) switch, and
manually adjustable potentiometer.
6. Tri-State Outputs: Provide two coordinated binary outputs for control of three-
point, floating-type electronic actuators.
7. Universal I/Os: Provide software selectable binary or analog outputs.
F. Power Line Filtering: Internal or external transient voltage and surge suppression for
controllers with the following:
1. Minimum dielectric strength of 1000 V.
2. Maximum response time of 10 nanoseconds.
3. Minimum transverse-mode noise attenuation of 65 dB.
4. Minimum common-mode noise attenuation of 150 dB at 40 to 100 Hz.
A. Unitary Controllers shall be LONMARK / BACNET certified and shall support, but not be
limited to, the following types of systems to address specific applications described in
the “Automatic Control Sequence Section” portion of this specification.
B. Unitary controllers shall support the following library of control strategies to address the
requirements of the sequences described in the “Automatic Control Sequence Section”
portion of this specification
C. Unitary Controllers shall provide an auxiliary binary output to serve as the interface to an
associated lighting relay and a provision for occupancy sensing overrides, as required.
Based upon the status of either an occupancy sensing device, the Unitary Controller
shall provide a contact output to automatically turn on or off the lights and either an
KEO/19-3262-0000 23 0900/7 Instrumentation And Control For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
Economy or Comfort mode. This accommodates occupant requirements while reducing
electrically consumption. Economy/Comfort and Lighting overrides shall be served by
the same occupancy override input.
A. Step Controllers: 6- or 10-stage type, with heavy-duty switching rated to handle loads
and operated by electric motor.
A. Sensors shall be capable of sensing the range expected for the point at the specified
accuracy.
C. Thermistor(s) can be used only in situations where RTD is not available. In no case shall
computer inputs be derived from pneumatic sensors. In no case shall thermocouple be
used.
D. Wall mounted sensors and thermostats in public areas shall be protected from
unauthorized use with clear covers.
2.06 THERMOSTAT
A. Thermostat shall be microprocessor based, digital type and compatible with the control
system.
B. Thermostats shall work from software programmed memory and application control
program that is resident within the same enclosure as the input / output circuitry.
D. Thermostat shall be provided with remote setpoint adjustment and momentary override
button to circumvent day/night programming.
F. FCU thermostat shall be provided with 3 position slide switch for manual control of fan
speed apart from auto mode position and cool/heat change over.
G. Sensor for VAV Boxes and Small FCU’s: It shall be basic user function; LCD display,
set point adjustment and tenant override.
H. Sensor for AHU and large FCU’s: It shall be full user function; LCD display, network-
variable access and tenant override and shall conform to current industry standards.
J. Multiple network variables shall be accessible and editable from sensor / thermostat.
B. Dew-point sensor shall employ a non-reactive organic bobbin material to give precise
dew-point reading with accuracy of not more than 1.50F. The unit shall incorporate an
integral draft shield as part of the instrument for air velocities in excess of 50 fpm. Dew-
point sensor shall operate over a minimum range suitable to application. One additional
bobbin assembly shall be provided with each dew-point sensor.
C. Earth temperature sensors for greenhouse applications will have a range of -50 to
+90C, pre-wired and have enclosure to IP 65.
E. Outdoor temperature sensors (also combined with humidity sensors) will be suitable for
-40 to +60°C range and have an extra cover for protection and shielding from sun. Pre-
wired and terminal block versions shall be available.
A. Strap-on temperature sensors, for measuring the temperature in a water pipe, shall
have a range of -50 to +110C. Pre-wired and terminal block versions shall be available
and shall be mounted on the pipe with a clamp.
B. Water temperature sensors will be provided with a separable copper, Monel or stainless
steel well.
C. Immersion temperature sensors, for measuring temperature in water pipes, with the
following characteristics:
1. Range of -50 to +130C
2. Pre-wired and terminal block versions shall be available
3. Mounted in the pipe with a well
4. Lengths from 95 to 300 mm shall be available.
5. Material shall be copper, brass or stainless steel depending on type
D. Fast temperature sensors, for detecting fast temperature changes, with the following
characteristics:
1. Stainless steel construction suitable for direct mounting into the pipe
2. Pre-wired, available with a NTC 20 element.
3. Lengths of 75, 220 and 300 mm, adjustable to pipe diameters.
A. Non-organic resistance type with adjustable set point and single pole, double throw
mercury switch, suitable for 24 volts, 1 phase, 50 hertz supply; with the following
operating ranges:
1. Temperature: 2 C to 57C (25F to 135F)
2. Humidity: 5 % to 95 % RH (non-condensing)
A. Air duct temperature sensors will have a range of -40 to +120°C. Pre-wired and
terminal block versions shall be available to mount in and outside the duct. Duct
temperature sensors will be rigid stem or averaging type as specified in the sequence of
operation
B. DDC duct sensors shall match the requirements of the associated controller
incorporating an electrical signal to insure exact and proportional relationship between
the measured variable and the transmitted signal.
A. Water Flow Switches: UL listed, adjustable differential pressure or flow type as specified
in the sequence of operation or data point summary. Devices shall be pressure rated, as
required. Differential pressure switches shall have manifold with isolating valve for
servicing. Water flow switches shall open an electrical contact as the differential
pressure falls below a pre-adjusted pressure range setting.
B. Water Flow Sensors: Analogue, solid state, precision, industrial type with stainless steel
meter body, flow element and manifold with isolating valves for calibration and
maintenance. Maximum error shall not exceed 0.5% of range. Pressure rated as
required.
A. Air Flow and Static Pressure Sensors: Analogue, high accuracy type suitable for low
velocity pressures encountered, with 4 to 20 mA output and adjustments for zero and
range. These shall be selected for approximately 50 % over range and connected to the
airflow measuring station, using lines for testing and calibration, through isolating valves
A. Status Inputs for Fans: Differential-pressure switch with pilot-duty rating and with
adjustable range of 0- to 5-inch wg (0 to 1240 Pa).
B. Status Inputs for Pumps: Differential-pressure switch with pilot-duty rating and with
adjustable pressure-differential range of 8 to 60 psig (55 to 414 kPa), piped across
pump.
C. Status Inputs for Electric Motors: Comply with ISA 50.00.01, current-sensing fixed- or
split-core transformers with self-powered transmitter, adjustable and suitable for 175
percent of rated motor current.
D. Voltage Transmitter (100- to 600-V ac): Comply with ISA 50.00.01, single-loop, self-
powered transmitter, adjustable, with suitable range and 1 percent full-scale accuracy.
E. Power Monitor: 3-phase type with disconnect/shorting switch assembly, listed voltage
and current transformers, with pulse kilowatt hour output and 4- to 20-mA kW output,
with maximum 2 percent error at 1.0 power factor and 2.5 percent error at 0.5 power
factor.
G. Electronic Valve/Damper Position Indicator: Visual scale indicating percent of travel and
2- to 10-V dc, feedback signal.
B. Carbon Dioxide Sensor and Transmitter: Single detectors using solid-state infrared
sensors; suitable over a temperature range of 23 to 130 deg F (minus 5 to plus 55
deg C) and calibrated for 0 to 2 percent, with continuous or averaged reading, 4- to 20-
mA output;, for wall mounting.
C. Oxygen Sensor and Transmitter: Single detectors using solid-state zircon cell sensing;
suitable over a temperature range of minus 32 to plus 1100 deg F (0 to 593 deg C) and
calibrated for 0 to 5 percent, with continuous or averaged reading, 4- to 20-mA output;
for wall mounting.
A. The outside air monitoring station shall consist of outside air temperature and relative
humidity sensors at roof level. The sensors shall be shielded from direct sunlight, and
shall be located away from any exhaust air outlets or other sources of heat which could
A. Damper / valve motors shall be sized to operate with sufficient reserve power to provide
smooth modulating action or two position action as specified.
B. Permanent split capacitor or shaded poles type motors of 24V/1 phase/50 Hz power
supply with oil immersed and sealed gear trains. Motors installed in outdoor locations
and in outside air intakes shall be furnished with ‘O-Ring” gaskets designed to make
motors completely weatherproof. Internal heater shall be provided to permit normal
operation at - 40 C (- 40 F).
C. Spring returned motors sized for running torque rating of 1.73 Kg-M (150 inch-lb.) and
break away torque rating of 150 inch pounds shall be provided where indicated on
drawings or stipulated in operational sequence. Spring shall be integral spiral type in
enclosed housing designed for easy removal for service or adjustment of limit switches,
auxiliary switches or feedback potentiometer. Running time of spring for 90 degree
should not be more than 15 seconds in case of damper motor and 18 sec in case of
valve stroke.
D. Non-spring return motors sized for running torque rating of 1.73 Kg-M (150 inch-lb.) and
breakaway torque rating of 3.46 Kg-M (300 inch-lb.) shall be provided for:
1. Dampers larger than 2.32 M2 (25 ft2).
2. Valves larger than 65 mm (2½ inch).
E. Electrical scope shall be from the outgoing terminal of isolators provided by electrical
discipline. It shall also include zonal transformers to supply actuators.
A. Auxiliary switches and an external position indicator shall be available. Voltage feedback
valve position to the controller shall be included.
B. Actuators shall be suitable for 24 or 240 volts / 1 phase / 50 Hertz power supply and
selected to close valves against pump shut off head.
D. Run time shall be 100 second per 90° and provide 7 Nm torque.
E. Modulating Actuators shall provide flexibility by allowing 2-10 volts / 0-10 volts switching
and reversible operating direction and available in 5, 10 and 30 Nm torque ranges.
F. Small Rotary Floating Actuators shall be pre-wired and be available in 24 volts ac and
240 volts ac versions.
A. General: Designed to high quality specifications for reliable long time use, with the
following:
1. Equal percentage or modified parabolic flow characteristics, rangeability of 30:1
for fan-coils and VAV reheat coils and 50:1 for large coils.
2. Actual valve coefficient value (Cv) shall not deviate from the curve Cv and quoted
CV by more than 10 %.
3. Adjustable stroke limitation, pressure compensation and integrated flow control to
ensure optimisation in hydraulic systems with high differential pressures and high
temperatures.
4. Optimised range, leakage rate, temperature range and close-off pressure.
5. Indicators clearly marked to show fully open and closed positions.
B. Two-way Valves:
1. Type: Bronze with threaded ends (up to and including 50 mm ND) ductile / cast
iron with flanged ends (65 mm ND and above), globe pattern, two port valve with
the polished stainless steel trim and spring-loaded, self-adjusting, Teflon packing.
2. Control valves shall be selected for a maximum pressure drop of 34.5 kPa (5
psig) and shall be either equal or one size smaller than pipe size.
3. The seat shall be replaceable type of chrome nickel.
4. The spindle/stem shall be stainless steel.
5. Plug shall be made of stainless steel for sizes less than 100 mm, for 100 and
larger it shall be made of gun metal/bronze.
6. Valves to have either replaceable composition disk or stainless steel ball.
7. wo way valves shall be modulating type.
B. Frame: Fabricated from minimum 1.5 mm (16 gauge) galvanized steel sheets with holes
for enclosed duct mounting.
C. Blades: Fabricated from minimum 1.5 mm (16 gage) galvanized steel sheets, stiffened
as appropriate, with maximum blade width of 200 mm (8 inch). Blades shall be secured
to 12 mm (½ inch) diameter zinc-plated axles using zinc-plated hardware. Nylon thrust
bearings shall be provided for each blade. Blade linkage hardware shall be of zinc-
plated steel and brass.
E. Type for standard applications: Parallel or opposed blade design with optional closed-
cell neoprene edging.
F. Type for low-leakage applications: Parallel or opposed blade design with inflatable seal
blade edging or replaceable rubber seals, rated for leakage at less than 10 cfm/ft2 of
G. Outside air dampers shall have adjustable minimum settings so that ventilation can be
adjusted for each space or room.
A. Provide screwed or Flanged Water meters suitable for Cold or Hot water
B. For Cold Water Fluid Temperature range - 0º to 40ºC (ice free) and Maximum working
pressure, as required.
C. For Hot water Fluid temperature range - 0º to 90ºC (ice free) and Maximum operating
pressure, as required.
A. Provide KWH meters that gives open collector pulsed output signal or analog.
C. Use voltage and current transformers provided with motor starters to provide signals to
the CPU for KW monitoring
A. Electronic and fiber-optic cables for control wiring are specified in Division 27 Section
“Communications Horizontal Cabling.”
PART 3 - EXECUTION
3.01 EXAMINATION
A. When installation of the system is complete, Forward to the Engineer data relevant to
point index, functions, limits, sequences, interlocks, and other pertinent information for
the system.
C. Prior to on-line operation, calibrate equipment, verify transmission media operation and
perform in the presence of the Engineer a complete demonstration and readout of the
computer real-tile responsibilities of surveillance and command. This demonstration,
having satisfactorily met previously approved submittals, shall, with the Engineers
written acceptance, allow commissioning of the control system for on-line operation.
G. Provide a cross-check of each control point within the system by making a comparison
between the control command and the field-controlled device.
H. Verify that all systems are operable from local controls in the specified failure mode
upon panel failure or loss of power.
I. Humidity sensors to be checked for accuracy using a wet / dry bulb thermometer.
L. The control contractor shall revisit the site after handover to check and adjust the
parameters for the control to optimize settings.
3.02 COORDINATION
A. Contractor shall ensure that the work under this section shall not interfere with those of
other trades. Where work is installed in close proximity to or will interfere with work of
other trades, the Contractor shall assist in working out satisfactory space arrangements.
Only those, which cannot be solved without changes to structure or those, which
involves major changes to system design shall be referred to the Engineer.
3.03 INSTALLATION
C. Verify location of thermostats, humidistats, and other exposed control sensors with
Drawings and room details before installation. Install devices [60 inches (1530 mm)]
above the floor, or as directed by engineer.
1. Install averaging elements in ducts and plenums in crossing or zigzag pattern.
J. Forward to the Engineer submittal data relevant to valve schedules damper schedules
and other pertinent equipment information requiring approval prior to field installation.
Upon receipt of approval, proceed with installation, set up, calibrating and checking out
the various control and monitoring system.
K. DDC shall be protected from interference by the operation of hand held radio
transmitters, radio pagers, etc., within 1 metre of the equipment.
L. Any modifications made to the system shall be incorporated into the operations and
maintenance manuals, and other documentation affected.
A. Install raceways, boxes, and cabinets according to Division 26 Section “Raceway and
Boxes for Electrical Systems.”
B. Install building wire and cable according to Division 26 Section “Low-Voltage Electrical
Power Conductors and Cables.”
F. Conduits and wiring shall be properly supported and run in a neat and workmanlike
manner; run parallel to or at right angles to building structure when exposed and in
equipment rooms.
G. Wiring shall be installed in such a way that minimises coupling of electromagnetic and
electrostatic interference on low voltage signals and data wiring, in order to avoid
KEO/19-3262-0000 23 0900/18 Instrumentation And Control For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
disturbance of DDC equipment operation. This shall preferably be achieved by, but not
limited to:
1. Physical separation of greater than 50 mm between the power supply cables and
the signal and data cables
2. Use of braided screen mains cable, dressed close to metalwork, where mixed
wiring is unavoidable (Tenderers shall clearly specify the methods by which he
intends to eliminate any such interference with his signal and data transmission).
B. Perform the following field tests and inspections and prepare test reports:
1. Operational Test: After electrical circuitry has been energized, start units to
confirm proper unit operation. Remove and replace malfunctioning units and
retest.
2. Test and adjust controls and safeties.
3. Leak Test: After installation, charge system and test for leaks. Repair leaks and
retest until no leaks exist.
4. Pressure test control air piping at 30 psig (207 kPa) or 1.5 times the operating
pressure for 24 hours, with maximum 5-psig (35-kPa) loss.
5. Pressure test high-pressure control air piping at 150 psig (1034 kPa) and low-
pressure control air piping at 30 psig (207 kPa) for 2 hours, with maximum 1-psig
(7-kPa) loss.
6. Test calibration of [electronic] controllers by disconnecting input sensors and
stimulating operation with compatible signal generator.
7. Test each point through its full operating range to verify that safety and operating
control set points are as required.
8. Test each control loop to verify stable mode of operation and compliance with
sequence of operation. Adjust PID actions.
9. Test each system for compliance with sequence of operation.
10. Test software and hardware interlocks.
C. DDC Verification:
1. Verify that instruments are installed before calibration, testing, and loop or leak
checks.
2. Check instruments for proper location and accessibility.
3. Check instrument installation for direction of flow, elevation, orientation, insertion
depth, and other applicable considerations.
4. Check instrument tubing for proper fittings, slope, material, and support.
5. Check installation of air supply for each instrument.
6. Check flow instruments. Inspect tag number and line and bore size, and verify
that inlet side is identified and that meters are installed correctly.
7. Check pressure instruments, piping slope, installation of valve manifold, and self-
contained pressure regulators.
8. Check temperature instruments and material and length of sensing elements.
9. Check control valves. Verify that they are in correct direction.
10. Check air-operated dampers. Verify that pressure gages are provided and that
proper blade alignment, either parallel or opposed, has been provided.
11. Check DDC system as follows:
3.06 ADJUSTING
3.07 DEMONSTRATION
A. Demonstration of the control system to the End User for acceptance shall be carried out
after a full system test has been passed and one weeks notice has been given to the
commissioning Engineer.
1. Field Equipment Demonstration shall include but not limited to the followings:
a. Automatic control operation shall be verified by introducing an error into
the system and observing the proper corrective system response.
b. Selected time and set point schedules shall be verified by changing the
schedule and observing the correct response on the controlled outputs.
c. An output channel will be commanded (on/off, stop/start, adjust, etc.) and
operation verified.
d. An analog input channel will be verified for proper operation.
e. A digital input channel will be verified by changing the state of the field
device and observing the appropriate change of displayed value.
f. Typical occupancy control device function shall be demonstrated.
g. If a point should fail testing, perform necessary repair action and retest
failed point and all interlocked points.
2. The specialist control Contractor shall commission and handover the system to
the client or client’s representative on a point-to-point basis.
3. Services of competent personnel, having at least five (5) years experience in the
field and who have gained an intimate understanding of the project throughout its
design stages, shall be provided by the Contractor to commission the control
system.
4. Contractor shall prepare and submit a program of commissioning; clearly stating
other disciplines involved and services required for each activity.
5. Where work is being carried out in an occupied building the management of the
building shall be kept fully informed regarding the nature of the testing and
commissioning. Steps shall be taken to ensure that any possible hazards or
inconvenience that may arise due to the testing and commissioning shall be
minimized.
6. System Handover shall include but not limited to the followings:
a. Any issues required corrective actions to be documented and agreed date
determined for clearance.
b. All access levels and passwords recorded and backed up.
c. Two Copies of all system and database files supplied on CD with
appropriate identification.
d. Two bound hardcopies of Maintenance manuals including datasheets for
each item of equipment.
e. Two bound hardcopies of Operations manuals including safety checks
and start-up and close down procedures.
f. Six (6) hardcopies of control system drawings matching the installed
networks, equipment and peripheral connections, plus two soft copies of
CAD drawings on separate CDs.
g. Two bound hardcopies of the Flow charts of the control software
programs utilized in the Temperature Control System.
h. Two bound hardcopies of the Control Programs used in each DDC
controller.
KEO/19-3262-0000 23 0900/21 Instrumentation And Control For Hvac
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
i. Consumables, printer ribbons, printer paper at agreed levels.
j. All keys necessary for access to panels and equipment.
k. Training of engineers and operators to be checked complete or program
for completion agreed.
l. Operating and maintenance cautions and instructions.
m. Recommended spare parts list with contact details for suppliers.
3.08 TRAINING
B. The control Contractor shall provide detailed on-site and off-site operation and
programming training to selected client staff. Training will be carried out separately for
both engineering and operator staff. Factory trained control engineers and technicians
shall provide training sessions for the client’s personnel. Training shall include but not
limited to the followings:
1. Explanation of drawings, operations and maintenance manuals
2. Overview of HVAC system
3. Walk-through of the job to locate control components.
4. Use of Occupancy Controls.
5. Use of Keypad/Display devices with customised menus.
6. Use of Overrides and Passwords.
7. Use of Datalogs, Time Schedules and Alarms handling.
8. Communication Controller, DDC Controller, ASC operation/function.
9. Operator control functions including graphic generation and field panel
programming.
10. Explanation of adjustment, tuning, calibration and replacement procedures.
11. Since the Client may require personnel to have more comprehensive
understanding of the hardware and software, additional training must be
available from the control contractor. If such training is required by the Client, it
will be contracted at a later date.
3.09 MAINTANENCE
A. The specialist contractor shall maintain the system and its operation for a period as
stipulate in the contract documents
B. The contractor shall cover preventive maintenance, breakdown call out, replacement of
consumable items and a list of recommended spares for holding by the client.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes control sequences for HVAC systems, subsystems, and
equipment.
1.03 DEFINITIONS
1.04 GENERAL
A. The HVAC system controls (air temperature, volume, static pressure, etc.) shall be the
responsibility of the HVAC System Contractor. HVAC Contractor shall utilize the
services of a leading BAS control specialist.
B. The HVAC Contractor shall obtain all automatic temperature control equipment and
provide full and comprehensive automatic temperature control schematics and
interconnecting wiring diagrams of all specified system. BAS Contractor shall install the
necessary automatic temperature control equipment in ducts or pipes, as provided by
control specialist.
D. The HVAC Contractor shall include for the installation of all items of control equipment
such as immersion wells, control valves, damper motors, thermostats or detectors in
pipe line walls or ducts etc.
E. The HVAC Contractor shall also include for the installation of low voltage power
(including transformer, wiring and all accessories) wiring to all HVAC equipment
wherever necessary.
F. HVAC contractor shall coordinate with fire alarm contractor so all necessary controls,
control wiring for each HVAC equipment are provided up to fire alarm panel.
A. Provide necessary interlocks between HVAC equipment that either run together or run
when other stops.
B. The set points for temperature, humidity, pressure, flow, power consumption. pH level
run time etc. shall be adjustable.
H. Provide differential pressure sensing devices for all fans. This point shall be used as
start / stop feedback for points specified as status on the point list.
I. Water flow for each pump shall be indicated by means of a differential pressure switch,
which opens an electrical contact as the differential pressure falls below a pre-adjusted
pressure range setting.
J. Use auxiliary contacts provided with motor controls of fans and pumps for start / stop
feedback
K. Provide three-mode relays at the motor control stations for hand/off/auto control
B. If the equipment is not proven after the delay time, an alarm shall be raised, and the
equipment shall be switched off.
A. Outside air monitoring station shall consist of outside air temperature and relative
humidity sensors at roof level. Sensors shall be shielded from direct sunlight and shall
be located away from any exhaust air outlets or other sources which could affect the
accuracy of the reading. Temperature and relative humidity values shall be transmitted
globally to all systems requiring these values
A. Plant Configuration
1. The Energy Recovery Unit shall comprise of an AHU supply air fan and extract
fan provided with variable speed motor, DX cooling coil / CHW cooling coil with
modulating valve, Enthalpy Wheel, 2 banks of filters (panel & bag filters) and 1
bank of filter on exhaust side, temperature & RH sensors and set of modulating
dampers.
G. Motorized Damper
1. The FAHU shall be provided with on/off motorized damper on the intake air duct
which will be normally open in case of unit operation and closes in case of unit is
off.
2. The BAS shall control the operation of the damper and monitor the status of the
damper.
AHU Unit shall comprise of Supply fan, CHW / DX cooling coil with modulating
Control Valve & Filter banks (panel and bag filters as applicable) and set of dampers.
A. Temperature Control
1. The BAS shall take over the operations of the AHUs when the Hand-Off-Auto
switch is in the ‘AUTO” position. The AHUs shall be switched on automatically as
per the dictates of the time channels defined in the DDC controllers. Under
D. Safety Controls:
1. Smoke detectors approved for duct installation shall be installed by fire alarm
contractor and hard wired to automatically shut down fans. For this purpose,
smoke detectors shall be provided as follows:
a. At a suitable location in the return air stream prior to mixing with outdoor
air, and
b. At a suitable location in the main supply duct, if required.
E. Smoke detectors shall be provided with auxiliary contact and connected to fire alarm
interface, for remote indication. Smoke detector shall comply with NFPA/90A
F. Return / supply / thermostat / air sensor will modulate cooling coil control valve to
maintain the desired discharge air temperature.
1. Sensors located in return air duct will be used for constant air volume AHUs
2. Sensors located in supply air duct will be used for variable air volume AHUs
G. The AHU supply fan shall start based on a predetermined time schedule in the DDC
controller or on load requirement. Controls shall be energized when flow is proven. The
supply fan shall run continuously with outside air damper open to an adjustable
minimum position.
H. AHU condition will be monitored by differential pressure switch (installed across the fan)
and an alarm signal will be generated in the event of a discrepancy between the start-
stop command and the corresponding differential pressure switch.
I. Variable frequency drives shall operate based the static pressure sensor located on the
¾ of the longest supply duct run upstream on the AHU. The set point shall be
established during testing adjusting and balancing (TAB).
K. Unoccupied Mode: The AHU supply fan shall be switched OFF and the controls shall be
de-energized. However, if the space temperature exceeds 30 deg C. in summer, the
DDC controller shall revert the AHU to the night cycle mode and cycle the fan with full
cooling.
L. The AHU filters shall be monitored by differential Pressure Switch and alarmed when
dirty.
M. Electrical and control panels shall be installed inside AHU Room (or nearby AHU).
N. AHUs (and fresh air supply and exhausted fans) will be scheduled to a holiday program.
O. If the electric heater battery was operating immediately prior to a shutdown command,
then:
1. Supply and / or return fans will run-on for a period of 15 minutes in order to
dissipate residual heat from the electric heater battery, after which time the fans
shall be stopped.
2. Air flow and thermal cut-out interlocks shall be provided for heater.
Q. Fixed time commands for AHU: On receiving stop command from the fixed time
program:
1. Supply fan and extract fan shall stop
2. Fresh air and extract dampers shall close
3. Heater battery steps shall be switched off
4. Cooler battery control valve shall be driven closed to the coil
R. Alarm on Failure: In the event of a supply or extract fan failure, as detected by its
differential pressure switch and / or its starter contractor auxiliaries, the failed fan shall
be shut down and an alarm shall be raised.
S. AHU shall not re-enter the normal automatic control sequence until the fault on the fan
has been cleared.
T. In AHU, a velocity controller installed in the fresh air intake guarantee minimum fresh air
as total flow is reduced by ensuring that dampers are open sufficiently to provide the
minimum flow required.
A. FCU controllers for public areas and service / utility rooms shall be connected to the
BASworkstation for monitoring and control of FCU’s via Return air sensor behind the
FCU.
B. A low voltage digital room thermostat with built – in 3 – speed switch and capable of
communicating with DDC will command the control valve to maintain design
temperature in space.
E. Thermostat shall be suitable for wall mounting for high level and concealed type units.
For floor-mounted units the switch shall be integral part of the unit.
G. Space / return air temperature sensors shall provide out of limits alarms when the
sensed temperature rises 2.0 C (adjustable) above or below set-point. Alarms shall be
inhibited when the FCU is shutdown or for a timed period of 30 minutes (adjustable)
after plant start up.
H. Space thermostat / temperature sensor shall be located adjacent to the room light
switch or as agreed with the Engineer.
A. Chilled water pumps shall be switched on locally or remotely through the BMS.
B. The pump set will operate as duty, and 1 standby depending on the VFD will modulate
speed to keep a constant loop pressure. The standby pump shall operate as a duty
pump according to a schedule, and in case of other pump failure.
C. The chilled water treatment automatic dosing system shall be provided with all the
necessary electrical wiring and controls for the complete package efficient and
satisfactory operation.
D. The pumps are driven by a variable frequency drive (VFD). VFD driven will be working
based on the reading from the differential pressure sensor (dp) placed between the
header supply and return lines at the hydraulically most remote location in the system.
the pumps are operated in a sequence so that when one pump is running at full speed
another pump is turned on and its speed is increased so that the pressure difference set
point is achieved. The number and the running speed of the pumps are determined by
the cooling load of the building at that particular time. The remote dp set point will be
maintained between maximum and minimum pressures. the maximum pressure limit is
the pressure required to provide full flow to all chilled water control valves
simultaneously (per tab). The minimum pressure limit is the pressure correlating to the
lowest speed the pump motor is allowed to be operated as per motor specification and
tab.
E. The PICV shall be controlled by the building side chilled water temperature and the
return chilled water temperature of the primary circuit. The electrically activated control
valve of PICV will respond to control signal from the controller.
A. Intelligent controller shall be providing for all VRF systems. Each group / VRF system
shall be connected to one main controller. Each system controller shall monitor and
control their system, (indoor units & outdoor units). The required control shall be as per
manufacturer recommendation to ensure efficient and optimum operation. All required
and necessary wiring, controls, interconnection instrument, each VRF system controller
A. A low voltage digital room thermostat capable of communicating with DDC will maintain
design temperature in space.
C. Thermostat shall be suitable for wall mounting for high level and concealed type units.
For floor-mounted units the switch shall be integral part of the unit.
D. Differential pressure switches will monitor and report fan status to DDC.
E. Space thermostat / temperature sensor shall be located adjacent to the room light
switch or as agreed with the Engineer.
F. The BMS (if applicable) shall monitor the DX split units for the unit panel healthy
monitoring.
A. The smoke fans and make up air fans shall be directly controlled by the fire alarm panel.
The fans shall be directly interlocked with the fire alarm panel. There shall be a
motorized damper on the exhaust duct connecting the smoke exhaust fans and on the
makeup air duct to each floor.
B. The fans shall operate directly on receipt of fire alarm signal. However, the fans run
status is monitored on BMS through a digital input signal to DDC from differential
pressure air flow switch mounted across each fan.
C. The smoke/ makeup air fans shall have a dedicated duct risers and branch ducts
connected to each floor. The branch ducts shall have motorized on/off dampers. The
dampers shall open at the fire floor based on a fire alarm signal. Motorized dampers on
all other floors without fire shall remain closed.
D. After the fire event the smoke exhaust fans shall be operated to purge the smoke from
affected levels.
E. ALARMS:
1. Alarms will be generated on the BMS in case of following conditions:
a. Fan trip
b. Fire Alarm
B. ALARMS:
1. Alarms shall be generated on the BMS in case of following conditions:
a. Staircase/Lift differential pressure exceeds pre-defined high limit of 65 Pa
(adjustable)
A. In case of fire, the fire alarm panel shall command the following:
1. Shut-off AHU / FCU and normally working fans in the smoke zone
2. Energize lift well and stairwell pressurization fans.
3. Close or open motorized dampers in accordance to smoke control scheme, and
upon proof of the intake dampers open, the associated fans shall operate.
4. Open exterior doors by the use of door actuators to allow fresh air in.
5. Energize smoke ventilation fans shall be working during fire mode to provide safe
egress route.
B. All necessary wiring, piping, conduits, etc., shall be installed and brought to the nearest
fire alarm panel.
C. The signals from the smoke system fans shall be made available at the building
automation system. Make all necessary control wiring connection to smoke control
panel.
D. Smoke ventilation system and air conditioning fans shall be connected to and operable
from the fire alarm control panel. As well as, provision shall be made, in the BAS or
otherwise, for manually stopping HVAC system in the event of fire.
E. Stair pressurization fans shall be with VFD connected to pressure sensor at mid-point in
stairwell to give full speed operation between pressure of 50 Pascal (minimum
emergency operation level) to 120 Pascal. When the pressure in the stairwell reaches
more than 50 Pascal the fan speed will reduced accordingly
F. Basement smoke ventilation system: The basement is provided with fresh air supply and
smoke exhaust fans. The motorized dampers shall be interlocked with the supply and
smoke exhaust fans.
G. Atrium system: Natural intake and exhaust. During fire/smoke mode the ground floor
lobby doors and smoke exhaust ventilators in the skylights open automatically.
B. ALARMS:
1. Alarms will be generated on the BMS in case of following conditions:
a. No air flow detected across the fans in the event of fans being
commanded to switch-on (Fan will be commanded to shutdown)
b. Fan is not running in Auto Mode
A. VAV Boxes with VAV DDC controller shall be provided in space as shown. The space
thermostat with digital display and set point adjustment shall control the VAV to maintain
space temperature at the desired set-point.
B. All information available in VAV Boxes controller to be available to BAS. Also VAV Box
controller to be networked together to the BAS to provide information for control of AHU
based on space load conditions.
C. When the AHU is in the heating mode, the control action of the VAV controller shall be
reversed.
D. Space thermostat / temperature sensor shall be located adjacent to the room light
switch or as agreed with the Engineer.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes fuel-oil and diesel-fuel-oil distribution systems and the following:
1. Pipes, tubes, and fittings.
2. Piping and tubing joining materials.
3. Piping specialties.
4. Valves.
5. Vertical, steel, fuel-oil ASTs.
6. Horizontal, steel, fuel-oil ASTs.
7. Containment-dike, steel, fuel-oil ASTs.
8. Insulated, steel, fuel-oil ASTs.
9. Concrete-vaulted, steel, fuel-oil ASTs.
10. Steel, fuel-oil USTs with STI-P3.
11. Composite, steel, fuel-oil USTs.
12. Jacketed, steel, fuel-oil USTs.
13. FRP fuel-oil USTs.
14. Fuel-oil AST accessories.
15. Fuel-oil UST accessories.
16. Fuel-oil storage tank piping specialties.
17. Fuel-oil storage tank pumps.
18. Fuel-transfer pumps.
19. Fuel maintenance system.
20. Liquid-level gage system.
21. Leak-detection and monitoring system.
22. Mechanical sleeve seals.
23. Grout.
24. Concrete bases.
1.02 DEFINITIONS
D. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred
spaces, pipe and duct shafts, unheated spaces immediately below roof, spaces above
ceilings, unexcavated spaces, crawlspaces, and tunnels.
B. Delegated Design: Design restraint and anchors for fuel-oil piping, ASTs, and
equipment, including comprehensive engineering analysis by a qualified professional
engineer, using performance requirements and design criteria indicated.
1.05 SUBMITTALS
A. Product Data: For each type of product indicated. Include construction details, material
descriptions, and dimensions of individual components and profiles. Also include,
where applicable, rated capacities, operating characteristics, electrical characteristics,
and furnished specialties and accessories.
1. Piping specialties.
2. Valves: Include pressure rating, capacity, settings, and electrical connection
data of selected models.
3. Each type and size of fuel-oil storage tank. Indicate dimensions, weights, loads,
components, and location and size of each field connection.
4. Fuel-oil storage tank accessories.
5. Fuel-oil storage tank piping specialties.
6. Fuel-oil storage tank pumps.
7. Fuel-oil transfer pumps.
8. Fuel maintenance system.
9. Liquid-level gage system.
10. FM approved Leak-detection and monitoring system.
B. Shop Drawings: For facility fuel-oil piping layout. Include plans, piping layout and
elevations, sections, and details for fabrication of pipe anchors, hangers, supports for
multiple pipes, alignment guides, expansion joints and loops, and attachments of the
same to building structure. Detail location of anchors, alignment guides, and expansion
joints and loops.
1. Shop Drawing Scale: 1/4 inch per foot (1:50).
2. For fuel-oil storage tanks and pumps, include details of supports and anchors.
D. Coordination Drawings: Plans and details, drawn to scale, on which fuel-oil piping is
shown and coordinated with other installations, using input from installers of the items
involved.
E. Site Survey: Plans, drawn to scale, on which fuel-oil piping and tanks are shown and
coordinated with other services and utilities.
H. Brazing certificates.
I. Welding certificates.
K. Operation and Maintenance Data: For fuel-oil equipment and accessories to include in
emergency, operation, and maintenance manuals.
A. Brazing: Qualify processes and operators according to ASME Boiler and Pressure
Vessel Code: Section IX.
E. Comply with ASME B31.9, "Building Services Piping," for fuel-oil piping materials,
installation, testing, and inspecting.
G. Comply with NFPA 30, "Flammable and Combustible Liquids Code," and NFPA 31,
"Installation of Oil Burning Equipment," for fuel oil piping materials, components,
installations, testing, and inspecting.
A. Lift and support fuel-oil storage tanks only at designated lifting or supporting points, as
shown on Shop Drawings. Do not move or lift tanks unless empty.
B. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through
shipping, storage, and handling to prevent pipe end damage and to prevent entrance of
dirt, debris, and moisture.
C. Store pipes and tubes with protective PE coating to avoid damaging the coating and to
protect from direct sunlight.
1.08 COORDINATION
A. Coordinate sizes and locations of concrete bases with actual equipment provided.
1.10 WARRANTY
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Provide an electric gauging system compatible with tank size that provides a continuous
signal. Gauging system shall be unaffected by change in the specific gravity of the tank
liquid. A high / low level alarm switch shall be mounted on the gauges. Provide all
contacts and necessary connection as required for monitoring the levels by the control
system.
B. Scales to be calibrated on one side in litres graduated for equal litre units based on
actual tank dimensions, on the other side in millimetre/centimetre graduated for every 6
mm of tank depth.
C. Each gauge shall be filled with red indicating fluid having a specific gravity of not more
than 3.0.
D. Connections between tank and gauges shall consist of double copper tubing encased in
flameproof covering. The copper tubing shall be not less than 3 mm (1/8") O.D. and
provided with suitable end connections.
E. Tank fittings shall be provided with a 38 mm (1 1/2") male pipe thread with a stuffing box
and stuffing box nut through which 13mm (1/2") pressure pipe extends. The pressure
fitting shall be provided with a 13 mm (1/2") female pipe thread. Tank fittings and
pressure fittings shall be made of solid bar stock to prevent leak possibilities.
A. Provide all diesel fuel oil piping, fill lines, water tight fill boxes, vents, vent caps, flame
arresters to vent pipes as required by NFPA, tank foot valves, quick closing spring
actuated fusible link valves on supply and return and other accessories.
B. All piping shall be provided with ground joint unions at piece of apparatus to facilitate
connecting and disconnecting.
C. All piping, unless otherwise specified, shall be standard weight black wrought iron pipe
with standard galvanized malleable iron fittings. All valves shall be designed for 610
KEO/19-3262-0000 23 1113/5 Facility Fuel Oil Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
kg/m2 (125 lb/ft2) steam working pressure. Provide relief valves. Underground fuel
piping shall be extra heavy with galvanized malleable iron fittings and shall be painted
with asphaltum.
D. Galvanized steel vent pipe lines shall run from the fuel oil storage tanks, carried to the
proper height within building construction and terminating with vent fittings. Fittings shall
be "Bronze Ventilating Brick" with thickness of 20 mesh bronze wire gauge in front of
louvered opening, as manufactured by Preferred Utilities Mfg. Corp..
E. Oil suction line piping shall be tested at 625 mm (25") vacuum prior to backfilling.
F. Install the fuel oil piping inside a secondary containment piping system of fiber glass UL
listed reinforced epoxy resin red thread pipe with split two-piece fittings. The
containment pipe shall be one pipe size larger than the fuel piping.
A. Provide packaged type duplex fuel oil pumping and straining set (with one electrical
pump with flame proof motor) with a capacity of two times the total fuel consumption of
engine at full load. Pump sets shall be factory assembled, piped, wired and tested.
Pumps shall be activated by a switch in the day tank. Provide one manual pump of
equal capacity and make necessary piping connections with valves.
B. Support base shall be fabricated of not less than 6 mm steel plate with 75 mm side rails
continuously welded to form a 25 mm high overflow lip, complete with 13 mm drain plug.
Strainer and pumps shall be bolted to individual bases, which, in turn, are welded to the
support base.
C. Piping shall be complete to suction, discharge and return line connections. Provide gate
valves and unions arranged to permit removal of either pump while the system is in
operation. Install check valves and relief valves on pump outlet and gate valves on the
inlet side of pressure gauges.
D. Suction strainer shall be flanged connection, duplex type, one-piece, cast-iron body,
ASTM A 48 Class 30, with 1.2 mm perforation brass baskets.
E. Oil pump set shall be factory assembled on a structural steel channel beam base to
include pumps, motors, flexible couplings etc. Pump set shall be suitable for diesel oil.
F. Valves
1. Gate valves to be bronze body, screwed connection, 1378 kPa.
2. Check valves to be bronze body, angle type, screwed connection, stamped 413
kPa, adjustable 275 to 550 kPa, similar to Bailey No. 118.
A. Exhaust pipes shall be of Schedule 40 black steel and of adequate size to ensure that
back pressure does not exceed the value specified by the manufacturer.
B. The exhaust pipe shall be connected through airtight flexible coupling to the engine.
Bends in exhaust pipe shall have a radius of not less than three times the pipe diameter.
D. When exhaust pipes pass through walls or roof a suitable weatherproof sleeve or
thimble shall be provided to isolate exhaust pipe from the building. A silencer of heavy
duty residential type shall be provided in the exhaust system and it shall also be lagged.
E. Exhaust pipes and mufflers shall be supported from the ceiling by special vibration
isolating hangers and the pipe shall be slanted away from the engine and a condensate
trap fitted at the lowest points. Approved rain caps shall be installed at the discharge
end of the exhaust pipes on the roof.
A. Fuel supply to the engines shall be maintained by daily service tanks of sufficient
capacity for minimum eight (8) hour operation of the sets (or as specified on drawing)
when running at full load. The tanks shall be welded 2mm thick sheet steel construction
treated to resist corrosion, and mounted on suitable angle iron steel structure. Each tank
shall be provided with oil strainer, vent pipe, high and low level control switches, drain
valve, engine supply and return piping connections, daily tank supply and overflow
piping connections, dial type level indicator and electrically operated solenoid valve with
manual reset lever. The engine supply connection shall terminate 25mm above bottom
of tank and provided with a valve. Upon receiving a signal from control panel indicating
a fire in the generator room, actuate each solenoid valve to shut down the fuel supply
lines to the engine.
A. See Part 3 piping schedule articles for where pipes, tubes, fittings, and joining materials
are applied in various services.
B. Steel Pipe: ASTM A 53/A 53M, black steel, Schedule 40, Type E or S, Grade B.
1. Malleable-Iron Threaded Fittings: ASME B16.3, Class 150, standard pattern.
2. Wrought-Steel Welding Fittings: ASTM A 234/A 234M, for butt and socket
welding.
3. Unions: ASME B16.39, Class 150, malleable iron with brass-to-iron seat, ground
joint, and threaded ends.
4. Forged-Steel Flanges and Flanged Fittings: ASME B16.5, minimum Class 150,
including bolts, nuts, and gaskets of the following material group, end
connections, and facings:
a. Material Group: 1.1.
b. End Connections: Threaded or butt welding to match pipe.
c. Lapped Face: Not permitted underground.
d. Gasket Materials: Asbestos free, ASME B16.20 metallic, or
ASME B16.21 nonmetallic, gaskets compatible with fuel oil.
e. Bolts and Nuts: ASME B18.2.1, cadmium-plated steel.
5. Protective Coating for Underground Piping: Factory-applied, three-layer coating
of epoxy, adhesive, and PE.
a. Joint Cover Kits: Epoxy paint, adhesive, and heat-shrink PE sleeves.
C. Drawn-Temper Copper Tube: Comply with ASTM B 88, Type K (ASTM B 88M, Type A).
1. Copper Fittings: ASME B16.22, wrought copper, streamlined pattern.
KEO/19-3262-0000 23 1113/7 Facility Fuel Oil Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Bronze Flanges and Flanged Fittings: ASME B16.24, Class 150.
a. Gasket Material: Asbestos free, ASME B16.20, metallic, or ASME B16.21
nonmetallic, gaskets compatible with fuel oil.
b. Bolts and Nuts: ASME B18.2.1, cadmium-plated steel.
D. Annealed-Temper Copper Tube: Comply with ASTM B 88, Type K (ASTM B 88M,
Type A).
1. Copper Fittings: ASME B16.22, wrought copper, streamlined pattern.
2. Flare Fittings: Comply with ASME B16.26 and SAE J513.
a. Copper fittings with long nuts.
b. Metal-to-metal compression seal without gasket.
c. Dryseal threads complying with ASME B1.20.3.
B. Y-Pattern Strainers:
1. Body: ASTM A 126, Class B, cast iron with bolted cover and bottom drain
connection.
2. End Connections: Threaded ends for NPS 2 (DN 50) and smaller; flanged ends
for NPS 2-1/2 (DN 65) and larger.
3. Strainer Screen: 60 -mesh startup strainer, and perforated stainless-steel basket
with 50 percent free area.
4. CWP Rating: 125 psig (860 kPa).
C. Basket Strainers:
1. Body: ASTM A 126, Class B, high-tensile cast iron with bolted cover and bottom
drain connection.
2. End Connections: Threaded ends for NPS 2 (DN 50) and smaller; flanged ends
for NPS 2-1/2 (DN 65) and larger.
3. Strainer Screen: 60-mesh startup strainer, and perforated stainless-steel basket
with 50 percent free area.
4. CWP Rating: 125 psig (860 kPa).
D. T-Pattern Strainers:
1. Body: Ductile or malleable iron with removable access coupling and end cap for
strainer maintenance.
2. End Connections: Grooved ends.
3. Strainer Screen: 60-mesh startup strainer, and perforated stainless-steel basket
with 57 percent free area.
4. CWP Rating: 750 psig (5170 kPa).
B. Welding Filler Metals: Comply with AWS D10.12/D10.12M for welding materials
appropriate for wall thickness and chemical analysis of steel pipe being welded.
C. Brazing Filler Metals: Alloy with melting point greater than 1000 deg F (540 deg C)
complying with AWS A5.8/A5.8M. Brazing alloys containing more than 0.05 percent
phosphorus are prohibited.
A. See valve schedule in Part 3 for where each valve type is applied in various services.
B. General Requirements for Metallic Valves, NPS 2 (DN 50) and Smaller for Liquid
Service: Comply with UL 842.
1. CWP Rating: 125 psig (860 kPa).
2. Threaded Ends: Comply with ASME B1.20.1.
3. Dry seal Threads on Flare Ends: Comply with ASME B1.20.3.
4. Tamperproof Feature: Locking feature for valves indicated in the valve schedule.
5. Service Mark: Initials "WOG" shall be permanently marked on valve body.
C. General Requirements for Metallic Valves, NPS 2-1/2 (DN 65) and Larger: Comply with
UL 842.
1. CWP Rating: 125 psig (860 kPa).
2. Flanged Ends: Comply with ASME B16.5 for steel flanges.
3. Tamperproof Feature: Locking feature for valves indicated in the valve schedule.
4. Service Mark: Initials "WOG" shall be permanently marked on valve body.
E. Two-Piece, Full-Port, Bronze Ball Valves with Bronze Trim: MSS SP-110.
1. Body: Bronze, complying with ASTM B 584.
2. Ball: Chrome-plated bronze.
3. Stem: Bronze; blowout proof.
4. Seats: Reinforced TFE; blowout proof.
5. Packing: Threaded-body packnut design with adjustable-stem packing.
6. Ends: Threaded, flared, or socket as indicated in the valve schedule.
7. CWP Rating: 600 psig (4140 kPa).
8. Service Mark: Initials "WOG" shall be permanently marked on valve body.
F. Two-Piece, Regular-Port Bronze Ball Valves with Bronze Trim: MSS SP-110.
KEO/19-3262-0000 23 1113/10 Facility Fuel Oil Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Body: Bronze, complying with ASTM B 584.
2. Ball: Chrome-plated bronze.
3. Stem: Bronze; blowout proof.
4. Seats: Reinforced TFE.
5. Packing: Threaded-body packnut design with adjustable-stem packing.
6. Ends: Threaded, flared, or socket as indicated in the valve schedule.
7. CWP Rating: 600 psig (4140 kPa).
8. Service Mark: Initials "WOG" shall be permanently marked on valve body.
A. Description: UL 142 and STI F921, double-wall, horizontal, steel tank; with primary- and
secondary-containment walls and interstitial space.
D. Supports: Manufacturer's standard type, steel or cast-iron cradles, for field installation.
1. Number of Supports: .
A. Description: Jacketed, horizontal, steel tank; complying with UL 58, and with plastic or
fiberglass jacket and corrosion-protection system according to UL 1746 and STI F922.
B. Construction: Tank fabricated with welded carbon steel, and jacket fabricated with
plastic or fiberglass and vacuum-sealed interstitial space; suitable for operation at
atmospheric pressure and with integral leak-detection device. Tank fabricated for the
following loads:
1. Depth of Bury: 3 feet (1 m) from top of tank to finished surface.
2. External Hydrostatic Pressure: To withstand general buckling with safety factor
of 2:1 if hole is fully flooded.
3. Surface Loads: AASHTO's "Specifications for Highway Bridges," H-20 axle
loads of 32,000 lb (14 515 kg).
A. Apply manufacturer's standard prime coat to exterior steel surface of AST and supports.
C. Shop Cleaning: After fabrication, blast clean according to SSPC-SP 6/NACE No. 3.
E. If surface develops rust before prime coat is applied, repeat surface preparation.
F. Apply manufacturer's standard prime coat to shop-cleaned, dry surface same day as
surface preparation.
A. Tank Manholes: 22-inch- (560-mm-) minimum diameter; bolted, flanged, and gasketed,
with extension collar; for access to inside of tank.
C. Threaded pipe connection fittings on top of tank for fill, supply, return, vent, sounding,
and gaging, in locations and of sizes indicated. Include cast-iron plugs for shipping.
D. Striker Plates: Inside tank, on bottom below fill, vent, sounding, gage, and other tube
openings.
F. Ladders: Carbon-steel ladder inside tank, anchored to top and bottom. Include
reinforcement of tank at bottom of ladder.
G. Supply Tube: Extension of supply piping fitting into tank, terminating 6 inches (150 mm)
above tank bottom and cut at a 45-degree angle (1:1 slope).
H. Sounding and Gage Tubes: Extension of fitting into tank, terminating 6 inches (150 mm)
above tank bottom and cut at a 45-degree angle (1:1 slope).
KEO/19-3262-0000 23 1113/13 Facility Fuel Oil Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
I. Containment Sumps: Fiberglass with sump base, add-on extension pieces as required,
sump top, lid, and gasket-seal joints. Include sump entry boots for pipe penetrations
through sidewalls.
J. Sump Entry Boots: Two-part pipe fitting for field assembly and of size required to fit
over pipe. Include gaskets shaped to fit sump sidewall, sleeves, seals, and clamps as
required for liquid-tight pipe penetrations.
K. Anchor Straps: Storage tank manufacturer's standard anchoring system, with straps,
strap-insulating material, cables and turnbuckles, of strength at least one and one-half
times maximum uplift force of empty tank without backfill in place.
L. Filter Mat: Geotextile woven or spun filter fabric, in 1 or more layers, for minimum total
weight of 3 oz./sq. yd. (101.7 g/sq. m).
A. Tank Manholes: 22-inch- (560-mm-) minimum diameter; bolted, flanged, and gasketed;
centered on top of tank.
B. Tank Manholes: 22-inch- (560-mm-) minimum diameter; bolted, flanged, and gasketed;
on top and at side of tank.
C. Threaded pipe connection fittings on top of tank, for fill, supply, return, vent, sounding,
and gaging. Include cast-iron plugs for shipping.
D. Threaded pipe connection fittings on top or sides of tank as indicated, for fill, supply,
return, vent, sounding, and gaging. Include cast-iron plugs for shipping.
E. Striker Plates: Inside tank, on bottom below fill, vent, sounding, gage, and other tube
openings.
G. Ladders: Carbon-steel ladder inside tank, anchored to top and bottom, and located as
indicated. Include reinforcement of tank at bottom of ladder.
H. Ladders: Carbon-steel ladder outside tank, anchored to top and side wall. Comply with
requirements in Division 05 Section "Metal Fabrications" for exterior steel ladder.
1. Cage: Include welded steel cage around ladders for tanks 20 feet (6 m) high or
higher.
I. Supply Tube: Extension of supply piping fitting into tank, terminating 6 inches (150 mm)
above tank bottom and cut at a 45-degree angle (1:1 slope).
J. Sounding and Gage Tubes: Extension of fitting into tank, terminating 6 inches (150 mm)
above tank bottom and cut at a 45-degree angle (1:1 slope).
A. Fitting Materials: Cast iron, malleable iron, brass, or corrosion-resistant metal; suitable
for fuel-oil service.
1. Surface, Flush-Mounted Fittings: Waterproof and suitable for truck traffic.
2. Aboveground-Mounted Fittings: Weatherproof.
B. Spill-Containment Fill Boxes: Flush mounting, with drainage feature to drain oil into
tank, threaded fill-pipe connection, and wrench operation.
C. Fill Boxes: Flush mounting, with threaded fill-pipe connection and wrench operation.
D. Locking Fill Boxes: Flush mounting, with locking-type inner fill cap for standard padlock
and threaded fill-pipe connection.
E. Supply and Sounding Drop Tubes: Fuel-oil supply piping or fitting, inside tank,
terminating 6 inches (150 mm) above bottom of tank, and with end cut at a 45-degree
angle (1:1 slope).
J. Metal Manholes: 22-inch- (560-mm-) minimum diameter frame and cover. Furnish
manhole units of adequate size for access to fittings if size is not indicated.
C. Controls:
1. Run pumps to maintain minimum manifold pressure with outdoor-air temperature
less than 60 deg F (16 deg C) .
KEO/19-3262-0000 23 1113/15 Facility Fuel Oil Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Run pumps on seven-day schedule.
3. Stage pumps on pressure at a common supply manifold.
4. Alternate pumps to equalize run time.
5. Alarm motor failure.
6. Manual reset dry-run protection. Stop pumps if fuel level falls below pump
suction.
7. Deenergize and alarm pump locked rotor condition.
8. Alarm open circuit, high and low voltage.
9. Indicating lights for power on, run, and off normal conditions.
10. Interface with automatic control system is specified in Division 23 Section
"Instrumentation and Control for HVAC" to control and indicate the following:
a. Start/stop pump set when required by schedule, fuel-fired appliance
operation, day tank level control, or weather conditions.
b. Operating status.
c. Alarm off-normal status.
D. Motor: Comply with NEMA designation, temperature rating, service factor, enclosure
type, and efficiency requirements for motors specified in Division 23 Section "Common
Motor Requirements for HVAC Equipment."
1. Motor Sizes: Minimum size as indicated. If not indicated, large enough so driven
load will not require motor to operate in service factor range above 1.0.
2. Controllers, Electrical Devices, and Wiring: Comply with requirements for
electrical devices and connections specified in Division 26 Sections.
E. Piping Furnished with Pumps: Steel with ferrous fittings and threaded or welded joints.
A. Description: Factory fabricated and wired fuel maintenance system for fuel-oil filtration;
with enclosure, filter, fuel-oil pump, and controls; FM approved, listed, and labeled by an
NRTL acceptable to authorities having jurisdiction.
1. Enclosure: NEMA 250, Type 3R, painted steel containing pumps, filters,
accessories, and controls. Hinged door on the front of enclosure.
2. Pump: Comply with HI M109, steel-gear-with-crescent, positive-displacement,
direct- coupled, rotary-type.
KEO/19-3262-0000 23 1113/16 Facility Fuel Oil Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Materials: Cast-iron housing; bronze bearings; steel shaft; mechanical seals;
and built-in, pressure relief bypass valve.
4. Motor: Comply with NEMA designation, temperature rating, service factor,
enclosure type, and efficiency requirements for motors specified in Division 23
Section "Common Motor Requirements for HVAC Equipment."
a. Motor Sizes: Minimum size as indicated. If not indicated, large enough
so driven load will not require motor to operate in service factor range
above 1.0.
b. Controllers, Electrical Devices, and Wiring: Comply with requirements for
electrical devices and connections specified in Division 26 Sections.
5. Piping: Steel with malleable-iron fittings and threaded joints or wrought-steel
fittings and welded joints.
6. Multistage Filter: Spin-on, replaceable types.
a. Stage 1: 100-mesh strainer.
b. Stage 2: Centrifuge to separate particulates and water from oil.
c. Stage 3: Coalescing water and particulate filter.
d. Stage 4: 30-micron particulate removal.
e. Stage 5: 10-micron particulate removal.
f. Stage 6: Minimum 99.5 percent water removal with see-through bowl and
water-sensor probe.
g. Stage 7: 1.5-micron particulate removal.
7. Multiple-Tank Manifolds:
a. Manifold fabricated of Schedule 80, black steel pipe and threaded nipples
for two tanks.
b. Solenoid valves for supply and return piping to each tank.
c. Strainers for each tank supply connection.
8. Programmable Logic Controller:
a. Alarm on maximum 15-in. Hg (51-kPa) vacuum at pump suction indicating
plugged filter.
b. Alarm on high water level in filter.
c. Alarm leak in enclosure.
d. Touch screen; with minimum 2-line, 20-character, backlit, LCD display.
e. Controller strip heater with thermostat.
9. Interface with automatic control system is specified in Division 23 Section
"Instrumentation and Control for HVAC" to control and indicate the following:
a. Start/stop system when required by schedule.
b. Operating status.
c. Alarm off-normal status.
A. Description: Calibrated, liquid-level gage system complying with UL 180 with floats or
other sensors and remote annunciator panel.
B. Annunciator Panel: With visual and audible, high-tank-level and low-tank-level alarms,
fuel indicator with registration in gallons (liters), and overfill alarm. Include gage volume
range that covers fuel-oil storage capacity.
B. Diesel Fuel Oil: ASTM D 975, Grade Low Sulfur, high volatility.
2.24 SLEEVES
A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized
steel, plain ends.
A. Description: Modular sealing element unit, designed for field assembly, to fill annular
space between pipe and sleeve.
1. Sealing Elements: EPDM interlocking links shaped to fit surface of pipe.
Include type and number required for pipe material and size of pipe and sleeve.
2. Pressure Plates: Stainless steel.
3. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of
length required to secure pressure plates to sealing elements. Include one nut
and bolt for each sealing element.
2.26 ESCUTCHEONS
H. Split-Casting, Floor-Plate Escutcheons: Cast brass with concealed hinge and set screw.
2.27 GROUT
A. Precast Concrete Manhole Sections: ASTM C 478 (ASTM C 478M), base and
concentric-cone sections with integral ladder or steps.
A. Pressure test and inspect fuel-oil storage tanks, after fabrication and before shipment,
according to ASME and the following:
1. Horizontal, Double-Wall Steel ASTs: UL 142, STI F921, and STI R931.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine roughing-in for fuel-oil piping system to verify actual locations of piping
connections before equipment installation.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 EARTHWORK
3.03 PREPARATION
A. Close equipment shutoff valves before turning off fuel oil to premises or piping section.
B. Comply with NFPA 30 and NFPA 31 requirements for prevention of accidental ignition.
A. Install underground fuel-oil piping buried at least 18 inches (457 mm) below finished
grade. Comply with requirements in Division 31 Section "Earth Moving" for excavating,
trenching, and backfilling.
1. If fuel-oil piping is installed with less than 12 inches (305 mm) of cover to finished
grade, install in containment piping.
D. Install vent pipe at a minimum slope of 2 percent downward toward fuel-oil storage tank
sump.
E. Assemble and install entry boots for pipe penetrations through sump sidewalls for liquid-
tight joints.
F. Install metal pipes and tubes, fittings, valves, and flexible connectors at piping
connections to AST and UST.
H. Install system components with pressure rating equal to or greater than system
operating pressure.
J. Underground, Exterior-Wall Pipe Penetrations: Install cast-iron "wall pipes" for sleeves.
Seal pipe penetrations using mechanical sleeve seals. Select sleeve size to allow for
1-inch (25-mm) annular clear space between pipe and sleeve for installing mechanical
sleeve seals.
L. Install pressure gage on suction and discharge from each pump. Pressure gages are
specified in Division 23 Section "Meters and Gages for HVAC Piping."
A. Drawing plans, schematics, and diagrams indicate general location and arrangement of
piping systems. Indicated locations and arrangements were used to size pipe and
calculate friction loss, expansion, and other design considerations. Install piping as
indicated unless deviations to layout are approved on Coordination Drawings.
B. Arrange for pipe spaces, chases, slots, sleeves, and openings in building structure
during progress of construction, to allow for mechanical installations.
C. Install piping in concealed locations unless otherwise indicated and except in equipment
rooms and service areas.
D. Install piping indicated to be exposed and piping in equipment rooms and service areas
at right angles or parallel to building walls. Diagonal runs are prohibited unless
specifically indicated otherwise.
E. Install piping above accessible ceilings to allow sufficient space for ceiling panel
removal.
I. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and
floors at pipe penetrations. Seal pipe penetrations with firestop materials. Comply with
requirements in Division 07 Section "Penetration Firestopping."
L. Conceal pipe installations in walls, pipe spaces, or utility spaces; above ceilings; below
grade or floors; and in floor channels unless indicated to be exposed to view.
M. Prohibited Locations:
1. Do not install fuel-oil piping in or through circulating air ducts, clothes or trash
chutes, chimneys or gas vents (flues), ventilating ducts, or dumbwaiter or
elevator shafts.
2. Do not install fuel-oil piping in solid walls or partitions.
N. Use eccentric reducer fittings to make reductions in pipe sizes. Install fittings with level
side down.
P. Install unions in pipes NPS 2 (DN 50) and smaller at final connection to each piece of
equipment and elsewhere as indicated. Unions are not required on flanged devices.
D. Install metal tag attached with metal chain indicating fuel-oil piping systems.
E. Identify valves as specified in Division 23 Section "Identification for HVAC Piping and
Equipment."
F. Install pressure relief valves in distribution piping between the supply and return lines.
G. Install one-piece, bronze ball valve with hose end connection at low points in fuel-oil
piping.
B. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before
assembly.
C. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1.
Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs
and restore full ID. Join pipe fittings and valves as follows:
1. Apply appropriate tape or thread compound to external pipe threads unless dry
seal threading is specified.
2. Damaged Threads: Do not use pipe or pipe fittings with threads that are
corroded or damaged. Do not use pipe sections that have cracked or open
welds.
E. Brazed Joints: Construct joints according to AWS's "Brazing Handbook," "Pipe and
Tube" Chapter.
F. Flanged Joints: Install gasket material, size, type, and thickness for service application.
Install gasket concentrically positioned.
G. Flared Joints: Comply with SAE J513. Tighten finger tight, then use wrench according
to fitting manufacturer's written recommendations. Do not overtighten.
H. Fiberglass-Bonded Joints: Prepare pipe ends and fittings, apply adhesive, and join
according to pipe manufacturer's written instructions.
A. Excavate to sufficient depth for a minimum of 3 feet (1 m) of earth cover from top of tank
to finished grade. Allow for cast-in-place, concrete-ballast base plus 6 inches (150 mm)
of sand or pea gravel between ballast base and tank. Extend excavation at least 12
inches (300 mm) around perimeter of tank.
B. Set tie-down eyelets for hold-down straps in concrete-ballast base and tie to reinforcing
steel.
C. Place 6 inches (152 mm) of clean sand or pea gravel on top of concrete-ballast base.
E. Connect piping.
H. Backfill excavation with clean sand or pea gravel in 12-inch (305-mm) lifts and tamp
backfill lift to consolidate.
I. Install filter mat between top of backfill material and earth fill.
J. Install steel USTs with the STI-P3 corrosion-protection system according to STI R821
and STI R891. Protect anodes during tank placement and backfilling operations.
K. Install composite, steel USTs according to STI R913 and STI R891.
L. Install jacketed, steel USTs according to STI R923 and STI R891.
M. Install FRP USTs with FRP hold-down straps, manhole extensions, and manhole risers.
B. Install hangers for horizontal steel piping with the following maximum spacing and
minimum rod sizes:
1. NPS 1-1/4 (DN 32) and Smaller: Maximum span, 84 inches (2130 mm);
minimum rod size, 3/8 inch (10 mm).
2. NPS 1-1/2 (DN 40): Maximum span, 108 inches (2740 mm); minimum rod size,
3/8 inch (10 mm).
3. NPS 2 (DN 50): Maximum span, 10 feet (3 m); minimum rod size, 3/8 inch (10
mm).
4. NPS 2-1/2 (DN 65): Maximum span, 11 feet (3.4 m); minimum rod size, 1/2 inch
(13 mm).
5. NPS 3 (DN 80): Maximum span, 12 feet (3.7 m); minimum rod size, 1/2 inch (13
mm).
6. NPS 4 (DN 100): Maximum span, 13 feet (4 m); minimum rod size, 5/8 inch (16
mm).
C. Support vertical steel pipe at each floor and at spacing not greater than 15 feet (4.5 m).
D. Install hangers for horizontal, drawn-temper copper tubing with the following maximum
spacing and minimum rod sizes:
1. NPS 3/4 (DN 20) and Smaller: Maximum span, 60 inches (1524 mm); minimum
rod size, 3/8 inch (10 mm).
2. NPS 1 (DN 25): Maximum span, 72 inches (1830 mm); minimum rod size, 3/8
inch (10 mm).
3. NPS 1-1/4 (DN 32): Maximum span, 84 inches (2130 mm); minimum rod size,
3/8 inch (10 mm).
4. NPS 1-1/2 and NPS 2 (DN 40 and DN 50): Maximum span, 96 inches (2440
mm); minimum rod size, 3/8 inch (10 mm).
5. NPS 2-1/2 (DN 65): Maximum span, 108 inches (2740 mm); minimum rod size,
1/2 inch (13 mm).
6. NPS 3 (DN 80): Maximum span, 10 feet (3 m); minimum rod size, 1/2 inch (13
mm).
7. NPS 4 (DN 100): Maximum span, 11 feet (3.4 m); minimum rod size, 5/8 inch
(16 mm).
E. Support vertical copper tube at each floor and at spacing not greater than 10 feet (3 m).
A. Submersible Pumps:
1. Suspend pumps from supply piping and anchored to bottom of tank.
B. Transfer Pumps:
1. Install pumps with access space for periodic maintenance including removal of
motors, impellers, and accessories.
2. Set pumps on and anchor to concrete base.
H. Install vacuum and pressure gage, upstream and downstream respectively, at each
pump to measure the differential pressure across the pump. Pressure gages are
specified in Division 23 Section "Meters and Gages for HVAC Piping."
A. Install suction line, with foot valve, at one end of storage tank, 1 inch (25 mm) from the
bottom of tank.
B. Install return line at the opposite end of storage tank from suction line.
A. Install liquid-level gage system. Locate panel inside building where indicated.
A. Install leak-detection and monitoring system. Install alarm panel inside building where
indicated.
1. Double-Wall, Fuel-Oil Storage Tanks: Install probes Use factory-installed integral
probes in interstitial space.
2. Single-Wall, Fuel-Oil Storage Tanks: Install probes as indicated.
3. Double-Containment, Fuel-Oil Piping: Install leak-detection sensor probes in
fuel-oil storage tank containment sumps and at low points in piping.
4. Install liquid-level gage.
3.15 CONNECTIONS
B. Install unions, in piping NPS 2 (DN 50) and smaller, adjacent to each valve and at final
connection to each piece of equipment having threaded pipe connection.
C. Install flanges, in piping NPS 2-1/2 (DN 65) and larger, adjacent to flanged valves and at
final connection to each piece of equipment having flanged pipe connection.
D. Connect piping to equipment with ball valve and union. Install union between valve and
equipment.
C. Install detectable warning tape directly above fuel-oil piping, 12 inches (304 mm) below
finished grade, except 6 inches (152 mm) below subgrade under pavements and slabs.
Terminate tracer wire in an accessible area, and identify as "tracer wire" for future use
with plastic-laminate sign.
1. Piping: Over underground fuel-oil distribution piping.
2. Fuel-Oil Storage Tanks: Over edges of each UST.
A. Prepare and touch up damaged exterior surface of AST and supports as specified in
"Shop Painting of AST" Article.
C. Field Cleaning: After fabrication, blast clean according to SSPC-SP 6/NACE No. 3
cleaning, remove dust or residue from cleaned surfaces.
D. If surfaces develop rust before prime coat is applied, repeat surface preparation.
E. Prepare surface of AST and supports and apply painting systems according to
specifications in Division 09 Section "High-Performance Coatings" for severe
environment finish for ferrous metal.
A. Comply with requirements in Division 09 painting Sections for painting interior and
exterior fuel-oil piping.
B. Paint exposed, exterior metal piping, valves, and piping specialties, except components
with factory-applied paint or protective coating.
1. Alkyd System: MPI EXT 5.1D.
a. Prime Coat: Alkyd anticorrosive metal primer.
b. Intermediate Coat: Exterior alkyd enamel matching topcoat.
c. Topcoat: Exterior alkyd enamel (flat).
d. Color: Gray.
C. Paint exposed, interior metal piping, valves, and piping specialties, except components
with factory-applied paint or protective coating.
1. Latex Over Alkyd Primer System: MPI INT 5.1Q.
a. Prime Coat: Alkyd anticorrosive.
b. Intermediate Coat: Interior latex matching topcoat.
c. Topcoat: Interior latex (flat).
d. Color: Gray.
2. Alkyd System: MPI INT 5.1E.
a. Prime Coat: Alkyd anticorrosive primer.
b. Intermediate Coat: Interior alkyd matching topcoat.
c. Topcoat: Interior alkyd (flat).
KEO/19-3262-0000 23 1113/27 Facility Fuel Oil Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
d. Color: Gray.
D. Damage and Touchup: Repair marred and damaged factory-applied finishes with
materials and by procedures to match original factory finish.
E. Fuel-oil piping and equipment will be considered defective if it does not pass tests and
inspections.
3.21 DEMONSTRATION
A. Underground fuel-oil piping shall be one of the following. Size indicated is carrier-pipe
size.
1. Flexible, double-containment piping.
2. Rigid, double-containment piping.
B. Underground fuel-oil-tank fill and vent piping shall be one of the following:
1. NPS 2 (DN 50) and Smaller: Steel pipe, steel or malleable-iron threaded fittings,
and threaded joints. Coat pipe and fittings with protective coating for steel piping.
2. NPS 2-1/2 (DN 65) and Larger: Steel pipe, steel welding fittings, and welded
joints. Coat pipe and fittings with protective coating for steel piping.
C. Containment Conduit: Steel pipe with wrought-steel fittings and welded joints. Coat
pipe and fittings with protective coating for steel piping.
A. Distribution piping valves for pipe NPS 2 (DN 50) and smaller shall be one of the
following:
1. One-piece, bronze ball valve with bronze trim.
2. Two-piece, full-port, bronze ball valves with bronze trim.
B. Distribution piping valves for pipe NPS 2-1/2 (DN 65) and larger shall be one of the
following:
1. Two-piece, full regular-port, bronze ball valves with bronze trim.
2. Bronze, nonlubricated plug valve.
C. Valves in branch piping for single appliance shall be one of the following:
1. One-piece, bronze ball valve with bronze trim.
2. Two-piece, full-port, bronze ball valves with bronze trim.
B. Oil suction line piping shall be tested at 0.25" vacuum prior to backfilling. The test shall
be witnessed by consultant and Engineer.
C. The system indicated in the tender documents is for guidance only, contractor shall
ensure complete design, supply and installation of the fuel system in accordance with
KNPC regulations whether indicated in the contract documents or not without additional
cost. The contractor shall obtain necessary approval from KNPC and all other
authorities having jurisdiction.
END OF SECTION
REFRIGERANT PIPING
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.03 SUBMITTALS
A. General: Submit each item in this article according to the conditions of the contract.
B. Product Data: For each type of valve and refrigerant piping specialty indicated. Include
pressure drop, based on manufacturer's test data, for the following:
1. Thermostatic expansion valves.
2. Solenoid valves.
3. Hot-gas bypass valves.
4. Filter dryers.
5. Strainers.
6. Pressure-regulating valves.
C. Shop Drawings: Show layout of refrigerant piping and specialties, including pipe, tube,
and fitting sizes, flow capacities, valve arrangements and locations, slopes of horizontal
runs, oil traps, double risers, wall and floor penetrations, and equipment connection
details. Show interface and spatial relationships between piping and equipment.
KEO/19-3262-0000 23 2300/1 Refrigerant Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
D. Refrigerant piping indicated on Drawings are diagrammatic. Size piping and design
actual piping layout, including oil traps, double risers, specialties, and pipe and tube
sizes to accommodate, as a minimum, equipment provided, elevation difference
between compressor and evaporator, and length of piping to ensure proper operation
and compliance with warranties of connected equipment.
E. Refrigerant pipes to be sized to meet the actual sensible and total cooling capacity as
provided in the equipment schedule based on the actual distance between the Indoor
and Outdoor units.
F. Welding certificates.
H. Operation and Maintenance Data: For refrigerant valves and piping specialties to
include in maintenance manuals.
A. Welding: Qualify procedures and personnel according to ASME Boiler and Pressure
Vessel Code: Section IX, "Welding and Brazing Qualifications."
C. Comply with ASME B31.5, "Refrigeration Piping and Heat Transfer Components."
E. Listing and Labeling : Provide products specified in this section that are UL Listed and
Labeled.
A. Store piping in a clean and protected area with end caps in place to ensure that piping
interior and exterior are clean when installed.
1.06 COORDINATION
A. Coordinate size and location of roof curbs, equipment supports, and roof penetrations.
These items are specified in Division 07 Section "Roof Accessories."
1.07 Definitions
2.01 MANUFACTURERS
A. All refrigerant piping assembled at site shall consist of copper tubing to ASTM
specification B -88 type “k” hard drawn and soldered joints. Joints fittings shall be of
wrought copper or cast brass. Where required for gauges etc. tubing not larger than
3/8” may be of type “k” soft ( annealed) with flared tube or double ferrule
compression fitting suitable for high pressure . flux and solder, recommended by
the manufactures of tubing and fittings and, shall only be used during
installation.
C. Refrigerant stop valves shall be of back seating, key operated, seal up type .
Valves which are to be in constant use shall have hand wheels and shall be of
backless type . Valves connected in copper tubing shall have solder type ends
or flanged ends and soldered flange adapters.
D. Accessories for field assembled piping systems like oil separators, liquid receivers, heat
exchangers, expansion valves, strainers, sight glass, etc., shall be installed as per
manufacturers recommendations and specifications.
A. Copper Tube: ASTM B 88, Type K or L (ASTM B 88M, Type A or B) ASTM B 280,
Type ACR.
D. Solder Filler Metals: ASTM B 32. Use 95-5 tin antimony or alloy HB solder to join
copper socket fittings on copper pipe.
F. Flexible Connectors:
A. Steel Pipe: ASTM A 53/A 53M, black steel with plain ends; Type, Grade, and wall
thickness as selected in Part 3 piping applications articles.
C. Steel Flanges and Flanged Fittings: ASME B16.5, steel, including bolts, nuts, and
gaskets, bevel-welded end connection, and raised face.
D. Welding Filler Metals: Comply with AWS D10.12/D10.12M for welding materials
appropriate for wall thickness and chemical analysis of steel pipe being welded.
E. Flanged Unions:
1. Body: Forged-steel flanges for NPS 1 to NPS 1-1/2 (DN 25 to DN 40) and ductile
iron for NPS 2 to NPS 3 (DN 50 to DN 80). Apply rust-resistant finish at factory.
2. Gasket: Fiber asbestos free.
3. Fasteners: Four plated-steel bolts, with silicon bronze nuts. Apply rust-resistant
finish at factory.
4. End Connections: Brass tailpiece adapters for solder-end connections to copper
tubing.
5. Offset Performance: Capable of minimum 3/4-inch (20-mm) misalignment in
minimum 7-inch- (180-mm-) long assembly.
6. Pressure Rating: Factory test at minimum 400 psig (2760 kPa).
7. Maximum Operating Temperature: 330 deg F (165 deg C).
F. Flexible Connectors:
1. Body: Stainless-steel bellows with woven, flexible, stainless-steel-wire-reinforced
protective jacket
2. End Connections:
a. NPS 2 (DN 50) and Smaller: With threaded-end connections.
b. NPS 2-1/2 (DN 65) and Larger: With flanged-end connections.
3. Offset Performance: Capable of minimum 3/4-inch (20-mm) misalignment in
minimum 7-inch- (180-mm-) long assembly.
4. Pressure Rating: Factory test at minimum 500 psig (3450 kPa).
5. Maximum Operating Temperature: 250 deg F (121 deg C).
B. Packed-Angle Valves:
1. Body and Bonnet: Forged brass or cast bronze.
2. Packing: Molded stem, back seating, and replaceable under pressure.
3. Operator: Rising stem.
4. Seat: Nonrotating, self-aligning polytetrafluoroethylene.
5. Seal Cap: Forged-brass or valox hex cap.
6. End Connections: Socket, union, threaded, or flanged.
7. Working Pressure Rating: 500 psig (3450 kPa).
8. Maximum Operating Temperature: 275 deg F (135 deg C).
C. Check Valves:
1. Body: Ductile iron, forged brass, or cast bronze; globe pattern.
2. Bonnet: Bolted ductile iron, forged brass, or cast bronze; or brass hex plug.
3. Piston: Removable polytetrafluoroethylene seat.
4. Closing Spring: Stainless steel.
5. Manual Opening Stem: Seal cap, plated-steel stem, and graphite seal.
6. End Connections: Socket, union, threaded, or flanged.
7. Maximum Opening Pressure: 0.50 psig (3.4 kPa).
8. Working Pressure Rating: 500 psig (3450 kPa).
9. Maximum Operating Temperature: 275 deg F (135 deg C).
D. Service Valves:
1. Body: Forged brass with brass cap including key end to remove core.
2. Core: Removable ball-type check valve with stainless-steel spring.
3. Seat: Polytetrafluoroethylene.
4. End Connections: Copper spring.
5. Working Pressure Rating: 500 psig (3450 kPa).
E. Solenoid Valves: Comply with ARI 760 and UL 429; listed and labeled by an NRTL.
1. Body and Bonnet: Plated steel.
2. Solenoid Tube, Plunger, Closing Spring, and Seat Orifice: Stainless steel.
3. Seat: Polytetrafluoroethylene.
4. End Connections: Threaded.
5. Electrical: Molded, watertight coil in NEMA 250 enclosure of type required by
location with 1/2-inch (16-GRC) conduit adapter, and 24/115/208 -V ac coil.
6. Working Pressure Rating: 400 psig (2760 kPa).
7. Maximum Operating Temperature: 240 deg F (116 deg C).
8. Manual operator.
F. Safety Relief Valves: Comply with ASME Boiler and Pressure Vessel Code; listed and
labeled by an NRTL.
1. Body and Bonnet: Ductile iron and steel, with neoprene O-ring seal.
2. Piston, Closing Spring, and Seat Insert: Stainless steel.
3. Seat Disc: Polytetrafluoroethylene.
4. End Connections: Threaded.
5. Working Pressure Rating: 400 psig (2760 kPa).
6. Maximum Operating Temperature: 240 deg F (116 deg C).
H. Hot-Gas Bypass Valves: Comply with UL 429; listed and labeled by an NRTL.
1. Body, Bonnet, and Seal Cap: Ductile iron or steel.
2. Diaphragm, Piston, Closing Spring, and Seat Insert: Stainless steel.
3. Packing and Gaskets: Non-asbestos.
4. Solenoid Tube, Plunger, Closing Spring, and Seat Orifice: Stainless steel.
5. Seat: Polytetrafluoroethylene.
6. Equalizer: Internal/External.
7. Electrical: Molded, watertight coil in NEMA 250 enclosure of type required by
location with 1/2-inch (16-GRC) conduit adapter, and 24/115/208 -V ac coil.
8. End Connections: Socket.
9. Set Pressure.
10. Throttling Range: Maximum 5 psig (34 kPa).
11. Working Pressure Rating: 500 psig (3450 kPa).
12. Maximum Operating Temperature: 240 deg F (116 deg C).
A. Straight-Type Strainers:
1. Body: Welded steel with corrosion-resistant coating.
2. Screen: 100-mesh stainless steel.
3. End Connections: Socket or flare.
4. Working Pressure Rating: 500 psig (3450 kPa).
5. Maximum Operating Temperature: 275 deg F (135 deg C).
B. Angle-Type Strainers:
1. Body: Forged brass or cast bronze.
2. Drain Plug: Brass hex plug.
3. Screen: 100-mesh monel.
4. End Connections: Socket or flare.
5. Working Pressure Rating: 500 psig (3450 kPa).
6. Maximum Operating Temperature: 275 deg F (135 deg C).
C. Moisture/Liquid Indicators:
1. Body: Forged brass.
2. Window: Replaceable, clear, fused glass window with indicating element
protected by filter screen.
3. Indicator: Color coded to show moisture content in ppm.
4. Minimum Moisture Indicator Sensitivity: Indicate moisture above 60 ppm.
5. End Connections: Socket or flare.
6. Working Pressure Rating: 500 psig (3450 kPa).
7. Maximum Operating Temperature: 240 deg F (116 deg C).
F. Mufflers:
1. Body: Welded steel with corrosion-resistant coating.
2. End Connections: Socket or flare.
3. Working Pressure Rating: 500 psig (3450 kPa).
4. Maximum Operating Temperature: 275 deg F (135 deg C).
2.07 REFRIGERANTS
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine roughing-in for compliance with requirements for installation tolerances and
other conditions affecting performance of refrigerant piping. Do not proceed with
installation until unsatisfactory conditions have been corrected.
D. Install piping in short and direct arrangement with minimum number of joints, elbows
and fittings.
E. Install piping in concealed locations unless otherwise indicated and except in equipment
rooms and service areas.
F. Arrange piping to allow normal inspection and service of compressor and other
equipment. Install valves and specialties in accessible locations to allow for service and
inspection.
G. Install piping with adequate clearance between pipe and adjacent wall and hangers, or
between pipes for insulation installation. Use sleeves through floors, walls, or ceilings,
sized to permit installation of full-thickness insulation.
1. Insulate suction lines and liquid lines together.
2. Do not install insulation until system testing has been complete and all leaks
have been eliminated.
KEO/19-3262-0000 23 2300/8 Refrigerant Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
H. Install branch lines to parallel compressors of equal length, and pipe and identically and
symmetrically.
I. Install copper tubing in rigid or flexible conduit in locations where copper tubing will be
exposed to mechanically injury.
L. Install exposed piping at right angles or parallel to building walls. Diagonal runs are not
permitted, unless expressly indicated.
M. Reduce pipe size using eccentric reducer fittings installed with level side down.
O. Install flexible connectors at the inlet and discharge connection, at right angles to axial
movement of compressor, parallel to crankshaft.
R. When brazing, remove solenoid-valve coils; remove sight glasses; and remove stems,
seats, and packing of valves, and accessible internal parts of refrigerant specialties. Do
not apply heat near bulb of expansion valve.
V. Charge and purge systems, after testing, and dispose of refrigerant following ASHRAE
15 procedures.
B. Install service valves for gage taps at inlet and outlet of hot-gas bypass valves and
strainers if they are not an integral part of valves and strainers.
C. Install a check valve at the compressor discharge and a liquid accumulator at the
compressor suction connection.
F. Install solenoid valves upstream from each expansion valve and hot-gas bypass valve.
Install solenoid valves in horizontal lines with coil at top.
H. Install safety relief valves where required by ASME Boiler and Pressure Vessel Code.
Pipe safety-relief-valve discharge line to outside according to ASHRAE 15.
I. Install moisture/liquid indicators in liquid line at the inlet of the thermostatic expansion
valve or at the inlet of the evaporator coil capillary tube.
J. Install strainers upstream from and adjacent to the following unless they are furnished
as an integral assembly for device being protected:
1. Solenoid valves.
2. Thermostatic expansion valves.
3. Hot-gas bypass valves.
4. Compressor.
K. Install filter dryers in liquid line between compressor and thermostatic expansion
valve, and in the suction line at the compressor.
A. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
B. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before
assembly.
C. Fill pipe and fittings with an inert gas (nitrogen or carbon dioxide), during brazing or
welding, to prevent scale formation.
E. Brazed Joints: Construct joints according to AWS's "Brazing Handbook," Chapter "Pipe
and Tube."
1. Use Type BcuP, copper-phosphorus alloy for joining copper socket fittings with
copper pipe.
2. Use Type BAg, cadmium-free silver alloy for joining copper with bronze or steel.
F. Threaded Joints: Thread steel pipe with tapered pipe threads according to
ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends
to remove burrs and restore full ID. Join pipe fittings and valves as follows:
1. Apply appropriate tape or thread compound to external pipe threads unless dry-
seal threading is specified.
2. Damaged Threads: Do not use pipe or pipe fittings with threads that are
corroded or damaged. Do not use pipe sections that have cracked or open
welds.
G. Steel pipe can be threaded, but threaded joints must be seal brazed or seal welded.
I. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service
application. Install gasket concentrically positioned. Use suitable lubricants on bolt
threads.
A. Hanger, support, and anchor products are specified in Division 23 Section "Hangers and
Supports for HVAC Piping and Equipment."
C. Install hangers for copper tubing with the following maximum spacing and minimum rod
sizes:
1. NPS 1/2 (DN 15): Maximum span, 60 inches (1500 mm); minimum rod size, 1/4
inch (6.4 mm).
2. NPS 5/8 (DN 18): Maximum span, 60 inches (1500 mm); minimum rod size, 1/4
inch (6.4 mm).
3. NPS 1 (DN 25): Maximum span, 72 inches (1800 mm); minimum rod size, 1/4
inch (6.4 mm).
4. NPS 1-1/4 (DN 32): Maximum span, 96 inches (2400 mm); minimum rod size,
3/8 inch (9.5 mm).
5. NPS 1-1/2 (DN 40): Maximum span, 96 inches (2400 mm); minimum rod size,
3/8 inch (9.5 mm).
KEO/19-3262-0000 23 2300/11 Refrigerant Piping
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
6. NPS 2 (DN 50): Maximum span, 96 inches (2400 mm); minimum rod size, 3/8
inch (9.5 mm).
7. NPS 2-1/2 (DN 65): Maximum span, 108 inches (2700 mm); minimum rod size,
3/8 inch (9.5 mm).
8. NPS 3 (DN 80): Maximum span, 10 feet (3 m); minimum rod size, 3/8 inch (9.5
mm).
9. NPS 4 (DN 100): Maximum span, 12 feet (3.7 m); minimum rod size, 1/2 inch
(13 mm).
D. Install hangers for steel piping with the following maximum spacing and minimum rod
sizes:
1. NPS 2 (DN 50): Maximum span, 10 feet (3 m); minimum rod size, 3/8 inch (9.5
mm).
2. NPS 2-1/2 (DN 65): Maximum span, 11 feet (3.4 m); minimum rod size, 3/8 inch
(9.5 mm).
3. NPS 3 (DN 80): Maximum span, 12 feet (3.7 m); minimum rod size, 3/8 inch (9.5
mm).
4. NPS 4 (DN 100): Maximum span, 14 feet (4.3 m); minimum rod size, 1/2 inch
(13 mm).
B. Adjust high- and low-pressure switch settings to avoid short cycling in response to
fluctuating suction pressure.
D. Perform the following adjustments before operating the refrigeration system, according
to manufacturer's written instructions:
1. Open shutoff valves in condenser water circuit.
2. Verify that compressor oil level is correct.
3. Open compressor suction and discharge valves.
4. Open refrigerant valves except bypass valves that are used for other purposes.
5. Check open compressor-motor alignment and verify lubrication for motors and
bearings.
E. Replace core of replaceable filter dryer after system has been adjusted and after design
flow rates and pressures are established.
3.09 CLEANING
A. Before installation of copper tubing other than Type ACR, clean tubing and fittings with
trichlorethylene.
B. Any leaks or faults discovered during such tests shall be remedied at once by the
contractor at his own expenses and the tests repeated until the engineer is satisfied that
the section under tests is sound and the engineer ‘ s decision whether the test is sound
or not shall be final.
A. Before charging the system with the refrigerant, it must be dehydrated through, using a
high efficiency vacuum pump and vacuum indicator. Dehydrating operation shall
continue until a reading of 35 FWB at a pressure of 0.204” HG absolute is reached.
3.012 COMMISSIONING
END OF SECTION
METAL DUCTS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes metal ducts for supply, return, outside, and exhaust air-distribution
systems in pressure classes from minus 500 to plus 2500Pa. Metal ducts include the
following:
1. Rectangular ducts and fittings.
2. Single-wall, round, and flat-oval spiral-seam ducts and formed fittings. (If
Applicable)
3. Double-wall, round, and flat-oval spiral-seam ducts and formed fittings. (If
Applicable)
4. Duct liner.
5. Fire Rated Ductwork.
1.02 SUBMITTALS
B. Shop Drawings: CAD-generated and drawn to scale not greater than 1:100. Show
fabrication and installation details for metal ducts.
1. Fabrication, assembly, and installation, including plans, elevations, sections,
components, and attachments to other work.
2. Duct layout indicating sizes and pressure classes.
3. Elevations of top and bottom of ducts.
4. Dimensions of main duct runs from building grid lines.
5. Fittings.
6. Reinforcement and spacing.
7. Seam and joint construction.
8. Penetrations through fire-rated and other partitions.
9. Equipment installation based on equipment being used on Project.
10. Duct accessories, including access doors and panels.
11. Hangers and supports, including methods for duct and building attachment,
vibration isolation, and seismic restraints.
KEO/19-3262-0000 23 3113/1 Metal Ducts
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. Coordination Drawings: Reflected ceiling plans, drawn to scale, on which the following
items are shown and coordinated with each other, based on input from installers of the
items involved:
1. Ceiling suspension assembly members.
2. Other systems installed in same space as ducts.
3. Ceiling- and wall-mounting access doors and panels required to provide access
to dampers and other operating devices.
4. Ceiling-mounting items, including lighting fixtures, diffusers, grilles, speakers,
sprinklers, access panels, and special moldings.
D. Welding certificates.
E. Field quality-control test reports: Indicate and interpret test results for compliance with
performance requirements.
F. Record Drawings: Indicate actual routing, fitting details, reinforcements, supports, and
installed accessories and devices.
B. NFPA Compliance:
1. NFPA 90A, "Installation of Air Conditioning and Ventilating Systems”, unless
otherwise indicated.
2. NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems”,
unless otherwise indicated.
C. Comply with NFPA 96, "Ventilation Control and Fire Protection of Commercial Cooking
Operations," Ch. 3, "Duct System," for range hood ducts, unless otherwise indicated.
B. Where possible, store ductwork inside and protect from weather. Where necessary to
store outside, store above grade and enclose with waterproof wrapping.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for
acceptable materials, material thickness, and duct construction methods, unless
otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller
marks, stains, discolorations, and other imperfections.
D. Flexible Ducts
1. UL 181, Class 1, aluminum-polyester composite film with latex adhesive,
supported by helical wound spring steel wire; fiberglass insulation; aluminized
KEO/19-3262-0000 23 3113/3 Metal Ducts
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
vapor barrier film and PVC jacket, K value of 0.23 maximum @ 75 F mean
temperature.
2. Pressure Rating: 2,500 Pa (10-inch WG) positive.
3. Maximum Velocity: 25 M / Sec. (4,900 fpm)
4. Temperature Range: - 30 C to 140 C (-22 F to 284 F).
A. Fibrous-Glass Liner: Comply with NFPA 90A or NFPA 90B and with NAIMA AH124.
1. Materials: ASTM C 1071; surfaces exposed to airstreams shall be coated to
prevent erosion of glass fibers.
a. Thickness: 25mm, unless otherwise indicated.
b. Thermal Conductivity (k-Value): 0.037 at 24 deg C mean temperature.
c. Fire-Hazard Classification: Maximum flame-spread index of 25 and
smoke-developed index of 50 when tested according to ASTM E 84.
d. Liner Adhesive: Comply with NFPA 90A or NFPA 90B and with ASTM C
916.
e. Mechanical Fasteners: Galvanized steel suitable for adhesive
attachment, mechanical attachment, or welding attachment to duct
without damaging liner when applied as recommended by manufacturer
and without causing leakage in duct.
2. Tensile Strength: Indefinitely sustain a 23kg tensile, dead load test
perpendicular to duct wall.
3. Fastener Pin Length: As required for thickness of insulation and without
projecting more than 3mm into airstream.
4. Adhesive for Attaching Mechanical Fasteners: Comply with fire-hazard
classification of duct liner system.
B. Flexible Elastomeric Duct Liner: Comply with NFPA 90A or NFPA 90B.
1. Materials: Unicellular polyethylene thermal plastic, preformed sheet insulation
complying with ASTM C 534, Type II, except for density.
a. Thickness: 19mm, unless otherwise indicated.
b. Thermal Conductivity (k-Value): 0.034 at 24 deg C mean temperature.
c. Fire-Hazard Classification: Maximum flame-spread index of 25 and
smoke-developed index of 50 when tested according to ASTM C 411.
d. Liner Adhesive: As recommended by insulation manufacturer and
complying with NFPA 90A or NFPA 90B.
A. Joint and Seam Sealants, General: The term "sealant" is not limited to materials of
adhesive or mastic nature but includes tapes and combinations of open-weave fabric
strips and mastics.
C. Duct Attachments: Sheet metal screws, blind rivets, or self-tapping metal screws;
compatible with duct materials.
D. Trapeze and Riser Supports: Steel shapes complying with ASTM A 36/A 36M.
1. Supports for Galvanized-Steel Ducts: Galvanized-steel shapes and plates.
2. Supports for Stainless-Steel Ducts: Stainless-steel support materials.
3. Supports for Aluminum Ducts: Aluminum support materials unless materials are
electrolytically separated from ducts.
A. Fabricate ducts, elbows, transitions, offsets, branch connections, and other construction
according to SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" and
complying with requirements for metal thickness, reinforcing types and intervals, tie-rod
applications, and joint types and intervals. Where duct sizes exceed those listed in the
referenced standards, the duct manufacturer shall determine the proper material
thickness and reinforcement requirements in accordance with SMACNA’s Chapter 7,
Functional Criteria, "HVAC Duct Construction Standards--Metal and Flexible."
1. Lengths: Fabricate rectangular ducts in lengths appropriate to reinforcement and
rigidity class required for pressure class.
2. Deflection: Duct systems shall not exceed deflection limits according to
SMACNA's "HVAC Duct Construction Standards--Metal and Flexible."
D. Cross Breaking or Cross Beading: Cross break or cross bead duct sides 480mm and
larger and 0.9mm thick or less, with more than 0.93 sq. m of nonbraced panel area
unless ducts are lined.
Up to 18 (450) 24
19 to 42 (475 to 1050) 22
43 to 54 (1075 to 1350) 20
55 to 72 (1375 to 1800) 18
A. Adhere a single layer of indicated thickness of duct liner with at least 90 percent
adhesive coverage at liner contact surface area. Attaining indicated thickness with
multiple layers of duct liner is prohibited.
B. Apply adhesive to transverse edges of liner facing upstream that do not receive metal
nosing.
C. Butt transverse joints without gaps and coat joint with adhesive.
D. Fold and compress liner in corners of rectangular ducts or cut and fit to ensure butted-
edge overlapping.
E. Do not apply liner in rectangular ducts with longitudinal joints, except at corners of ducts,
unless duct size and standard liner product dimensions make longitudinal joints
necessary.
F. Apply adhesive coating on longitudinal seams in ducts with air velocity of 12.7 m/s.
G. Secure liner with mechanical fasteners 100mm from corners and at intervals not
exceeding 300mm transversely; at 75mm from transverse joints and at intervals not
exceeding 450mm longitudinally.
H. Secure transversely oriented liner edges facing the airstream with metal nosings that
have either channel or "Z" profiles or are integrally formed from duct wall. Fabricate
edge facings at the following locations:
1. Fan discharges.
2. Intervals of lined duct preceding unlined duct.
3. Upstream edges of transverse joints in ducts where air velocities are greater than
2500 fpm (12.7 m/s) or where indicated.
I. Terminate inner ducts with buildouts attached to fire-damper sleeves, dampers, turning
vane assemblies, or other devices. Fabricated buildouts (metal hat sections) or other
B. Diameter as applied to flat-oval ducts in this Article is the diameter of a round duct with a
circumference equal to the perimeter of a given size of flat-oval duct.
D. Duct Joints:
1. Ducts up to 500mm in Diameter: Interior, center-beaded slip coupling, sealed
before and after fastening, attached with sheet metal screws.
2. Ducts 535 to 1830mm in Diameter: Three-piece, gasketed, flanged joint
consisting of two internal flanges with sealant and one external closure band with
gasket.
3. Ducts Larger than 1830mm in Diameter: Companion angle flanged joints per
SMACNA "HVAC Duct Construction Standards--Metal and Flexible," Figure 3-2.
4. Round Ducts: Prefabricated connection system consisting of double-lipped,
EPDM rubber gasket. Manufacture ducts according to connection system
manufacturer's tolerances.
E. 90-Degree Tees and Laterals and Conical Tees: Fabricate to comply with SMACNA's
"HVAC Duct Construction Standards--Metal and Flexible," with metal thickness specified
for longitudinal-seam straight ducts.
F. Diverging-Flow Fittings: Fabricate with reduced entrance to branch taps and with no
excess material projecting from fitting onto branch tap entrance.
A. Fire rated ductwork Shall be applicable for Smoke extract system, Car park ventilation
system, kitchen extract system, corridor pressurization system and all emergency
ventilation system.
B. Fire rated ductwork shall be NON coated galvanized steel with integral flanges.
C. Fire rated ductwork shall provide at least 2 Hrs fire rating as per BS 476 Part 24 and BS
5588 Part 9 standard.
D. Fire rated ductwork shall be tested, assessed and certified by independent laboratories
such as Warrington or British Research BRE.
G. The approval of non-coated fire rated duct system is subject to third party approval
certificate – Certifier CF761.
H. Non-coated fire rated ductwork is acceptable equal for use in applications of fire rated
ductwork where specifications may refer to any coated duct systems without any
prejudice so as long as performance criteria such as fire resistance required rating is
met.
I. The Fire Rated ductwork shall be tested for both Type A (Fire Outside) and Type B (Fire
Inside and Outside) as per BS 476; Part 24:1987 (ISO 6944:1985) to meet design
guidelines in accordance to BS 5588: Part 9:1989, Method 3, for both horizontal and
vertical ductwork test.
K. The ductwork should be capable of providing Type A (fire outside) or Duct B (fire inside)
fire containment and, under normal non-fire operating conditions, should conform to the
pressure classification of the current HVCA DW/144 Specification for Sheet Metal
Ductwork.
M. In addition to above the fire rated ducts should meet requirements as mentioned below.
1. Fire rated Ductwork for Smoke Control Systems (both exhaust and make-up air
ducts) shall be of at least 2-hour fire resistance rated.
2. Where a duct passes through other fire compartments of higher rating, the duct
shall be constructed to have the same rating of that compartment. The rating
shall apply to fire exposure from both interior and exterior of the duct or structure.
3. Such fire rating of smoke control system ducts shall be evaluated and approved
for fire rating as well as for Stability, Integrity and Insulation Criteria for fire rating.
4. The complete duct system including supports, hangers, joints, gaskets, sealant
etc. shall be in compliance with the approved test standards and fire rating
criteria.
5. Ducts for Smoke control systems (Type A, Rated for both fire outside and Type
B, fire outside and inside, 1 hour and 2 hour fire rated, tested and approved for
PART 3 - EXECUTION
A. Construct and install each duct system for the specific duct pressure classification, duct
seal class and duct leakage class indicated in the Duct System Schedule article of this
section.
A. Drawings indicate general arrangement of ducts, fittings, and accessories. Not all
required fittings or offsets are shown, the Contractor shall coordinate the installation with
other trades and provide all necessary offsets and fittings.
C. Install round and flat-oval ducts in lengths not less than 3.7m unless interrupted by
fittings.
E. Install fabricated fittings for changes in directions, size, and shape and for connections.
F. Install couplings tight to duct wall surface with a minimum of projections into duct.
Secure couplings with sheet metal screws. Install screws at intervals of 300mm, with a
minimum of 3 screws in each coupling.
G. Install ducts, unless otherwise indicated, vertically and horizontally and parallel and
perpendicular to building lines; avoid diagonal runs.
H. Install ducts close to walls, overhead construction, columns, and other structural and
permanent enclosure elements of building. Ductwork located in high bay spaces, where
the floor-to-floor clearance is in excess of 5.5 meters, shall be installed no higher than
600 mm above finished ceiling.
I. Install ducts with a clearance of 25mm, plus allowance for insulation thickness.
KEO/19-3262-0000 23 3113/11 Metal Ducts
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
J. Conceal ducts from view in finished spaces. Do not encase horizontal runs in solid
partitions unless specifically indicated.
K. Coordinate layout with suspended ceiling, fire- and smoke-control dampers, lighting
layouts, and similar finished work.
L. Seal all joints and seams. Apply sealant to male end connectors before insertion, and
afterward to cover entire joint and sheet metal screws.
M. Electrical Equipment Spaces: Route ducts to avoid passing through transformer vaults
and electrical equipment spaces and enclosures.
N. Non-Fire-Rated Partition Penetrations: Where ducts pass through interior partitions and
exterior walls and are exposed to view, conceal spaces between construction openings
and ducts or duct insulation with sheet metal flanges of same metal thickness as ducts.
Overlap openings on 4 sides by at least 38mm.
O. Fire-Rated Partition Penetrations: Where ducts pass through interior partitions and
exterior walls, install appropriately rated fire dampers, sleeves, and firestopping sealant.
Fire and smoke dampers are specified in Section 23 "Duct Accessories." Firestopping
materials and installation methods are specified in Section 23 "Through-Penetration
Firestop Systems."
P. Install ducts with hangers and braces designed to withstand, without damage to
equipment, seismic force required by applicable building codes. Refer to SMACNA's
"Seismic Restraint Manual: Guidelines for Mechanical Systems."
Q. Protect duct interiors from the elements and foreign materials until building is enclosed.
Follow SMACNA's "Duct Cleanliness for New Construction."
R. Supply and return air ductwork, outside the building shall be single wall, insulated, and
finished with a weatherproof aluminum jacket (If Applicable).
A. Install ducts to allow for thermal expansion through 1110 deg C temperature range.
B. Install ducts without dips or traps that may collect residues unless traps have continuous
or automatic residue removal.
C. Install access openings at each change in direction and at intervals defined by NFPA
96; locate on sides of duct a minimum of 38mm from bottom; and fit with grease-tight
covers of same material as duct.
A. Duct liner application is allowed immediately upstream and downstream of air handling
equipment and up to 3m downstream of air terminal units, unless accepted by Engineer.
A. Install rigid round, rectangular, and flat-oval metal duct with support systems indicated in
SMACNA's "HVAC Duct Construction Standards--Metal and Flexible."
B. Support horizontal ducts within 600mm of each elbow and within 1200mm of each
branch intersection.
D. Install upper attachments to structures with an allowable load not exceeding one-fourth
of failure (proof-test) load.
3.07 CONNECTIONS
B. Comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for
branch, outlet and inlet, and terminal unit connections, unless specifically indicated
otherwise.
A. Perform the following field tests and inspections according to SMACNA's "HVAC Air
Duct Leakage Test Manual" and prepare test reports:
1. Disassemble, reassemble, and seal segments of systems to accommodate
leakage testing and for compliance with test requirements.
2. Test approximately 25 percent of the installed ductwork having a SMACNA Duct
Construction Class of 1000 Pa (4 inches water column) or above. The ductwork
to be tested shall be randomly selected by the EMPLOYER.
3. Follow the procedures outlined in SMACNA HVAC Air Duct Leakage Test
Manual, latest edition.
4. Testing apparatus and procedures shall be reviewed and accepted by the
Employer before the start of tests. Tests shall be carried out in the presence of
the Employer who shall verify the test results. Contact the Employer to
coordinate the time of testing.
5. The leakage amount shall not exceed the SMACNA leakage class indicated in
the Duct System Schedule.
6. Remake leaking joints and retest until leakage is equal to or less than maximum
allowable.
KEO/19-3262-0000 23 3113/13 Metal Ducts
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
7. Submit a test report for Employer review. The test report shall be in accordance
with the reporting requirements in the SMACNA Air Duct Leakage Test Manual.
Note:
1. All exposed to view ducts with insulation (if any) shall be covered with aluminium
jacketing minimum 0.7mm thick.
A. Mark position of dampers and air-directional mechanical devices before cleaning, and
perform cleaning before air balancing.
B. Use service openings, as required, for physical and mechanical entry and for inspection.
1. Create other openings to comply with duct standards.
2. Disconnect flexible ducts as needed for cleaning and inspection.
3. Remove and reinstall ceiling sections to gain access during the cleaning process.
C. Vent vacuuming system to the outside. Include filtration to contain debris removed from
HVAC systems, and locate exhaust down wind and away from air intakes and other
points of entry into building.
D. Clean the following metal duct systems by removing surface contaminants and deposits:
1. Air outlets and inlets (registers, grilles, and diffusers).
2. Supply, return, and exhaust fans including fan housings, plenums (except ceiling
supply and return plenums), scrolls, blades or vanes, shafts, baffles, dampers,
and drive assemblies.
3. Air-handling unit internal surfaces and components including mixing box, coil
section, air wash systems, spray eliminators, condensate drain pans, humidifiers
and dehumidifiers, filters and filter sections, and condensate collectors and
drains.
4. Coils and related components.
5. Return-air ducts, dampers, and actuators except in ceiling plenums and
mechanical equipment rooms.
6. Supply-air ducts, dampers, actuators, and turning vanes.
F. Cleanliness Verification:
1. Visually inspect metal ducts for contaminants.
2. Where contaminants are discovered, re-clean and re-inspect ducts.
END OF SECTION
HVAC CASINGS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes HVAC casings for field-erected and / or factory fabricated air-
handling systems and for housing mechanical equipment.
1.03 SUBMITTALS
A. Product Data: For factory-fabricated casings, sealant materials, and acoustic liner
materials.
D. Welding certificates.
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in section 23.
B. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These
items are specified in section 23 "Roof Accessories."
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Galvanized Sheet Steel: Lock-forming quality; complying with ASTM A 653/A 653M and
having [G90 (Z275)] [G60 (Z180)] coating designation; ducts shall have mill-
phosphatized finish for surfaces exposed to view.
C. Tie Rods: Galvanized steel, 1/4-inch (6-mm) minimum diameter for lengths 36 inches
(900 mm) or less; 3/8-inch (10-mm) minimum diameter for lengths longer than mm36
inches (900 mm).
D. Miscellaneous Materials and Products: Types and sizes required to comply with HVAC
casing system requirements, including proper connection of ducts and equipment.
A. Joint and Seam Sealants, General: The term "sealant" is not limited to materials of
adhesive or mastic nature but includes tapes and combinations of open-weave fabric
strips and mastics.
B. Water-Based Joint and Seam Sealant: Flexible, adhesive sealant, resistant to UV light
when cured, UL 723 listed, and complying with NFPA requirements for Class 1 ducts.
B. Shop fabricate casings, to greatest extent possible, with a minimum number of joints
and to minimize field fabrication and assembly.
C. Fabricate casings with standing seams and angle reinforcements. Fabricate close-off
sheets from casing sides, top, and bottom to damper, coil, and filter frames. Fabricate
close-off sheets at joints between stacked coils. Bolt close-off sheets to frame flanges
and housings. Support coils on stands fabricated from galvanized-steel angles or
channels.
E. Seal joints with liquid-type, high-pressure duct sealant to eliminate air leakage.
F. Fabricate drain pans for cooling coils, humidifiers, and eliminator blade sections in
casings with external connections and vented deep-seal traps for drainage piping with
3/4-inch (20-mm) pipe connections. Fabricate and reinforce drain pans of same
material and thickness as housing, 2 inches (50 mm) deep with rolled edges. Solder
seams.
G. Fabricate casings with reinforced openings for access doors at least 20 inches (500
mm) wide by 48 inches (1200 mm) high and located for access to each item of
equipment housed. Refer to Division 23 Section "Air Duct Accessories" for access
doors.
H. Fabricate casings to receive flexible or outlet connectors for fans. Refer to Division 23
Section "Air Duct Accessories" for flexible connectors.
B. Panel Fabrication: Solid, galvanized sheet steel exterior shell and solid, galvanized
sheet steel interior shell; with 2- or 4-inch (50- or 100-mm) space between shells, as
indicated.
1. Fabricate with a minimum number of joints.
2. Weld exterior and interior shells to perimeter; to interior, longitudinal, galvanized-
steel channels; and to box-end internal closures. Paint welds.
3. Exterior Shell Thickness: 0.040 inch (1.0 mm) minimum.
4. Interior Shell Thickness: 0.034 inch (0.85 mm) minimum.
5. Interior Shell Thickness: 0.034 inch (0.85 mm) minimum, with 3/32-inch (2.4-
mm) perforations at 3/16-inch (5-mm) staggered spacing for 23 percent open
area.
6. Fabricate perimeter and interior, longitudinal channel members with galvanized-
steel shapes.
7. Fill each panel assembly with insulating material that is noncombustible, inert,
mildew resistant, and vermin proof, and that complies with NFPA 90A.
8. Fabricate panels with tongue-and-groove, continuous self-locking joints effective
inside and outside each panel.
C. Trim Items: Fabricate from a minimum of 0.052-inch (1.3-mm) galvanized sheet steel,
furnished in standard lengths for field cutting.
D. Access Doors: Fabricate personnel access doors at least 24 by 60 inches (600 by 1500
mm) and other access doors in sizes indicated.
1. Fabricate doors of same thickness as panels, with a minimum 0.040-inch (1.0-
mm) solid, interior and exterior, galvanized sheet steel shell.
2. Install a minimum of two ball-bearing hinges and two wedge-lever-type latches,
operable from inside and outside. Install doors to open against air pressure
differential. Install neoprene gaskets around entire perimeters of door frames.
3. Fabricate windows in doors consisting of double-glazed, wire-reinforced safety
glass with an air space between panes and sealed with interior and exterior
rubber seals.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine concrete bases and roof curbs for compliance with requirements for conditions
affecting installation and performance of HVAC casings.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 INSTALLATION
C. Field-cut openings for pipe and conduit penetrations; insulate and seal according to
SMACNA's "HVAC Duct Construction Standards--Metal and Flexible."
E. Support components rigidly with ties, braces, brackets, seismic restraints, and anchors
of types that will maintain housing shape and prevent buckling.
A. Adhere a single layer of indicated thickness of duct liner with at least 90 percent
adhesive coverage at liner contact surface area. Attaining indicated thickness with
multiple layers of duct liner is prohibited.
B. Apply adhesive to liner that faces direction of airflow not receiving metal nosing.
C. Butt transverse joints without gaps and coat joint with adhesive.
D. Fold and compress liner in corners of casings or cut and fit to ensure butted-edge
overlapping.
E. Do not apply liner with longitudinal joints, except at corners of casings, unless casing
size and standard liner product dimensions make longitudinal joints necessary.
H. Secure transversely oriented liner edges facing the airstream with metal nosings that
have either channel or "Z" profile or are integrally formed from casing wall. Fabricate
edge facings at the following locations:
1. Fan discharges.
2. Intervals of lined casing preceding unlined casing.
3. Upstream edges of transverse joints in casings.
A. Perform the following field tests and inspections according to SMACNA's "HVAC Air
Duct Leakage Test Manual" and prepare test reports:
1. Conduct tests at static pressures equal to maximum design pressure of system
or section being tested. If pressure classes are not indicated, test entire system
at maximum system design pressure. Do not pressurize systems above
maximum design operating pressure. Give seven days' advance notice for
testing.
2. Determine leakage from entire system or section of system by relating leakage to
surface area of test section. Comply with requirements for leakage classification
of ducts connected to casings.
3. Remake leaking joints and retest until leakage is equal to or less than maximum
allowable.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUBMITTALS
B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads,
required clearances, method of field assembly, components, and location and size of
each field connection.
1. Special fittings.
2. Manual-volume damper installations.
KEO/19-3262-0000 23 3300/1 Air Duct Accessories
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Motorized-control damper installations.
4. Fire-damper, smoke-damper, and combination fire- and smoke-damper
installations, including sleeves and duct-mounting access doors.
5. Wiring Diagrams: Power, signal, and control wiring.
A. Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," and
NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems."
B. Following spare parts shall be furnished, properly packed and labelled with equipment
no. / location.
1. Two (2) nos. of fusible links of Fire dampers of each type and size used in the
project.
2. Four (4) sets of Motor with damper blades and actuators for each type and size
of Smoke control dampers used in the Project.
3. Four (4) sets of Motors with damper blades and actuators for each type and size
of Motorized volume control dampers used in the project.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible" for
acceptable materials, material thicknesses, and duct construction methods, unless
otherwise indicated.
B. Galvanized Sheet Steel: Lock-forming quality; complying with ASTM A 653/A 653M and
having G60, Z180, G90 or Z275 coating designation; ducts shall have mill-phosphatized
finish for surfaces exposed to view.
E. Extruded Aluminum: ASTM B 221 (ASTM B 221M), alloy 6063, temper T6.
G. Tie Rods: Galvanized steel, 1/4-inch (6-mm) minimum diameter for lengths 36 inches
(900 mm) or less; 3/8-inch (10-mm) minimum diameter for lengths longer than 36 inches
(900 mm).
E. Damper Hardware: Zinc-plated, die-cast core with dial and handle made of 3/32-inch-
(2.4-mm-) thick zinc-plated steel, and a 3/4-inch (19-mm) hexagon locking nut. Include
center hole to suit damper operating-rod size. Include elevated platform for insulated
duct mounting.
C. Frame: Curtain type with blades inside airstream Curtain type with blades outside
airstream and Multiple-blade type; fabricated with roll-formed, 0.034-inch- (0.85-mm-)
thick galvanized steel; with mitered and interlocking corners.
H. Fusible Links: Replaceable, 165 deg F (74 deg C) 212 deg F (100 deg C) rated.
B. Frame: Galvanized sheet steel, round or rectangular, style to suit ceiling construction.
D. Fusible Links: Replaceable, 165 deg F (74 deg C) 212 deg F (100 deg C) 285 deg F
(141 deg C) rated.
2.08 SMOKE and COMBINATION FIRE AND SMOKE DAMPERS (If Applicable)
D. Round Units:
1. Outer Casings:
a. ASTM A 653/A 653M, G90 (Z275) galvanized sheet steel.
b. Up to 24 Inches (600 mm) in Diameter: 0.034 inch (0.85 mm) thick.
c. 26 through 40 Inches (660 through 1000 mm) in Diameter: 0.040 inch
(1.0 mm) thick.
d. 42 through 52 Inches (1060 through 1300 mm) in Diameter: 0.052 inch
(1.3 mm) thick.
e. 54 through 60 Inches (1370 through 1500 mm) in Diameter: 0.064 inch
(1.62 mm) thick.
f. Casings fabricated of spiral lock-seam duct may be one size thinner than
that indicated.
2. Interior Casing, Partitions, and Baffles:
a. ASTM A 653/A 653M, G90 (Z275) galvanized sheet steel.
b. At least 0.034 inch (0.85 mm) thick and designed for minimum
aerodynamic losses.
E. Sheet Metal Perforations: 1/8-inch (3-mm) diameter for inner casing and baffle sheet
metal.
F. Fill Material: Inert and vermin-proof fibrous material, packed under not less than 5
percent compression.
1. Erosion Barrier: Polymer bag enclosing fill and heat-sealed before assembly.
A. General Description: Fabricate doors airtight and suitable for duct pressure class.
B. Door: Double wall, duct mounting, and rectangular; fabricated of galvanized sheet metal
with insulation fill and thickness as indicated for duct pressure class. Include vision
panel where indicated. Include 1-by-1-inch (25-by-25-mm) butt or piano hinge and cam
latches.
1. Frame: Galvanized sheet steel, with bend-over tabs and foam gaskets.
2. Provide number of hinges and locks as follows:
a. Less Than 12 Inches (300 mm) Square: Secure with two sash locks.
b. Up to 18 Inches (450 mm) Square: Two hinges and two sash locks.
c. Up to 24 by 48 Inches (600 by 1200 mm): Three hinges and two
compression latches with outside and inside handles.
d. Sizes 24 by 48 Inches (600 by 1200 mm) and Larger: One additional
hinge.
C. Door: Double wall, duct mounting, and round; fabricated of galvanized sheet metal with
insulation fill and 1-inch (25-mm) thickness. Include cam latches.
1. Frame: Galvanized sheet steel, with spin-in notched frame.
D. Pressure Relief Access Door: wall and duct mounting; fabricated of galvanized sheet
metal with insulation fill and thickness as indicated for duct pressure class. Include
vision panel where indicated, latches, and retaining chain.
1. Frame: Galvanized sheet steel, with bend-over tabs and foam gaskets.
KEO/19-3262-0000 23 3300/7 Air Duct Accessories
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
E. Seal around frame attachment to duct and door to frame with neoprene or foam rubber.
B. Metal-Edged Connectors: Factory fabricated with a fabric strip 5-3/4 inches (146 mm)
wide attached to two strips of 2-3/4-inch- (70-mm-) wide, 0.028-inch- (0.7-mm-) thick,
galvanized sheet steel or 0.032-inch- (0.8-mm-) thick aluminum sheets. Select metal
compatible with ducts.
C. Indoor System, Flexible Connector Fabric: Glass fabric double coated with neoprene.
1. Minimum Weight: 26 oz./sq. yd. (880 g/sq. m).
2. Tensile Strength: 480 lbf/inch (84 N/mm) in the warp and 360 lbf/inch (63 N/mm)
in the filling.
3. Service Temperature: Minus 40 to plus 200 deg F (Minus 40 to plus 93 deg C).
D. Outdoor System, Flexible Connector Fabric: Glass fabric double coated with
weatherproof, synthetic rubber resistant to UV rays and ozone.
1. Minimum Weight: 24 oz./sq. yd. (810 g/sq. m).
2. Tensile Strength: 530 lbf/inch (93 N/mm) in the warp and 440 lbf/inch (77 N/mm)
in the filling.
3. Service Temperature: Minus 50 to plus 250 deg F (Minus 45 to plus 121 deg C).
I. Insulated-Duct Connectors: UL 181, Class 1, aluminum laminate and polyester film with
latex adhesive supported by helically wound, spring-steel wire; fibrous-glass insulation;
polyethylene or aluminized vapor barrier film.
1. Pressure Rating: 10-inch wg (2500 Pa) positive and 1.0-inch wg (250 Pa)
negative.
2. Maximum Air Velocity: 4000 fpm (20.3 m/s).
3. Temperature Range: Minus 20 to plus 210 deg F (Minus 28 to plus 99 deg C).
K. Flexible Duct Clamps: Stainless-steel band with cadmium-plated hex screw to tighten
band with a worm-gear action, in sizes 3 through 18 inches (75 to 450 mm) to suit duct
size.
A. Instrument Test Holes: Cast iron or cast aluminum to suit duct material, including screw
cap and gasket. Size to allow insertion of pitot tube and other testing instruments and of
length to suit duct insulation thickness.
B. Adhesives: High strength, quick setting, neoprene based, waterproof, and resistant to
gasoline and grease.
PART 3 - EXECUTION
C. Install backdraft dampers on exhaust fans or exhaust ducts nearest to outside and
where indicated.
D. Install volume dampers in ducts with liner; avoid damage to and erosion of duct liner.
E. Provide balancing dampers at points on supply, return, and exhaust systems where
branches lead from larger ducts as required for air balancing. Install at a minimum of
two duct widths from branch takeoff.
F. Provide test holes at fan inlets and outlets and elsewhere as indicated.
G. Install fire and smoke dampers, with fusible links, according to manufacturer's UL-
approved written instructions.
H. Install duct silencers independent of ducts with flexible duct connectors, lagged with
loaded vinyl sheet on inlets and outlets.
I. Install duct access doors to allow for inspecting, adjusting, and maintaining accessories
and terminal units as follows:
1. On both sides of duct coils.
2. Downstream from volume dampers, turning vanes, and equipment.
3. Adjacent to fire or smoke dampers, providing access to reset or reinstall fusible
links.
L. Install the following sizes for duct-mounting, pressure relief access doors:
1. One-Hand or Inspection Access: 7 inches (175 mm) in diameter.
2. Two-Hand Access: 10 inches (250 mm) in diameter.
3. Head and Hand Access: 13 inches (330 mm) in diameter.
4. Head and Shoulders Access: 19 inches (480 mm) in diameter.
M. Label access doors according to Division 23 Section "Identification for HVAC Piping and
Equipment."
O. For fans developing static pressures of 5-inch wg (1250 Pa) and higher, cover flexible
connectors with loaded vinyl sheet held in place with metal straps.
P. Connect terminal units to supply ducts directly or with maximum 12-inch (300-mm)
lengths of flexible duct. Do not use flexible ducts to change directions.
Q. Connect diffusers or light troffer boots to low pressure ducts directly or with maximum
60-inch (1500-mm) lengths of flexible duct clamped or strapped in place.
R. Connect flexible ducts to metal ducts with liquid adhesive plus tape or adhesive plus
sheet metal screws.
S. Install duct test holes where indicated and required for testing and balancing purposes.
3.02 ADJUSTING
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 RELATED SECTION: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
A. Section 23 0548 – Vibration and Seismic Control. Of HVAC Piping and Equipment.
1.03 REFERENCES
D. AMCA 301 - Method of Calculating Fan Sound Rating from Laboratory Test
1.05 SUBMITTALS
A. Product Data: Include rated capacities, furnished specialties, and accessories for each
type of product indicated and include the following:
1. Certified fan performance curves with system operating conditions indicated.
2. Certified fan sound-power ratings.
3. Motor ratings and electrical characteristics, plus motor and electrical accessories.
4. Material thickness and finishes, including color charts.
5. Dampers, including housings, linkages, and operators.
6. Fan speed controllers.
B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads,
required clearances, method of field assembly, components, and location and size of
each field connection.
1. Wiring Diagrams: Power, signal, and control wiring.
2. Design Calculations: Calculate requirements for selecting vibration isolators and
seismic restraints and for designing vibration isolation bases.
3. Vibration Isolation Base Details: Detail fabrication, including anchorages and
attachments to structure and to supported equipment. Include auxiliary motor
slides and rails, and base weights.
C. Coordination Drawings: Show fan room layout and relationships between components
and adjacent structural and mechanical elements. Show support locations, type of
support, and weight on each support. Indicate and certify field measurements.
E. Operation and Maintenance Data: For axial fans to include in emergency, operation,
and maintenance manuals.
B. AMCA Compliance: Products shall comply with performance requirements and shall be
licensed to use the AMCA-Certified Ratings Seal.
C. NEMA Compliance: Motors and electrical accessories shall comply with NEMA
standards.
B. Disassemble and reassemble units, as required for moving to final locations, according
to manufacturer's written instructions.
C. Lift and support units with manufacturer's designated lifting or supporting points.
1.08 COORDINATION
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
1. Belts: One set(s) for each belt-driven unit.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 GENERAL
D. Fans for out door installation shall be weather protected and provided with anticorrosion
paint.
E. Fans used for kitchen exhaust shall be inline bifurcated type complete with grease trap
and drain connection.
F. Static - pressures given in the equipment Schedules are only for guidance. The
Contractor should submit static pressure calculations for all fans for approval before
ordering the equipment’s. The Contractor should give the required fan and motor h.p.
Without additional cost. The contractor may propose lower motor hp as per the
calculations and as approved.
A. Description: Fan wheel and housing, factory-mounted motor with belt drive or direct
drive, an inlet cone section, and accessories.
F. Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1. Service Factor Based on Fan Motor Size (as per NEMA): 1.2
2. Fan Shaft: Turned, ground, and polished steel designed to operate at no more
than 70 percent of first critical speed at top of fan's speed range.
3. Fan Pulleys: Cast iron with split, tapered bushing; dynamically balanced at
factory.
4. Motor Pulleys: Adjustable pitch for use with motors through 5 hp; fixed pitch for
use with larger motors. Select pulley so pitch adjustment is at the middle of
adjustment range at fan design conditions.
5. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt
drives.
6. Belt Guards: Fabricate of steel for motors mounted on outside of fan cabinet.
7. Motor Mount: Adjustable base.
8. Shaft Bearings: Radial, self-aligning ball or roller bearings.
a. Ball-Bearing Rating Life: ABMA 9, L10 of 100,000 hours.
b. Roller-Bearing Rating Life: ABMA 11, L10 of 100,000 hours.
c. Extend lubrication lines to outside of casing and terminate with grease
fittings.
G. Accessories:
1. Companion Flanges: Rolled flanges of same material as housing.
2. Inspection Door: Bolted door allowing limited access to internal parts of fan, of
same material as housing.
3. Propeller Access Section Door: Short duct section bolted to fan inlet and outlet
allowing access to internal parts of fan for inspection and cleaning, of same
material as housing.
4. Swingout Construction: Assembly allowing entire fan section to swing out from
duct for cleaning and servicing, of same material as housing.
5. Mounting Clips: Horizontal ceiling or Vertical mounting clips welded to fan
housing, of same material as housing.
I. Factory Finishes:
1. Sheet Metal Parts: Prime coat before final assembly.
2. Exterior Surfaces: Baked-enamel finish coat after assembly.
3. Coatings: Epoxy Zinc or Synthetic resin Color-match enamel or Hot-dip
galvanized Powder-baked enamel.
a. Apply to finished housings.
b. Apply to fan wheels.
A. Description: Fan wheel and housing, straightening vane section, factory-mounted motor
with belt drive or direct drive, an inlet cone section, and accessories.
1. Variable-Pitch Fans: Internally mounted pneumatic electric electronic actuator,
externally mounted positive positioner, and mechanical-blade-pitch indicator.
E. Wheel Assemblies: Cast-aluminum hub assembly, machined and fitted with threaded
bearing wells to receive blade-bearing assemblies with replaceable, cast-aluminum
blades; factory mounted and balanced.
F. Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1. Service Factor Based on Fan Motor Size (as per NEMA): 1.2
2. Fan Shaft: Turned, ground, and polished steel designed to operate at no more
than 70 percent of first critical speed at top of fan's speed range.
3. Fan Pulleys: Cast iron with split, tapered bushing; dynamically balanced at
factory.
4. Motor Pulleys: Adjustable pitch for use with motors through 5 hp; fixed pitch for
use with larger motors. Select pulley so pitch adjustment is at the middle of
adjustment range at fan design conditions.
5. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt
drives.
6. Belt Guards: Fabricate of steel for motors mounted on outside of fan cabinet.
7. Motor Mount: Adjustable base.
8. Shaft Bearings: Radial, self-aligning ball or roller bearings.
a. Ball-Bearing Rating Life: ABMA 9, L10 of 100,000 hours.
b. Roller-Bearing Rating Life: ABMA 11, L10 of 100,000 hours.
c. Extend lubrication lines to outside of casing and terminate with grease
fittings.
G. Accessories:
1. Companion Flanges: Rolled flanges of same material as housing.
2. Inspection Door: Bolted door allowing limited access to internal parts of fan, of
same material as housing.
3. Propeller Access Section Door: Short duct section bolted to fan inlet outlet inlet
and outlet allowing access to internal parts of fan for inspection and cleaning, of
same material as housing.
4. Swingout Construction: Assembly allowing entire fan section to swing out from
duct for cleaning and servicing, of same material as housing.
5. Mounting Clips: Horizontal ceiling Vertical mounting clips welded to fan housing,
of same material as housing.
6. Horizontal Support: Pair of supports bolted to fan housing, of same material as
housing.
7. Vertical Support: Short duct section with welded brackets bolted to fan housing,
of same material as housing.
8. Inlet and Outlet Screens: Wire-mesh screen on fans not connected to ductwork
of same material as housing.
9. Backdraft Dampers: Butterfly style, for mounting with flexible connection to the
discharge of fan or direct mounted to the discharge diffuser section of same
material as housing.
10. Stall Alarm Probe: Sensing probe capable of detecting fan operation in stall and
signaling control devices. Control devices and sequence of operation are
specified in Division 23 Sections "Instrumentation and Control for HVAC" and
"Sequence of Operations for HVAC Controls."
11. Flow Measurement Port: Pressure measurement taps installed in the inlet of fan
to detect and signal airflow readings to temperature-control systems. Control
devices and sequence of operation are specified in Division 23 Sections
KEO/19-3262-0000 23 3413/6 Axial Hvac Fans
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
"Instrumentation and Control for HVAC" and "Sequence of Operations for HVAC
Controls."
12. Shaft Seal: Elastomeric seal and Teflon wear plate, suitable for up to300 deg F
(148 deg C).
13. Motor Cover: Cover with side vents to dissipate motor heat, of same material as
housing.
14. Inlet Vanes: Adjustable; with peripheral control linkage operated from outside of
airstream, bronze sleeve bearings on each end of vane support, and provision for
manual or automatic operation of same material as housing.
15. Inlet Bell: Curved inlet for when fan is not attached to duct, of same material as
housing.
16. Inlet Cones: Round-to-round transition of same material as housing.
17. Outlet Cones: Round-to-round transition of same material as housing.
18. Stack Cap: Vertical discharge assembly with backdraft dampers, of same
material as housing.
I. Factory Finishes:
1. Sheet Metal Parts: Prime coat before final assembly.
2. Exterior Surfaces: Baked-enamel finish coat after assembly.
3. Coatings: Epoxy or Synthetic resin Color-match enamel Hot-dip galvanized or
Powder-baked enamel.
a. Apply to finished housings.
b. Apply to fan wheels.
A. Description: Fan wheel and housing, straightening vane section, factory-mounted motor
with belt drive, and accessories.
D. Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1. Service Factor Based on Fan Motor Size (as per NEMA): 1.2
2. Fan Shaft: Turned, ground, and polished steel designed to operate at no more
than 70 percent of first critical speed at top of fan's speed range.
KEO/19-3262-0000 23 3413/7 Axial Hvac Fans
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Fan Pulleys: Cast iron with split, tapered bushing; dynamically balanced at
factory.
4. Motor Pulleys: Adjustable pitch for use with motors through 5 hp; fixed pitch for
use with larger motors. Select pulley so pitch adjustment is at the middle of
adjustment range at fan design conditions.
5. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt
drives.
6. Motor Mount: Adjustable base.
7. Shaft Bearings: Radial, self-aligning ball or roller bearings.
a. Ball-Bearing Rating Life: ABMA 9, L10 of 100,000 hours.
b. Roller-Bearing Rating Life: ABMA 11, L10 of 100,000 hours.
c. Extend lubrication lines to outside of casing and terminate with grease
fittings.
E. Accessories:
1. Mounting Clips: Horizontal ceiling or Vertical mounting clips welded to fan
housing, of same material as housing.
2. Inlet and Outlet Screens: Wire-mesh screen on fans not connected to ductwork
of same material as housing.
3. Backdraft Dampers: Butterfly style, for mounting with flexible connection to the
discharge of fan or direct mounted to the discharge diffuser section of same
material as housing.
4. Motor Cover: Cover with side vents to dissipate motor heat, of same material as
housing.
5. Inlet Bell: Curved inlet for when fan is not attached to duct, of same material as
housing.
6. Inlet Cones: Round-to-round transition of same material as housing.
7. Outlet Cones: Round-to-round transition of same material as housing.
8. Stack Cap: Vertical discharge assembly with backdraft dampers, of same
material as housing.
G. Factory Finishes:
1. Sheet Metal Parts: Prime coat before final assembly.
2. Exterior Surfaces: Baked-enamel finish coat after assembly.
3. Coatings: Epoxy or Synthetic resin or Color-match enamel or Hot-dip galvanized
Powder-baked enamel.
a. Apply to finished housings.
b. Apply to fan wheels.
B. Construction: Casings shall be heavy gauge, mild sheet steel, roll formed and welded,
then hot dipped galvanized to BS 729. Hubs shall be die cast aluminum alloy. Fan shall
be complete with adjustable pitch aerofoil impellers with blades pressure die cast
aluminum alloy or polyester powder coated steel.
C. Motor: Motors shall be foot mounted totally enclosed metric type to IP55, with sealed for
life bearings, standard industrial paint finish and Class H insulation to BS 4999 Part 20,
IEC 34/1, suitable for operating at high temperatures, motors are to be wired using high
temperature rated weatherproofed cable to an IP55 protected terminal box mounted on
the outside of the unit casing.
D. Units are to be designed and manufactured with procedures as defined in BSEN ISO
9001: 1994. EEC Directives shall be met. Motor shall be tested for high temperature
operation in accordance with BS 7346 (Part 2) and PR EN 12101-3.
E. Performance: Fan unit is tested to either National or European draft standards. Smoke
extract axial fans shall be tested to ISO 5801 (1997) – Airside Performance, and BS 848
Part 2 (1985) – Sound level performance.
A. All window or wall mounted extract fans shall be suitable for Kuwait outdoor conditions.
They shall be provided with outside baffles for protection against weather. Fans shall be
completely enclosed designed with draft proof automatic electrically operated shutters.
A. Sound-Power Level Ratings: Comply with AMCA 301, "Methods for Calculating Fan
Sound Ratings from Laboratory Test Data." Factory test fans according to AMCA 300,
"Reverberant Room Method for Sound Testing of Fans." Label fans with the AMCA-
Certified Ratings Seal.
B. Fan Performance Ratings: Establish flow rate, pressure, power, air density, speed of
rotation, and efficiency by factory tests and ratings according to AMCA 210, "Laboratory
Methods of Testing Fans for Rating."
PART 3 - EXECUTION
3.01 INSTALLATION
B. Support floor-mounting units using spring isolators or restrained spring isolators having
a static deflection of 1 inch (25 mm). Vibration- and seismic-control devices are
specified in Division 23 Section "Vibration and Seismic Controls for HVAC Piping and
Equipment."
1. Secure vibration and seismic controls to concrete bases using anchor bolts cast
in concrete base.
E. Support suspended units from structure using threaded steel rods and spring hangers
with vertical-limit stops having a static deflection of 1 inch (25 mm). Vibration-control
devices are specified in Division 23 Section "Vibration and Seismic Controls for HVAC
Piping and Equipment."
3.02 CONNECTIONS
A. Duct installation and connection requirements are specified in other Division 23 Section-
23 3113. Drawings indicate general arrangement of ducts and duct accessories. Make
final duct connections with flexible connectors. Flexible connectors are specified in
Section 23 3300 "Air Duct Accessories."
A. Perform the following field tests and inspections and prepare test reports:
1. Verify that shipping, blocking, and bracing are removed.
2. Verify that unit is secure on mountings and supporting devices and that
connections to ducts and electrical components are complete. Verify that proper
thermal-overload protection is installed in motors, starters, and disconnect
switches.
3. Verify that cleaning and adjusting are complete.
4. Disconnect fan drive from motor, verify proper motor rotation direction, and verify
fan wheel free rotation and smooth bearing operation. Reconnect fan drive
system, align and adjust belts, and install belt guards.
5. Adjust belt tension.
6. Adjust damper linkages for proper damper operation.
7. Verify lubrication for bearings and other moving parts.
8. Verify that manual and automatic volume control and fire and smoke dampers in
connected ductwork systems are in fully open position.
B. Test and adjust controls and safeties. Replace damaged and malfunctioning controls
and equipment.
3.04 ADJUSTING
C. Lubricate bearings.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Section Includes:
1. High-Plume Dilution Laboratory Exhaust Fans
B. Related Sections:
1. All sections, drawing plans, specifications and contract documents.
1.02 REFERENCES
B. ANSI/AMCA Standard 204-05, "Balance Quality and Vibration Levels for Fans"
D. AMCA Publication 211-05, "Certified Ratings Program – Product Rating Manual for Fan
Air Performance"
E. AMCA Standard 260-07, "Laboratory Methods of Testing Induced Flow Fans for Rating"
F. ANSI/AMCA Standard 300-08, "Reverberant Room Method for Sound Testing of Fans"
G. AMCA Publication 311-05, "Certified Ratings Program – Product Rating Manual for Fan
Sound Performance"
P. OSHA guideline 1926.300 – General requirements for safe operation and maintenance
of hand and power tools. (www.osha.gov)
1.03 SUBMITTALS
A. Provide dimensional drawings and product data on each high-plume dilution laboratory
exhaust fan assembly.
B. Provide fan curves for each fan at the specified operation point, with the flow, static
pressure and horsepower clearly plotted.
C. Provide nozzle velocity of exhaust fan, total exhaust flow, and discharge plume rise at
specified wind velocity.
A. Performance ratings: Conform to ANSI/AMCA Standards 210, 260 and 300. Fans must
be tested in accordance with AMCA Publications 211, 260 and 311 in an AMCA
accredited laboratory and certified for air and sound performance. Fan shall be licensed
to bear the AMCA ratings seal for air performance (AMCA 210), sound performance
(AMCA 300), and induced flow fan for high plume dilution blowers (AMCA 260).
Manufacturers that are not licensed to bear the AMCA 210 and 260 ratings seal, must
provide performance witness testing (at the manufacturer's expense), per paragraph
1.4.D.
C. Each fan shall be vibration tested before shipping, as an assembly, in accordance with
ANSI/AMCA Standard 204. Each assembled fan shall be test run at the factory at the
specified fan RPM and vibration signatures shall be taken on each bearing in three
planes - horizontal, vertical, and axial. The maximum allowable fan vibration shall be
less than 0.10 in. /sec peak velocity; filter-in reading as measured at the fan RPM. This
report shall be provided at no charge to the customer upon request.
D. Manufacturers that do not comply with paragraph 1.4.A must also provide, at the owner
and engineer's option and manufacturer's expense, witness testing of fan discharge and
entrainment airflow, performed in an AMCA accredited laboratory, in accordance with
AMCA 210 and 260. This test shall verify the critical and safety related dilution
performance of the high plume dilution blower, as stated by the manufacturer.
B. Store materials in a dry area indoor, protected from damage, and in accordance with
manufacturer’s instructions. For long term storage, follow manufacturer’s Installation,
Operation and Maintenance manual.
C. Handle and lift fans in accordance with the manufacturer’s instructions. Protect materials
and finishes during handling and installation to prevent damage. Follow all safety
warnings posted by the manufacturer.
A. Do not operate fans for any purpose until ductwork is clean, filters are in place,
bearings have been lubricated, and fan has been test run under observation.
1.07 WARRANTY
A. Provide two year manufacturer warranty from the date of substantial completion.
B. Refer to the “General Requirements and Scope of Works” for additional warranty
requirements.
1.08 SPARES
B. Contractor shall provide all required spares as specified in the “General Requirements
and Scope of Works”.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 GENERAL
B. Fans shall be selected to deliver the required air volume flow rate and meet the noise
levels indicated.
D. All fan resistances stated have been calculated based on a particular selection of
equipment. The installer shall recalculate the total system resistances based on
E. Similarly, if the fan power requirements and sound power level changes, the installer
shall reselect the necessary motor size, wiring and suitable attenuation to achieve the
noise levels stated elsewhere at no additional cost.
F. The installer shall ensure that the fan is capable of generating sufficient pressure to
meet the required volume flow in the ductwork system as installed including any effect
on fan performance from suction and discharge connections.
G. Fan resistances shall take account of pressure drop across filters in dirty conditions.
H. Individual components shall, in addition to the requirements of this section, comply with
other relevant sections of this specification.
I. Manufacturing drawings shall be submitted to the Engineer of all fans for approval prior
to manufacture.
K. Manufacturer’s test certificates, acoustic data and fan curves shall be submitted to the
Engineer. Fan curves shall indicate performance under all likely operating conditions.
M. Externally mounted fans and internal exposed surfaces on fans handling outside air
shall be protected against corrosion.
N. Fans and drives shall be resiliently mounted. Mountings and supports shall be arranged
to prevent undue movement of fans relative to adjacent ductwork systems or building
structure.
P. All fans shall be capable of operating at ambient temperatures of 50 degree Celsius and
the casing material shall be able to withstand sun radiation temperature up to 85 degree
Celsius.
Q. All fans used for life safety operations or hazardous operations shall be subject to Civil
Defense Department approval.
S. Fans selected shall be capable of accommodating static pressure and flow variations of
+/- 15% of scheduled values.
W. Curb cap shall be hot rolled steel [316 stainless steel] coated with corrosion resistant
coating.
X. Fan assemblies that use flexible connectors that can fail and cause loss of laboratory
containment shall not be acceptable.
Y. Fan assembly shall be designed for a minimum of 125-mph wind loading, without the
use of guy wires.
Z. Motor cover shall be hinged with removable side panels for ease of maintenance to
allow the servicing of the motor and drive.
A. All fan and system components (fan, nozzle, windband and plenum) shall be corrosion
resistant coated with LabCoat™, a two part electrostatically applied and baked,
sustainable, corrosion resistant coating system. Standard finish color to be RAL 7023,
concrete grey.
B. All parts shall be cleaned and chemically prepared for coating using a multi-stage wash
system which includes acid pickling that removes oxide, increases surface area, and
improves coating bond to the substrate.
C. The first powder coat applied over the prepared surface shall be a zinc rich epoxy
primer (no less than 70% zinc) and heated to a gelatinous consistency (partial cure) at
which the second powder coat of polyester resin shall be electrostatically applied and
simultaneously be cured at a uniform temperature of 400°F.
E. Note that 10-20 mil thick wet coating systems pollute the environment (air and water),
and that these manually applied coatings are not uniform over the impeller surface and
can cause fan imbalance and vibration.
B. Fan housing shall be bifurcated, allowing all drive components, including the motor, to
be serviced without contact of the contaminated airstream. Must be manufactured of
welded steel and meet specification section 2.15 for corrosion resistant coating. No
uncoated metal fan parts will be acceptable.
C. Fan housings that are fabricated of polypropylene or fiberglass that have lower
mechanical properties than steel, have rough interior surfaces in which corrosive,
hazardous compounds can collect, and / or which chalk and structurally degrade due to
the UV component of the sunlight shall not be acceptable.
KEO/19-3262-0000 23 3413.13/5 High Plume Dilution Laboratory Exhaust Fan
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
D. A multi-stage air induction discharge nozzle shall be supplied by the fan manufacturer
be designed to efficiently handle an outlet velocity of up to 7000 FPM. The multi-stage
nozzle shall induce ambient air up to 270% of fan capacity. Nozzle / windband
assemblies that are manufactured by third party vendors or that are fabricated of plastic
or resins, having mechanical properties less than steel shall not be acceptable.
E. An integral fan housing drain shall be used to drain rainwater when the fan is de-
energized.
G. Fan assembly shall be AMCA type C spark resistant construction minimum or as noted
on the schedule.
A. Fan impeller shall be mixed flow design with non-stall characteristics. The impeller shall
be electronically balanced both statically and dynamically exceeding AMCA Standards.
B. Fan impeller shall be manufactured of welded and coated steel. Reference specification
clause 2,03 for corrosion resistant coating.
C. Fan impellers that are fabricated of polypropylene or fiberglass that have lower
mechanical properties than steel and lower maximum tip speeds are not acceptable.
D. Vacuum Seal: Fan impeller shall include a secondary fan blade located on the impeller
back plate. This secondary impeller shall create a negative pressure at the shaft
opening; preventing hazardous or toxic exhaust fumes from escaping through the
housing shaft opening. Mechanical shaft seals that wear out and need to be replaced or
seal systems that use hoses or tubes that can leak, are not acceptable.
A. For constant volume systems, the fan / nozzle assembly shall be connected directly to
roof curb and exhaust duct without the need of the bypass air plenum. Fans mounted
directly to roof curb shall be provided with a damper tray located in the roof curb for
mounting of the gravity isolation damper.
B. For variable volume systems, a bypass air plenum shall be provided. The plenum shall
be provided with bypass air damper(s) for introducing outside air at roof level upstream
of the fan, complete with bypass air weatherhood and bird screen.
C. The plenum shall be constructed of welded and coated steel and meet specification
clause 2,03 for corrosion resistant coating. Plenums that are fabricated of plastics or
resins that are combustible and have mechanical properties less than steel shall not be
acceptable.
D. The bypass air plenum shall be mounted on factory fabricated roof curb provided by the
fan manufacturer, as shown on the project drawings (See section 2.5).
E. Fan designs that use inlet flexible connectors that can leak causing loss of lab exhaust
shall not be permitted.
G. If stated in the schedule notes, an optional, integral bypass air packed acoustic
attenuator fabricated of stainless steel construction shall be provided by the fan
manufacturer (if shown on the drawings).
H. Fan isolation damper(s), shall be parallel-blade design, airfoil design, fabricated of steel
[304 stainless steel construction] for structural rigidity as standard. Damper(s) shall be
coated up to 4 mils of chemically resistant Hi-Pro Polyester resin, electrostatically
applied and baked. Isolation damper(s) shall have plated steel damper rods (if specified
as 304 stainless steel damper, stainless steel damper rods will be provided), stainless
steel sleeved bearings, 301 stainless steel jamb seals and the blades shall have
polymer edge seals. Damper model shall be equal to or exceed a heavy duty control
damper, Greenheck HCD-130. Damper blade drive linkage shall be set by manufacturer
and welded to eliminate linkage slippage. All damper access and service (drive
actuators) shall be performed outside of the contaminated airstream.
I. Isolation damper actuator(s), if scheduled shall be factory mounted and shall be wired to
a step-down transformer. Actuator and transformer are located in a weatherproof
enclosure.
J. Blower / Plenum vibration isolation shall be limited to neoprene / cork vibration pads.
A. Exhaust system manufacturer shall supply a structural support curb for the plenum of
specified height as shown on the drawings.
D. When properly anchored to the roof structure, the standard curb / plenum / blower
assembly shall withstand wind loads of up to 125 mph without additional structural
support.
A. Motors shall be premium efficiency, standard NEMA frame, 1800 or 3600 RPM, TEFC
with a 1.15 service factor. A factory-mounted NEMA 4X disconnect switch shall be
provided for each fan.
C. Drive belts and sheaves shall be sized for 200% of the fan operating brake horsepower,
and shall be readily and easily accessible for service, if required. Drive shall consist of a
minimum of two belts under all circumstances.
D. Fan shaft to be turned and polished of 1040 steel material [316 stainless steel] as
standard, coated with corrosion resistant coating.
E. Fan shaft bearings shall be Air Handling Quality, ball or roller pillow block type and be
sized for an
F. L-10 life of no less than 200,000 hours. Bearings shall be fixed to the fan shaft using
concentric mounting locking collars, which reduce vibration, increase service life, and
improve serviceability. Bearings that use setscrews shall not be acceptable.
G. All shaft bearings and non-permanently lubricated motors shall have stainless steel
braided extended lube lines with Zerk fittings.
H. Belt drive motors shall have ventilated motor cover. Motor cover shall be hinged with
removable side panels for ease of maintenance to allow the servicing of the motor and
drive(s).
2.09 FANS WITH AIR FLOW MONITORING SELECTED SHALL INCLUDE THE
FOLLOWING
A. Flow monitoring station shall monitor the pressure difference between the fan inlet and
the smallest diameter of the inlet cone.
C. Flow monitoring station shall not use air restricting flow devices that reduce fan
performance or create additional fan sound.
D. Two (2) equidistantly spaced sensor orifices to be drilled in the smallest diameter of the
inlet cone venturi. Flow tubes from each venturi sensor shall be extended to a
termination location mounted on the fan housing.
E. High-pressure flow port(s) shall be mounted in low velocity fan inlet. Flow ports from the
high-pressure sensor shall extend to a termination location mounted on the fan housing.
G. Flow monitoring station shall accurately measure the pressure differential to within +/-
3%.
H. Flow monitoring station to be installed by the fan manufacturer as part of the standard
fan assembly.
I. Flow monitoring station to be supplied with electronics package that includes pressure
transmitter and LCD digital readout.
K. Tubing: black polyethylene, UV resistant, chemically inert tubing, interior and exterior
(standard), Temperature range: -100 - 175°F (-73 - 80°C)
L. Tube Fittings: Stainless steel compression fittings, interior. Brass compression fittings,
exterior
2.010 FANS WITH A FAN MONITORING SYSTEM SELECTED SHALL INCLUDE THE
FOLLOWING
C. Bearing Vibration: Used to detect and monitor vibration on fan shaft bearing(s) or motor
bearing.
1. Velocity vibration sensor, corrosion resistant stainless steel casing
2. Temperature Range: -40 to 185°F (-40 to 85°C)
3. Input Voltage: 10 VDC minimum, 30 VDC maximum
4. Output Signal: 4-20 mA
5. Accuracy: 5% transverse sensitivity, ±2% repeatability
6. Each kit includes sensor unit, base and cable.
D. Fan monitor programmed with fault setting for alarm and IO for trend analysis indicating
bearing condition.
G. Bearing Temperature: Used to detect and monitor temperature on fan shaft bearings.
1. J type thermocouple terminal ring with wiring
2. Push button temperature transmitter with LED for visual sensor fault and
programming mode
3. NEMA 4X (IP 66) transmitter mounting enclosure
4. Temperature Range:
a. Temperature Terminal Ring: 32 to 482°F (0 to 250°C)
b. Transmitter: -4 to 158°F (-20 to 70°C)
5. Input Voltage: 24 VDC
6. Output Signal: 4-20 mA
7. Accuracy: ±0.9°F (±0.5°C)
H. Fan monitor programmed with fault setting for alarm and IO for trend analysis indicating
future bearing health and real-time temperature status reading.
J. Fan monitor to provide fault setting for alarm exceeding maximum limit, actual run time
and maintenance for fan bearing lubrication, motor lubrication and belt replacement.
L. Fan monitor to provide a system fault for high and/or low temperature and active status
reading.
PART 3 - EXECUTION
3.01 INSTALLATION
C. Install flexible connections specified in Section 23 3300 between axial fan inlet and
discharge ductwork. Ensure metal bands of connectors are parallel with minimum 25
mm flex between ductwork and axial fan while running.
H. Provide access to adjustable blade axial fan wheels for varying blade angle setting.
Adjust blades for varying range of volume and pressure.
I. Provide floor mounted axial fans with reinforced legs. Provide ceiling suspended units
with support brackets bolted to casing flange.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 RELATED SECTION: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
A. Section 23 0548 – Vibration and Seismic Control. Of HVAC Piping and Equipment.
1.03 REFERENCES
D. AMCA 301 - Method of Calculating Fan Sound Rating from Laboratory Test
1.05 SUBMITTALS
A. Product Data: Include rated capacities, furnished specialties, and accessories for each
type of product indicated and include the following:
1. Certified fan performance curves with system operating conditions indicated.
2. Certified fan sound-power ratings.
3. Motor ratings and electrical characteristics, plus motor and electrical accessories.
4. Material thickness and finishes, including color charts.
5. Dampers, including housings, linkages, and operators.
B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads,
required clearances, method of field assembly, components, and location and size of
each field connection.
1. Wiring Diagrams: Power, signal, and control wiring.
2. Design Calculations: Calculate requirements for selecting vibration isolators and
seismic restraints and for designing vibration isolation bases.
3. Vibration Isolation Base Details: Detail fabrication, including anchorages and
attachments to structure and to supported equipment. Include auxiliary motor
slides and rails, and base weights.
C. Coordination Drawings: Show fan room layout and relationships between components
and adjacent structural and mechanical elements. Show support locations, type of
support, and weight on each support. Indicate and certify field measurements.
B. AMCA Compliance: Products shall comply with performance requirements and shall be
licensed to use the AMCA-Certified Ratings Seal.
C. NEMA Compliance: Motors and electrical accessories shall comply with NEMA 1.
C. Lift and support units with manufacturer's designated lifting or supporting points.
1.08 COORDINATION
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
1. Belts: One set(s) for each belt-driven unit.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
B. Housings: Formed panels to make curved-scroll housings with shaped cutoff, with
doors or panels to allow access to internal parts and components.
1. Panel Bracing: Steel angle- or channel-iron member supports for mounting and
supporting fan scroll, wheel, motor, and accessories.
2. Horizontally split, bolted-flange housing.
3. Spun inlet cone with flange.
4. Outlet flange.
D. Shafts: Statically and dynamically balanced and selected for continuous operation at
maximum rated fan speed and motor horsepower, with final alignment and belt
adjustment made after installation.
1. Turned, ground, and polished hot-rolled steel with keyway. Ship with protective
coating of lubricating oil.
2. Designed to operate at no more than 70 percent of first critical speed at top of
fan's speed range.
H. Belt Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1. Service Factor Based on Fan Motor Size: 1.5
2. Fan Pulleys: Cast iron or cast steel with split, tapered bushing; dynamically
balanced at factory.
3. Motor Pulleys: Adjustable pitch for use with motors through 5 hp ; fixed pitch for
use with larger motors. Select pulley so pitch adjustment is at the middle of
adjustment range at fan design conditions.
4. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt
drives.
5. Belt Guards: Fabricate to comply with OSHA and SMACNA requirements of
diamond-mesh wire screen welded to steel angle frame or equivalent, prime
coated. Secure to fan or fan supports without short circuiting vibration isolation.
Include provisions for adjustment of belt tension, lubrication, and use of
tachometer with guard in place.
6. Motor Mount: Adjustable for belt tensioning.
I. Accessories:
1. Scroll Access Doors: Shaped to conform to scroll, with quick-opening latches
and gaskets.
2. Cleanout Door: Quick-opening, latch-type gasketed door allowing access to fan
scroll, of same material as housing.
3. Scroll Drain Connection: NPS 1 (DN 25) steel pipe coupling welded to low point
of fan scroll.
4. Companion Flanges: Rolled flanges for duct connections of same material as
housing.
5. Variable Inlet Vanes: With blades supported at both ends with two permanently
lubricated bearings of same material as housing. Variable mechanism
terminating in single control lever with control shaft for double-width fans.
6. Discharge Dampers: Assembly with parallel or opposed blades constructed of
two plates formed around and to shaft, channel frame, and sealed ball bearings;
with blades linked outside of airstream to single control lever of same material as
housing.
7. Inlet Screens: Grid screen of same material as housing.
8. Shaft Cooler: Metal disk between bearings and fan wheel, designed to dissipate
heat from shaft.
9. Spark-Resistant Construction: AMCA 99.
10. Shaft Seals: Airtight seals installed around shaft on drive side of single-width
fans.
11. Weather Cover: Enameled-steel sheet with ventilation slots, bolted to housing.
KEO/19-3262-0000 23 3416/4 Centrifugal Hvac Fans
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
J. Motors: Comply with requirements in Division 23 Section "Common Motor
Requirements for HVAC Equipment."
1. Enclosure Type: Totally enclosed, fan cooled.
B. Housings: Formed panels to make curved-scroll housings with shaped cutoff; with
doors or panels to allow access to internal parts and components.
1. Panel Bracing: Steel angle- or channel-iron member supports for mounting and
supporting fan scroll, wheel, motor, and accessories.
2. Horizontally split, bolted-flange housing.
3. Spun inlet cone with flange.
4. Outlet flange.
D. Shafts: Statically and dynamically balanced and selected for continuous operation at
maximum rated fan speed and motor horsepower, with final alignment and belt
adjustment made after installation.
1. Turned, ground, and polished hot-rolled steel with keyway. Ship with a protective
coating of lubricating oil.
2. Designed to operate at no more than 70 percent of first critical speed at top of
fan's speed range.
H. Belt Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1. Service Factor Based on Fan Motor Size: 1.5.
2. Fan Pulleys: Cast iron or cast steel with split, tapered bushing; dynamically
balanced at factory.
I. Accessories:
1. Scroll Access Doors: Shaped to conform to scroll, with quick-opening latches
and gaskets.
2. Cleanout Door: Quick-opening, latch-type gasketed door allowing access to fan
scroll, of same material as housing.
3. Scroll Drain Connection: NPS 1 (DN 25) steel pipe coupling welded to low point
of fan scroll.
4. Companion Flanges: Rolled flanges for duct connections of same material as
housing.
5. Variable Inlet Vanes: With blades supported at both ends with two permanently
lubricated bearings of same material as housing. Variable mechanism
terminating in single control lever with control shaft for double-width fans.
6. Discharge Dampers: Assembly with parallel or opposed blades constructed of
two plates formed around and to shaft, channel frame, and sealed ball bearings;
with blades linked outside of airstream to single control lever of same material as
housing.
7. Inlet Screens: Grid screen of same material as housing.
8. Shaft Cooler: Metal disk between bearings and fan wheel, designed to dissipate
heat from shaft.
9. Spark-Resistant Construction: AMCA 99.
10. Shaft Seals: Airtight seals installed around shaft on drive side of single-width
fans.
11. Weather Cover: Enameled-steel sheet with ventilation slots, bolted to housing.
B. Housings: Formed panels to make curved-scroll housings with shaped cutoff; with
doors or panels to allow access to internal parts and components.
1. Panel Bracing: Steel angle- or channel-iron member supports for mounting and
supporting fan scroll, wheel, motor, and accessories.
2. Horizontally split, bolted-flange housing.
3. Spun inlet cone with flange.
KEO/19-3262-0000 23 3416/6 Centrifugal Hvac Fans
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4. Outlet flange.
D. Shafts: Statically and dynamically balanced and selected for continuous operation at
maximum rated fan speed and motor horsepower, with final alignment and belt
adjustment made after installation.
1. Turned, ground, and polished hot-rolled steel with keyway. Ship with protective
coating of lubricating oil.
2. Designed to operate at no more than 70 percent of first critical speed at top of
fan's speed range.
H. Belt Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1. Service Factor Based on Fan Motor Size: 1.5.
2. Fan Pulleys: Cast iron or cast steel with split, tapered bushing; dynamically
balanced at factory.
3. Motor Pulleys: Adjustable pitch for use with motors through 5 hp; fixed pitch for
use with larger motors. Select pulley so pitch adjustment is at the middle of
adjustment range at fan design conditions.
4. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt
drives.
5. Belt Guards: Fabricate to comply with OSHA and SMACNA requirements of
diamond-mesh wire screen welded to steel angle frame or equivalent, prime
coated. Secure to fan or fan supports without short circuiting vibration isolation.
Include provisions for adjustment of belt tension, lubrication, and use of
tachometer with guard in place.
6. Motor Mount: Adjustable for belt tensioning.
I. Accessories:
1. Scroll Access Doors: Shaped to conform to scroll, with quick-opening latches
and gaskets.
2. Cleanout Door: Bolted Quick-opening, latch-type gasketed door allowing access
to fan scroll, of same material as housing.
3. Scroll Drain Connection: NPS 1 (DN 25) steel pipe coupling welded to low point
of fan scroll.
4. Companion Flanges: Rolled flanges for duct connections of same material as
housing.
KEO/19-3262-0000 23 3416/7 Centrifugal Hvac Fans
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
5. Variable Inlet Vanes: With blades supported at both ends with two permanently
lubricated bearings of same material as housing. Variable mechanism
terminating in single control lever with control shaft for double-width fans.
6. Discharge Dampers: Assembly with parallel opposed blades constructed of two
plates formed around and to shaft, channel frame, and sealed ball bearings; with
blades linked outside of airstream to single control lever of same material as
housing.
7. Inlet Screens: Grid screen of same material as housing.
8. Shaft Cooler: Metal disk between bearings and fan wheel, designed to dissipate
heat from shaft.
9. Spark-Resistant Construction: AMCA 99.
10. Shaft Seals: Airtight seals installed around shaft on drive side of single-width
fans.
11. Weather Cover: Enameled-steel sheet with ventilation slots, bolted to housing.
C. Shafts: Statically and dynamically balanced and selected for continuous operation at
maximum rated fan speed and motor horsepower, with final alignment and belt
adjustment made after installation.
1. Turned, ground, and polished hot-rolled steel with keyway. Ship with protective
coating of lubricating oil.
2. Designed to operate at no more than 70 percent of first critical speed at top of
fan's speed range.
H. Accessories:
1. Shaft Cooler: Metal disk between bearings and fan wheel, designed to dissipate
heat from shaft.
2. Spark-Resistant Construction: AMCA 99.
3. Shaft Seals: Airtight seals installed around shaft on drive side of single-width
fans.
C. Shafts: Statically and dynamically balanced and selected for continuous operation at
maximum rated fan speed and motor horsepower, with final alignment and belt
adjustment made after installation.
1. Turned, ground, and polished hot-rolled steel with keyway. Ship with protective
coating of lubricating oil.
2. Designed to operate at no more than 70 percent of first critical speed at top of
fan's speed range.
G. Belt Drives: Factory mounted, with final alignment and belt adjustment made after
installation.
1. Service Factor Based on Fan Motor Size: 1.5
2. Fan Pulleys: Cast iron or cast steel with split, tapered bushing; dynamically
balanced at factory.
3. Motor Pulleys: Adjustable pitch for use with motors through 5 hp; fixed pitch for
use with larger motors. Select pulley so pitch adjustment is at the middle of
adjustment range at fan design conditions.
4. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt
drives.
5. Belt Guards: Fabricate to comply with OSHA and SMACNA requirements of
diamond-mesh wire screen welded to steel angle frame or equivalent, prime
coated. Secure to fan or fan supports without short circuiting vibration isolation.
Include provisions for adjustment of belt tension, lubrication, and use of
tachometer with guard in place.
6. Motor Mount: Adjustable for belt tensioning.
H. Accessories:
1. Shaft Cooler: Metal disk between bearings and fan wheel, designed to dissipate
heat from shaft.
2. Spark-Resistant Construction: AMCA 99.
3. Shaft Seals: Airtight seals installed around shaft on drive side of single-width
fans.
A. Sound-Power Level Ratings: Comply with AMCA 301, "Methods for Calculating Fan
Sound Ratings from Laboratory Test Data." Factory test fans according to AMCA 300,
"Reverberant Room Method for Sound Testing of Fans." Label fans with the AMCA-
Certified Ratings Seal.
B. Fan Performance Ratings: Establish flow rate, pressure, power, air density, speed of
rotation, and efficiency by factory tests and ratings according to AMCA 210, "Laboratory
Methods of Testing Fans for Rating."
D. Fans for outdoor installation shall be weather protected and provided with anticorrosion
paint.
E. Fans used for kitchen exhaust shall be inline bifurcated type complete with grease trap
and drain connection. Motor and / or drive shall be outside of the air stream. Fan shall
be rated for higher temperature as appropriate
F. Static - pressures given in the equipment Schedules are only for guidance. The
Contractor should submit static pressure calculations for all fans for approval before
ordering the equipment’s. The Contractor should give the required fan and motor hp.
Without additional cost. The contractor may propose lower motor hp as per the
calculations and as approved.
G. Contractor shall select fans for low noise application and shall provide all necessary
measures such as provision of sound attenuators, Acoustic enclosures, acoustic lining
to limit sound to acceptable noise levels as indicated in Section 23 0100 & Acoustic
report. Contractor shall submit noise calculations for the selected fan and
attenuators/and or acoustic enclosures for the approval prior to ordering the equipment.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Do not operate fans for any purpose until ductwork is clean, filters are in place, bearings
lubricated, and fan has been test run under observation.
C. Install flexible connections specified in Section 23 3343 between fan inlet and discharge
ductwork. Ensure metal bands of connectors are parallel with minimum on inch (25mm)
flex between ductwork and fan while running. Flexible connections shall not be used for
fans used for smoke exhaust applications.
H. For all fans (normal/smoke vent fans) provide fan starter switch in the space served by
the fan and location of starter switch to be as indicated on shop drawing or as approved.
Make necessary interconnections with light switch.
KEO/19-3262-0000 23 3416/11 Centrifugal Hvac Fans
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
I. Install centrifugal fans level and plumb.
J. Support floor-mounting units using restrained spring isolators having a static deflection
of 1 inch (25 mm). Vibration- and seismic-control devices are specified in Division 23
Section "Vibration and Seismic Controls for HVAC Piping and Equipment."
1. Secure vibration and seismic controls to concrete bases using anchor bolts cast
in concrete base.
M. Support suspended units from structure using threaded steel rods and spring hangers
spring hangers with vertical-limit stops having a static deflection of 1 inch (25 mm).
Vibration-control devices are specified in Division 23 Section "Vibration and Seismic
Controls for HVAC Piping and Equipment."
3.02 CONNECTIONS
A. Perform the following field tests and inspections and prepare test reports:
1. Verify that shipping, blocking, and bracing are removed.
2. Verify that unit is secure on mountings and supporting devices and that
connections to ducts and electrical components are complete. Verify that proper
thermal-overload protection is installed in motors, starters, and disconnect
switches.
3. Verify that cleaning and adjusting are complete.
4. Disconnect fan drive from motor, verify proper motor rotation direction, and verify
fan wheel free rotation and smooth bearing operation. Reconnect fan drive
system, align and adjust belts, and install belt guards.
5. Adjust belt tension.
6. Adjust damper linkages for proper damper operation.
7. Verify lubrication for bearings and other moving parts.
8. Verify that manual and automatic volume control and fire and smoke dampers in
connected ductwork systems are in fully open position.
9. Refer to Division 23 Section "Testing, Adjusting, and Balancing for HVAC" for
testing, adjusting, and balancing procedures.
KEO/19-3262-0000 23 3416/12 Centrifugal Hvac Fans
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
10. Remove and replace malfunctioning units and retest as specified above.
B. Test and adjust controls and safeties. Replace damaged and malfunctioning controls
and equipment.
3.04 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
1.02 SUBMITTALS
A. Product Data: For each type of product indicated, include rated capacities, furnished
specialties, sound-power ratings, and accessories.
C. Coordination Drawings: Reflected ceiling plans, drawn to scale, on which the following
items are shown and coordinated with each other, based on input from installers of the
items involved:
1. Ceiling suspension assembly members.
2. Method of attaching hangers to building structure.
3. Size and location of initial access modules for acoustical tile.
4. Ceiling-mounted items including lighting fixtures, diffusers, grilles, speakers,
sprinklers, access panels, and special moldings.
D. Operation and Maintenance Data: For air terminal units to include in emergency,
operation, and maintenance manuals. In addition to items specified in Division 01
Section "Operation and Maintenance Data" include the following:
1. Instructions for resetting minimum and maximum air volumes.
2. Instructions for adjusting software set points.
A. Product Options: Drawings indicate size, profiles, and dimensional requirements of air
terminal units and are based on the specific system indicated. Refer to Division 01
Section "Product Requirements."
C. NFPA Compliance: Install air terminal units according to NFPA 90A, "Standard for the
Installation of Air Conditioning and Ventilating Systems."
1.04 COORDINATION
A. Coordinate layout and installation of air terminal units and suspension system with other
construction that penetrates ceilings or is supported by them, including light fixtures,
HVAC equipment, fire-suppression system, and partition assemblies.
B. Following spare parts shall be furnished properly packed and labelled with equipment
no. / location.
1. 6 Nos. of Damper actuator / motor for each type and size.
2. 6 Nos. of Air Flow Transducers for each type and size.
3. Four (4) sets of VAV units complete with controller for each type and size.
4. Two (2) sets of Air Valves for each type and size.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Configuration: Damber assembly inside unit casing with control components located
inside a protective metal shroud.
B. Casing: Minimum 22-gauge galvanized steel. Internally lined with high density
fiberglass insulation which complies with UL 181 and NFPA 90A.
C. Casing Lining: 1/2-inch- (13-mm-) thick, coated, high density duct liner complying with
ASTM C 1071; secured with adhesive.
1. Air Inlet: Round stub connection for duct attachment.
2. Air Outlet: S-slip and drive connections.
3. Access: Removable panels for access to diverter and other parts requiring
service, adjustment, or maintenance; with airtight gasket.
D. Damper: Damper Assembly shall be made of heavy gauge galvanized steel blades,
mounted in self-lubricating bearings; designed for uniform airflow over the whole face at
all flows. Seals shall be attached to the blades, to ensure tight closure.
KEO/19-3262-0000 23 3600/2 Air Terminal Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
E. Erosion Prevention: All exposed insulation edges shall be coated with NFPA 90A
approved sealant to prevent entrainment of fibers in the air stream.
F. The VAV / CAV box shall be with low pressure drop design.
G. Sound Rating of the VAV / CAV box shall be within the rating permitted for the area
served, whether the bypass is fully closed or fully open.
H. Pressure independent, DDC controlled, single duct, variable air volume boxes. The
capacity of each VAV / CAV box is indicated on the Drawings while the schedule
indicates a group of VAV / CAV boxes falling under a selected nominal L/S rating. VAV /
CAV boxes shall be capable of maintaining +/- 5% of the rated air flow in up to 1500 Pa
(6 IWG) pressure.
I. VAV boxes shall reset between minimum and maximum L/S from a room thermostat
without changing orifices or other parts. L/S limiters are not acceptable. DDC
controllers shall be also calibrated and set for the minimum and maximum scheduled air
flow rates.
J. VAV Units shall be suitable for change over function. The control action of the VAV
DDC Controller shall be reversed when the AHU is in the heating mode. Provide
necessary provision for morning warm-up interface with BAS.
K. Electrical and control components shall be situated in a protective enclosure. Fit each
DDC controller with a terminal board on which all field connections are made. Label all
terminals clearly. Provide for field calibration, readjustment volt free contact for remote
control and alarm.
L. Actuator: Shall be electric type suitable for 24 volt power supply and capable of
supplying a minimum torque of 35 in/lb to the damper shaft to exert positive force in both
the opening and closing directions. Actuator shall be easily accessible for maintenance,
without disturbing ductwork. Actuators shall be direct shaft mount type without linkage.
M. Actuators shall be non-spring return type and shall exert positive force in both the
opening and closing directions. Include in each actuators a built in limit to interrupt the
current to the actuator at the constant stroke limit in each direction. Each actuator shall
be energized only when the controller signals change in damper position.
N. Multi-point air flow sensors independent of duct air temperature shall be supplied for
accurate control of air flow.
P. Individual room sensor / thermostat with digital display shall be provided to control VAV
box (es).
Q. Provide sound attenuators built–in VAV boxes, if the noise levels of VAV boxes found to
be exceeding the set limits.
S. Multioutlet Attenuator Section: With two, three or four 6-inch- (150-mm-), 8-inch- (200-
mm-) or 10-inch- (250-mm-) diameter collars; each with locking butterfly balancing
damper.
A. Configuration: Volume control damper assembly inside unit casing with control
components located inside a protective metal shroud.
B. Casing: Minimum 22-gauge galvanized steel. Internally lined with high density
fiberglass insulation which complies with UL 181 and NFPA 90A.
1. Casing Lining: 1-inch- (25-mm-) thick, coated, fibrous-glass duct liner complying
with ASTM C 1071; secured with adhesive. Cover liner with nonporous foil and
perforated metal.
2. Casing Lining: Adhesive attached, 3/4-inch- (19-mm-) thick, polyurethane foam
insulation complying with UL 181 erosion requirements, and having a maximum
flame-spread index of 25 and a maximum smoke-developed index of 50, for both
insulation and adhesive, when tested according to ASTM E 84.
3. Air Inlet: Round stub connection or S-slip and drive connections for duct
attachment.
4. Air Outlet: S-slip and drive connections, size matching inlet size.
5. Access: Removable panels for access to dampers and other parts requiring
service, adjustment, or maintenance; with airtight gasket.
C. Volume Damper: Galvanized steel with peripheral gasket and self-lubricating bearings.
1. Maximum Damper Leakage: ARI 880 rated, 2 percent of nominal airflow at 6-
inch wg (1500-Pa) inlet static pressure.
2. Damper Position: Normally open.
E. Multioutlet Attenuator Section: With two three or four 6-inch- (150-mm-) 8-inch- (200-
mm-) or 10-inch- (250-mm-) diameter collars; each with locking butterfly balancing
damper.
F. Hot-Water Heating Coil (If applicable): Copper tube, mechanically expanded into
aluminum-plate fins; leak tested underwater to 200 psig (1380 kPa); and factory
installed.
G. Electric Heating Coil: Slip-in-type, open-coil design with integral control box factory
wired and installed. Include the following features:
1. Primary and secondary overtemperature protection.
2. Nickel chrome 80/20 heating elements.
3. Airflow switch.
4. Noninterlocking disconnect switch.
5. Fuses (for coils more than 48 A).
6. Mercury contactors.
7. Pneumatic-electric switches and relays.
8. Magnetic contactor for each step of control (for three-phase coils).
K. Control Sequence:
1. Suitable for operation with duct pressures between 0.25- and 3.0-inch wg (60-
and 750-Pa) inlet static pressure.
2. Factory-mounted and -piped, 5-micron filter; velocity-resetting, adjustable, high-
limit control; and amplifying relay.
3. System-powered, wall-mounting thermostat.
A. Construction:
1. 16 gauge spun aluminum valve body with continuous welded seam.
2. Shaft bearing surfaces: Polypropylene (PP) or Polyphenylene Sulfide (PPS).
3. Spring grade stainless steel spring and PPS slider assembly.
4. Supply valves insulated with 3/8" (9.5 mm) flexible closed-cell polymer-based
foam. Flame/smoke rating 25/50. Density is 1.5 lb/ft3 (24.0 kg/m3).
5. Seal wheel material: Polypropylene.
B. Operating Range
1. 32-122 °F (0-50 °C) ambient.
2. 10-90% non-condensing RH
C. Performance
1. Pressure independent over a 0.3"-3.0" WC (75-750 Pa) drop across valve.
2. Volume control accurate to ±10% of airflow command signal.
3. No additional straight duct runs needed before or after the valve.
B. Volume Damper: Galvanized steel with peripheral gasket and self-lubricating bearings.
1. Damper Position: Normally open.
F. Control Sequence:
1. Suitable for operation with duct pressures between 0.25- and 3.0-inch wg (60-
and 750-Pa) inlet static pressure.
2. Factory-mounted and -piped, 5-micron filter; velocity-resetting, adjustable, high-
limit control; and amplifying relay.
3. System-powered, wall-mounting thermostat.
G. Integral thermally powered actuators, sensing duct and room temperature, control
diffusion dampers.
A. Identification: Label each air terminal unit with plan room number, nominal airflow,
maximum and minimum factory-set airflows, coil type, and ARI certification seal.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Install air terminal units level and plumb. Maintain sufficient clearance for normal
service and maintenance.
B. Provide ceiling access doors or locate units above easily removable ceiling components.
C. Support unit individually from structure. Do not support from adjacent ductwork.
D. Co-ordinate VAV box locations with other services and ensure that enough space for
maintenance is available.
F. All installation, power supply, conducting and necessary wiring for VAV Units from
outgoing terminal of power point provided by electrical discipline shall be part of this
Section
G. Electrical works by this section shall include providing of central transformers which
shall serve several VAV Boxes and dampers and their interconnecting wiring.
Alternatively, each VAV box can be provided with own transformer and 240 volt power
supply.
3.02 CONNECTIONS
A. Connect ducts to air terminal units according to Division 23 Section "Metal Ducts"
KEO/19-3262-0000 23 3600/7 Air Terminal Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. Ground units with electric heating coils according to Division 26 Section "Grounding and
Bonding for Electrical Systems."
B. Perform the following field tests and inspections and prepare test reports:
1. After installing air terminal units and after electrical circuitry has been energized,
test for compliance with requirements.
2. Leak Test: After installation, fill water coils and test for leaks. Repair leaks and
retest until no leaks exist.
3. Operational Test: After electrical circuitry has been energized, start units to
confirm proper motor rotation and unit operation.
4. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
3.05 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Section Includes: Supply and installation of air outlets and inlets Ceiling and wall-
mounted diffusers, registers, and grilles.
B. Related Sections:
1. Section 23 3113: Metal Duct
2. Section 23 3114: Pre-Insulated Duct
3. Section 23 3300: Air Duct Accessories
1.02 SUBMITTALS
A. Supply and install air outlets and inlets compliance in accordanceGrilles, diffusers,
registers, louvers etc. shall be constructed from extruded aluminum, unless mentioned
otherwise elsewhere.
KEO/19-3262-0000 23 3713/1 Diffusers, Registers And Grilles
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. Grilles, diffusers, registers, etc. are to be furnished with a factory finish to a color
specified by the interior designer.
C. Decorative grille for the fresh air makeup shall be coordinated and approved by interior
designer.
D. Regulatory Requirements
1. ADC Test Code: Test and rate air outlets and inlets in certified laboratory under
the requirements of Air Diffusion Council (ADC) Equipment Test Code 1062
“Certification, Rating and Test Manual”.
2. ANSI / NFPA Standards: Install air outlets and inlets in accordance with National
Fire Protection Association (NFPA) Standard 90A “Installation of Air Conditioning
and Ventilating Systems”.
B. Store outlets and inlets in original cartons and protect from weather and construction
work traffic. Where possible, store indoors; when necessary to store outdoors, store
above grade and enclose with waterproof wrapping.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
B. Performance: Provide ceiling air diffusers that have, as minimum, temperature and
velocity traverses, throw and drop, static pressure drop and noise criteria ratings for
each size device as listed in manufacturer’s current data.
C. Ceiling Compatibility: Provide diffusers with border styles that are compatible with
adjacent ceiling systems and that are specifically manufactured to fit into ceiling module
with accurate fit and adequate support.
D. Types: Provide ceiling diffusers of type, capacity and with accessories as listed on
diffuser schedule.
E. Diffusers shall be square or rectangular suitable for ceiling installation and ductwork
application as shown on project drawings. They shall be provided with rubber gasket or
foam tape at the outer edge of the frame to produce a positive air seal at the mounting
KEO/19-3262-0000 23 3713/2 Diffusers, Registers And Grilles
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
surface. They shall be produced with removable core and provided with equalizing grids.
Faceplates shall be furnished with concealed hinges and clips. Duct collars connecting
duct of diffuser shall be airtight and not interfere with the volume control damper.
F. Supply air diffuser shall be equipped with opposed blade volume damper adjustable
from the face of the diffuser without removing the core.
A. Provide linear diffusers with internal damper vanes, adjustable from face of diffuser
without removing or disturbing installation. These variable vanes shall provide 180
degree discharge pattern, left, right or vertical adjustable in each slot.
B. Connect diffuser frame to acoustically lined plenum. Connect plenum to supply duct or
supply branch takeoff with flexible duct. Provide damper at takeoff from supply branch
duct.
C. Where continuous strips are required, provide strip diffusers with blank off covers for
dummy diffusers.
D. Where linear diffusers are used for return air, the appearance from the room shall be
identical to supply diffusers.
C. Wall/Floor Compatibility: Provide registers and grilles with border styles that are
compatible with adjacent wall/ floor systems, and that are specifically manufactured to fit
into wall/floor construction with accurate fit and adequate support.
D. Types: Provide registers, grilles and perforated floor panels of type, capacity, and with
accessories as listed on register and grille schedule or as shown on drawings.
E. They shall be furnished with sponge rubber gaskets or foam tape behind the frame to
eliminate air leakage and with nylon bushings or PVC at the blades connection to the
frame to eliminate corrosion and vibration. Free cross-sectional area shall be at least 65
percent.
F. Supply air registers shall have individually adjustable horizontal front blades and vertical
rear blades.
H. Return and exhaust air registers and grilles shall have fixed single deflection blades set
at an angle 35º.
I. Return and exhaust air registers shall be with key operated, opposed blade volume
control damper.
J. All opposed blade volume control dampers shall be polyester coated even baked with
black color finish.
K. Provide perforated floor tiles specially designed for computer centre floor system.
Provide volume damper operated from the face of floor tile. Limit discharge velocity to
300 FPM.
A. Continues 1/8-inch face bars with 1/2 (half) inch centers and 0 or 15 deg. core deflection
to satisfy needed throw.
C. Provide frame with face screw mounting holes or with steel snap-in friction springs as
required per application. Frames shall be provided also with gasket to prevent air
leakage. Heavy duty mounting frame shall be provided for floor / sill application.
D. Provide Registers/Grilles with galvanised steel sheet plenum as required, internally lined
with ½ inch thick acoustic insulation. Circular spigots are provided and fitted with
volume control dampers.
A. Continues ¾ inch width slot/s with adjustable control vanes and volume control
dampers. It shall be fully adjustable from the face of the diffuser, to any horizontal,
vertical or any intermediate setting of air flow pattern to satisfy needed throw.
C. Provide concealed mounting brackets fit in a hemmed duct collar or frame to positively
hold the diffuser in ceiling or sidewall installations.
D. Provide diffusers with galvanized steel sheet plenum as required, internally lined with 1
(one) inch thick acoustic insulation. Circular spigots are provided and fitted with volume
control dampers.
2.07 FLOW BAR DIFFUSERS: (LINEAR AND MODULAR SLOT DIFFUSERS) (If Applicable)
B. Provide all continuous linear slot and modular slot diffusers as shown on the drawings.
The slot diffusers shall integrate into the ceiling system. Where curved linear slot
diffusers are indicated, they shall be stretched formed to the exact radii required. Rolled
or segmented linear slot diffusers will not be accepted.
C. The linear slot diffusers shall have a single slot unless shown otherwise and shall be
capable of being used for supply air, return air, exhaust air or any combination.
D. The linear slot diffusers shall be capable of supporting the ceiling system. Linear
diffusers supported by screws in the flanges or from air plenums are unacceptable. For
lay-in ceiling, provide hanger wire support clips that are integral with the linear slot
diffusers allowing the linear slot diffusers to be supported from the building structure with
ceiling wire. For hard ceilings, provide clips that are integral with the linear slot diffusers
allowing the diffusers to be secured directly to the ceiling framing without the
requirement for hanger supports. Provide spline clips to secure joints and ceiling tees to
the diffusers.
E. Provide ends and corners as required. Ends shall be butt type, field installed, or mitered
picture frame type factory installed, as indicated herein or shown on the drawings.
Corners shall be mitered one-piece unit.
G. Material shall be minimum wall thickness 0.062 inches extruded aluminum. Spring steel
retainers shall be used under the spacers to hold the slot diffusers assembly tightly
together and allow the slot diffusers to be disassembled easily for field trimming.
Materials other than extruded aluminum and spring steel will not be accepted.
H. Flanges exposed to view shall be painted factory standard white. All other surfaces shall
be painted flat black. Provide paint samples if requested.
I. All slot diffusers shall be manufactured by the same manufacturer of the plenums and
hoods. No exceptions shall be allowed. Plenum lengths and entry collar sizes shall be
as indicated on the plan schedules.
J. Plenums shall be minimum 24-gauge galvanized steel and lined inside with black matte
fiberglass insulation. Hoods shall be 51 percent free area and constructed of 24-gauge
perforated sheet metal painted flat black.
L. Air test and balance of linear and modular slot diffusers systems shall be by this section
and be in accordance with the testing and balancing portion section of the
specifications. Position all Flow Bar pattern controllers in their normal operation
positions and perform all air testing and balancing of all slot diffuser systems in full
accordance with manufacturer’s recommendations.
M. All slot diffusers shall be performance tested with air plenums as a composite assembly
in full accordance with ASHRAE, and/or ARI standards. If requested, the contractor shall
provide for a visit by the mechanical consulting engineer to the product testing
laboratory to verify performance data and testing procedures. All cost associated thereto
shall be provided at the expense of the contractor.
N. Diffusers shall be selected to achieve a throw to room length ratio which meets the
requirements of the ASHRAE 2001 Fundamentals Handbook, Chapter 32, Table 4, at
both maximum design flow rate, and for VAV systems, at the minimum flow rate
expected during partial occupancy. Diffusers shall be selected to achieve a minimum of
70 percent ADPI over the range of expected loads in the space. The diffusers’ reported
performance shall be based on tests conducted in accordance with ASHRAE Standard
70–2006. ADPI performance on at least one-unit size of the selected diffuser shall have
been tested in accordance with ASHRAE Standard 113–1990, to validate conformance
and applicability to the ASHRAE table.
A. Circular disc valves, suitable for supply and extract air, comprising valve ring with
peripheral seal, central disc with threaded spindle and locknut and installation sub frame
with volume flow rate adjustment by rotating the central disc.
B. Face sections sheet steel with electrostatic powder coating, galvanised steel threaded
spindle and lock nut, installation sub frame galvanised sheet steel.
A. Jet nozzles suitable for long throw distances with optimum acoustic properties,
preferably used for heating and cooling in critical areas. The adjustment facility –
manual or automatic via internal or externally mounted electric actuation – allows
variation in discharge angle to compensate for changing temperature differences,
adjustment angular range 30° upwards to 30° downwards. The manually adjustable
version can also be rotated through 360°.
B. The fixed jet nozzle consists of an aerodynamically shaped discharge nozzle deep-
drawn in one piece, with fixing holes. Adjustable construction consists of a discharge
nozzle with spherical outlet mounted in housing, a mounting flange and in a circular duct
rear connection spigot for direct connection to a circular duct. Also available with rear-
mounted duct connecting element with peripheral flange and optional spigot or saddle
connection with flange for fixing to the side of rectangular or circular ducts; the rear
contour of the saddle connection is profiled to the duct diameter.
D. The surface shall be pre-treated, and powder coated in white (RAL 9010) or another
RAL color to suit the architectural finishes (the spigots remain galvanised finish)
A. It shall consist of two closely spaced grilles with connection collar. The grille shall have
fixed deflection blades set at an angle 35 degrees and parallel to long dimension with
mounting frame. The free area of the transfer grille shall not be less than 65% of the
total face area.
A. The frame shall be separate from the blades by an extruded rigid PVC track whish shall
be an integral part of the frame. The blades shall be of V-shapes, mounted in the PVC
track and spaced 12.5 mm on centers
A. The displacement flow units consist of a casing with a perforated metal face plate (for
one-directional discharge) or additional perforated metal side plates (for three directional
discharge), a rectangular spigot located either on top or at the bottom of the unit as
required, and an internal perforated plate basket for even air distribution.
B. Casing, perforated face plate and perforated sheet steel basket are made of galvanised
sheet steel.
C. Casing and perforated plates are pre-treated, and powder coated white RAL 9010, gloss
level 50 %, any other or another RAL color to suit the architectural finishes. The rear
surface to the casing and the perforated sheet steel basket are coated black RAL 9005
PART 3 - EXECUTION
3.01 GENERAL
A. Provide all grilles, registers or diffusers which are suitable for installation in the ceiling,
wall or floor finishes. Provide all required accessories to facilitate installation.
B. Provide all air distribution devices from one manufacturer unless otherwise noted.
3.02 INSPECTION
A. Examine areas and conditions under which outlets and inlets are to be installed. Do not
proceed with work until unsatisfactory conditions have been corrected.
3.03 INSTALLATION
B. Provide an internally lined supply air plenum for all linear grilles, bar grilles and slot
diffusers. The lining shall be 1-inch thick minimum.
C. Coordinate with other work, including ductwork and duct accessories, as necessary to
interface installation of outlets and inlets with other work.
D. Locate ceiling air diffusers, registers, and grilles, as indicated on general construction
“Reflected Ceiling Plans”. Unless otherwise indicated, locate units in center of
acoustical ceiling modules.
E. Install perforated floor panels after full coordination with computer equipment contractor
and as approved by the Engineer’s Representative.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes factory-fabricated air-filter devices and media used to remove
particulate matter from air for HVAC applications.
1.02 DEFINITIONS
D. Section Includes: Factory Fabricated Air Filters devices and media used to remove
particulate matter from air for HVAC applications. Work includes but is not limited to the
following:
1. Pre-filter
2. Final Filter
3. Grease Filter
4. Carbon Filter
5. Air Cleaners
6. Sand Trap Louvers
E. Related Section:
1. Section 23 7313 – Modular Indoor and outdoor Central – Station Air –
Handling Units.
2. Section 23 8123 – Computer – Room Air – Conditioners
3. Section 23 8126 – Split- System Air – Conditioners.
4. Section 23 8216 – Air Coils.
5. Section 23 8219 – Fan Coil Units
1.03 SUBMITTALS
B. Shop Drawings: Include plans, elevations, sections, and details to illustrate component
assemblies and attachments.
C. Operation and Maintenance Data: For each type of filter and rack to include in
emergency, operation, and maintenance manuals.
A. Product Options: Drawings indicate size, profiles, and dimensional requirements of air
filters and are based on the specific system indicated. Refer to Division 01 Section
"Product Requirements."
D. Comply with ASHRAE 52.1 and ASHRAE 52.2 (MERV) for method of testing and rating
air-filter units.
I. Regulatory Requirements
1. NFPA Compliance: Comply with applicable portions of ANSI / NFPA 90A and
90B.
2. UL Compliance: Comply with UL Standards pertaining to safety and performance
of air filter units.
3. ASHRAE Compliance: Comply with provisions of ASHRAE Standard 52-76 for
method of testing including a weight test and a dust spot test and require that
values for both be reported (MERV) minimum efficiency reporting values for air
cleaner particle size efficiency and for recording and calculating air flow rates.
4. ARI Compliance: Comply with Section 7.4 of ARI Standard 850-78 for
performance tolerances.
5. DIN-EN 779, EIN-EN 1822 for manufacturing, filters classes, and testing of
coarse dust (pre-filters), fine filters and HEPA filters.
6. AFI: Air Filter Institute.
7. NIST: National Institute of Standard and Technology.
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 MATERIALS
A. General:
1. The task of air filters in HVAC systems is not only to protect the ventilated rooms
from too severe a level of contamination but also the HVAC system itself. This is
guaranteed by the use of pre-filters, fine filters of filter classes as specified. Filter
grades are measured in according with ASHRAE standards, filter classes in
accordance with DIN-EN 779 and EUROVENT 4/5.
2. Filters Classification:
a. Pre-filters : G1 to G4 according to DIN-EN 779
EU1 to EU4 according to EUTOVENT 4/5
b. Final filters : F5 to F9 according to DIN-EN 779
EU5 to EU9 according to EUTOVENT 4/5
c. High efficiency particulate
air filters : H10 to H14 according to DIN-EN 1822
d. Ultra low penetration air
filters : U15 to U17 according to DIN-EN 1822
3. The pressure loss of a filter section loaded with duct shall not exceed the values
given in Table-1. Lower final pressure drops can be also specified where
appropriate.
The final pressure drops tabulated in Table-1 are typical maximum values for air-
handling units in operation and lower than those used in EN 779 for classification
purposes, for reasons of energy saving, and the performance obtained from tests
according to EN 779 are not necessarily met at these lower pressure drops.
B. Pre-filters:
1. Replaceable (Throw away) Panel Filters: Provide factory-fabricated, viscous-
coated, flat panel type replaceable air filters with holding frames; where shown, in
sizes indicated, with 50mm (2”) thick UL Class 2 throwaway media material;
construct media of interlaced glass fibers, spray with non-flammable adhesive,
frame in throwaway fiberboard casings, and sandwich between perforated metal
grills. Construct ductwork-holding frames of 20 gage galvanised steel, capable of
holding media and media frame in place, and gasketed to prevent unfiltered air
by-passing between media frames and holding members. Provide filters with
rated face velocity of 76 metres per minute (250 fpm), initial resistance of not
greater than 8mm (0.30”) w.g., final rated resistance of 13mm (0.60”) w.g., and
average arrestance of 80%.
2. Cleanable (Washable) Panel Filters: Provide factory fabricated, flat panel type
cleanable air filters with holding frames; where shown, in sizes indicated, with
50mm (2”) thick cleanable filtering media constructed of galvanized woven and
crimped steel screening; with 20 gage galvanized steel frame. Construct
ductwork-holding frames of 18 gage galvanized steel and capable of holding
media and media frame in place, and gasketed to prevent unfiltered air by-
passing between media frames and holding members. Provide cleanable filters
with rated face velocity of 90 metres per minute (300 fpm), initial resistance not
KEO/19-3262-0000 23 4100/4 Particulate Air Filtration
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
greater than 2.5mm (0.10”) w.g., final rated resistance of 13mm (0.60”) w.g., and
average arrestance of 75%.
3. Foam Filter:
a. Cleanable (washable) panel filters: Provide factory fabricated, flat (zig
zag folded) panel type cleanable air filters with frame, cleanable filtering
media constructed of polyurethane foam on polyether basis in controlled
porosities, filter class G4 as indicated, with aluminium frame.
b. Filter media easily removable from frame for changing or washing
purposes: Provide cleanable filters with rated face velocity between 300 –
350 fpm initial differential pressure according to filter class and
dimensions as indicated.
C. Final Filters
1. Bag Type Filters: Provide factory-fabricated, dry, extended surface pocket type
filters with holding frames where shown, in sizes indicated. Construct media
from ultrafine glass fibers. Divide each pocket into six tubes by sealed stitch
lines running the entire length of the pocket. Construct holding frames of 16
gage galvanized steel 100mm (4”) in depth and provide suitable fasteners and
gasketing to hold media and media frame and to prevent unfiltered air passing
between media frames and holding devices. Supply frames with heavy duty
rotary spring latches that hold the header against the gaskets with force. Provide
a single piece steel header that channels the air directly into each tube through
countered openings in the header. Attach each tube individually to flanges on
the air leaving side of the header with high strength epoxy glue. Design holding
frames which are suitable for bolting together into built-up filter banks. Provide
filters with rated velocity of 152 metres per minute (500 fpm), initial resistance of
10mm (0.40”) w.g. with 90-95% dustspot efficiency, and final rated average
resistance of 25mm (1.0”) w.g.
2. Extended Surface Self-Supporting Filters: Provide factory-fabricated, dry,
extended surface self-supporting filters with holding frame; where indicated.
Equip with UL Class I fibrous media material constructed so that individual pleats
are maintained in tapered form by flexible internal supports under rated airflow
conditions. Construct holding frames of 18 gage galvanized steel and provide
suitable fasteners and gasketing to hold filter units and to prevent unfiltered air
passing between media frames and holding devices. Design holding frames
which are suitable for bolting together into built-up filter banks. Provide filters
with rated face velocity of 76 metres per minute (250 fpm), initial resistance of
6mm (0.25”) w.g. with 90-95% efficiency, and final rated resistance of 25mm
(1.0”) w.g.
D. Very high-efficiency dry filters, HEPA (high-efficiency particulate air) filers, and ULPA
(ultra low-penetration air) filters are made in an extended-surface configuration of deep
space folds of submicrometre glass fiber paper. These filters operate at duct velocities
near 250 fpm, with resistance rising from 0.5 to more than 2.0 in. of water over their
services lift. These filters are the standard for cleanroom, nuclear, and toxic-particulate
applications.
A. At the Contractor’s option select either of the two following frame types. Provide any
necessary empty sections, upstream, downstream and/or side access.
1. Front and Rear Access Filter Frames: Provide filter bank framing system,
constructed of aluminium framing members having minimum thickness of 23mm
(0.90”). Design system for either upstream (front) or downstream (rear) filter
servicing. Cut to size and pre-punch members for easy assembly into modules
of size and capacity as scheduled or noted on the Drawings. Provide
permanently gasketed framing members to prevent bypass of unfiltered air. If
vertical support members are required to prevent deflection of horizontal
members, install so as not to interfere with either installation or operation of
filters. Incorporate separate track for prefilters, removable from front, or
removable from back after removal of after-filters. Provide factory-installed
positive sealing device for each row of filters, to insure seal between gasketed
filter elements. Provide hardware necessary for field assembly.
2. Side Servicing Housings: Provide factory-assembled side servicing housings
with flanges for insertion into ductwork system as indicated. Construct of 16
gage galvanized steel. Provide integral pre-filter tracks to accommodate 50mm
(2”) throw away or cleanable filters. Provide access doors with continuous
gasketing on perimeter and positive locking devices. Incorporate positive-sealing
gasket material on channels to seal top and bottom of filter cartridge frames to
prevent bypass. Arrange so filter cartridges can be loaded from either access
door.
KEO/19-3262-0000 23 4100/6 Particulate Air Filtration
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2.04 FILTER GAGES
A. Provide magnetic dial type gauge for each filter bank, with logarithmic curve tube gage,
with integral levelling gage, graduated to read from 0mm to 75mm (0” to 3”) w.g.
1. Provide pressure tips, tubing, gage connections, and mounting bracket.
B. Ecology unit shall be from the ISO 9001, EMS 14001 & OHSAS 18001 on quality
management, the occupational health and safety management system & the
environmental management Certified Company and have the experience of at least 5
Yrs. of continuously engaged in manufacturing.
C. Ecology unit shall be ETL Listed Conforming to UL STD 710 ( Exhaust Hoods for
Commercial Cooking Equipment )
D. FILTERATION SECTIONS:
1. First Stage of filtration system shall include:
Air is drawn by the blower through a washable metal mesh pre-filter & Bag Filter which
traps large dust particles. The remaining particles, some as small as 0.01 microns, pass
into a strong electrical field (ionizing section) where the particulate receives an electrical
charge. The charged particles then pass into a collector plate section made up of a
series of equally spaced parallel plates. Each alternate plate is charged with the same
polarity as the particles, which repel, while the interleaving plates are grounded, which
attract and collect. This section should have following features: -
• Solid State Power Supply
• Spiked Ionizing Blades
• Extra Depth Collector Cells
• Electrical Component Box Mounted out of Air Stream
• Self Glazing Ceramic Insulators: Out of Airstream; Impervious to Liquids; Provide
Operational Longevity and Power Supply Life; Easy to Clean
• Spiked Ionizer: No Ionizing Wires to Replace, Reducing Maintenance and
Replacement Cost
• High Efficiency: Up to 95% on Single Pass.
• Permanent Ionizer/Collector Elements: No Filter Replacement Cost; Just Wash,
Dry and Reinstall
• Low Pressure Drop: Lower Energy Cost to Operate Compared to Media and
Cartridge Units
E. FAN SECTION:
1. FANS:
2. Fans:
Fans, backward curved, DIDW, shall be licensed to bear the AMCA Air and
Sound Certified Ratings Seal. The test standard used shall be ANSI/AMCA
210-85, ANSI/ASHRAE Standard 51-1985 “Laboratory Method of Testing
Fans for Rating” and AMCA 300 “Reverberant Room Method for Sound
Testing of fans”.
All fans shall be dynamically trim-balanced to ISO1940 and AMCA 204/3 - G2.5
quality grade after assembly.
Fan outlet velocity shall not exceed 10 m/s and maximum fan speed shall be
1450 rpm for fan up to 450 mm dia. For fans above 450 mm dia the outlet
velocity shall be within 11.5 m/sec. and maximum fan speed shall not close to
critical speed.
3. Housing:
4. Fan Wheel:
All Ventilation Fan wheel shall be backward curved inclined non-over loading
type. Fan wheel and housing shall be statically and dynamically balanced to G2.5
quality grade.
5. Shaft:
6. Bearings:
Bearings shall be of self-alignment (concentric) type with adaptor sleeve bearing.
Bearings of eccentric locking collar with grub screw type are not acceptable.
Bearing shall be maintenance free with permanently lubricated sealed ball
bearing type. Bearing life shall be at least 75,000 hours based on basic rating
life, L10 of ISO 281 standard.
7. Motors:
Fan motor shall be suitable for 415 10% volts, 50 cycle 3 phase power supply,
squirrel cage, TEFC motor, provided with class F insulation, and of approved
make. Motor nameplate horsepower shall exceed brake horsepower by a
minimum of 10%. Motor shall be designed especially for quiet operation. The fan
and motor combination selected for the particular required performance, shall be
of the most efficient (smallest horse power), so that noise level and power
consumption are lowest.
8. Drive:
Drive to fan shall be provided through belt with adjustable motor. Belt shall be of
the oil resistant type.
Belts and pulleys shall be sized for a minimum 150% of the installed motor
horsepower. The belt speed shall not exceed 30m/s. The pulley shall be of Taper
Lock SPZ, SPA, SPB or SPC type. Conventional type of pulley is not acceptable.
9. Vibration Isolation:
GSS / MS base shall be provided for both fan & motor, built as an integral part,
and shall be mounted on a concrete foundation through vibration spring
isolators/cushy foot mountings.
F. CABINET CONSTRUCTION:
1. Filter Section Module Construction:
a. Filter Section: Pentapost design & have strong three-way angle
joints of reinforced nylon corners to form a rigid frame
structure. Rigid frame work comprises an assembly of
externally chamfered extruded aluminium profile & nylon corner
joints.
b. Inner & Outer Skin: standard pre-coated GI sheet, the double
skin (25/50 mm) is to retain the insulation surface clean & to
have a smooth surface.
c. Cabinet should be designed based on ≤2 m/s Filter across
Velocity.
9. Options:
a. Single odour control module.
b. Odour liquid low-level alarm.
c. 24-hour timer for odour control system.
d. Provide UL/ULC listed fire damper actuated by fusible link at outlet.
e. Module to be complete with four pressure switches to monitor pre-filter,
high efficiency, absolute filter and filter missing.
f. Fifth pressure switch for final monitoring (filter missing).
g. Provide terminal strip and all necessary relays and/or interlocks to remote
monitoring of all unit functions via the building’s DDC system. Provide
ability to remotely start and stop kitchen ventilation system via signal from
DDC system. Items to include at terminal strip:
1) System start/stop from DDC.
2) Filter alarm (for each filter).
H. Provide certificate of approval (air) for exhaust emissions as per local authorities.
2.06 All components meet National Building Standards, National Fire Codes, and National
Fire Protection Association (NFPA96) guidelines. They are tested, listed and labeled to
Underwriters Laboratories Standards in Canada and the USA (ULC and UL)
A. Framing System: Aluminum framing members with access for either upstream (front) or
downstream (rear) filter servicing, cut to size and prepunched for assembly into
modules. Vertically support filters prevent deflection of horizontal members without
interfering with either filter installation or operation.
C. Sealing: Factory-installed, positive-sealing device for each row of filters to ensure seal
between gasketed filter elements to prevent bypass of unfiltered air.
PART 3 - EXECUTION
3.01 INSTALLATION
B. Position each filter unit with clearance for normal service and maintenance. Anchor filter
holding frames to substrate.
E. Install filter gage static-pressure tips upstream and downstream from filters to measure
pressure drop through filter. Mount filter gages on outside of filter housing or filter
plenum in an accessible position. Adjust and level inclined gages.
3.02 CLEANING
A. After completing system installation and testing, adjusting, and balancing air-handling
and air-distribution systems, clean filter housings and install new filter media.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes, modular air-handling units with coils for indoor and outdoor
installations.
1.02 REFERENCES
C. AMCA 300 - Test Code for sound Rating Air Moving Devices.
D. AMCA 301 - Method of Publishing Sound Ratings for Air Moving Devices.
G. ANSI/AFBMA 11- Load Ratings and Fatigue Life for Roller Bearings.
KEO/19-3262-0000 23 7313/1 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
N. EN 13053 - Ventilation for Buildings – Air Handling Units – Rating and Performance for
Units, Components and Sections.
1.03 SUBMITTALS
A. Product Data: For each type of modular indoor air-handling unit indicated. Include the
following:
1. Certified fan-performance curves with system operating conditions indicated.
2. Certified fan-sound power ratings.
3. Certified coil-performance ratings with system operating conditions indicated.
4. Motor ratings, electrical characteristics, and motor and fan accessories.
5. Material gages and finishes.
6. Filters with performance characteristics.
7. Dampers, including housings, linkages, and operators.
F. Static pressures given in the A.H.U. Schedules are only for guidance. The Contractor
shall calculate the external and internal static pressures for all A.H.U.s and shall obtain
Engineer's approval before ordering the equipment’s. The Contractor should provide the
required fan and motor h.p. without additional cost
KEO/19-3262-0000 23 7313/2 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1.04 QUALITY ASSURANCE
A. Source Limitations: Obtain modular indoor air-handling units through one source from a
single manufacturer.
E. Certification: Modular indoor air-handling units and their components shall be factory
tested according to Eurovent or AHRI 430, "Central-Station Air-Handling Units," and
shall be listed and labeled by AHRI.
1.05 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
B. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These
items are specified in Division 07 Section "Roof Accessories."
B. Furnish extra materials that match products installed and as recommended by the
manufacturer, including but not limited to the following shall be furnished properly
packed and labelled with equipment no. / location to the owner:
1. Gaskets: One set for each access door.
2. Two sets of matched fan belts (V belts) for each type and size of AHU if belt
driven fans used.
3. Two set of Fan bearings of each type and size of AHU fans used in the project.
4. One set of all replaceable filters of full set for all AHUs used in the project.
5. 10 Nos. of AHU door handlers of each size and type used.
6. One no. of electrical motor for each type and size of AHU Fans used.
C. Tools and spare parts supplied under this clause shall be provided in original packing,
clearly labelled and referenced.
KEO/19-3262-0000 23 7313/3 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
D. Spare Parts furnished under this clause shall not be used during the maintenance
period without the written permission of the owner (Contractor shall procure spare parts,
tools etc., fulfill his obligations to operate and maintain the system in the contract period)
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Draw-through, modular indoor air-handling units shall be factory assembled and consist
of fans, motor and drive assembly, coils, dampers, plenums, filters, condensate pans,
mixing section, dampers, control devices, 2” thick washable synthetic filter, Long
efficiency bag filter, sand trap louvers ( If shown on the drawings), UV light , electric
heater( If provided in the equipment schedules), and all required accessories. Drain pan
shall extend over the entire coil length & shall be of stainless steel construction for
corrosive resistance and shall be insulated.
B. The Air handling supplier should supply the first line product, which should be AHRI /
Eurovent Certified. The AHRI / Eurovent certificate should show the product series, AHU
sizes, models range, Country of origin etc.
C. On units with VFDs, factory dynamic fan balancing shall be conducted from 14Hz to
50Hz to identify and eliminate critical speeds to ensure stable operation through the
entire operating range of the fan and drive assembly. Field fan balancing is not
acceptable. Forward factory balancing test report to Engineer upon request.
D. Provide factory grommets at all pipe and electrical conduits penetrations through
cabinets.
E. Furnish each unit with a durable, deep etched, .025” thick, factory installed aluminum
identification plate, permanently mounted with the following information:
1. Unit identification as indicated on Contract Drawings.
2. Serial Number.
3. Model Number.
4. Capacity (CFM) and static pressure.
5. Motor HP.
6. Unit power supply: Volts / PH / Amps.
7. Supply Fan Type.
8. Coil GPM and pressure drop.
9. Sales Order #.
10. Date unit manufactured.
2.03 CABINET
KEO/19-3262-0000 23 7313/4 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Air Handling Unit shall be assembled on a heavy galvanized steel channel base
frame. The minimum acceptable height for the base frame is 150 mm for indoor
unit
2. AHUs shall be entirely of double skin construction with Aluminium pentapost
frame and galvanized steel construction for the outer and inner skins. Self
supported modular panels fixed to the baseframe and non-removable panels
supported from inside are not acceptable.
3. The unit panel’s skin thickness should be not less than 1.0 MM for outer and
inner skin. The panels should fabricated of galvanized steel sheet.
4. The outer panel skin should be made of galvanized steel thoroughly degreased
and then phosphatized before application of an average 60micron backed
electrostatic dry powder coating in RAL 7032 color scheme. . The walls from
inside and outside should be completely smooth.
5. All panels should be removable from the casing with quick release fasteners.
Rubber surrounds shall be provided to each panel joint and door to ensure
absolute air tightness. The sealing strips should of cellular rubber with close
pores. The panel shall be mounted flush with the frame members to create a
smooth surface inside and outside.
6. Full size hinged access doors, cam-locks and sturdy handles should be provided
for access section, filters, electric heaters & fans etc.
7. Air handing unit Intake and discharge openings should be fitted with a flanged
duct connection frame.
8. Walk in units should have internal door handles and reinforced floors.
9. The Fan section, Bag filter section, should be supplied with double plastic glass
inspection window not less than 190 Dia. sealed with rubber from the inside and
outside panel skin
10. Material thickness and finishes. Casing material shall exceed 1000-hour, 5% salt
spray solution test at 95F (35C) and 95% relative humidity without any sign of
red rust when tested in accordance with ASTM B-117.
B. Cabinet Insulation
1. The framework should be clad with minimum 60 mm thick, Penta-post frame with
double skinned panel insulated with polyurethane insulation sandwiched having a
density of not less than 48 kg/m³. Thermal conductivity for the casing should not
exceed 0.02W/(mK).
C. Certification
1. The casing should meet Eurovent EN1886 with the following mechanical
characteristics:
Casing Strength D1
Casing Air Leakage Class at - L2
400Pa
Casing Air Leakage Class at L2
+700Pa
Thermal Transmittance Class T2
Thermal Bridging Factor TB2
Filter Bypass Class F9
D. Accessories
KEO/19-3262-0000 23 7313/5 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2.04 Light fitting 60W, Lamp connected to switch outside the casing shall be provided.FAN
AND MOTOR
C. Direct drive single inlet centrifugal fans shall be backward curved high performance
centrifugal impellors with rotation diffuser, mounted on EC external rotor motor with
integrated control electronics.
D. Impellor shall be made of aluminum, with backward curved, continuously welded blades;
flow optimized inlet nozzle made of galvanized steel with pressure tap.
E. Motorized impellor balanced in two planes (static and dynamic) as per DIN ISO 1940 to
G 6.3 balance quality.
F. EC external rotor motor with Efficiency class IE4, magnets without use of rare earths,
maintenance free ball bearings with long term lubrication, theoretical nominal service life
of atleast 40,000 operating hours, soft start, integrated current limitation, wide input
voltage range 1-phase 200─277V, 50 or 3-phase 380─480V, 50Hz fan suitable for use
with all standard power supply systems with no effect on air performance.
G. Integrated electronics, low noise commutation logic; 100% speed control; PID
controllers; motors with power ratings of 750W shall be provided with an
RS485/MODBUS RTU interface.
H. Terminal box shall be made of aluminum with readily accessible connection area with
spring terminals, environment resistant cable glands or with brought out variable
connection cables (K3G250-AT39 and K3G280-AT04 only.)
I. Fan shall comply with the relevant EMC regulations and requirements with regard to
circuit feedback; documentation and marking conform to the applicable EU directives.
J. Performance data, air performance measurements on inlet side chamber test rig shall
be in accordance with ISO 5801 and DIN 24163, noise measurements in low reflection
acoustic test chamber as per DIN EN ISO 3745.
L. Fans shall have a sharply rising pressure characteristic extending through the operating
range and continuing to rise beyond the peak efficiency to ensure quiet and stable
operation. Fans shall have non overloading design with self limiting horsepower
characteristics and shall reach a peak in the normal selection area.
KEO/19-3262-0000 23 7313/6 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
M. Factory Run Test for one AHU: All fans prior to shipment shall be completely assembled
and test run as a unit at the specified operating speed or maximum RPM allowed for the
particular construction type.
N. Blank off panels: Each multiple fan section to be provided with one fan blank off panel to
enable manual isolation of fan for servicing.
O. The following fan options shall be made available for multiple fans:
1. Piezometer Ring: Airflow station shall be factory installed in each fan inlet.
Tubing shall be manifolded so that the measurement is representative of all fans
in the array. The device shall have a measurement accuracy of ±5%.
2. Backdraft damper: Backdraft damper shall be provided for automatic isolation of
individual fans for duty and standby configuration.
P. Shafts: Solid hot rolled steel, ground and polished, with key-way, and protectively
coated with lubricating oil. Critical speed minimum 20% greater than maximum ACMA
class speed.
Q. Fans should capable of accommodating static pressure and airflow variation of minimum
plus or minus 10 percent. Do not increase the speed by more than 20 percent from
specified criteria.
A. Performance Ratings: Tested and rated according to AHRI 410 and ASHRAE 33.
D. Tubes: ASTM B 743 copper, minimum 0.049 inch (1.245 mm) thick.
F. Suction and Distributor Piping: ASTM B 88, Type L (ASTM B 88M, Type B) copper tube
with brazed joints.
G. Frames: Galvanized-steel channel frame, minimum 0.0625 inch (1.6 mm) thick for
flanged mounting.
H. Frames: ASTM A 666, Type 316 stainless steel, minimum 0.0625 inch (1.6 mm) thick
for flanged mounting.
A. Coil Specifications: Refer to Air Coil section with the following superseding
specifications:
KEO/19-3262-0000 23 7313/7 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. The coil should be supplied from the same supplier of the Air Handling Unit
Manufacturer
2. The coil body should be mounted on galvanized steel rails so that it can be
withdrawn from the unit casing
3. Coils of fresh air units shall be provided with factory applied epoxy.
4. Chilled water-cooling coils of capacities as indicated on schedules shall be
fabricated from heavy gauge copper tubing expanded into aluminum fins to give
a mechanical bond. Return bends shall be die formed. Headers shall be heavy
section seamless copper tubing with connections made in steel pipe with anti-
corrosion protection paint and with external screw thread. All joints shall be silver
brazed. Fittings shall include plugged vent and drain taps for each section. Coils
in contact with outside air (either mixed or full) shall be provided with factory
applied baked heresite coating and anti-fungal paint.
5. The coil shall be designed to operate at 16 bar NP.
6. Coil-Performance Tests: Factory-test cooling and heating coils, except sprayed
surface coils for rating according to AHRI 410, "Forced-Circulation Air-Cooling
and Air-Heating Coils."
7. Maximum Face Velocity of 2.5 m/s, Coils will be tested to 30 bars, with a
maximum design operating pressure of 16 bars.
2.07 FILTERS
A. Dampers shall have contra-rotating heavy gage galvanized steel Profiled blades. The
blades shall be fitted with durable neoprene edge seals.
B. Damper axles shall be galvanized steel rotating in Bronze / Nylon bearings with bushes
of plastic.
KEO/19-3262-0000 23 7313/8 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
D. Dampers shall be interconnected by stainless steel push rods and linkages suitable for
motor operation; formed in one unit with plastic bearings and mounted in galvanized
sheet steel frame.
E. Damper motors and fittings, including a position indicator, shall be supplied loose for
fitting on site by the installer.
A. All specifications in this section for indoor units should be applicable for outdoor version
in addition to the following:
1. The outdoor Air Handling Units should be specifically designed for outdoor
installation. Indoor air handlers weatherized for outdoor use not accepted
2. The outdoor units outer joint of the unit should be sealed with permanently
flexible sealing compound.
3. A full-size sloping roof with drip nose for the outdoor units, which is both longer
and wider than the unit and painted in optional color.
4. All outdoor units shall be constructed and delivered on a base fabricated frame
from heavy duty structure galvanized steel channel painted in optional color. The
minimum acceptable height for the base frame is 150 mm.
5. For outdoor extract units the discharge should be fitted with an exhaust hood with
bird screen and the casing drainage shall be provided in the discharge sections.
6. The intake dampers should have contra-rotating stainless-steel profile blades
and fitted internally in a separate section. Also, for the Mixing Box the dampers
should fitted internally.
7. Provide special PVC / epoxy coating for the outer skin.
8. Fresh air inlet shall be through weather proof louver. Case stainless steel drain
pan shall be provided in the intake section.
A. Material: Hygroscopic type rotor heat exchanger designed for the transfer of both
sensible and latent heat. Bearings should be permanently lubricated roller type.
C. Thermal efficiency: The thermal wheels efficiency shall be at not less than 75%.
Measured at the recovery side.
D. Modular unit matching with air handling unit modules in all respects comprising, but not
limited to the following to reclaim coolness / heat from the exhaust air and transfer to the
outside air intake:
1. Wheel filled with a matrix of Aluminium foil.
a. Speed controlled drive unit.
b. High performance seal provides tightness around the wheel surround and
between the air inlet and air outlet.
c. The desiccant should be water molecule selective and non-migratory.
d. The desiccant should be molecular sieve 3 Angstrom, so as to keep the
cross contamination to absolute minimum and also ensure the exclusion
of contaminants from the air streams, while transferring the water vapour
molecules.
KEO/19-3262-0000 23 7313/9 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
e. The thermal wheel is equipped with a purge section to enable continuous
wheel cleaning.
F. Wheel matrix should be only from pure aluminum foil to allow for quick and efficient
uptake of thermal energy, sufficient mass for optimum heat transfer, maximum sensible
heat recovery during low rotational speed of 20 to 25 rpm.
G. The Desiccant for Enthalpy wheel should be water molecule selective and non-
migratory. The Desiccant should be molecular sieve 3Å, so as to keep the cross
contamination to absolute minimum and also ensure the exclusion of contaminants from
the air streams, while transferring the water vapor molecule. The desiccant should be of
sufficient mass, and should be coated with non-masking porous binder adhesive on the
aluminum substrate (matrix) so as to allow quick and easy uptake and release of water
vapor. The weight of desiccant coating and the mass of aluminum foil shall be in a ratio
so as to ensure equal recovery of both sensible and latent heat over the operating
range.
H. The Rotor/Wheel matrix shall have Equal sensible and latent recovery in the range of 60
to 80%.
I. The Rotor shall be made of alternate flat and corrugated aluminum foil of uniform width.
The Rotor honeycomb matrix foil should be so wound and adhered as to make a
structurally very strong and rigid media un-affected by temperature and humidity
changes.
J. Subject to wheel size, sectioned wheel with pie segments, capable of being assembled
at site can be acceptable as an option.
K. The surface of the wheel/rotor should be highly polished to ensure that the vertical run
out does not exceed ± 1mm for every 1 meter diameter , ensuring negligible leakage.
L. The number of wraps (of alternative corrugated and flat foil ) of the rotor over the radii
shall be very consistent so as to ensure uniform air flow and performance over the entire
face in the air stream. Flute height and pitch will be consistent to a very tight tolerance to
ensure uniform pressure drop and uniform airflow across the rotor face.
M. The rotor shall be non clogging aluminum media, having a multitude of narrow aluminum
channels, thus ensuring a laminar flow and will allow particles up to 800 microns to pass
through it.
N. The rotor should rotate at a speed lower than 20 to 25 rpm, ensuring long life of belts
and reduce wear and tear of seals.
O. The media shall be cleanable with compressed air, or low pressure steam or light
detergent, without degrading the latent recovery.
KEO/19-3262-0000 23 7313/10 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
P. The recovery wheel cassette/casing shall be manufactured from tubular construction to
provide a self supporting rigid structure, complete with access panels, purge sector,
rotor, bearings, seals, drive mechanism complete with belts. The cassette/ casing shall
be finished weather proof painting.
Q. The rotor shall have a field adjustable purge mechanism to provide definite separation of
air flow minimizing the carryover of bacteria, dust and other pollutants, from the exhaust
air to supply air. With proper adjustments the cross contamination shall be limited to less
than 0.04% of the exhaust air concentration.
R. The face and radial seals shall be 4 pass non contact labyrinth seals for effective
sealing and also for minimum wear and tear.
2.11 Thermal wheels sensible and enthalpy shall be supplied with electronic speed control
center ( If shown on the schedules). The electronic speed control center shall be fully
integrated to BAS ( building automation system)
A. General
1. Heat pipes shall be included within the AHU and wrapped around the main
cooling coil. The wrap-around heat pipes precool the fresh/return air allowing
more of the cooling coil surface to be utilized for the removal of moisture. The
dehumidified air is then passively reheated by the heat pipe to the supply
condition. The incorporation of the heat pipe allows for a reduction in the size of
chiller and cooling coil as well as replacing the conventional methods of reheat
and their associated system components.
2. Heat pipes for enhanced dehumidification will comprise a precool fin block
upstream of the main cooling coil linked to a reheat fin block downstream of the
cooling coil by means of ‘wrap-around’ pipes. The heat pipes will be delivered to
the AHU manufacturer fully charged and sealed, for inclusion in the air treatment
section of the AHU.
B. Fins
The external fins shall be of aluminium with a minimum thickness of 0.15mm. Fins shall
be of the continuous plate type to maximize the external surface area rather the
individually finned tube pattern. The fins shall be of the louvered type to optimize the
airside heat transfer and spaced at such a distance as required by the conditions
specified.
C. Tubes
Tubes shall be of refrigeration standard seamless copper C106 for heat exchanger use.
Tube diameter shall be 12mm with a grooved inner surface to enhance the internal
surface area and prevent pooling of liquid. The minimum root thickness of the tube shall
be 0.35mm. The number of rows of tubes shall be selected to suit the application.
Multiple row heat pipes shall have tubes in a staggered, equilateral pattern to optimize
the airside heat transfer.
D. Casing
Casings shall be from galvanized sheet steel with a minimum thickness of 1.6mm. The
casing shall incorporate tube plates and top and bottom plates around both the precool
KEO/19-3262-0000 23 7313/11 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
and reheat heat pipe blocks. Cover boxes shall be provided around the wrap-around
pipes both to protect the exposed pipes and to rigidly join the two sections. Extra sheet
metal shall be provided to ensure rigidity during manufacture and transport.
E. Working Fluid
1. The working fluid shall be refrigerant type classified as ASHRAE safety group A1.
The refrigerant shall be R134a. The heat pipe circuits shall be factory charged
and hermetically sealed with the calculated weight of refrigerant.
2. If working fluid is water, the heat pipe circuit shall be factory charged with the
calculated weight of water and hermitically sealed. Individual heat pipe shall be
manufactured in such a way as to ensure that all non-condensable gases are
removed from the tubes.
F. Circuitry
1. Heat pipes shall be formed from an array of complete loops such that the working
fluid flows around the loop in only one direction i.e. liquid and vapour flow in the
same direction to ensure that returning liquid is not entrained by the vapour.
2. There shall be a multitude of loops in the height of the heat pipe and each loop
shall be individually charged. Heat pipes with header assemblies containing a
single circuit are not suitable as a single leak will render the entire heat pipe
inoperative.
3. When multiple row heat pipes are used the rows shall be connected together in a
counter flow orientation to optimize the performance of the heat pipe. Rows shall
not be manifolded together.
4. Heat pipe loops shall be arranged to slope down to the precool side to allow
gravity assisted liquid return to maximize the internal heat transfer.
G. Performance
Heat pipes shall be designed to comply with the specified conditions when subject to the
air volumes given in the specification. Heat pipe performance shall be independently
type tested and certified in line with the requirements of British Standards BS 5141 pt1 /
European Standards EN 305 & 306 / American Standards AHRI 410 / AHRI 1060 for
testing and rating of heat exchangers. All software used to predict the performance of
heat pipes shall be based upon the results of these independent tests
A. Air handling unit sound power data shall be submitted for review. Sound data shall be
given at the supply connections and return connections.
B. Calculations shall be provided for the investigation of the requirements for Sound
Attenuators.
15 23 29 31 28 31 33 dB (A)
PART 3 - EXECUTION
KEO/19-3262-0000 23 7313/12 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3.01 SELECTION
A. The size of units shall be selected to fit into the space available.
B. Variable speed AHU shall be provided with VFD’s. VFD’s and controllers shall be
connected to BAS system.
3.02 EXAMINATION
A. Examine areas and conditions for compliance with requirements for installation
tolerances and other conditions affecting performance.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.03 INSTALLATION
B. Concrete Bases: Install floor mounting units on 4-inch- (100-mm-) high concrete bases.
See Division 23 Section "Common Work Results for HVAC" for concrete base materials
and fabrication requirements.
C. Install modular indoor air-handling units with the vibration control devices as specified in
Division 23 Section "Vibration and Seismic Controls for HVAC Piping and Equipment."
E. Arrange installation of units to provide access space around modular indoor air-handling
units for service and maintenance.
G. Air handling units are to be properly supported to prevent flexing, bending or distorting
base rails.
H. All coils are to be cleaned prior to substantial completion if units are used during
construction.
I. Clean all air handling units and return to original manufacturer's condition prior to
substantial completion. Vacuum clean all debris from inside air handling equipment.
J. Install piping to unit with full size 6 inch long dirt leg with 1/2" valve at bottom for
cleaning.
K. Provide for positive gravity drainage of coil condensate. Pipe full size of unit connection.
L. Adjust fan drives as required to obtain scheduled capacities as directed by the Test and
Balance Firm to include sheave and belt replacement.
KEO/19-3262-0000 23 7313/13 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
M. Align belts to eliminate wear and vibration of belts.
3.04 CONNECTIONS
C. Connect piping to modular indoor air-handling units mounted on vibration isolators with
flexible connectors.
KEO/19-3262-0000 23 7313/14 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Charge refrigerant coils with refrigerant and test for leaks. Remove
malfunctioning coils, replace with new units, and retest.
3. Fan Operational Test: After electrical circuitry has been energized, start units to
confirm proper motor rotation and unit operation. Remove malfunctioning units,
replace with new units, and retest.
4. Automatic Roll Filter Operational Test: Operate filters to demonstrate
compliance with requirements. Test for leakage of unfiltered air while system is
operating. Correct malfunctioning units, then retest to demonstrate compliance.
Remove and replace units that cannot be corrected with new units, and retest.
5. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
D. Refer to Division 23 Section "Testing, Adjusting, and Balancing for HVAC" for modular
indoor air-handling system testing, adjusting, and balancing.
3.07 ADJUSTING
KEO/19-3262-0000 23 7313/15 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3.08 CLEANING
B. After completing system installation and testing, adjusting, and balancing modular
indoor air-handling and air-distribution systems, clean filter housings and install new
filters.
3.09 DEMONSTRATION
END OF SECTION
KEO/19-3262-0000 23 7313/16 Modular Indoor And Outdoor Air Handling Units Fresh Air Handling
Units
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
SECTION 23 8126
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUBMITTALS
A. Product Data: Submit manufacturers’ technical product data, including rated capacities
of selected model clearly indicated, weights, furnished specialties and accessories; and
installation and start-up instructions. Include performance data in terms of capacities,
outlet velocities, static pressures, sound power characteristics, motor requirements, and
electrical characteristics.
C. Wiring Diagrams: Submit manufacturer’s electrical requirements for power supply wiring
for split D/X cooling units. Submit manufacturer’s ladder-type wiring diagrams for
interlock and control wiring. Clearly differentiate between portions of wiring that are
factory installed and portions to be field installed.
D. Samples for Initial Selection: For units with factory-applied color finishes.
C. Regulatory Requirements:
1. ARI Compliance
KEO/19-3262-0000 23 8126/1 Split System Air Conditioners
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
a. Test and rate split D/X cooling units for 135,000 btu/hr capacity or over in
accordance with ARI 360 “Standard for Commercial and Industrial Unitary
Air-Conditioning Equipment”.
b. Test and rate split D/X cooling units under in accordance with ARI 210
“Standard for Commercial and Industrial Unitary Air-Conditioning
Equipment”, and provide Certified Rating. Sound test and rate units in
accordance with ARI 270 “Standard for Sound Rating of Outdoor Unitary
Equipment”, and provide Certified Rating.
2. ASHRAE Compliance: Construct refrigeration system of split D/X units in
accordance with ASHRAE Standard 15 “Safety Code for Mechanical
Refrigeration”.
3. UL Compliance: Provide split D/X cooling units which are designed,
manufactured, and tested in accordance with UL requirements.
G. Units shall be complied with MEW latest regulation and acceptable to PAHW.
I. Units shall be provided with all necessary accessories like crank case heater for
condenser, TXV for refrigerant coil, solenoid valves etc.
J. The DX indoor / outdoor units and refrigeration pipes shall be selected based on the
specified actual capacity without deration.
A. Handle split D/X cooling units and components carefully to prevent damage, breaking,
denting and scoring. Do not install damaged split D/X cooling units or components;
replace with new.
B. Store split D/X cooling units and components in clean dry place. Protect from weather,
dirt, fumes, water, construction debris, and physical damage.
C. Comply with Manufacturer’s rigging and installation instructions for unloading split D/X
cooling units, and moving them to final location.
1.05 COORDINATION
A. Coordinate size and location of concrete bases for units. Cast anchor-bolt inserts into
bases. Concrete, reinforcement, and formwork are specified in Division 03 Section
"Cast-in-Place Concrete."
C. Coordinate and establish the shortest refrigeration pipe length through wall metal
sleeves.
1.06 WARRANTY
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
1. Filters: One set of filters for each unit.
2. Fan Belts: One set of belts for each unit. (If Applicable)
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Chassis: Galvanized steel with flanged edges, removable panels for servicing, and
insulation on back of panel.
1. Insulation: Faced, glass-fiber duct liner.
2. Drain Pans: Galvanized steel, with connection for drain; insulated.
B. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with
ARI 210/240, and with thermal-expansion valve.
E. Air filters shall be of permanent cleanable and washable type and shall be easily
accessible; thickness shall be minimum 25mm.Wiring Terminations: Connect motor to
chassis wiring with plug connection.
A. Cabinet: Enameled steel with removable panels on front and ends in color selected by
Architect.
1. Discharge Grille: Steel with surface-mounted frame or Welded steel bars forming
a linear grille and welded into supporting panel.
2. Insulation: Faced, glass-fiber, duct liner.
3. Drain Pans: Galvanized steel, with connection for drain; insulated.
B. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with
ARI 210/240, and with thermal-expansion valve.
B. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with
ARI 210/240, and with thermal-expansion valve. Provide non-ferrous construction with
aluminum plate fins mechanically bonded to seamless copper tubes; with brazed tubing
joints. Circuit evaporator to provide full active face on minimum cooling step.
B. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with
ARI 210/240, and with thermal-expansion valve. Provide non-ferrous construction with
aluminum plate fins mechanically bonded to seamless copper tubes; with brazed tubing
joints. Circuit evaporator to provide full active face on minimum cooling step.
A. Casing: Steel, finished with baked enamel in color selected by Architect, with
removable panels for access to controls, weep holes for water drainage, and mounting
holes in base. Provide brass service valves, fittings, and gage ports on exterior of
casing.
C. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with
ARI 210/240, and with liquid subcooler.
A. Condensing unit
1. Cu/al condenser coil with inner grooved pipe
2. Scroll compressor for single and tree phase with crank case heater. .
3. Top discharge condenser fan
4. High /low pressure switches.
KEO/19-3262-0000 23 8126/5 Split System Air Conditioners
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. Evaporator unit
1. Direct drive double fan
2. Cu/al evaporator coil with inner grooved pipe.
3. Thermal Expansion valve
4. 1” Aluminum washable filter.
2.08 ACCESSORIES
A. Thermostat: Low voltage with subbase to control compressor and evaporator fan.
D. Refrigerant Line Kits: Soft-annealed copper suction and liquid lines factory cleaned,
dried, pressurized, and sealed; factory-insulated suction line with flared fittings at both
ends.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Examine areas and conditions under which split D/X cooling units are to be installed.
Do not proceed with work until unsatisfactory conditions have been corrected.
B. General: Install split D/X cooling units in accordance with manufacturer’s installation
instructions. Install units plumb and level, firmly anchored in approval locations, and
maintain manufacturer’s recommended clearances.
H. Electrical Wiring: Install electrical devices furnished by manufacturer but not specified to
be factory-mounted. Furnish copy of manufacturer’s wiring diagram submittal
3.02 CONNECTIONS
C. Refrigeration piping indicated in the drawings are diagrammatic. Contractor shall verify
the equivalent distance between the indoor and outdoor unit and cross check with pipe
sizes. Provide bigger pipe sizes if required without additional cost to the client.
D. Provide adequate number of traps in the refrigerant line as per the manufacturers
recommendation.
B. Perform the following field tests and inspections and prepare test reports:
1. Leak Test: After installation, charge system and test for leaks. Repair leaks and
retest until no leaks exist.
2. Operational Test: After electrical circuitry has been energized, start units to
confirm proper motor rotation and unit operation.
3. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
3.05 DEMONSTRATION
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes DX VRF / VRV split-system air-conditioning and heat pump units
consisting of separate evaporator-fan and compressor-condenser components. Units
are designed for exposed or concealed mounting and may be connected to ducts.
B. All indoor and Outdoor Units with DX coils and connected to Outdoor VRF system.
1.02 SUBMITTALS
A. Product Data: Include rated capacities, furnished specialties, and accessories for each
type of product indicated. Include performance data in terms of capacities, outlet
velocities, static pressures, sound power characteristics, motor requirements, and
electrical characteristics.
B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other
work.
E. Samples for Initial Selection: For units with factory-applied color finishes.
A. Product Options: Drawings shall indicate size, profiles, and dimensional requirements
of split-system units based on the specific systems indicated.
F. All the fans shall be coated with anti- corrosion paint to avoid any rust.
G. VRF system shall be suitable for operation at the ambient temperature of 0 deg C to 55
degC.
1.04 COORDINATION
A. Coordinate size and location of concrete bases for units. Cast anchor-bolt inserts into
bases. Concrete, reinforcement, and formwork are specified in Division 03 Section
"Cast-in-Place Concrete."
B. Coordinate size, location, and connection details with roof curbs, equipment supports,
and roof penetrations specified in Division 07 Section "Roof Accessories."
1.05 WARRANTY
B. Warranty Period: from date of Substantial Completion and shall be in accordance with
specification section 23 9010.
A. Standard Warranty shall be as per contract terms and condition with a 5-year warranty
for compressor. Spare Parts list shall be as per the manufacture’s recommendation for 2
years.
B. Spare Parts furnished under this clause shall not be used during the maintenance
period without the written permission of the owner (Contractor shall procure spare parts,
tools etc., fulfill his obligations to operate and maintain the system in the contract
period).
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. The condensing unit shall have special design suitable for high ambient climatic
conditions. The system shall be capable of cooling with external ambient temperatures
from –5oC to +55oC and provide heating with ambient temperatures down to –20oC.
Third party test report shall be submitted (minimum 2-hour operation).
B. The Indoor units shall be capable to control proper temperature and humidity in
occupied space under the conditions specified in tender design documents. The
systems shall provide extra Power savings in mild ambient conditions by changing
evaporation temperature of Refrigerant via ‘Variable Refrigerant Technology’.
C. The VRV / VRF system shall control varying flow of refrigerant through the fan coil units,
by means of an electronic expansion valve fitted in each indoor unit.
E. The VRV / VRF system shall have the ability to sustain refrigerant piping lengths of up to
165m with a level difference up to 50m between fan coil units and condensing unit if the
outdoor unit is located above the highest-level indoor unit. An option shall be available
to increase the level difference of the pipe work to 90m between fan coil units and
condensing unit if the outdoor unit is located above the lowest level indoor unit.
Manufacturer shall submit live computer model to check the pipe lengths.
F. The manufacturer shall ensure that the units selected provide cooling capacity at design
conditions of temperatures (indoor and outdoor) and pipe lengths (vertical and
horizontal).
H. The VRV / VRF system shall operate with Refrigerant R410A, the refrigerant shall be a
zeotropic blend constituted of a maximum of two different refrigerants providing a
maximum temperature glide of less than 0.17K to avoid fractionation problems.
I. The equipment manufacturer shall be fully certified and registered to comply in the
areas of MEW, local authority having jurisdiction,, Eurovent, ISO9001 and ISO14001.
J. All equipment shall be run tested in accordance with the following procedures prior to
leaving place of manufacture.
1. Pressure tested at 39 Bar & System vacuum test to 2 Torr
2. Refrigerant test to within 0.3% & Run test with Refrigerant Filled in
3. Laser camera check for unit completion and unit shall not be manually handled
afterwards.
4. Electronic leak testing shall be carried out to ensure maximum system refrigerant
containment.
KEO/19-3262-0000 23 8127/3 Dx-Vrf-vrv Split System Air Conditioners
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
5. Electrical tests shall include flash testing at 1440V AC to ensure that current
leaks above 5mA are detected, megger test at 500V DC to ensure resistance
levels are above 10 mega Ohm and earth continuity tests.
A. General- The unit shall be manufactured with Galvanized steel plate partially insulated
with closed cell expanded polyurethane foam.
B. The unit shall be exposed decorative type of, ceiling cassette, ceiling concealed (ducted
split) ceiling suspended, wall mounted, floor mounted exposed and concealed
configuration as shown and specified and detailed below:
C. Units shall be designed for refrigerant R- 410 A for COOLING/HEATING application with
self-contained direct expansion heat pump types evaporating coil gas distributor in fan
coil unit with linear expansion valves. Evaporation coils shall be aluminum fins
mechanically bonded copper tubes Factory leak tested . Fan shall be centrifugal direct
driven types, statically and dynamically balanced and shall on permanently lubricated
bearing. Fan motor shall be low noise with multi-speed (as per recommended by
manufacturer) motor with internal thermostat.
D. All Air handling / FCU/ indoor unit shall be supplied with self-diagnostic functional
thermostats and washable filter or as manufacturer’s recommendations.
E. These units must be connected to a single outdoor unit. Refrigeration system must be
only two pipes network either cooling or heating one time the entire system connected
in their respective group. Each outdoor shall be able to group with minimum 2 to 50
indoor units of different capacities and types with in the total capacity of the connected
out door unit.
F. The flow of refrigerant through the heat exchanger will be controlled by a linear
expansion valve. This valve will be controlled by two pipe thermistors and a return air
thermistor, capable of controlling variable capacity of the indoor unit between 15% and
100%.
G. Each indoor unit to be suitable for fuzzy logic signal 30vdc from the outdoor unit via a 2
core non-polar screened cable.
H. In case of malfunction / power failure on any indoor unit the remaining indoor units and
its corresponding outdoor unit should continue to perform without total system break
down.
A. Units should have adjustable air outlet such as 1, 2 or 4 ways as per site requirement
with swing louvers and adjustable blades from sides. An airflow control mechanism must
be factory built-in to distribute the air evenly over the vane’s upper and lower surfaces to
prevent the air from hitting the ceilings. Air intake must be from center bottom of the unit
through fixed decorative blade grill and factory supplied washable air-filter.
B. Cassette unit should be equipped with drain water lift up mechanism. Evaporator fan
should be centrifugal turbo fan or sirocco fan multi-speed low noise motor. Refrigerant
pipe and condensate drain connection to be in separate corners for easy installation and
maintenance.
KEO/19-3262-0000 23 8127/4 Dx-Vrf-vrv Split System Air Conditioners
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2.05 CEILING CONCEALED (DUCTED)
B. The return air to the unit shall be through the back of the unit as standard however shall
have bottom return option. The heat exchanger coils shall be manufactured from copper
tubes and aluminium fins and have 3 rows of cooling coil. It shall have electronic
expansion valve to control refrigerant flow rate in response to the load variation in the
conditioned space. The expansion valve shall be controlled by an integral computerized
PID control system to maintain correct room temperature. Unit height shall not exceed
245mm for capacities up to 16 kW.
C. The unit casing shall be manufactured from galvanized steel plate and shall be insulated
at all applicable panels. The use of a polystyrene only construction for the outer casing
will not be acceptable. Facility shall be provided for duct connection for introduction of
fresh air to the unit and branch ductwork from the unit.
D. The fan motor shall be DC inverter motor. The unit static pressure shall be automatically
adjustable from the unit wired remote controller (service mode). Unit height Shall not
exceed 250mm.
E. The nominal fan external static pressure shall be from 30 to 140 Pa The sound pressure
level of these indoor units shall in no case exceed 45 dbA at high fan speed mode when
measured 1.5m distance from the unit.
F. A factory installed condensate lift pump shall be provided within the unit and shall be
capable of discharging above the drain outlet. Filed fitted drain pumps will not be
accepted.
G. The basic unit shall consist of cooling coil, one or more centrifugal fans, electric motor
condensate drain pan, and galvanized steel casing and electric junction box.
H. Air will be discharged by the centrifugal fans which shall be of the forward curved non-
overloading type to the front of the unit to allow for field supply ductwork and air outlets
to distribute the air into the room through air out lets.
I. Return air will be brought to the rear of the unit to allow for proper return air to be either
ducted from room or taken from the ceiling void. The fans shall be statically and
dynamically balanced and specially designed for quiet operation. The motor should be
three speed built-in and resiliently mounted with adjustable mounting, direct driven as
recommended by the manufacturer.
J. The condensate drain pan shall be constructed of heavy gauge galvanized steel
adequately treated against corrosion, insulated and pitched for positive drainage with
the unit-installed level. The basic unit casing shall be constructed from galvanized steel
plate partially insulated with closed cell expanded urethane foam.
K. The unit shall be provided with washable air filter or as recommended by the
manufacturer, mounted on the box enclosure of the unit in a sealed way to prevent air
by passing.
B. The air handling basic unit shall consist of cooling coil, one or more centrifugal fans,
electric motor condensate drain pan, and galvanized steel casing and electric junction
box.
C. Air will be discharged by the centrifugal fans which shall be of the forward curved non-
overloading type to the front of the unit to allow for field supply duct work and air outlets
to distribute the air into the room.
D. Fresh air from Outdoor will be brought through sand trap louvers, pre -filter installed in
the inlet of the fresh air duct connected to the air handling unit.
E. The fans shall be statically and dynamically balanced and specially designed for quiet
operation. The motor shall be built-in and resiliently mounted with adjustable mounting,
direct driven or as recommended by the manufacturer.
F. Required amount of treated fresh air shall be discharged through duct to the areas as
shown on the drawing- for capacity and details refer A/C schedule.
G. The condensate drain pan shall be constructed of heavy gauge galvanized steel
adequately treated against corrosion, insulated and pitched for positive drainage with
the unit –installed level. The basic unit casing shall be constructed from galvanized
steel plate partially insulated with closed cell expanded urethane foam.
H. The unit shall be provided with high efficiency air filter mounted on the box enclosure of
the unit in a sealed way to prevent air by passing.
A. Shall be of decorative slim dimension for indoor ceiling mounted with front horizontal air
discharge and auto swing louver for proper air distribution. This auto swing vane should
act as a shutter when the unit is turned off. Air intake shall be from the bottom fixed
blade air grill and washable air filter.
B. Evaporator fan should be centrifugal sirocco directly driven by multispeed low noise
motor. Condensate drainpipe connection should be either from left or right side of the
unit to facilitate the site condition.
A. Shall be of decorative slim dimension suitable indoor wall mounting. The unit base shall
be fabricated from galvanized steel sheet and shall be internally insulated to prevent
condensation. The external decorative cabinet shall be of ABS plastic material with
necessary provision for air intake in the center through fixed blade air grill and washable
factory supplied air filter. Air discharge should be through auto flap shutter for uniform
airflow. This flap should act as a shutter when the unit is turned off.
B. The evaporator fan should be centrifugal line flow type directly driven by multi speed low
noise motor. Provision for five ways refrigerant piping and four ways condensate drain
should be feasible in order to connect the unit as per the site condition. All screws
B. Floor Mounted Unit shall be with single or two number centrifugal sirocco fan driven by
low noise multi speed motor. Motor and moving parts should be mounted on rubber
mounting to reduce noise and vibrations. Provision for five ways refrigerant piping and
four ways condensate drain should be feasible in order to connect the unit as per the
site condition. All screws securing the unit should be accessible from the front of unit for
easy installation and maintenance.
A. Effective heat recovery and ventilation should be accomplished by the forced expulsion
of stale air with substantial savings by providing efficient heat recovery techniques for
reducing treated fresh air load to the corridor or locations as shown in the drawings and
schedule.
B. The units will be manufactured from galvanized steel plate partially insulated with closed
cell expanded polyurethane foam. Temperature and humidity are to be exchanged
between the supply air and exhaust air.
C. The units will comprise of a semi-permeable cross flow heat exchanger for waste heat
recovery as per drawing and schedule. The unit shall have 2 forward curved centrifugal
fans and motors supplying and extracting through the cross flow heat exchanger at the
same rate, either High or Low fan speed. The units will have electronic bypass damper
control and heat recovery control depending on which mode the unit is set.
A. Effective heat recovery and ventilation should be accomplished by the forced expulsion
of stale air with substantial savings by providing efficient heat recovery techniques for
reducing treated fresh air load to the corridor or locations as shown in the drawings and
schedule. The units will be manufactured from galvanized steel plate partially insulated
with closed cell expanded polyurethane foam. Temperature and humidity are to be
exchanged between the supply air and exhaust air.
A. Unit shall be rom the same manufacturer or other manufacturer compatible with VRF
outdoor unit.
B. Supply and install as indicated in the schedule of equipment, Air Handling Units (AHUs)
/ Fresh Air Handling Units (FAHUs), each capable of the duty as mentioned in the
schedule of equipment. The space available for the unit to be physically verified at the
site and dimensions of the units shall be selected to fit into the spaces available. Where
necessary the units may be built on site, subject to acceptance of the finished units for
warranty purposes by the original supplier and his local agent.
C. The units shall be double skin construction, draw-thru type comprising of various
sections such as mixing box (wherever the RA, FA is ducted), filter section, heat
recovery components, DX cooling coil, electric heater and fan section as per the details
shown either in the drawings or specified in the schedule of equipment. Fresh air
handling units with heat recovery systems shall be provided with heat recovery wheels /
heat pipes as indicated in the schedule of quantity.
D. Quality Assurance
1. The equipment manufacturer shall strictly adhere to following standards &
specification:
a. ISO 9001:2008 certificate of the manufacturing facility required.
b. The equipment manufacturer shall produce test reports for successfully
carrying out the following tests as per BS EN 1886: 2007 and ISO
3744:2009 standards carried out at TUV-NORD test laboratory in
Germany applicable. The test results should comply with the construction
for Fresh Air Handling Units and the Air Handling Units in contact with
ambient air.
1) Casing strength to CLASS D1
2) Casing air leakage minus 400 Pa to CLASS L1
3) Casing air leakage plus 700 Pa to CLASS L1
4) Thermal transmittance CLASS T2
5) Thermal bridge factor CLASS TB2
6) Filter bypass leakage factor CLASS F9
E. Unit Construction
1. The unit casings shall be of double skinned panels not less than 45-50 MM
thickness. Casing shall be assembled with self supporting modular panel
elements with an integrated base frame made of zincoated steel and sections
along upper sides of the units.
2. The frame work shall be of extruded aluminium thermal break construction using
polyamide profiles for thermal bridging (thermal break using gasket not
acceptable) for all Fresh Air Handling Units and also for all the Air Handling Units
in contact with ambient air.
3. Sheet metal thickness shall be not less than 0.8 MM for the inner skin and 0.8
MM for the outer skin and shall be made from 270 GSM zincated steel sheets.
The outer skin shall be pre-painted galvanised steel sheet having 7 to 9 microns
of primer coat and 20 to 25 microns of polyester coat on the outer surface. For
additional protection, outer surface of the outer skin shall be provided vinyl guard
film for scratch protection. Inside and outside of panel walls shall be completely
smooth.
4. All casing panels shall be insulated with injected CFC free polyurethane foam
insulation and shall be in accordance to Class O of ISO 1182.2 standards. The
insulation density shall be 45 Kg /m³ and having thermal conductivity of 0.022
W/m K.
5. The base frame of the units shall be made from galvanized sheet metal for size
with largest dimensions upto 2500 MM, and hot dip galvanized U-profile for larger
units.
6. Access doors shall be provided with special gasket and locking device. Access
doors 400MM and larger shall be provided with hinges and handles and access
doors with width smaller than 400MM shall be removable type fitted with quick
release flap turn lock with spring pressure arrangement. Sealant between panels
shall be an anti fungicide sealant material.
7. The manufacturer shall guarantee that no condensation shall take place on the
exterior of panels. In the event that any condensation problems appear after
installation, the contractor shall undertake all remedial measures to rectify and to
the satisfaction of the consultants. Any stacked or double height coils shall have
separate drain pans to reduce carry over.
8. Units installed outdoors shall be fitted with weather proof aluminium canopy.
28 29 31 34
G. Vibration Isolation: The Air Handling Unit shall have internal vibration isolation system
by mounting fan, motor and drive assembly on spring isolators designed for 93%
isolation. The fan discharge shall be connected to the air handling unit casing through
H. Filter Section: Filter cells shall be of standard sizes and shall be obtained from reputed
European manufacturer. The filters shall be sealed against the filter frame using a
permanently elastic gasket to a standard compatible with the filter efficiency.
1. Pressure drop tapings shall be integrated into the frame to allow a manometer or
filter monitor to be fitted. Filter materials shall be flame-retardant, incombustible,
non-odorous and offer no sustenance to vermin. Each filter section has to be
provided with manometer.
2. The filter material shall be pleated to provide a large effective area. Filter section
should be provided with an inspection door.
3. The contractor shall supply set of all filters per AHU as spares for replacement
after testing and commissioning and prior to handing over of the installation in
accordance with specification section 23 9010.
4. Panel Filter: The Panel filter material shall be synthetic media, pleated to provide
a large effective area and shall be supported by a wire mesh and frame. The filter
cells shall be suitable for side withdrawal on the inspection side. The filter class
shall be EU-4 as per Eurovent 4/5 or G4 as per EN 779.
5. Bag Filter: Bag filters material shall be synthetic media, of standard readily
available sizes. The filters shall be clamped against the frame using a cam
locking bar. The filter class should be EU7 as per Eurovent 4/5 or G7 as per EN
779. Bag filters shall be provided for both Fresh Air Handling Units and Re-
circulated Air Handling Units.
I. Fan & Fan Motor: Fans shall be double inlet, double width, and backward curved
centrifugal type with galvanized steel casings. Fans shall be tested in accordance with
AMCA 300-85. Every individual fan shall be run before delivery to check bearing
condition and vibration. Fan shafts shall be mounted in taper sleeve bearings designed
for continuous operation and a mean useful life of 200,000 hours. Backward curved
impeller should be coated with 60 micron epoxy painting of high quality.
1. Fans shall be designed in accordance to the specified operating class of AMCA
standard 99-2408-69 – performance class limits for centrifugal fans. The impeller
& fan shaft shall be statically and dynamically balanced to a balancing grade of G
2.5.
2. The fan shall be connected to the outlet opening by means of an airtight flexible
connection. Fans shall not exceed a maximum outlet velocity of 12 m/sec.
3. The degree of protection shall be IP55 with mounting method B3 and Class F
insulation for the electric motors.
4. Fan drive shall be rated at 150% of the maximum motor power of the units and
shall be fitted with adjustable belt tension arrangement.
5. Belt guards or screen protection door in Fan section shall be provided in
accordance with CEN Standard.
6. The fan motor shall be suitable for operating 415V, 3Ph, 50Hz electrical power
supply. The fan motor shall be wired to the safety isolation switch or connection
box.
7. The contractor shall select power input and speed of the fan subsequent to
ascertaining system static pressure in accordance with pressure drop
calculations to the approval of the engineer.
8. The fan motor shall meet the safety requirements of the CE and compatible with
variable frequency drives.
9. The motor shall be mounted on a common rigid, galvanized steel base frame.
N. AHU Controller
1. Air handling unit controller must be from the VRF Outdoor unit manufacturer an
interface to allow connection to third party manufactured/ field supplied Air
handling equipment.
2. The AHU controller shall include but not limited to LEV expansion device’s,
discharge, return air temperature and nessary pipe sensors with temperature
set point by control 0-10 VDC , auto mode error input, etc.
A. The units shall be air-cooled type incorporating 4 sides heat exchanger coils
manufactured from copper tubes and aluminum fins, factory treated to reduce the effect
of atmospheric corrosion. The unit casing shall be manufactured from (70µ) polyester
powder coated baked enamel finish sheet steel in order to have a high corrosion
resistance and to protect against salt laden environment close to where the units may
be installed. The colour shall be manufacturer’s standard ‘Ivory White’. The air outlet
shall have plastic coated wire guards.
B. The 4 sides Condenser coil Fins shall have Factory applied, Bluefin PE coating or
similar having 1000 hr salt spray withstand test.
C. The outdoor units shall have all inverter driven Scroll compressor(s) electronically
controlled and capable of changing speed to follow the variation in cooling or heating
requirements, and from same manufacturer of main equipment.
KEO/19-3262-0000 23 8127/12 Dx-Vrf-vrv Split System Air Conditioners
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
D. The compressor shall be scroll type with fixed and orbiting scrolls. The low pressure
refrigerant shall be fed directly into the scroll and the discharge refrigerant shall cool the
motor windings and place the compressor shell under discharge pressure. The
lubrication oil of the compressor shall be fed through the centre of the crankshaft and
then across the complete area of the scrolls from the centre outwards to ensure the
complete contact area is positively lubricated maximizing compressor efficiency and
minimizing wear and tear. HIPOR compressors are not acceptable due to built in oil
pump in compressor/s.
E. The outdoor unit fan motor will be inverter driven ODM (Outer Rotor DC Motor) type and
without shaft and shall operate electronically by sensing operational temperatures,
pressures and ambient temperature and monitoring the dictates of the indoor units. For
Easy commissioning, The Outdoor unit shall be able to communicate and upload /
download data directly from software via VRV / VRF Configurator. The outdoor unit shall
have 3-digit, 7-segment display.
F. The units shall be fitted with all key components such as Inverter compressor(s),
electronic expansion valve(s), oil separator(s), suction accumulator, high pressure
switches, inverter driven fan motors, safety thermostat, over current relay, inverter
overload protection, fuses, necessary solenoid valves, liquid shutoff valves, gas line
shut off valves, short re-cycling guard timer and all necessary sensors for optimized,
safe and trouble free operation. Shall be fitted with an in built Earth Leakage protection.
The access to the internal components for maintenance purposes shall be by removable
panels.
I. Free Combination shall be possible to make alternative selections with energy efficient
or space saving as per project requirements
K. All refrigerant connections both internal within the unit and the external connections to
the indoor units shall be brazed. Flared or mechanical connections will not be
acceptable on the outdoor unit.
L. The unit shall have required interface for the advanced online Failure Predictive system
provided by Manufacturer.
M. The system shall be tested by a recognized 3rd party as per AHRI 1230:2010 and shall
meet or exceed relevant Local Standards
O. The condensing units shall be of the air-cooled type, designed for use with refrigerant R-
410 A for cooling and heating of capacity as shown in the drawings and schedule.
System shall be suitable for a two pipe system with either branch pipe or header pipe
arrangement. The refrigeration process of the outdoor unit to be maintained by
pressure and temperature sensors controlling solenoid valves, check valves and bypass
valves. The heating or cooling mode of the outdoor unit to be controlled by two 4 way
valves which should reverse the cycle of the refrigerant to change the mode of the
outdoor unit. Control shoulld be via a 30 vdc signal generated by the outdoor unit. This
signal to be sent to the indoor units via a 2 core non polar screened cable.
P. The condensing unit shall comprise of propeller fan, fan motor, heat exchanger
(condenser coil) accumulator, sub cooling coil , oil separator, four way valve, for heat
cool model, compressor control box and heat inter change circuit to allow for better
refrigerant distribution and control with Electronic expansion valves.
R. The compressors shall be full inverter scroll type only capable of controlling 1 HZ
increments plus, mounted on external spring isolators, provided with crankcase heater
,oil separator and accumulator. Compressor shall be located in a separate section
isolated from the condenser coil and fans.
S. The condenser fans shall be of the Variable speed propeller type, arranged for top air
discharge. The fan shall be weather proofed, statically and dynamically balanced, direct
driven by a totally enclosed and permanently lubricated resiliently mounted electric
motor. Fans shall have safety guards.The fan shall be factory set for zero pascal ESP
with additioanl dip switch to factlity for field adjustment capable of normal operation for
additional requiremt up to 60 Pascal.
T. The condenser coils shall be constructed of heavy gauge seamless copper tubes
mechanically bonded to aluminum plate fins, weather proof treated against corrossion
and saline condition such as herasite, blue guard or factory applied protective coatings.
The coils will be capable of being divided into smaller sectiions to enable the outdoor
unit capacity to match the capacity required by the indoor unit. The coils shall be
circuited for subcooling and shall have guard protection for the condenser fins. Coils to
be leak tested at the factory.
A. The unit shall be provided with all necessary factory assembled terminal block where in
the power supply should pass through a noise filter to DC reactor with safety device to
protect from rush current to the inverter board for smooth linear compresor operation
along with built in controls such as but not limited to H.P switches, HP&LP sensers
B. Compressor: Each outdoor unit module shall be equipped with one inverter driven scroll
hermetic compressor. Non-inverter-driven compressors will not be allowed.
C. Inverter: Inverters should be protected by built in factory supplied DC bus current inorder
to control the frequency.
D. Fan Controller: Should include over current protector ,inverter board, and inteligent
power module for linear operation of fan motor to conctrol the fan speed in line with
compressor operation .
E. Main Board: Should include cooling heating auto changeover relay centralized control
transmission board, power supply terminals for main and controls.
F. Refrigerant Cooled Inverter Board: Should have necessary power supply terminals, 105
C rated smoothing capacitor, over current detection resistor Earth leakage protection
and serial transmission point to main board Cooling of inverter board shall provide by
dedicated refrigerant circuit ensuring constant temperature of 40 C. Air-cooled heat sink
will not be approved for middle east climatic zone (T3 )use.
G. Outline of control method:-The out door units should be arranged in the order of
capacity from large to small in case of combination units to meets the total load by
factory buit in dip swithes
I. Control at Start-up: The upper limit of frequency during the first 3 minutes of the
operation is 50Hz. When the power is turned on, normal operation will start after the
initial start-up mode has been completed (with a restriction on the frequency).
J. By Pass Capacity Control: Solenoid valve factory built-in to by pass high and low
pressure side to facilitate when compressor is started, compressor stops in cool or
heating mode, after operation stops, during oil recovery operations, during low “Hz”
operation, when the high pressure increased or discharge temperature rises.
A. From the same A/C manufacturer factory built- in, in the outdoor unit control panel
weather protected, with self –diagnostic function for easy reading and maintenance. A
four – digit LCD display should give all service information, fault history and must
constantly monitor all operation of respective out door and connected indoor units,
room’s thermostats either in cooling or heating mode.
A. General:
1. Room thermostat Should be located 1.4 Meter from the finished floor level
location as shown in the drawings and as per site condition, with LCD display,
easy to read, operate with icon display.
2. The VRF Controls Network should be capable of supporting remote controllers,
schedule timers, system controllers, centralized controllers, an integrated web
based interface, graphical user workstation, and system integration to Building
Management Systems.
B. Electrical Characteristics
1. The controls network should operate at 24VDC. Controller power and
communications should be via a common non-polar communications bus.
2. Wiring: Control wiring should be installed in a system daisy chain configuration
from indoor unit to indoor unit, and to the outdoor unit. Control wiring to remote
controllers shall be run from the indoor unit terminal block to the controller
associated with that unit. Wiring should be 2-conductor plus spare wire (in-
accordance with specification section 23 9010) (16 AWG), twisted shielded pair,
and stranded wire, as defined by the VRF system manufacturer Design Tool soft
ware in AutoCAD output.
3. Network wiring should be CAT-5e or more with RJ-45 connection.
C. Remote Controller:
1. The Remote Controller should be capable of controlling up to 16 indoor units
(defined as 1 group).
D. Centralized Controller:
1. Each floor shall have one central controller; location shall be finalized along with
other building services
2. The Centralized Controller should be capable of controlling a maximum of 150
indoor units across the outdoor units. The Centralized Controller should support
operation superseding that of the remote controllers, system configuration,
daily/weekly scheduling, monitoring of operation status, and malfunction
monitoring.
3. The Centralized Controller should have five basic operation controls which can
be applied to an individual indoor unit, a group of indoor units (up to 150 indoor
units), or all indoor units (collective batch operation). This basic control set of
operation controls for the Centralized Controller should include on/off, operation
mode selection (cool, heat, dry, and fan), temperature setting, fan speed setting,
and airflow direction setting.
4. The Centralized Controller should allow the user to define both daily and weekly
schedules with operations consisting of ON/OFF, mode selection, temperature
setting, and vane direction, fan speed, and permit/prohibit of remote controllers.
5. The Centralized Controllers should be equipped with one RJ-45 Ethernet port to
support interconnection with a network PC via a closed/direct Local Area
Network (LAN).
6. The Centralized Controller should be capable of performing initial settings via the
9” high-resolution, backlit, color touch panel on the controller or via a PC.
7. Optional software functions should be available so that the building manager can
securely log into each Centralized Controller to support operation monitoring,
scheduling, error email, personal browser for PCs, and online maintenance
diagnostics. BACnet® / LONWORKS® interface should be available through an
adapter.
F. Control Wires:
1. A two (2+1 spare) non-polarized transmission line should allow for simple and
foolproof connection of each indoor and remote controller. The cable should be
either factory supplied or as recommended by the local supplier/ dealer. Empty
conduit for the same with pull wire shall be fixed/made available by the main
contractor. The sub Contractor shall be responsible for the interconnecting
control wiring between the indoor and outdoor units and control wiring between
remote controllers, centralised control and relevant components. This work shall
be co-ordinated with the Electrical Sub Contractor for the rooting and trunking of
the cables.
2. All control wiring are to be carried out in 2 core 1.5mm PVC shielded cabling
with colour coding and tagged with ID number at 3 metre intervals as per
schematics for ease of identification and maintenance.
3. Control wiring shall not be run next to power wiring. A minimum space of 100mm
between both control and power cables shall apply.
B. Suction and discharge refrigerant piping shall be of dehydrated copper tube. They shall
be separately insulated with closed cell rubber foam with a minimum thickness of 19
mm. Both the pipes wrapped with canvas cloths 6 oz applied with white tough washable
abrasion-resistant coating.
C. Piping penetrating walls shall pass through a PVC sleeve with adequate diameter and
sealed according to general specifications. Longest possible lengths of copper pipe
should be utilised to minimise joints on site. Joints in copper pipe shall be brazed.
Brazing shall be carried out to the requirements of the HVCA Code of Practise – Brazing
and Bronze Welding of Copper Pipe and Sheet.
D. Piping penetrating roof slab shall pass through PVC sleeve and to be sealed for
waterproof and the contractor should submit detail-working drawing for the way
proposed for consultant’s approval.
E. Copper pipe straight length “L “type manufactured in line with ASTM B280 hard drawn
cleaned and caped to be used on all possible areas. Soft coils in accordance with ASTM
B 280 and ANSI B 91 can be used to avoid sharp bend within 1 meter to connect the
indoor unit from the main raiser. Contractor/Installer should close both end of copper
pipe at the end of every working day till installation period to ensure no foreign particles
could penetrate inside the system. Installer should allow 5 to 10 psig (OFN) Oxygen
Free Nitrogen as an inert gas through the pipes during all joints/ brazing work is in
process till completion to avoid any carbon deposits and moisture presence in the pipe
F. Prior to the final connection the system should be thoroughly flushed with nitrogen and
pressure tested and this test should be seen and approved by the Consultant/Engineer.
G. Pipework to be properly fixed and supported at a minimum of 1.5 metres centres . All
indoor pipe work should run in cable tray or with proper supports without lagging as
recommended by the local supplier / manufacturer .Roof exposed pipe work should run
in cable tray with aluminum cladding.
H. Pressure test: After installation of pipework, and prior to sealing of insulation joints and
starting of equipment, pipework should be pressure tested. 3(43.5 psig) bar test for 3
minutes minimum, then 15 bar (218 Psig )for 3 minimum, then 33 bar( 478 psgi ) for 3
minutes minimum, then strength test to 41.5 bar(601 psig ) check the system for leaks
and deformation, then lower the pressure back to 33 bar( 478 psig ) and pressure test
24 hours and checked for leaks.
I. Vaccum test :Use a vaccum pupp with reverse flow check valve to Vacuum /dehydrated
to achive the level to5 Torr (650 Pa) and hold at that setting for 12 hours (minimum)
J. Refrigerat charge :
1. The charging should be carried out with an appropriate charging station.
2. Refrigerant charge weight must be calculated, to the actual installed length of
pipework in accordance to VRF manufacturer recommendations by their soft
ware .
3. Break the vaccum in the pipe work with ozne friendly refrigerant recommended
by the manufacturer, same as of the matching refrigerant in the out door unit for
the amount as calculated by the manufacture soft ware for additioanl refrigerant
charge and then open the service valve of the corrresponding out door unit to
equvalise the pressure in the systyem .
A. U PVC drain pipe should be used for the same with insulation to avoid condensation
from pipes connected to nearest floor trap or as directed by the consultant. A cleanout
with U trap should be provided for easy maintenance.
PART 3 - EXECUTION
3.01 INSTALLATION
3.02 CONNECTIONS
B. Perform the following field tests and inspections and prepare test reports:
1. Leak Test: After installation, charge system and test for leaks. Repair leaks and
retest until no leaks exist.
2. Operational Test: After electrical circuitry has been energized, start units to
confirm proper motor rotation and unit operation.
3. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
3.05 DEMONSTRATION
END OF SECTION
AIR COILS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the following types of air coils that are not an integral part of air-
handling units:
1. Chilled-water. (If applicable)
2. Refrigerant.
3. Electric. (If applicable)
1.02 SUBMITTALS
A. Product Data: For each type of product indicated. Include construction details, material
descriptions, dimensions of individual components and profiles, and finishes for each air
coil. Include rated capacity and pressure drop for each air coil.
C. Coordination Drawings: Reflected ceiling plans, drawn to scale, on which coil location
and ceiling-mounted access panels are shown and coordinated with each other.
E. Operation and Maintenance Data: For air coils to include in operation and maintenance
manuals.
PART 2 - PRODUCTS
2.02 GENERAL
A. Provide extended surface type coils with tubes of copper and fins of aluminum.
B. Space fins 12 per inch maximum and minimum tube Ida. 5/8”. Helical fins may be
crimped. The whole fin shall be without any holes for easy cleaning
D. Fin collar shall cover entire tube, so there is no air contact with tube.
F. Bends in tubes shall be smooth without wrinkles to reduce erosion and pressure drop.
G. Performance rating shall be established at a maximum coil face air velocity of 2.54 mps
(500 fpm) or as per manufacturer standards.
H. Drip / drain pan shall be of sturdy construction and with inherit protection against
corrosion.
I. Protect coils so fins are not damaged. Replace loose and damaged fins. Comb out bent
fins.
A. Performance Ratings: Tested and rated according to ARI 410 and ASHRAE 33 or
equivalent Eurovent standards.
D. Tubes: ASTM B 743 copper, minimum 0.049 inch (1.245 mm) thick.
G. Frames: Galvanized-steel channel frame, minimum 0.0625 inch (1.6 mm) thick for slip-
in flanged mounting.
H. Frames: ASTM A 666, Type 316 stainless steel, minimum 0.0625 inch (1.6 mm) thick
for flanged mounting.
A. Performance Ratings: Tested and rated according to ARI 410 and ASHRAE 33.
D. Tubes: ASTM B 743 copper, minimum 0.049 inch (1.245 mm) thick.
F. Suction and Distributor Piping: ASTM B 88, Type L (ASTM B 88M, Type B) copper tube
with brazed joints.
G. Frames: Galvanized-steel channel frame, minimum 0.0625 inch (1.6 mm) thick for
flanged mounting.
H. Frames: ASTM A 666, Type 316 stainless steel, minimum 0.0625 inch (1.6 mm) thick
for flanged mounting.
E. Frames: Galvanized-steel channel frame, minimum 0.0625 inch (1.6 mm) thick for
flanged mounting.
F. Control Panel: Unit or Remote mounted with disconnecting means and overcurrent
protection. Include the following controls:
1. Magnetic contactor.
2. Mercury contactor.
3. Toggle switches; one per step.
4. Step controller.
5. Time-delay relay.
6. Pilot lights; one per step.
7. Airflow proving switch.
KEO/19-3262-0000 23 8216/3 Air Coils
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
G. Refer to Division 23 Section "Instrumentation and Control for HVAC" for thermostat.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine ducts, plenums, and casings to receive air coils for compliance with
requirements for installation tolerances and other conditions affecting coil performance.
B. Examine roughing-in for piping systems to verify actual locations of piping connections
before coil installation.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
B. Install coils in metal ducts and casings constructed according to SMACNA's "HVAC
Duct Construction Standards, Metal and Flexible."
D. Install moisture eliminators for cooling coils. Extend drain pan under moisture
eliminator.
F. Clean coils using materials and methods recommended in writing by manufacturers, and
clean inside of casings and enclosures to remove dust and debris.
C. Connect water piping with unions and shutoff valves to allow coils to be disconnected
without draining piping. Control valves are specified in Division 23 Section
"Instrumentation and Control for HVAC," and other piping specialties are specified in
Division 23 Section "Hydronic Piping."
A. Perform the following field tests and inspections and prepare test reports:
1. Operational Test: After electrical circuitry has been energized, operate electric
coils to confirm proper unit operation.
2. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes supply, installation and testing of Building Automation System
(BAS)
1.03 DEFINITIONS
A. Advanced Application Controller (AAC): A device with limited resources relative to the
Building Controller (BC). It may support a level of programming and may also be
intended for application specific applications.
C. Building Automation System (BAS): The entire integrated management and control
system.
D. Building Controller (BC): A fully programmable device capable of carrying out a number
of tasks including control and monitoring via direct digital control (DDC) of specific
systems, acting as a communications router between the LAN backbone and sub-LANs,
and data storage for trend information, time schedules, and alarm data.
F. Control Systems Server (CSS): This shall be a computer (or computers) that maintain
the systems configuration, historical trend data and programming database.
H. Local Area Network (LAN): General term for a network segment within the architecture.
Various types and functions of LANs are defined herein.
J. Operator Interface (OI): A device used by the operator to manage the BAS including
operator workstations, portable operator terminals and hand held devices.
1.04 SCOPE
C. The system shall permit unlimited expansion of both capacity and functionality through
the addition of sensors, actuators, DDC’s, PLC’s, ASC’s, and operator devices.
A. Arrangements shall be made for all system equipment to be able to withstand transient
disturbances from the input power supply. Surge Suppressors or other approved means
shall be fitted to all devices input and output points for protection against voltage
transients, spikes etc., where applicable.
B. Controllers shall be isolated against transient disturbances via optical couplers or other
approved means.
B. Structured Cabling System shall be used within the buildings as much as practicable
KEO/19-3262-0000 25 0000/1 Building Automation System (BAS)
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. In addition, proprietary specification cables most suited to each application as
recommended by manufacturer shall be used.
F. All new building automation system products on this project shall be provided by a firm
that is a registered ISO 9001:2000 manufacturer at time of bid.
1. The manufacturer of the Building Automation System digital controllers shall
provide documentation supporting compliance with ISO 9001:2000 (Model for
Quality Assurance in Design/Development, Production, Installation and
Servicing).
2. Provide a copy of the registration certificate that contains the ISO 9001:2000
Certification bearing the name of the registered auditor
G. All controllers provided as part of this system and used for indoor applications shall
operate under ambient environmental conditions of 0°C to 50°C dry bulb and 5% to 90%
relative humidity, non-condensing as a minimum.
I. Acceptable Products:
1. BACnet Testing Laboratory (BTL listed) using Device Profile BACnet Building
Controller (B-BC) or BACnet Advanced Application Controller (B-AAC)
2. LonMark certified with the appropriate Functional Profile to their application so
long as an appropriate LonMark Functional Profile
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
1.10 SUBMITTALS
B. Electronic Submittals: Control submittals and O&M information shall be provided as four
hard copies and electronically in Adobe PDF format. Control drawings shall be
KEO/19-3262-0000 25 0000/1 Building Automation System (BAS)
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
electronically provided in Adobe PDF in a size no less than 11”x17”. Documents will be
converted from their native electronic format directly to Adobe PDF format. Any text
documents scanned as images must be converted to a searchable text format using
OCR (Optical Character Recognition) and reduced in size prior to submission.
D. Product Data: Submit manufacturer's technical product data for each control device,
panel, and accessory furnished, indicating dimensions, capacities, performance and
electrical characteristics, and material finishes. Also include installation and start-up
instructions.
E. Samples: Material submittals, relevant samples shall also be submitted for approval.
F. Shop Drawings: Submit shop drawings for each control system. Submit a completed
drawing for each air handling unit, system, pump, device, etc. with all point descriptors,
addresses and point names indicated. Shop drawings shall be submitted both on paper
and electronic media. Each shop drawing shall contain the following information:
1. System architecture one-line diagram indicating schematic location of all control
units, workstations, gateways, etc. Indicate address and type for each control
unit. Indicate protocol and type of each LAN. The entire schematic shall be
updated, maintained and submitted.
2. Schematic flow diagram of each air and water system showing fans, coils,
dampers, valves, pumps, heat exchange equipment and control devices. Include
verbal description of sequence of operation. Where applicable indicate
equipment and devices operating via factory controller and details of BAS
interface to factory controller.
3. All physical points shall be indicated with names, descriptors, and point
addresses identified.
4. With each schematic, provide a detailed points list on the drawings with all
physical and virtual points included and functionally grouped. Include names,
descriptors, addresses and point types with applicable range as a minimum.
5. Label each control device with setting or adjustable range of control.
6. Label each input and output with the appropriate range.
7. Provide a Bill of Materials with each schematic. Indicate device identification to
match schematic and actual field labeling, quantity, actual product ordering
number, manufacturer, description, size, voltage range, pressure range,
temperature range, etc. as applicable.
8. Provide a Control Valve Schedule listing valve and actuator information including:
size, Cv, design flow, design pressure drop, manufacturer, model number, close
off rating, control signal, etc. Indicate normal positions of valves with fail
positions.
9. Provide a Control Damper Schedule listing damper and actuator information
including: size, material, blade arrangement, manufacturer, model number,
control signal, close off rating, etc. Indicate normal positions of automatic return
dampers.
10. Provide an Air Flow Monitoring Station Schedule listing the following information:
size, manufacturer, model number, control signal, CFM range, etc.
11. Indicate all required electrical wiring. Electrical wiring diagrams shall include
both ladder logic type diagram for motor starter, control, and safety circuits and
detailed digital interface panel point termination diagrams with all wire numbers
and terminal block numbers identified. Provide panel termination drawings on
separate drawings. Ladder diagrams shall appear on system schematic. Clearly
KEO/19-3262-0000 25 0000/1 Building Automation System (BAS)
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
differentiate between portions of wiring that are existing, factory-installed and
portions to be field-installed.
12. Provide details of control panels, including controls, instruments, and labeling
shown in plan or elevation indicating the installed locations and allocated service
clearances.
13. Points list including all physical I/O and virtual points. Points list shall be
provided in electronic format (EXCEL spreadsheet format is an acceptable
format).
14. Sheets shall be consecutively numbered.
15. Each sheet shall have a title indicating the type of information included and the
HVAC system or other MEP system controlled.
16. Table of Contents listing sheet titles and sheet numbers.
17. Legend and list of abbreviations.
G. Laminated Control Drawings: Provide laminated control drawings within each control
panel for the devices controlled from that panel. System control schematics shall be
mounted adjacent to key pieces of equipment for that system. Panel termination
drawings shall be mounted in proper document holder fixed on inside of the panel door
respective panels inside
I. Submit one complete set of programming and operating manuals for all digital
controllers concurrently with control logic documentation.
L. Manufacturers Certificates: For all listed and/or labeled products, provide certificate of
conformance.
B. Electronic copies of product data and control shop drawings updated to reflect the final
installed condition.
C. Record copies of approved control logic programming and database will be provided to
the Architect/ Engineer. Accurately record actual setpoints and settings of controls, all
BACnet objects and their properties, and actual sequence of operation, including
changes to programs made after submission and approval of shop drawings and
including changes to programs made during specified testing.
D. Record copies of approved project specific graphic software stored with backup.
E. Maintain project record documents throughout the warrantee period and submit final
documents at the end of the warrantee period
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the final design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
B. Following spare parts shall be furnished, properly packed and labelled with equipment
no. / location.
1. 4 # Pressure Transmitter for Air ducts of each type and size used.
2. 4 # Temperature Transmitter for Air ducts of each type and size used.
3. 2 # Pressure Transmitter for Chilled Water of each type and size used.
4. 2 # Temperature Transmitter for Chilled water of each type and size used.
5. 2 # Kilowatt transmitter of each type and size used.
6. 2 # Flow Control Valve Actuator for each type and size used.
7. 2 # Damper Actuator of each type and size used.
8. 4 # Differential Pressure Switches for fans of each type and size used.
9. 2 # Differential Pressure Switches for Pumps of each type and size used.
10. 4 # DDC Controllers of each type and size used.
11. 4 # VAV Damper motors/Actuators of each type and size used.
12. 8 # Room Temperature Sensors of each type and size used.
13. 8 # Pressure probes of each tyye and size used,
14. 4 # VAV controllers of each tyoe and size used.
15. 4# Air flow transducers at VAVs of each type and size used.
16. 2 # Air Flow Measure stations of each type and size used.
17. 2 # Air Velocity Sensors of each type and size used.
18. 1 # Outdoor Air Temperature Sensor.
19. 1 # Outdoor Air Humidity Sensor.
20. 4 # Printer Ribbons.
21. 1 # Toner cartridges for Laser printer.
22. 1 # Battery for Network Controller.
23. 1# Back up Battery for Laptop Computer.
24. 2 set Cartridges for color printer
A. Provide factory shipping cartons for each piece of equipment and control device.
Maintain cartons during shipping, storage and handling as required to prevent
equipment damage, and to eliminate dirt and moisture from equipment. Store
equipment and materials inside and protect from weather.
A. The BAS and components shall be listed by Underwriters Laboratories (UL 916) as an
Energy Management System.
KEO/19-3262-0000 25 0000/1 Building Automation System (BAS)
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. The BAS shall be listed by Underwriters Laboratories (864) UUKL for supervised smoke
control.
PART 2 - PRODUCTS
B. The system elements shall form an open, interoperable system configured for multi site
access and control.
C. The system shall be fully integrated with third party vendor equipment for all aspects of
the system control and management.
D. The basic elements of the system structures shall be manufacturer's latest standard
products that comply with the specification requirements and are kept in inventory by the
BAS supplier / manufacturer. The components shall not require customizing, other than
adding software programming to perform required functions.
E. The system shall have standalone capability in the event of a network failure. Failure of
any single component or network connections shall not interrupt the execution of control
strategies at the operational devices. In the event of a power failure the BAS controllers
shall continue to be fully operational with full time program capability.
F. The system shall allow standard graphics to be created for configurable devices so that
it is possible for all instances of points for the same device type to use the same
graphic.
G. All starters such as VFD, and other BAS components such as DDC, should match MEW
regulation to withstand severe ambient temperature.
I. Security
KEO/19-3262-0000 25 0000/1 Building Automation System (BAS)
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Data Security shall be assured. Up to date authentication and encryption
techniques shall be used to prevent unauthorized access.
2. Password Protection: A minimum of three levels of password access protection
shall be provided to allow the user / manager to limit control, display, and data
base manipulation capabilities as he deems appropriate for each user, based
upon the assigned password. Passwords shall be exactly the same for all
operator devices. Access shall be supported, for example:
a. Level 1 - Data Access and Display
b. Level 2 - Level 1 + Operator Overrides and Commands.
c. Level 3 - Level 2 + Database Generation and Modification
3. A minimum of four passwords shall be supported at each MMI.
4. User-definable, automatic log-off timers of from 1 to 60 minutes shall be provided
to prevent operators from inadvertently leaving devices logged on.
J. Networking / Communications
1. The system design shall have the ability to monitor and control the system either
via a local network or remotely using standard web browsers through LAN /
Internet.
2. Local Area Network
a. Ethernet TCPIP (Intra-building LAN and Inter-building Campus LAN) shall
be used for operator communication. The network architecture is shown on
drawings.
b. General Network Design:
1) Commonly available, multiple-sourced, networking components
shall be used.
2) Use of an approved, industry standard protocol
3) Access to system data shall not be restricted by a hardware
configuration of the system.
4) All operator devices shall have the ability to access all point status
and application data on the network.
5) Global Data Sharing shall allow point data to be shared between
controllers
K. Supervisory control
1. Server PC and Operating System
a. Web based supervisory software shall not require any proprietary
software to be installed on the Operators workstation.
2. Supervising the BAS System
a. The supervisor shall directly connect to the Controller’s internal / external
web server.
b. The web server shall retrieve logged point data and alarm data if required.
The web server shall provide central alarm management for the entire
system.
c. The web server shall provide central management of logged data for all
input and output
3. Browser Clients
a. The server shall be capable of supporting a minimum of 4 concurrent
clients using Microsoft Internet Explorer or equivalent approved.
b. The web pages shall allow these minimum functions:
1) Displaying of real-time values automatically without requiring a
manual ‘refresh’ of the web page.
2) All graphics shall be stored in the web server without a need for
storage of graphical screens on the client machine.
3) Support for animations in HTML pages
KEO/19-3262-0000 25 0000/1 Building Automation System (BAS)
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4) Automatically created tables for alarms, set-points, hardware
points and virtual points without the need to create graphics.
5) Automatically created menus and corresponding HTML pages for
data logs and data log groups without the need to create graphics.
6) Automatically created network page with navigation to other
Communication Controllers.
A. These shall be BACnet Building Controller profile modular controllers that utilize 32 bit
processors and integrate all control and management functions. Distributed I/O Modules
shall be connected to the Controller.
B. Data Communication
Data communication shall be achieved utilizing:
1. Integrated Ethernet 10/100 Base-T interface for direct communication over IP
networks.
2. Integrated LonWorks interface for direct integration of LonWorks and LonMark
devices, such as distributed I/O modules, Room & Zone controllers or building
automation controllers.
C. The controller shall have an Integrated XML web-server for the full operation of all
application related functionality, data points, time schedules, calendars, parameters,
historical data (trending), data points, alarm buffer, operational hours counter via
standard Browser, such as Internet Explorer. Login shall be with username and
password.
D. There shall be no limit to the number of BACnet objects configured in the controller it
shall have the capability to have minimum 300 Lon network variables.
E. The controller shall be capable of flexible memory expansion at any stage of the product
life.
F. Controller scheduling: a scheduling tool shall be provided for creating, editing and
maintaining controller time schedules. The controller scheduling tool shall be
constructed in a way that allows full compatibility with new controller types.
The controller scheduling tool shall have integrated graphical interface that allows
downloading of schedules to several controllers in a single operation.
G. The controller shall be capable of being constructed with many different combinations of
physical inputs and outputs both analog and/or digital. In addition, it should have analog
and digital software points, including pseudo and global points.
1. Input or output modules of any one type shall be capable of being connected to
the same Controller .
2. The I/O modules shall be LonMark® Association-compliant. The connection to
the Controller shall be via a 2-wire LonWorks® bus. Proprietary communication
will not be acceptable.
3. The remote input/output modules shall consist of the I/O module itself and a
wiring terminal subbase, which allows for direct wiring to the corresponding field
equipment (sensors, actuators, etc.). The wiring subbase shall provide all
required field terminals, i.e. one terminal per signal plus a separate ground for
every signal.
J. Programming:
K. Global Data:
1. A single process shall be able to incorporate measured or calculated data from
any and all other DDC Controllers or Other Controllers on the network. In
addition, a single process shall be able to issue commands to points in any and
all other DDC Controllers or application specific controllers on the network.
L. Messaging:
1. Processes shall be able to generate operator messages and advisories to
operator I/O devices. A process shall be able to directly send a message to a
specified device or cause the execution of a dial-up connection to a remote
device such as a printer or pager.
2. The system shall be able to be set to alert the operator in the form of emails or
SMS and screen alarms so the problems can be taken care of immediately
M. Data Logging:
1. DDC Controllers shall store point history data for selected analog and digital
inputs and outputs.
2. Any point, physical or calculated may be designated for data logging.
3. Adjustable sample intervals shall be provided for Time Interval Data logs. Each
DDC Controller shall have a dedicated RAM-based buffer for data logs and shall
be capable of storing a minimum of 64,000 data samples in total.
2.05 HARDWARE
B. Workstation
1. The Workstation shall comprise the following minimum hardware:
a. Intel Core i7 Processor running at a minimum of 2.7 GHz
b. Min 64 GB DDR4
c. High end graphic card with DVI video out. Two graphics cards shall be
required to support 4 LCD monitors.
d. 1 TB SSD Hard disk drive.
e. DVD +/-RW drive capable of playing DVD and CDROM discs, and
recording on DVDRW, DVDR, and CDRW disks
f. 4 x USB ports
g. Ethernet network card
h. Keyboard and Mouse: 12 function-key keyboard and Mouse pointing
device, preferably optical
2. Operating System Software at the Workstation shall comprise of:
a. Windows 10 or later
b. TCP/IP Networking
c. Graphic Display Building Editor
d. Application software
e. The networking software shall use the industry standard TCP/IP LAN
protocol.
f. All system peripherals shall be capable of being connected to the server
computer via the LAN.
g. Browser: Internet Explorer/ Edge
C. Printers
1. High-quality, high-speed laser printers for hardcopy system printouts.
2. The printer shall be multi font, Color output.
3. It shall have a minimum operating speed of 200 characters / second or higher
4. Printer shall be formatted to print on standard A3 and A4 paper.
5. Minimum of 300 dpi.
6. Refer the system drawings for the location and quantity of the printers.
A. General: A state of the art Portable Operator's Terminal (POT) shall be provided for
readout of system variables; override; control and adjustment of parameters. The POT
will be handheld and plug directly into individual controllers for power and data.
B. The POT shall be capable of system-wide information from anywhere in the system.
D. POT shall be complete with command keys, data entry keys, cursor control keys and a
24-character liquid crystal alphanumeric display. Access is to be via self-prompting
menu selection with arrow key control of next menu/previous menu and step
forward/step backward within a given menu.
E. Connection of a POT to a controller shall not interrupt nor interfere with normal peer
network operation in any way, prevent alarms from being transmitted, or preclude
central initiated commands and system modification.
A. General
1. All necessary software to form a complete system shall be provided. The
operating system shall be the latest WINDOWS
2. The software programs specified in this section shall be provided as an integral
part of the relevant system components, and shall not be dependent upon any
higher-level computer for execution.
3. Provide all software updates and verify operation in the system. These updates
shall be accomplished in a timely manner, fully coordinated with the system
operators, and shall be incorporated into the operations and maintenance
manuals, and software documentation.
C. Calendars
1. Monthly calendars for a 60-month period shall be provided which allow for
simplified scheduling of holidays and special days in advance. Holidays and
special days shall be user-selected with the pointing device and shall
automatically reschedule equipment operation.
D. Help
1. Help shall be available for all applications and shall provide the relevant data for
that particular screen.
E. Energy Management Applications: Digital Panels shall have the ability to perform any or
all of the following energy management routines
1. Time of Day Scheduling
2. Calendar Based Scheduling
3. Holiday Scheduling
4. Optimal Start
5. Optimal Stop
6. Heating/Cooling Interlock
7. Average/High/Low Signal Select and Reset
F. All programs shall be executed automatically without the need for operator intervention,
and shall be flexible enough to allow user customization. Programs shall be applied to
building equipment described in the "Automatic Control Sequence, Section
KEO/19-3262-0000 25 0000/1 Building Automation System (BAS)
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Optimal Run Time:
a. The Optimal Run time (ORT) program shall control the start-up and
shutdown times of HVAC equipment during both the heating and cooling
seasons to provide the most efficient operating strategy during potentially
energy wasteful periods of the day. The ORT program shall base it
control decisions primarily upon occupancy schedules, outside air
temperature, seasonal requirement, interior room mass temperature of the
building etc.
b. For start-up, ORT program shall use outside air temperature / room mass
temperatures etc. to "learn" the building's thermal characteristic through
an adaptive modeling technique. The adaptive model shall allow the
system to predict how long the building shall take to warm-up (Heating
and buildings shall take to warm-up (Heating mode) or cool-down (cooling
mode) under different outside and inside temperature conditions.
c. For shutdown, ORT program shall use the outside air temperature and
other required factors to determine how early it can shutdown the system
without adversely affecting ventilation requirements.
d. The ORT program shall analyze multiple buildings mass sensors to
automatically determine the seasonal mode and worst case condition for
every day of the year. Analysis shall require occupancy schedule date and
desired mass temperatures etc
e. Optimization Program: This program shall calculate automatically the
optimum start and stop times for HVAC plant consistent with internal and
external temperatures in order to conserve energy
G. Chiller Manager
1. The Chiller Manager (CM) feature shall be controlled and serviced by the Energy
Manager, which is the supervisory program which coordinates the activities of all
energy application features. The Chiller manager shall be a supervisory program
overseeing the functions of Chilled Water Temperature Rest and Chiller
sequencing. The Chiller manager shall be provided to support either Imperial or
Metric units of measurement.
2. Each Chiller manager system shall be assigned a unique identifier and expanded
identifier. The expanded identifier shall be used further identify or label the CM
system.
3. Chiller Manager System, points and parameter shall be defined on-line by the
user. Any addition, modifications, or deletions shall be made on-line.
a. Chilled Water Reset: Chilled water Reset (CHR) program shall be
provided to automatically reset the chilled water temperature to the
highest possible value which will still satisfy the cooling coil requiring the
greatest cooling.
b. Condenser Water Reset: Condensate Water Reset (CWR) program shall
be provided to automatically reset the condenser valve which will still
satisfy the outside wet bulb temperature and the load being handed by all
chillers on the condenser loop.
4. The BAS shall completely integrate with the chillers by taking the values directly
from the microprocessor for its complete control, however the internal chiller
management shall be carried out by the chillers own controls.
J. Alarm Management: alarm management shall be provided to monitor, buffer, and direct
alarm reports to operator workstations filter alarms to minimize operator interruption due
to non-critical alarms.
1. Point Change Report Description: All alarm or point change reports shall include
the point's description and the time and date of occurrence.
2. Prioritizing: the user shall be able to define the specific system reaction for each
point. Alarms shall be prioritized to minimize nuisance reporting and to speed
operator response to critical alarms. A minimum of three priority levels shall be
KEO/19-3262-0000 25 0000/1 Building Automation System (BAS)
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
provided. Users shall have the ability to manually inhibit alarm reporting for each
point. The user shall also be able to define condition under which need to be
acknowledged by an operator, and/or logged for analysis at a later date.
3. Report Routing: Alarm reports and messages shall be directed to an operator
device.
4. Alarm Messages: In addition, to the point's description and the time and date,
the user shall be able to print, display or store a 60-character alarm message to
more fully describe the alarm condition and / or operator response.
5. Selected alarms shall be routed to mobile phones / PDA’s / email, exact
requirements to be advised by Project Manager during system commissioning
stage
6. Remote Alarm Horn: The alarm horn feature shall be silenced when the critical
alarm is acknowledged.
K. A data collection utility shall be provided to automatically sample, store, and display
system data.
1. Provide data logging capabilities that allow the user to easily monitor and
preserve records of system activity over an extended period of time. Any system
point may be data logged automatically at time-based intervals or changes of
value (Time–Stamped Data logs), both of which shall be user-definable. Data log
data shall be automatically stored for future diagnostics and reporting.
2. Data log report graphics shall be provided to allow the user to view all data
logged point data. Reports may be customized to include individual points or pre-
defined groups of up to 6 points. Provide additional functionality to allow any data
logs to be transferred easily to an off-the-shelf spreadsheet package such as
Microsoft Excel either from archived data on hard disk or directly from any
controller in real time. This must allow the user to perform custom calculations
such as energy usage, equipment efficiency and energy costs and allow for
generation of these reports on high-quality plots, graphs and charts.
3. Provide additional functionality that allows the user to view trended data on data
log graph displays. Displays shall be actual plots of both static and/or real-time
dynamic point data. A minimum of 6 points may be viewed simultaneously on a
single graph, with color selection and line type for each point being user-
definable.
4. Provide capability to print any graph on the system printer for use as a building
management and diagnostics tool.
5. It shall be possible for any point in the BAS system to be data logged on a time
interval basis in real-time on the operator’s workstation PC.
6. All graphical trend displays of data shall be capable of multiple display styles,
including but not limited to 2-D and 3-D line, bar and pie charts.
L. Runtime Totalization: DDC shall automatically accumulate and store runtime hours for
binary input and output points specified in the "Execution" portion of this specification.
1. The user shall have the ability to define a warning limit for Runtime totalization.
Unique, user-specified messages shall be generated when the limit is reached.
M. Event Totalization: DDC shall have the ability to count events, such as the number of
times a pump or fan system is cycled on and off.
1. The Even Tantalization feature shall be able to store the records associated with
a minimum of 9,999,999 events before reset.
2. The user shall have the ability to define a warning limit. Unique, user-specified
message shall be generated when the limit is reached.
A. The BAS system server shall be based around the Microsoft Windows 32/64 bit multi-
tasking environment, Windows 2010 or latest. The BAS system shall be a true 32-bit
application to take advantage of Microsoft Windows enabling technologies.
B. Standard services supported by the server computer operating system will include the
following:
1. Multi-tasking Multi-user support
2. TCP/IP Network Support with firewalls filtering internet traffic.
3. Graphic Display Building Editor
4. Application software
5. Check pointing and recovery as in Windows Server 2010 or latest
A. The BAS system server shall consist of BAS application software and database and
utilities for backup.
C. Complete latest version of Microsoft Office Suite software shall be provided having
Microsoft Word, Excel, PowerPoint, Access, etc
A. The workstations will come equipped with web browser and graphics applications and
run-time libraries, network management software, intrusion detection software, database
backup tools, and virus scan software with live virus update.
Sensors shall be capable of sensing the range expected for the point at the specified
accuracy. Input / output sensors and devices shall be closely matched to the
requirements of the DDC for accurate, responsive, noise free signal input / output.
A. Temperature Sensors
Passive temperature sensors with NTC 20K ohm, Balco500 and PT1000 elements shall
be used for different applications.
1. Outdoor temperature sensors (also combined with humidity sensors) with extra
covers for protection and shielding the sun. Prewired and terminal block versions
shall be available. Their temperature range shall be –40 to +60°C.
2. Earth temperature sensors for greenhouse applications. These prewired NTC 20
sensor shall be rated to IP65. Their temperature range shall be –50 to +90°C.
3. Room temperature sensors (also combined with setpoint adjustment and
fan/presence switches). These shall be available with NTC 20, PT1000 and
Balco500 elements in an attractive, appealing housing, with terminal blocks for
D. Humidity Sensors
Active humidity sensors shall be available in combination with temperature sensing with
NTC 20K ohm, Balco500 and PT1000 elements for different applications. The operating
voltage for the capacitive humiditiy sensing element shall be 24V. The following types
shall be available:
1. Outdoor humidity sensors with terminal blocks and a temperature range of –30
to .+50°C.
2. Capacitive room humidity sensors with NTC 20, PT1000 and Balco500
temperature sensors, and with terminal blocks, output for humidity of 0 to 1 or 0
to 10V, and a temperature range of –0 to .+50°C.
3. Capacitive air duct humidity sensors with NTC 20, PT1000 and Balco500
temperature sensors, and with terminal blocks, output for humidity of 0-1 or 0-
10V, a temperature range of –0 to +50°C, and mountable on the air duct.
4. Duct mounted sensors shall be provided with a sampling chamber.
5. Wall mounted sensors shall be provided with covers identical to temperature
sensors.
E. Pressure Transmitters
1. Differential pressure transmitters shall be used for controlling pressure in air
conditioning or other ventilation applications, such as filter monitoring, pressure
or flow control, maximum pressure control, etc. The transmitters can be used for
overpressure, vacuum or differential pressure measurement with non-aggressive
G. Pressure Transmitters for Heating, District Heating, Cooling and Other Applications
These pressure transmitter shall be available with welded stainless steel sensors, an
output signal of 0 to 10V, supply voltage of 24Vac +/- 20 % or 24-26Vdc, pressure
ranges selectable by jumper, zero point adjustment by potentiometer, and shall conform
to protection class IP 65. The following pressure ranges (selectable by jumper) shall be
available:
1. 0-1 / 0.5 / 0.2 bar max 3 bar
2. 0-3 / 1.5 / 0.6 bar max 7.5 bar
3. 0-6 / 3 / 1.2 bar max 18 bar
4. 0-10 / 5 / 2 bar max 30 bar
5. 0-25 / 12.5 / 5 bar max 70 bar
6. 0-40 / 20 / 8 bar max 80 bar
7. A 2-½ digit LED display module shall also be available. These transmitters shall
be available in LON versions conforming to pressure profile 1030, with service
and operation LED visible and Neuron button accessible from outside.
H. Differential Pressure Transmitters for Heating, District Heating, Cooling and Other
Applications
These pressure transmitters shall be available with a welded stainless steel sensor, a
pressure connection G ½” (DIN 16 288), an output signal of 0 to 10V, a supply voltage
of 24Vac +/- 20 % or 24-26Vdc, pressure ranges adjustable through zero point and end
point potentiometer, and shall conform to protection class IP 65. The following types
shall be available:
1. pressure range smallest range max. pressure
2. 0-500 mbar, 125 mbar 10 bar
3. 0-1 bar, 250 mbar 15 bar
4. 0-2.5 bar 0.7 bar 15 bar
5. 0-5 bar 1.25 bar 15 bar
6. 0-10 bar 2.5 bar 25 bar
7. A 2-½ digit LED display module shall also be available. These transmitters shall
be available in LON versions conforming to pressure profile 1030, with service
and operation LED visible and Neuron button accessible from outside.
B. Type for standard applications: Parallel or opposed blade design with optional closed-
cell neoprene edging.
C. Type for low-leakage applications: Parallel or opposed blade design with inflatable seal
blade edging or replaceable rubber seals, rated for leakage at less than 10 cfm/ft2 of
damper area, at differential pressure of 1,000 Pa (4 inch WG) when damper is being
held under torque of 22.7 Kg (4.17 ft-lb).
D. Outside air dampers shall have adjustable minimum settings so that ventilation can be
adjusted for each space or room.
A. General: Designed to high quality specifications for reliable long time use, with the
following:
1. Equal percentage or modified parabolic flow characteristics, rangeability of 30:1
for fan-coils and VAV reheat coils and 50:1 for large coils
2. Actual valve coefficient value (Cv) shall not deviate from the curve Cv and quoted
CV by more than 10 %
3. Adjustable stroke limitation, pressure compensation and integrated flow control to
ensure optimisation in hydraulic systems with high differential pressures and high
temperatures.
4. Optimised range, leakage rate, temperature range and close-off pressure.
5. Metal to metal seating and self-adjusting packing to ensure long life, where
appropriate.
6. Indicators clearly marked to show fully open and closed positions
B. Two-way Valves:
1. Type: Bronze with threaded ends (up to and including 50 mm ND) ductile / cast
iron with flanged ends (65 mm ND and above), globe pattern, two port valve with
the polished stainless steel trim and spring-loaded, self-adjusting, Teflon packing.
2. Control valves shall be selected for a maximum pressure drop of 34.5 kPa (5
psig) and shall be either equal or one size smaller than pipe size
3. The seat shall be replaceable type of chrome nickel.
4. The spindle/stem shall be stainless steel.
5. Plug shall be made of stainless steel for sizes less than 100 mm, for 100 and
larger it shall be made of gun metal/bronze.
6. Valves to have either replaceable composition disk or stainless steel ball.
7. Two way valves shall be modulating type.
C. Three-way Valves:
1. Type: Bronze with threaded ends (up to and including 50 mm ND) / cast iron with
flanged ends (65 mm ND and above), globe pattern, three port valve with
polished stainless steel trim and spring-loaded, self-adjusting, Teflon packing
A. Water Flow Switches: UL listed, adjustable differential pressure or flow type as specified
in the sequence of operation or data point summary. Devices shall be pressure rated, as
required. Differential pressure switches shall have manifold with isolating valve for
servicing. Water flow switches shall open an electrical contact as the differential
pressure falls below a pre-adjusted pressure range setting
B. Water Flow Sensors: Analogue, solid state, precision, industrial type with stainless steel
meter body, flow element and manifold with isolating valves for calibration and
maintenance. Maximum error shall not exceed 0.5% of range. Pressure rated as
required.
A. The outside air monitoring station shall consist of outside air temperature and relative
humidity sensors at roof level. The sensors shall be shielded from direct sunlight, and
shall be located away from any exhaust air outlets or other sources of heat which could
affect the accuracy of the temperature reading. The temperature and relative humidity
shall be transmitted globally to all systems requiring these values.
PART 3 - EXECUTION
3.01 COORDINATION
A. Contractor shall ensure that the work under this section shall not adversely affect the
work of other trades. Where work is installed in close proximity to or will interfere with
KEO/19-3262-0000 25 0000/1 Building Automation System (BAS)
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
work of other trades, the Contractor shall work out satisfactory arrangements for the
approval of the Engineer.
B. At the operator’s workstation, sufficient 13A mains sockets shall be provided by the
electrical contractor to prevent the need for distribution adapters. Refer to drawings.
3.02 INSTALLATION
A. Forward to the Engineer submittal data relevant to valve schedules damper schedules
and other pertinent equipment information requiring approval prior to field installation.
Upon receipt of approval, proceed with installation, set up, calibrating and checking out
the various control and monitoring system
B. Conduits and wiring shall be properly supported and run in a neat and workmanlike
manner; run parallel to or at right angles to building structure when exposed and in
equipment rooms.
C. Wiring shall be installed in such a way that minimizes coupling of electromagnetic and
electrostatic interference on low voltage signals and data wiring, in order to avoid
disturbance of DDC equipment operation. This shall preferably be achieved by, but not
limited to:
1. Physical separation of greater than 50 mm between the power supply cables and
the signal and data cables
2. Use of braided screen mains cable, dressed close to metalwork, where mixed
wiring is unavoidable (Tenderers shall clearly specify the methods by which he
intends to eliminate any such interference with his signal and data transmission)
D. DDC shall be protected from interference by the operation of hand held radio
transmitters, radio pagers, etc., within 1 meter of the equipment.
E. Any modifications made to the system shall be incorporated into the operations and
maintenance manuals, and other documentation affected.
3.03 VERIFICATION
A. When installation of the system is complete, Forward to the Engineer data relevant to
point index, functions, limits, sequences, interlocks, and other pertinent information for
the system
B. Prior to on-line operation, calibrate equipment, verify transmission media operation and
perform in the presence of the Engineer a complete demonstration and readout of the
computer real-tile responsibilities of surveillance and command. This demonstration,
having satisfactorily met previously approved submittals, shall, with the Engineers
written acceptance, allow commissioning of the Building Automation System for on-line
operation.
F. Provide a cross-check of each control point within the system by making a comparison
between the control command and the field-controlled device.
G. Verify that all systems are operable from local controls in the specified failure mode
upon panel failure or loss of power.
I. All high priority alarm conditions to be simulated and the appropriate workstation
display/printer/pager/email etc responses verified.
K. The BAS Contractor shall revisit the site after handover to check and adjust the
parameters for BAS control to optimize settings.
A. Demonstration of the BAS system to the End User for acceptance shall be carried out
after a full system test has been passed and two weeks’ notice has been given to the
Architect/ Engineer.
1. Field Equipment Demonstration shall include but not limited to the followings:
a. Automatic control operation shall be verified by introducing an error into
the system and observing the proper corrective system response.
b. Selected time and set point schedules shall be verified by changing the
schedule and observing the correct response on the controlled outputs.
c. An output channel will be commanded (on/off, stop/start, adjust, etc.) and
operation verified.
d. An analog input channel will be verified for proper operation as displayed
at the operators workstation.
e. A digital input channel will be verified by changing the state of the field
device and observing the appropriate change of displayed value.
f. Typical occupancy control device function shall be demonstrated.
g. If a point should fail testing, perform necessary repair action and retest
failed point and all interlocked points.
2. Workstation Demonstration shall include but not limited to the followings:
a. Communication with typical Main Plant and ASC controllers will be
demonstrated.
b. Operator commands will be explained and demonstrated.
c. Selected control sequences shall be demonstrated for proper operation.
d. Review of Time Schedules and Alarm priorities.
e. Selected system reports and logs shall be demonstrated at the System
Workstation.
f. Correct system start-up and shutdown procedures shall be demonstrated.
g. Selected controllers shall be demonstrated to operate in a standalone
mode.
KEO/19-3262-0000 25 0000/1 Building Automation System (BAS)
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
h. The contractor shall demonstrate on-site all of the software features
contained in this specification
3. The specialist BAS Contractor shall commission and handover the system to the
client or client’s representative on a point-to-point basis.
4. Services of competent personnel, having at least five (5) years’ experience in the
field and who have gained an intimate understanding of the project throughout its
design stages, shall be provided by the Contractor to commission the BAS.
5. Contractor shall prepare and submit a programme of commissioning; clearly
stating other disciplines involved and services required for each activity.
6. Where work is being carried out in an occupied building the management of the
building shall be kept fully informed regarding the nature of the testing and
commissioning. Steps shall be taken to ensure that any possible hazards or
inconvenience that may arise due to the testing and commissioning shall be
minimized.
7. System Handover shall include but not limited to the followings:
a. Any issues required corrective actions to be documented and agreed date
determined for clearance.
b. All access levels and passwords recorded and backed up.
c. Four Copies of all system and database files supplied on CD with
appropriate identification.
d. An Operator's Reference Table listing the addresses of all connected
points. Settings shall be shown where applicable.
e. Four bound hardcopies of Maintenance manuals including datasheets for
each item of equipment.
f. Two bound hardcopies of Operations manuals including safety checks
and start-up and close down procedures.
g. Six (6) hardcopies of BAS system drawings matching the installed
networks, equipment and peripheral connections, plus two soft copies of
CAD drawings on separate CDs.
h. Two bound hardcopies of the Flow charts of the control software
programs utilized in the Temperature Control System.
i. Two bound hardcopies of the Control Programs used in each DDC
controller.
j. Consumables, printer ribbons, printer paper at agreed levels.
k. All keys necessary for access to panels and equipment.
l. Training of engineers and operators to be checked complete or program
for completion agreed.
m. Operating and maintenance cautions and instructions.
n. Recommended spare parts list with contact details for suppliers.
A. Provide operator instruction both prior to Substantial Completion of the Project and
throughout the Maintenance Period. During Defects Liability Period Operator(s) to
attend at Site.
B. The BAS Contractor shall provide detailed on-site and off-site operation and
programming training to selected client staff. Training will be carried out separately for
both engineering and operator staff. Factory trained control engineers and technicians
shall provide training sessions for the client’s personnel. Training shall include but not
limited to the followings:
1. Explanation of drawings, operations and maintenance manuals
2. Overview of HVAC system
KEO/19-3262-0000 25 0000/1 Building Automation System (BAS)
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Walk-through of the job to locate control components.
4. Operator workstation and peripherals.
5. Operation of portable operator's workstation including any wireless equipment.
6. Use of Occupancy Controls.
7. Use of Keypad/Display devices with customized menus.
8. Use of Overrides and Passwords.
9. Use of Data logs, Time Schedules and Alarms handling.
10. Communication Controller, DDC Controller, ASC operation/function.
11. Operator control functions including graphic generation and field panel
programming.
12. Explanation of adjustment, tuning, calibration and replacement procedures
C. Since the Client may require personnel to have more comprehensive understanding of
the hardware and software, additional training must be available from the BAS
Contractor. If such training is required by the Client, it will be contracted at a later date at
no additional cost.
A. Control sequences are specified in "Sequence of Operations for HVAC Controls" section
23 0993 of HVAC specifications.
3.07 MAINTENANCE
A. Maintenance Period: 2 years from date of Substantial Completion of the project or until
issuance of final completion certificate.
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
END OF SECTION
Equipment/Function Description
Trip Status
x
x
Auto/Manual-HOA Status
Smoke Detector
x
Diff.Pressure switch
Pulsed KWHr Meter
DIGITAL INPUT
Temperature
Humidity
Damper/valves Actuators Feedback
CO Sensor
NO2 Sensor
CO2/Air Quality Sensor
Level Sensor
BTU Transmitter
Flow in USGPM
Flow in CFM
Pressure / DPSensor
Velocity Sensor
The number of points listed is the minimum. Contractor shall provide any additional point to make sure the system fully complete and fully functional without any additional cost to client
Kilowatt
Valves Control
Enable/Disable
x
x
Start/Stop
Open/Close
DIGITAL
OUTPUT
BACnet Data
x
x
Graphics
x
x
General Alarm
x
x
Critical Alarm
x
x
Maintenance Alarm
Chillier Optimization
Time Program
Sequence Control
SOFTWARE
Energy Calculation
Reports
Remarks
BAS POINT SCHEDULE Project: 19-3262-0000, 12NHC- C12 - Children Club
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
Cooling coil shall be controlled by VRF
VAV Air Handling Units ,
controller and rest of the points shall be
AHU Nos.(Refer to Plans)
controlled by DDC/BMS
Supply Fan with VFD ─ x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x
Return /Exhaust Fan with VFD ( If Applicable refer to the equipment schedule). x x x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Air Ducts ( If Applicable refer to the equipment schedule). ─ x x x x x x
Mixed Air ─ x x x
Filters ─ x x x x x x
Dampers ─ x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Heating Coil Control (where required refer schedules) ─ x x x x x
CO2 Sensor Interlocked with Fresh Air Inlet Motorized damper. x x x x x x x
Cooling coil shall be controlled by VRF
Energy Recovery Unit ERU (ALL ERUs) controller and rest of the points shall be
controlled by DDC/BMS
Supply Fan with VFD Interlocked with Supply Air Flow Differential Pressure ─ x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Fan with VFD Exhasut Air Flow Differential Pressure ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x x x
Outside Air Duct ─ x x x x x x x x
Return/Exhaust Air Ducts ─ x x x x x x x x
Supply Air Filters ( All Filters) ─ x x x x
Exhaust Air Filters ─ x x x x
Dampers ─ x x x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Thermal Wheel ─ x x x x x x x x x x
Heating Coil Control ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
Cooling coil shall be controlled by VRF
VAV Air Handling Units ,
controller and rest of the points shall be
AHU Nos.(Refer to Plans)
controlled by DDC/BMS
Supply Fan with VFD ─ x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x
Return /Exhaust Fan with VFD ( If Applicable refer to the equipment schedule). x x x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Air Ducts ( If Applicable refer to the equipment schedule). ─ x x x x x x
Mixed Air ─ x x x
Filters ─ x x x x x x
Dampers ─ x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Heating Coil Control (where required refer schedules) ─ x x x x x
CO2 Sensor Interlocked with Fresh Air Inlet Motorized damper. x x x x x x x
Cooling coil shall be controlled by VRF
Energy Recovery Unit ERU (ALL ERUs) controller and rest of the points shall be
controlled by DDC/BMS
Supply Fan with VFD Interlocked with Supply Air Flow Differential Pressure ─ x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Fan with VFD Exhasut Air Flow Differential Pressure ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x x x
Outside Air Duct ─ x x x x x x x x
Return/Exhaust Air Ducts ─ x x x x x x x x
Supply Air Filters ( All Filters) ─ x x x x
Exhaust Air Filters ─ x x x x
Dampers ─ x x x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Thermal Wheel ─ x x x x x x x x x x
Heating Coil Control ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
Cooling coil shall be controlled by VRF
Energy Recovery Unit ERU (ALL ERUs) controller and rest of the points shall be
controlled by DDC/BMS
Supply Fan with VFD Interlocked with Supply Air Flow Differential Pressure ─ x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Fan with VFD Exhasut Air Flow Differential Pressure ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x x x
Outside Air Duct ─ x x x x x x x x
Return/Exhaust Air Ducts ─ x x x x x x x x
Supply Air Filters ( All Filters) ─ x x x x
Exhaust Air Filters ─ x x x x
Dampers ─ x x x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Thermal Wheel ─ x x x x x x x x x x
Heating Coil Control ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
VAV Air Handling Units ,
AHU Nos.(Refer to Plans)
Supply Fan with VFD ─ x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x
Return /Exhaust Fan with VFD ( If Applicable refer to the equipment schedule). x x x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Air Ducts ( If Applicable refer to the equipment schedule). ─ x x x x x x
Mixed Air ─ x x x
Filters ─ x x x x x x
Dampers ─ x x x x x
Refrigerant Flow Control Command/Set Point Command ─ x x x BACnet Analog Out for Flow Control Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Heating Coil Control (where required refer schedules) ─ x x x x x
CO2 Sensor Interlocked with Fresh Air Inlet Motorized damper. x x x x x x x
Energy Recovery Unit ERU (ALL ERUs)
Supply Fan with VFD Interlocked with Supply Air Flow Differential Pressure ─ x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Fan with VFD Exhasut Air Flow Differential Pressure ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x x x
Outside Air Duct ─ x x x x x x x x
Return/Exhaust Air Ducts ─ x x x x x x x x
Supply Air Filters ( All Filters) ─ x x x x
Exhaust Air Filters ─ x x x x
Dampers ─ x x x x x x x
Refrigerant Flow Control Command/Set Point Command ─ x x x BACnet Analog Out for Flow Control Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Thermal Wheel ─ x x x x x x x x x x
Heating Coil Control ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
VAV Box with Electric Reheat- Modulating Volumetric Damper- (Shutoff Type)
Applicable for VAV A/C Systems. Refer to the
Modulating Volumetric Damper- Damper Control ─ x x x x x x
drawings and equiptment schedules.
Zone Temperature ─ x x x x x
Heating Coil Control (where required) ─ x x x x x
Life Safety Smoke Ventilation Systems
Make up Air Fans with VFDs ─ x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Smoke Exhaust Fans ─ x x x x x x x x x x
Trip Status
x
x
Auto/Manual-HOA Status
Smoke Detector
x
x
Diff.Pressure switch
Pulsed KWHr Meter
DIGITAL INPUT
`Flow Switch
x
Temperature
Humidity
x
Flow in USGPM
Flow in CFM
Pressure / DPSensor
x
Velocity Sensor
The number of points listed is the minimum. Contractor shall provide any additional point to make sure the system fully complete and fully functional without any additional cost to client
Kilowatt
Valves Control
ANALOG OUTPUT
Enable/Disable
x
x
Start/Stop
Open/Close
DIGITAL
OUTPUT
BACnet Data
x
x
Graphics
x
x
General Alarm
x
x
Critical Alarm
x
x
Maintenance Alarm
Chillier Optimization
Time Program
Sequence Control
SOFTWARE
Energy Calculation
Reports
Remarks
BAS POINT SCHEDULE Project: 19-3262-0000, 12NHC- C08 - Post Office
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
Cooling coil shall be controlled by VRF
VAV Air Handling Units ,
controller and rest of the points shall be
AHU Nos.(Refer to Plans)
controlled by DDC/BMS
Supply Fan with VFD ─ x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x
Return /Exhaust Fan with VFD ( If Applicable refer to the equipment schedule). x x x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Air Ducts ( If Applicable refer to the equipment schedule). ─ x x x x x x
Mixed Air ─ x x x
Filters ─ x x x x x x
Dampers ─ x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Heating Coil Control (where required refer schedules) ─ x x x x x
CO2 Sensor Interlocked with Fresh Air Inlet Motorized damper. x x x x x x x
Cooling coil shall be controlled by VRF
Energy Recovery Unit ERU (ALL ERUs) controller and rest of the points shall be
controlled by DDC/BMS
Supply Fan with VFD Interlocked with Supply Air Flow Differential Pressure ─ x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Fan with VFD Exhasut Air Flow Differential Pressure ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x x x
Outside Air Duct ─ x x x x x x x x
Return/Exhaust Air Ducts ─ x x x x x x x x
Supply Air Filters ( All Filters) ─ x x x x
Exhaust Air Filters ─ x x x x
Dampers ─ x x x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Thermal Wheel ─ x x x x x x x x x x
Heating Coil Control ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
Cooling coil shall be controlled by VRF
VAV Air Handling Units ,
controller and rest of the points shall be
AHU Nos.(Refer to Plans)
controlled by DDC/BMS
Supply Fan with VFD ─ x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x
Return /Exhaust Fan with VFD ( If Applicable refer to the equipment schedule). x x x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Air Ducts ( If Applicable refer to the equipment schedule). ─ x x x x x x
Mixed Air ─ x x x
Filters ─ x x x x x x
Dampers ─ x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Heating Coil Control (where required refer schedules) ─ x x x x x
CO2 Sensor Interlocked with Fresh Air Inlet Motorized damper. x x x x x x x
Cooling coil shall be controlled by VRF
Energy Recovery Unit ERU (ALL ERUs) controller and rest of the points shall be
controlled by DDC/BMS
Supply Fan with VFD Interlocked with Supply Air Flow Differential Pressure ─ x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Fan with VFD Exhasut Air Flow Differential Pressure ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x x x
Outside Air Duct ─ x x x x x x x x
Return/Exhaust Air Ducts ─ x x x x x x x x
Supply Air Filters ( All Filters) ─ x x x x
Exhaust Air Filters ─ x x x x
Dampers ─ x x x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Thermal Wheel ─ x x x x x x x x x x
Heating Coil Control ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
Cooling coil shall be controlled by VRF
Fresh / Makeup Air Handling Units ,
controller and rest of the points shall be
AHU Nos.(Refer to Plans)
controlled by DDC/BMS
Supply Fan with VFD ─ x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x
Outdoor Air Ducts ─ x x x x x x
Filters ─ x x x x x x
Dampers ─ x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Heating Coil Control (where required refer schedules) ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
CO2 Sensor Interlocked with Fresh Air Inlet Motorized damper. x x x x x x x
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
Cooling coil shall be controlled by VRF
VAV Air Handling Units ,
controller and rest of the points shall be
AHU Nos.(Refer to Plans)
controlled by DDC/BMS
Supply Fan with VFD ─ x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x
Return /Exhaust Fan with VFD ( If Applicable refer to the equipment schedule). x x x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Air Ducts ( If Applicable refer to the equipment schedule). ─ x x x x x x
Mixed Air ─ x x x
Filters ─ x x x x x x
Dampers ─ x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Heating Coil Control (where required refer schedules) ─ x x x x x
CO2 Sensor Interlocked with Fresh Air Inlet Motorized damper. x x x x x x x
Cooling coil shall be controlled by VRF
Energy Recovery Unit ERU (ALL ERUs) controller and rest of the points shall be
controlled by DDC/BMS
Supply Fan with VFD Interlocked with Supply Air Flow Differential Pressure ─ x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Fan with VFD Exhasut Air Flow Differential Pressure ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x x x
Outside Air Duct ─ x x x x x x x x
Return/Exhaust Air Ducts ─ x x x x x x x x
Supply Air Filters ( All Filters) ─ x x x x
Exhaust Air Filters ─ x x x x
Dampers ─ x x x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Thermal Wheel ─ x x x x x x x x x x
Heating Coil Control ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
Cooling coil shall be controlled by VRF
VAV Air Handling Units ,
controller and rest of the points shall be
AHU Nos.(Refer to Plans)
controlled by DDC/BMS
Supply Fan with VFD ─ x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x
Return /Exhaust Fan with VFD ( If Applicable refer to the equipment schedule). x x x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Air Ducts ( If Applicable refer to the equipment schedule). ─ x x x x x x
Mixed Air ─ x x x
Filters ─ x x x x x x
Dampers ─ x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Heating Coil Control (where required refer schedules) ─ x x x x x
CO2 Sensor Interlocked with Fresh Air Inlet Motorized damper. x x x x x x x
Cooling coil shall be controlled by VRF
Energy Recovery Unit ERU (ALL ERUs) controller and rest of the points shall be
controlled by DDC/BMS
Supply Fan with VFD Interlocked with Supply Air Flow Differential Pressure ─ x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Fan with VFD Exhasut Air Flow Differential Pressure ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x x x
Outside Air Duct ─ x x x x x x x x
Return/Exhaust Air Ducts ─ x x x x x x x x
Supply Air Filters ( All Filters) ─ x x x x
Exhaust Air Filters ─ x x x x
Dampers ─ x x x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Thermal Wheel ─ x x x x x x x x x x
Heating Coil Control ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
Cooling coil shall be controlled by VRF
Energy Recovery Unit ERU (ALL ERUs) controller and rest of the points shall be
controlled by DDC/BMS
Supply Fan with VFD Interlocked with Supply Air Flow Differential Pressure ─ x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Fan with VFD Exhasut Air Flow Differential Pressure ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x x x
Outside Air Duct ─ x x x x x x x x
Return/Exhaust Air Ducts ─ x x x x x x x x
Supply Air Filters ( All Filters) ─ x x x x
Exhaust Air Filters ─ x x x x
Dampers ─ x x x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Thermal Wheel ─ x x x x x x x x x x
Heating Coil Control ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
Cooling coil shall be controlled by VRF
VAV Air Handling Units ,
controller and rest of the points shall be
AHU Nos.(Refer to Plans)
controlled by DDC/BMS
Supply Fan with VFD ─ x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x
Return /Exhaust Fan with VFD ( If Applicable refer to the equipment schedule). x x x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Air Ducts ( If Applicable refer to the equipment schedule). ─ x x x x x x
Mixed Air ─ x x x
Filters ─ x x x x x x
Dampers ─ x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Heating Coil Control (where required refer schedules) ─ x x x x x
CO2 Sensor Interlocked with Fresh Air Inlet Motorized damper. x x x x x x x
Cooling coil shall be controlled by VRF
Energy Recovery Unit ERU (ALL ERUs) controller and rest of the points shall be
controlled by DDC/BMS
Supply Fan with VFD Interlocked with Supply Air Flow Differential Pressure ─ x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Fan with VFD Exhasut Air Flow Differential Pressure ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x x x
Outside Air Duct ─ x x x x x x x x
Return/Exhaust Air Ducts ─ x x x x x x x x
Supply Air Filters ( All Filters) ─ x x x x
Exhaust Air Filters ─ x x x x
Dampers ─ x x x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Thermal Wheel ─ x x x x x x x x x x
Heating Coil Control ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
Life Safety Smoke Ventilation Systems
Make up Air Fans with VFDs ─ x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Smoke Exhaust Fans ─ x x x x x x x x x x
DIGITAL
HVAC System (VRF) DIGITAL INPUT ANALOG INPUT ANALOG OUTPUT
OUTPUT
SOFTWARE
Chillier Optimization
Pulsed KWHr Meter
Maintenance Alarm
Energy Calculation
Fire Alaram Signal
Sequence Control
Flow in USGPM
BTU Transmitter
Smoke Detector
Enable/Disable
Valves Control
General Alarm
Time Program
BACnet Data
Critical Alarm
Level Sensor
Temperature
`Flow Switch
Flow in CFM
NO2 Sensor
Open/Close
CO Sensor
Trip Status
Start/Stop
Graphics
Humidity
Reports
Kilowatt
Equipment/Function Description Remarks
VRF (For quantity Refer to Plans) Interfaced with BMS for control and monitor.
Unit Start/Stop ─ x x x x x x x BACnet Binary Output for Control
Run Status ─ x x x x x BACnet Binary Input for Monitoring
Fault Status ─ x x x x x x x x x BACnet Binary Input for Monitoring
SetPoint (Sets the set temperature of the indoor units) ─ x x x x x BACnet Analog Output for SP Adjust
FanSpeed Control (Sets the fan speed of all indoor units) ─ x x x x x BACnet Multistate Output for Speed Adjust
FanSpeed Status (Reads the fan speed of all indoor units) ─ x x x BACnet Multistate Input for Speed Value
Filter Status (Reads the Filter Status of all indoor units) ─ x x x BACnet Binary Input for Monitoring
Occupied Cool Setpoint ─ x x x BACnet Analog Value for SP Value
Occupied Heat Setpoint ─ x x x BACnet Analog Value for SP Value
Error Code (Reads the alarm code status of the indoor & Outdoor units) ─ x x x x x BACnet Multistate Input for Error Codes
ConsumptionTotal (Indicates Total consumption) ─ x x x BACnet Analog Input
Refrigerant Flow Value ─ x x x x x x BACnet Analog Input
Compressor Run Status ─ x x x x x x BACnet Binary Input
Cooling coil shall be controlled by VRF
VAV Air Handling Units ,
controller and rest of the points shall be
AHU Nos.(Refer to Plans)
controlled by DDC/BMS
Supply Fan with VFD ─ x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x
Return /Exhaust Fan with VFD ( If Applicable refer to the equipment schedule). x x x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Air Ducts ( If Applicable refer to the equipment schedule). ─ x x x x x x
Mixed Air ─ x x x
Filters ─ x x x x x x
Dampers ─ x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Heating Coil Control (where required refer schedules) ─ x x x x x
CO2 Sensor Interlocked with Fresh Air Inlet Motorized damper. x x x x x x x
Cooling coil shall be controlled by VRF
Fresh / Makeup Air Handling Units ,
controller and rest of the points shall be
AHU Nos.(Refer to Plans)
controlled by DDC/BMS
Supply Fan with VFD ─ x x x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x
Outdoor Air Ducts ─ x x x x x x
Filters ─ x x x x x x
Dampers ─ x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Heating Coil Control (where required refer schedules) ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
CO2 Sensor Interlocked with Fresh Air Inlet Motorized damper. x x x x x x x
Cooling coil shall be controlled by VRF
Energy Recovery Unit ERU (ALL ERUs) controller and rest of the points shall be
controlled by DDC/BMS
Supply Fan with VFD Interlocked with Supply Air Flow Differential Pressure ─ x x x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Return/Exhaust Fan with VFD Exhasut Air Flow Differential Pressure ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Supply Air Duct ─ x x x x x x x x x x x
Outside Air Duct ─ x x x x x x x x
Return/Exhaust Air Ducts ─ x x x x x x x x
Supply Air Filters ( All Filters) ─ x x x x
Exhaust Air Filters ─ x x x x
Dampers ─ x x x x x x x
BACnet Analog Out for Flow Control
Refrigerant Flow Control Command/Set Point Command ─ x x x
Command
Refrigerant Flow Value ─ x x x BACnet Analog Input for Flow Value
Thermal Wheel ─ x x x x x x x x x x
Heating Coil Control ─ x x x x x
Heat Pipe (as applicable) ─ x x x x
Life Safety Smoke Ventilation Systems
Car Park Smoke Exhaust Fans (All SEFs) with VFDs ─ x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Car Park Make up Air Fans (ALL FAFs) with VFDs ─ x x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Make up Air Fans with VFDs ─ x x x x x x x x x x x x x (0-10v) VFD Feedback to be connected
Smoke Exhaust Fans ─ x x x x x x x x x x
Cooler / Freezer
HVAC System (VRF)
BAS POINT SCHEDULE
Equipment/Function Description
Trip Status
x
x
x
Auto/Manual-HOA Status
Smoke Detector
x
x
Diff.Pressure switch
Pulsed KWHr Meter
DIGITAL INPUT
Temperature
Humidity
Damper/valves Actuators Feedback
CO Sensor
NO2 Sensor
CO2/Air Quality Sensor
Level Sensor
BTU Transmitter
Flow in USGPM
Flow in CFM
Pressure / DPSensor
Velocity Sensor
The number of points listed is the minimum. Contractor shall provide any additional point to make sure the system fully complete and fully functional without any additional cost to client
Kilowatt
Valves Control
ANALOG OUTPUT
x
x
Enable/Disable
x
x
x
Start/Stop
Open/Close
DIGITAL
OUTPUT
BACnet Data
x
x
x
Graphics
x
x
x
General Alarm
x
x
x
Critical Alarm
x
x
x
Maintenance Alarm
Chillier Optimization
Time Program
Sequence Control
SOFTWARE
Energy Calculation
Reports
Remarks
Runtime Toalaization
Chillier Optimization
Analog Totalization
Maintenance Alarm
(Auxiliary Contract)
Holiday Program
Flow in USGPM
Alarm Message
System Display
Pressure / DPS
Setpoint Adjust
Critical Alarm
Equipment/Function Description Remarks
Temperature
Flow in CFM
DDC Output
Flow Switch
Load Shed
Start/Stop
Kilowatts
Humidity
Quantity
Status
Spare
Spare
Trip
PLUMBING & FIRE PROTECTION
Domestic Water Supply System
Booster Pump (Set) VFD lot x x x x x x x x x
Transfer Pump (Set) lot x x x x x x x x x
Transfer Filtration Pump (Set) lot x x x x x x x x x
Domestic Filters lot x x x x x
Central Water Heaters lot x x x x x
Hot Water Circulation Pump (Set) lot x x x x x x x
Domestic and Fire Water Tanks (tank with two
compartments considered as two tanks) lot x x x x x x x x
Drainage System
Submersible Pumps Sets lot x x x x x x x x
Sump Level Control lot x x x x x x x x
Fire Protection System
Fire Pumps lot x x x x x x x x x x
Jockey Pump lot x x x x x x x x x x
Foam System lot x x x x x x
Clean Agent System lot x x x x x x x
Compressors & Vacuum pumps
Compressors set 1 x x x x x x x x x
Vacuum pumps set 1 x x x x x x x x x
KEO/19-3262-0000
12 Neighborhood Centers
Public Authority for Housing Welfare, Kuwait 25 0000-2 BAS Points Schedule - Plumbing Fire Fighting
ELECTRICAL POINTS MONITORED/ CONTROLLED BY BAS/ IBMS
KEO/19-3262-0000
12 Neighborhood Centers
Public Authority for Housing Welfare, Kuwait 25 0000-3/1 BAS Points Schedule - Electrical
ELECTRICAL POINTS MONITORED/ CONTROLLED BY BAS/ IBMS
Alarm Monitored
KEO/19-3262-0000
12 Neighborhood Centers
Public Authority for Housing Welfare, Kuwait 25 0000-3/2 BAS Points Schedule - Electrical
ELECTRICAL POINTS MONITORED/ CONTROLLED BY BAS/ IBMS
KEO/19-3262-0000
12 Neighborhood Centers
Public Authority for Housing Welfare, Kuwait 25 0000-3/3 BAS Points Schedule - Electrical
SECTION 26 0500
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. The contractor shall complete, commission and hand over the works in accordance with
the design intent expressed in contract documents. In general, the project comprises the
following works. General elements of scope of work include:
1. Provision of all labour, equipment and materials required to complete the works
according to the Design Intent. Provision means supply, installation, test,
commission and put to operation.
2. Additional hardware, incidentals and any other work necessary for completion of
the works and safe, correct operation of each system, whether such item or work
is detailed in Specifications and on Drawings or not.
3. Verification of existing conditions on site prior to tendering. Arranging with and
paying for the Ministry of Electricity and Water & Renewable Energy (MEW)
authorities to re-route their services should such services exist on site.
4. Temporary power supplies for construction purposes for the duration of the
works.
5. Arranging for and carrying out necessary approvals with the MOC for the
telephone system.
6. Arranging for and carrying out necessary approvals with the Kuwait Fire Force
(KFF) if required.
7. Preparation of shop / construction / installation drawings for approval.
8. Builder's work, ducts, inserts and sleeves required for the works
9. On-site coordination with all other services and trades, liaison with members of
the professional team, attendance on meetings as required.
10. Testing, commissioning and certification that the work has been completed and
inspected in accordance with the requirements of the relevant Regulations.
11. “As Built” drawings, “Operation and Maintenance Manuals” and other project-
specific record documents.
12. Training of the Employer’s staff in the operation of the systems installed.
13. Defects Notification: refer to contract conditions specified in this Section Clause
3.05.
14. Maintenance during the Defect Notification Period: refer to contract conditions in
this Section Clause 3.05.
15. Spare parts: refer to this Section Clause 1.13.
B. Electrical System
1. Containment system (spaces, wire ways, cable ducts, trays, conduits etc.) for
Electrical system.
2. Electrical installations cabling and equipment, switchboards, distribution boards,
earthing system etc.
a. Provision of final sub-circuits and electrical services such as power and
lighting.
KEO/19-3262-0000 26 0500/1 Common Requirements For Electrical Installations
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
b. Small power, general power outlets and equipment outlets.
c. Provision of internal, external, Exit and emergency lighting.
3. Electrical services for other trades. Power and relevant controls for elevators, fire
protection equipment, air conditioning, ventilation, plumbing and auxiliary
equipment such as kitchen equipment, electric water heaters, electric hand
dryers, etc. Motors, starters, controls and the like, electrically operated doors,
interlocks between electric doors and the fire alarm system where required.
Dampers and other devices operated by signals from fire alarm system. (The
supply and final connections of mechanical equipment is specified in Divisions
21, 22, 23 and 25).
4. Earthing
5. Lighting control and dimming
6. Engine Generators
7. Static Uninterruptible Power Supply
8. Power Factor Correction Equipment
9. Transfer Switches
10. Lightning Protection for Structures
11. Interior Lighting
C. Communications
1. Telephone System
2. Communications Cabling System
3. AV System
4. IPTV/ Digital Signage System
5. Queue Management System
6. Emergency Call System for Special Need Persons
E. Integrated Automation
1. Building Automation System
F. Exact location of all equipment and components to be approved on site by the Engineer.
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the final design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor's designed
portion of the Works.
A. The proposed manufacturer(s) must hold a quality system certificate such as ISO, Key
Mark or equivalent, for his manufacturing assembly process and quality control.
C. All the main equipment should be from a manufacturer with appropriate standards
compliance and certification from the country of origin.
E. The Supplier should be an approved agent for all the installed equipment.
G. The Supplier must be able to fully support any warrantees associated with the
equipment and the complete installation undertaken by them.
H. The Supplier must be capable of providing and supporting any maintenance activities
associated with the equipment by trained personnel.
I. The Supplier must carry a stock of critical parts in the event of breakdown and must be
able to supply consumables under any planned maintenance schedules within a
maximum agreed time.
J. The Supplier must be able to provide training to any nominated 3rd party operators
using the equipment.
C. Lighting Systems
1. Lighting system well-coordinated with the interiors is provided for the entire
project.
A. Electrical Supply
1. Entire Electrical system shall be designed to Ministry of Electricity and Water &
Renewable Energy (MEW) compliant power supply
B. Climatic Condition
1. The climate in Kuwait in the summer months is hot and humid and a humidity of
100% at 30ºC has been recorded.
2. Violent sand and dust storms of several hours duration occur and even on
comparatively still days, fine dust is carried in suspension in the atmosphere.
3. All apparatus and equipment shall, therefore be so designed and constructed
that they operate satisfactorily and without any deleterious effect for prolonged
and continuous periods in the conditions stated above and at the following
ambient temperature conditions:
a. Maximum sun radiation temperature in summer - 84 ºC
b. Maximum ambient temperature in summer - 52 ºC
c. Average max. ambient temperature in summer - 45 ºC
d. Minimum ambient temperature in winter - 6 ºC
e. The altitude of Kuwait may be taken as sea level.
4. The temperature quoted above make no allowance for heat generated from
equipment itself or from any other equipment in the vicinity.
5. The capacity and ratings of all electrical equipment and materials given are,
unless otherwise indicated, for Kuwait climatic conditions. Provide the basis of
the de-rating factors applied in each case.
6. Where specific sizes are indicated eg cable sizes, due allowances have been
made in the design for the climatic conditions of Kuwait and de-rating has been
applied.
7. Where no ratings or sizes are indicated for components and other accessories,
supply equipment which will give trouble free service in the ambient conditions
stated above.
A. The contractor is deemed to have visited and inspected the site to familiarize himself
with the existing site conditions and services at tender stage.
B. The contractor shall obtain the existing services record drawings from Kuwait Mucipality
and various utility services departments.
C. Co-ordination between shop drawings, work on site and existing services shall be
carried out by the Contractor.
D. The Contractor shall be fully responsible for rerouting and reconfiguring of existing
services within the site, as well as for any damages to the existing services including
repairs, and penalties imposed by the concerned parties etc. and for removing any site
obstacles such as underground cables, pipes, civil works etc. which is obstructing his
work on site.
E. The Contractor shall also be responsible for liaison with Ministry of Electricity and Water
& Renewable Energy (MEW) and all other government utility departments to disconnect
the existing services supply to the existing site prior to demolishing.
B. Single-Source Responsibility:
1. Ensure that each category of selected material or equipment shall be of a
particular range of one manufacturer who would take full responsibility of the
product.
C. Certificate Of Origin:
1. Provide certificate of origin along with the packing list on delivery of material and
equipment.
C. Prior to the commencement of works the Contractor shall notify of his intended site
staffing levels.
D. Contractor shall appoint minimum one Graduate Electrical Engineers for the site work,
(at least one of them with A Grade license form Ministry of Electricity and Water &
Renewable Energy (MEW)) with minimum 10 year experience in similar installations.
E. The name, qualifications and experience of the nominated engineers shall be submitted
to the Engineer for approval within 15 days of the receipt of the order to commence the
works.
G. Qualified and Experienced Electricians shall be available on site to carry out the works
in accordance with the Project program.
1.10 SUBMITTALS:
B. Progress Drawings
1. The Contractor shall provide one full set of shop drawings and keep it at the job
throughout the construction period for purpose of recording any changes whether
additions, deletions or relocation resulting thereof from any co-ordination VO’s,
RFI’s and/or site instructions. This set of drawings will be the basis upon which
the contractor will prepare the As-built Drawings.
C. As-built Drawings
1. Upon completion of each facility under this contract, the Contractor shall prepare
and furnish as-built drawings. The as-built drawings shall be a record of the
construction as installed and completed by the Contractor. They shall include all
the information shown on the contract set of drawings and all other related
KEO/19-3262-0000 26 0500/7 Common Requirements For Electrical Installations
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
drawings, modifications, or changes from those drawings, however minor, which
were incorporated in the work, including all additional work not appearing on the
contract drawings, and all changes which are made after any final inspection of
the contract work. In the event the Contractor performed additional work, which
changes the as-built conditions of the facility after submission of the final as-built
drawings, the Contractor shall furnish revised and/or additional drawings and
drawing files as required supporting final as-built condition.
2. The Contractor shall certify and label all systems at the completion of the
installation project, and after any modifications are made to an existing system.
All labeling shall be plastic or metal tags that will withstand fading and/or
corrosion. Labels shall be white, ¾” high by length suitable to have address
printed with ½” black lettering. All labels shall be mechanically fastened to
surface adjacent to device with stainless steel screws or pop rivets. Glue or
plastic strip labels neither shall be used nor will it be accepted.
3. The Main Contractor shall engage qualified and accredited Design Consultant to
upload Construction As Built Documents to the approving Authorities as per
submittal and conditions of such authorities.
4. Contractor shall be responsible for all conditions and completeness level for all
planned or required Field Construction Inspection required for final Authority
approval, including but not limited to the final power and utilities connections by
such Authorities
A. Provide warning signs, as well as prohibitions mandatory and safety signs for giving
safety information in accordance with BS 5378 Part 1: 1980 and identify materials and
equipment and circuits so marked for easy recognition in a durable and lasting manner
as required by the BS7671: 2008 Requirements for Electrical Installations.
B. The Contractor shall certify and label all systems at the completion of the installation
project. All labeling shall be plastic or metal tags that will withstand fading and/or
corrosion. Labels shall be white, suitable to be printed with black lettering. All labels
shall be mechanically fastened to surface adjacent to device with stainless steel screws
or pop rivets. Glue or plastic strip labels neither shall be used nor will be accepted.
1.12 TESTING
A. General
1. Testing and commissioning of equipment and services of a specialized nature
shall be supervised by the manufacturers’ technical representative(s).A visual
inspection of the installation should be made to ensure all equipment and
materials comply with the relevant standards and regulations. A checklist for
initial inspection should include those items indicated in the BS7671:2008
Requirements for Electrical Installations.
2. During erection and/or completion, the electrical installation shall be tested
before it is connected to the power supply. Sequence of test and testing
methods shall be as stipulated in the BS 7671.
A. General
1. Submit a list of all spare parts required for two years of proper operation starting
from the date of issue of the Maintenance Certificate.
2. Provide sufficient spare parts as may be required for the proper and satisfactory
operation of the respective electrical equipment or part of equipment.
3. Spare parts required shall include but not necessarily be limited to,
a. Items listed below.
b. Specified elsewhere in other sections of the Contract Documents.
c. Where quantities for each part or equipment are recommended by the
manufacturer.
4. Spare parts shall be delivered to the Owner’s central storage facility.
B. Detailed Pricelist
1. The contractor shall submit with his offer detail prices of the spare parts required
to be provided under the Contract indicating the unit rate of each item.
C. Compulsory Items Required: The following items shall be furnished in all major
equipment rooms (such as HT Room, transformer rooms, LT Room, Electrical Rooms,
Main Telecom Rooms, Site Security Room etc.) prior to project handing over:
1. Rubber mat
2. First Aid Tools
3. Framed single line diagrams, etc.
PART 2 - PRODUCTS
2.01 GENERAL
B. Prior to placing order for any equipment or material, the contractor shall submit
comprehensive documentation comprising working drawings, catalogues and
descriptive literature of components, maintenance manuals, samples etc for review and
acceptance.
C. Review and acceptance of the Engineer’s Representative does not relieve the
Contractor from his contractual obligations for deviations from the requirements of the
Contract Documents.
PART 3 - EXECUTION
A. Electrical penetrations occur when raceways, cables, wire ways, cable trays, or bus
ways penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall
assemblies.
B. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or
formed openings are used. Install sleeves during erection of slabs and walls.
C. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
D. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall
assemblies unless openings compatible with fire stop system used are fabricated during
construction of floor or wall.
E. Cut sleeves to length for mounting flush with both surfaces of walls.
G. Size pipe sleeves to provide 6.4-mm annular clear space between sleeve and raceway
or cable, unless indicated otherwise.
H. Seal space outside of sleeves with grout for penetrations of concrete and masonry
KEO/19-3262-0000 26 0500/10 Common Requirements For Electrical Installations
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Promptly pack grout solidly between sleeve and wall so no voids remain. Tool
exposed surfaces smooth; protect grout while curing.
I. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between
sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location
of joint. Comply with requirements in Division 07 Section "Joint Sealants".
B. Use type and number of sealing elements recommended by manufacturer for raceway
or cable material and size. Position raceway or cable in center of sleeve. Assemble
mechanical sleeve seals and install in annular space between raceway or cable and
sleeve. Tighten bolts against pressure plates that cause sealing elements to expand
and make watertight seal.
3.04 FIRESTOPPING
A. Apply fire stopping to penetrations of fire-related floor and wall assemblies for electrical
installations to restore original fire-resistance rating of assembly. Fire stopping materials
and installation requirements are specified in Division 07 Section “Penetration Fire
stopping.
A. Contractor shall be completely responsible for repairing, replacing with new to the
satisfaction of Owner, all and any Electrical installed system found defective or not
satisfactorily operating, for a period of 2 years from the date of substantial completion,
without any extra cost to the Owner.
3.06 MAINTENANCE
A. Maintenance Service
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Section Includes:
1. This Section specifies the general requirements for power cables and small
wiring systems. It shall be read in conjunction with other parts of the Project
Documentation.
2. PVC Insulated armored cables (LSF sheath)
3. PVC Insulated armoured cables (PVC sheath):
4. PVC Insulated LSF sheathed (PVC/LSF) cable
5. PVC Insulated PVC sheathed (PVC/PVC) cable
6. Single core PVC wires
7. Heat resistant and high temperature cable
8. Flexible cable
9. 600/1000V rated XLPE insulated cable (LSF sheath)
10. 600/1000V rated XLPE insulated cable (PVC sheath)
11. Fire resistant cables: (up to 25mm²)
12. Fire resistant cables (multi-core up to 400mm²)
13. Mineral Insulated Cable
14. Cable glands
15. Cable sealing compounds
16. Cleats
17. Cable markers
1.03 DEFINITIONS
A. Definitions include:
1. AWA: Aluminium Wire Armoured
KEO/19-3262-0000 26 0519/1 Low Voltage Electrical Cables
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. CuWA: Copper Wire Armoured
3. LSF: Low Smoke Fume
4. LSZH: Low Smoke Zero Halogen
5. PVC: Polyvinyl Chloride
6. SWA: Steel Wire Armoured
7. XLPE: Cross Linked Poly Ethylene
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
A. Validate suitability of the size of cables selected to be used for the selected electric
energy-operating equipments. Refer to the technical tables of the cables available from
the approved manufacturer, with due consideration to the following parameters,
1. Type of cable and wire
2. Ambient conditions
3. Method of installation
4. The disposition of each cable relative to other cables
5. Fault power level
6. Protective device ratings
B. Voltage drop at the final point of utilization shall not exceed 2.5% measured from the
main electric service of the installations.
C. Voltage drop and current ratings shall be calculated according to BS7671 (latest edition)
Requirements for Electrical Installations and local power supply Authorities.
D. All cables and wires shall be suitable for installation and continuous service in the
ambient conditions described in SECTION 26 0500, and shall be manufactured to ISO
9000 or equivalent.
E. Cable routes and equipment power ratings indicated on the Project Drawings are for
guidance for tendering purposes. The Contractor shall determine exact cable lengths
from site measurements and calculate cable size from the power ratings of the actual
equipment being proposed. The Contractor shall be responsible for any increase in
costs or redesign work associated with proposed equipment, which has different
electrical characteristics than the equipment on which the design was based.
F. Cables selected shall be from manufacturers whose product have been in satisfactory
use in similar services and environments. Substantiate with certification.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
A. The Contractor shall be aware of the need to supply and install all wire and cables for
this Contract, which are most suitable for the special environmental conditions prevailing
in the country.
B. All conductors shall have good fatigue resistance and not be subject to breaks due to
nicks or cuts when terminating.
2.03 CABLES
A. Unless otherwise specified, cables and wires of the following specified voltage ratings
shall be used as indicated.
1. 600/1000 V rated cables: Main and sub-main distribution panels, motor control
centers, circuits serving process equipment
2. 450/750 V rated cables: Final sub-circuit supplies for lighting, socket outlets, etc.
3. 300/500 V rated cables: Instrumentation
KEO/19-3262-0000 26 0519/4 Low Voltage Electrical Cables
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4. 250 V rated cables: Extra low voltage wiring, communication circuits where the
maximum voltage is 50 V.
B. General:
1. Conductors shall be high conductivity copper, to BS 6360 (IEC 228) unless
otherwise indicated
2. Flexible cords shall have fine stranded conductors
3. Cable color: In addition to the safety compliance and quality assurance issues,
cables should fully align with those widely-used national and international
standards. Insulation for each conductor shall be color coded or otherwise
identified as required by the local authority regulations. Color coding shall be
maintained throughout the installation.
4. All cables shall be as far as practicable, of one manufacturer only.
I. Flexible Cable:
1. To BS 6007, or BS 6500, rated in accordance with manufacturer’s tables flexible
cables subject to excessive heat shall be insulated as (8) above, (a) or (b) as per
the Project Documentation requirement.
P. Cable Glands
1. Cable glands shall be used for terminating cables to switch gear, switch boards,
motor control centers, motors and other equipment
2. They shall be brass compression glands and comply with the relevant part of BS
6121, except for MICC cables, which shall comply with BS 6207 Part 2.
KEO/19-3262-0000 26 0519/8 Low Voltage Electrical Cables
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Glands for armored or screened cables shall have suitable clamps
4. External compression glands shall have close fitting PVC shrouds
5. earthing for armoring and metallic sheaths: suitable brass or copper clamps, and
copper strip conductor in accordance with local power authority requirements,
and not less than 2.5 sq. mm
R. Cleats:
1. shall be approved claw type cast aluminum, gunmetal, plastic or brass of
approved type, two bolts fixing for cables greater than 50 mm diameter.
S. Cable Markers:
1. Shall be precast concrete, minimum size 300 x 300 mm x 100 mm deep
2. The markers shall be engraved “HV CABLE”, “ELECTRIC CABLE”, “ELV
CABLE”, “EARTH PIT” or “CABLE JOINT”, as applicable cable marker
construction details and engravings shall be as per local power authority
regulations.
PART 3 - INSTALLATION
3.01 GENERAL
A. Installing cables:
1. Pull cable into position by hand, where possible using an adequate number of
operative roller guides suitably positioned along cable length.
2. Obtain approval of pulling cables by winch or similar appliance.
3. When pulling by winch or the like, fit a suitable tension gauge into the haulage
line between winch and cable. Pulling tension shall not exceed the limit
recommended by the cable manufacturer.
4. Do not allow cable to twist or rotate about its longitudinal axis.
5. Lay 3 phase groups of single core cables in trefoil formation. If this is not possible
obtain instructions.
6. Install cables to allow any one cable to be subsequently removed without
disturbing the remainder.
7. Maintain an underground cable horizontal separation of a minimum of 150 mm.
8. Remove all damaged cables.
B. Bending Radius:
1. Maintain a bending radius as large as possible. Do not bend cable a radius less
than that specified in the relevant British Standard, Local Electricity & Water
Regulatory Authority or manufacturer’s recommendation, whichever is largest.
G. Cable Supports:
1. Support cables in accordance with the methods described in table 4A of BS
7671.
2. Support cables at regular intervals and at spacing a maximum of 400 mm for
cleats for horizontal runs and 550 mm for vertical runs.
3. Vertical cable runs exceeding 100 m shall incorporate tension releasing sections
steel cable supports which shall be provided at 300 mm intervals
4. MICC Cables:
a. Run on surface of walls or ceilings. Where embedded, run in a PVC
trough or conduit.
KEO/19-3262-0000 26 0519/10 Low Voltage Electrical Cables
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
b. Run cables in square symmetrical lines. Where single core cables are run
in groups, bend the sheaths at maximum 50 mm centers.
c. Fix surface run cables with saddles at maximum 300 mm centers.
I. Flexible Cables:
1. Flexible cable shall be kept to a minimum and concealed if possible.
2. Mechanical retainment shall not depend on electrical connections.
J. Sealing Cables:
1. Seal both ends of cables immediately after tests.
2. Seal MICC cables immediately after cutting to prevent hygroscopic action by the
dielectric. All cables shall give an infinity test when tested on a 1000 volt Megger
immediately, and 48 hours after sealing.
3. Seal aluminium sheathed cables with a metal cap plumbed to the sheath.
4. Seal plastic sheathed cables with a plastic cap embracing the wires and outer
sheath.
5. Mark cable ends in accordance with the relevant BS.
A. Generally:
1. Install cables on trays in a single layer, unless otherwise specified
2. Use purpose made straps or saddles to maintain cables in a neat regular
disposition
3. Secure cables with load bearing cleats securely fixed to the tray. Where trays do
not directly support the cables space cleats, saddles and straps at maximum
centres shall be as recommended by cable manufacturers.
A. Conceal cables in finished walls, ceilings, and floors, unless otherwise indicated.
C. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips
that will not damage cables or raceway.
E. Support cables according to Division 26 Section "Hangers and Supports for Electrical
Systems."
3.04 CONNECTIONS
B. Make splices and taps that are compatible with conductor material and that possess
equivalent or better mechanical strength and insulation ratings than unspliced
conductors.
1. Use oxide inhibitor in each splice and tap conductor for aluminum conductors.
C. Wiring at Outlets: Install conductor at each outlet, with at least 300 mm of slack.
A. Coordinate sleeve selection and application with selection and application of fire
stopping specified in Division 07 Section "Penetration Fire stopping."
B. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or
formed openings are used. Install sleeves during erection of slabs and walls.
C. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
E. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall
assemblies unless openings compatible with fire stop system used are fabricated during
construction of floor or wall.
F. Cut sleeves to length for mounting flush with both wall surfaces.
H. Edit paragraph below as required for Project design conditions and seismic-criteria
status.
I. Size pipe sleeves to provide 6.4-mm annular clear space between sleeve and cable
unless sleeve seal is to be installed or unless seismic criteria require different clearance.
J. Seal space outside of sleeves with grout for penetrations of concrete and masonry and
with approved joint compound for gypsum board assemblies.
K. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between
sleeve and cable, using joint sealant appropriate for size, depth, and location of joint
according to Division 07 Section "Joint Sealants."
O. Underground Exterior-Wall Penetrations: Install cast-iron "wall pipes" for sleeves. Size
sleeves to allow for 25-mm annular clear space between cable and sleeve for installing
mechanical sleeve seals.
B. Use type and number of sealing elements recommended by manufacturer for cable
material and size. Position cable in center of sleeve. Assemble mechanical sleeve
seals and install in annular space between cable and sleeve. Tighten bolts against
pressure plates that cause sealing elements to expand and make watertight seal.
3.07 FIRESTOPPING
A. Apply fire stopping to electrical penetrations of fire-rated floor and wall assemblies to
restore original fire-resistance rating of assembly according to in Division 07 Section 07
8400 "Firestopping."
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections
and prepare test reports.
F. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Engineers review outlining all deficiencies and
course of action. The contractor shall ensure all deficiencies outlined are rectified,
retested, and certified.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This section covers the furnishing and installing of a complete Earthing system for the
facility including but not limited to:
1. Earth Continuity Conductors
2. Main Earth Loops
3. Rod Electrodes
4. Earth Pit Covers
5. Equipotential bonding between various system and light non protective system
6. Connectors and exothermic welding
C. Comply with the requirements of the Local Electricity & Water Regulatory Authority
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
1.05 SUBMITTALS
C. Qualification Data: For testing agency and testing agency’s field supervisor.
E. Operation and Maintenance Data: For Earthing to include the following in emergency,
operation, and maintenance manuals:
1. Instructions for periodic testing and inspection of Earthing features at test wells
based on BS 7430
a. Tests shall be to determine if Earth resistance or impedance values
remain within specified maximums, and instructions shall recommend
corrective action if they do not.
b. Include recommended testing intervals.
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Spare parts recommended by manufacturer for two years of normal operations.
2. Tools recommended for maintenance.
PART 2 - PRODUCTS
2.02 MATERIALS
A. General
1. Products used in the earthing system shall be copper or an approved copper
alloy.
D. Rod electrodes:
1. Shall be the earth rod electrode type, unless impracticable to drive deep into the
particular soil.
2. Earth rod electrodes: 16mm diameter stainless steel, comprising a high strength
steel alloy core with a molten welded copper covering.
KEO/19-3262-0000 26 0526/3 Earthing And Bonding For Electrical Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Shall be 3.6m long, in 1.2m sections coupled by strong bronze couplers.
E. Earth connectors
1. For connection of rod electrodes: bolted type; Copper or Copper Alloy, Bolted
pressure type with at least two bolts. Pipe Connector: Clamp type sized for
pipe. Welded Connectors: Exothermic welding kits of types recommended by
Kit Manufacturer for material being joined in installation condition.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Circuit Wiring
1. Shall have a green/yellow coloured insulated earth continuity cable connecting
the earth bus or earth terminal in switchboards, switchgears, motor control
centres and panel boards to the motor, equipment, outlet and other device by
earthing lugs. All hand rails and other metal works within 2 m of a potentially
live metal surface shall be earthed.
E. Bolted connections
1. Multiple bolt type.
2. Where bare copper has bolted in connections provide electroplated silver
contact surfaces.
F. Brazed connections
1. Where earthling terminal connections are to be brazed to equipment, thoroughly
clean metal prior to brazing and repaint impaired surfaces to prevent corrosion.
H. Equipment Earthing
1. Connect all non-current carrying metallic parts of the electrical/mechanical
installation to the earthing system.
2. Non-current carrying metallic parts of the electrical installation include:
a. Metal conduit cable armor (steel and aluminum) raceways, outlet boxes,
cabinets, and the like.
b. Exposed metal parts of apparatus.
c. Enclosures, doors, grilles, barriers and the like protecting or shielding
electrical equipment from direct access.
3. Series earthing of one piece of equipment to another is not acceptable. Each
item shall be individually connected the earthing system.
K. Motors Earthing
1. Connect the motor terminal box to the relative earth loop. The terminal must be
mechanically connected to the frame or, where this is not feasible
2. Extend the earthing conductor through an insulated bushed opening in the
connection box and connect to the frame.
R. Earthing Bus: Install in electrical and telephone equipment rooms, in rooms housing
service equipment, and elsewhere as indicated.
1. Install bus on insulated spacers 25 mm, minimum, from wall 150 mm above
finished floor, unless otherwise indicated.
2. Where indicated on both sides of doorways, route bus up to top of door frame,
across top of doorway, down to specified height above floor, and connect to
horizontal bus.
S. Signal and Communication Equipment: For telephone, alarm, voice and data, and
other communication equipment, insulated earthing conductor in raceway from
earthing electrode system to each service location, terminal cabinet, wiring closet, and
central equipment location.
1. Service and Central Equipment Locations and Wiring Closets: Terminate
earthing conductor on a earthing bus.
2. Terminal Cabinets: Terminate earthing conductor on cabinet earthing terminal.
3. Ensure the potential rise in telecommunications circuits due to power system
earth faults is limited in accordance with BS 6701.
B. The resistance of any point in the earth continuity system to the main earth electrode
shall not exceed 1 ohm.
C. Install additional earth electrodes if the above figures are not met.
3.04 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular
inspection and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.04 SUBMITTALS
1. Product Data: For the following:
2. Steel slotted support systems.
3. Nonmetallic slotted support systems.
B. Shop Drawings: Signed and sealed by a qualified class ‘A’ Engineer professional
engineer. Show fabrication and installation details and include calculations for the
following:
1. Trapeze hangers. Include Product Data for components.
2. Steel slotted channel systems. Include Product Data for components.
3. Nonmetallic slotted channel systems. Include Product Data for components.
4. Equipment supports.
A. Comply with BS Standards and Local Electricity & Water Regulatory Authority.
1.07 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
B. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These
items are specified in Division 07 Section "Roof Accessories."
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Spare parts recommended by manufacturer for two years of normal operations.
2. Tools required for maintenance.
PART 2 - PRODUCTS
D. Conduit and Cable Support Devices: Steel hangers, clamps, and associated fittings,
designed for types and sizes of raceway or cable to be supported.
F. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M, steel
plates, shapes, and bars; black and galvanized.
G. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items
or their supports to building surfaces include the following:
1. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened portland
cement concrete, steel, or wood, with tension, shear, and pullout capacities
appropriate for supported loads and building materials where used.
2. Mechanical-Expansion Anchors: Insert-wedge-type, zinc-coated steel, for use in
hardened portland cement concrete with tension, shear, and pullout capacities
appropriate for supported loads and building materials in which used.
3. Concrete Inserts: Steel or malleable-iron, slotted support system units similar to
MSS Type 18; complying with MFMA-4 or MSS SP-58.
4. Clamps for Attachment to Steel Structural Elements: MSS SP-58, type suitable
for attached structural element.
5. Through Bolts: Structural type, hex head, and high strength. Comply with
ASTM A 325.
6. Toggle Bolts: All-steel springhead type.
7. Hanger Rods: Threaded steel.
PART 3 - EXECUTION
3.01 INSTALLATION
B. Install anchoring devices and other fasteners in accordance with manufacturer’s printed
instructions.
3.02 APPLICATION
A. Maximum Support Spacing and Minimum Hanger Rod Size for Raceway: Space
supports shall be as required by the BS 7671 –Requirements for Electrical Installations.
B. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted
or other support system, sized so capacity can be increased by at least 25 percent in
future without exceeding specified design load limits.
C. Spring-steel clamps designed for supporting single conduits without bolts may be used
for 38-mm and smaller raceways serving branch circuits and communication systems
above suspended ceilings and for fastening raceways to trapeze supports.
C. Drill holes for expansion anchors in concrete at locations and to depths that avoid
reinforcing bars.
D. Pull out tests for anchors for densely installed areas as required by Consultants shall be
provided.
E. For heavy installation, calculations on type and size of the anchors, rods and brackets
including support distances should be submitted for Consultant approvals.
KEO/19-3262-0000 26 0529/4 Hangers And Supports For Electrical Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3.04 INSTALLATION OF FABRICATED METAL SUPPORTS
B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and
elevation to support and anchor electrical materials and equipment.
A. Construct concrete bases of dimensions indicated but not less than 100 mm larger in
both directions than supported unit, and so anchors will be a minimum of 10 bolt
diameters from edge of the base.
3.06 PAINTING
A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas
immediately after erecting hangers and supports. Use same materials as used for shop
painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.
B. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply
galvanizing-repair paint to comply with ASTM A 780.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical
wiring
1. Rigid PVC conduit and fittings
2. Rigid Steel conduit and fittings
3. Flexible Steel conduit and fittings
4. Flexible PVC conduit
5. Hinged cover enclosures and cabinets
6. Cable Trunking
1.03 SUBMITTALS
A. Samples: Cut-away samples of all sizes of conduits, conduit boxes and fittings of each
type fixed to a board and submitted.
C. Shop Drawings: Submit drawings of proposed conduit layouts and obtain approval
before commencing work.
E. Shop Drawings: For the following raceway components. Include plans, elevations,
sections, details, and attachments to other work:
1. Custom enclosures and cabinets.
F. Coordination Drawings: Conduit routing plans, drawn to scale, on which the following
items are shown and coordinated with each other, based on input from installers of the
items involves:
1. Structural members in the paths of conduit groups with common supports.
2. HVAC and plumbing items and architectural features in the paths of conduit
groups with common supports.
B. Conform to the related latest BS for metallic and non-metallic conduits and accessories
stipulated in this Section.
C. Coordinate layout and installation of raceway and boxes with other construction
elements to ensure adequate headroom, working clearance, and access.
A. All electrical installations shall be carried out in accordance with the best International
Standards and Codes of Practice specifically with the current issue of IEE Regulations
(BS 7671) and the requirements of the local electrical power supply authority.
C. Listed below are the standards and codes referred to in this section.
1. BS 4607 Non-metallic conduits and fittings for electrical
installations rigid PVC conduits and conduit fittings.
2. BS EN 61386-1:2008 Conduit systems for cable management. General
requirements
3. BS EN 61386-21 Specification for conduit systems for electrical
installations
4. BS EN 61386-23:2004 Conduit systems for cable management. Particular
requirements. Flexible conduit systems
5. BS EN 61386-24:2010 Conduit systems for cable management. Particular
requirements. Conduit systems buried underground
6. BS EN 60423 Conduits for electrical purposes. Outside diameters
of conduits for electrical installations and threads
for conduits and fittings
7. BS EN 50085-1:2005 Cable trunking systems and cable ducting systems
for electrical installations. General requirements
8. BS EN 50085-2-1 Cable trunking systems and cable ducting systems
for electrical installations
9. BS 4678-2 Cable trunking. Steel underfloor (duct) trunking
10. BS EN 10346:2015 Continuously Hot-Dip Strip and Sheet of low carbon
steels for cold forming
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Spare parts recommended by manufacturer for two years of normal operations.
2. Tools required for maintenance.
B. All components and their installations shall be free from defects. Any defective
material or workmanship and any resulting damage to work of other trades shall be
replaced or repaired as directed during the Warranty Period at the contactors
expense. Comply with General Conditions, agreeing to repair or replace any
components that have failed within the warranty period.
PART 2 - PRODUCTS
2.02 GENERAL
A. Light and power circuits, fire alarm, telephone, signal and other low current system
wiring shall be drawn in conduits unless otherwise indicated
B. Conduit system shall generally be concealed and installed. Minimum conduit size shall
be 20mm diameter.
C. Light and power circuits, fire alarm wiring, telephone wiring, signal wiring and low
current system wiring shall each be run in separate conduit and wire way.
A. Standards:
1. Conduit and fittings shall comply with BS 4607: Part 1 & 2 and CEE Publication
26. In addition, conduit and fittings shall comply with this specification where
requirements are more stringent.
B. Physical Properties:
1. Conduit and fittings shall be:
a. Resistant to high temperatures
b. Non-hygroscopic
c. Self-extinguishing
d. Of adequate insulation resistance and electric strength
e. Inert to all liquid normally discharged from residential, commercial and
industrial premises
f. Suitable for installation, storage and transportation at temperatures
normally below -5°C. or above 85°C. and at these temperatures shall
not:
1) Soften or suffer any structural degradation
2) Show signs of cracking, or deform so that cables cannot be easily
drawn in or are likely to be damaged when drawing in, when bent,
compressed or exposed to extreme temperature
g. Of adequate mechanical strength and thermal stability
h. Suitably and indelibly marked and identified. Markings shall include
nominal size and be easily legible
i. Smooth inside and outside and free from burrs and sharp edges.
Surfaces and corners over which cables may be drawn shall be smooth
and well rounded.
2. Sizes of Conduit:
a. Conduits shall not be less than 20 mm diameter
b. Where size is not indicated: select in accordance with the regulations
and as proper to the number and size of conductors.
3. Fittings:
a. Conduit entries shall be designed to ensure a watertight joint.
4. Expansion fittings:
a. Provide fittings that provide expansion and contraction for at least 0.06
mm per meter of length of straight run per degree of temperature
change.
A. Flexible Conduit:
1. To BS EN 61386-23, watertight, PVC sheathed, spiraled metal type. The
conduit shall be terminated at boxes and equipment by means of approved
compression glands
2. To be of the unpacked type for normal atmospheric conditions and non-
asbestos packaged for damp situations. Adapters shall be of the solid type
3. Flexible conduit shall be used for the final connection of rigid conduit to the
terminal boxes of machines fitted with a means of drive adjustment and/or
where vibrations is likely to occur.
4. Length of flexible conduit for recessed and semi-recessed light fixtures shall be
maximum 1.5 meters.
B. Flexible Connections:
1. Where connections to electrical machines are to be by multicore glands, the
final termination shall be by ring type universal glands and locknuts, and
KEO/19-3262-0000 26 0533/6 Raceway And Boxes For Electrical Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
adequate slack cable in the form of a loop or spiral being left to allow for the
movement of motors necessitated by belt re-tensioning, vibration, etc.
A. Design
1. Surface-mounted or free-standing type, fabricated from zinc coated or
galvanized sheet steel minimum 1.5mm thick, Paint finish as approved for
distribution boards.
2. Fixed cover and padlocked hinged door; operable without obstruction.
3. Protected IP-31 for internal and IP-65 for outdoor use.
PART 3 - EXECUTION
3.01 GENERAL
3.02 PREPARATION
A. General
1. Run conduit in square, symmetrical lines, parallel to or at right angles to walls
and in accordance with the accepted practice
2. Conduit system shall be mechanically continuous and watertight after
installation. All conduit system shall be arranged wherever possible to be self
draining
3. Conduit runs between draw-in positions shall conform to local Regulations
regarding number of bends and extent of straight run
4. Conduit fill shall generally be less than 45%.
5. Keep conduits at least 100 mm from pipes and other non-electrical services
6. Where conduit runs are to be concealed in the structure or are to pass through
floor slabs, the Contractor shall be responsible for marking the accurate
positions of all chases and holes on site. The Contractor shall arrange the
conduit routing to make maximum use of any preformed conduit holes and slots
provided in structural beams. Conduit installation on shear walls shall be kept to
a minimum. All routings necessary on shear walls shall be agreed with the
Engineer’s Representative before work is put in hand
7. Install conduits so as not to interfere with ceiling inserts, lights or ventilation
outlets.
8. Earth continuity of steel conduits shall be mechanically & electrically continuous
throughout.
9. Provide pull wire in all empty conduits.
E. Concealed Conduit:
1. Fix securely to prevent movement before casting of concrete and screeds,
application of plaster and the like
2. Spacing of clips shall be not greater than as follows:
Conduit size Spacing
a. Up to 25 mm 600 mm
b. 32-38 mm 900 mm
c. 50 mm 1000 mm
3. Supports for exposed conduit shall be fixed at each side of bends.
F. Expansion Fittings:
1. Fix in conduit wherever it crosses as expansion joint in the structure to which it
is fixed.
H. Conduit Boxes:
1. Fix at all outlet points.
A. All conduits must be secured to outlet boxes, junction boxes or cabinets by placing
locknuts on outside of box and locknuts and bushings on the inside of box.
B. Conduits connecting recessed fixtures and their adjacent junction boxes must be
flexible metallic conduit 20 mm minimum size and shall be of sufficient length to permit
dropping of the fixture below the ceiling and to gain access to the junction box.
C. Conduit to motors shall be terminated in the conduit fittings on the motors, the final
connection being made with liquid tight flexible conduit and suitable liquid tight
connectors.
D. A green insulated 4 mm2 (minimum) tinned copper earth connection shall be made
between the solid conduit or cable sheath and the equipment, the copper cable being
run inside the flexible conduit. Couplings fitted to removable covers or non-metallic
equipment etc. shall be bonded to the earthing terminal of the equipment etc. Where
changes to flexible conduits occur, a watertight outlet box with threaded entries shall
be inserted and the earth connection made to an internal terminal. The cover screws
shall not be used for earthing connections.
A. Anchor enclosures and cabinets securely to wall and structural supports at each
corner.
B. Support trunking at 1.0m intervals with trapeze type hangers or wall brackets.
D. Support cables in vertical runs with pin-type supports at maximum 15m centers.
E. On vertical runs exceeding 6m support cable with projecting pin-type supports with
heat shrunk sleeve fixed to trunking body by welding or pop riveting.
F. Make connections to accessories with pop riveted or welded joints. Radius or gusset
bends and tees.
I. Provide galvanized draw wire in every trunking conduit which is left for wires and
cables. Not less than 300mm slack shall be left at each end of the draw wire.
3.07 FIRESTOPPING
A. Install conduits sealing where they enter or leave hazardous locations. Provide
firestopping at fire compartment areas. Locate fittings at suitable, approved, accessible
locations and fill them with approved sealing compound.
3.08 CLEANING
A. The conduit outlets when installed and before wiring shall be temporarily closed by
means of well fitting wooden plugs, and immediately before cables are drawn in,
conduits systems shall be thoroughly swabbed out until they are dry and clean.
B. Upon completion of installation of system, including outlet fittings & devices, inspect
exposed finish, remove burrs, dirt & construction debris and repair damages finish
including chips, scratches & abrasions.
3.09 PROTECTION
C. Repair damage to PVC or paint finishes with matching touch up coatings per
manufacturer’s recommendations.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section to include the supply, installation and missioning of Cable trays, Ladder
racks, Wire basket cable Trays and accessories work in accordance with the Project
Documentation.
1. Cable trays, supports and accessories
2. Wire basket cable trays, supports and accessories
3. Ladder racks, supports and accessories
1.03 SUBMITTALS
A. Product Data: Include data indicating dimensions and finishes for each type of cable
tray/ ladder racks indicated.
C. Coordination Drawings: Floor plans and sections, drawn to scale. Include scaled cable
tray/ ladder racks layout and relationships between components and adjacent structural,
electrical, and mechanical elements. Show the following:
1. Vertical and horizontal offsets and transitions.
2. Clearances for access above and to side of cable trays/ ladder racks.
3. Vertical elevation of cable trays/ ladder racks above the floor or bottom of ceiling
structure.
B. Source Limitations: Obtain cable tray components through one source from a single
manufacturer.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
A. Store indoors to prevent water or other foreign materials from staining or adhering to
cable tray/ ladder racks. Unpack and dry wet materials before storage.
1.08 COORDINATION
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Spare parts recommended by manufacturer for two years of normal operations.
2. Tools required for maintenance.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.02 GENERAL
A. The cable tray system shall be of one manufacturer and shall include factory-made
trays, tray fittings, connectors and necessary accessories and supports to form a
complete cable support system.
B. The cable tray system shall include the following factory-made tray elements:
1. Straight cable trays and ladder racks
2. Fittings as horizontal and vertical bends of various angles, crosses, tees, wyes,
reducers, vertical riser elements
3. Connectors
4. All necessary fixing accessories.
C. Manufacturer’s standard accessories shall be used and site fabrication shall not be
permitted.
E. Determine the sizes of the cable trays based on the number and size of cables laid on
the cable trays plus 20% space for future growth. Cables laid on cable trays shall be
spaced twice their overall diameter (consider the largest cable as reference). In case of
discrepancy with the contract documents this clause shall prevail, unless approved.
A. The cable tray material shall be hot rolled or cold rolled steel sheet to
B. BS 1449-1.1:1991. The whole of the tray work, trays, fittings, and supports shall be of
mild steel hot dipped galvanized after manufacture to BS EN ISO 1461:2009. The
thickness of the protective sheath on any element shall not be less than 55 microns.
C. Cable trays shall be constructed from mild steel hot dip galvanized.
D. Insert elements, bolts, screws, pins, etc., shall be mild steel zinc plated.
F. All trays (straight and fittings) shall be welded construction and be a heavy duty returned
flanged, perforated type, unless specified otherwise. The minimum thickness of heavy
duty returned flanged cable trays shall be 1.5mm for trays up to 300mm wide and
2.0mm for trays up to 600mm wide.
G. Tray components shall be accurately rolled or formed to close tolerances and all edges
rounded. Flanges shall have full round smooth edges.
H. For all trays, flanges shall be a minimum of 50 mm deep, unless otherwise specified.
I. Cable tray width and radius of curved sections shall be selected to suit the number of
cables as shown on drawings and to the approval of the Engineer.
A. Fittings: Tees, crosses, risers, elbows, and other fittings as indicated, of same materials
and finishes as cable tray.
C. Cable tray shall consist of continuous, rigid, welded steel wire mesh cable management
system, to allow continuous ventilation of cables and maximum dissipation of heat, with
UL Classified splices where tray acts as Equipment Grounding Conductor (EGC).
Provide splices, supports, and other fittings necessary for a complete, continuously
grounded system. Wire mesh cable tray shall have continuous Safe-T-Edge T-welded
top side wire to protect cable insulation and installers.
1. Mesh: 50 x 100 mm.
2. Straight Section Lengths: 3,000 mm.
3. Wire Diameter: Patented design includes varying wire sizes to meet application
load requirements; to optimize tray strength; and to allow tray to remain
lightweight.
4. Safety Edge: Patented Safety Edge technology on side wire to protect cable
insulation and installers’ hands.
5. Fittings: Wire mesh cable tray fittings are field-fabricated from straight tray
sections, in accordance with manufacturer’s instructions.
A. Fittings/Supports: Wire mesh cable tray fittings are field fabricated from straight tray
sections, in accordance with manufacturer’s instructions. Supports will include the FAS
(Fast Assembly System) where possible so that screws, bolts, and additional tools are
not required for cable tray mounting; installation time is reduced; and tray path can
adapt to installation obstacles without the need for additional parts. Place supports so
that support span does not exceed as per manufacturer’s recommendations.
1. Ceiling-mounted supports mount to ceiling structure directly or with ¼”, 3/8” or ½”
threaded rod.
2. Wall-mounted supports
3. Underfloor supports mount directly to floor or to floor posts.
4. Splices, including those approved for electrical continuity (bonding), as
recommended by cable tray manufacturer.
5. Accessories: As required to protect, support, and install a cable tray system.
A. Ladder rack shall be supplied and installed in the locations indicated on the drawings.
C. The profile of the side members shall remain constant for the straight cable ladder and
the cable ladder fittings.
D. The longitudinal side members shall have a height of 125mm and a flange width of
25mm.
G. The transverse members shall be evenly spaced at 300mm centers along the length of
the straight cable ladder.
I. Ladder racks shall be manufactured from Steel Deep galvanized (generally complying to
grade S355 to BS EN 10025) and shall be deep galvanized after manufacture to twice
the coating thickness specified by BS EN ISO 1461.and capable of carrying cables in a
single layer formation with a maximum deflection of 14mm (between supports) when the
rack is fully loaded.
K. The couplers shall be profiled to match the profile of the cable ladder. The couplers shall
be secured using M10 square-shouldered bolts with rounded heads. The bolts shall be
secured with M10 hex nuts and M10 shake-proof washers as standard. The couplers
shall have a slot pattern which prevents slip between adjacent straight ladder lengths
and between cable ladder fittings. The couplers shall have a slot pattern which allows
for easy connection to cut lengths of straight cable ladder without the need for onsite
drilling.
PART 3 - EXECUTION
3.01 GENERAL
3.02 EXAMINATION
3.03 PREPARATION
B. Prepare surfaces using the methods recommended by the manufacturer for achieving
the best result for the substrate under the project conditions.
A. Install as a complete system, including all necessary fasteners, hold-down clips, splice-
plate support systems, barrier strips, hinged horizontal and vertical splice plates,
elbows, reducers, tees, and crosses.
B. In General the distance between two cables on cable tray shall not be less than twice
the diameter of the largest cable.
C. Remove burrs and sharp edges from cable trays/ ladder rack.
E. Make connections to equipment with flanged fittings fastened to cable tray/ ladder rack
and to equipment. Support cable tray/ ladder rack independent of fittings. Do not carry
weight of cable tray/ ladder rack on equipment enclosure.
F. Install expansion connectors where cable tray/ ladder rack crosses building expansion
joint. Space connectors and set gaps according to applicable standard.
I. Seal penetrations through fire and smoke barriers according to Division 07 Section
"Firestopping."
J. Sleeves for Future Cables [where required]: Install capped sleeves for future cables
through firestop-sealed cable tray/ ladder rack penetrations of fire and smoke barriers.
K. Workspace: Install cable trays/ ladder rack with enough space to permit access for
installing cables.
L. After installation of cable trays/ ladder rack is completed, install warning signs in visible
locations on or near cable trays/ ladder racks.
A. Install cables only when cable tray/ ladder rack installation has been completed and
inspected.
KEO/19-3262-0000 26 0536/7 Cable Trays And Ladder For Electrical System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. Fasten cables on horizontal runs with cable clamps or cable ties. Tighten clamps only
enough to secure the cable, without indenting the cable jacket.
C. On vertical runs, fasten cables to tray every 450 mm. Install intermediate supports
when cable weight exceeds the load-carrying capacity of the tray/ rungs.
D. In existing construction, remove inactive or dead cables from cable tray/ ladder rack.
A. Cable trays/ ladder rack and accessories shall be electrically and mechanically
continuous throughout their length.
B. The entire cable tray/ ladder rack system shall be bonded and 12 mm x 2.5 mm tinned
copper links shall be bolted across each joint in the system by means of bronze nut and
bolts, complete with flat and spring washers.
C. All cable trays/ ladder rack shall be provided with earth continuity copper tape (3 x
25mm) along the whole route of cable trays which shall be bonded to the main earthing
system of the facility. The earth continuity copper tape shall be fixed on cable tray/
ladder rack by means of PVC covered saddles or by other means approved by the
Engineer.
B. Earth cable trays against fault current, noise, lightning, and electromagnetic interference
by mounting grounding wire to each 3m cable tray section with earthing clamp as per
manufacturer recommendations
A. After installing cable trays/ ladder racks and after electrical circuitry has been energized,
survey for compliance with requirements. Perform the following field quality-control
survey:
1. Visually inspect cable insulation for damage. Correct sharp corners,
protuberances in cable tray/ ladder rack, vibration, and thermal expansion and
contraction conditions, which may cause or have caused damage.
2. Verify that there is no intrusion of such items as pipe, hangers, or other
equipment that could damage cables.
3. Remove deposits of dust, industrial process materials, trash of any description,
and any blockage of tray/ ladder rack ventilation.
4. Visually inspect each cable tray/ ladder rack joint and each ground connection for
mechanical continuity. Check bolted connections between sections for corrosion.
Clean and retorque in suspect areas.
5. Check for missing or damaged bolts, bolt heads, or nuts. When found, replace
with specified hardware.
6. Perform visual and mechanical checks for adequacy of cable tray/ ladder rack
earthing; verify that all takeoff raceways are bonded to cable tray/ ladder rack.
3.09 PROTECTION
3.010 FIRESTOPPING
A. Install sealing fittings wherever cable trays/ ladder racks enter or leave hazardous
locations. Provide firestopping at fire compartment areas. Locate fittings at suitable,
approved, accessible locations and fill them with approved sealing compound.
B. Fire stopping materials and installation requirements are specified in Division 07 Section
07 8400 "Firestopping."
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This section specifies the requirements for duct bank and manholes.
1.03 DESCRIPTION
A. Duct bank and manholes shall be provided as specified and shown on the drawings.
1.04 SUBMISSIONS
A. Shop Drawings submission shall include dimensional drawings of the duct bank and
manholes, including sections and elevations, showing the following:
1. Sizes and positions of manholes
2. Duct routing
3. Location of entry to buildings
4. Other pertinent data.
B. Coordinate layout and installation of Underground Ducts and Raceways with other
construction elements to ensure adequate working clearance.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Spare parts recommended by manufacturer for two years of normal operations.
2. Tools required for maintenance.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.02 GENERAL
B. The specification shall be in accordance with latest edition of local and International
regulations.
KEO/19-3262-0000 26 0543/2 Underground Ducts And Raceways For Electrical Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. The product selected and proposed shall include manufacturer's instructions that
indicate application conditions and limitations of use stipulated by the product testing
agency specified under Regulatory Requirements.
D. The contractor shall select the product only from the manufacturer specializing in
manufacturing products specified in this section with minimum five years documented
experience of the products being satisfactorily in use in a similar service and climatic
conditions.
E. The contractor shall ensure proper co-ordination with related civil and other project
associated activities prior to the selection of the equipment.
F. The contractor shall clearly show locations and arrangements of fittings on the drawings.
H. Provide detail routing and termination locations of duct bank prior to excavation. for
rough in.
B. Rigid Plastic Underground Conduit: UL 651A, Type A PVC; UL 651A, Type EB PVC;
High-density polyethylene, Schedule 40 or Fibreglass-reinforced epoxy as specified or
indicated.
B. Joining Method: Tapered bell and spigot joints, threaded joints or saw-cut system as
specified.
KEO/19-3262-0000 26 0543/3 Underground Ducts And Raceways For Electrical Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2.07 PRE-CAST CONCRETE MANHOLES
2.08 ACCESSORIES
A. Underground Warning Tape: 100 mm wide plastic tape, detectable type, coloured yellow
with suitable warning legend describing buried electrical lines.
A. Frames and Covers: ASTM A48; Class 30B gray cast iron, 686 or 762 mm size as
specified or other approved standard and size, machine finished with flat bearing
KEO/19-3262-0000 26 0543/4 Underground Ducts And Raceways For Electrical Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
surfaces. Provide cover marked ELECTRIC, TELEPHONE or as directed by the
Engineer to indicate utility.
E. Cable Racks: Steel channel, 38 x 19 x 350 mm or other approved size, with fastener to
match mounting channel.
F. Cable Supports: Porcelain, Maple or other approved type clamps and saddles.
H. Sump Covers: ASTM A48; Class 30B gray cast iron or other approved standard.
PART 3 - EXECUTION
A. Install duct to locate top of ductbank at depths as indicated on drawings or install duct to
locate top of ductbank minimum specified or indicated mm below finished grade.
B. Install duct with minimum slope of 100 mm per 25.4 m (0.33 percent) or as specified or
indicated. Slope duct away from building entrances.
C. Cut duct square using saw or pipe cutter; de-burr cut ends.
F. Wipe non-metallic duct dry and clean before joining. Apply full even coat of adhesive to
entire area inserted in fitting. Allow joint to cure for 20 minutes, minimum.
G. Install no more than equivalent of two 90-degree bends between pull points.
K. Use suitable separators and chairs installed not greater than 1200 mm on centres.
O. Provide minimum 75-mm or other specified concrete cover at bottom, top, and sides of
ductbank.
P. Provide specified or indicated steel reinforcing bars in top of bank under paved areas.
S. Provide suitable pull string in each empty duct except sleeves and nipples.
T. Swab duct. Use suitable caps to protect installed duct against entrance of dirt and
moisture.
B. Install and seal precast sections in accordance with ASTM C891 or other approved
standard.
D. Use precast neck and shaft sections to bring manhole cover to finished elevation.
F. Where specified or indicated, install drains in manholes and connect to site drainage
system or provide DN100 pipe terminating in 1/4 cu m crushed gravel bed under
provisions of relevant section.
G. Damp proof exterior surfaces, joints, and interruptions of manholes after concrete has
cured 28 days, under provisions of relevant section.
B. Formwork: Form inside and outside manhole surfaces in accordance with provisions of
relevant section.
D. Concrete: Provide air-entrained, 2000 psi (20 mPa) compressive strength at 28 days
under the provisions of relevant section or as specified.
KEO/19-3262-0000 26 0543/6 Underground Ducts And Raceways For Electrical Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
E. Shape: As specified or indicated.
I. Base: Include 350 mm drain opening and two 25 mm ground rod openings where
specified. Slope to drain at 6.35 mm per m (2 percent).
J. Top: Include 1000-mm diameter or other approved size and shape opening; cast 13-
mm rod in opening to accept ladder hook.
N. Construct brick collar with 760-mm or approved size clear opening to bring cover to
proper elevation.
O. Manhole Steps: Cast steps at 300 or specified mm on centre vertically or install ladder
in each manhole.
Q. Install drains in manholes and connect to site drainage system or provide 100 mm pipe
terminating in 0.25 cu m crushed gravel bed under provisions of relevant section where
specified or indicated.
R. Damp-proof exterior surfaces, joints, and interruptions of manholes after concrete has
cured 28 days, under provisions of relevant section.
A. General
1. The manufacturer shall provide proof of a stringent Quality Control (QC) Plan or
Inspection Test Plan (ITP). In particular the main equipment manufacturing
stages sanctioned by appropriate tests such as: incoming components
inspection, discrete sub-assembly tests and complete functional checks on the
final product. Final inspection and calibration operations shall be documented in
a report drawn up by the supplier’s Quality Inspection department.
2. The Assembly shall not leave the manufacturer’s works until the works test
sheets have been duly approved and stamped by the Engineer and written
permission is obtained for their dispatch to site.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.03 SUBMITTALS
C. Samples: For each type of label and sign to illustrate size, colors, lettering style,
mounting provisions, and graphic features of identification products.
B. Installers Qualifications: Firm with at least 3 years of installation experience with projects
utilizing electrical identification work similar to that required for this project.
1.06 COORDINATION
C. Coordinate installation of identifying devices with location of access panels and doors.
D. Install identifying devices before installing acoustical ceilings and similar concealment.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
A. Comply with latest Edition ANSI A.13.1 for minimum size of letters for legend and for
minimum length of color field for each raceway and cable size.
C. Self-Adhesive Vinyl Labels: Preprinted, flexible label laminated with a clear, weather and
chemical resistant coating and matching wraparound adhesive tape for securing end of
legend label.
F. Self-Adhesive Vinyl Tape: Colored, heavy duty, waterproof, fade resistant; 50 mm wide;
compounded for outdoor use.
A. Color-Coding Conductor tape: Colored, self-adhesive vinyl tape not less than 0.08 mm
thick by 25 to 50 mm wide.
C. Aluminum Wraparound Marker Labels: Cut from 0.35mm thick aluminum sheet, with
stamped, embossed, or scribed legend, and fitted with tabs and matching slots for
permanently securing around wire or cable jacket or around groups of conductors.
D. Metal Tags: Brass or aluminum, 50 by 50 by 1.3 mm, with stamped legend, punched for
use with self-locking nylon tie fastener.
E. Write-On Tags: Polyester tag, 0.38 mm thick with corrosion-resistant grommet and
polyester or nylon tie for attachment to conductor or cable.
1. Marker for Tags: Permanent, waterproof, black in marker recommended by tag
manufacturer.
E. Warning label and sign shall be in both English and Arabic and shall include, but are not
limited to the following legend:
1. Multiple Power Source Warning: “DANGER – ELECTRICAL SHOCK HAZARD –
EQUIPMENT HAS MULTIPLE POWER SOURCES.”
2. Medium Voltage: “DANGER-MEDIUM VOLTAGE, KEEP AWAY, BURIED
CABLE, DO NOT TOUCH SWITCH.”
3. High Voltage “DANGER HIGH VOLTAGE”, “KEEP AWAY”, “BURIED CABLE”,
“DO NOT TOUCH SWITCH”.
A. Engraved, laminated acrylic or melamine plastic, minimum 1.6 mm thick for signs up to
129 sq. cm and 3.2 mm thick for larger sizes and done in both Arabic and English
languages.
1. Engraved legend with black letters on white face
2. Punched or drilled for mechanical fasteners.
3. Framed with mitered acrylic molding and arranged for attachment at applicable
equipment.
B. Adhesive Film Label with Clear Protective Overlay: Machine printed, in black, by
thermal transfer or equivalent process. Minimum letter height shall be 10 mm. Overlay
shall provide a weatherproof and ultraviolet-resistant seal for label.
E. Stenciled Legend: In nonfading, waterproof, black, ink or paint. Minimum letter height
shall be 25 mm.
A. Cable Ties: Fungus-inert, self-extinguishing, 1-piece, self-locking, Type 6/6 nylon cable
ties.
1. Minimum Width: 5 mm.
2. Tensile Strength: 22.6 kg, minimum.
3. Temperature Range: Minus 40 to plus 85 deg C.
4. Color: Black, except where used for color-coding.
B. Paint: Paint materials and application requirements are specified in Division 09 painting
Sections.
1. Exterior Concrete, Stucco and Masonry (Other Than Concrete Unit Masonry)
a. Semi-gloss Acrylic-Enamel Finish: Two finish coats over a primer
1) Primer: Exterior concrete and masonry primer.
2) Finish coats: Exterior semi-gloss acrylic enamel.
2. Exterior Concrete Masonry
a. Semi-gloss Acrylic-Enamel Finish: Two finish coats over a block filler
1) Primer: Concrete unit masonry block filler.
2) Finish coats: Exterior semi-gloss acrylic enamel.
3. Exterior Ferrous Metal
a. Semi-gloss Alkyd-Enamel Finish: Two finish coats over a primer.
1) Primer: Exterior ferrous-metal primer.
2) Finish coats: Exterior semi-gloss alkyd enamel.
4. Exterior Zinc Coated Metal (except Raceways).
a. Semi-gloss Alkyd-Enamel Finish: Two finish coats over a primer.
1) Primer: Exterior zinc coated metal primer.
2) Finish coats: Exterior semi-gloss alkyd enamel.
5. Interior Concrete and Masonry (other than Concrete Unit Masonry)
a. Semi-gloss Alkyd-Enamel Finish: Two finish coats over a primer.
1) Primer: Interior concrete and masonry primer.
2) Finish coats: Interior semi-gloss alkyd enamel.
6. Interior Concrete Unit Masonry
a. Semi-gloss Acrylic Enamel Finish: Two finish coats over a primer.
1) Block Filler: Concrete unit masonry block filler.
2) Finish coats: Interior semi-gloss acrylic enamel.
7. Interior Gypsum Board
a. Semi-gloss Acrylic Enamel Finish: Two finish coats over a primer.
1) Primer: Interior Ferrous-metal primer.
2) Finish coats: Interior semi-gloss acrylic enamel.
8. Interior Ferrous Metal
a. Semi-gloss Acrylic Enamel Finish: Two finish coats over a primer.
1) Primer: Concrete ferrous metal primer.
2) Finish coats: Interior semi-gloss acrylic enamel.
9. Interior Zinc Coated Metal (except Raceways)
KEO/19-3262-0000 26 0553/5 Identification For Electrical Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
a. Semi-gloss Acrylic Enamel Finish: Two finish coats over a primer.
1) Primer: Interior zinc coated metal primer
2) Finish coats: Interior semi-gloss acrylic enamel.
C. Fasteners for Labels and Signs: Self-tapping stainless steel screws or stainless steel
machine screws with nuts and flat and lock washers
PART 3 - EXECUTION
3.01 APPLICATION
A. Raceways and Duct banks More Than 600 V Concealed within Building: 100 mm wide
black stripes on 250mm centers over orange background that extends full length of
raceway or duct and is 300mm wide. Stencil legend “DANGER CONCEALED” HIGH
VOLTAGE WIRING” witn 75mm high black letters on 500mm centers. Stop stripes at
legends. Apply to the following finished surfaces:
1. Floor surface directly above conduits running beneath and within 300mm of a
floor that is in contact with earth or is framed above unexcavated space.
2. Wall surface directly external to raceways concealed within wall.
3. Accessible surfaces of concrete envelope around raceways in vertical shafts,
exposed in the building, or concealed above suspended ceilings.0
B. Accessible Raceways and Metal-Clad Cables, 600 V: Identify with “DANGER HIGH
VOLTAGE” in black letters at least 50mm high, with self-adhesive vinyl labels snap
around labels. Repeat legend at 3m maximum intervals.
C. Accessible Raceways and Metal-Clad cables, 600 V or less, Service, Feeder and
Branch Circuits More Than 13 A: Identify with orange self-adhesive vinyl label snap-
around label self-adhesive vinyl tape applied in bands,
D. Accessible Raceways and Cables of Auxiliary Systems: Identify the following systems
with color-coded, self-adhesive vinyl tape applied in bands, snap around color coding
bands.
1. Fire Alarm System: Red
2. Fire Suppression Supervisory and Control System: Red and Yellow
3. Combine Fire Alarm and Security System: Red and Blue
4. Security System: Blue and Yellow
5. Mechanical and Electrical Supervisory System: Green and blue.
6. Telecommunication System: Green and yellow.
7. Control Wiring: Green and red.
F. Branch-Circuit Conductor Identification: Where there are conductors for more than
three branch circuits in same junction or pull box, use color-coding conductor tape
marker tape aluminum wrap around marker labels. Identify each ungrounded conductor
according to source and circuit number.
G. Conductors to Be Extended in the Future: Attach marker tape to conductors and list
source and circuit number.
KEO/19-3262-0000 26 0553/6 Identification For Electrical Systems
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
H. Auxiliary Electrical Systems Conductor Identification: Identify field-installed alarm,
control, signal, sound, intercommunications, voice, and data connections.
1. Identify conductors, cables, and terminals in enclosures and at junctions,
terminals, and pull points. Identify by system and circuit designation.
2. Use system of marker tape designations that is uniform and consistent with
system used by manufacturer for factory-installed connections.
3. Coordinate identification with Project Drawings, manufacturer's wiring diagrams,
and Operation and Maintenance Manual.
I. Locations of Underground Lines: Identify with underground lines warning tape for
power, lighting, communication and control wiring and optical fiber cable. Limit use of
underground line warning tape to direct buried cables. Install underground line
warning tape for both direct buried cables and cables in raceway.
J. Warning Labels for Indoor Cabinets, Boxes, and Enclosures for Power and Lighting:
Comply with BS Standards and apply self-adhesive warning labels baked enamel
warning signs metal backed buried butyrate warning signs. Identify system voltage with
black letters on an orange background. Apply to exterior of door, cover, or other
access.
1. Equipment with Multiple Power or Control Sources: Apply to door or cover of
equipment including, but not limited to, the following:
a. Power transfer switches.
b. Controls with external control power connections.
2. Equipment Requiring Workspace Clearance According to latest BS Standards:
Unless otherwise indicated, apply to door or cover of equipment but not on flush
panel boards and similar equipment in finished spaces.
K. Instruction Signs:
1. Operating Instructions: Install instruction signs in both English and Arabic
languages to facilitate proper operation and maintenance of electrical systems
and items to which they connect. Install instruction signs with approved legend
where instructions are needed for system or equipment operation.
2. Emergency Operating Instructions: Install instruction signs in both English and
Arabic languages with white legend on a red background with minimum 10mm
high letters for emergency instructions at equipment used for power transfer load
shedding.
3.02 INSTALLATION
B. Location: Install identification materials and devices at locations for most convenient
viewing without interference with operation and maintenance of equipment.
C. Apply identification devices to surfaces that require finish after completing finish work.
E. Attach non adhesive signs and plastic labels with screws and auxiliary hardware
appropriate to the location and substrate.
F. System Identification Color Banding for Raceways and Cables: Each color band shall
completely encircle cable or conduit. Place adjacent bands of two-color markings in
contact, side by side. Locate bands at changes in direction, at penetrations of walls and
floors, at 15-m maximum intervals in straight runs, and at 7.6-m maximum intervals in
congested areas.
H. Aluminum Wraparound Marker Labels and Metal Tags: Secure tight to surface of
conductor or cable at a location with high visibility and accessibility.
J. Painted Identification: Prepare surface and apply paint according to painting Section.
END OF SECTION
SWITCHBOARDS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section shall include the supply, installation, testing and commissioning of all
Switchboards including Low Voltage Panel (MLTB), Main Switchboards (MSB), Sub-
main Switchboards (SMSB) in accordance with the specifications and drawings.
1.03 SUBMITTALS
A. Product Data: For each type of switchboard, over-current protective device, transient
surge protection voltage suppression device, ground-fault protector, accessory, and
component indicated. Include dimensions and manufacturers' technical data on
features, performance, electrical characteristics, ratings, and finishes.
B. The prototype assemblies shall be with same components as proposed & shall confirm
to following 9 type tests (design verification by type testing) defined in IEC 61439(Part-
1&2):-
1. Verification of Strength of materials and parts (clause 10.2)
2. Verification of Degree of protection of enclosures (clause 10.3)
3. Verification of Clearances and creepage distances (clause 10.4)
4. Verification of Protection against electric shock and integrity of protective circuits
(clause 10.5)
5. Verification of Dielectric properties (clause 10.9)
6. Verification of Temperature-rise limits (clause 10.10)Temperature rise test shall
be conducted at 50degC lab temperature.
7. Verification of Short-circuit withstand strength (clause 10.11)
8. Verification of Electromagnetic Compatibility- EMC (clause 10.12)
9. Verification of Mechanical operation (clause 10.13)
C. The prototype assemblies shall confirm to following 3 design verification by design rules
as defined in IEC 61439(Part-1&2):-
1. Verification of Incorporation of switching devices and components (clause 10.6)
2. Verification of Internal electrical circuits and connections (clause 10.7)
3. Verification of Terminals for external conductors (clause 10.8)
D. The above Design Verification type test certificate along with drawing and details of the
original tested assembly and comparison study of the proposed board with the certified
assembly, shall be produced from one of these internationally recognized High voltage
Laboratories under ASTA or KEMA.
E. The local switchboard factory must have ASTA Diamond or KEMA Keur certification for
the proposed switchboards to guarantee final product quality.
F. Routine test: The panel assembler shall perform the routine test and provide the test
certificates as defined in IEC standards. The routine test shall include but not limited to
the following:
1. Inspection of the assembly including inspection of wiring and electrical
operational test (IEC Clause 8.3.1);
2. Dielectric test & Insulation resistance test (IEC Clause 8.3.2 & 8.3.4);
KEO/19-3262-0000 26 2413/2 Switchboards
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Checking of protective measures and of the electrical continuity of the protective
circuits (IEC Clause 8.3.3)
4. Functional test as per the approved test procedure.
G. Routine test certificates and test readings shall be submitted to the consultant engineer
for verification.
H. Prior to placing order of the equipment, ensure that the physical dimensions of the
equipment do not infringe the working space required by the applicable standards.
J. The switchgear manufacturer must have a previous record of satisfactory service for at
least (10) years.
L. Routine tests of all main switchboards and motor control centers manufactured by
overseas manufacturer shall be submitted for testing by an internationally approved
laboratory testing agency and test certificates issued accordingly shall be submitted
prior to delivery to shipment. Locally manufactured switchboards and control centers
shall be tested at the manufacturer’s testing laboratory witnessed. The tests shall be
done in accordance with IEC 61439-1&2 and other required tests as approved by the
Engineer.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
C. For those parts of equipment, where no mention is made of the relevant standard,
reference is made to the latest IEC standards.
D. In a situation where a conflict occurs between these standards, the most stringent shall
be applied.
A. The Contractor shall carry out and provide an over-current protective device. Co-
ordination study as part of his material submission, as outlined below:
C. All over-current protective devices on this project and the first upstream device of the
electrical system shall be coordinated so that they will perform as follows. When two or
more over-current protective devices (including the first upstream protective device of
the system) in series with each other experience current flow greater than their rated
current, the device with the lowest rated current shall trip and/ or open the circuit first
and thereby prevent the higher rated devices from operating.
D. The supplier of the over-current protective devices shall prepare a co-ordination study to
verify the above stated performance requirements. The study shall be documented by
the Supplier and the documents shall include but not be limited to the following:
1. A composite drawing or drawings (on full size, reproducible, log-log paper)
showing the entire electrical system (including the first upstream protective
device of the system) showing all protective device curves (including motor
overloads), short circuit duties, motor starting curves and damage curves for
motors, equipment and conductors. This drawing or drawings shall show that all
protective devices are properly coordinated to perform as stated above.
2. Manufacturer’s over-current operating curves (on full size, reproducible, log-log
paper) for each over-current device. In the case of fuses, both minimum melt and
maximum clearing time curves shall be included.
3. Reproducible copies of all project single line diagrams so marked to show short
circuit duties at all switchboards and motor control centers, and which operating
curve applies to each over-current device on the diagram (the operating curves
shall also be correspondingly marked)
4. A tabulation of the short circuit duties at all switchboards and motor control
centers, sizes and ratings of all over-current protective devices so that the
performance requirements are met. Protective devices which have earth fault
protection features are specifically required to meet this performance
requirement.
E. This documented coordination study shall be submitted for review before the over-
current devices are supplied for the Project.
KEO/19-3262-0000 26 2413/4 Switchboards
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1.07 DELIVERY, STORAGE, AND HANDLING
A. Deliver in sections or lengths that can be moved past obstructions in delivery path.
B. Store indoors in clean dry space with uniform temperature to prevent condensation.
Protect from exposure to dirt, fumes, water, corrosive substances, and physical
damage.
A. Installations Pathway: Remove and replace access fencing, doors, lift-out panels, and
structures to provide pathway for moving switchboards into place.
B. Product Selection for Restricted Space: Drawings indicate maximum dimensions for
Switchboard, including clearances. Comply with indicated maximum dimensions.
1.010 COORDINATION
B. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. 2% spare molded case circuit breakers of all different frame sizes, but in any
case not less than 2 nos. circuit breakers of each size.
2. 5% spare indicating lamps for each indicating lamp in the switchgear.
3. One set of tools required for switchgear maintenance.
4. Provide complete spare parts as recommended by the manufacturer for different
sizes of ACB.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.02 GENERAL
A. Provide complete distribution equipment which shall include Low Voltage Panel (MLTB/
Main Switchboards (MSB), Sub-main Switchboards (SMSB) and Feeder Pillars (FP).
A. General
1. The Low voltage panel shall be of indoor construction, dead front, metal
enclosed multi-cubicle type, free standing, dust and vermin protected, front
operated and of clean and modern appearances.
2. The Low voltage panel shall be assembled and coordinated by one manufacturer
and shall be constructed to Form 4B Type 7 in accordance with the requirements
of IEC61439-1 & 2. The Low voltage panel shall be made of folded steel
construction; minimum 2mm thickness, fully rust proofed and stove enameled.
The panel shall be IP-52 rated.
3. All exposed bolts or screw heads shall be chrome or cadmium plated.
4. All doors and removable covers or plates shall be provided with suitable PVC or
neoprene gaskets to prevent the ingress of dust, vermin and insects.
5. Each unit of the Low voltage panel shall be housed in its own cell fitted with a
hinged door mechanically interlocked in such a manner that the cell door can
only be opened when the switch is in the "OFF" position.
6. Switching units shall be arranged in separate compartments or sections to
prevent when handling the elements in the section and to prevent the spreading
of faults from one section to the other.
7. Adequate cableways shall be provided in the switchboard accessible by hinged
lids or removable covers.
8. The equipment in the switch boards shall be accessible with indicating
instruments mounted not higher than 2 m and the center lines of operating
devices not higher than 1.9 m above Low voltage panel base. The Low voltage
KEO/19-3262-0000 26 2413/6 Switchboards
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
panel shall be properly fixed to the floor with foundation bolts grouted in the floor
or bolted to channels laid across the cable trench.
9. The Low voltage panel shall have top or bottom cable entry as required. Main
incoming cables shall be bottom entry, with necessary cable glands.
10. The Low voltage panel shall contain the air circuits breakers, bus bars, bus
couplers, MCCBs, instruments, etc., as specified hereunder with ratings and
arrangement as shown on the Drawings and shall be complete with all-internal
wiring and connections.
11. The Low voltage panel shall be tested, at the manufacturer’s premises as well as
after installation in accordance with tests stipulated in IEC 61439-1 & 2 and
witnessed. “Design verification” type test certificates shall be submitted as part
of material submittal.
B. Busbars
1. Busbars shall be of electrolytic hard drawn copper to B.S. 159 with rating as
indicated on the Drawings, air insulated and rigidly supported by suitable non-
hygroscopic, anti-tracking insulators so as to withstand forces due to thermal
expansion under normal operating conditions and the fault currents specified and
neatly arranged for 500 V, Hz, 3 phase, 4 wire operation.
2. Busbars shall extend through the length of the board with the same cross section
throughout.
3. Busbars bracing shall maintain the same mechanical strength and current
carrying capacity under normal operating conditions and fault conditions as
indicated on the drawings.
4. Busbars shall be housed in separate adequately ventilated compartment, which
shall not contain any wiring or apparatus other than that required for connection
to busbars. Access to busbars and busbar connections shall be gained only by
removal of covers secured by bolts or studs. Busbars shall be covered with
colored PVC sleeves or painted for phase identification.
D. Current Transformers
1. Current transformer shall be of the bar primary type, air cooled and suitably
insulated. They shall be of Class 1 accuracy for measurements and of Class 10
P10 accuracy for protection in accordance with IEC 61869. The secondary
windings shall be rated at 5A.
E. Instruments
1. The measuring instruments shall include ammeters, voltmeters, power factor
meters, maximum demand indicators and selector switches and associated
accessories (such as measuring circuit protection) as indicated on the Drawings.
2. Measuring instruments shall be moving iron vane type, flush pattern with dust
and moisture-proof enclosures. The instruments shall have anti-glare glass
fronts, anti-parallax scales and white faces with black numerals and markings. All
instruments shall be a long scale 240°, with full load indicating approximately at
180° The instrument cases shall be semi-flush mounted and shall be 36 x 36mm
square. Accuracy shall be one per cent of full-scale values. Moving elements
shall be provided with zero adjustments external to the cases, located at face of
dial.
3. Ammeters shall be moving iron type, to BS 89 scaled in accordance to their
circuit breakers. Ammeters shall be capable of withstanding twice the rated
current for ten (10) minutes and overload sustained under fault conditions,
without damage or loss of accuracy.
4. Voltmeters shall be moving iron type to BS 90 scaled 0-500V and provided with
6-position selector switches allowing reading of line to line and line to neutral
voltages.
5. Voltmeters shall withstand twice the rated full-scale voltage, for 1.0 minute,
without damage.
6. Maximum demand indictors shall be of the thermal type with a 20-minute time
delay.
7. Digital indictors for above-mentioned measuring instruments may be provided
subject to approval.
F. Meters
1. Kilowatt-hour meters shall be provided as per the requirements of the local
Electrical Power Authority. They shall be dust and vermin proof and shall be of
robust construction so that they will keep their accuracy over many years of
service under the local climatic conditions. The counters shall be of the
cyclometer type with six digits to give direct reading of power consumptions, the
lowest figure being units and not tenths of units. Pointer type counters are not
acceptable. The calibrating adjustment should be operated by screwdriver only.
KEO/19-3262-0000 26 2413/9 Switchboards
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
Meters should have not less than 5-mm diameter terminal holes and shall be
operated through three suitably rated current transformers and the counter of the
meter should be calibrated to read the primary KWH.
2. All meters shall be handed over to the Power Supply Authorities for calibration
prior to final installation and connection.
3. All Kilowatt-hour meters shall be equipped with a pulse output (equivalent to the
metered energy), to provide an energy consumption scheme at a remote control
and monitoring system.
I. Protection Relays
1. Protection relays shall comply with IEC 60255.
2. Thermal overload relays shall be used for motors ratings, up to and including
11kW, giving protection against:
a. Over-current unbalance
b. Single phase
c. Earth fault
3. For motors rated above 11KW, multi-functional relays shall be used. Multi-
functional relays to include protection, metering, control, monitoring and
annunciating functions. It is envisaged that the following functions are available.
a. Overload
b. Over-current
c. Single phase
d. Earth fault
e. Under voltage
f. Over voltage
4. Plus digital indication of:
a. Relay settings % of FLC that the motor is taking
b. Continuous monitoring of thermal capacity of motor
c. Thermal capacity used during start of motor
d. If tripped, how much time before restart to take place
e. Stall or short circuit trip
f. Earth fault trip
g. Starting
5. Documentary evidence must be produced, showing the current/time
characteristic of each overload at its setting (hot/cold for the thermal overload)
overlaid on the motor manufacturers thermal stability time/current characteristic,
KEO/19-3262-0000 26 2413/11 Switchboards
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
for comparison. Consideration must be given as to the requested method of
starting (DOL, star delta, etc.).
6. All motor overload relays shall include a manual resetting facility.
K. Earth Bus
1. The earth bus shall be copper, minimum half the size of the main busbars
extending throughout the length of the switchboard and fixed to brass nuts
brazed to the steel members of the switchboards. The earth bus shall be
extended at the ends for connection to the earth electrodes and shall have
provision for terminating earth continuity conductors.
B. Battery: Maintenance free long life Nickel cadmium sealed type complying with
BSEN60623. System batteries shall be suitable for service at an ambient temperature of
50 deg C. Limit variation of current output to 0.8 percent. The battery should be of
adequate capacity to maintain full operation of the relevant load equipment plus an
additional 20 percent, for a period of 8 hours during main failure, assuming a normal
charge condition at the start of the mains failure.
C. All batteries shall be protected from mechanical damage and any accidental electric
shorting. All batteries shall be supplied in banks sized for easy handling and all
interconnections shall be included Batteries shall not be so ventilated that gases do not
permeate into adjacent equipment.
D. Charger: Static-type silicon rectifier equipped with automatic regulation and provision for
manual and automatic adjustment of charging rate. Unit shall automatically maintain
output voltage within 0.5 percent from no load to rated charger output current, with ac
input-voltage variation of plus or minus 10 percent and input-frequency variation of plus
or minus 3 Hz. Other features of charger include the following: The charger shall include
but not limited to the following features:
1. DC ammeter
2. DC Voltmeter: Maximum error of 5 percent at full-charge voltage; operates with
toggle switch to
3. Select between battery and charger voltages.
4. Ground Indication: Two appropriately labeled lights to indicate circuit ground,
connected in series between negative and positive terminals, with midpoint
junction connected to ground by normally open-push button contact.
5. Capacity: Sufficient to supply steady load, float-change battery between 2.20 and
2.25 V per cell and equalizing charge at 2.33 V per cell.
A. General:
1. The main/ sub-switch boards shall comprise of main isolator, bus bars, branch
circuit moulded circuit breakers, earth leakage relays, ammeters, voltmeters,
indicating lamps etc. all housed in a sheet steel cabinet, rust-proof stove
enameled, equipped with a hinged door fitted with a suitable locking device.
2. The assembly of the boards shall be such that the main isolator and the outgoing
MCCBs cannot be reached when the door(s) of the cabinet are open. To gain
access to the components, cables and terminations of a switch board, another
cover metal sheet fastened to the cabinet by screws need to be removed.
3. The switchboards shall be assembled taking into account the requirement of
ample space and adequate clearance to allow for wiring terminations and air
circulation to encounter heat dissipation.
B. Construction
1. The Main/ sub-switch boards shall be floor standing, totally enclosed, cubicle
type, dust protected and vermin proof, containing the main components shown
on the drawings and/or specified herein above.
2. Switchboards shall be factory assembled and constructed to Form 2A Type 2 in
accordance with IEC 61439-1&2, unless indicated otherwise elsewhere in the
Project Documents. The panels shall be IP-52 rated if located indoor and IP-65
rated if located outdoor.
3. Cabinet to be suitable to withstand the fault current stresses available.
4. Cabinet to be constructed from sheet metal panels built up on main/ substantial
rolled steel or folded sheet steel sections framework.
5. Sheet metal for building large panels shall be not less than 16 SWG.
6. Switchboard shall be divided integrally with sheet metal webs to separate low
voltage equipment from instruments and control equipment and to ensure
overheating does not occur.
7. Access doors shall have concealed hinges, stops and interlocks where required,
and a dust excluding gasket contained in a rebate.
8. Door handles shall be the rotating type closing onto ramps, of approved pattern,
finished in a black, hard wearing non-conductive material.
9. Cabinet shall have adequate means for lifting and shall be capable of being
rolled or moved into the installation position and bolted directly to the floor.
10. Switchboards shall have necessary cut-outs, drillings and the point of entry of
feeders.
KEO/19-3262-0000 26 2413/14 Switchboards
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
11. After fabrication, steelwork shall be cleaned; zinc sprayed and stove enameled
with one primer coat, two undercoats and one finishing coat, the surface being
rubbed down after each coat.
12. Finished color: light grey.
13. The Main/ sub-switch boards shall be tested, at the manufacturer’s premises as
well as after installation in accordance with tests stipulated in IEC 61439-1&2 and
witnessed. Type test certificates by the manufacturer shall be submitted as part
of material submittal.
C. Components:
1. Components shall be the product of one manufacturer.
2. Switching and protective devices shall have clear on/off identification.
3. Circuit devices shall be individually mounted in a cubicle form, front accessible
for installation, adjustment and inspection and rear accessible for connection with
line and load connection terminals.
4. Components shall be labeled for easy identification.
D. Internal Wiring:
1. PVC insulated, color coded cables.
2. Factory installed, neatly bunched and supported and extended on to labeled
terminal boards for the connection of external services.
3. Terminals: anti-turn solder less type suitable for cable sizes shown on the
Drawings.
G. Bus Bars:
1. Electro-tinned, hard drawn, high conductivity copper suitably sleeved for phase
identification.
2. Rating: as indicated on the Drawings.
3. To be adequately supported by porcelain or moulded insulators spaced at
suitable centers so that the complete assembly can withstand the maximum
mechanical stresses to which it may be main/ subjected under fault conditions.
4. To be enclosed in separate compartments and arranged so that all conductors
can be brought onto the bars without undue bending.
5. Bus bar compartments shall not be used as switchboard wiring ways.
6. An earth bus bar, minimum half size of the main bus-bars, shall be provided for
the full length of each switchboard with each separate section of the board
bonded to it.
PART 3 - EXECUTION
3.01 GENERAL
A. Comply with the applicable installation requirements of the BS 7671: latest edition –
Requirements for Electrical Installations.
B. Conform to the requirements of the local power supply authorities having jurisdiction.
E. Frame and mount printed, basic operating instructions for switchboards, including
control and key interlocking sequences, and emergency procedures, fabricate frame of
3.02 IDENTIFICATION
A. Identify field-installed wiring and components and provide warning signs as specified
and required. Refer Division 26 Section “Identification for Electrical Services”.
B. Label each switchboard with engraved metal or laminated plastic nameplate mounted
with corrosion resistant screws.
A. Manufacturer's Field Services: Arrange and pay for the services of a factory-authorised
service representative to supervise the pre-testing and adjustment of switchboard
components.
D. Visual and Mechanical Inspections: Include the following Inspections and related work:
1. Inspect for defects and physical damage, testing laboratory, labels, and
nameplate compliance with up-to-date circuit connections.
2. Verify that potential transformers, including their overcurrent protection and
current transformers meet specified requirements.
3. Perform operational test and exercise of mechanical components and other
operable devices in accordance with manufacturer's instruction manual.
4. Check switchboard anchorage, area clearances, and alignment and fit of
components.
KEO/19-3262-0000 26 2413/17 Switchboards
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
5. Check tightness of bolted electrical connections with calibrated torque wrench.
Refer to manufacturer's instructions for proper torque values.
6. Clean switchboard interior and exterior-using manufacturer's approved methods
and materials.
7. Perform visual and mechanical inspection and related work for Overcurrent
Protective Devices
A. The complete installation shall be tested and commissioned by a certified third party
independent of the supplier and the contractor. The contractor shall be responsible to
demonstrate the operation of the system to the satisfaction of the Client's personnel.
The third Party testing agency shall submit the testing and commissioning reports for the
Engineers review outlining all deficiencies and course of action. The contractor shall
ensure all deficiencies outlined are rectified, retested, and certified by the third party
testing agency.
B. Infrared Scanning: Within 2 months of handover of the works, perform an infrared scan
of switchboard bus joints and connections. Open or remove metal doors, covers,
inspection plates, and barriers to make joints and connections accessible to a portable
scanner.
C. Follow-up Infrared Scanning: Perform 2 additional follow-up infrared scans of the same
joints and connections, one 4 months after handover and one 11 months after handover.
3.05 CLEANING
3.07 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
END OF SECTION
DISTRIBUTION BOARDS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section shall include the supply, installation, testing and commissioning of all
Distribution boards in accordance with the specifications and drawings.
1.03 SUBMITTALS
A. Product Data: For each type of distribution board, over-current protective device,
accessory, and component indicated. Include dimensions and manufacturers' technical
data on features, performance, electrical characteristics, ratings, and finishes.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
1. IEC 60898/ BS EN60 898: Specification for circuit breakers for over-current
protection for household and similar
installations.
2. IEC/ BS EN 61008-1-1996 Residual Current Circuit Breakers (RCCB)
without integral over-current protection for
household and similar uses.
3. IEC/ BS EN 61009-1-1996 Residual Current Circuit Breakers (RCBO)
with integral over-current protection for
household and similar uses.
4. IEC 60947-2 Low-voltage switchgear and controlgear - Part
2: Circuit-breakers
5. IEC 60529 Degree of protection of enclosures
6. IEC 61439-3 Distribution boards
A. Do not install panel boards until spaces are enclosed and weather tight wet work in
spaces is complete and dry, work above panel board is complete and temporary HVAC
System is operation and maintain ambient temperature and humidity condition at
occupancy levels during the remaindered the construction period.
1.08 COORDINATION
A. Coordinate layout and installation of panel boards and components with other
construction that penetrates walls or is supported by them, including electrical and other
B. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. 2% spare moulded case circuit breakers (MCCB) of all different frame sizes, but
in any case not less than 2 nos. circuit breakers of each size.
2. 5% spare miniature circuit breakers (MCB) of all different frame sizes, but in any
case not less than 2 nos. MCBs of each size.
3. 5% spare of load break switch (isolators) of each size.
4. 5% spare of Residual Current Devices (RCDs)
5. Lamps – provide five percent (5%) lamps of each size and type for indicating
panels and pilot lights installed for different systems.
6. One set of tools required for maintenance.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
A. Distribution Boards feeding lights, fans, sockets outlets and other appliances:
B. Cabinet:
1. Construction: robust sheet steel, fully rust proofed and stove enameled. The
Distribution Boards to a minimum of IP 41 if located indoor and IP 65 if located
outdoor and damp locations
2. Cabinet shall have a hinged door fitted with a lock and key.
3. The cabinet shall be constructed so that it is necessary to open the door to
operate miniature circuit breakers. Access to interior components and internal
wiring shall be gained by dismantling and removing a separate barrier within the
enclosure.
4. Gutter extension and barrier should be the same gauge and finishes panel board
enclosure.
5. Directory card: Inside the panel board mounted in transparent card holder.
C. Bus Bars:
1. To be of appropriate current carrying capacity at least equal to the rating of the
main incoming MCCB isolator.
2. To be copper.
F. Lighting Contactors:
1. To IEC 60947-4
2. Single coil, electrically operated, mechanically held type
3. Positive locking shall be obtained without the use of hooks, latches or semi-
permanent magnets.
4. Contactor rating and number of poles: as shown on the drawings
5. Operating coil; suitable for 240V, 50Hz supply
6. Main contacts: double break silver to silver type protected by arcing contacts
7. Contacts: self-aligning, renewable from the front panel
8. Solenoids: shaded pole pattern of such construction that lamination noise is
eliminated
9. Control of contactor: by local or remote switches as indicated. A manual
operating lever shall also be included
10. Separate bus bar shall be provided in the distribution boards for the
11. contactors controlling part of the lighting circuits
12. Lighting contactors controlling all or part of the lighting circuits of distribution
boards shall be mounted in the board enclosures
PART 3 - EXECUTION
A. Distribution board shall be flush mounted/surface mounted to suit the situation and as
directed at site. They shall be installed with the vertical sides plumb and the top of
Distribution Board at 220cm above finished floor level or as directed.
B. The boards shall be properly earthed by connecting an earthing conductor from the
main distribution earth bus bar to an earth connector welded to the cabinet and earthing
bushings on the incoming and outgoing feeder circuits.
D. Stub four 25mm empty conduits from distribution board into accessible ceiling space or
space designated to be ceiling space in the future. Stub four 25mm empty conduits into
raised floor space or below slab not on grade.
E. Arrange conductors in gutters into groups and bundle and wrap with wire ties after
completing load balancing.
3.02 CONNECTIONS
3.03 IDENTIFICATION
B. Create a directory to indicate installed circuit loads after balancing distribution board
loads. Obtain approval before installing. Use a computer or typewriter to create
directory; handwritten directories are not acceptable.
C. Distribution board Nameplates: Label each distribution board with engraved metal or
laminated-plastic nameplate mounted with corrosion-resistant screws.
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Engineers review outlining all deficiencies and
course of action. The contractor shall ensure all deficiencies outlined are rectified,
retested, and certified.
3.06 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
3.08 CLEANING
END OF SECTION
MOTOR-CONTROL CENTERS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section shall include the supply, installation, testing and commissioning of all
motor-control centers in accordance with the specifications and drawings.
1.03 SUBMITTALS
A. Product Data: For each type of controller and each type of motor-control center. Include
dimensions and manufacturer's technical data on features, performance, electrical
characteristics, ratings, and finishes.
A. “Design Verification” by type testing shall be performed for motor control centers as
defined in IEC 61439 (Part-1&2) standards through one of the international laboratories
listed under ASTA or KEMA.
B. The prototype assemblies shall be with same components as proposed & shall confirm
to following 9 type tests (design verification by type testing) defined in IEC 61439 (Part-
1&2):-
1. Verification of Strength of materials and parts (clause 10.2)
2. Verification of Degree of protection of enclosures (clause 10.3)
3. Verification of Clearances and creepage distances (clause 10.4)
4. Verification of Protection against electric shock and integrity of protective circuits
(clause 10.5)
5. Verification of Dielectric properties (clause 10.9)
6. Verification of Temperature-rise limits (clause 10.10)
Temperature rise test shall be conducted at 50degC lab temperature.
7. Verification of Short-circuit withstand strength (clause 10.11)
8. Verification of Electromagnetic Compatibility- EMC (clause 10.12)
9. Verification of Mechanical operation (clause 10.13)
C. The prototype assemblies shall confirm to following 3 design verification by design rules
as defined in IEC 61439(Part-1&2):-
1. Verification of Incorporation of switching devices and components (clause 10.6)
2. Verification of Internal electrical circuits and connections (clause 10.7)
3. Verification of Terminals for external conductors (clause 10.8)
D. The above Design Verification type test certificate along with drawing and details of the
original tested assembly and comparison study of the proposed board with the certified
assembly, shall be produced from one of these internationally recognized High voltage
Laboratories under ASTA or KEMA.
E. The local switchboard factory must have ASTA Diamond or KEMA Keur certification for
the proposed switchboards to guarantee final product quality.
F. Routine test: The panel assembler shall perform the routine test and provide the test
certificates as defined in IEC standards. The routine test shall include but not limited to
the following:
1. Inspection of the assembly including inspection of wiring and electrical
operational test (IEC Clause 8.3.1);
2. Dielectric test & Insulation resistance test (IEC Clause 8.3.2 & 8.3.4);
3. Checking of protective measures and of the electrical continuity of the protective
circuits (IEC Clause 8.3.3)
4. Functional test as per the approved test procedure.
G. Routine test certificates and test readings shall be submitted to the consultant engineer
for verification.
J. The switchgear manufacturer must have a previous record of satisfactory service for at
least (10) years.
L. Routine tests of all motor control centers manufactured by overseas manufacturer shall
be submitted for testing by an internationally approved laboratory testing agency and
test certificates issued accordingly shall be submitted prior to delivery to shipment.
Locally manufactured switchboards and control centers shall be tested at the
manufacturer’s testing laboratory witnessed. The tests shall be done in accordance with
IEC 61439-1&2 and other required tests as approved by the Engineer.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
C. For those parts of equipment, where no mention is made of the relevant standard,
reference is made to the latest IEC standards.
A. The Contractor shall carry out and provide an over-current protective device. Co-
ordination study as part of his material submission, as outlined below:
C. All over-current protective devices on this project and the first upstream device of the
electrical system shall be coordinated so that they will perform as follows. When two or
more over-current protective devices (including the first upstream protective device of
the system) in series with each other experience current flow greater than their rated
current, the device with the lowest rated current shall trip and/ or open the circuit first
and thereby prevent the higher rated devices from operating.
D. The supplier of the over-current protective devices shall prepare a co-ordination study to
verify the above stated performance requirements. The study shall be documented by
the Supplier and the documents shall include but not be limited to the following:
1. A composite drawing or drawings (on full size, reproducible, log-log paper)
showing the entire electrical system (including the first upstream protective
device of the system) showing all protective device curves (including motor
overloads), short circuit duties, motor starting curves and damage curves for
motors, equipment and conductors. This drawing or drawings shall show that all
protective devices are properly coordinated to perform as stated above.
2. Manufacturer’s over-current operating curves (on full size, reproducible, log-log
paper) for each over-current device. In the case of fuses, both minimum melt and
maximum clearing time curves shall be included.
3. Reproducible copies of all project single line diagrams so marked to show short
circuit duties at all switchboards and motor control centers, and which operating
curve applies to each over-current device on the diagram (the operating curves
shall also be correspondingly marked)
4. A tabulation of the short circuit duties at all switchboards and motor control
centers, sizes and ratings of all over-current protective devices so that the
performance requirements are met. Protective devices which have earth fault
protection features are specifically required to meet this performance
requirement.
E. This documented coordination study shall be submitted for review before the over-
current devices are supplied for the Project.
A. Deliver motor-control centers in shipping splits of lengths that can be moved past
obstructions in delivery path in professional manner.
1. Handle motor-control centers according to the Instructions of the manufacturer
for the Handling, Installation, Operation, and Maintenance of Motor Control
Centers rated not more than 600 Volts.
KEO/19-3262-0000 26 2419/4 Motor-Control Centers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Handle per Internationally recommended practices for installing and maintaining
Motor Control Centers.
A. Do not install Motor-Control Center until spares are enclosed & weather tight, wet work
in spaces is complete & dry, and temporary HVAC system is operating and maintain
ambient temperature & humidity control.
B. Product Selection for Restricted Space: Drawings indicate maximum dimensions for
MCCs, including clearances. Comply with indicated maximum dimensions.
1.010 COORDINATION
B. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03
Section "Cast-in-Place Concrete."
C. Coordinate features of motor-control centers, installed units, and accessory devices with
pilot devices and control circuits to which they connect.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. 5% spare moulded case circuit breakers (MCCB) of all different frame sizes, but
in any case not less than 2 nos. circuit breakers of each size.
2. Lamps – provide five percent (5%) lamps of each size and type for indicating
panels and pilot lights installed for different systems.
3. 5% spare combination magnetic motor starters.
4. 5% spare HRC fuses for each rating.
5. 5% spare of load break switch (isolators) of each size.
6. 5% spare of Residual Current Devices (RCDs)
7. One set of tools required for maintenance.
8. Provide complete spare parts as recommended by the manufacturer for different
sizes of ACB.
KEO/19-3262-0000 26 2419/5 Motor-Control Centers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. Spare parts shall be delivered to the Owner’s central storage facility.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.02 GENERAL
A. Motor control panel and starter control panel shall be of the same manufacturer as the
low voltage panel, switchboard and distribution boards.
B. Compartments: Modular; individual doors with concealed hinges and quick-captive crew
fasteners. Interlocks on combination controller units requiring disconnecting means in off
position before door can be opened or closed, except by operating a permissive release
device.
C. Wiring Spaces: Wiring channel in each vertical section for vertical and horizontal wiring
to each unit compartment; supports to hold wiring in place.
E. Short-Circuit Current Rating for Each Section: Equal to or greater than indicated
available fault current in symmetrical amperes at motor-control center location
2.04 BUSBARS
A. Bus bars shall be of electrolytic hard drawn copper to B.S. 159 with rating as indicated
on the Drawings, air insulated and rigidly supported by suitable non-hygroscopic, anti-
tracking insulators so as to withstand forces due to thermal expansion under normal
operating conditions and the fault currents specified and neatly arranged for 500 V, Hz,
3 phase, 4 wire operation.
B. Bus bars shall extend through the length of the board with the same cross section
throughout.
C. Bus bars bracing shall maintain the same mechanical strength and current carrying
capacity under normal operating conditions and fault conditions as indicated on the
drawings.
D. Bus bars shall be housed in separate adequately ventilated compartment, which shall
not contain any wiring or apparatus other than that required for connection to bus bars.
Access to bus bars and bus bar connections shall be gained only by removal of covers
secured by bolts or studs. Bus bars shall be covered with colored PVC sleeves or
painted for phase identification.
A. The moulded case circuit breakers shall comply with IEC60947-1 and IEC 60947-2
standards quick make and quick break type free toggle mechanism of utilization
category 'A' having rated service breaking capacity (Ics), suitable for isolation as per IEC
60947-2. The breaker shall be available in 3 or 4 pole version. . Evidence of the service
breaking capacity (Ics) shall be produced by test certificates from ASTA, KEMA or
CECI, the internationally recognized HV testing laboratories.
KEO/19-3262-0000 26 2419/7 Motor-Control Centers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. All MCCBs shall be factory tested by the manufacturer before dispatch and routine test
certificates shall be available. Random sampling test by the manufacturer is not
acceptable.
D. Tripping Characteristic: Circuit breakers shall have inverse time tripping characteristic
with automatic release secured through action of a combination of thermal-magnetic or
electronic trip units, tripping free the handle in case of an overload or a short circuit.
G. Electronic Trip Unit Circuit Breakers: MCCB with ratings up to 630A shall be equipped
with thermal magnetic or electronic trip units. The MCCB over 630 A frame size shall be
equipped with electronic trip units and shall sense the actual RMS values for the
following field-adjustable settings:
1. Instantaneous trip.
2. Long- and short-time pickup levels
3. Long- and short-time time adjustments
A. Heavy-duty type.
A. Stop lock-off push buttons for motors shall be the mushroom red stay-put type with
automatic latching, the units having to be key operated to be released.
2.014 METERS:
B. The measuring instruments shall include ammeters, voltmeters, power factor meters,
maximum demand indicators and selector switches and associated accessories (such
as measuring circuit protection) as indicated on the Drawings.
C. Measuring instruments shall be moving iron vane type, flush pattern with dust and
moisture-proof enclosures. The instruments shall have anti-glare glass fronts, anti-
parallax scales and white faces with black numerals and markings. All instruments shall
be a long scale 240°, with full load indicating approximately at 180° The instrument
cases shall be semi-flush mounted and shall be 36 x 36mm square. Accuracy shall be
one per cent of full-scale values. Moving elements shall be provided with zero
adjustments external to the cases, located at face of dial.
E. Voltmeters shall be moving iron type to BS 90 scaled 0-500V and provided with 6-
position selector switches allowing reading of line to line and line to neutral voltages.
F. Voltmeters shall withstand twice the rated full-scale voltage, for 1.0 minute, without
damage.
G. Maximum demand indictors shall be of the thermal type with a 20-minute time delay.
I. Power Monitoring Unit: The unit shall be microprocessor- based and shall be capable of
measuring and indicating incomer currents on each phase, voltages between phases
and phase to neutral, active and reactive powers, power factor and total energy
consumed. The KWH meter reading shall be stored in password protected non-volatile
memory. The unit shall be mounted on the incomer cubicle at a height not more than
1.6m from floor level. The backlit display unit shall be high contrast type, having light
emitting characters, of height not less than 15mm. The unit shall work on the system
voltage, without the need for any separate auxiliary power. The function of power
monitoring unit for remote indication and alarm shall be included.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine areas and surfaces to receive motor-control centers for compliance with
requirements, installation tolerances, and other conditions affecting performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 APPLICATIONS
A. Select features of each controller to coordinate with ratings and characteristics of supply
circuit and motor; required control sequence; duty cycle of motor, controller, and load;
and configuration of pilot device and control circuit affecting controller functions.
3.03 INSTALLATION
A. Anchor each motor-control center assembly to steel-channel sills arranged and sized
according to manufacturer's written instructions. Attach by bolting. Level and grout sills
flush with motor-control center mounting surface.
A. Coordinate size and location of concrete bases. Verify structural requirements with
structural engineer.
B. Concrete base is specified in Division 26 Section "Hangers and Supports for Electrical
Systems," and concrete materials and installation requirements are specified in
Division 03.
3.05 IDENTIFICATION
3.07 CONNECTIONS
3.09 ADJUSTING
3.010 TRAINING
A. The complete installation shall be tested and commissioned by a certified third party
independent of the supplier and the contractor. The contractor shall be responsible to
demonstrate the operation of the system to the satisfaction of the Client's personnel.
The third Party testing agency shall submit the testing and commissioning reports for the
Engineers review outlining all deficiencies and course of action. The contractor shall
ensure all deficiencies outlined are rectified, retested, and certified by the third party
testing agency.
3.012 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
WIRING DEVICES
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This section shall include all labor, materials, equipment, appliances and accessories
necessary for the complete performance of all switches, socket outlets etc. In
accordance with the Specifications and Drawings.
1.03 SUBMITTALS
B. Shop Drawings: List of legends and description of materials and process used for pre
marking wall plates.
C. Samples: One for each type of device and wall plate specified, in each color specified.
E. Operation and Maintenance Data: For wiring devices to include in all manufacturers'
packing label warnings and instruction manuals that include labeling conditions.
A. Source Limitations: Obtain each type of wiring device and associated wall plate through
one source from a single manufacturer. So far as they are available, obtain all wiring
devices and associated wall plates from a single manufacturer and one source.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Disconnecting Switches (Isolators) and Switch Fuses: 5% spare switch of each
size.
2. Plug fuses – provide ten percent (10%) of the number of each size and type of
fuses installed, but in any case not less than 6 nos. fuses of each size.
3. Wall switches – provide five percent (5%) of the number of each size and type of
wall switch installed.
4. Socket outlets – provide five percent (5%) of the number of each size and type
installed.
5. Tools required for maintenance.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
KEO/19-3262-0000 26 2726/2 Wiring Devices
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.02 GENERAL
A. All individual items of materials shall be of the same make throughout the Project unless
specifically approved by the Engineer.
B. All individual items of materials shall be of the same make throughout the Project unless
specifically approved by the Engineer.
Location Finishes
Back of House (BOH) Metalclad
Face plate of all Highly polished stainless-
switches, switched steel.
socket outlets, telephone
socket outlets, T.V.
socket outlets, computer
socket outlets…etc, used
for internal installation
D. Wiring shall be carried out in strict accordance with cable sizes and circuit details
provided in load schedules and on drawings. All wirings on multi point sub circuits shall
be carried out as a “loop in” system and no joints at any point in cable runs shall be
allowed.
E. Single phase circuits taken from TP and N Distribution Boards shall have their own
neutral connections.
F. Contractor shall pay attention to segregation of L. V. and wiring system for fire
detection, ICT, AV, security. system which may be either installed by him or by other
specialist sub- Contractors, to ensure that no interaction may occur between various
systems. Segregation of wiring system shall strictly comply with requirements of 16th
edition of IEE regulations, inclusive and equipment.
G. Coloring code and identification of cable cores shall be in accordance with IEE
regulations. All luminaires and wiring accessories shall be as described and specified in
schedule of luminaires and equipment.
A. Outlet Boxes:
1. Galvanized one piece pressed steel, sizes and designs shall suit devices to be
fitted and shall be complete with adjustable lugs and earth terminals
B. Outlet boxes mounted externally or in damp locations shall be totally sealed to ensure
water tightness.
2.04 SWITCHES
A. Lighting Switches
1. To BS EN 60669 - 1
2. To be rated 10, 15 or 20 amps depending on connected load, as stipulated in the
Ministry of Electricity and Water & Renewable Energy (MEW) regulations
3. Recessed with concealed conduit, surface pattern elsewhere
4. Quick make and break type
5. Single pole, double pole, one way, two way or intermediate as indicated
6. Surface mounted switches to be metallic and as indicated in the Project
Documentation
7. Flush mounted switches to be of the grid fixing type with finish as noted in the
Project document.
B. Waterproof Switches:
1. To be watertight IP 56 or as indicated in the Project Documentation
2. To be made of polycarbonate for indoor application in damp and wet areas.
C. Switch Plates
1. Where two or more switches are grouped together and connected to the same
phase, multi-gang devices and common plates shall be used.
A. Ceiling roses shall be of the all insulated type conforming to BS 67 with a white finish.
B. Ceiling roses shall be provided with insulated terminals for the switched live, neutral and
protective conductors; loop-in facilities shall be provided
C. Plug-in ceiling roses shall be used in areas, with extensive false ceiling system.
C. Weatherproof Sockets:
1. 13A Sockets: to BS 1363
2. 3 rectangular pins, switched type
3. To be water and dust tight enclosure, rated at IP 66 when in use
4. To be made from UV stable thermoplastic material and utilizing a gel gasket seal
and easy to open catch mechanism
D. Shuttered Sockets:
1. The Shutters shall effectively screen & isolate the line & neutral socket outlets to
exclude dust & interference & shall only be operable when the interlocked earth
pin in the associated plug top has been inserted.
E. Provide /16A 32A/ 63A, 3P+N+E or 2P+N+E plug with each socket
A. Cooker control units shall incorporate a 45 Amp double pole switch and neon indicator
light.
B. Cooker control unit shall be provided with lower level Cooker Connection unit
C. Both cooker control unit and connection unit shall be flush mounted.
A. 240 V fused spur units shall be switched, shall comply with BS 5733 and shall be fitted
with a fuse complying with BS 1362 with a rating as specified.
C. Live contacts shall not be exposed under normal operating conditions when replacing a
fuse.
E. The type of fused connection unit, particularly relating to the flex outlet, shall be
authorized by the Engineer prior to the ordering of accessories.
B. 13A rated
D. Protection degree: IP 56
A. The Junction Box shall be completed with a terminal block suitable for connecting up to
10 mm2 copper conductor (phase, neutral and earth) and an all insulated moulded white
cover plate with removal covers and shall comply with BS 5733.
A. Provide segregated one/ two/ three/ four compartment flush installed service and
junction boxes cast in floor screed/ concrete.
B. Provide each service box with 13A twin switched socket outlet and telecommunication
outlet as indicated.
C. Provide boxes manufactured from pressure die cast zinc alloy material, single piece
base frame, trap frame and cover. Base plate shall be 2.5mm galvanized steel riveted to
frame.
D. Cover and trap frame shall have epoxy coated or galvanized finish.
E. Provide leveling bolts with locknuts at the base of height adjustment during screed.
F. Covers shall have 6mm recess to accept floor finish and shall have level adjustment
bolts fitted to the box frame. The bolts are to be of hard drawn brass finished with
cadmium plating.
G. Fixing screws: Brass or cadmium plated steel. Self-tapping screws are not permitted.
2.013 TIMER
B. Timers shall be suitable for operation from supply voltage of 240V, 1-phase, and 50Hz
system.
KEO/19-3262-0000 26 2726/6 Wiring Devices
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. Timer output contacts shall be suitable for both a.c. and d.c. control circuits. The
contacts shall be suitable for duty of AC-2 or DC-3 utilization category. The rating of
output contacts shall be coordinated with the application requirements.
D. Timers shall be provided with 2 independent timing scales with sets of change-over
output contacts:
1. 10 200 seconds
2. 0.10 20 seconds
G. Upon supply of rated voltage to the input terminals, the timer shall start, the output relay
remains in rest position. After the set time, the output relay pulls in. The relay resets
after the input supply has been cut-off.
A. Operation of the contactors for switching on the external lights as indicated in the
distribution board schedule shall be by means of photo electric cell.
B. Photo-electric control switch or cell shall operate from a supply voltage of 240V, 50Hz
and turn ON shall occur at 40 lux and turn OFF at 80 lux.
D. Photo - electric switches or cell shall be weatherproof complying with BS 5490, IP 54.
A. General
1. To be metal clad with front operated handles interlocked with switch fuse case to
prevent opening switch in the “ON” position.
2. Switch shall have “ON/OFF” indication and provision for locking in “OFF”
position.
3. Utilisation category AC 23A.
4. The disconnect switches and switch fuses installed in public places shall have
aesthetically pleasing appearance.
C. Disconnect Switches
KEO/19-3262-0000 26 2726/7 Wiring Devices
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Same design as switch-fuses, with solid copper links in place of fuses
2. Single pole and neutral, or triple pole and neutral
3. Ratings, as indicated.
D. Outdoor Equipment
1. Equipment intended for outdoor use shall be certified by the manufacturer as
being weatherproof and suitable for the use outside in the prevailing conditions.
A. The lighting control dimming system shall include various types of lighting control
modules which provide flexible addressable switching and dimming of the various light
sources.
A. The mounting heights of wiring accessories shall be as stipulated in the local power
authority regulations, or as otherwise as indicated on the drawings or approved by the
Engineer.
PART 3 - EXECUTION
A. Location of Boxes:
1. Determine exact location of boxes on site and obtain the Engineer’s approval
before commencing installation
2. Make allowance for overhead pipes, ducts, variations in arrangement, thickness
of finish, window trim, panelling and other construction when locating boxes.
3. Outlet boxes in all food preparation areas shall be recessed such that all wiring
devices shall be mounted flush with walls.
B. Fixing:
1. Fix outlet boxes securely
2. Fix exposed outlet boxes to permanent inserts or lead anchors with machine
screws.
C. Mounting Heights:
1. Mount boxes as indicated or as approved by the Engineer
2. Where mounting height is not shown or specified, obtain instructions
3. Boxes for similar equipment: mount at uniform heights within same or similar
areas.
A. Lighting Switches:
1. Locate at the strike side of the door, approximately 150 mm from the edge of
door frame
B. All sockets, switches, disconnect switches, fused switches, etc. located in food
preparation areas shall be mounted flush to wall.
A. Generally:
1. Fix junction, pull and terminal boxes where indicated and where required to
facilities pulling of wires and cables and connection of future appliances
2. Locate boxes as inconspicuously as possible, but accessible after work is
completed.
B. Pull Boxes:
1. Fix at maximum 10m spacing and to limit the number of bends in conduit to not
more than two 90° bends.
3.04 TESTING
A. Test all switches, socket outlets etc. for correct polarity and continuity of conductors in
the presence of and to the entire satisfaction of the Engineer.
B. Carry out live phase to earth loop impedance tests at all switches and socket outlets
with an approved earth loop impedance tester to the entire satisfaction of the Engineer.
Ensure that all device plates have satisfactory earth continuity to the protective
conductor system.
C. Test all socket outlets for instantaneous tripping of associated distribution board current
operated earth leakage circuit breaker using testing equipment, approved by the
Engineer.
END OF SECTION
FUSES
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.1 SUMMARY
1.3 SUBMITTALS
A. Product Data: Include the following for each fuse type indicated:
1. Dimensions and manufacturer's technical data on features, performance,
electrical characteristics, and ratings.
2. Let-through current curves for fuses with current-limiting characteristics.
3. Time-current curves, coordination charts and tables, and related data.
C. Operation and Maintenance Data: For fuses to include in emergency, operation, and
maintenance manuals.
1. In addition to items specified in Division 01 Section "Operation and Maintenance
Data," include the following:
a. Let-through current curves for fuses with current-limiting characteristics.
b. Time-current curves, coordination charts and tables, and related data.
c. Ambient temperature adjustment information.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
C. For those parts of equipment, where no mention is made of the relevant standard,
reference is made to the latest IEC standards.
D. In a situation where a conflict occurs between these standards, the most stringent shall
be applied.
1.7 COORDINATION
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
1. Fuses: Quantity equal to five percent of each fuse type and size, but no fewer
than two of each type and size.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Characteristics: nonrenewable cartridge fuse; class and current rating indicated; voltage
rating consistent with circuit voltage.
PART 3 - EXECUTION
3.1 EXAMINATION
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Install fuses in fusible devices. Arrange fuses so rating information is readable without
removing fuse.
3.3 IDENTIFICATION
A. Install labels indicating fuse replacement information on inside door of each fused
switch.
3.4 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the following individually mounted, enclosed switches and circuit
breakers:
1. Molded-case circuit breakers.
2. Molded-case switches.
3. Enclosures.
1.3 SUBMITTALS
A. Product Data: For each type of enclosed switch, circuit breaker, accessory, and
component indicated. Include dimensioned elevations, sections, weights, and
manufacturers' technical data on features, performance, electrical characteristics,
ratings, and finishes.
1. Enclosure types and details for types other than IP55.
2. Current and voltage ratings.
3. Short-circuit current rating.
4. UL listing for series rating of installed devices.
5. Features, characteristics, ratings, and factory settings of individual overcurrent
protective devices and auxiliary components.
6. Include time-current coordination curves (average melt) for each type and rating
of overcurrent protective device; include selectable ranges for each type of
overcurrent protective device.
B. Shop Drawings: For enclosed switches and circuit breakers. Include plans, elevations,
sections, details, and attachments to other work.
H. Operation and Maintenance Data: For enclosed switches and circuit breakers to include
in emergency, operation, and maintenance manuals. In addition to items specified in
Division 01 Section "Operation and Maintenance Data," include the following:
1. Manufacturer's written instructions for testing and adjusting enclosed switches
and circuit breakers.
2. Time-current curves, including selectable ranges for each type of circuit breaker.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
C. For those parts of equipment, where no mention is made of the relevant standard,
reference is made to the latest IEC standards.
C. Product Selection for Restricted Space: Drawings indicate maximum dimensions for
enclosed switches and circuit breakers, including clearances between enclosures, and
adjacent surfaces and other items. Comply with indicated maximum dimensions.
1.6 COORDINATION
A. Coordinate layout and installation of switches, circuit breakers, and components with
other construction, including conduit, piping, equipment, and adjacent surfaces.
Maintain required workspace clearances and required clearances for equipment access
doors and panels.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Potential Transformer Fuses: 10% of each type installed.
2. Control-Power Fuses: 10% of each type installed.
3. Fuses and Fusible Devices for Fused Circuit Breakers: 10% of each type
installed.
4. Fuses for Fusible Switches: 10% of each type installed.
5. Fuses for Fused Power Circuit Devices: 10% of each type installed.
6. Spare Indicating Lights: 10% of each type installed.
7. Tools required for maintenance.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Molded-Case Circuit Breaker: Comply with applicable BS, with interrupting capacity to
meet available fault currents.
1. Thermal-Magnetic Circuit Breakers: Inverse time-current element for low-level
overloads and instantaneous magnetic trip element for short circuits. Adjustable
magnetic trip setting for circuit-breaker frame sizes 250 A and larger.
2. Adjustable Instantaneous-Trip Circuit Breakers: Magnetic trip element with front-
mounted, field-adjustable trip setting.
3. Electronic Trip-Unit Circuit Breakers: RMS sensing; field-replaceable rating plug;
with the following field-adjustable settings:
a. Instantaneous trip.
b. Long- and short-time pickup levels.
c. Long- and short-time time adjustments.
d. Ground-fault pickup level, time delay, and I2t response.
4. Current-Limiting Circuit Breakers: Frame sizes 400 A and smaller.
5. Integrally Fused Circuit Breakers: Thermal-magnetic trip element with integral
limiter-style fuse listed for use with circuit breaker and trip activation on fuse
opening or on opening of fuse compartment door.
2.3 ENCLOSURES
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine elements and surfaces to receive enclosed switches and circuit breakers for
compliance with installation tolerances and other conditions affecting performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
A. Coordinate size and location of concrete bases. Verify structural requirements with
structural engineer.
B. Concrete base is specified in Division 26 Section "Hangers and Supports for Electrical
Systems," and concrete materials and installation requirements are specified in
Division 03.
3.3 INSTALLATION
A. Comply with applicable portions of BS for installation of enclosed switches and circuit
breakers.
B. Mount individual wall-mounting switches and circuit breakers with tops at uniform height,
unless otherwise indicated. Anchor floor-mounting switches to concrete base.
D. Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets
and temporary blocking of moving parts from enclosures and components.
3.4 IDENTIFICATION
C. Testing Agency: Engage a qualified testing and inspecting agency to perform the
following field tests and inspections and prepare test reports:
D. Perform the following field tests and inspections and prepare test reports:
1. Test mounting and anchorage devices according to requirements in Division 26
Section "Vibration and Seismic Controls for Electrical Systems."
2. Perform each electrical test and visual and mechanical inspection as per BS /
IEC standards. Certify compliance with test parameters.
3. Correct malfunctioning units on-site, where possible, and retest to demonstrate
compliance; otherwise, replace with new units and retest.
4. Infrared Scanning:
a. Initial Infrared Scanning: After Substantial Completion, but not more than
60 days after Final Acceptance, perform an infrared scan of each
enclosed switch and circuit breaker. Open or remove doors or panels so
connections are accessible to portable scanner.
b. Follow-Up Infrared Scanning: Perform an additional follow-up infrared
scan of each unit 11 months after date of Substantial Completion.
c. Instruments, Equipment and Reports:
1) Use an infrared scanning device designed to measure temperature
or to detect significant deviations from normal values. Provide
calibration record for device.
2) Prepare a certified report that identifies enclosed switches and
circuit breakers included and describes scanning results. Include
notation of deficiencies detected, remedial action taken, and
observations after remedial action.
3.6 TRAINING
3.8 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Architect/ Engineer for approval.
3.10 ADJUSTING
3.11 CLEANING
A. On completion of installation, vacuum dirt and debris from interiors; do not use
compressed air to assist in cleaning.
END OF SECTION
ENCLOSED CONTROLLERS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes ac, enclosed controllers rated 600 V and less, of the following
types:
1. Direct online (DOL) starters
2. Star-delta starters
3. Soft starters
1.3 SUBMITTALS
A. Product Data: For each type of enclosed controller. Include dimensions and
manufacturer's technical data on features, performance, electrical characteristics,
ratings, and finishes.
G. Load-Current and Overload-Relay Heater List: Compile after motors have been
installed and arrange to demonstrate that selection of heaters suits actual motor
nameplate full-load currents.
H. Load-Current and List of Settings of Adjustable Overload Relays: Compile after motors
have been installed and arrange to demonstrate that dip switch settings for motor
running overload protection suit actual motor to be protected.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
C. For those parts of equipment, where no mention is made of the relevant standard,
reference is made to the latest IEC standards.
D. In a situation where a conflict occurs between these standards, the most stringent shall
be applied.
B. Source Limitations: Obtain enclosed controllers of a single type through one source
from a single manufacturer.
E. Product Selection for Restricted Space: Drawings indicate maximum dimensions for
enclosed controllers, minimum clearances between enclosed controllers, and for
adjacent surfaces and other items. Comply with indicated maximum dimensions and
clearances.
A. Store enclosed controllers indoors in clean, dry space with uniform temperature to
prevent condensation. Protect enclosed controllers from exposure to dirt, fumes, water,
corrosive substances, and physical damage.
B. If stored in areas subject to weather, cover enclosed controllers to protect them from
weather, dirt, dust, corrosive substances, and physical damage. Remove loose packing
and flammable materials from inside controllers; install electric heating of sufficient
wattage to prevent condensation.
1.7 COORDINATION
B. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03
Section "Cast-in-Place Concrete."
C. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These
items are specified in Division 07 Section "Roof Accessories."
D. Coordinate features of enclosed controllers and accessory devices with pilot devices
and control circuits to which they connect.
E. Coordinate features, accessories, and functions of each enclosed controller with ratings
and characteristics of supply circuit, motor, required control sequence, and duty cycle of
motor and load.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
KEO/19-3262-0000 26 2913/3 Enclosed Controllers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. Spare parts required shall include but not necessarily be limited to,
1. Spare Fuses: Furnish one spare for every five installed, but no fewer than one
set of three of each type and rating.
2. Indicating Lights: Two of each type installed.
3. Tools required for maintenance.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
2.2 GENERAL
A. Enclosed controllers shall be of the same manufacturer as the low voltage panel,
switchboard, motor control center and distribution boards.
A. All Motor starters shall comply with IEC 60947-4. The components of the starter shall be
type tested and ASTA certified to achieve Type 2 co-ordination in accordance with IEC
60947-4.
B. The Manufacturer shall supply certified test results to confirm that the starter has been
tested to substantiate designs according to applicable standards. The tests shall verify
not only the performance of the unit and integrated assembly, but also the suitability of
the enclosure venting, rigidity and bus bracing. In addition, the unit shall be factory
tested in accordance with applicable standards.
C. The Manufacturer shall be prepared to show proper evidence of having tested for noise
immunity on both input and output power connections
E. Motor starters shall be rated to carry the full load current of its rated duty at its most
severe load conditions. All starters shall be capable of at least 20 starts per hour at
100% full load torque.
1. Motor starters shall be housed in a separate cubicle compartment of the relevant
motor control center and each starter cubicle shall contain the following
components, or as otherwise indicated on the Project Drawings or Project
Documentation.
2. 1 No. triple pole MCCB/ MPCB or fuse switch, as indicated on the Project
Drawings, externally operated and interlocked with the cubicle door. There shall
be provision for padlocking in the OFF position.
3. 1 No. motor protection relay.
4. 1 No. set of auxiliary relays and timers required to provide the necessary
indication and control sequence. Timers shall be totally enclosed dust proof.
5. 1 No. set of main motor terminals and auxiliary terminals for remote controls
and indications.
6. 1 No. set of terminals for remote lock-off and emergency stop push buttons.
7. 1 No. control circuit transformer, where applicable.
8. 1 No. anti-condensation heater, if specified.
9. 1 No. set of power factor correction capacitors with separate fuses for all drives
above 11 kW, to give a power factor of not less than 0.95, if specified.
10. 1 No. Thermistor relays where applicable.
11. Shall contain a totally enclosed dust proof timer.
F. The following equipment shall be mounted on the door of the starter cubicle, or as
otherwise indicated in the Drawings.
1. 1 No. ammeter with selector switch and current transformer fitted with
suppressed scale to read motor running and starting current with red pointer to
indicate full load current for each motor rated 25HP and above.
2. 2 No. pilot lamps to indicate “SUPPLY ON” (Green) and “MOTOR RUNNING”
(Red).
3. 1 No. pilot lamp to indicate “MOTOR FAILED” (Amber).
4. 1 No Pilot lamps (a separate lamp for each motor fault conditions).
5. 1 No. “Hand/OFF/AUTO” Selector switch
6. 1 set “Start/Stop” push button
7. 1 No. externally operated overload reset push button
8. 1 Lamp test push button
A. DOL starters shall consist of a TP/SP contactor for switching direct on line in
accordance with IEC 60947-4-1 and fitted with auxiliary contacts.
A. Star-delta starters shall be provided with contactors as for DOL starters, arranged in
such a manner to ensure the star contactor opens before the delta contactor closes.
C. For closed transition type star-delta starters, further requirements shall be wire wound
porcelain core resistor banks of sufficient thermal rating to allow three (3) consecutive
starts of 30 seconds starting period followed by a 15 minutes rest and another 30
seconds starting period. Resistance value shall be chosen to give high starting current
with low transient current. A thermal cut out shall be provided for transient resistor
banks. Starter cubicles incorporating resistor banks shall be well ventilated with vermin
proof and dust ventilation louvers.
B. DESIGN SPECIFICATION;
1. The solid-state reduced-voltage starter shall be UL and CSA listed. The solid-
state reduced-voltage starter shall be an integrated unit with power SCRs, logic
board, paralleling bypass contactor, and electronic overload relay enclosed in a
single molded housing.
2. The SCR-based power section shall consist of six (6) back-to-back SCRs and
shall be rated for a minimum peak inverse voltage rating of 1500 volts PIV.
3. Units using triacs or SCR/diode combinations shall not be acceptable.
4. Resistor/capacitor snubber networks shall be used to prevent false firing of SCRs
due to dV/dT effects.
5. The logic board shall be mounted for ease of testing, service and replacement. It
shall have quick disconnect plug-in connectors for current transformer inputs, line
and load voltage inputs and SCR gate firing output circuits.
6. The logic board shall be identical for all ampere ratings and voltage classes and
shall be conformally coated to protect environmental concerns.
7. The paralleling run bypass contactor shall energize when the motor reaches 90
of full speed and close/open under one (1) times motor current.
8. The paralleling run bypass contactor shall utilize an intelligent coil controller to
limit contact bounce and optimize coil voltage during varying system conditions.
9. Starter shall be provided with electronic overload protection as standard and
shall be based on inverse time-current algorithm. Overload protection shall be
capable of being disabled during ramp start for long acceleration loads via a DIP
switch setting on the device keypad.
10. Overload protection shall be adjusted via the device keypad and shall have a
motor full load ampere adjustment from 30 to 100% of the maximum continuous
ampere rating of the starter.
KEO/19-3262-0000 26 2913/6 Enclosed Controllers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
11. Starter shall have selectable overload class setting of 5, 10, 20 or 30 via a DIP
switch setting on the device keypad.
12. Starter shall be capable of either an electronic or mechanical reset after a fault.
13. Units using bimetal overload relays are not acceptable.
14. Over temperature protection (on heat sink) shall be standard.
15. Starters shall provide protection against improper line-side phase rotation as
standard. Starter will shut down if a line-side phase rotation other than A-B-C
exists. This feature can be disabled via a DIP switch on the device keypad.
16. Starters shall provide protection against a phase loss or unbalance condition as
standard. Starter will shut down if a 50% current differential between any two
phases is encountered. This feature can be disabled via a DIP switch on the
device keypad.
17. Start shall provide protection against a motor stall condition as standard. This
feature can be disabled via a DIP switch on the device keypad.
18. Starter shall provide protection against a motor jam condition as standard. This
feature can be disabled via a DIP switch on the device keypad.
19. Starter shall be provided with a Form C normally open (NO), normally closed
(NC) contact that shall change state when a fault condition exists. Contacts shall
be rated 60 VA (resistive load) and 20 VA (inductive load). In addition, an LED
display on the device keypad shall indicate type of fault (Overtemperature, Phase
Loss, Jam, Stall, Phase Reversal and Overload).
20. The following control function adjustments on the device keypad are required:
a. Selectable Torque Ramp Start or Current Limit Start
b. Adjustable Kick Start Time: 0–2 seconds
c. Adjustable Kick Start Torque: 0–85%
d. Adjustable Ramp Start Time: 0.5–180 seconds
e. Adjustable Initial Starting Ramp Torque: 0–85%
f. Adjustable Smooth Stop Ramp Time: 0–60 seconds.
21. Units enclosed in motor control centers shall be of the same manufacturer as that
of the circuit breaker and motor control center for coordination and design issues.
22. Maximum continuous operation shall be at 115% of continuous ampere rating.
23. Pump Control Option – Provide control algorithm for pump start-up and shut
down sequences. Control algorithm shall reduce the potential for water hammer
in a centrifugal pump system. Upon a start command, the speed of the motor is
increased, under the control of the IT. Soft Starter microprocessor, to achieve a
gentle start. After the speed has reached its nominal value, the bypass
contactors close and the pump. Upon a stop command, the bypass contactors
are opened and the motor speed is decreased in a tapered manner, to gradually
slow the flow until the motor is brought to a stop. The start and stop ramp times
are user adjustable and are to be set for the application requirements. The pump
control option shall be factory installed.
2.7 ENCLOSURES
A. Local starter panels for equipment will be freestanding or wall mounting type unless
otherwise indicated to comply with environmental conditions at installed location
1. Indoor Locations: IP 52.
2. Outdoor Locations: IP 65.
3. Kitchen Areas: IP54, stainless steel.
4. Other Wet or Damp Indoor Locations: IP54.
2.8 ACCESSORIES
KEO/19-3262-0000 26 2913/7 Enclosed Controllers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
A. Devices shall be factory installed in controller enclosure, unless otherwise indicated.
F. Meters: Panel type, 64-mm minimum size with 90- or 120-degree scale and plus or
minus 2 percent accuracy. Where indicated, provide transfer device with an off position.
Meters shall indicate the following:
1. Ammeter: Output current, with current sensors rated to suit application.
2. Voltmeter: Output voltage.
3. Frequency Meter: Output frequency.
H. Phase-Failure and under voltage relays: Solid-state sensing circuit with isolated output
contacts for hard-wired connection. Provide adjustable under voltage setting.
PART 3 - EXECUTION
A. Examine areas and surfaces to receive enclosed controllers for compliance with
requirements, installation tolerances, and other conditions affecting performance.
1. Proceed with installation only after unsatisfactory conditions have been
corrected.
3.2 APPLICATIONS
A. Select features of each enclosed controller to coordinate with ratings and characteristics
of supply circuit and motor; required control sequence; duty cycle of motor, controller,
and load; and configuration of pilot device and control circuit affecting controller
functions.
3.3 INSTALLATION
A. For control equipment at walls, bolt units to wall or mount on lightweight structural-steel
channels bolted to wall. For controllers not at walls, provide freestanding racks
complying with Division 26 Section "Hangers and Supports for Electrical Systems."
D. Enclosed Controller Fuses: Install fuses in each fusible switch. Comply with
requirements in Division 26 Section "Fuses."
A. Coordinate size and location of concrete bases. Verify structural requirements with
structural engineer.
B. Concrete base is specified in Division 26 Section "Hangers and Supports for Electrical
Systems," and concrete materials and installation requirements are specified in
Division 03.
3.5 IDENTIFICATION
3.7 CONNECTIONS
C. Perform the following field tests and inspections and prepare test reports:
1. Perform each electrical test and visual and mechanical inspection, except
optional tests, Motor Control - Motor Starters. Certify compliance with test
parameters.
2. Correct malfunctioning units on-site, where possible, and retest to demonstrate
compliance; otherwise, replace with new units and retest.
3.9 ADJUSTING
3.10 TRAINING
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Architect/ Engineers review outlining all
deficiencies and course of action. The contractor shall ensure all deficiencies outlined
are rectified, retested, and certified.
3.12 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Architect/ Engineer for approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This section describes the type of frequency converter shall be supplied for fan and
pump speed control. The frequency converter shall not be a general purpose product,
but a dedicated HVAC engineered design.
1.03 DEFINITIONS
A. Definitions include:
1. BAS: Building automation system.
2. IGBT: Integrated gate bipolar transistor.
3. LAN: Local area network.
4. PID: Control action, proportional plus integral plus derivative.
5. PWM: Pulse-width modulated.
6. VFD: Variable frequency drive
1.04 SUBMITTALS
A. Product Data: For each type of VFD. Include dimensions, mounting arrangements,
location for conduit entries, shipping and operating weights, and manufacturer's
technical data on features, performance, electrical ratings, characteristics, and finishes.
E. Operation and Maintenance Data: For VFDs, all installed devices, and components to
include in emergency, operation, and maintenance manuals. In addition to items
specified in Division 01 Section "Operation and Maintenance Data," include the
following:
1. Routine maintenance requirements for VFDs and all installed components.
2. Manufacturer's written instructions for testing and adjusting overcurrent
protective devices.
3. Addressing sequence of operations, Input/output hardwire and data
communications connections to BAS, Fire Alarm System, remote field devises
and the VFD configuration that are loaded by keypad or PC.
F. Load-Current and Overload-Relay Heater List: Compile after motors have been
installed and arrange to demonstrate that selection of heaters suits actual motor
nameplate full-load currents.
G. Load-Current and List of Settings of Adjustable Overload Relays: Compile after motors
have been installed and arrange to demonstrate that dip switch settings for motor
running overload protection suit actual motor to be protected.
H. Harmonic analysis studies shall be performed for all large motor loads (over 37.3kW) or
large quantities of smaller motor loads to verify compliance, or where VFD\s are added
to existing services with high harmonic content. The building primary services entrance
shall be considered the Point of Common Coupling (PCC) for establishing current
harmonic limits. Total harmonic voltage distortion (THD) shall not exceed 5% at any
point in the building distribution system, except in separately derived systems dedicated
to the harmonic producing equipment.
A. Manufacturer Qualifications:
1. The manufacturer shall demonstrate a continuous period of manufacture and
development for at least 20 years.
2. The frequency converter shall be supported locally by the manufacturer who will
provide full technical support, spares holding and troubleshooting capability from
their own local facility. A training course shall be provided by the manufacturer to
the consultant / contractor / maintenance engineers.
3. Equipment supplied must conform to recognized International Standards and be
manufactured to ISO 9001 quality standards and carry the CE and C-tick mark
on EMC Compliance.
B. Frequency converters shall be suitable for use in either a ‘Stand Alone’ mode complete
with all necessary protection or as part of a centrally controlled system via a serial
C. Tests Functionality: Every AC Drive has to be tested functionally. The inverter part of the
AC Drive or each inverter module at least has to be tested by running it with a motor at
full nominal load. A test report of the tests made shall be delivered by the Frequency
Converter Manufacturer on engineer’s request.
D. Source Limitations: Obtain VFDs of a single type through one source from a single
manufacturer.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
A. Deliver VFDs in shipping splits of lengths that can be moved past obstructions in
delivery path.
B. Store VFDs indoors in clean, dry space with uniform temperature to prevent
condensation. Protect VFDs from exposure to dirt, fumes, water, corrosive substances,
and physical damage.
C. If stored in areas subject to weather, cover VFDs to protect them from weather, dirt,
dust, corrosive substances, and physical damage. Remove loose packing and
flammable materials from inside controllers; install electric heating of sufficient wattage
to prevent condensation.
B. Spare parts required shall include but not necessarily be limited to,
1. Specify one full set of spare fuses in each driver
2. Spare parts recommended by manufacturer.
3. Tools required for maintenance.
B. Product Selection for Restricted Space: Drawings indicate maximum dimensions for
VFDs, including clearances between VFDs, and adjacent surfaces and other items.
Comply with indicated maximum dimensions.
1.011 COORDINATION
A. Coordinate layout and installation of VFDs with other construction including conduit,
piping, equipment, and adjacent surfaces. Maintain required workspace clearances and
required clearances for equipment access doors and panels.
B. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
C. Coordinate features of VFDs, installed units, and accessory devices with pilot devices
and control circuits to which they connect.
D. Coordinate features, accessories, and functions of each VFD and each installed unit
with ratings and characteristics of supply circuit, motor, required control sequence, and
duty cycle of motor and load.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
KEO/19-3262-0000 26 2923/4 Variable Frequency Motor Controllers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
A. The frequency converter (VFD) shall be rated for 3 phase, 400V +/-10%, 50/60 Hz
mains supply. At full speed, full load the VFD shall be able to deliver full rated motor
voltage (400 V) and therefore full rated motor output torque over the +/- 10% mains
voltage range.
B. The VFD shall continue to deliver full motor output torque even if the supply is at 400 V -
10% continuously.
C. The voltage to frequency ratio shall be suitable for centrifugal pump and fan control to
optimize energy usage.
E. The use of high efficiency motors with the VFD shall be considered as an acceptable
alternative to this function.
F. The VFD shall be rated for connection to any point in the supply network with a
prospective short circuit current of up to 100kA.
G. If additional components are required to meet this rating, these should be housed inside
the VFDs enclosure.
H. The VFD shall work in conjunction with any IEC standard design motor (IEC 60034-17)
and shall not require dv/dt or sinus filters for cable lengths of less than 50 metres, shall
not require the motors to be derated, or cause the motor temperature to rise above the
Class B rise expected on normal mains operation.
I. If the VFD cannot maintain Class B temperature rise even when running at low speeds
(<10Hz), then the motor shall be oversized and derated or an external blower for cooling
the motor shall be required.
J. If the VFD requires motor’s compliance with IEC 60034-25 (inverter duty rated motors),
this need to be clearly stated in the manufacturer’s data sheets and offers.
K. The VFD shall limit motor terminal pulse voltage (peak voltage and rise time) to below
that defined in IEC 60034-17 with a minimum 30m motor cable. If the motor terminal
KEO/19-3262-0000 26 2923/5 Variable Frequency Motor Controllers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
peak voltages are above these limits, the VFD shall include an output filter (dv/dt filter or
sinus filter) or inverter duty rated motors shall be required.
L. The VFD shall incorporate an Automatic Motor Adaptation (AMA) function for the
induction motors (IM) as well as permanenet magner motors (PMM). The AMA function
shall ensure tuning of the VFD to the motor in order to optimize motor performance,
improve start capabilities and compensate for motor cable variances. This function shall
be carried out with the IM / PMM at standstill (i.e. without spinning the motor) and
without the need to decouple the motor from the driven load.
M. The VFD shall be capable of controlling parallel motors (IM as well as PMM) of mixed
ratings, and allow disconnection of any motor whilst running without causing tripping.
The VFD shall be capable of running with no motor connected for service functions.
N. The VFD shall be fully tested at the frequency converter manufacturers works, including
motor loading. Certificates of Compliance should be available on request.
O. The VFD shall be of sufficient capacity to provide a quality wave form so as to achieve
full output torque of the motor, without causing additional heat rise under the following
operating conditions:
1. Rated input voltage 400 V +/- 10%, 3 phase, 48-62Hz +/- 1%.
2. Output voltage range 0 to full mains input voltage, 3 phase even at full mains
voltage -10% input.
3. Minimum efficiency at 100% load= 97% at 20% load = 92%
4. Working ambient temperature range -10C to +45C full load with no derating,
humidity to 95% RH, and vibration of 0.7G RMS in 3 directions.
5. Switching frequency within 2 kHz to 14kHz
6. The VFD shall have a manually adjustable carrier frequency that can be
adjusted in 0.5khz increments to allow the user to select the desired
opereating characteristics. It shall also able to perform automatically reduce
its carrier frequency to avoid tripping due to thermal overload.
P. The VFD shall allow connection of motors one frame size larger and 4 sizes smaller
than the nominal converter rating.
R. The VFD shall accept 0-10 VDC and 0/4-20 mA inputs as a control signal.
S. The VFD shall provide two output relays, 2A , 230V to provide status signals including -
ready, run and tripped and be programmable for other selected information.
T. The VFD shall provide two analogue outputs of 0/4-20 mA, programmable to transmit
motor current, motor power, sensor feedback, speed or other variables to the BAS.
These shall alternatively be programmable as two digital outputs providing 24Vdc to
signal a choice of 27 status conditions to the BAS.
U. The VFD shall log and display total kWh consumed and total hours run by the motor
without additional instrumentation with the facility to reset these counters. The
inaccuracy of kWh meter shall not exceed 7% and the manufacturer must provide a
certificate from a credible international organization such as NABERS, TUV etc.
confirming the inaccuracy of the kWh meter to be within 7%
V. 20 preset speeds shall be available (programmable values) for duties such as night
setback, smoke extract and morning boost settings.
KEO/19-3262-0000 26 2923/6 Variable Frequency Motor Controllers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
W. The VFD shall provide 4 skip frequencies of adjustable bandwidth to overcome
mechanical or air resonance.
Y. VFD acoustic noise shall not exceed 75dBA at full load and 60dBA at 50% load.
Z. VFD shall meet ISO 13373 standard for Condition Monitoring and
AA. Diagnostics of Machines offer Predictive Maintenance such as motor status winding
monitoring before failure and vibration monitoring.
BB. The VFD shall design heat sink cooling fan for 10 years without the need for
replacement every 3 to 5 years
A. Harmonics:
1. The VFD shall comply IEC 61000-3-12 and be fitted with a harmonic filter
(D.C. link or equivalent) on both inductive and capacitive elements to control
the main borne harmonics. The filter shall be mounted within the same
enclosure of the VFD. Any externally fitted harmonic filter or harmonic filter
that causes voltage drop shall be rejected.
B. EMC:
1. The VFD shall be CE marked in accordance with European Union (EU)
legislation and C-Tick marked in accordance with Australian Communications
Authority (ACA) regulations.
2. The VFD shall include a radio frequency suppression filter, within its
enclosure, to ensure compliance with both the following:
a. The VFD shall comply with the emission and immunity requirements of
IEC61800.3 2nd Edition 2004 for Category C1 (EN55011 Class B) products
with 50m screened motor cable up to 90kw.
b. The VFD shall comply with the emission and immunity requirements of
IEC61800.3 2nd Edition 2004 for Category C2 (EN55011 Class A1)
products with 150m screened motor cable from 110kw to 450kw and
above.
c. The VFD shall comply with the emission and immunity requirements of
IEC61800.3 2nd Edition 2004 for distance longer than 150m and above
with unshielded cables of unlimited length with standard EN55011, Group
1, Class B when using vsd in combination with special filter to meet the
higher requirement for longer distance.
d. VFD shall comply with 20V/m immunity according to EN (IEC)
e. 61000-4-3: 2006+A1+A2 from 80-1000Mhz.
D. The VFD design shall comprise a diode input bridge, fixed voltage DC link section with
both inductors and capacitors to form a filter, and inverting bridge comprising IGBTs
(Insulated Gate Bipolar Transistors). All equipment must be housed within the VFD
enclosure.
G. The VFD shall use overriding frequency fold back control techniques to prevent damage
in the event of excessive load during either running or starting.
H. The VFD shall model the motor in its software to predict motor overheating without the
use of thermistors in the motor. When overheat is predicted, an alarm or warning shall
be initiated.
I. For motors fitted with thermistors, the VFD shall include a thermistor input as standard
to provide motor thermal protection without the need for external thermistor interface
relays.
J. The VFD shall exhibit near unity displacement fundamental power factor at all loads and
speeds, and should not require the addition of external AC/DC line reactors for power
factor improvement, harmonic control or prevention of zero voltage notching.
K. The output circuit shall be of such a design as to allow unlimited switching of the motor
circuit, at any load/speed without causing damage to the VFD. Otherwise an auxiliary
early break, late make contact must be supplied to the output disconnect switch and the
control wiring routed back to a safety circuit via conduit or cable tray.
L. VFDs shall have self adjusting modulation frequency control. The control form shall be
such as to allow the VFD to deliver full output at all times without derating, by optimizing
the switching frequency dependent on the output load.
M. Full galvanic isolation between power and control components shall be incorporated to
ensure compliance with VDE 0160 PELV (Protective Extra Low Voltage) to prevent
damage to BAS interface and ensure operator safety. Short circuiting of the control
terminals shall not damage the control card
O. The VFD shall include a Smart Logic Controller within its enclosure that offers a wide
range of PLC functions that include logic operators, comparators and timer functions.
P. The VFD shall have an automatic “sleep” mode function timer complete with boost
function, operating when loads are below minimum settings.
R. In order to support AHU diagnostics, the VFD shall have AHU Air Flow measurements
capability by connecting a pair of hoses across the fan, measuring pressure developed
by the fan, utilizing the “k” value of the fan and air density. The VFD shall not require
any external flow measurement device or any external pressure transmitters for this
measurement.
S. The design shall include a full 3-zone, 3 setpoint PID controller as standard to provide
closed loop control direct from up to 3 signal transmitters without the need for external
signal conditioning. The PID controller shall permit the VFD to control the motor speed
based on the following feedback selections: highest/lowest, average, sum, difference, 3-
zone min, 3-zone max. VFDs without a 3-zone controller must add this capability to
their package.
T. The VFD shall not exhibit an inrush current when a ‘start’ signal is given, and current
must not exceed 110% at any time to prevent damage to connected equipment.
U. The VFD design shall include a motor preheat circuit to prevent condensation forming in
the motor during shutdown periods.
V. The VFD shall not be damaged if it is energized with a ‘start’ signal without a motor
connected.
X. VFD shall not include any buttons on the keypad allowing the motor direction to be
reversed.
Y. VFD shall incorporate a fault diagnostic memory storing the last 10 trips displayed in
alpha-numeric format. The data immediately preceeding the last fault shall also be
stored to assist fault finding.
AA. The design technology and operator keypad shall be common through the whole series
of VFD offered. The VFD shall be factory pre-commissioned for building services use
and require minimal site setting.
BB. Real Time Clock (RTC). For applications without a BAS the VFD shall provide a RTC
option with the following functionality:
1. Ability to display current time and date on VFD display.
2. Capable of initiating functions including start/stop, change of speed and
change of setpoint (e.g. for night setback).
3. Capable of controlling VFD relay outputs for control of remote devices.
4. Provide up to 20 programmable events.
5. Ability to enable/disable the RTC by external control signal for disabling during
shut down periods (e.g. holidays).
6. The RTC option shall be installed inside the VFD to ensure it cannot
easily/accidentally be removed by operating or maintenance personnel
thereby ensuring once commissioned the VFD continues to operate according
to the RTC settings.
7. Maintain its setting with power removed from the VFD for up to 100 hours
allowing maintenance to be carried out without resetting the time.
8. When fitted with the RTC, the VFD shall date/time stamp the last 10 faults in
the fault log.
CC. Fire safety function. The VFD shall have a digital input which can be used in the event
of a fire signal from the fire system. Depending on the application and system design
the function of this input should force the VFD into one of the following operating states:
1. Stop the VFD
KEO/19-3262-0000 26 2923/10 Variable Frequency Motor Controllers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Start and run the VFD at a fixed (programmable) speed in the forward
direction.
3. Start and run the VFD at a fixed (programmable) speed in the reverse
direction (e.g. smoke extract)
4. Start and run the VFD at a fixed (programmable) speed in the forward
direction and if the VFD trips, automatically activate a relay output which can
be used to control a by-pass starter
DD. When operating in states b) or c) the VFD should continue to operate overriding all its
warnings and alarms, normal application parameter settings and motor protection
features in order to secure continued operation until such time that the fire command is
manually overridden or that a fire has rendered the VFD inoperable. In the event of
serious fault conditions, such as earth fault or short circuit fault on the VFD output, the
VFD should trip but then continuously attempt to automatically reset and restart, even if
that results in running to destruction.
EE. The VFD shall have proven serial communication protocol capabilities with BAS
systems to include Johnson Controls Metasys N2, Siemens FLN, Andover X-driver,
Modbus RTU, Lonworks and BACnet over IP. The VFD manufacturer shall be
responsible for technical support to the BAS vendor in the implementation of serial
communication interface to the BAS System. The BAS vendor shall be responsible for
the complete “integration and interoperability” of the VFD through the BAS via the serial
interface.
FF. When integrated into the BAS serial communication network the VFD’s hardware I/O
points shall be made available as remote I/O for the BAS. The VFD shall provide at
least the following status/control I/O points:
1. 6 x digital inputs
2. 2 x digital outputs (provided by relays with changeover volt free contacts
(rated for 240V AC) and on/off delay timers)
3. 2 x analogue inputs (each selectable for voltage or current signals, direct or
reverse acting, with the minimum and maximum range independently
scaleable from 0-10V DC and 0-20mA)
4. 1 x analogue output (0/4-20mA)
GG. The VFD shall have the facility to expand its I/O capability through the addition of option
modules. These should be available as factory mounted modules, with the complete
VSD including the modules tested at the manufacturer’s works and also available as
simple field mounted options using rigid connectors to plug into the VSD. The following
I/O points should be provided by these option modules:
1. Additional digital inputs
2. Additional digital outputs including additional relay outputs
3. Additional analogue inputs
4. Additional analogue outputs (0/4-20mA and 0-10V DC)
5. Pt1000/Ni1000 temperature sensor inputs
HH. It shall be possible to read the status of all digital and analogue inputs (including those
on I/O expansion modules) via the high level interface making them available as remote
inputs for the BAS.
II. It shall be possible to control all digital and analogue outputs (including those on the I/O
expansion modules) via the high level interface making them available as remote
outputs for control by the BAS. When controlled by the BAS in the event of the high
level interface network failing the digital/analogue outputs shall override to a
programmable default condition/value.
KEO/19-3262-0000 26 2923/11 Variable Frequency Motor Controllers
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
JJ. Voltage dip Ride Through. The VFD shall comply to voltage dip ride through
requirement and perform in accordance to the characteristic and meet the demands
stated in Semi F47 without the need of disabling any protective feature of the VFD.
KK. The VFD shall design the capacitor for 10 years life span without need to replace any
capacitor every 3 to 5 years.
A. The VFD shall be contained in a single enclosure having minimum ingress protection of
IP55 level for the VFD sizes up 90kW and IP54 level for the VFD sizes above 90kW.
The VFD shall incorporate all accessories necessary to meet the specification without
having to use a secondary enclosure. Any local / non-proprietary made enclosures will
be strictly unacceptable.
B. The VFD shall include load dependent in-built cooling fans. This increases life
expectancy of the in-built cooling fans. VFDs without this functionality shall include as a
part of their offer, extra costs for the heat sink cooling fans replacement every 3 years.
E. The design of the VFD shall allow up to at least 100 meters of SWA (Single Wire
Armour) cable to be used between the VFD and the motor and allow the use of Fire
rated cable in the motor circuit for fire locations.
2.05 ACCESSORIES
E. Standard Displays:
1. Output frequency (Hz).
2. Set-point frequency (Hz).
3. Motor current (amperes).
4. DC-link voltage (VDC).
5. Motor torque (percent).
6. Motor speed (rpm).
7. Motor output voltage (V).
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine areas, surfaces, and substrates to receive VFDs for compliance with
requirements and other conditions affecting performance.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 APPLICATIONS
A. Select features of each VFD to coordinate with ratings and characteristics of supply
circuit and motor; required control sequence; and duty cycle of motor, controller, and
load.
B. In application where the driver will be more than 33 cable meters from the motor
coordinate with the motor manufacturer to ensure that the motor is suitable for the
application or to provide a motor protecting dV/dT filter on the driver output to protect the
motor
D. Electrical Service: feed the drive directly from the main building switchboard or from a
feeder that is dedicated to mechanical loads. Isolation transformers or line reactors
maybe considered on installations where Total Harmonic Distortion (THD) limits cannot
be achieved as described above.
3.03 INSTALLATION
A. Anchor each VFD assembly to steel-channel sills arranged and sized according to
manufacturer's written instructions. Attach by bolting. Level and grout sills flush with
mounting surface.
B. Concrete base is specified in Division 26 Section "Common Work Results for Electrical,"
and concrete materials and installation requirements are specified in Division 03.
3.05 IDENTIFICATION
B. Operating Instructions: Frame printed operating instructions for VFDs, including control
sequences and emergency procedures. Fabricate frame of finished metal, and cover
instructions with clear acrylic plastic. Mount on front of VFD units.
A. Install wiring between VFDs and remote devices according to Division 26 Section "Low-
Voltage Electrical Power Conductors and Cables."
3.07 CONNECTIONS
3.09 ADJUSTING
B. Ensure that the VFD programming and motor protective devices are properly calibrated
and set.
3.10 DEMONSTRATION
3.11 TRAINING
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Engineers review outlining all deficiencies and
course of action. The contractor shall ensure all deficiencies outlined are rectified,
retested, and certified.
3.13 MAINTENANCE
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Scope of Work: The contractor shall be responsible for providing a complete and
operable Photovoltaic (PV) System On-Grid connection type that meets applicable
MEW (Ministry of Electricity and Water & Renewable energy) guidelines/regulations.
The contractor will be required to design the photovoltaic system, select the most
appropriate photovoltaic equipment, and install the photovoltaic system. The
contractor shall provide qualified and experienced staff for all aspects of the Project,
and such staff shall be specifically qualified and experienced in the engineering,
design, and installation of photovoltaic systems. The contractor shall be Qualified and
registered in MEW CCI and/or CCII EPC List. Preference shall be given to MEW
approved EPC firms with previous PAHW approvals.
B. Related Sections:
1. Section 26 0500 - Common Requirements For Electrical Installations
2. Section 26 0526 - Earthing And Bonding For Electrical Systems
3. Section 26 0553 - Identification For Electrical Systems
4. Section 26 0519 - Low Voltage Electrical Cables
5. Section 26 0533 - Raceway And Boxes For Electrical Systems
6. Section 26 0536 - Cable Trays And Ladder For Electrical System
7. Section 26 2726 - Wiring Devices
8. Section 26 2413 - Switchboards
A. All work, materials, and equipment shall comply with the rules and regulations of all
codes and ordinances of the local, state, and federal authorities having jurisdiction.
Such codes, when more restrictive, shall take precedence over these plans and
specifications. The specifications and standards listed below form part of this
specification. The system shall fully comply with the latest issue of these standards, if
applicable.
1. Latest MEW Solar PV Connection Guidelines
2. MEW - R1 "Regulations for Electrical Installations"
3. National Electrical Code - NFPA 70 (2017) - Article 690 - Solar Photovoltaic
4. National Electrical Safety Code - ANSI/IEEEC2-2002
5. OSHA
6. Outdoor enclosures shall be NEMA 3 (minimum) or equivalent.
7. ANSI/IEEE 519 1992 Guide for harmonic control and reactive compensation of
static power controllers
8. IEEE 1262 Recommended Practice for Qualifications of Photovoltaic Modules
9. IEEE 928-1986 Recommended Criteria for Terrestrial Photovoltaic Power
Systems
KEO/19-3262-0000 26 3100/1 Solar Photovoltaic System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
10. IEC 61215 ed.2
11. IEC 61730
12. IEC 61727
13. IEC 61829
14. IEC 61701
15. IEC 61721
16. Electrical Protection Class II and ICE-guidelines.
17. ISO 9001 and ISO14001
18. UL 1741-2001 for Inverters and Charge Controllers
19. UL 1703 for Photovoltaic Modules
20. FCC Regulations Electromagnetic Interference
1.04 SUBMITTALS
A. The contractor shall submit drawings and specifications for approval before
commencement of works. Submittals should be in strict accordance with contract
requirements and as follows:
B. Product Data: contractor shall include data on features, components, ratings and
performance, which shall include but not be limited to a dimensioned outline plan and
elevation drawings of photovoltaic arrays and other specified components; the
physical and electrical characteristics of the individual solar panels, including
manufacturer name and model number; and the time-current characteristic curves for
protective devices.
D. Field Test and Observation Reports: contractor shall indicate and interpret test results
and inspection records relative to compliance with performance requirements.
A. This Section includes the photovoltaic equipment, including but not limited to the
following equipment and accessories:
1. Solar PV Modules
2. Solar Power Inverters
3. Mounting Systems and necessary hardware
4. Solar Cables and accessories
5. DC Junction boxes, combiner boxes (if any)
6. AC Combiners / DBs: Refer to relevant section(s) under Division 26
7. Protections and Disconnection devices: Refer to relevant section(s) under
Division 26
8. AC Cables: Refer to relevant section(s) under Division 26
9. Grounding System: Refer to relevant section(s) under Division 26
10. Electrical Containments: Refer to relevant section(s) under Division 26
11. Plant monitoring, graphical display system and off-site data transmission
system as required by the Project Owner.
12. Solar PV metering and protection panels for connection with building grid as
per MEW requirements (including metering, protection provisions). Refer to
Section 26 2413 - Switchboards
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
PART 2 - PRODUCTS
C. A number of solar modules shall be connected in series and parallel to form a solar
array to give the required parameters.
1. Solar PV module conversion efficiency should be greater than 20% for
crystalline with solder free cells.
2. Each solar module shall be from latest production in the latest 2 years max. of
Contract award and have special manufacturer's warranties as indicated herein
under clause 3.03.
E. The module shall have a back film to increase weather resistance and to aid light
absorption.
H. For Framed Solar PV modules; the module own frame shall be supplied with holes or
slides for mechanical attachments/grounding and be made of anodized aluminum
alloy.
I. Electrical connection shall be made on a sturdy terminal bloc with min. IP67 junction
box in which at least three (3) by-pass diodes shall be incorporated to prevent hot
spots.
J. For Crystalline Modules: High-performance modules with crystalline, Four (4) bus-bar
cell technology minimum.
K. The electrical characteristics of the solar modules shall be stated with the solar
parameters and be listed on a non-removable sticker on the back side of the solar
module.
N. Site and panel temperatures shall be taken into account for the performance of the
solar modules.
P. The PV panels/modules shall meet or exceed the quality assurance and testing
requirements as applicable to standards listed under clause 1.02. The manufacturer
should be certified and registered to ISO 9001 and ISO 14001.
R. Power Tolerance of each module shall be within +3% of the rated power at Standard
Test Conditions which is Irradiance = 1000w/m2 cell temperature = 25 °C. Only +ve
tolerance modules shall be accepted.
S. Open Circuit Voltage (Voc) shall be within 10% of data sheet at Standard Test
Conditions. i) Module Power shall not be diminished more than 0.5% per degree C
above25-degreeC under full sun conditions.
B. Quality Assurance
1. The system needs to be durable with special manufacturer's warranties as
indicated elsewhere in this section or other contract documents. The products
shall be long-lasting and highly resistant to corrosion forms inhibited by local
site conditions with a service life of 25 years or greater.
2. The mounting structure should be aesthetically acceptable.
3. Quality assurance & Environmental / HSE management shall be carried out by
the Manufacturer pursuant to DIN EN ISO 9001, ISO 14001 and OHSAS 18001
or other equivalent International Standards.
4. Solar Mounting systems from China origin are ONLY acceptable from
Manufacturers with proven track record worldwide and with existing Solar PV
installations in Kuwait, having In-house engineering and R&D facility, complying
with all technical specifications for mounting systems and listed in globally
recognized Stock Exchange. Proof MUST be submitted for project approvals in
Kuwait.
C. The contractor shall provide all hardware required for assembling the System and
attaching the System to the mounting structure.
D. The mounting system shall be suitable for commercial solar installations and shall be
manufactured by a specialist mounting company with at least 5 years' experience in
KEO/19-3262-0000 26 3100/8 Solar Photovoltaic System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
manufacturing and delivering solar racking and mounting systems. The Manufacturing
facility shall have ISO 9001, ISO 14001 and OHSAS 18001 certifications at minimum.
E. The mounting structure shall comply with the following Standards (as applicable); ISO
657, GB50009, JIS-G3192. Anodized Aluminum sections or profiles / accessories
(6005-T5 or 6105-TF Aluminum Alloy) with minimum anodic oxide film mean thickness
of 10 microns or better; may be used for the structure subject to compliance with the
following Standard JISC8955 or Equivalent.
F. Hot dipped galvanized sections of steel shall comply with the following Standards: BS
EN ISO 1461, ASTM A-123 or GBT13912. At all cases; the minimum mean coating
thickness of the galvanizing shall not be less than 85 microns for steel section
thickness upto 6.3mm, for steel section thickness 6.4mm the minimum mean coating
thickness shall not be less than 100 microns.
G. System shall be fabricated with corrosion resistant materials such as aluminum or hot-
dipped galvanized steel. Stainless steel fasteners with minimum SAE 304 grade; or
better; must be used.
H. The roof mounting system shall be a non-penetrating system and shall maintain the
structural integrity of roofs, basin covers and other related systems. Provide material
compatible with roof construction between mounting elements and roof surface, unless
specifically allowed by roofing manufacturer.
J. The use of non-plated ferrous metals and any wood components for support structures
shall not be permitted.
K. PV Module Standards:
1. IEC 61215 " Silicon terrestrial photovoltaic (PV) modules -Design qualification
and type approval".
2. IEC 61646 "Thin-film terrestrial photovoltaic (PV) modules - Design qualification
and type approval".
3. IEC 61730-1 "Photovoltaic (PV) module safety qualification - Part 1:
Requirements for construction".
4. IEC 61730-2 "Photovoltaic (PV) module safety qualification - Part 2:
Requirements for testing"
5. IEC/TS 62804-1: "Photovoltaic (PV) modules-test methods for the detection of
potential-inducted degradation - Part 1: Crystalline silicon".
6. UL 1703 "Standard for Flat-Plate Photovoltaic Modules and Panels".
7. IEC 61701 "Salt mist corrosion testing of photovoltaic (PV) Modules".
8. IEC 61345 "UV test for photovoltaic (PV) modules".
9. IEC 62716 "Photovoltaic (PV) modules - Ammonia corrosion testing".
10. IEC 61853-1 "Photovoltaic (PV) module performance testing and energy rating
- Part 1: Irradiance and temperature performance measurements and power
rating".
11. EN 50380 "Datasheet and nameplate information for photovoltaic modules".
12. EN 50548 "Junction boxes for photovoltaic modules".
13. IEC 60068-2-68 "Environmental testing - Part 2-68: Tests - Test L: Dust and
sand".
A. General Description:
1. Multiple solar inverters (String or Central) shall be utilized to invert DC power
from the photovoltaic modules into AC power for interconnection to the grid.
The chosen solar inverters shall have a wide input voltage range up to 1000V
DC and their AC output shall be compatible with the local grid at 3-phase rated
at 415V, 50Hz
2. Solar inverters shall be sourced from a single reliable supplier with products
that are compliant to international testing standards as included under clause
1.02 herein.
3. The Solar PV Contractor shall source grid tied inverters from a manufacturer
that has set up an office or maintenance service center in any of the GCC
countries.
4. The building electrical interconnection point shall be provided to the Solar PV
Contractor via a circuit breaker in an MLTB/ MSB panel that is capable of
handling the current generated by the photovoltaic system. The Solar PV
Contractor shall be responsible for coordinating the required size of the circuit
breaker at the MLTP/ MSB with the appointed Electrical Contractor.
B. The DC power produced is fed to inverter for conversion into AC. In an On-grid system
AC power is fed to the Building grid at 415V three phases. Power generated from the
solar system during the daytime is utilized fully by powering the building loads from
MLTP/MSB.
C. Solar Inverters (String / Central) shall meet the following specifications as a minimum:
1. Integrated microprocessor based MPPT (More than single MPPT Input is
preferable)
2. Maximum efficiency of > 97.5% for string inverters and > 98% for central
inverters
3. European efficiency of > 97%
4. Total harmonic Distortion (THD) < 3%
5. Accessible DC disconnect switch to isolate the PV array from the inverter
6. Equipped with Ethernet communication or communication bus with equivalent
data transmission speed built into the inverter
7. SunSpec TCP communication
E. The inverter shall be provided with Liquid Crystal display (LCD) to provide
instantaneous information for the following as minimum:
1. Power level
2. Daily and life time energy production
3. PV array voltage and current
4. Utility voltage and frequency
5. Time or line fault message.
KEO/19-3262-0000 26 3100/11 Solar Photovoltaic System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
F. The inverter shall be manufactured not earlier than (1) One year from Project
Enterprise Date or latest. The Inverters shall be furnished with special Manufacturer's
warranties as indicated elsewhere herein.
G. Contractor shall be responsible for identifying the existing service and applicable
inverter current source type suitable.
2.04 DC CABLING
A. Rate DC cables for the maximum voltage and current of the PV array. Ensure account
is taken of the system voltage/currents of the series/parallel connected modules
making up the array. Include maximum output of the individual modules.
B. Select cables to withstand the environmental, voltage and current conditions at which
they may be expected to operate. Ensure the heating effects of current and solar gain
are considered.
C. The cable shall be two-layer construction with a low smoke halogen-free, flame
retardant and sunlight resistant cross-linked compound outer layer and halogen-free
thermoset polyolefin inner layer.
1. Suitable for continuous operating temperature of 90ºC Wet or Dry.
2. UL listed / TUV tested as Sunlight resistant.
3. Excellent UV and Ozone resistant
4. Suitable for wet, damp and humid locations.
5. Specially designed for excellent flexibility.
6. Compatible with all major connectors.
7. Cold bend and impact: -10º to +90ºC.
8. Applicable Listing:
a. TUV Certification 2 Pfg 1169/08.2007
b. TUV listed as PV1-F, 1000V (60038697)
c. UL listed as Type USE-2 or RHW-2: 600V (E76090)
d. 90ºC temperature rating: Temperature index in excess of 120ºC
e. RoHS Compliant.
A. Rate DC cables for the maximum voltage and current of the PV array. Ensure account
is taken of the system voltage/currents of the series/parallel connected module making
up the array. Include maximum output of the individual modules.
D. Ensure connectors have the same or greater voltage and current ratings as the
string/dc main cable to which they are fitted.
E. Provide each plug and socket connector with an outdoor label bearing the wording:
'Do not disconnect DC plugs and sockets under load - turn off DC supply first'
F. Ensure labeling is clear, legible, and located so as to be easily visible, and durably
constructed and affixed to last.
L. Minimum IP65 (IP 67 recommended) sealing protection against dust and water;
resistant to UV and ozone damage.
2.06 DC ISOLATORS
A. Provide a main DC isolation switch for each PV array, located as near as practically
possible to the inverter input unless provided already within the String Inverter or within
the MCB for the Central Inverters.
C. inverters for inverter maintenance. Switches shall be installed near the inverter
locations and shall be clearly marked to indicate array number and inverter served.
D. Switches shall be suitable for DC safety switch applications in NEMA 1 enclosures for
indoor use and NEMA 3 enclosures for outdoor use.
F. Labels must be clear, easily visible and constructed so as to remain legible and in
place for the design lifespan of the system.
G. DC isolation methods and locations should enable the open circuit voltage Voc and
the short circuit current Isc to be safely measured.
A. Solar PV Monitoring system shall be provided complete with all necessary hardware,
data-logger and software. The system should be capable of providing real-time
monitor and transmit (locally or remotely, as per Client's approval) the plant
performance data remotely and any 3rd party graphical display system as specified
hereunder. The minimum plant performance data shall include (but not limited to) the
following:
1. Performance Ratio - (Day, Week, Month and Year)
2. Energy Generation - (Day, Week, Month and Year)
3. Ambient Temperature - (Day, Week, Month and Year)
4. Module Temperature - (Day, Week, Month and Year)
5. Ambient temperature - Day, Week, Month and Year
6. Relative Humidity- (Day, Week, Month and Year)
7. Global Horizontal Irradiance - (Day, Week, Month and Year)
8. Irradiance on Collector Plane - (Day, Week, Month and Year)
B. High Quality Weather monitoring station needs to install in the plant near arrays in an
approved location by The Client with all necessary supporting hardware; from an
approved / reputable make. The station shall be robust, stand alone and low
maintenance installation to monitor the following at minimum:
1. Global Horizontal Irradiance
2. Collector plane Irradiance - Reference cell (or equivalent approved means)
3. Ambient temperature
4. Module temperature
5. Relative humidity
C. Solar PV Plant shall be furnished with Professional graphical Display system suitable
for Indoor installation. The system shall be complete with all display, built-in control
computer, adjustable mounting and cables/accessories hardware. The System
display should support IPS technology and LED for LCD Backlight technology with
minimum resolution of 1080p (Full HD). The system should have a minimum service
life of 30,000 Hours and should support animations and video files via all types of
interfaces including HDMI, DVI, VGA (HD-15), RJ 45 Ethernet (LAN), and WiFi. The
system should be furnished with adequate number of speaker output ports (min. 2)
and USB ports (min. 2) and shall be furnished with hand-held Remote Control. The
system should be "Energy Star" Qualified and to have Online Management
functionality with Individual Content & design capabilities and dynamic customizable
content according to user requirements.
PART 3 - EXECUTION
3.01 INSTALLATION
D. All required over-current protection devices shall be included in the system and
accessible for maintenance. Each shall have trip ratings no greater than the de-rated
amperage of the conductor it protects.
F. Installation should be organized and neat. Module connections and wiring should be
neatly prepared and easily accessed by service persons.
G. All cables, conduit, exposed conductors, and electrical boxes should be secured and
supported according to code requirements.
H. System switching equipment shall have convenient access for resetting or repair
during electrical outages.
I. Site shall be maintained and kept secure, free of excessive debris and in safe condition
during the construction period.
J. Special attention shall be paid to minimizing the risk from exposed fasteners, sharp
edges, and potential damage to the modules or support structures. Corrosion
resistance and durability of the mechanical hardware shall be emphasized - the use
of stainless-steel fasteners and aluminum support structures are required. The use of
ferrous metals, wood, or plastic components is not acceptable.
B. Modules may be delivered in containers that can be easily supported by the roof.
Contractor shall insure proper placement of point loads on the roof for equipment
staging and installation.
C. Contractor shall maintain the integrity of the roof surface during delivery, handling and
installation, including laying out mats, insulation/plywood layers, etc. Any damage to
the roof surface shall be identified and repaired by the contractor.
D. Each module shall be visually inspected for defects by the contractor and the Engineer
prior to installation.
E. PV modules shall be free of dirt and construction debris prior to system start up
procedures.
A. The Solar PV Contractor should also provide a warranty covering the complete PV
Plant; including mechanical structure, total electrical system of solar power plants;
against any manufacturing / design / installation defects for a period of Five (5) years.
C. Special warranties specified in this Article shall not deprive Owner of other rights
Owner may have under other provisions of the Contract Documents and shall be in
addition to, and run concurrent with, other warranties made by contractor under
requirements of the Contract Documents.
D. The warranty period will start from the date of successful Acceptance of the PV plant.
E. In Addition to the above system warranty; the following product warranties shall be
provided as indicated below:
F. PV Modules
1. The Contractor shall submit a written warranty signed by the manufacturer
agreeing to repair, restore or replace any defective equipment specified during
the warranty period. Manufacturer's materials and workmanship warranties
include, but are not limited to, the following:
a. Faulty operation of PV modules.
b. Defects in design, material, workmanship or manufacture that materially
impede their functioning
c. Warranty Period: 10 years from date of delivery.
2. Manufacturer's Special Minimum Power Output Warranty: Manufacturer agrees
to repair or replace components of PV modules that fail to exhibit the minimum
power output within specified warranty period. Special warranty, applying to
modules only, applies to materials only, on a prorated basis, for period
specified. Manufacturer's minimum power output warranties include, but are not
limited to, the following warranty periods, from date of delivery:
a. Power output warranty: minimum for 25 years from the date of taking over
certificate. Guaranteed power output performance shall ensure:
1) First year: degradation in power performance of the PV modules
does not exceed 1.5% of nominal rated power value at Standards
Test Condition (STC) as minimum.
2) The PV modules power degradation should be linear with a final
derating after 25Years by 80% of the nominal power rating at STC
as minimum.
3) PV String Combiner: 5 years from the date of taking over certificate.
Supplier must give an extendable warranty option. Proceeding shall
be at Employer discretion.
4) PV plant controller and monitoring equipment: 5years from the date
of taking over certificate. Supplier must give an extendable warranty
option. Proceeding shall be at Employer discretion.
5) Other equipment/system equipment: All other
equipment/components inside the PV solar system shall be provided
with two years' warranty from the date of taking over certificate.
G. Inverters
1. Manufacturer's Special Warranty: Manufacturer agrees to repair or replace
components of inverters that fail in materials or workmanship within specified
warranty period. Manufacturer's materials and workmanship warranties include,
but are not limited to, the following:
a. Faulty operation of inverters
H. Mounting Structure
1. Manufacturer's Special Warranty: Manufacturer agrees to repair or replace
components of the mounting structure that fail in materials or workmanship
within specified warranty period.
a. Manufacturer's materials and workmanship warranties include, but are not
limited to, the following:
1) Faulty operation of PV modules.
2) Defects in design, material, workmanship or manufacture that
materially impede their functioning
3) Warranty Period: 10 years from date of purchase.
I. Service
1. Qualifications
a. Contractor shall be locally based and have in-house first response
technicians certified by panel and inverter manufacturer. Contractor shall
demonstrate locally based service capabilities on the Project Team
Organization Chart.
b. During the contractual maintenance period, contractor shall conduct, and
document all recommended preventative maintenance. Preventative
maintenance shall include the following and be performed no less than
annually by direct qualified employees of the contractor:
1) Visual and mechanical inspection of all equipment
2) Random checking of mounting system operation
3) Verification of electrical dc continuity via ammeter readings
4) Inspection and replacement of all fuses.
5) A Preventative Maintenance plan shall be submitted to the Engineer
for review and approval prior to being included as part of the O&M
Manual.
A. The contractor shall leave a supply of System materials on-site that match the products
that are installed in the System as follows:
1. PV Modules. 1% of used PV Module.
2. (1) Spare inverter from each model used (or main spare parts for the central
inverter).
3. DC Disconnect Switches. (1) for each model used in the System.
A. The Solar System monitoring & recording controller must a use standard
communication protocols with public IP to insure full integration and live data
accessibility between project Solar System and existing Solar System at MEW HQ.
B. The Solar System monitoring & recording controller should provide extension module
and gateway web access permissions for Third Party controller at MEW Head Quarter
which operates with BACnet/IP communications for full communication and
integration.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUMMARY
A. Section Includes:
1. Testing and commissioning.
2. Cold Commissioning.
3. Hot Commissioning.
4. Earthing.
5. Cables.
6. Electrical Equipment
7. Switchboards
8. Calibration.
9. Commissioning process documents.
B. Related Requirements:
1. Section 26 2413 - Switchboards
2. Section 26 0519 - Low Voltage Electrical Cables
3. Section 26 0526 - Earthing And Bonding For Electrical Systems
4. Section 26 3100 - Solar Photovoltaic System
5. Section 26 4113 - Lightning Protection for Structures
1.03 DEFINITIONS
B. kV: Kilovolts
PART 3 - EXECUTION
A. All testing and commissioning to be executed in compliance with IEC 62446 Grid
Connected Photovoltaic systems - Minimum Requirements for system documentation,
commissioning tests and inspection.
C. All materials, labour, instruments and tools required for carrying out of the tests will be
supplied by the contractor.
D. Test, inspect and operate all equipment, materials and components, whether the tests
are detailed in this specification or not.
E. Test reports to be submitted in a neat and legible format. The report should specify
the component or system being tested, the test date and the test results.
B. All trial tests, adjustments, calibration and balancing as required shall be conducted
by the Contractor.
C. Ensure phasing and phase rotation on all three-phase cables are the same throughout
the system.
3.04 EARTHNG
A. Conduct earthing tests to confirm compliance with the system design and local
standards and as per Section 26 0526 - Earthing And Bonding For Electrical Systems.
3.05 CABLES
B. Conduct a cable insulation resistance test to confirm insulation between phases and
phase to ground with all circuits installed and connected.
A. Carry out complete tests as per manufacturer's instruction details and all routine tests.
3.08 CALIBRATION
A. All meters should be calibrated and sealed in the presence of the client and the utility's
representative and as per MEW requirements, if required.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
C. Scheduled/Preventative Maintenance
1. The scheduling and frequency of preventative maintenance is dictated by a
number of factors. These include the technology selected, environmental
conditions of the site, warranty terms and seasonal variances. The scheduled
maintenance is generally carried out at intervals planned in accordance with
the manufacturers' recommendations, and as required by the equipment
warranties. Scheduled maintenance should be conducted during early morning
or evening.
2. Specific scheduled maintenance tasks are covered in the following sections.
a. Module Cleaning
1) Module cleaning shall be carried out manually by contractor's
manpower as per predetermined cleaning schedule which approved
by the engineer and following to recommendations of the
manufacturer of PV modules system and also when there is need
for cleaning like after each sand storm. All safety precautions shall
be taken into consideration while cleaning.
b. Module Connection Integrity
1) Checking module connection integrity is important for systems that
do not have string level monitoring. This is more likely for central
inverter systems for which no string monitoring at the
junction/combiner boxes has been designed. In such cases, faults
within each string of modules may be difficult to detect. Therefore,
KEO/19-3262-0000 26 3120/1 Operation and Maintenance of Solar Energy
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
the connections between modules within each string should be
checked periodically (this may include measuring the string current).
c. Junction or String Combiner Box (If any)
1) All junction boxes or string combiner boxes should be checked
periodically for water ingress, dirt or dust accumulation and integrity
of the connections within the boxes. Loose connections could affect
the overall performance of the PV plants. Any accumulation of water,
dirt or dust could cause corrosion or short circuit within the junction
box. Where string level monitoring is not used, periodic checks on
the integrity of the fuses in the junction boxes, combiner boxes and
in some cases, the module connection box should be conducted.
d. Hot Spots
1) Potential faults across the PV plants can often be detected through
thermography. This technique helps identify weak and loose
connections in junction boxes and inverter connections. It can also
detect hot spots within inverter components and along strings of
modules that are not performing as expected. Thermography should
be conducted by a trained specialist using a thermo-graphic camera.
e. Inverter Servicing
1) Generally, inverter faults are the most common cause of system
downtime in PV power plants. Therefore, the scheduled
maintenance of inverters should be treated as a centrally important
part of the O&M strategy. The maintenance requirements of
inverters vary with size, type and manufacturer. The specific
requirements of any particular inverter should be confirmed by the
manufacturer and used as the basis for planning the maintenance
schedule.
2) The preventative maintenance for an inverter should, as a minimum,
include:
a) Visual inspections.
b) Cleaning/replacing cooling fan filters. Removal of dust from
electronic components. Tightening of any loose connections.
c) Any additional analysis and diagnostics recommended by the
manufacturer.
f. Structural Integrity
1) The module mounting assembly, cable conduits and any other
structures built for the PV plants should be checked periodically for
mechanical integrity and signs of corrosion.
2) This will include an inspection of support structure foundations for
evidence of erosion from water run-off.
g. Balance of Plants
1) The remaining systems within PV power plants, including the
monitoring and security system, auxiliary power supplies, and
communication systems should be checked and serviced regularly.
Communications systems within the PV power plants and to the
power plants should be checked for signal strength and connection.
Inspection
Inspection Actions required
No Frequency
A Solar Modules
Once in a
1 Dust deposition Cleaning of modules
month
Module Junction box
Replace the Module
2 malfunction, visual 1 Month
in case of failure.
inspection
Improper Module Cable Replace the Cables /
3 1 Month
Connectors Connectors
De-lamination,
4 discoloration Replace the Module 1 Month
leading to low output
5 Module Cracks Replace the module 1 Month
Solar Module Mounting Structure
Check Fasteners –
take remedial
measures in case of
B Inspection of Mounting issues.
3 Month
Structure and Hardware
Check lugs of
earthing conductors
for corrosion –
change as needed.
C SSM - String Monitoring Box
Check for Loose cable Tighten the
1 3 Months
Termination connection
2 Fuse Failed Replace Fuse 3 Months
Check the
3 Surge Suppression Device connections - 3 Months
Replace if it is failed
SSM - String Monitoring Box (Out Put) Technical Parameters
D measured at >800 W/m²
1 Open Circuit Voltage (Voc) 3 Months
2 Output Current 3 Months
F Inverter
Tighten the
1 Loose cable Termination 6 months
connection
2 Dust Deposition Cleaning Monthly
2 Current 3 Months
3 Frequency 3 Months
H LV Panel
Tighten the
1 Loose cable termination
connection
1 Voltage Monthly
2 Current Monthly
3 Frequency Monthly
J Power Optimizer
Check for loose cable Tighten the
1 3 months
connection connection.
E. All periodic maintenance & inspections shall be done as specified by the equipment
manufacturers.
F. Unscheduled Maintenance
1. Unscheduled maintenance is carried out in response to failures. As such, the
key parameter when considering unscheduled maintenance is diagnosis,
speed of response and repair time. Although the shortest possible response is
preferable for increasing energy yield, this should be balanced against the likely
increased contractual costs of shorter response times.
2. The agreed response time shall be within 12 hours.
3. The majority of unscheduled maintenance issues are related to the inverters.
This can be attributed to their complex internal electronics, which are under
constant operation.
4. Depending on the nature of the fault, it may be possible to rectify the failure
remotely - this option is clearly preferable if possible.
5. Other common unscheduled maintenance requirements include:
a. Tightening cable connections that have loosened.
b. Replacing blown fuses. Repairing lightning damage.
c. Repairing equipment damaged by intruders or during module cleaning.
Rectifying SCADA faults.
d. Repairing mounting structure faults.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.1 SUMMARY
A. This section includes the supply, installation, testing and commissioning of standby
diesel fuelled generators with the following features:
1. Diesel Engine
2. Unit Mounted Cooling System
3. Unit Mounted Control and Monitoring
4. Fresh air intake and exhaust air systems
5. Fuel supply, day tank, pumping and filtering
6. Batteries & battery chargers.
7. Grounding (Earthing).
B. Functional Description: When the mode selector switch on the control and monitoring
panel is in the "automatic" position, remote control contacts in one or more separate
automatic transfer switches initiate the starting and stopping of the generator set. When
the mode selector switch is placed in the "manual" position, the generator set starts
manually. The "off" position of the same switch initiates shutdown of the generator set.
Upon specific malfunction of the generator set it shall be made to shut down
automatically and initiate alarms. Operation of a remote emergency stop switch also
shuts down the unit.
D. In the event of a mains power failure, the following actions shall be initiated
automatically from the BAS and or from the automatic transfer switch: All the major
loads that are connected to the Generator sets shall be set to “manual mode”, to be
restarted only manually by the operator and subsequently transferred to “automatic
mode”.
E. A BAS software flag shall be available for the operator to select either manual or
automatic restart after a power failure for all Low Voltage motors. If “Automatic” is
selected, then these motors shall be started sequentially, one process area at a time.
Automatic control sequences and timer-controlled operations shall also be resumed. If
the flag is set to “manual” then all controls shall be set to manual, and be ready for
restart by the operator.
1.4 SUBMITTALS:
A. Product Data: Include Manufacturer’s product literature and performance data, sufficient
to verify compliance to specification requirements.
1. A paragraph by paragraph specification compliance statement, highlighting
thereby any deviations whatsoever and indicating the implications as applicable.
2. Dimensioned outline plan and elevation drawings of engine generator set and
other components specified.
3. Thermal damage curve for generator.
4. Time-current characteristic curves for generator protective device.
C. Field Test and Observation Reports: Indicate and interpret test results and inspection
records relative to compliance with performance requirements.
E. Factory Test Reports: For units to be shipped for this Project, showing evidence of
compliance with specified requirements.
J. Maintenance Data: For each packaged engine generator and accessories to include in
the operation & maintenance manuals including the following:
1. List of tools and replacement items recommended to be stored at the Project for
ready access. Include part and drawing numbers, current unit prices, and source
of supply.
2. Detail operating instructions for both normal and abnormal conditions.
B. The manufacturer should have a local agent with a proven successful experience record
in the installation, testing, commissioning and maintenance of diesel generators of the
size specified herein. The local agent should have a local spare parts warehouse where
all the generator regular consumables shall be available on shelf.
C. The agent should have been associated with the manufacturer for a minimum period of
five years.
D. Engine Exhaust Emissions Comply with applicable state and local government
requirements.
E. The emergency power supply system and its components shall be such as may be
properly maintained and serviced without the necessity of carrying expensive spare
parts stocks, or being subjected to interrupted service due to the lack of spare parts
F. An engine of the same model, bore, stroke and configuration, rated at the same or
higher bhp and rpm shall have performed satisfactorily (i.e. without failures involving a
major component, such as crankshaft, valve, cam shafts, piston, injector and the like) for
a minimum of 2000 hours of actual operation under average rated load conditions of
75% or greater over a two year period, either at the manufacturer's factory or a
stationary power plant.
H. Emergency generator set shall be designed to allow easy replacement of major items
subject to wear.
I. The size of the set shall be the same or next higher standard size nearest to the rating
specified, when operating at specified frequency, voltage, altitude and maximum
ambient temperature.
J. Provide factory test, startup by a supplier authorized by the manufacturer, and on-site
testing of the system.
K. The generator set manufacturer shall warrant all equipment provided under this section
so that there is one source for warranty and product service. Technicians specifically
KEO/19-3262-0000 26 3213/3 Engine Generator Set With Fuel Day Tank
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
trained and certified by the manufacturer to support the product and employed by the
generator set supplier shall service the generator sets.
L. Comply with applicable sustainable design standards and local authority requirements
for max. noise level and NO2 emission at adjacent property boundaries due to sound
and harmful gases emitted by Generator set.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
A. Deliver engine generator set and system components to their final locations in protective
wrappings, containers, and other protection that will exclude dirt and moisture and
prevent damage from construction operations. Remove protection only after equipment
is safe from such hazards.
A. General Warranty: Special warranty specified in this Article shall not deprive Owner of
other rights Owner may have under other provisions of the Contract Documents and
shall be in addition to, and run concurrent with, other warranties made by Contractor
under requirements of the Contract Documents.
D. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
KEO/19-3262-0000 26 3213/4 Engine Generator Set With Fuel Day Tank
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Indicator Lamps: Two for every six of each type used, but not less than two of
each.
2. Filters: four sets each of lubricating oil, fuel, and combustion-air filters.
3. Belt – four sets
4. Fuse – four sets
5. Tools recommended by the manufacturer – one set
C. Complete itemized list of different spare parts/tools for the emergency generator to be
included and priced by the contactors. The list shall be furnished by the generator
proposed vendor to ensure proper maintenance for two years.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
C. Performance
1. Voltage regulation shall be less than ± ½ % (steady state) and less than ±1% (no
load to full load). Random voltage variation with any steady load from no load to
full load shall not exceed ± ½ %.
2. Frequency regulation shall be isochronous from steady state no load to steady
state rated load. Random frequency variation with any steady load from no load
to full load shall not exceed ± ¼%.
3. The diesel engine-generator set shall be capable of single step load pick up of
100% nameplate kW and power factor, less applicable de-rating factors, with the
engine-generator set at operating temperature.
4. The generator set shall be capable of sustaining a minimum of 90% of rated no
load voltage with the specified kVA load at near zero power factor applied to the
generator set.
D. Connections
1. The generator set load connections shall be composed of silver or tin plated
copper bus bars, drilled to accept mechanical or compression terminations of the
number and type as shown on the drawings. Sufficient lug space shall be
provided for use with cables of the number and size as shown on the drawings.
2. Power connections to auxiliary devices shall be made at the devices, with
required protection located at a wall-mounted common distribution panel.
3. Generator set control interfaces to other system components shall be made on a
common, permanently labeled terminal block assembly.
E. Exciters:
1. Fast response type with a rotating 3-phase full wave bridge rectifier.
F. Voltage Regulator:
1. Hermetically sealed, silicon controlled rectifier type employing a zener reference
to give a voltage stability of 1.5% with allowance for up to 3% speed variation.
2. To provide automatic protection of the unit on 3 phase short circuits.
3. To include automatic under frequency protection to allow the generator to be
operated under load, at less than synchronous speeds, for engine start-up and
shutdown procedures. Switches and/or fuses shall not be used to give this
protection.
4. Transient variations shall be limited to a maximum 17% for a duration not
exceeding 0.25 seconds.
KEO/19-3262-0000 26 3213/6 Engine Generator Set With Fuel Day Tank
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
G. Manual Voltage Rheostat:
1. To be fitted to control panel for fine adjustments.
2.3 ENGINE
A. The engine shall be diesel, 4 cycle, radiator and fan cooled. The horsepower rating of
the engine at its minimum tolerance level shall be sufficient to drive the alternator and all
connected accessories. Two cycle engines are not acceptable.
B. The engine shall be direct injection, four stroke, 1500 RPM, naturally aspirated or
turbocharged diesel engine to provide sufficient output power for the generator.
D. The engine shall be with integral air cooled radiator and shall include air filter, fuel and
lubricating oil filters, water pump, fuel and lubricating oil pumps, oil cooler, governor,
flywheel, starter motor, tachometer, service hour counter, safety devices and all other
accessories. The air filter shall be of the dry element type. The fuel filters shall be
suitable for preventing all particles of 10 micron size or larger from passing.
E. A pressure type lubricating system with gear type oil pump and filters shall be fitted to
the engine. A graduated dipstick shall be provided, located in an accessible position.
F. A heat-exchanger must be fitted in the cooling-water circuit for cooling the lubricating-oil
and shall be capable of keeping lubricating-oil temperature within safe limits at all
conditions of load-requirements at worst climatic conditions. The drain connection for
draining of sump-oil must be brought on side of the generator base. Method of
lubrication should be fully described in the offer. It is preferable that the camshaft-
bearing lubrication be directly fed from the lubricating-oil pump and not through the main
bearing.
H. The engine shall run steadily at any load at its rated speed. Changes in speed shall
comply with ISO 8528 Class G2. The engine shall have safety devices for stopping the
engine and giving alarm in cases of high water temperature, low oil pressure and
overspeed.
I. Drain plugs and cocks for oil, water and fuel shall be provided in readily accessible
locations.
K. Engine mounted wiring shall be by means of MICC cables properly fixed and protected
and terminating in a common terminal box mounted on the engine.
KEO/19-3262-0000 26 3213/7 Engine Generator Set With Fuel Day Tank
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
L. The diesel engine shall be derated according to ISO 3046 for operation in locations of
high ambient temperatures. Engine manufacturer's certificate for engine deration shall
be submitted to approval.
A. The diesel engine generator set is cooled with an integral radiator (set mounted). The
radiator shall be heavy-duty tropical design with mechanically driven fan of sufficient
capacity to maintain safe operation at the site in worst climatic conditions. Coils shall be
of copper alloy tubing with copper fins.
B. The radiator shall be provided with fan guard and shall be connected by flexible
connections to engine water pipes.
C. A thermostatically controlled valve shall be provided in the cooling system to assist rapid
heating up of the water in the engine jacket when starting from cold. A thermostatically
controlled electric heater, suitable for connection to mains supply shall be located in the
cooling water circuit with 'ON/OFF' switch in the control panel. The heater shall be
capable of maintaining the whole of the cooling water at a temperature of 20 ºC with an
ambient temperature of 0 ºC. Indicating lamps in the control panel shall indicate when
heater is 'ON'. The heater shall be switched 'OFF' automatically when the engine starts
and switched 'ON' when it stops. The heater shall be connected through HRC fuses.
Heaters shall be easily removable for replacement.
A. Starting and control batteries shall be made of high performance lead acid, vented type,
24 volt DC, sized as recommended by the engine manufacturer, complete with battery
cables and connectors
B. Batteries size shall be heavy duty such that lead acid cells are not discharged below
75%.
C. Batteries output capacity shall be such that if the engine does not start at the first
attempt, there is sufficient starting attempts. The minimum number of repeat starts
required, each of 10sec duration, should be three.
D. Batteries charging shall be provided from a suitable full wave rectification static-charger
with auto trickle-charge enclosed in an adequately ventilated sheet steel case and
incorporated within the control panel with associated instruments and controls mounted
on front of panel.
E. An ammeter and voltmeter in the control panel shall indicate the state of the battery and
its charging rate.
F. The starting batteries of the diesel engines shall be at least dimensioned for at least four
start attempts and suitable for six hours continuous. The battery shall be provided with
re-charging equipment.
KEO/19-3262-0000 26 3213/8 Engine Generator Set With Fuel Day Tank
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2.7 CONTROL PANEL:
A. Each generator control panel shall be electronic modular, generator-mounted type. The
control panel shall be environmentally sealed, solid-state, microprocessor based module
for engine control and AC metering. The control panel shall provide the following control
and monitoring features:
1. Automatic/manual start-stop engine control with programmable safety shut
downs and associated flashing LED indicators for low oil pressure, high coolant
temperature, overspeed, overcrank and emergency stop.
2. Cycle cranking adjustable 1-60 second crank/rest periods.
3. Cool down timer, adjustable 0 - 30 minutes.
4. LCD digital read out for: Engine oil pressure, coolant temperature, engine RPM,
system DC volts, engine running hours, generator AC volts, AC amperes and
frequency.
5. Control system diagnostic codes: Loss of engine speed signal, invalid engine
control switch signal, internal circuit fault, loss of coolant temperature signal.
6. Engine Control Switch
7. Voltmeter, ammeter, KWH meter, frequency meter, PF meter.
8. Voltmeter Phase Selector Switch
9. Emergency Stop Push Buttons
10. Indicator/Display Test Button
11. Voltage Adjust Potentiometer
12. Provision for interface through RS 485 port.
B. The control Panel shall include all interfaces necessary for proper operation with the
paralleling equipment provided under this contract. The generator set supplier shall be
responsible for complete compliance to all specification requirements for both the
generator set and the paralleling equipment.
B. The fuel supply system shall be considered as mechanical support system for the diesel
generator set and indicated in the relevant Mechanical drawings. Refer Division 23
related Sections for compliance.
The system includes two types of fuel tanks.
1. Main fuel tank or storage fuel tank.
2. Each Generator room shall be provided with fuel oil tank (day tank). Refer to
Mechanical drawings for the capacity of the fuel oil tank.
C. Day Tank: Comply with UL 142, freestanding, factory-fabricated fuel tank assembly,
with integral, float-controlled transfer pump and the following features:
1. Tank Capacity: As recommended by engine manufacturer for an uninterrupted
period of 8 hours' operation at 100 percent of rated power output of engine-
generator system without being refilled
2. Pump Capacity: Exceeds maximum flow of fuel drawn by engine-mounted fuel
supply pump at 110 percent of rated capacity, including fuel returned from
engine.
3. Low-Level Alarm Sensor: Liquid-level device operates alarm contacts at 25
percent of normal fuel level. Provide interface to. BMS
4. High-Level Alarm Sensor: Liquid-level device operates alarm and redundant fuel
shutoff contacts at midpoint between overflow level and 100 percent of normal
fuel level. Provide interface to. BMS
KEO/19-3262-0000 26 3213/9 Engine Generator Set With Fuel Day Tank
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
5. Piping Connections: Factory-installed fuel supply and return lines from tank to
engine; local fuel fill, vent line, overflow line; and tank drain line with shutoff
valve.
6. Redundant High-Level Fuel Shutoff: Actuated by high-level alarm sensor in day
tank to operate a separate motor device that disconnects day-tank pump motor.
Sensor shall signal solenoid valve, located in fuel suction line between fuel
storage tank and day tank, to close. Both actions shall remain in shutoff state
until manually reset. Shutoff action shall initiate an alarm signal to control panel
but shall not shut down engine-generator set.
A. Associated engine exhaust system, except the silencers / mufflers as supplied with the
diesel engine, will be furnished and installed under the scope of Mechanical contract as
shown and indicated in the relevant drawing.
A. As part of the supply and installation of the diesel / alternator set, the Contractor shall
furnish and install the cooling and aspiration air intake.
B. The system includes the engine radiator exhaust air system plus that of the generator
room ventilation system. These shall be under the scope of HVAC contract as shown
and indicated in the relevant drawing.
D. The acoustic treatment and ductwork system shall be such as not to reduce the
efficiency of the engine or output of the alternator.
A. The following internal controls shall be provided within the master control section:
1. Programmable controller for interface with touchscreen, and to provide load
demand, load pick-up, and load shed functions.
2. Load pick-up output contacts, rated 10 A at 600 VAC (3 contacts per level).
3. Load shed output contacts, rated 10 A at 600 VAC (3 contacts per level).
4. Provide all other components required, such as properly sized current
transformers, transducers, terminal blocks, etc., for reliable system operation.
E. Bus Overload:
1. If a bus overload occurs for any reason, a load shed signal will be generated to
initiate load shedding in the system.
2. If the bus does not return to proper frequency within a predetermined period of
time, additional load shed signals will be generated.
H. Distribution Equipment
1. Provide emergency feeder distribution breakers of the number and size as shown
on the project drawings.
2. The breakers provided shall be molded case breakers, motorized type, with
electronic trip units. Breakers shall be provided with lugs of the number and size
as shown on the project drawings.
3. The breakers shall be group-mounted in a distribution panel board which is bus
connected to the paralleling equipment. Provide equipment in enclosure with
sufficient space for cable connection, and with access as shown on the drawings.
A. The container shall be brand new, suitably sized ISO standard container and shall have
enough space to house the generator set and its ancillaries.
C. Air inlet and discharge flows are through sound attenuators positioned at each end of
the container and constructed in splitter or baffle form to achieve effective noise
absorption with minimum air resistance. Each sound attenuator incorporates fixed blade
weather louvers and bird guards.
D. The noise level shall be 85dbA @ 1 meter distance from the enclosure with the
generator set operating at 100% prime rating.
E. It shall incorporate personnel hinged access doors, with one single door on each side.
These have a peripheral compression seal and are fitted with heavy-duty single point
handle and fastener. It shall be fitted with internal panic release mechanism and all
doors are lockable. Emergency stop button shall also be fitted on the container exterior
and equipped with safety measures to prevent un-necessary operation.
F. The exhaust system pipe work shall be insulated with heat resistant material inside the
container.
G. Lube oil, engine breather and cooling water drain shall be piped out to the exterior of the
soundproof container. The lube oil, cooling water drain shall be plugged and a catch
basin shall be installed at the end of the engine breather pipe for excess oil.
H. A daily service tank of sufficient capacity for 8 hours full load operation shall be
integrated with the soundproof container base. It shall be fitted with strainers, control
cocks, drain cocks, piping to the engine, vents, all necessary fuel lines and fittings.
I. A load connection point with weather proof access cover shall be provided on the side of
the container. The bus bars shall be enclosed in a weather proof cabinet and flexible
cable of sufficient capacity shall connect the bus bars and the circuit breaker. The
external AC outlet plug point shall be installed inside the weather proof access cover.
J. The container shall be equipped with sufficient DC lighting with corresponding timer
switch and AC lighting necessary for inspection and maintenance inside the container.
3.1 EXAMINATION
A. Examine areas, equipment foundations, and conditions, with Installer present, for
compliance with requirements for installation and other conditions affecting packaged
engine generator performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.3 INSTALLATION
D. Install packaged engine generator to provide access for periodic maintenance, including
removal of drivers and accessories.
E. Install cooling-system piping, accessories, hangers and supports, and anchors for
complete installation.
G. Install exhaust-system piping for diesel engines. Extend to point of termination outside
structure. Size piping according to manufacturers written instructions.
H. Install condensate drain piping for diesel-engine exhaust system. Extend drain piping
from low points of exhaust system and from muffler to condensate traps and to point of
disposition.
I. Electrical Wiring: Install electrical devices furnished by equipment manufacturers but not
specified to be factory mounted.
3.4 CONNECTIONS
A. Electrical wiring and connections are specified in Division 26 Section “Wiring Devices”
3.5 IDENTIFICATION
3.6 TESTING
A. Factory Test:
1. The Diesel Engine shall be tested at the manufacturer's plant for its output-power
and relevant temperatures. Test certificate to be submitted the complete
Generator Set. The test shall be performed on the actual unit which will be
delivered to the project site.
B. Field Tests:
1. Full performance test including speed and voltage regulations and the test shall
include the following to be performed at site before handing over:
a. Partial load test.
b. Full load test for three hours
c. 110% load test for one hour
2. Detailed records of the foregoing tests shall be submitted.
3. Test at site before taking over and after the sets are completely installed at the
site, full performance operation shall be carried out on the set at the worst
specified conditions in summer of 3 hrs of continuous running to the approval.
4. Provide a resistive load bank and make temporary connections for full load test, if
necessary.
5. Top up diesel fuel and all other liquids after field test completion.
6. The commissioning should be carried out by the Diesel Engine Manufacturer's
engineer or his Authorised Representative.
A. Prior to shipment, all final performance test shall be witnessed at the factory. Contractor
shall arrange and pay for all related expenses for the team of four persons from PAAET,
including Travel, transportation, accommodation and per diem for seven days.
B. The contractor during that period shall provide labor and parts maintenance on the
installed system. During that period, the contractor shall be responsible for the regular
inspection and maintenance as recommended by the manufacturer. Full maintenance
by skilled employees of the manufacturer's designated service organization for the life of
warranty. Include quarterly exercising to check for proper, starting, load transfer, and
running under load. Include routine preventive maintenance as recommended by
manufacturer and adjusting as required for proper operation. Maintenance agreements
shall include parts and supplies as used in the manufacture and installation of original
equipment.
KEO/19-3262-0000 26 3213/14 Engine Generator Set With Fuel Day Tank
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. Operation & Maintenance
1. The Contractor shall be fully responsible for the satisfactory operation of diesel
generator installation during the operation and maintenance period and
thereafter during the maintenance (defect liability) period. He shall carry out
necessary inspection, preventive maintenance and testing to keep the sets ready
all the time. The set shall function satisfactorily during power failures. The
Contractor shall carry out routine testing. The testing shall be carried out in the
presence of Owner’s Representative. The Contractor shall provide all electrical
and mechanical spare parts, grease, lucubrating oils, touch-up paints, etc.,
required for the maintenance of the D/G Installation. The Contractor shall prepare
log-books listing full details of maintenance work and each log-book entry shall
be signed by the Owner’s Representative.
3.9 TRAINING
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Architect/ Engineers review outlining all
deficiencies and course of action. The contractor shall ensure all deficiencies outlined
are rectified, retested, and certified.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.1 SUMMARY
A. UPS Components: The UPS shall consist of the following main components:
1. UPS system with N Configuration module containing Rectifier(s), Inverter(s),
Battery Charger(s), Static Bypass, and associated Control and Monitor Panel.
2. Battery string(s), either internal or in external cabinets or Racks .
3. Non-matching wall mounted or floor standing maintenance bypass cabinets or
multi-module parallel tie cabinets.
B. UPS Module Modes of Operation: The UPS Module shall operate as an on-line, fully
automatic system in the following modes:
1. Normal: Utilising commercial AC power, the critical load shall be continuously
supplied by the Inverter. The Inverter shall power the load while regulating both
voltage and frequency. The Rectifier shall derive power from the commercial AC
source and shall supply DC power to the Inverter. Simultaneously, the Battery
Charger shall charge the battery.
2. Battery: Upon failure of the commercial AC power, the critical load shall continue
to be supplied by the Inverter, which shall obtain power from the batteries without
any operator intervention. There shall be no interruption to the critical load upon
failure or restoration of the commercial AC source.
3. Recharge: Upon restoration of the AC source, the Charger shall recharge the
batteries and simultaneously the Rectifier shall provide power to the Inverter.
KEO/19-3262-0000 26 3353/1 Static Uninterruptible Power Supply
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
This shall be an automatic function and shall cause no interruption to the critical
load.
4. Bypass: If the UPS module must be taken out of the Normal mode for overload,
load fault, or internal failures, the static bypass switch shall automatically transfer
the critical load to the commercial AC power. Return from Bypass mode to
Normal mode of operation shall be automatic. No-break transfer to and from
Bypass mode shall be capable of being initiated manually from the front panel.
5. Back feed Protection : The UPS systems must have built in back feed protection
complying to IEC 62040-1
6. Energy Saver: The UPS shall continuously monitor the voltage and frequency of
the bypass source. When the source parameters are within acceptable limits, the
UPS will utilise a minimal/optimal combination of its internal subsystems to
ensure acceptable power is always delivered to the critical load, at a system
efficiency of 99% or greater, over the range of 60% to 100% load. The Energy
Saver System shall be enabled by the user, and shall be adjustable. It shall
incorporate a “High Alert Mode” to automatically (without user intervention)
provide maximum power conditioning any time bypass source variation levels
exceed pre-set, adjustable limits. When Energy Saver System is utilised, the
UPS must attenuate ANSI C62.41-type line transients to within IEC and ITIC
limits. The Energy Saver System shall be able to distinguish between upstream
(utility) faults and downstream (load) faults, and react appropriately to protect and
support the critical load, without interruption.
7. Manual Bypass: The UPS shall include an internal manual maintenance bypass
switch that shall enable safe access to internal major assemblies whilst the load
is supplied by mains power.
1.4 REFERENCES
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
1.5 SUBMITTALS
A. The UPS shall be supplied with sufficient documentation, including the following
manuals:
1. Installation and Operation Manual: One copy of the installation and operation
manual shall be furnished. It shall possess sufficient detail and clarity to enable
1.6 QUALIFICATIONS
A. The UPS manufacturer shall have a minimum of twenty five years’ experience in the
design, manufacture and testing of solid-state UPS systems.
B. The UPS manufacturer shall have ISO 9001 certification for engineering/R&D,
manufacturing facilities and service organisation.
C. The UPS manufacturer shall maintain a staffed 7x24x365 call centre for technical and
emergency support either directly or through authorised service providers.
D. Spare Parts Support: Parts supplies shall be located in the field to provide 80% of all
emergency needs. The factory shall serve as the central stocking facility where a
dedicated supply of all parts shall be available within 24 hours.
E. Product Enhancement Program: The UPS manufacturer shall make available feature
upgrade service offerings to all users as they are developed. These upgrades shall be
available as optional field-installable kits.
A. The UPS shall withstand any combination of the following external environmental
conditions without operational degradation.
1. Operating Temperature: 5 degrees C to +40 degrees C continuous without de-
rating (excluding batteries). UPS systems rated for continuous operation at 35
degree C with restrictions for operation at 40 deg C are not acceptable.
2. Storage Temperature: - 25 degrees C to + 55 degrees C . Prolonged storage
above +40 degrees C will cause rapid battery self-discharge.
3. Relative Humidity (operating and storage): 5-95% non-condensing.
4. Elevation:
a. Operational: 1000m maximum without de-rating. De-rate by 1% for every
100m above 1000m, to a maximum of 2000m.
b. Transportation: Capable of air transport, up to 15,000m.
A. The UPS Systems must be fully compliant with IEC 62040-1 with built in back feed
protection
1.9 WARRANTY
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
D. Manufacturer shall also include Start-up services consisting of: 5x8 Start-up service of
UPS and batteries, with option for 7x24 Start-up. On-site user training, Site Audit,
installation and commissioning of monitoring service, and validation of one-year limited
factory warranty will be performed during the start-up.
E. Manufacturer shall also offer an optional service plan to provide 7x24 on-site coverage
(preventive and corrective) for UPS and batteries, guaranteed response time, remote
monitoring, Web access to service site history, annual Site Audit, UPS and battery
preventive maintenance visit, and discounts on upgrade and modification kits.
Manufacturer shall also provide an optional battery service plan to provide parts-and-
labour coverage for partial and full battery strings, either with preventive maintenance or
replacement coverage.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Fuses: One for every 10 of each type and rating, but not less than 1 of each.
2. Cabinet Ventilation Filters: One complete set.
KEO/19-3262-0000 26 3353/4 Static Uninterruptible Power Supply
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. One spare circuit board for each critical circuit.
4. Tools required for maintenance.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
B. Monitoring and control components: The following components shall provide monitor
and control capability:
1. Control panel: Colour LCD, Touch sensitive, with separate LED status indicators.
2. Alarm and metering display.
3. Building alarm monitoring.: ModBUS TCP
4. Communication ports: RS-232 and USB.
C. Battery management system: The UPS shall contain a battery management system
which has the following features:
1. The battery management system shall charge the batteries using an intermittent
charging cycle. The active battery charger states are constant-current (charge
mode), constant-voltage (float mode) and no-charge (rest mode). The charge
mode shall equalise and charge the batteries to near full capacity before entering
into float mode. In float mode a constant voltage float charge shall charge the
batteries for a minimum of 48 hours or until the batteries are fully charged. The
batteries are then put into rest mode. The battery shall be monitored whilst in rest
mode and the charge cycle shall automatically re-start should the battery voltage
drop below pre-determined levels. The charging control system shall activate an
alarm should the battery capacity drop below the pre-determined levels. The
charge cycle will automatically restart after a utility disturbance. The batteries
shall not be physically disconnected from the UPS DC bus during the charge
cycle and shall be available at all times to supply the inverter.
2. The battery management system shall automatically test the battery string(s) to
ensure that the battery is capable of providing greater that 80% of its rated
capacity. Testing the batteries shall not jeopardise the operation of the critical
load. Upon detection of the battery string(s) not capable of providing 80%, the
UPS system will alarm that the battery needs attention/replacement. The battery
test shall be able to detect the following:
KEO/19-3262-0000 26 3353/6 Static Uninterruptible Power Supply
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
a. Open battery string
b. Shorted battery string
c. Battery capacity (runtime) less than 80% of “new” battery capacity
D. Wiring Terminals: The UPS module shall contain terminals (adequately sized to
accommodate 90C wiring) for securing user wiring to the following locations:
1. Rectifier/charger input connections (4-wire plus ground)
2. Bypass input connections (4-wire plus ground, 400Vac)
3. DC link connections for battery cabinets (positive and negative plus ground).
4. AC output connections (4 wire plus ground)
B. For parallel UPS systems provide redundant load sharing mechanisms between
individual UPS systems to mitigate risk of loss of communication.
1. The redundant UPS system configuration must be fault tolerant without single
point of failure.
2. The load sharing between the UPS systems in the parallel configuration should
not be dependent on the parallel communication link.
3. Even in case of failure of the parallel communication cables or communication
interfaces, the UPS modules should continue to share the load equally, even if
the output load conditions change or loss of mains power occurs.
4. The load must be shared between the power modules within a UPS System in
single or parallel configuration
5. In the event of a parallel system communication error, when the UPS systems
are healthy , it must be possible to reinstate the parallel communication and
bring the installation to “ NORMAL OPERATION” without shutting down the UPS
systems forming the parallel configuration
A. The UPS system shall consist of the following options and accessories as required:
B. Network Adapter and UPS Power Monitoring Software: Optional PX Gateway card
adapter shall provide a communications interface between the UPS module and the
following network management systems.
1. SNMP v.1, v.3
2. Modbus TCP
3. BACnet/WS or /IP
4. IPv6
This capability shall allow the unit to be monitored remotely over an Ethernet network
using a standard web browser.
C. UPS Power Monitoring Software: This system shall continuously monitor critical power
elements associated with the UPS, using the communications port on each module and
a customer furnished PC. The system shall automatically alarm if any problems arise
KEO/19-3262-0000 26 3353/7 Static Uninterruptible Power Supply
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
and notify local or remote personnel of the alarm condition via email, page, or text
message
D. Relay Card: Serial dry contact card providing 4 isolated dry output contacts, 1 isolated
input.
E. Battery Cabinet: The battery cabinet shall feature valve regulated, high-rate discharge,
lead-acid batteries which provide energy to the support the critical load during a
momentary loss of input power to the rectifier. The batteries shall be flame retardant in
accordance with UL 94V2 requirements. The battery cabinet shall have the following
features:
1. The battery cabinet shall be the same depth and height as the UPS module.
2. The battery cabinet shall feature a mechanical enclosure of like appearance to
the UPS module and shall feature wheels. Each battery cabinet shall require
front access only for installation, service and maintenance. The battery cabinet
shall provide bottom or side cable entry.
3. Power wiring internal to each battery cabinet shall be factory provided. Each
battery cabinet shall feature up to 6 battery trays. Each battery tray shall be
firmly secured to the battery cabinet frame with fasteners. Each battery tray shall
be removable from the front of the battery cabinet.
4. Each battery cabinet shall feature a DC rated circuit breaker. The circuit breaker
within the battery cabinet shall only provide protection to the battery string within
that battery cabinet. For battery configurations involving multiple battery
cabinets, a battery string in one battery cabinet may be isolated from the DC link
via its circuit breaker without removing other battery strings from the DC link and
the UPS module.
5. The circuit breaker in each battery cabinet shall feature an A/B auxiliary switch.
The UPS module shall be capable of monitoring and alarming an open battery
cabinet circuit breaker condition.
6. The circuit breaker in each battery cabinet shall feature a 24VDC or 48VDC
shunt trip device. The shunt trip shall operate to trip the battery breaker(s) for an
emergency power off command or battery disable command.
7. Power and Control wiring between the co-located battery cabinet and the UPS
shall be factory provided with compression type connectors between cabinets.
8. Expected battery life: 10 year standby design life at 25oC or 200 complete full
load discharge cycles, whichever occurs first, when operated and maintained
within specifications.
9. Appropriately designed open rack system also shall be accepted.
B. Rectifier/charger input:
1. Nominal three phase input voltage: 400 Vac:
2. 4-wire plus ground
3. Operating input voltage range: +20%, -15% of average nominal input voltage at
full load and +20%, -40% of average nominal input voltage at half load without
battery discharge.
KEO/19-3262-0000 26 3353/8 Static Uninterruptible Power Supply
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4. For 50Hz systems, operating input frequency range shall be 45 to 65Hz.
5. Input power factor 0.99 lagging.
6. Normal input current limit: The UPS shall have the following programmable input
current limit settings while operating in normal mode:
a. Rectifier/charger input current limit shall be adjustable from 100 to 115%
of full-load input current.
b. Battery input current limit shall be adjustable from 5% to 7% of the UPS
full load input current regardless of the actual load on the UPS.
7. On generator input current limit: The UPS shall have the following
programmable input current limit settings while operating in normal mode on
generator:
a. Rectifier/charger input current limit shall be adjustable from 100% to 115%
of full-load input current.
b. Battery recharge input current limit shall be adjustable from 5% to 7% of
the UPS full load input current regardless of the actual load on the UPS.
8. Input current total harmonic distortion (THD) shall be less than 3% at nominal line
voltage and 5% nominal source impedance.
9. Power walk-in: Ramp-up to full utility load adjustable from 10 amps per second
to 1 amp per second.
C. Bypass input:
1. Synchronising bypass voltage range shall be +10, -15% of average nominal input
voltage.
2. Synchronising bypass frequency range is +/- 0.5hz to +/-4hz, user adjustable,
and is centred on the nominal frequency. Default setting is +/- 4hz.
3. Slew rate: 1hz per second, maximum.
4. Bypass and rectifier inputs can be supplied from out of phase sources if required.
5. Input surge withstand capability: The UPS shall be in compliance with IEEE 587
(ANSI C62.41), category A & B (6kV).
D. Rectifier/charger output:
1. Nominal DC voltage shall be either 486VDC (432 VDC open circuit battery
voltage) or either 540VDC (480 VDC open circuit battery voltage).
2. Steady state voltage regulation shall be +/- 0.5%.
3. Voltage ripple shall be less that 0.5% (peak-to-peak).
4. Capacity: The rectifier/charger shall support a fully loaded inverter and recharge
the battery to 90% of its full capacity within 10 times the discharge when input
current limit is set at maximum.
5. Low line operation: The rectifier/charger shall be capable of sharing the DC load
with the battery when the input voltage falls below the specified operation input
voltage range, the On Battery indicator shall enunciate operation in this mode.
6. DC sensing: Redundant DC voltage sensing methods shall be incorporated for
providing battery over-voltage protection.
7. Battery charger characteristics: The UPS battery charging system shall have the
following characteristics:
a. The charger shall be capable of being configured for several charge
modes including:
1) A charging mode that increases battery life by allowing the battery
to rest, reducing positive plate corrosion
KEO/19-3262-0000 26 3353/9 Static Uninterruptible Power Supply
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2) A charging mode floating the battery at a set level, which can be
adjusted via software, used for flooded cell applications
a) Nominal Float Voltage: 2.25 V per cell.
b) Equalising Voltage: 2.38 V maximum per cell (adjustable).
b. UPS module will automatically adjust battery shutdown based upon
loading and battery capacity.
1) The UPS module shall automatically adjust the final discharge
voltage between 1.67 and 1.75 Volts per cell based on the existing
load and the rate and length of discharge.
2) The absolute minimum operational voltage is 1.67 V per cell
(adjustable).
F. Battery
1. Each UPS System shall have a single battery bank compatible with N
configuration.
2. Battery bank shall consist of sufficient number of strings in parallel. Each battery
bank shall be rated to carry full load for 60 minutes at 25 degree C
G.
A. Enclosures: The UPS shall be housed in a free-standing double front enclosure (safety
shields behind door) equipped with wheels and levelling feet. The enclosure shall be
designed for critical applications. The front door shall have a lock to prevent
unauthorised entry.
1. The UPS enclosure dimensions shall not exceed:
a. 50kW to 150kW systems (or systems scalable to 100kW or 150kW) shall
measure 560mm Wide , 914mm Deep x 1876mm High.
b. 160kW and 200kW (or systems scalable to 200kW) shall measure 760mm
Wide , 914mm Deep x 1876mm High.
KEO/19-3262-0000 26 3353/11 Static Uninterruptible Power Supply
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
c. 300 kW (or systems scalable to 450 kW) shall measure 1890mm Wide ,
880mm Deep x 1880mm High.
d. 600 kW (or systems scalable to 1100 kW) shall measure 4450mm Wide ,
880mm Deep x 1880mm High.
C. Ventilation: The UPS and shall be designed for forced-air cooling. Air inlets shall be on
the front of the unit. Air outlet configuration for the UPS shall be exhaust at the rear of
the cabinet. 200mm of clearance shall be required for proper air circulation at the rear
of the UPS. A washable air filter shall be mounted in the front door of the UPS module.
An optional rear chimney attachment shall enable front to top ventilation if required.
D. No back or side clearance or access shall be required for servicing the system. The
side enclosure covers shall be capable of being located directly adjacent to a wall.
E. Front access: All serviceable subassemblies shall be modular and capable of being
replaced from the front of the UPS (front access only required). Side or rear access for
installation, service, repair or maintenance of the UPS system shall not be required.
F. Service area requirements: The system shall require no more than 900mm of front
service access room and shall not require side or rear access for service or installation.
A. Microprocessor controlled circuitry: The UPS controls shall have the following design
and operating characteristics:
1. Fully automatic operation of the UPS shall be provided through the use of
microprocessor controlled Digital Signal Processing. DSP shall eliminate
variances from component tolerance or drift, and provide consistent operational
responses.
2. All operating and protection parameters shall be firmware controlled, thus
eliminating a need for manual adjustments. The logic shall include system test
capability to facilitate maintenance and troubleshooting. Periodic maintenance
reminders shall be communicated to the User via the front panel display. Printed
circuit board replacement shall be possible without requiring calibration.
3. Start-up and transfers shall be automatic functions.
B. Digital Front Panel Display: The UPS control panel shall be a 7” touch sensitive, backlit
LCD front panel display that includes LED indicators for basic UPS status. Large,
luminous, colour coded LED pillars (vertical bars) shall show the UPS status (green,
amber, red), and be clearly visible up to 30m from the UPS. The LCD shall display:
1. UPS status (home screen): the LCD screen shall have a colour coded border
(header) that turns red on alarm, and shows basic UPS status in the header of
the display, visible at all times. The header shall alternately show UPS status
output voltage and battery time remaining, and be visible constantly in all display
screens. The home screen shall show load level, average efficiency, and power
consumption in kWh. The home screen shall show a system mimic diagram with
a colour-highlighted power path, operating mode, and active events.
KEO/19-3262-0000 26 3353/12 Static Uninterruptible Power Supply
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Controls tab: Single button controls for turning the UPS on and off, transfer
to/from bypass, and enabling or disabling the battery charger, initiating a battery
test, and enabling or disabling Energy Saver System (ESS).
3. Metering tab: The metering screen shall show voltages currents, temperatures,
kW, kVA, and power factor (as applicable) for the UPS input, output, bypass
source, and battery. Colour coded (green, amber, red) bar graph indicators will
accompany power and temperature measurements
4. Logs tab: alarm/event queue, active alarms and alarm history, events, status
changes and commands, all timed to the 1/1000th second for tracking and
analysis.
5. Statistics tab: Numerically and graphically displays the savings afforded by ESS
operation over time in kWh.
6. Settings tab: shall provide button access to user adjustable settings such as, but
not limited to: date/time, building alarm designations, communications parameter
setup, UPS name, user passwords, and display language.
C. Control Panel Lamp Indicators: The UPS control panel shall provide the following
monitoring functions with indicator (icon) LED’s:
1. NORMAL: This green LED shall indicate that the commercial AC utility or
generator source is supplying power to the rectifier and the inverter is supporting
the critical load.
2. BYPASS: This amber LED shall indicate that the UPS has transferred the load
to the bypass circuit.
3. BATTERY: This amber LED shall indicate that the commercial AC utility or
generator source has failed and the battery is supplying power to the inverter,
which is supporting the load.
4. ALARM: This red LED and the accompanying audible alarm horn, shall indicate
that the UPS detects an alarm condition, outlined in detail in the Logs tab from
the home screen and in the operator’s manual.
D. Interface panel: The UPS shall be equipped with an interface panel, located behind a
protective cover, which provides the following signals and communication features in a
Class 2 environment:
1. Alarm contact: A dry contact for annunciating a summary alarm shall be
provided for customer use. This contact shall be Form “C” capable of supplying
both N/O and N/C contacts. Contact ratings shall be 5A max at a voltage not to
exceed 28VDC or 277VAC.
2. RS232 (EIA / TIA-232) and USB communications interfaces: Circuitry shall be
provided for one “host”, and one “device” USB connector, and one RS232 (EIA /
TIA-232) communication port for connection to automated service department
diagnostic tools. This port may be used with simple (“dumb”) terminals to gain
remote access to all unit operation information.
3. Building alarms: Five inputs shall be provided for monitoring the status of
external dry contacts. Building alarms shall be set up through the UPS
configuration mode function on the UPS front panel display or via the RS232
(EIA / TIA-232) port.
4. External Emergency Power Off contacts: Shall be provided to connect an
external remote emergency power off switch to shut down the UPS and de-
energise the critical load. Normally open or normally closed contacts shall be
acceptable.
2.8 COMMUNICATIONS
B. Remote Monitoring:
1. Optional WEB/SNMP communication capabilities will be available for all systems.
2. The UPS shall be able to be monitored remotely via communications devices.
UPS manufacturer shall provide optional communications devices capable of
communicating via various industry standard protocols such as RS232, SNMP,
BACnet and ModBus. Monitoring of UPS status may also be performed through
isolated dry contact Form C relays.
3. The UPS communication capability should be able to integrate into any industry
standard Building Management System (BMS) and/or Network Management
System (NMS). The UPS must also be able to be monitored via any standard
Internet browser.
4. All optional hardware interfaces shall be “Hot-swappable” (UPS maintains power
to critical applications while changing interfaces).
C. Shutdown:
1. There shall be a mechanism that provides graceful, orderly, unattended,
sequential shutdown of one or multiple computers powered by one UPS. This
shutdown shall be performed via in-network or out-of-network means. The order
of shutdown shall be user-defined, allowing the maximisation of runtime on
battery for more critical systems.
2. The UPS shall also be capable of interfacing with an operating system’s built-in
shutdown routine. This shall be done through a cable connection to the
communication interface card.
D. Notification:
1. There shall be a mechanism to send alerts to key personnel via email or SNMP
traps. An alarm notification may also be sent by a network message.
C. Electronic current limiting circuitry and fuses in the Inverter circuit shall provide output
protection.
A. System Configuration:
1. The outputs of the parallel UPS modules shall be connected to the critical bus
within the UPS output distribution switchboard .
2. An external maintenance bypass switch shall be located either in a separate
enclosure or shall be incorporated in the UPS Output distribution board
B. Module Interconnections:
KEO/19-3262-0000 26 3353/14 Static Uninterruptible Power Supply
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. No inter-UPS module signals or control connections shall be required for
balanced UPS module load sharing.
2. No inter-UPS module signals or control connections shall be required for UPS
module selective tripping.
3. This wireless paralleling method shall not rely on information to be shared
between the UPS modules, thereby eliminating the need for inter-UPS module
communications.
4. This wireless selective tripping method shall not rely on information to be shared
between the UPS modules.
5. The external maintenance bypass switch shall include an interlock arrangement
with auxiliary contacts for each UPS module to ensure that each module is
operating on static bypass before the external maintenance bypass switch is
closed.
E. Load Sharing:
1. The UPS shall share the critical load between the UPS modules equally so that
each UPS module’s load is always within 5% of the others.
2. The UPS shall be capable of providing balanced load sharing without any inter-
UPS module connections.
3. Each UPS module shall need to monitor only its own input and output power in
order to remain phase locked with the other UPS modules. This wireless
paralleling method shall not rely on information to be shared between the UPS
modules.
F. Selective Tripping:
1. The UPS shall be able to selectively trip a failed UPS module off-line without any
inter-UPS module connections.
2. Each UPS module shall look only at itself to determine if a UPS module failure
has occurred. If a UPS module failure does occur, the faulty UPS module shall
identify its own internal failure and subsequently remove itself from the critical
bus by instantaneously shutting off the inverter and subsequently opening an
A. Rack Mounted UPS shall be provided and installed in IDF locations as indicated on the
drawings.
B. The UPS shall provide the following minimum performance and features:-
1. Output Power Capacity: 5kVA and 6kVA
2. Technology: On-line double-conversion with Power Factor
Correction (PFC) system
3. Nominal Voltage: 240V
4. Input voltage range: 100-276V
5. Input frequency range: 50/60 Hz +/- 5 Hz
6. Crest Factor: 3.1/90A
7. Efficiency at Full Load: Up to 94% in Online mode,
98% in Hi-Efficiency mode
8. Overload capacity: 102-130% : 120s, 130-150%: 30s,
125-150%: 10s, >150%: 100ms
9. Outputs: Terminal block + 2 controlled groups of 4 IEC
C13 (10A) + 2 IEC C19 (16A)
10. Battery Type: Maintenance-free sealed Lead-Acid leak
proof battery with suspended electrolyte
11. Battery autonomy: 30 minutes
12. Battery management: Temperature compensated charging method,
Automatic battery test and deep discharge
protection
13. Communication: 1 slot for Network-M2, Network-MS, ModBus-
MS
14. Noise level: <46dB
15. Safety: IEC/EN 62040-1, UL 1778 & CSA 22.2 (5 &
6kVA RT only)
16. EMC performance: IEC/EN 62040 -2 , IEC/EN 62040-3
17. Approvals: CE, CB report (TUV)
KEO/19-3262-0000 26 3353/16 Static Uninterruptible Power Supply
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
PART 3 - EXECUTION
3.1 INSTALLATION
3.2 COMMISSIONING
B. The following procedures and tests shall be performed by Field Service personnel
during the UPS start-up:
1. Visual Inspection:
a. Visually inspect all equipment for signs of damage or foreign materials.
b. Observe the type of ventilation, the cleanliness of the room, the use of
proper signs, and any other safety related factors.
2. Mechanical Inspection:
a. Check all the power connections for tightness.
b. Check all the control wiring terminations and plugs for tightness or proper
seating.
3. Electrical Pre-check:
a. Check the DC bus for a possible short circuit.
b. Check input and Bypass power for proper voltages and phase rotation.
c. Check all lamp test functions.
4. Initial UPS Start-up:
a. Verify that all the alarms are in a “go” condition.
b. Energise the UPS module and verify the proper DC, walk-up, and AC
phase on.
c. Check the DC link holding voltage, AC output voltages, and output
waveforms.
d. Check the final DC link voltage and Inverter AC output. Adjust if required.
e. Check for the proper synchronisation.
f. Check for the voltage difference between the Inverter output and the
Bypass source.
g. Optional on site full-load, step-load, and battery discharge tests using
supplier furnished load bank, shall also be offered.
5. Operational Training: Before leaving the site, the field service engineer shall
familiarise responsible personnel with the operation of the UPS. The UPS
equipment shall be available for demonstration of the modes of operation.
3.3 TRAINING
3.4 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Architect/ Engineer for approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
This specification for capacitor banks to improve power factor in low voltage electrical
distribution systems, issued latest by the Ministry of Electricity and Water & Renewable Energy
(MEW), Kuwait, shall govern all government and private sector projects and installations
throughout the State of Kuwait as applicable under the Ministerial Decree No. 5/2010 dated
18th January 2010. The specification and/or any part thereof cannot be altered or amended
without the knowledge of the Ministry of Electricity & Water, Kuwait, and attention is drawn to
all Consumers/Owners, Consultants, Suppliers, Manufacturers and Contractors that while
specifying and making provision for such capacitor banks, the Ministry specification shall be
strictly adhered to in its full extent and the Ministry only will be the sole authority to give the
technical approval. Should there be a need to deviate from and/or to include any specific
requirement for a particular project; a written approval shall be obtained in all cases from the
Ministry of Electricity & Water. The Ministry has the right to take all administrative procedures
and legal implications of the violation of this resolution.
All previous issues of this specification and issue of any part or section thereof are now
obsolete and superseded by this present issue.
A. The equipment required shall be suitable for the electrical distribution systems, the
characteristics of which are:
1. System voltage 11 KV 415 volts.
KEO/19-3262-0000 26 3533/1 Power Factor Correction Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. System Highest Voltage 12 KV 457 volts.
3. Frequency 50 Hz. 50 Hz.
4. Neutral point Earthed solidly or through Solidly earthed
10.5 Ohms resistance.
C. What is mentioned under (i) and (ii) above applies to wherever BSS is mentioned in the
different clauses of this specification.
A. Climatic conditions in Kuwait are rigorous and the summer season during which the
equipment will function under continuous maximum load conditions is long and shall be
considered to fall during the period starting from 15th April till 15th November. The
remainder of the year shall be considered as winter season since autumn and spring
seasons are very short in Kuwait.
C. Provides of high humidity are common and a humidity of 100% has been recorded at 30
degrees centigrade. However, high temperature is normally accompanied with low
humidity. Violent sand and dust storms occur with wind speeds up to 120 Km/hour, and
even on comparatively still days, fine dust is carried in suspension in the atmosphere.
The average rainfall in a year is 15 cms. but this can be concentrated into 2 or 3 severe
downpours.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Spare parts recommended by manufacturer for two years of normal operations.
2. Tools required for maintenance.
PART 2 - PRODUCTS
In addition to the above listed standards, the regulations for electrical installations
issued by the Ministry of Electricity & Water, Kuwait shall also be adhered to.
4. Drawings and Information:
The consumer/owner and/or his consultant or contractor shall prepare and
furnish the following drawings and documents along with their submittal for
approval of the capacitor bank by the Ministry of Electricity & Water.
a. A copy of the load form which has been made available to the Electrical
Installation Department of the Ministry of Electricity & Water.
b. Project’s schematic diagram of the electrical distribution system.
c. Design calculations for KVAR capacity of the capacitor banks in originals
as per the Ministry of Electricity and Water & Renewable Energy (MEW)
practice, duly signed and stamped by the consultant/contractor and
manufacturer.
d. Design calculations for harmonic distortions in originals duly signed and
stamped by the consultant/contractor and manufacturer. A declaration
shall be submitted stating that active harmonic filters will be provided in
case the measurements after installation lead to such requirements.
e. Consultant/Contractor’s study report on the type of electrical load of the
project along with Supplier/Manufacturer’s recommendation on the
suitability of the proposed capacitor bank duly signed and stamped.
f. Manufacturer’s technical brochure/catalogues for various major
components.
g. Dimensional drawings showing constructional details of capacitor banks
with details of all components including schematics for protection and
controls of the capacitor bank.
h. Complete type test reports and certificates for a 400 KVAR capacitor
bank, capacitor units and other major components from independent test
laboratory (ASTA, KEMA or, CESI).
i. Technical manual giving installation, operation and maintenance
instructions
j. Supplier’s/manufacturer’s/contractor’s guarantee on the capacitor banks
in original letterhead for a period of three (3) years from the date of
commissioning for fully satisfactory operation and running of the
equipment and against any manufacturing defect and mal-functioning.
k. Letter of confirmation on the provision of air-conditioning for the
Electrical/LT room wherein the capacitor banks will be installed.
l. Declaration by the manufacturer/local agent that testing and
commissioning of the capacitor banks will be carried out by qualified and
trained manufacturer’s and/or local agent’s engineer/specialist.
m. Original payment receipt along with a copy of the same. Original receipt
will be returned after scrutinizing.
B. CAPACITOR UNITS:
The capacitor units required for the different types of low voltage capacitor banks shall
be Dry or Oil Capacitors, self-healing type with individual discharge resistors and shall
KEO/19-3262-0000 26 3533/5 Power Factor Correction Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
be protected against internal faults, over pressure, etc., and manufactured in full
compliance with and tested to the requirements of the International Electro-technical
Commission Publication No. IEC 60831, Part-1 and Part-2.
1. The capacitor units will be installed in an electrical distribution system having
system voltage of 415 volts (System highest voltage 457 volts) and shall be rated
at 525 volts or higher due to the voltage rise caused by connecting the detuned
series reactors and considering the worst temperature conditions encountered in
Kuwait.
2. The capacitor units shall be of single phase or three phase type.
3. The ambient temperature category of the capacitor units shall be -5/D as a
minimum to IEC Publication No. 60831, Part-1.
4. The capacitance of the capacitor units shall not differ from the rated capacitance
by more than –5 % to +10 % for units and banks up to 100 KVAR and –5 % to +5
% for units and banks above 100 KVAR.
5. The capacitors shall be of the self-healing type and the dielectric for dry capacitor
units shall be from low-loss metallised polypropylene film. The dielectric for oil
capacitor units shall be from double metallised paper and polypropylene or
metallised polypropylene having PCB-free oil impregnation.
6. The dry capacitor units shall be completely leakge proof and of dry type
construction without any filling of jelly, wax, etc.
7. The capacitor element casings for dry capacitor units shall be from Aluminum or
high temperature withstanding nonflammable material and for oil capacitor units
the casings shall be Aluminum.
8. The capacitor units shall have suitable adequate protection to ensure safe
disconnection from the circuit in case of an excessive internal temperature rise
and/or an abnormal increase of the internal pressure either by having an internal
fuse link combined with a secondary solid foil electrode or by an overpressure
disconnector device. The capacitor units with overpressure disconnector device
shall have visual indication for easy identification of damaged units with naked
eye.
9. The capacitors shall have permanently connected built-in discharge resistors to
ensure safe discharge of the capacitors to less than 50 volts in 1 minute after
switch off.
10. The total losses including discharge resistors to be less than 0.5 Watt/KVAR.
11. All exposed terminals and discharge resistors of the capacitor units shall be
adequately shrouded.
12. The capacitors shall be rated for a minimum of 130% continuous current
overload and 110% continuous voltage overload based on the Rated Voltage of
the capacitors.
13. Suitable rating plates from non-corrosive material shall be provided on each
capacitor unit giving fully detailed information as follows:
Capacitor Unit Rating Plate:
a. Manufacturer.
b. Serial number and manufacturing year.
c. Rated total output in kilovars (KVAR)
d. Rated voltage in volts (V).
e. Rated frequency in hertz (Hz).
f. Temperature category and temperature range.
g. Discharge device.
h. Reference of self-healing design.
i. Connection symbol.
j. Internal fuses (if provided).
k. Indication for the overpressure.
l. Insulation level in kilovolts (KV).
KEO/19-3262-0000 26 3533/6 Power Factor Correction Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
m. Reference to IEC 60831 (plus year of issue of the edition).
D. SWITCH-DISCONNECTORS:
1. The capacitor bank shall have a suitably rated switch-disconnector at the
incomer. The switchdisconnector shall be three-pole and shall fully comply with
the requirements of the IEC 60947-1 & 3. The rated insulation voltage of the
switch-disconnector shall be minimum 690 V and it shall be designed for
continuous operation in ambient temperatures of up to 52oC or shall be derated
accordingly. The rated operational current shall be at least 1.5 times the full load
current of the capacitor bank and the rated short time withstand current, 50 kA for
0.5 second. It shall have a class of duty AC-22B. It shall have a rotary front
operating door mounted handle and should be interlocked with the door to
ensure that the capacitor bank is de-energised when door is open.
2. Each stage of the capacitor bank shall have a suitably rated moulded case circuit
breaker (MCCB) or high rupturing capacity (HRC) fuses together with a thermal
magnetic overcurrent relay for overload protection. The circuit breaker and the
thermal magnetic overcurrent relay shall be adjusted to trip if the RMS current of
the stage exceeds 130%.
F. ELECTROMAGNETIC CONTACTOR:
1. The electromagnetic contactors shall be 660 Volts rated, of 3-pole type suitable
for switching 'on' and switching 'off' operations of capacitor banks and shall
comply with the requirements of the IEC 60947-1 & 4-1. The supplier shall
choose a contactor of a suitable operational current rating taking into
consideration the inrush current and the special considerations of capacitor
switching duty. Incidence of higher inrush current in the case of successive
switching of capacitor banks shall also be taken into account. The supplier shall
furnish data sheet of contactor in support of proper selection of the contactor
rating including the making and breaking current ratings. The contactors shall
isolate all three supply phases to the capacitor on switch off.
2. The rated voltage of control coil shall be 415V (phase-to-phase). This voltage is
subject to a variation of (+) 10% and (-) 15%. The contactors shall work
satisfactorily within this voltage range. The pickup voltage of coil shall be 60%
and drop out voltage shall not be more than 50% of rated voltage.
3. The mechanical endurance of the contactors shall not be less than 3 million
operating cycles at no load. The electrical endurance at normal utilization duty for
capacitor shall not be less than 200,000 operations.
4. The contactors shall be subject4d to routine and type tests as described in IEC
60947.
Total Voltage
Individual Voltage
Bus Voltage at PCC Distortion THD
Distortion (%)
(%)
69 kV and below 3.0 5.0
69.001 kV through
1.5 2.5
161 kV
161.001 kV and
1.0 1.5
above
NOTE – High-voltage systems can have up to 2.0% THD
where the cause is an HVDC terminal that will attenuate by
the time it is tapped for a user.
Measurements/Displays:
Notes :
1. In case of i) to iv) above, normal automatic functioning of the capacitor bank will
resume after the specified values in all these cases are maintained for two
minutes.
2. In case of v) above, the Contactor/thyristor will not switch ON again till the fault
condition is attended to.
L. INTERNAL WIRING:
1. All small wiring within the capacitor banks shall be from 600/1000 volts grade, 2.5
sq. mm. single core cables insulated with Type-TI3 PVC as per Table 1, BS EN
50363-3:2005 or XLPE insulated and shall have stranded copper conductors. All
wiring shall be suitably terminated and fitted with identification ferrules and
marked with circuit numbers in accordance with “British Central Electricity
Authority Engineering Recommendations” S-12 standard numbers for small
wiring or similar approved standard. The trip circuits shall have an additional
ferrule coloured red and marked trip.
2. All terminal blocks shall be from an approved design and all exposed terminals
shall be enclosed by detachable covers. The trip circuit cables shall be coloured
black and the instrument transformer cables (C.Ts) coloured with their respective
phase colours. Alternatively, all small wiring can be uniform colour (e.g., grey) but
instrument transformer cables shall have additional coloured ferrules at both
ends of each conductor run (in accordance with their phase colours). The wiring
of the auxiliary circuits shall be segregated from the main circuit by heat resistant
tubes made of insulating material covered by earthed metallic partitions. Terminal
blocks, small wiring terminations, ferrules and wire numbering and colouring shall
be subject to the approval of the Purchaser.
PART 3 - EXECUTION
B. Provision of proper earthing of the metallic enclosure of the capacitor bank shall be
made. The capacitor banks at the Main LV Distribution Boards and Sub-main
Distribution Boards shall be connected to the earth ring bus by 1000 Volts grade cables
of adequate cross-sections.
C. The capacitor bank at the service intake of the consumers shall have an earthing
system consisting of a set of two (2) Nos. 1.5 metres (to make a 3.0 metres long rod) x
19 mm dia. copper bonded earth rods and connected by 1000 Volts grade insulated
cable of 70 sq. mm.. The earth rods are to be installed inside pre-cast hand holes of 30
cm. x 30 cm. clear opening and a depth of 55 cm. provided with a heavy duty concrete
cover to enable checking of the connection and measurement of the earth resistance.
D. The testing and commissioning of the capacitor banks shall always be carried out by
qualified and trained manufacturer’s and/or local agent’s engineer/specialist in full
compliance with the specification.
3.02 TESTS
A. GENERAL:
1. The supplier/manufacturer/contractor of the capacitor banks shall carry out the
tests specified in any applicable International Electro-technical Commission (IEC)
and/or British Standard (BS) Specifications, unless otherwise agreed upon and
such additional tests as in the opinion of the Purchaser or his representative are
necessary to determine that the works comply with the conditions of this
specification.
2. All instrument used for testing purposes, shall be calibrated by an approved
authority and calibration certificates shall be submitted along with the inspection
reports.
3. The test results/readings recorded during measurements and other observations
noted shall be compiled/tabulated separately for each item of equipment and
furnished to the Purchaser in a fully professional manner in three (3) complete
sets. Electronic copies of the reports shall also be submitted in three (3)
complete sets of compact disks (CDs).
Notes:
1. The temperature of the case during the ageing test shall be the maximum
ambient temperature i.e., 55oC plus the difference between the measured
temperature of the case and the cooling air temperature recorded at the end of
the thermal stability test carried out on an identical unit.
2. After placing the capacitor in the unheated enclosure, the thermostat shall be set
at a temperature equal to that as above.
1) Complete Capacitor Banks:
All type tests shall be carried out in an internationally recognized
independent testing laboratory (ASTA, KEMA or CESI) at their
laboratory of country of origin in accordance with the latest issues
of the International Electro-technical Commission (IEC)
Publication Nos. IEC 61921 and IEC 61439-1.
2) Design Verification Tests:
Design verification tests shall be carried out as per IEC 61439-1
to relevant clauses as mentioned against each test and shall
comprise the following:
3) Construction:
a) Strength of materials and parts tests (Cl. 10.2).
b) Degree of protection test for enclosures (Cl 10.3).
c) Clearances and creepage distances (Cl. 10.4).
d) Protection against electric shock and integrity of protective
circuits (Cl. 10.5).
e) Incorporation of switching devices and components (Cl.
10.6).
f) Internal electrical circuits and connections (Cl. 10.7).
g) Terminals for external conductors (Cl. 10.8).
4) Performance:
KEO/19-3262-0000 26 3533/20 Power Factor Correction Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
a) Dielectric properties (Cl. 10.9).
b) Temperature rise (Cl. 10.10.2) (See Notes below)
c) Short-circuit withstand strength (Cl. 10.11).
d) Electromagnetic compatibility (Cl. 10.12).
e) Mechanical operation (Cl. 10.13).
Notes:
1. The temperature rise test shall be carried out by the method of verification by
testing current at an ambient temperature of 52oC with all capacitor units,
detuned series reactors and other components assembled and connected and
injecting full load current.
2. Conditions of Cl. 7.2.1 of IEC 61921 shall apply.
1) Disconnectors, Series Reactors, Thyristors, Electro-magnetic
Contactor, Current Transformers:
Complete type test certificates for all major components, like
MCCBs, Series Reactors, Thyristors, Electro-magnetic Contactor,
Current Transformers, etc. shall be submitted as per the relevant
IEC/BS specifications.
2) Low Voltage Cables:
All type tests shall be carried out in accordance with the latest
IEC Publication No. 60502-1 and supplements.
C. ROUTINE TESTS:
a. All routine tests shall be carried out in accordance with the relevant
IEC/BS specifications. Routine test results shall be produced and must be
available at the time of delivery of the equipment.
1) Individual Capacitor Units:
All routine tests shall be carried out in accordance with the
International Electro-technical Commission (IEC) Publication No.
IEC 60831 as per the relevant clauses mentioned against each
test. Routine tests shall be carried out by the manufacturer on
every capacitor before delivery.
2) Capacitance measurement and output calculation (Cl. 7).
a) Measurement of the tangent of the loss angle (tan δ) of the
capacitor (Cl. 8).
b) Voltage test between terminals (Cl. 9.1).
c) Voltage test between terminals and container (Cl.10.1).
d) Test of the internal discharge device (Cl. 11).
e) Sealing test (Cl. 12).
3) Complete Capacitor Banks:
All routine tests shall be carried out in accordance with the latest
issues of the International Electrotechnical Commission (IEC)
Publication Nos. IEC 61921 and IEC 61439-1. Routine tests shall
be carried out by the manufacturer on every capacitor bank
before delivery.
b. Routine VerificationTests:
Routine verification tests shall be carried out as per IEC 61439-1 to
relevant clauses as mentioned against each test and shall comprise
the following:
1) Construction:
a) Clearances and creepage distances (Cl. 11.3).
b) Protection against electric shock and integrity of protective
circuits (Cl. 11.4).
c) Incorporation of built-in components (Cl. 11.5).
KEO/19-3262-0000 26 3533/21 Power Factor Correction Equipment
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
d) Internal electrical circuits and connections (Cl. 11.6).
e) Terminals for external conductors (Cl. 11.7).
f) Mechanical Operation (Cl. 11.8).
2) Performance:
a) Dielectric properties (Cl. 11.9).
b) Wiring, operational performance and function (Cl. 11.10).
D. SITE TESTS:
All site tests shall be carried out by qualified and trained manufacturer’s and/or
local agent’s engineer/specialist in the presence of and to the satisfaction of the
Purchaser or his representative. The following site tests/inspection shall be
carried out prior to energizing the capacitor banks:
a. Mechanical Tests:
1) Checking of panel conformity to drawing and Engineer’s
requirements.
2) Checking of all devices for proper mounting and all conductors and
cables for proper routing.
3) Checking of creepage and clearance distances.
4) Checking effectiveness of all mechanical devices, e.g. handles,
locks, interlocks, operating devices, etc.
5) Checking of all electrical connections for tightness/surface area
contacts.
6) Checking of Labels, Identifications, Nameplates, Danger Signs,
etc..
7) Checking of installation works of capacitor banks and cabling,
earthing, etc..
8) Checking of capacitor bank enclosure for overall workmanship and
smooth finish.
b. Electrical Tests:
1) Insulation resistance measurements on the buses, phase to phase
and phase to ground, with all breakers in the fully connected
position and contacts open. Insulation resistance shall exceed 10
megaohms.
2) Control circuit insulation resistance to ground.
3) Flash test all main circuit at 2.5 kV for one minute. Leakage current
shall be measured and recorded.
4) Repeat insulation resistance measurements to verify the same has
not been affected by the dielectric test.
5) Primary and secondary injection tests of all relays, CT’s and
indicating and metering instruments.
c. Functional Tests:
1) Functional test of all circuit breakers, switches, contactors, relays,
etc. and every circuit to verify correct operation.
2) Operate the equipment through all design functions, including
remote operation, actuation of alarm and indicating devices,
mechanical and electrical tripping and closing, and operation of the
protective devices.
3) Inspect all relays and protective devices, and verify settings in
accordance with the manufacturer’s instructions.
E. GUARANTEES
The supplier/manufacturer/contractor of the capacitor banks shall submit the following
guarantees:
1. Guarantee that all the capacitor banks and all parts and components thereof like,
capacitor units, series reactors, thyristor switched contactors, electromagnetic
contactors, power factor controllers, power quality meters, current transformers,
switch-disconnectors, MCCBs, Fuses, thermal magnetic overcurrent relays, etc.,
will give continuous trouble free service at Kuwait’s extreme ambient temperature
(52 deg C) and weather conditions (100% RH), and any capacitor bank and/or
any parts/components thereof that will fail, malfunction or burn out within a period
of three (3) years will be replaced and reinstalled free of charge.
2. The supplier/manufacturer/contractor shall further guarantee fully satisfactory
operation and running of the entire equipment for a period of three (3) years from
the date of commissioning.
Note:
1. The above guarantees shall be submitted by the manufacturer and/or local agent
on their original letterhead indicating the serial number of the capacitor bank(s)
duly signed and stamped by the manufacturer and/or local agent and the
contractor.
3.03 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular
inspection and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
END OF SECTION
TRANSFER SWITCHES
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes transfer switches rated 600 V and less, including the following:
1. Furnish and install automatic transfer & bypass-isolation switch (ATS/BPS)
system(s) with number of poles, amperage, voltage, withstand and close-on
ratings as shown on the plans. Each automatic transfer shall consist of an
inherently double throw power transfer switch mechanism and a microprocessor
controller to provide automatic operation. All automatic transfer & bypass-
isolation switches and controllers shall be the products of the same
manufacturer.
2. Bypass/isolation switches.
3. Remote annunciation systems.
4. Remote annunciation and control systems.
1.03 SUBMITTALS
A. Product Data: For each type of product indicated. Include rated capacities, weights,
operating characteristics, furnished specialties, and accessories.
B. Shop Drawings: Dimensioned plans, elevations, sections, and details showing minimum
clearances, conductor entry provisions, gutter space, installed features and devices, and
material lists for each switch specified.
1. Single-Line Diagram: Show connections between transfer switch,
bypass/isolation switch, power sources, and load; and show interlocking
provisions for each combined transfer switch and bypass/isolation switch.
C. Operation and Maintenance Data: For each type of product to include in emergency,
operation, and maintenance manuals. In addition to items specified in Division 01
Section "Operation and Maintenance Data," include the following:
1. Features and operating sequences, both automatic and manual.
2. List of all factory settings of relays; provide relay-setting and calibration
instructions, including software, where applicable.
KEO/19-3262-0000 26 3600/1 Transfer Switches
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
D. Manufacturer Seismic Qualification Certification: Submit certification that capacitor
equipment will withstand seismic forces defined in Division 26 Section “Vibration and
Seismic Controls for Electrical Systems.” Include the following:
1. Basis of Certification: Indicate whether withstand certification is based on actual
test of assembled components or on calculation.
2. The term “withstand” means “the unit will remain in place without separation of
any parts from the device when subjected to the seismic forces specified.”
3. The term “withstand” means “the unit will remain in place without separation of
any parts from the device when subjected to the seismic forces specified and the
unit will be fully operational after the seismic event.”
4. Dimensioned Outline Drawings of Equipment: Identify center of gravity and locate
the describe mounting and anchorage provisions.
5. Detailed description of equipment anchorage devices on which the certification is
based and their installation requirements.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
1.07 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. One percent minimum plus two replacements for each specialized part.
2. Tools required for maintenance.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
A. The transfer switch shall be electrically operated and mechanically held. The electrical
operator shall be a momentarily energized, single-solenoid mechanism. Main operators
which include overcurrent disconnect devices, linear motors or gears shall not be
acceptable. The switch shall be mechanically interlocked to ensure only two possible
positions, normal or emergency.
KEO/19-3262-0000 26 3600/3 Transfer Switches
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. All transfer switch sizes shall use only one type of main operator for ease of
maintenance and commonality of parts.
C. The switch shall be positively locked and unaffected by momentary outages, so that
contact pressure is maintained at a constant value and contact temperature rise is
minimized for maximum reliability and operating life.
D. All main contacts shall be silver composition. Switches rated 800 amperes and above
shall have segmented, blow-on construction for high withstand and close-on capability
and be protected by separate arcing contacts.
E. Inspection of all contacts shall be possible from the front of the switch without
disassembly of operating linkages and without disconnection of power conductors.
Switches rated 600 amps and higher shall have front removable and replaceable
contacts. All stationary and moveable contacts shall be replaceable without removing
power conductors and/or bus bars.
G. Neutral conductors shall be provided with fully rated overlapping neutral transfer
contacts. The neutrals of the normal and emergency power sources shall be connected
together only during the transfer and retransfer operation and remain connected
together until power source contacts close on the source to which the transfer is being
made. The overlapping neutral contacts shall not overlap for a period greater than 100
milliseconds. Neutral switching contacts which do not overlap are not acceptable.
H. Where neutral conductors are to be solidly connected as shown on the plans, a neutral
conductor plate with fully rated AL-CU pressure connectors shall be provided.
A. A two-way bypass-isolation switch shall provide manual bypass of the load to either
source and permit isolation of the automatic transfer switch from all source and load
power conductors. All main contacts shall be manually driven.
B. Power interconnections shall be silver-plated copper bus bar or tinned bus bar. The
only field installed power connections shall be at the service and load terminals of the
bypass-isolation switch. All control inter-wiring shall be provided with disconnect plugs.
C. Separate bypass and isolation handles shall be utilized to provide clear distinction
between the functions. Handles shall be permanently affixed and operable without
opening the enclosure door. Designs requiring insertion of loose operating handles or
opening of the enclosure door to operate are not acceptable.
F. When the isolation switch is in the "Test" or "Open" mode, the bypass switch shall
function as a manual transfer switch.
G. Designs requiring operation of key interlocks for bypass isolation or ATSs which cannot
be completely withdrawn when isolated are not acceptable.
A. The controller’s sensing and logic shall be provided by a single built-in microprocessor
for maximum reliability, minimum maintenance, and the ability to communicate serially
through an optional serial communication module.
B. A single controller shall provide twelve selectable nominal voltages for maximum
application flexibility and minimal spare part requirements. Voltage sensing shall be true
RMS type and shall be accurate to 1% of nominal voltage. Frequency sensing shall
be accurate to 0.2%. The panel shall be capable of operating over a temperature
range of -20 to +60 degrees C and storage from -55 to +85 degrees C.
D. All customer connections shall be wired to a common terminal block to simplify field-
wiring connections.
E. The controller shall meet or exceed the requirements for Electromagnetic Compatibility
(EMC) as follows:
1. EN 55011:1991 Emission standard - Group 1, Class A
2. EN 50082-2:1995 Generic immunity standard, from which:
3. EN 61000-4-2:1995 Electrostatic discharge (ESD) immunity
4. ENV 50140:1993 Radiated Electro-Magnetic field immunity
5. EN 61000-4-4: 1995 Electrical fast transient (EFT) immunity
6. EN 61000-4-5:1995 Surge transient immunity
7. EN 61000-4-6:1996 Conducted Radio-Frequency field immunity
2.05 ENCLOSURE
KEO/19-3262-0000 26 3600/5 Transfer Switches
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
A. The ATS/BPS shall be furnished in a Type 1 enclosure unless otherwise shown on the
plans.
B. All standard and optional door-mounted switches and pilot lights shall be 16-mm
industrial grade type or equivalent for easy viewing & replacement. Door controls shall
be provided on a separate removable plate, which can be supplied loose for open type
units.
2.06 OPERATION
C. Time Delays
1. An adjustable time delay of 0 to 6 seconds shall be provided to override
momentary normal source outages and delay all transfer and engine starting
signals. Capability shall be provided to extend this time delay to 60 minutes by
providing an external 24 VDC power supply.
2. A time delay shall be provided on transfer to emergency, adjustable from 0 to 60
minutes, for controlled timing of transfer of loads to emergency.
3. Two time delay modes (which are independently adjustable) shall be provided on
re-transfer to normal. One time delay shall be for actual normal power failures
and the other for the test mode function. The time delays shall be adjustable
from 0 to 60 minutes. Time delay shall be automatically bypassed if the
emergency source fails and the normal source is acceptable.
4. A time delay shall be provided on shut down of engine generator for cool down,
adjustable from 0 to 60 minutes.
5. A time delay activated output signal shall also be provided to drive an external
relay(s) for selective load disconnect control. The controller shall have the ability
to activate an adjustable 0 to 5 minute time delay in any of the following modes:
a. Prior to transfer only.
b. Prior to and after transfer.
c. Normal to emergency only.
d. Emergency to normal only.
e. Normal to emergency and emergency to normal.
f. All transfer conditions or only when both sources are available.
6. The controller shall also include the following built-in time delays for optional
Closed Transition and Delayed Transition operation:
a. 1 to 5 minute time delay on failure to synchronize normal and emergency
sources prior to closed transition transfer.
b. 0.1 to 9.99 second time delay on an extended parallel condition of both
power sources during closed transition operation.
c. 0 to 5 minute time delay for the load disconnect position for delayed
transition operation.
7. All time delays shall be adjustable in 1 second increments, except the extended
parallel time, which shall be adjustable in .01 second increments.
8. All time delays shall be adjustable by using the LCD display and keypad or with a
remote device connected to the serial communications port.
D. Additional Features
1. A three position momentary-type test switch shall be provided for the test /
automatic / reset modes. The test position will simulate a normal source failure.
The reset position shall bypass the time delays on either transfer to emergency
or retransfer to normal.
2. A SPDT contact, rated 5 amps at 30 VDC, shall be provided for a low-voltage
engine start signal. The start signal shall prevent dry cranking of the engine by
requiring the generator set to reach proper output, and run for the duration of the
cool down setting, regardless of whether the normal source restores before the
load is transferred.
3. Auxiliary contacts, rated 10 amps, 250 VAC shall be provided consisting of one
contact, closed when the ATS is connected to the normal source and one contact
closed, when the ATS is connected to the emergency source.
At the end of the specified duration the switch shall transfer the load back
to normal and run the generator for the specified cool down period. A 10-
year life battery that supplies power to the real time clock in the event of a
power loss will maintain all time and date information.
7. The following feature shall be built - into the controller, but capable of being
activated through keypad programming or the communications interface port.
Note: The transfer switch will operate in a non-automatic mode with this feature
activated.
a. Terminals shall be provided for a remote contact which opens to signal
the ATS to transfer to emergency and for remote contacts which open to
inhibit transfer to emergency and/or retransfer to normal. Both of these
inhibit signals can be activated through the keypad or serial port.
b. System Status - The controller LCD display shall include a “System
Status” screen which shall be readily accessible from any point in the
menu by depressing the “ESC” key a maximum of two times. This screen
shall display a clear description of the active operating sequence and
switch position. For example,
1) Normal Failed
2) Load on Normal
3) TD Normal to Emerg
KEO/19-3262-0000 26 3600/8 Transfer Switches
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4) 2min15s
C. Service Representation
1. The ATS/BPS manufacturer shall maintain a national service organization of
company-employed personnel located throughout the contiguous United States.
The service center's personnel must be factory trained and must be on call 24
hours a day, 365 days a year.
2. The manufacturer shall maintain records of each switch, by serial number, for a
minimum of 20 years.
PART 3 - EXECUTION
3.01 INSTALLATION
3.02 CONNECTIONS
A. Wiring to Remote Components: Match type and number of cables and conductors to
control and communication requirements of transfer switches as recommended by
manufacturer. Increase raceway sizes at no additional cost to Owner if necessary to
accommodate required wiring.
E. Report results of tests and inspections in writing. Record adjustable relay settings and
measured insulation and contact resistances and time delays. Attach a label or tag to
each tested component indicating satisfactory completion of tests.
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Engineers review outlining all deficiencies and
course of action. The contractor shall ensure all deficiencies outlined are rectified,
retested, and certified.
3.05 TRAINING
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the lightning protection installation shall consist of air termination
network, down conductors, earthing and bonding to prevent side flashing.
1.3 SUBMITTALS
C. Qualification data for firms and persons specified in "Quality Assurance" Article to
demonstrate their capabilities and experience.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
1.6 COORDINATION
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Spare parts recommended by manufacturer for two years of normal operations.
Contractor shall provide a list of spare part as part of Tender submission
2. Tools required for maintenance.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
PART 2 - PRODUCTS
2.1 MANUFACTURERS
B. The Specialist Lightning Protection Installer shall submit the Risk Evaluation for R1 and
R2 and the achieved Lightning Protection Level (LPL) calculation based on BS EN
62305 - Part 2. SIRAC is not allowed. In the absence of such an evaluation,
employment of LPL - I will be deemed mandatory. The Specialist Lightning Protection
Installer shall then submit the shop drawings based on the achieved LPL and shall
employ the air termination network consisting of mesh of either 5m x 5m or less, in co-
ordination with rolling sphere (size as per the protection level). All the service entries to
the structure i.e. power line, telecom line, gas line, water line etc. shall be protected by
installing current surge protectors (either 25KA or 18.75KA or 12.5 KA rating, tested on
10/350µs wave form), depending on the Lightning Protection Level (LPL) to be used to
R
bring down the risk (R) below the tolerable risk level ( T ). Also based on the R2
calculation, the Type 2 over voltage SPDs must be installed in the downstream
Distribution boards.
A. The Specialist Lightning Protection Installer shall use 25x3 mm bare copper tape of
99.99% purity (complying with BS EN 13601), (or PVC coated as the case may require,
complying with the same) to form the air-termination mesh on the uppermost part of the
structure (typically the roof) and ring conductor around the structure (the spacing
between the ring conductors shall depend on the size of the rolling sphere) to prevent
from side flashes.
B. Air termination network should be extended and it’s determined by using rolling sphere
method.
D. Typically, if LPL I is employed, then the first horizontal conductor shall be at 20m level
(from ground). From 20m to 120m, horizontal conductors shall be installed at every 20
meters or every 5 floors. From 120m up to 400 meters, horizontal conductors shall be
installed at every 10 meters or every 3 floors, from 400 meters and above, the horizontal
conductors shall be installed at every 5 meters or every floor. However, if the structure is
more than 120m in height then the top 20% of the building height is protected using ring
conductors every floor and then follow the above rule.
E. Based on the above the Specialist Lightning Protection Installer shall use 25x3mm
copper tape as ring conductor and this tape should be bonded to all down conductors
around the periphery and a branch conductor to be taken horizontally and all these
down conductors to be bonded to the aluminum cladding wall using bi-metallic clamps.
F. Any roof (e.g. staircase) on top of the main roof shall have air termination network and it
shall be connected to lower roof network.
G. All the fixing clips for the copper tape shall be metallic (complying with Class ‘H’ of the
electrical testing based on BSEN 50164) and shall be fixed at an interval of 500mm
(1000 mm fixing distance for fixing conductors on vertical surface up to 20m from the
ground level and on the horizontal surface i.e. roof).
H. The vertical terminals shall be installed to protect any equipment on the roof above the
air termination network at a calculated separation distances'. The zone of protection
accorded by the air terminal must be in accordance with the BSEN 62305 - part III of the
standard. The service lines from these equipment going inside the structure must be
bonded using either a Type 2 Over voltage SPD (surge protection device) or a Type 1
SPD, depending on the achievement of the separation distance 's'.
I. Refer lightning protection system layout drawings for the details of air termination
network. All air terminals shall be rigidly bonded together with the air termination copper
tape at the roof.
A. The down conductors shall be placed around the periphery of the building. The number
and spacing of the down conductors shall be in accordance to the risk assessment
carried out as per the BSEN 62305 – part II. A minimum of two dedicated re-enforcing
bars shall be used as down conductors in each column. The minimum overlap
dimension to connect two re-bars shall be at least 20 times the diameter of the re-bar. If
it not practical to arc-weld two re-bars then suitable clamps should be used at a distance
of each 10cm till the above dimension is achieved. Re-enforcement bars in the
designated columns should be used as down conductors, with a suitable junction box to
be recessed at approx. 500mm above the ground for the test link..
B. The composite glass panel shall be bonded to all the down conductors at the various
slab levels as per the rolling sphere spacing by using bi-metallic clamps complying to
BSEN 50164.
C. The electrical continuity of the reinforcing bars shall be determined by electrical testing
between the uppermost part and the ground level. The overall electrical resistance
KEO/19-3262-0000 26 4113/4 Lightning Protection For Structures
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
should not be greater than 0.2Ω, measured using test equipment suitable for this
purpose. If this value is not achieved, or it is not practical to conduct such testing, the
reinforcing bar shall not be used as a natural down conductor.
A. Sufficient number of earth electrodes shall be installed with proper hand hole and cover,
outside the building periphery or within the building Basement as shown on the drawing
and connected to related down conductor. Every down conductor shall be connected to
an earth electrode via test link in accordance with BSEN 62305 (Part I – IV) and every
electrode shall be interconnected with a perimeter ring conductor as part of the
integrated earthing system. The earthing shall be done as per local authorities
requirements. A minimum of 3000 mm solid copper electrode shall be provided with
each down conductor separately. However, the contractor shall submit the calculation
for deciding the number of earth rods in each earth pit. Wherever the soil resistivity is
low (typically below <50 Ωm), the contractor must use either solid copper rods or
stainless steel rods to ensure the longitivity of the earth termination network.
B. The complete Lightning Protection System measured at any point, should not exceed 10
ohms. With the test clamp disconnected, the resistance of each individual earth should
be no more than ten times the number of down conductors in the complete system.
D. The terminated head of each electrode shall be located in a light weight inspection pit. If
clear earth is not available, then the Specialist Lightning Protection Installer has to install
the earth pit inside the building using specially designed earth electrode seals. Where a
rod type earth electrode and inspection pit are to be installed inside a building making it
necessary that the foundation slab and therefore the water proof membrane be
penetrated, the Specialist Lightning Protection Installer or Contractor shall ensure the
building is protected against ingress of water through installation of an appropriate earth
rod seal.
E. The earth rod seal selected shall meet the requirements of IEC 62561-5, be designed
for use in concrete slabs of nominal thickness from 300 mm to 3000 mm and be capable
of withstanding water pressure up to 80 psi (5.5 Bar).
F. The earth rod seal shall provide an effective, reliable and watertight seal to both the
earth rod electrode and damp proof membrane. For best practice installation, an earth
rod seal capable of sealing the damp proof membrane between upper and lower
flanges.
G. Provide a concrete pit (outside the building)/Polymer pit (within the building Basement)
complete with a heavy duty concrete cover (outside the building) or Polymer cover
(within the building Basement) with recessed lifting hook to the Engineers written
approval, at the head of the earth rod, to protect the rod and allow access to
connections for testing.
A. The Specialist Lightning Protection Installer shall install suitable surge protectors at local
power distribution boards feeding vulnerable equipment, in order to protect these
B. Type 2 and Type 3 Protectors shall be tested in accordance with the requirements of:
1. BS EN 62305:2011 – Electrical & Electronics Systems Protection within
structures (Part 4),
2. BS 2914:1972 ‘Specification for surge diverters for alternating current power
circuits’,
3. IEEE C62.41-1991 ‘Recommended practice on surge voltages in low voltage AC
power circuits’.
C. Protectors for a given Location Category shall be rated for a High Exposure Level (as
defined by BS EN 62305 - 4), unless contrary information is available.
D. The protector must not interfere with or restrict the system’s normal operation. It should
not:
1. corrupt the normal mains power supply
2. break or shutdown the power supply during operation
3. have an excessive earth leakage current.
E. The protector shall be rated for a peak discharge current of no less than 10kA (8/20µs
waveform) between any two conductors (phase to neutral, phase to earth and neutral to
earth).
F. The protector shall limit the transient voltage to below equipment susceptibility levels.
Unless otherwise stated, the peak transient let-through voltage shall not exceed 600
volts, for protectors with a nominal working voltage of 230 or 240 volts, when tested in
accordance with BS EN 62305 Part - 4 (6kV 1.2/50 µs open circuit voltage, 3kA 8/20µs
short circuit current).
G. This peak transient let-through voltage shall not be exceeded for all combinations of
conductors:
1. phase to neutral
2. phase to earth
3. neutral to earth.
H. Mains protectors (installed in shunt/parallel) should have continuous indication of its
protection status and the presence of power. Status indication should clearly show per
phase:
J. Specialist Lightning Protection Installer also has to ensure, based on BSEN 62305 – IV,
that suitable coordinated over-voltage surge protection devices with an extra low let –
A. The Specialist Lightning Protection Installer shall also install transient overvoltage
protectors on all data communication/signal/telephone lines in order to protect
equipment connected to the line, against transient over voltage (Where data lines link
equipment in separate buildings, transient overvoltage protectors should be installed at
both ends of the line in order to protect both pieces of equipment.)
C. Protectors shall be rated for Location Category - High Exposure Level (as defined by
BS EN 62305 – 4: 2006), unless contrary information dictates a lower Exposure Level.
D. The protector must not impair the system’s normal operation. It should not:
1. suppress the system’s normal signal voltage
2. restrict the system’s bandwidth or signal frequency
3. introduce excessive in-line resistance
4. cause signal reflections or impedance mismatches (high frequency systems
only).
E. The protector will have a low transient let-through voltage for tests conducted in
accordance with BS EN 62305 -4: 2006 (5kV 10/700µs test).
H. The protector shall be supplied with detailed installation instructions. The installer must
comply with the installation practice detailed by the protector manufacturer. The
protector manufacturer should allow for the facility to mount and earth large numbers of
protectors through an accessory combined mounting and earthing kit.
A. Lightning Protection Installer shall ensure proper co-ordination between the Structural ,
Civil , Electrical and the Cladding contractor.
B. All installation details shall be agreed with the Engineer prior to commencement of work.
The Specialist Lightning Protection Installer shall obtain an inspection certificate from
the manufacturer or its authorized representative towards the satisfactory installation of
the system and that proper material in accordance to the above standard has been
used.
D. For structures taller than 30 meters, the specialist lightning Protection installer shall
install the equipotential bonding at either the basement or the ground level and then
every 20 meters floor thereafter. Wherever protection of internal systems against over-
voltages caused by lightning discharge requires SPDs, these shall conform to BSEN
62305 – Part 4.
E. The gas, water and other metallic systems shall all be bonded directly to the equi-
potential bar located inside but close to the outer wall near the ground floor or basement
level. The power cable shall be bonded to the equi-potential bonding bar via a suitable
SPD. The screen of the antenna cable or any shielded power supply shall also be
bonded to the equipotential bar.
F. Service entry SPDs are for metallic electrical services only - gas and water do not fall
under this category. Metallic gas and water need to be directly bonded. The service
entry data and telecom lines can handle 2.5kA (10µs/350 µs) per line, so the specialist
lightning protection installer shall provide suitable SPDs in accordance to the above
specification as per the BSEN 62305 – Part 4
G. Since the service entrance SPDs are designed to protect against dangerous sparking
only as per BS EN 62305-3. The specialist lightning protection installer shall need to fit
additional protection at the sub-distribution and near equipment to protect electronic
equipment to BS EN 62305-4. Both types of SPD are a required in accordance with this
BS EN standard if the risk assessment demands this.
H. The bonding bar shall be located close to the main distribution board and shall be
connected to earth termination network at ≤ 1 ohm, with a very short length conductor
not exceeding 10 meters in length.
J. All the bonding bars at different levels shall be connected to each other, which in-turn is
earthed at 1 ohm.
K. Isolating spark gap (ISG) devices (to BS EN/ IEC 62561-3) suitable for equipotential
bonding of different earthing systems during transient activity shall be provided
2.9 MATERIALS
A. Materials shall comply in weight, size and composition with the requirements of BS EN
50164.
B. All surge protection devices to be used shall be from the same manufacturer who
supplies the structural lightning protection. Surge protectors shall be manufactured for
PART 3 - EXECUTION
3.1 INSTALLATION
B. Install conductors with direct paths from air terminals to ground connections. Avoid
sharp bends and narrow loops.
D. System conductors.
E. Down conductors.
F. Interior conductors.
G. Conductors within normal view from exterior locations at grade within 60 m of building.
3.2 TESTING
A. On completion of the installation or of any modification to it, the following isolated and
combined measurement and / or checks has to be made and the results recorded in a
lightning protection system logbook.
B. The resistance to earth of each local earth electrode and in addition the resistance to
earth of the complete earth termination system.
C. Each local earth electrode has be measured in isolation and the test point between the
down conductor and the earth electrode in the disconnected position (isolated
measurement)
D. A further measurement has to be taken with the test point in the connected position
(combined measurement)
E. The results of visual check of all conductors, bonds and joints and their measured
electrical continuity.
F. If the resistance to earth of a lightning protection system exceeds 10 ohms, the value
must be reduced. Necessary remedial action needs to be taken to reduce the value
below or equal to 10 ohms.
H. The manufacturer or the manufacturer’s authorized representative will certify the bill of
materials, provided by the Specialist Lightning Protection Installer for the project.
I. The Specialist Lightning Protection Installer must submit the Test Certificates of the
materials used as per BSEN 50164, which should be attested in original by the
manufacturer or the manufacturer’s authorized representative.
3.3 RECORDS
A. The person has to keep on site or the following records, responsible for the upkeep of
the installation:
1. Approved shop drawings, showing the nature, dimensions, materials and position
of all component parts of the lightning protection system.
2. The nature of the soil and any special earthing arrangements.
3. The type and position of the earth electrodes, including reference electrodes.
4. The test conditions and the result obtained.
5. Any alteration, additions or repairs to the system.
6. The name of the person responsible for the installation upkeep.
7. A label should be attached at the origin of the electrical installation, worded as
follows
8. “This structure is provided with a lightning protection system in accordance with
BSEN 62305 and BSEN 50164 and the bonding to the services and the main
equi-potential bonding should be maintained accordingly”
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Architect/ Engineers review outlining all
deficiencies and course of action. The contractor shall ensure all deficiencies outlined
are rectified, retested, and certified.
3.5 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
C. The periodic inspections and tests recommended will show what maintenance, if any is
needed. Tests have to be repeated at fixed intervals, as mentioned in the BSEN 62305
– Part III.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Architect/ Engineer for approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.1 SUMMARY
1. Cylinder.
2. Downlight.
3. Highbay, linear.
4. Highbay, nonlinear.
5. Linear industrial.
6. Lowbay.
7. Parking garage.
8. Recessed, linear.
9. Strip light.
10. Surface mount, linear.
11. Surface mount, nonlinear.
12. Suspended, linear.
13. Suspended, nonlinear.
1.3 DEFINITIONS
A. Definitions include:
C. Samples: For each luminaire and for each color and texture with standard factory-
applied finish.
D. Samples for Initial Selection: For each type of luminaire with custom factory-applied
finishes.
1. Include Samples of luminaires and accessories involving color and finish
selection.
A. Coordination Drawings: Reflected ceiling plan(s) and other details, drawn to scale, on
which the following items are shown and coordinated with each other, using input from
installers of the items involved:
1. Luminaires.
2. Suspended ceiling components.
3. Partitions and millwork that penetrate the ceiling or extend to within 300 mm of
the plane of the luminaires.
4. Structural members to which equipment and luminaires will be attached.
5. Initial access modules for acoustical tile, including size and locations.
6. Items penetrating finished ceiling, including the following:
a. Other luminaires.
KEO/19-3262-0000 26 5119/2 Led Interior Lighting
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
b. Air outlets and inlets.
c. Speakers.
d. Sprinklers.
e. Access panels.
f. Ceiling-mounted projectors.
g. Fire alarm detectors
h. Lighting control devices
7. Moldings.
8. Coordinate "Qualification Data" Paragraph below with qualification requirements
in Section 01 4000 "Quality Requirements" and as may be supplemented in
"Quality Assurance" Article.
B. Qualification Data: For testing laboratory providing photometric data for luminaires.
E. Product Test Reports: For each type of luminaire, for tests performed by manufacturer
and witnessed by a qualified testing agency.
F. Sample warranty.
A. Operation and Maintenance Data: For luminaires and lighting systems to include in
operation and maintenance manuals.
1. Provide a list of all lamp types used on Project; use British Standards, CIBSE
Society of Light and Lighting recommendations and manufacturers' codes.
A. Furnish extra materials that match products installed and that are packaged with
protective covering for storage and identified with labels describing contents.
1. Lamps (If applicable): Twenty for every 100 of each type and rating installed.
Furnish at least one of each type.
2. Glass, Acrylic, and Plastic Lenses, Covers, and Other Optical Parts: Five for
every 100 of each type and rating installed. Furnish at least one of each type.
3. Diffusers and Lenses: Five for every 100 of each type and rating installed.
Furnish at least one of each type.
4. Globes and Guards: Two for every 20 of each type and rating installed. Furnish
at least one of each type.
5. Twenty units of each type luminaries installed
C. Each luminaire type shall be binned within a three-step MacAdam Ellipse to ensure
color consistency among luminaires.
D. Mockups: For interior luminaires in room or module mockups, complete with power and
control connections.
1. Obtain Architect's approval of luminaires in mockups before starting installations.
2. Maintain mockups during construction in an undisturbed condition as a standard
for judging the completed Work.
3. Approval of mockups does not constitute approval of deviations from the
Contract Documents contained in mockups unless Architect specifically approves
such deviations in writing.
4. Subject to compliance with requirements, approved mockups may become part
of the completed Work if undisturbed at time of Substantial Completion.
1.10 WARRANTY
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Seismic Performance: Luminaires and lamps shall be labeled vibration and shock
resistant.
1. The term "withstand" means "the luminaire will remain in place without
separation of any parts when subjected to the seismic forces specified and the
luminaire will be fully operational during and after the seismic event."
D. NRTL Compliance: Luminaires for hazardous locations shall be listed and labeled for
indicated class and division of hazard by an NRTL.
E. FM Global Compliance: Luminaires for hazardous locations shall be listed and labeled
for indicated class and division of hazard by FM Global.
2.4 CYLINDER
B. Lamp:
1. Minimum allowable efficacy of 65 lm/W for general lighting.
2. CRI of minimum 80. CCT of 3000 K - 4000 K
3. Rated lamp life of 50,000 hours to L70.
4. Dimmable from 100 percent to 0 percent of maximum light output.
5. Internal driver.
6. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3 .
7. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping without use of tools.
Components are designed to prevent doors, frames, lenses, diffusers, and other
components from falling accidentally during relamping and when secured in operating
position.
G. Standards:
1. ENERGY STAR certified.
2. RoHS compliant.
3. UL Listing: Listed for damp location.
2.5 DOWNLIGHT
B. Lamp:
1. Minimum 250lm.
2. Minimum allowable efficacy of 65 lm/W.
3. CRI of minimum 80 . CCT of 3000 K - 4100 K.
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
c. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping without use of tools.
Designed to prevent doors, frames, lenses, diffusers, and other components from falling
accidentally during relamping and when secured in operating position.
F. Standards:
1. ENERGY STAR certified.
2. RoHS compliant.
3. UL Listing: Listed for damp location.
4. Recessed luminaires shall comply with BS EN60598-1,2, and 3.
B. Lamp:
1. Minimum 250lm.
2. Minimum allowable efficacy of 65 lm/W.
3. CRI of minimum 80 CCT of 3000K – 4000K
KEO/19-3262-0000 26 5119/6 Led Interior Lighting
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
8. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping without use of tools.
Components are designed to prevent doors, frames, lenses, diffusers, and other
components from falling accidentally during relamping and when secured in operating
position.
F. Standards:
1. Part L Building Regulations compliant.
B. Lamp:
1. Minimum 250lm.
2. Minimum allowable efficacy of 65lm/W.
3. CRI of minimum 80. CCT of 3000 K -4100 K.
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
8. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
2. Doors, Frames, and Other Internal Access: Smooth operating, free of light
leakage under operating conditions, and designed to permit relamping without
use of tools. Components are designed to prevent doors, frames, lenses,
diffusers, and other components from falling accidentally during relamping and
when secured in operating position.
E. Standards:
1. Part L Building Regulations compliant.
A. Lamp:
1. Minimum 250 lm.
2. Minimum allowable efficacy of 65 lm/W.
3. CRI of minimum 80. CCT of 3000K – 4000K.
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
8. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
B. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping without use of tools.
Components are designed to prevent doors, frames, lenses, diffusers, and other
components from falling accidentally during relamping and when secured in operating
position.
G. Standards:
1. Part L Building Regulations compliant.
2.9 LOWBAY
B. Lamp:
KEO/19-3262-0000 26 5119/8 Led Interior Lighting
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Minimum 250lm.
2. Minimum allowable efficacy of 80 lm/W.
3. CRI of minimum 65. CCT of 3000K-4000K.
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
8. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping without use of tools.
Components are designed to prevent doors, frames, lenses, diffusers, and other
components from falling accidentally during relamping and when secured in operating
position.
F. Standards:
1. Part L Building Regulations compliant.
B. Lamp:
1. Minimum 250 lm.
2. Minimum allowable efficacy of 65 lm/W.
3. CRI of minimum 80. CCT of 3000 K-4000 K.
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
8. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping without use of tools.
Components are designed to prevent doors, frames, lenses, diffusers, and other
components from falling accidentally during relamping and when secured in operating
position.
KEO/19-3262-0000 26 5119/9 Led Interior Lighting
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
E. Diffusers and Globes:
1. Refer to luminaire schedule.
2. Acrylic Diffusers: One hundred percent virgin acrylic plastic, with high resistance
to yellowing and other changes due to aging, exposure to heat, and UV radiation.
3. Glass: Annealed crystal glass unless otherwise indicated.
4. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
G. Standards:
1. Part L Building Regulations compliant.
B. Lamp:
1. Minimum 250 lm.
2. Minimum allowable efficacy of 65 lm/W.
3. CRI of minimum 80. CCT of 3000 K-4000 K.
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
8. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping without use of tools.
Components are designed to prevent doors, frames, lenses, diffusers, and other
components from falling accidentally during relamping and when secured in operating
position.
F. Standards:
1. Part L Building Regulations compliant.
B. Lamp:
1. Minimum 750 lm.
2. Minimum allowable efficacy of 65 lm/W.
KEO/19-3262-0000 26 5119/10 Led Interior Lighting
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. CRI of minimum 80. CCT of 3000 K 4000 K.
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
8. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping of luminaire without use of
tools. Components are designed to prevent doors, frames, lenses, diffusers, and other
components from falling accidentally during relamping and when secured in operating
position.
F. Standards:
1. Part L Building Regulations compliant.
B. Lamp:
1. Minimum 250 lm.
2. Minimum allowable efficacy of 65 lm/W.
3. CRI of minimum 80. CCT of 3000K-4000K.
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
8. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping without use of tools.
Components are designed to prevent doors, frames, lenses, diffusers, and other
components from falling accidentally during relamping and when secured in operating
position.
F. Standards:
1. Part L Building Regulations compliant.
B. Lamp:
1. Minimum 250 lm.
2. Minimum allowable efficacy of 65 lm/W.
3. CRI of minimum 80. CCT of 3000K-4000K.
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
8. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping without use of tools.
Components are designed to prevent doors, frames, lenses, diffusers, and other
components from falling accidentally during relamping and when secured in operating
position.
F. Standards:
1. ENERGY STAR certified.
2. RoHS compliant.
3. UL Listing: Listed for damp location.
B. Lamp:
1. Minimum 250 lm.
2. Minimum allowable efficacy of 65 lm/W.
3. CRI of minimum 80. CCT of 3000K-4000K.
KEO/19-3262-0000 26 5119/12 Led Interior Lighting
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
8. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping without use of tools.
Components are designed to prevent doors, frames, lenses, diffusers, and other
components from falling accidentally during relamping and when secured in operating
position.
F. Standards:
1. Part L Building Regulations compliant.
B. Lamp:
1. Minimum 250 lm.
2. Minimum allowable efficacy of 65 lm/W.
3. CRI of minimum 80. CCT of 3000K-4000K.
4. Rated lamp life of 50,000 hours to L70.
5. Dimmable from 100 percent to 0 percent of maximum light output.
6. Internal driver.
7. User-Replaceable Lamps:
a. Bulb shape complying with BS EN60598-1,2, and 3.
b. Lamp base complying with BS EN60598-1,2, and 3.
8. Lens Thickness: At least 3.175-mm minimum unless otherwise indicated.
C. Housings:
1. Refer to luminaire schedule.
D. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage
under operating conditions, and designed to permit relamping without use of tools.
Components are designed to prevent doors, frames, lenses, diffusers, and other
components from falling accidentally during relamping and when secured in operating
position.
F. Standards:
1. Part L Building Regulations compliant.
2.17 MATERIALS
A. Metal Parts:
1. Free of burrs and sharp corners and edges.
2. Sheet metal components shall be steel unless otherwise indicated.
3. Form and support to prevent warping and sagging.
A. Comply with requirements in Section 26 0529 "Hangers and Supports for Electrical
Systems" for channel and angle iron supports and nonmetallic channel and angle
supports.
B. Single-Stem Hangers: 13-mm steel tubing with swivel ball fittings and ceiling canopy.
Finish same as luminaire.
E. Hook Hangers: Integrated assembly matched to luminaire, line voltage, and equipment
with threaded attachment, cord, and locking-type plug.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance of
the Work.
B. Examine roughing-in for luminaire to verify actual locations of luminaire and electrical
connections before luminaire installation.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.3 INSTALLATION
B. Install luminaires level, plumb, and square with ceilings and walls unless otherwise
indicated.
D. Supports:
1. Sized and rated for luminaire weight.
2. Able to maintain luminaire position after cleaning and relamping.
3. Provide support for luminaire without causing deflection of ceiling or wall.
4. Luminaire-mounting devices shall be capable of supporting a horizontal force of
100 percent of luminaire weight and a vertical force of 400 percent of luminaire
weight.
E. Flush-Mounted Luminaires:
1. Secured to outlet box.
2. Attached to ceiling structural members at four points equally spaced around
circumference of luminaire.
3. Trim ring flush with finished surface.
F. Wall-Mounted Luminaires:
1. Do not attach luminaires directly to gypsum board.
G. Suspended Luminaires:
1. Ceiling Mount:
2. Refer to luminaire schedule.
3. Pendants and Rods: Where longer than 1200 mm, brace to limit swinging.
4. Stem-Mounted, Single-Unit Luminaires: Suspend with twin-stem hangers.
Support with approved outlet box and accessories that hold stem and provide
damping of luminaire oscillations. Support outlet box vertically to building
structure using approved devices.
5. Continuous Rows of Luminaires: Use tubing or stem for wiring at one point and
tubing or rod,wire support for suspension for each unit length of luminaire
chassis, including one at each end.
6. Do not use ceiling grid as support for pendant luminaires. Connect support wires
or rods to building structure.
H. Ceiling-Grid-Mounted Luminaires:
1. Secure to any required outlet box.
2. Secure luminaire to the luminaire opening using approved fasteners in a
minimum of four locations, spaced near corners of luminaire.
3. Use approved devices and support components to connect luminaire to ceiling
grid and building structure in a minimum of four locations, spaced near corners of
luminaire.
A. Identify system components, wiring, cabling, and terminals. Comply with requirements
for identification specified in Section 26 0553 "Identification for Electrical Systems."
B. Luminaire will be considered defective if it does not pass operation tests and
inspections.
3.7 ADJUSTING
3.8 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Architect/ Engineer for approval.
KEO/19-3262-0000 26 5119/16 Led Interior Lighting
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 DESCRIPTION
1.02 REFERENCES:
B. All wiring of telephone works shall be according to the latest Ministry of Communication
(MOC) Regulations and Specifications
A. Telephone work comprises the supply and installation of the following to provide a
telephone system in good working order as per MOC Regulations.
1. Telephone terminal cabinet and draw boxes
2. Telephone Socket outlets
3. Telephone cables
4. Conduits, cable trays and their accessories.
1.04 SUBMISSIONS
A. Shop Drawings:
1. Submit working drawings of the system, for approval
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Flush-mounting type
KEO/19-3262-0000 27 1000/1 Analogue Telephone System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. Dust vermin proof
C. Lockable type (barrel lock). hinged door type which is completely flush mounted
D. To be provided with LSA Cat6 110-type connecting blocks with color coded strips
E. Draw boxes hinged door type, which is completely flush mounted. The external
telephone draw-in box to be weatherproof of (IP-54).
A. Flush mount jacks for telephone shall be an eight-pin, eight conductor (8P8C) modular,
with an insulation displacement connector on the rear. They shall provide color-coding
for the T568B wiring schedule.
E. Faceplates shall be a single gang as identified on drawings, Jacks shall be of the same
manufacturer.
A. Horizontal cabling shall be a 100 ohm, 23 AWG, 4-Pair, Unshielded Twisted Pair (UTP),
of a LSZH construction, compliant with ANSI/TIA/EIA 568-C.2 for Category 6 / ISO
Class E performance, with swept frequency testing to at least 250 MHz. Cable
characteristics shall be as follows:
1. Conductor resistance at 20o C (max): 8.9 ohms/100m.
2. DC Resistance Unbalanced (max), Individual pair %: 3
3. Characteristics Impedance (Zc): 100 ohms (± 15%).
4. Delay Skew (max): 25 ns/100m
B. Have a construction comprised of 4-pairs of 0.57mm (0.022 in) (23AWG) solid bare
copper conductors utilizing a centre isolation member to maintain pair geometry for
optimal NEXT performance
C. Plenum rated
D. All copper components used in the horizontal system will be of the same manufacturer,
and will all be third party TESTED & VERIFIED to Cat 6 components, permanent link &
channel, complying with ANSI / TIA / EIA, ISO / IEC & CENELEC EN standards.
E. Each cable box/reel shall be individually tested by the manufacturer and be delivered
with manufacturer’s test results affixed.
G. Cable sheath shall be Low Smoke Zero Halogen jacket, meeting IEC 60332-1 (flame
retardant), IEC 60754-2, IEC 601034 fire resistance standards and low smoke emission
compliance EN 50267-2-1.
PART 3 - EXECUTION
3.01 INSTALLATION
3.02 GENERALLY
B. The general layout of ducts, cable tray and conduit and the positions of distribution
boxes shall be as shown on the drawings. Contractor shall co-ordinate with Laboratory
Benches supplier for exact location of entry of telephone and data services prior to
preparing shop drawings.
A. Fix where instructed by the Engineer or as per approved shop drawings. Telephone
socket locations are not final and these have to be coordinated with other trades and the
same to be finalized.
3.05 WIRING:
A. All drain wires shall be terminated on an earth pit, which ultimately shall be connected
by a conductor of minimum 16 sq. mm to an independent earthing system meant for the
telephone network. Such earthing shall be totally separate from the other earthing
systems of the building. Connection to the MDF/TTC post and the electrodes shall be of
the soldered type.
A. Testing:
1. Test the installation in accordance with the regulations of the Ministry of
Communication.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This section details the technical requirement for Communications Equipment Room
Fittings
B. Section Includes:
1. Backboards.
2. Boxes, enclosures, and cabinets.
3. Power strips.
1.02 DEFINITIONS
A. Unless stated otherwise or specifically mentioned in this Section, the Contractor shall
comply with all the standards of quality of materials and workmanship as specified in
the relevant articles of the following sections:
1. Division 26 Section 26 0526 "Earthing and Bonding for Electrical Systems"
2. Division 26 Section 26 0529 "Hangers and Supports for Electrical Systems"
3. Division 26 Section 26 0533 "Raceways and Boxes for Electrical Systems"
4. Division 26 Section 26 0536 "Cable Trays and Ladder for Electrical Systems"
5. Division 27 Section 271116 “Communications racks, frames, and enclosures”
6. Division 27 Section 27 1323 “Communications Optical Fiber Backbone Cabling”
7. Division 27 Section 27 1513 "Communications Copper Horizontal Cabling"
1.010 COORDINATION
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
B. All components and their installations shall be free from defects. Any defective
material or workmanship and any resulting damage to work of other trades shall be
replaced or repaired as directed during the Warranty Period at the contactors
expense. Comply with General Conditions, agreeing to repair or replace any
components that have failed within the warranty period.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents
B. Spare parts required shall include but not necessarily be limited to,
1. Power strips – 4 nos
2. Tools required for maintenance.
PART 2 - PRODUCTS
2.02 BACKBOARDS
PART 3 - EXECUTION
3.02 INSTALLATION
C. Bundle, lace, and train conductors and cables to terminal points without exceeding
manufacturer's limitations on bending radii. Install lacing bars and distribution spools.
F. Backboards:
1. Install from 150 mm to 2588 mm above finished floor. If plywood is fire rated,
ensure that fire-rating stamp is visible after installation.
2. Paint all sides of backboard with two coats of paint, leaving fire rating stamp
visible.
3. Comply with requirements for backboard installation in BICSI's "Information
Technology Systems Installation Methods Manual" and TIA-569-E.
A. Install sleeves and sleeve seals at penetrations of exterior floor and wall assemblies.
Comply with requirements in Section 26 0500 - Common Requirements for Electrical
Installations
3.04 FIRESTOPPING
KEO/19-3262-0000 27 1100/5 Communications Equipment Room Fittings
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
A. Comply with requirements in Section 07 8400 "Firestopping."
3.05 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the
installed system. During that period, the contractor shall be responsible for the regular
inspection and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for
the system and submit to the Engineer for his approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This section details the technical requirement for Communications Racks, Frames,
and Enclosures
B. Section Includes:
1. 19-inch equipment cabinets for Telecom Rooms
2. 19-inch equipment cabinets for Main Computer Room (MCR)
3. Rack mounted PDUs
4. Grounding
5. Labeling
1.02 DEFINITIONS
A. Unless stated otherwise or specifically mentioned in this Section, the Contractor shall
comply with all the standards of quality of materials and workmanship as specified in
the relevant articles of the following sections:
1. Division 26 Section 26 0526 "Grounding and Bonding for Electrical Systems"
2. Division 26 Section 26 0529 "Hangers and Supports for Electrical Systems"
3. Division 26 Section 26 0533 "Raceways and Boxes for Electrical Systems"
4. Division 26 Section 26 0536 "Cable Trays and Ladder for Electrical Systems"
5. Division 27 Section 27 1100 “Communications Equipment Room Fittings”
6. Division 27 Section 27 1323 “Communications Optical Fiber Backbone Cabling”
7. Division 27 Section 27 1513 "Communications Copper Horizontal Cabling"
B. Shop Drawings: For communications racks, frames, and enclosures. Include plans,
elevations, sections, details, and attachments to other work.
1. Detail equipment assemblies and indicate dimensions, weights, loads, required
clearances, method of field assembly, components, and location and size of
each field connection.
2. Equipment Racks and Cabinets: Include workspace requirements and access
for cable connections.
3. Grounding: Indicate location of TGB and its mounting detail showing standoff
insulators and wall-mounting brackets.
A. Qualification Data: For qualified layout technician, installation supervisor, and field
inspector.
1.010 COORDINATION
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
B. All components and their installations shall be free from defects. Any defective
material or workmanship and any resulting damage to work of other trades shall be
KEO/19-3262-0000 27 1116/3 Communications Racks, Frames, and Enclosures
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
replaced or repaired as directed during the Warranty Period at the contactors
expense. Comply with General Conditions, agreeing to repair or replace any
components that have failed within the warranty period.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents
B. Spare parts required shall include but not necessarily be limited to,
1. Cable Management Accessories – 5 % of total quantity
2. Rack mounted PDUs – 5 % of total quantity
3. Tools required for maintenance.
PART 2 - PRODUCTS
B. Rack and Cabinet TGBs: Rectangular bars of hard-drawn solid copper, accepting
conductors ranging from No. 14 to No. 2/0 AWG, NRTL listed as complying with
UL 467, and complying with TIA-606-C. Predrilling shall be with holes for use with lugs
specified in this Section.
1. Cabinet-Mounted TGB: Terminal block, with stainless-steel or copper-plated
hardware for attachment to cabinet.
2.05 LABELING
A. Comply with ANSI/TIA-606-C for a system of labeling materials, including label stocks,
laminating adhesives, and inks used by label printers.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Comply with BICSI TDMM for layout and installation of communications equipment
rooms.
B. Bundle, lace, and train conductors and cables to terminal points without exceeding
manufacturer's limitations on bending radii. Install lacing bars and distribution spools.
3.02 FIRESTOPPING
3.03 IDENTIFICATION
C. Paint and label colors for equipment identification shall comply with TIA-606-C for
Class 4 level of administration including optional identification requirements of this
standard.
3.04 TRAINING
C. Obtain employers staff signatures for attendance and submit as a record that the
training has been completed and to the satisfaction of the employer.
D. Distribute copies of the operation and maintenance manuals during the training and
go thru the content in details. Please note the copies distributed during the training are
not the official copies to submitted for close out purposes.
E. Schedule training with the Employer, through Engineer, with at least 14 days' advance
notice.
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Engineers review outlining all deficiencies
and course of action. The contractor shall ensure all deficiencies outlined are rectified,
retested, and certified.
B. The contractor during that period shall provide labor and parts warranty on the
installed system. During that period, the contractor shall be responsible for the regular
inspection and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for
the system and submit to the Engineer for his approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This section details the technical requirement for Communications Optical Fiber
Backbone Cabling
B. Section Includes:
1. Single-mode optical fiber cable
2. Multi-mode optical fiber cable
3. Optical fiber cable connecting hardware, patch panels, and cross-connects
(passive)
4. Cabling identification products.
5. Source quality control requirements for optical fiber cable.
1.02 DEFINITIONS
A. Unless stated otherwise or specifically mentioned in this Section, the Contractor shall
comply with all the standards of quality of materials and workmanship as specified in
the relevant articles of the following sections:
1. Division 26 Section 26 0529 "Hangers and Supports for Electrical Systems"
2. Division 26 Section 26 0533 "Raceways and Boxes for Electrical Systems"
3. Division 26 Section 26 0536 "Cable Trays and Ladder for Electrical Systems"
4. Division 27 Section 27 1100 - Communications Equipment Room Fittings
5. Division 27 Section 27 1116 “Communications Racks, Frames, and Enclosures”
6. Division 27 Section 27 1513 "Communications Copper Horizontal Cabling"
B. Backbone cabling cross-connects shall be located in MCR. Bridged taps and splitters
shall not be used as part of backbone cabling.
A. Maintenance Data: For optical fiber cable, splices, and connectors to include in
maintenance manuals.
A. The following section provides a summary of the mandatory requirements for the
technical submittal as a part of the tender response. This shall be accompanied by the
relevant manufacturer and installer documentation. The list outlined below is not
exhaustive and reference shall be made to the appropriate sections within this
document to ensure full compliance to all areas.
1. Manufacturer shall provide a list of the current applications and guaranteed
distances supported by the Fiber infrastructure.
2. All Passive Components in the SCS shall meet or exceed the relevant optical
fiber link specifications as detailed in the latest ANSI/TIA-568 and ISO 11801
series of standards.
3. Single mode fibre shall be Zero Water Peak Single mode (ZWP-SM) fiber. It
shall support next generation equipment and operate over the entire
wavelength range from 1280 nm to 1625 nm, removing the water peaks (high
attenuation) in the 1400 nm window, allowing up to 16 channels of CWDM
(Coarse Wave Division Multiplexing).
4. Manufacturer shall provide a list of the current applications and guaranteed
distances supported by the fiber infrastructure, including the number of MPO
and LC connectors.
5. Data Sheets for all specified products outlining compliance to the specifications
shall be provided.
6. Manufacturer shall guarantee that all current and future applications designed
to operate on a standards compliant cabling system, will be covered under the
terms and conditions of the Manufacturer’s warranty at the time of submission
of this project.
7. All components shall be manufactured solely by the proposed vendor. A full list
of the company’s manufacturing locations along with their ISO 9000
accreditations shall be included in the response. This includes all copper and
fiber cable and components.
8. Full details of the manufacturers’ 25-year Applications Assurance Warranty
shall be included within the response.
9. Full details of the installers’ credentials shall be provided, including up to date
manufacturers’ training requirements and CV’s of key personnel that will be
assigned to the project.
10. Full details of the manufacturers’ credentials shall be provided, including CV’s
of key personnel that will be assigned to the project.
11. The SCS Contractor shall comply with local authority requirements where these
take precedence over this specification. Where the SCS Contractor deters from
this course they are responsible for obtaining approvals from the relevant
authorities to change the requirement.
A. System Installers shall show competence in three main areas, as detailed below:
1. Company Experience.
2. Management, Design and Installation Experience.
3. Manufacturers Training Requirements.
B. Company Experience
1. The System Installer shall have a Registered Office in Kuwait for at least five
years.
2. The System Installer shall provide a valid trade license.
3. The System Installer shall provide three references of projects of a similar size
and nature, undertaken within the country.
A. Manufacturers of the proposed solution shall show competence in three main areas,
as detailed below:
1. Company Experience.
2. Regional Technical Support
3. Manufacturing Locations and Supply Chain
1.016 COORDINATION
C. Coordinate power receptacles locations with racks containing active LAN equipment.
D. Coordinate racks locations with other systems equipment that might be sharing the
same room in order to insure efficient use of the shared space.
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
B. All components and their installations shall be free from defects. Any defective
material or workmanship and any resulting damage to work of other trades shall be
replaced or repaired as directed during the Warranty Period at the contactors
expense. Comply with General Conditions, agreeing to repair or replace any
components that have failed within the warranty period.
C. The solution shall include a 25 Year Extended Product and Applications Assurance
Warranty.
KEO/19-3262-0000 27 1323/7 Communications Optical Fiber Backbone Cabling
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
D. The installation shall receive the 25 Year Extended Product Warranty and Applications
Assurance when completed and registered by the Certified Installation Partner.
E. Any active equipment (AIM) within the solution shall include a 3 Year Warranty when
completed and registered by the Certified Installation Partner.
F. The Manufacturer shall give the following assurances during the Warranty Period:
1. The Registered System will meet or exceed the System Performance
Specifications
2. The Registered System will support Applications as specified in the Application
Performance Specifications.
3. The Registered System will support future Applications introduced during the
Warranty Period, to the extent such Applications are defined to operate in
conformance with the applicable Application Performance Specification for the
Registered System.
H. The Manufacturer’s Warranty details and the Terms and Conditions shall be included
within the response.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Patch-Panel Units: 2% of each type.
2. Connecting Blocks: 2% of each type.
3. Tools recommended by the manufacturer.
PART 2 - PRODUCTS
2.03 PATHWAYS
B. Comply with requirements in Division 26 Section "Hangers and Supports for Electrical
Systems" for installation of conduits and wireways.
C. Comply with requirements in Division 26 Section "Cable tray and Ladder for Electrical
Systems" for installation of conduits and wireways.
D. Comply with requirements in Division 26 Section "Raceways and Boxes for Electrical
Systems" for installation of conduits and wireways.
A. Optical fibre cabling shall be available in internal, indoor/outdoor and outside plant
constructions for all fibre types.
B. The cable shall have a unique print string on the cable jacket. This unique identifier
shall also be used for on-line reference to a full set of factory tests that were performed
on a sample from the same mater reel. The test parameters shall include insertion
loss at 1310 and 1550 nm (Single mode). The on-line reference must be available on
the SCS manufacturers’ website, such that it can be accessed at any time.
C. Indoor/Outdoor Grade
1. Indoor/outdoor cabling must be available for campus based networks or those
requiring a simplified transition point between outdoor cabling and building
cable. Indoor/outdoor cabling shall meet the fire safety requirements of an
indoor environment, along with the rigors of an outdoor environment such as
extended temperature range, UV resistance and water blocking capabilities.
2. The fibre-optic SCS shall be available with a wide range of indoor/outdoor
cabling which include the following designs:
3. All dielectric stranded loose-tube
4. 250 micron buffered fibres up to 144 fibres
5. The LSZH Jacket must comply with the following Fire Safety standards:
a. ISO/IEC 60332-1: Vertical Flame Spread
b. ISO/IEC 60332-3c: Vertical Flame Spread
c. ISO/IEC 60754-2: Acidity
d. ISO/IEC 61034-2: Smoke Density
6. Indoor/outdoor LSZH cabling shall comply with appropriate sections of IEC
60794-2.
E. Applications Support, The cable shall support (but not limited to) the following
applications:
IEEE Applications
100Mb 100BASE-LX10
1G 1000BASE-LH
1000BASE-BX10
1000BASE-LX10
1000BASE-PX10-D
1000BASE-PX10-U
1000BASE-PX20-D
1000BASE-ZX
10G 10GBASE-LR
10BASE-LX4
10GBASE-ER
40G 40GBASE-LR4
100G 100GBASE-LR4
2.05 MULTIMODE
A. The multimode fiber shall meet a minimum of one of the DMD templates listed within
this document, accounting for the wider inner and outer mask specifications when
compared with TIA 492AAAc and IEC 60793-2-10 standards. Published
documentation on this and Third party verification of the DMD test results and testing
methodology must be provided with the bid response.
B. OM4 Multimode
1. The multimode fibres shall fully meet or exceed the OM4 fibre specifications in
the following standards:
a. EN 50173-1:2011
b. ISO/IEC 11801:2010
c. IEC/EN 60793-2-10 (A1a fibre)
d. ANSI/TIA-492AAAD standards
2. The OM4 multimode fibre shall be manufactured with an inside vapour
deposition process such as the MCVD (Modified Chemical Vapour Deposition)
or PCVD (Plasma Clad Vapour Deposition) processes. Multimode fibres
produced with outside vapour deposition processes, such as OVD or VAD, will
not be accepted. Inside vapour deposition manufacturing processes results in
superior control of Refractive Index Profile required for high bandwidth.
3. Application Support: The OM4 Multimode Fibre SCS shall be capable of
supporting, at minimum, the following IEEE Ethernet applications:
1GFC
2GFC
4GFC
8GFC
10GFC
16GFC
5. The OM4 multimode fibre shall comply with the following physical
specifications:
7. NOTE: this value reflects cabled fibre loss. Un-cabled fibre values will not be
accepted
8. The OM4 multimode fibres shall be colour coded to facilitate individual fibre
identification. Colour coding shall follow industry standard TIA-598-C Optical
Fibre Cable Color Coding
9. The coating shall be mechanically strippable.
10. Differential Mode Delay: The OM4 fibre shall meet a minimum of one of the
DMD templates listed below, accounting for the wider inner and outer mask
specifications when compared with TIA 492AAAc and IEC 60793-2-10
standards:
A. Fibre Optic Shelves shall be modular in design and available in Medium and High
Density Configurations and be available in 1U, 2U and 4U sizes that are compatible
with 19 inch mounting hardware.
E. The shelves shall be designed to accept individual modules, adaptor panels and
cassettes for both Multimode and Singlemode solutions.
G. The shelves shall provide adequate room for splice trays (Fusion & Mechanical) with
better cable management at the front and rear of the shelf.
H. Datacentre shall be designed with same capacity panels but MPO modules will be
used to connect pre terminated cables
A. Optical fibre cordage shall be available in simplex, duplex and fan-out configurations
and available in a variety of colors.
C. Single mode fibre patch cords shall be provided with OS2 fibre only.
A. Optical fibre pigtails shall be available in standard 900 micron tight buffered or
ruggedized with additional strength elements.
B. Single mode fibre patch cords shall be provided with OS2 fibre only.
A. Comply with ANSI/TIA-606-C for a system of labeling materials, including label stocks,
laminating adhesives, and inks used by label printers.
E. Cable will be considered defective if it does not pass tests and inspections.
PART 3 - EXECUTION
A. Coordinate backbone cabling with the protectors and demarcation point provided by
communications service provider.
A. Wiring Method: Install cables in raceways and cable trays except within consoles,
cabinets, desks, and counters and except in accessible ceiling spaces, in attics, and
in gypsum board partitions where unenclosed wiring method may be used . Conceal
raceway and cables except in unfinished spaces.
1. Install plenum cable in environmental air spaces, including plenum ceilings.
2. Comply with requirements for raceways and boxes specified in Division 26
Section "Raceway and Boxes for Electrical Systems."
B. Wiring within Enclosures: Bundle, lace, and train cables within enclosures. Connect
to terminal points with no excess and without exceeding manufacturer's limitations on
bending radii. Provide and use lacing bars and distribution spools.
A. Comply with requirements for demarcation point, pathways, cabinets, and racks
specified in Division 27 Section " Communications Racks, Frames, and Enclosures."
Drawings indicate general arrangement of pathways and fittings.
C. Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical
Systems" for installation of conduits and wireways.
B. Open-Cable Installation:
1. Install cabling with horizontal and vertical cable guides in telecommunications
spaces with terminating hardware and interconnection equipment.
2. Cable shall not be run through structural members or in contact with pipes,
ducts, or other potentially damaging items.
KEO/19-3262-0000 27 1323/16 Communications Optical Fiber Backbone Cabling
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. Installation of Cable Routed Exposed under Raised Floors:
1. Install plenum-rated cable only.
2. Install cabling after the flooring system has been installed in raised floor areas.
3. Coil cable 1800 mm long not less than 300 mm in diameter below each feed
point.
3.05 FIRESTOPPING
3.06 IDENTIFICATION
B. Paint and label colors for equipment identification shall comply with TIA-606-C for
Class 4 level of administration [ including optional identification requirements of this
standard].
D. Cable Schedule: Install in a prominent location in each equipment room and wiring
closet. List incoming and outgoing cables and their designations, origins, and
destinations. Protect with rigid frame and clear plastic cover. Furnish an electronic
copy of final comprehensive schedules for Project.
G. Labels shall be preprinted or computer-printed type with printing area and font color
that contrasts with cable jacket color but still complies with requirements in ANSI/TIA-
606-C, for the following:
1. Cables use flexible vinyl or polyester that flexes as cables are bent.
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
D. Document data for each measurement. Data for submittals shall be printed in a
summary report that is formatted similar to Table 10.1 in BICSI TDMM, or transferred
from the instrument to the computer, saved as text files, and printed and submitted.
E. Remove and replace cabling where test results indicate that they do not comply with
specified requirements.
F. End-to-end cabling will be considered defective if it does not pass tests and
inspections.
C. Obtain employers staff signatures for attendance and submit as a record that the
training has been completed and to the satisfaction of the employer.
D. Distribute copies of the operation and maintenance manuals during the training and
go thru the content in details. Please note the copies distributed during the training are
not the official copies to submitted for close out purposes.
E. Schedule training with the Employer, through Engineer, with at least 14 days' advance
notice.
A. The complete installation shall be tested and commissioned by a certified third party
independent of the supplier and the contractor. The contractor shall be responsible to
demonstrate the operation of the system to the satisfaction of the Client's personnel.
The third Party testing agency shall submit the testing and commissioning reports for
the Engineers review outlining all deficiencies and course of action. The contractor
shall ensure all deficiencies outlined are rectified, retested, and certified by the third
party testing agency.
3.010 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the
installed system. During that period, the contractor shall be responsible for the regular
inspection and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for
the system and submit to the Engineer for his approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This section details the technical requirement for Communications Copper Horizontal
Cabling
B. Section Includes:
1. Pathways
2. Cat6A U/UTP Cable Horizontal Cabling
3. Cable Bundling Materials
4. Cabling identification products.
5. Grounding
6. Source quality control requirements for twisted pair cable.
1.02 DEFINITIONS
A. Unless stated otherwise or specifically mentioned in this Section, the Contractor shall
comply with all the standards of quality of materials and workmanship as specified in
the relevant articles of the following sections:
1. Division 26 Section 26 0529 "Hangers and Supports for Electrical Systems"
2. Division 26 Section 26 0533 "Raceways and Boxes for Electrical Systems"
3. Division 26 Section 26 0536 "Cable Trays and Ladder for Electrical Systems"
4. Division 27 Section 27 1100 - Communications Equipment Room Fittings
5. Division 27 Section 27 1116 “Communications Racks, Frames, and Enclosures”
6. Division 27 Section 27 1323 “Communications Optical Fiber Backbone Cabling”
A. The following section provides a summary of the mandatory requirements for the
technical submittal as a part of the tender response. This shall be accompanied by the
relevant manufacturer and installer documentation. The list outlined below is not
exhaustive and reference shall be made to the appropriate sections within this
document to ensure full compliance to all areas.
1. The Registered SCS installation shall meet or exceed the permanent link
requirements of the latest ANSI/TIA-568 and ISO/IEC 11801 series of
standards
2. The Registered SCS shall meet or exceed the Category 6A Guaranteed
Channel Performance Claims provided by the Manufacturer. Manufacturers to
provide their Guaranteed Channel Performance Documentation for a full 4
connector, 100 meter channel. This should include Independent Test
Certificates (ETL/UL) showing ISO & TIA, Long & Short Channels.
3. All copper cabling shall be UTP throughout the channel with no shields or foils
included within the cable and component design. This includes cable, modules,
panels and cords.
4. Manufacturer shall provide a list of the current applications and guaranteed
distances supported by the copper infrastructure.
5. Data Sheets for all specified products outlining compliance to the specifications
shall be provided.
6. Manufacturer shall guarantee that all current and future applications designed
to operate on a standards compliant cabling system, will be covered under the
terms and conditions of the Manufacturer’s warranty at the time of submission
of this project.
7. All components shall be manufactured solely by the proposed vendor. A full list
of the company’s manufacturing locations along with their ISO 9000
accreditations shall be included in the response. This includes all copper and
fiber cable and components.
8. Full details of the manufacturers’ 25-year Applications Assurance Warranty
shall be included within the response.
A. System Installers shall show competence in three main areas, as detailed below:
1. Company Experience.
2. Management, Design and Installation Experience.
3. Manufacturers Training Requirements.
B. Company Experience
1. The System Installer shall have a Registered Office in Kuwait for at least five
years.
2. The System Installer shall provide a valid trade licence.
3. The System Installer shall provide three references of projects of a similar size
and nature, undertaken within the country.
A. Manufacturers of the proposed solution shall show competence in three main areas,
as detailed below:
1. Company Experience.
2. Regional Technical Support
3. Manufacturing Locations and Supply Chain
B. Company Experience
1. The Manufacturer shall provide a corporate overview of its business, including
Regional office locations and the number of employees in the Middle-East
region.
2. The Manufacturer shall have a Registered Office in the Middle East and been
operating within the local region for at least five years.
3. The Manufacturer shall provide five references of projects of a similar size and
nature, undertaken within the region.
4. The Manufacturer shall provide details of its participation in standards
development (such as TIA/ISO/IEEE). This shall include details of employees
participating in current standards development.
5. The Manufacturer shall provide details of its innovation program, including
current patents and its experience in the development of products and solutions
in the cabling infrastructure area.
1.015 COORDINATION
D. Coordinate racks locations with other systems equipment that might be sharing the
same room in order to insure efficient use of the shared space.
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the design, detailing of the works described
herein, including (without limitation) the comprehensive engineering analysis by a
qualified professional engineer, and shall provide a complete, and secure installation,
which shall meet the specified performance and design requirements indicated and
which shall be fit for their intended purpose. The Contractor indemnifies the Employer
and Design Consultant from any and all claims, costs and expenses arising from any
loss or damage in connection with any error in or failure of the Contractor’s designed
portion of the Works.
B. All components and their installations shall be free from defects. Any defective
material or workmanship and any resulting damage to work of other trades shall be
replaced or repaired as directed during the Warranty Period at the contactors
expense. Comply with General Conditions, agreeing to repair or replace any
components that have failed within the warranty period.
C. The solution shall include a 25 Year Extended Product and Applications Assurance
Warranty.
D. The installation shall receive the 25 Year Extended Product Warranty and Applications
Assurance when completed and registered by the Certified Installation Partner.
E. Any active equipment (AIM) within the solution shall include a 3 Year Warranty when
completed and registered by the Certified Installation Partner.
F. The Manufacturer shall give the following assurances during the Warranty Period:
1. The Registered System will meet or exceed the System Performance
Specifications
2. The Registered System will support Applications as specified in the Application
Performance Specifications.
3. The Registered System will support future Applications introduced during the
Warranty Period, to the extent such Applications are defined to operate in
conformance with the applicable Application Performance Specification for the
Registered System.
H. The Manufacturer’s Warranty details and the Terms and Conditions shall be included
within the response.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Patch-Panel Units: 10% of each type.
2. Connecting Blocks: 10% of each type.
3. Device Plates: 10% of each type.
4. Tools recommended by the manufacturer.
PART 2 - PRODUCTS
B. RoHS compliant.
2.04 PATHWAYS
B. Comply with requirements in Division 26 Section "Hangers and Supports for Electrical
Systems" for installation of conduits and wireways.
C. Comply with requirements in Division 26 Section "Cable tray and Ladder for Electrical
Systems" for installation of conduits and wireways.
D. Comply with requirements in Division 26 Section "Raceways and Boxes for Electrical
Systems" for installation of conduits and wireways.
A. Furnish and install, complete with all accessories, a Category 6A/ Class EA
Unshielded Twisted Pair (UTP) Structured Cabling System (SCS). The SCS shall
serve as the transport infrastructure for data, wireless, video and voice telephony
signals throughout the network from designated demarcation points to outlets located
at various Desktop, Workstation, Computer Room, Intelligent Building facilities or other
locations as indicated on the contract drawings and described herein.
D. Category 6A Cable
1. The LSZH Cable shall meet or exceed the Category 6A/Class EA attenuation
and NEXT requirements in the latest ISO/IEC 11801(ISO/IEC 11801-1,
ISO/IEC 11801-2, ISO/IEC 11801-3, ISO/IEC 11801-4, ISO/IEC 11801-5,
ISO/IEC 11801-6 where applicable), CENELEC EN50173, IEC 60603-7-4,
IEEE 802.3 where applicable, and ANSI/TIA-568 standards. The cable shall be
composed of solid copper conductors insulated with non-halogen high-density
polyethylene and jacketed with a low smoke zero halogen compound. The
Cable LSZH jacket shall be compliant with CPR Class Dca as minimum. The
solution shall fully comply with Local/National Codes and Regulations.
2. When configured in worst-case 100 metre channels with full cross-connects
and consolidation points with the other products proposed, the cable shall be
capable of delivering the minimum guaranteed channel performance specified
in above Section
3. The length of each individual run of horizontal cable from the
telecommunications closet on each floor to the telecommunications outlet shall
not exceed 90 metres, and shall be continuous without any joints or splices.
4. Contractor shall observe the bending radius and pulling strength requirements
of the 4-pair UTP cable during handling and installation.
5. The cable shall be round in construction, with a maximum nominal diameter of
no more than 7.3 mm
6. The cable will consist of eight 23 AWG copper conductors. Copper-clad
aluminium is not permitted.
7. The cable shall be available in Low-Smoke, Zero Halogen (LSZH).
8. The LSZH version must comply with the following Fire Safety standards:
a. ISO/IEC 60332-3-22: Vertical Flame Spread
b. ISO/IEC 60754-2: Acidity
c. ISO/IEC 61034-2: Smoke Density
9. 3rd Party verification of the Fire Safety/ Environmental tests listed above must
be provided as part of the bid response.
G. Face Plates
1. Faceplates shall be a single or double gang as identified on drawings, Jacks
shall be of the same manufacturer.
2. if required, to be coordinated with electrical contractor to match electrical
accessories finish
A. Provide hook and loop tape, 13mm Wide and of a length equal to 130% of the
circumference of the cable bundle.
B. Cable ties shall be of durable construction, UPVC a minimum of 6mm wide, and of a
length equal to 130% of the circumference of the cable bundle. Cable ties are to be
provided as per the recommendations of the cabling manufacturer.
C. When used in areas considered environmental air space, all bundling materials shall
be appropriately listed.
D. Cable bundles shall not to be over tightened such that deformation occurs to the
original geometry of the cables. Such practice will be rejected and damaged cables
shall be replaced at the Contractor’s cost.
E. Maximum 24 cables per bundle and cable wrap to be used to bundle the cable
F. the cable buddle is required all the way in the cable tray - from outlet to IDF /MDF
room
D. Trough Covers shall be provided for covering the patch cord field.
A. Comply with TIA-606-C and UL 969 for a system of labeling materials, including label
stocks, laminating adhesives, and inks used by label printers.
2.09 GROUNDING
C. Cable will be considered defective if it does not pass tests and inspections.
PART 3 - EXECUTION
A. Wiring Method: Install cables in raceways and cable trays except within consoles,
cabinets, desks, and counters. Conceal raceway and cables except in unfinished
spaces.
1. Install plenum cable in environmental air spaces, including plenum ceilings.
2. Comply with requirements for raceways and boxes specified in Division 26
Section "Raceway and Boxes for Electrical Systems."
B. Wiring within Enclosures: Bundle, lace, and train cables to terminal points with no
excess and without exceeding manufacturer's limitations on bending radii. Provide
and use lacing bars and distribution spools.
A. Comply with requirements for demarcation point, pathways, cabinets, and racks
specified in Division 27 Section " Communications Racks, Frames, and Enclosures."
Drawings indicate general arrangement of pathways and fittings.
B. Comply with ANSI/TIA-569-E for pull-box sizing and length of conduit and number of
bends between pull points.
C. Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical
Systems" for installation of conduits and wireways.
B. Open-Cable Installation:
1. Install cabling with horizontal and vertical cable guides in telecommunications
spaces with terminating hardware and interconnection equipment.
2. Suspend copper cable not in a wireway or pathway a minimum of 200 mm above
ceilings by cable supports not more than 1500 mm apart.
3. Cable shall not be run through structural members or in contact with pipes,
ducts, or other potentially damaging items.
3.04 FIRESTOPPING
3.05 GROUNDING
C. Locate grounding bus bar to minimize the length of bonding conductors. Fasten to
wall allowing at least 50-mm clearance behind the grounding bus bar. Connect
grounding bus bar with a minimum 25mm2 grounding electrode conductor from
grounding bus bar to suitable electrical building ground.
D. Bond metallic equipment to the grounding bus bar, using not smaller than 16mm2
equipment grounding conductor.
3.06 IDENTIFICATION
C. Paint and label colors for equipment identification shall comply with ANSI/TIA-606-B
for Class 2 level of administration, including optional identification requirements of this
standard.
D. Cable Schedule: Post in prominent location in each equipment room and wiring closet.
List incoming and outgoing cables and their designations, origins, and destinations.
Protect with rigid frame and clear plastic cover. Furnish an electronic copy of final
comprehensive schedules for Project.
G. Labels shall be preprinted or computer-printed type with printing area and font color
that contrasts with cable jacket color but still complies with requirements in ANSI/TIA-
606-C.
1. Cables use flexible vinyl or polyester that flex as cables are bent.
D. Document data for each measurement. Data for submittals shall be printed in a
summary report that is formatted similar to Table 10.1 in BICSI TDMM, or transferred
from the instrument to the computer, saved as text files, and printed and submitted.
E. End-to-end cabling will be considered defective if it does not pass tests and
inspections.
A. General
1. All testing shall conform to the latest release of the appropriate standards, the
manufacturer’s warranty criteria, and the project acceptance criteria.
2. The System Installer shall be responsible to repair or replace any cable that
does not meet specification with no additional cost to the project.
3. The System Installer shall review every test report for accuracy, completeness
and conformance to the Specifications.
4. After delivery of Materials to the Site, and prior to installation, all cables, cable
reels and shipping cartons shall be visually inspected to detect possible
damage incurred during the shipping and transport. Visibly damaged goods
should be immediately reported to the manufacturer for inspection.
5. All test results are required to be documented and submitted in hard copy
(summary only) and electronic (softcopy) format with the as-built
documentation.
6. The System Installer shall provide unaltered electronic test results submitted in
the original software format of the respective test equipment manufacturer. Text
files or files that have been imported into a word processor or other text editor
application shall not be acceptable.
KEO/19-3262-0000 27 1513/18 Communications Copper Horizontal Cabling
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
7. The Customer Representative retains the right to be present at any or all
testing. The System Installer shall provide due notice prior to the beginning of
the testing process.
8. Engineer reserves the right to mandate re-termination or other reasonable
rework to improve the performance of any cabling indicated as being a
“marginal pass”.
9. The owner should have the ability to retrieve the factory test result of any
installed cable on site by using a unique number printed on the cable jacket.
B. Copper Testing
1. The test equipment shall comply with the following standards:
a. Compliant with proposed ISO (IEC WG9 Standard IEC61935-1) Level V
accuracy requirements to 1000 MHz
b. Supports the complete suite of Resistance Unbalance standards needed
for Power over Ethernet (PoE) – IEC61935-1 & 11801-1-4, IEEE
802.3af, IEEE 802.3at, ANSI/TIA-568-2.D
c. Next generation balance drafts – IEEE 802.3, TIA TR42.7
Test Standards
TIA Cat 6A per TIA 568-2.D
ISO/IEC Class EA certification per ISO/IEC 11801:2002 and
amendments
3.09 TRAINING
D. Obtain employers staff signatures for attendance and submit as a record that the
training has been completed and to the satisfaction of the employer.
E. Distribute copies of the operation and maintenance manuals during the training and
go thru the content in details. Please note the copies distributed during the training are
not the official copies to submitted for close out purposes.
F. Schedule training with the Employer, through Engineer, with at least 14 days' advance
notice.
3.010 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the
installed system. During that period, the contractor shall be responsible for the regular
inspection and maintenance as recommended by the manufacturer.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for
the system and submit to the Engineer for his approval.
END OF SECTION
WIFI SYSTEM
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Contractor scope shall be limited to containment, draw wires, back boxes and
coordination with all other trades.
A. Wifi Layout Drawings (Plans and Details) and Wifi Schematic Diagram Drawings.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Contractor scope shall be limited to containment, draw wires, back boxes and
coordination with all other trades.
A. IP Data and Computer Layout Drawings (Plans and Details) and Schematic Diagram
Drawings.
END OF SECTION
AV SYSTEM
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Contractor scope shall be limited to containment, draw wires, back boxes and
coordination with all other trades.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Contractor scope shall be limited to containment, draw wires, back boxes and
coordination with all other trades.
A. SMATV, IPTV and Digital Information Display Layout Drawings (Plans and Details) and
System Schematic Diagram Drawings.
B. SMATV, IPTV and Digital Information Display System is identified in TV drawing series.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Contractor scope shall be limited to containment, draw wires, back boxes and
coordination with all other trades.
A. Queuing Management Layout Drawings (Plans and Details) and Schematic Diagram
Drawings.
END OF SECTION
GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. The contractor shall supply, install, test, connect and commission a high quality fast-
acting Paging and Professional Sound System.
B. The Paging and Prof. Sound System shall comprise of Digital audio matrix controller,
Active DSP lone array speaker, Wall mount column Speakers, Professional outdoor
Horn speaker, Power Amplifier ,16 channel Digital mixer console, Wired Microphones,
Wireless Microphone, Audio rack and Microphone Stand, AM/FM tuner and Blu- ray
player.
C. Prior to placing order for any equipment, the contractor shall submit comprehensive
document comprising working drawings, catalogues and descriptive literature of
components, acoustic Study (using EASE Program) to meet with STI requirements of
0.5 on the STI scale.
D. The contractor shall be required to train and instruct client's personnel in the correct
use, operation, and supervision of the system, preferably prior to the handing over of
the project.
E. The contractor shall make sure that all power tapping of the speakers must be carried
out as specified, even if the acoustic calculations indicate less power tapings.
F. The Contractor shall stick sharply to the approved brands list; alternative brands shall
not be acceptable
B. The Audio Rack shall be located where indicated on the layout drawing
C. The Main Audio control unit shall consist of Audio DSP control unit with 6 Mic/Aux
inputs. The unit shall have minimum 10 configurable MIC /AUX (LINE) (both balanced)
input, volume and bass / treble control for each input. It shall be 19” rack mountable
unit. It shall have the ability to internal electronic muting that works via control input
terminal.
D. Digital Audio matrix based public address controller shall route the signals as required.
The PA System rack shall contain at least one digital Signaling Audio matrix unit with
inbuilt Automatic Gain controller, Mixer and Matrix.
1.04 TESTING
A. The Contractor shall carry out the measurement of STI and SPL at the Pre-
Commissioning Stage and provide reports for the Engineer Approvals. The Contractor
shall insure minimum of 0.5 STI at 0% occupancy and minimum of 86dB across the
tested area +/- 3dB. The Back-Ground Noise, SPL testing must be carried out with
Calibrated Professional Tools. SPL testing must be carried out via Pink Noise insertion
into the system and measured over an average of 10 seconds.
PART 2 - PRODUCTS
A. The DSP shall contain minimum of 10 Speaker Circuits and the system shall be Digital
Signaling processor driven of 24bits of 48 KHz capable of audio processing for quality
sound reproduction for background as well as foreground music.
B. The DSP shall have up to 12 analogue control inputs. Each control can be associated
to any of the variable audio processing functions.
A. The Amplifier shall operate on 240 VAC and 24V DC input. The output stage utilizes
a specially wound transformer to allow full acoustic operation at high frequencies. The
Amplifier type shall be digital Class -D type.
B. Amplifier shall have electronic protection system against overcharge, short circuits,
and excessive heating. Besides, it shall include an energy savings system (STANDBY
mode) that automatically activates 30 seconds after detecting a lack of an input signal.
C. These units also have test inputs for connection of an ultrasonic remote control to test
the efficiency of connections. Balanced inputs allow the use of long cables without the
risk of humming or mains distortion.
C. Diversity Receiver
1. The unit shall operate within the UHF range 554 – 865MHz and the Working
range shall be 300ft (92 m) equipped with large LCD indicator and antenna.
2. The unit characteristics shall be:
f. Frequency response shall be 50 to 15 KHz
g. Dynamic range shall be > 105dB
h. RF sensitivity shall be 1.26 mW for 12dB
i. Image rejection shall be 65dB
j. Spurious rejection shall be 75dB
k. System distortion shall be 0.3% (<1%) THD typical
C. Boom stand for the Microphone should be supplied, with adjustable height.
D. The minimum specifications for the Audio mixer to be used in these facilities
E. shall be as follow:
1. 16-Channel Mixing Console
2. Max. 10 Mic / 16 Line Inputs (8 mono + 4 stereo)
3. 4 GROUP Buses + 1 Stereo Bus
4. 4 AUX (incl. FX)
5. “D-PRE” mic preamps with an inverted Darlington circuit
6. 1-Knob compressors
7. High-grade effects: SPX with 24 programs
8. 24-bit/192kHz 2in/2out USB Audio functions
9. Works with the iPad (2 or later) through the Apple iPad Camera Connection Kit
/ Lightning to USB Camera Adapter
10. Includes Cubase AI DAW software download version
11. PAD switch on mono inputs
12. +48V phantom power
13. XLR balanced outputs
14. Internal universal power supply for world-wide use
KEO/19-3262-0000 27 5116/1 Masjid Sound System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
15. Rack Mount Kit Included
16. Metal chassis
A. All central equipment shall be housed in 19” equipment racks sized to suit the proposed
equipment. Unused space shall be covered by 19” blanking panels. The equipment
racks shall provide the following features:
1. Welded steel frame
2. Front door
3. Steel and lockable Rear door
4. Steel and lockable Side panels
5. Transit castors
6. Leveling feet
7. Raised lid
8. Separate top plate for cable access
9. Field terminations on DIN terminals
10. At least 18U for Master voice alarm rack
A. 20-Watt Public Address Wall Mounted Column Speaker: The 20watts Wall mount column
speaker shall have the following as minimum specification:
1. 20W Rated power
2. 20W,10W, 5W & 2.5W Transformer tapings
3. Speaker shall be tapped at 30 Watts
4. 100V Line operation
5. 12Ω Driver impedance
6. 217Hz – 16.7kHz Effective frequency range
7. 100.3dB Sensitivity (1W/1m) peak
8. Dispersion (-6dB) @1kHz is 188º.
9. Dispersion (-6dB) @4kHz is 86º.
10. It shall be made in Europe.
B. 50watt Wall Mounted Column Speaker: The 50Watts Wall mount column speakers shall
have the following as minimum specification:
1. 50W Rated power
2. 50W,30W, 15W, 7.5W Transformer tapping’s
3. 100V Line operation
4. 8Ω Driver impedance
5. 110Hz – 18KHz frequency response
6. SPL @1m/1W peak shall be 102.8dB
7. 185-degree Dispersion horizontal angle @ 1kHz (-6 dB)
8. 33-degree dispersion vertical angle @ 1 KHz (-6 dB)
9. Color shall be RAL9006 ‘White Aluminium’
10. ABS Material
11. Indoor and Outdoor use.
12. IP 66 for Outdoor.
13. Materials shall be powder coated shock-resistant metal chassis and metal grille.
14. Mounting shall be using Swivel bracket.
C. Horn Speaker for Minaret: The Horn speaker for the Minaret shall have the following
as the minimum specifications:
KEO/19-3262-0000 27 5116/1 Masjid Sound System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. 60W Rated power
2. 60W, 30W ,15W Transformer tapping’s
3. Tapped at 60Watts.
4. 100V Line operation
5. 160 – 11000 Hz Effective frequency range
6. 110dB Sensitivity (1W/1m) 100Hz – 10kHz bandwidth
7. 128dB Sensitivity (60W/1m) 100Hz – 10kHz bandwidth
8. 50OOpening Angle
9. Aluminum alloy.
D. 6W Ceiling Speaker Frameless Type: The 6W full range BGM ceiling speaker shall
have the following specification:
1. The speaker shall give 92dBdB@1W/1m Average sensitivity.
2. 6Watt transformer for 6/3/1.5 volt or voice coil/8 Ohm Direct)
3. Frequency Response shall 56 –18000 Hz.
4. SPL at 1W/1m, peak shall be 97dB.
5. SPL Pmax/4m, peak shall be 92.7 dB
6. The unit shall have 6.5”full range driver with frameless front grill.
7. Dispersion -6dB, 500Hz h/v shall be 180°.
8. Dispersion -6dB, 1KHz h/v 180° shall be 175°.
9. Mounting type shall be Quick-mount clamp.
10. Speaker shall be of European or USA/Canada origin, fast east products shall
not be accepted.
1. The unit shall consist of a solid aluminum extrusion containing a linear driver
arrangement of 8 sources. The single cone full range drivers shall be a size of
4”.
2. The line array shall have an internal DSP and microcontroller where audio
signals shall be processed. The DSP shall have a 100dB SNR and 50 MIPS.
The Line array speaker shall be powered from the Class-D power amplifier
240W RMS output power. The new audio algorithms of the digital signal
processor shall allow to modify the sound diffusion, adapting the response to
the acoustical requirements of the installation
3. The Line array speaker shall have the following main features:
a. Manual lobe switching between configuration A or B
b. Constant direct SPL in all audience area.
c. Dual audio input: 0dB or L100V.
d. In & out XLR audio socket for daisy chain topology connection.
e. Electronic vertical dispersion manipulation.
f. VOX detection for automatic power switch.
g. Tone control: Bass & treble.
h. Volume control.
i. 15 band graphic equalizer.
j. Speech filter for increasing intelligibility.
k. Mute option.
4. The DSP shall provide powerful pre-processing on all audio input channels,
such as 14-band Graphical Equalization, pre-delay, audio mute, volume and
auto-gain.
5. The mechanical construction shall be based in aluminum to ensure many years
of Reliable operation in high humidity environments. In the power Consumption
shall be designed for an optimize Consumption with 3 states: ON, MUTE,
STANDBY.
6. The enclosure shall be made of extruded aluminum and finished in an epoxy
powder coating standardized on RAL 1015.
7. The complete Array shall meet the following criteria:
a. Frequency response shall be 80Hz to 20 kHz.
b. Power Amplifier shall be Class–D(PWM)
c. Amplifier output power shall be 240W RMS.
d. Max SPL shall be 90dB.
e. Input sensitivity line 0dB (XLR) shall be balanced /unbalanced 0dB.
f. Input sensitivity 100V (Euro block) shall be Balanced.
g. Programmer socket shall be RJ45
KEO/19-3262-0000 27 5116/1 Masjid Sound System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
h. Communication protocol shall be RS-485 half duplex.
i. Main voltage shall be 230VAC/ 50HZ.
j. Maximum power consumption shall be 400W
A. The Digital Audio Player shall be 19” rack mounted type where applicable. It shall be
equipped with a full function remote control with discs’ key and power ON/OFF. It shall
have independent Audio output and volume control for Music Player output and Radio
output.
B. The unit shall have two independent backlit LCD screens. One for control, navigation
in MP3 files and information on audio reproduction. The other screen shall show
information on the dial and selected pre-sets of the digital radio tuner.
PART 3 - EXECUTION
A. The Contractor should submit the Execution drawings along with the system proposal
for Client and Consultant approval within 30- 60 days from his appointment’s letter as
sub-contractor for MEP work.
3.02 INSTALLATION
A. The installer should ensure that all wiring complies with the following:
KEO/19-3262-0000 27 5116/1 Masjid Sound System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Method of cable support should be such that circuit integrity will not be reduced
below that afforded by the cable used, such as termination, distance, etc.
2. Installation of equipment and devices that pertain to other work in the contract
shall be closely coordinated with the appropriate subcontractors.
3. The manufacturer’s authorized representative shall provide onsite supervision
of installation.
4. Speakers’ Brackets, covers and connectors should be provided by the systems’
manufacturer.
3.04 WARRANTY;
A. The contractor shall warrant the complete system wiring and equipment to be free from
inherent mechanical and electrical defects for a period of one year from the date of the
complete and certified test (Final Commissioning)
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Contractor scope shall be limited to containment, draw wires, back boxes and
coordination with all other trades.
A. Public Address Layout Drawings (Plans and Details) and Schematic Diagram Drawings.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Work covered by this Section shall consist of furnishing labor, equipment, supplies,
materials, and testing unless otherwise specified, and in performing the following
operations recognized as necessary for the installation of the Standalone Emergency
Call System for Special Need Persons described on the Drawings and/or required by
these specifications.
B. Section Includes:
1. Alarm Controller
2. Door Light with sounder
3. Pull Cord
4. Reset Point
1.03 SUBMITTALS
C. Coordination Drawings: Detail system components that fit, match, and line up with
provisions made in equipment specified in other Sections or in separate contracts:
E. Field Tests Reports and Observations: Include record of final adjustments certified by
Installer.
C. Source Limitations: Obtain Emergency Call System for Special Need Persons
equipment through a single source authorized by manufacturer to distribute each
product.
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contact.
1.06 COORDINATION
A. Coordinate wiring paths and maintenance access at locations listed below. Coordinate
trim features and finishes at these locations to present a unified design appearance.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Spare parts required shall include but not necessarily be limited to,
1. Alarm Controller: 1 no.
2. Door Light with sounder – 1 no.
3. Pull Cord – 1 no.
4. Reset Point – 1 no.
5. Tools required for maintenance.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Alarm Controller
KEO/19-3262-0000 27 5223/3 Emergency Call System for Special Need Persons
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. The Alarm Controller shall form the heart of the disabled toilet alarm system and
shall be provided complete power supply & alarm unit in one.
2. Under normal conditions, the Alarm Controller ‘on’ LED shall illuminate orange
and the sounder and LED shall be off. When the Ceiling Pull Switch is activated
within the toilet area, the Alarm Controller audible sounder and high visibility LED
shall operate. The Overdoor Light / Sounder shall operate, simultaneously. The
call may be reset at the Alarm Controller and/or at the Reset Point within the
toilet, depending on system configuration.
B. Door Light
1. Door lights shall be local alarm annunciators.
2. This unit shall be mounted on a wall at a strategic location outside the toilet to
attract attention in the event of an alarm.
3. Door light shall be fitted with Red and Green LED’s which mimic the re-
assurance indicator on the call points. The unit shall be fully addressable and
only connects to the Network. The unit shall be provided with 2 sets of DIL
switches, and the unit will respond to any device between the Lower and Higher
device address. The unit shall be with an integral sounder.
C. Pull Cord
1. Pull cords shall be used by users to activate disabled toilets alarms.
2. Pull cords shall be mounted inside the toilet to enable users to call for assistance.
3. They shall be fitted with 3 metre length of cord terminated with an easy to
operate ‘G’ style pull and twin re-assurance indicators.
D. Reset Point
1. Reset points shall be used to reset activated disabled toilets alarms.
2. These points shall be mounted on the wall inside toilet to try to ensure that an
operator attends the location in response to an alarm.
3. Reset points shall be fitted with vandal resistant reset buttons.
PART 3 - EXECUTION
3.01 INSTALLATIONS
D. Install exposed raceways and cables parallel and perpendicular to surfaces or exposed
structural members and follow surface contours. Secure and support cables by straps,
staples, or similar fittings designed and installed so as not to damage cables.
E. Splices, Taps, and Terminations: Make splices, taps, and terminations on numbered
terminal strips in junction, pull, and outlet boxes, terminal cabinets, and equipment
KEO/19-3262-0000 27 5223/4 Emergency Call System for Special Need Persons
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
enclosures. Install terminal cabinets where there are splices, taps, or terminations for
eight or more conductors.
F. Impedance and Level Matching: Carefully match input and output impedances and
signal levels at signal interfaces. Provide matching networks if required.
3.02 GROUNDING
A. Comply with requirements in Division 26 - Earthing and Bonding for Electrical Systems"
for grounding conductors and connectors.
C. Retesting: Rectify deficiencies indicated by tests and completely retest work affected by
such deficiencies at Contractor's expense. Verify by the system test that the total
system meets these Specifications and complies with applicable standards. Report
results in writing.
D. Inspection: Verify that units and controls are properly labeled, and interconnecting wires
and terminals are identified.
3.04 DEMONSTRATION
3.05 MAINTENANCE
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Architect/ Engineer for approval.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Contractor scope shall be limited to containment, draw wires, back boxes and
coordination with all other trades.
A. Access Control System Layout Drawings (Plans and Details) and Schematic Diagram
Drawings.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Contractor scope shall be limited to containment, draw wires, back boxes and
coordination with all other trades.
A. Parking Guidance System Layout Drawings (Plans and Details) and Schematic Diagram
Drawings.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Contractor scope shall be limited to containment, draw wires, back boxes and
coordination with all other trades.
A. Security Video Surveillance System (CCTV) Layout Drawings (Plans and Details) and
Security Video Surveillance System (CCTV) Schematic Diagram Drawings.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. This Section includes the requirements for the installation, programming and
configuration of a complete intelligent analogue addressable network-based fire
detection and alarm system. The system shall include, but is not limited to:
1. Fire alarm control panel(s) including power supplies, battery chargers and
batteries.
2. Automatic and manually activated alarm initiating and notification devices and
appliances.
3. Automatic supervision devices and modules.
4. Automatic and manually activated voice evacuation subsystem.
5. Remote annunciator(s).
6. Conduits, wires and accessories required to furnish a complete and operational
system.
7. All conduit, wiring and accessories required to provide power to, and interconnect
with, devices supplied through other divisions including:
a. Electric and magnetic door holders.
b. Sprinkler system flow switches and supervisory switches.
c. Sprinkler system electrical and diesel pumps and fire water tanks.
d. Fire suppression system panels.
e. Elevator status and recall control panels.
f. Air handling units.
g. Smoke dampers and fans related to smoke control.
h. Electrical generator monitoring.
8. Equipment and labor not specifically referred to herein or on the plans, but which
are required to meet the functional intent of the system, shall be provided without
additional cost to the Owner. Refer to the tender drawings for the specific details.
9. Interface with BAS
10. Interface with Public address system
11. Interface with Elevators
12. Interface with Audio visual system
1.03 DEFINITIONS
A. All work, materials, and equipment shall comply with the rules and regulations of all
codes and ordinances of the local, state, and federal authorities having jurisdiction.
Such codes, when more restrictive, shall take precedence over these plans and
specifications. The specifications and standards listed below form part of this
specification. The system shall fully comply with the latest issue of these standards, if
applicable.
1. National Fire Protection Association (NFPA)
a. NFPA72—National Fire Alarm Code
b. NFPA101—Life Safety Code
c. NFPA13—Sprinkler Systems
2. Underwriters Laboratories (UL)
a. UL 864—UOJZ Control Units for Fire Protective Signaling Systems
b. UL 268—Smoke Detectors for Fire Protective Signaling Systems
c. UL 268A—Smoke Detectors for Duct Applications
d. UL 217—Smoke Detectors Single Station
e. UL 521—Heat Detectors for Fire Protective Signaling Systems
f. UL 228—Door Holders for Fire Protective Signaling Systems
g. UL 464—Audible Signaling Appliances
h. UL 1638—Visual Signaling Appliances
i. UL 38—Manually Activated Signaling Boxes
j. UL 346—Water flow Indicators for Fire Protective Signaling Systems
k. UL 1481—Power Supplies for Fire Protective Signaling Systems
l. UL 1711—Amplifiers for Fire Protective Signaling Systems
3. Local Civil Defense Department/ Fire Department (KFF) requirements.
B. System shall be listed by the national agencies as suitable for extinguishing release
applications. The system shall support release of high and low pressure CO2.
E. Supervisory signal initiation shall be by one or more of the following devices or actions:
1. Operation of a fire-protection system valve tamper.
2. Fire Pump
3. Generator
F. System trouble signal initiation shall be by one or more of the following devices or
actions:
1. Open circuits, shorts and grounds of wiring for initiating device, signaling line,
and notification-appliance circuits.
2. Opening, tampering, or removal of alarm-initiating and supervisory signal-
initiating devices.
3. Loss of primary power at the FACP.
4. Ground or a single break in FACP internal circuits.
5. Abnormal ac voltage at the FACP.
6. A break in standby battery circuitry.
7. Failure of battery charging.
8. Abnormal position of any switch at the FACP or annunciator.
9. Fire-pump power failure, including a dead-phase or phase-reversal condition.
10. Low-air-pressure switch operation on a dry-pipe or preaction sprinkler system.
G. System Trouble and Supervisory Signal Actions: Ring trouble bell and annunciate at the
FACP and remote annunciator (repeater). Record the event on system printer.
H. System shall be capable of Control By Events programming and other special features
like cross-zoning, co-operative multitasking for decision making, etc.
A. Environmental Limitations: Do not deliver or install cables and connecting materials until
wet work in spaces is complete and dry, and temporary HVAC system is operating and
maintaining ambient temperature and humidity conditions at occupancy levels during the
remainder of the construction period.
A. Notwithstanding the drawings and other information provided to the Contractor, the
Contractor shall be fully responsible for the Fire Alarms and Heat Detectors System i.e.
final design, detailing of the works described herein, including (without limitation) the
comprehensive engineering analysis by a qualified professional engineer, shall provide
a complete, and secure installation for heat detectors, coordination with all services
above the false ceiling ,kitchen appliances which shall meet the specified performance
and General design requirements as indicated in Contract Documents drawings
,Specifications and which shall be fit for their intended purpose. The Contractor shall
indemnify the Employer and Design Consultant from any and all claims, costs and
expenses arising from any loss or damage in connection with any error in or failure of
the Contractor’s designed portion of the Works.
1.09 SUBMITTALS
B. Shop Drawings:
1. Shop Drawings shall be prepared by persons with the following qualifications:
a. Trained and certified by manufacturer in fire alarm system design.
b. Certified by CDD
2. System Operation Description: Provide detailed description for this Project,
including method of operation and supervision of each type of circuit and
sequence of operations for manually and automatically initiated system inputs
and outputs. Manufacturer's standard descriptions for generic systems are not
acceptable.
3. Device Address List: Coordinate with final system programming.
4. Provide System riser diagram with device addresses, conduit sizes, and cable
and wire types and sizes.
5. Wiring Diagrams: Power, signal, and control wiring. Include diagrams for
equipment and for system with all terminals and interconnections identified.
Show wiring color code.
KEO/19-3262-0000 28 3100/4 Fire Detection and Alarm System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
6. Batteries: Provide size calculations.
7. Duct Smoke Detectors: Provide performance parameters and installation details
for each detector, verifying that each detector is listed for the complete range of
air velocity, temperature, and humidity possible when air-handling system is
operating.
8. Ductwork Coordination Drawings: Provide Plans, sections, and elevations of
ducts, drawn to scale and coordinating the installation of duct smoke detectors
and access to them. Show critical dimensions that relate to placement and
support of sampling tubes, the detector housing, and remote status and alarm
indicators. Locate detectors according to manufacturer's written
recommendations.
9. Floor Plans: Indicate final outlet locations showing address of each addressable
device. Show size and route of cable and conduits.
10. Provide Voltage drop calculations for wiring runs indicating cumulative current
draw and voltage drop from the panel to the last device in the loop
11. Provide cause and effect matrix.
12. Provide Mimic panel details.
E. Provide Operation and Maintenance Data for fire alarm system to include in emergency,
operation, maintenance manuals and daily, weekly, monthly, semiannual, annual
maintenance schedule. Comply with NFPA 72, Appendix A, recommendations for
Owner's manual. Include abbreviated operating instructions for mounting at the FACP.
G. Documentation:
1. Approval and Acceptance: Provide the "Record of Completion" form according to
NFPA 72 to Architect, and authorities having jurisdiction.
2. Record of Completion Documents: Provide the "Permanent Records" according
to NFPA 72 to Architect, and authorities having jurisdiction. Format of the written
sequence of operation shall be the optional input/output matrix.
a. Provide 8 colored Hard copies on paper to Architect, and authorities
having jurisdiction.
b. Provide 3 sets of Electronic media copies to Architect and authorities
having jurisdiction.
A. Installer Qualifications:
1. Installer must possess a valid License and have a minimum of 5 years’
experience in the business of installing fire alarm systems.
2. Installer shall be the manufacturer or a local authorized representative of the
manufacturer with a proven track record of being responsive, providing accurate
and complete submittals, meeting project schedules, and being prepared for
system testing and acceptance.
KEO/19-3262-0000 28 3100/5 Fire Detection and Alarm System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Installer shall be able to provide a fully equipped and qualified factory-trained
repair technician at the job site for any request for emergency services within the
time stipulated under Guarantee. This service shall be available 24 hours a day
during the term of warranty.
4. Installer shall furnish evidence that the fire alarm equipment supplier has an
experienced and effective service organization, which carries a stock of repair
parts for the system to be furnished. The installer must be able to provide any
replacement part on site within 48 hours during the warranty period.
C. Personnel shall be trained and certified by manufacturer for installation of units required
for this Project
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
C. Spare parts required shall include but not necessarily be limited to,
1. Lamps for Remote Indicating Lamp Units: Quantity equal to 10 percent of
amount installed, but not less than 1 unit.
2. Lamps for Strobe Units: Quantity equal to 10 percent of amount installed, but not
less than 1 unit.
3. Smoke, Heat, and Flame Detectors: Quantity equal to 10 percent of amount of
each type installed, but not less than 1 unit of each type.
4. Detector Bases: Quantity equal to 2 percent of amount of each type installed,
but not less than 1 unit of each type.
5. Keys and Tools: One extra set for access to lock and tamper proofed
components.
6. Audible and Visual Notification Appliances: One of each type installed.
7. Fuses: Two of each type installed in the system.
8. Manual Call Points: Quantity equal to 10 percent of amount installed, but not less
than 1 unit.
9. Spare parts recommended by manufacturer.
10. Tools recommended by the manufacturer.
B. All components and their installations shall be free from defects. Any defective material
or workmanship and any resulting damage to work of other trades shall be replaced or
repaired as directed during the Warranty Period at the contactors expense. Comply with
General Conditions, agreeing to repair or replace any components that have failed
within the warranty period.
PART 2 - PRODUCTS
A. General Description:
1. Fully automatic fire detection and alarm as described in detail in this section and
as shown on the drawings. Fire alarm Contractor should coordinate with other
Contractors for number of points, signal, controls and compatibility, so that the
system should be able to monitor, control and graphics for all points and
functions.
2. Modular, power-limited design with electronic modules, UL 864 listed.
3. Addressable initiation devices that communicate device identity and status.
a. Smoke sensors shall additionally communicate sensitivity setting and
allow for adjustment of sensitivity at the FACP.
b. Temperature sensors shall additionally test for and communicate the
sensitivity range of the device.
4. Addressable control circuits for operation of mechanical equipment.
B. Alphanumeric Display and System Controls: Arranged for interface between human
operator at the FACP and addressable system components including annunciation and
supervision. Display alarm, supervisory, and component status messages and the
programming and control menu.
1. Annunciator and Display: Liquid-crystal type, three line(s) of 80 characters,
minimum.
2. Keypad: Arranged to permit entry and execution of programming, display, and
control commands; and to indicate control commands to be entered into the
system for control of smoke-detector sensitivity and other parameters.
E. Circuits:
1. Signaling Line Circuits: NFPA 72, Class A.
a. System Layout: Each signaling line circuit would be not be loaded more
than 70% of its recommended capacity. See NFPA 72, Table 3-7, for
selection criteria.
2. Notification-Appliance Circuits: NFPA 72, Class A.
3. Actuation of alarm notification appliances, annunciation, smoke control, elevator
recall, and actuation of suppression systems shall occur within 10 seconds after
the activation of an initiating device.
4. Electrical monitoring for the integrity of wiring external to the FACP for
mechanical equipment shutdown and magnetic door-holding circuits is not
required, provided a break in the circuit will cause doors to close and mechanical
equipment to shut down.
F. Smoke-Alarm Verification:
1. Initiate audible and visible indication of an "alarm verification" signal at the FACP.
2. Activate a listed and approved "alarm verification" sequence at the FACP and the
detector.
3. Record events by the system printer.
4. Sound general alarm if the alarm is verified.
5. Cancel FACP indication and system reset if the alarm is not verified.
H. Elevator Controls: Heat detector operation shuts down elevator power by operating a
shunt trip in a circuit breaker feeding the elevator.
J. Power Supply for Supervision Equipment: Supply for audible and visual equipment for
supervision of the ac power shall be from a dedicated dc power supply, and power for
the dc component shall be from the ac supply.
K. Alarm Silencing, Trouble, and Supervisory Alarm Reset: Manual reset at the FACP after
initiating devices are restored to normal.
L. Walk Test: A test mode to allow one person to test alarm and supervisory features of
initiating devices. Enabling of this mode shall require the entry of a password. The
FACP and annunciators shall display a test indication while the test is underway. If
testing ceases while in walk-test mode, after a preset delay, the system shall
automatically return to normal.
O. Service Modem: Ports shall be RS-232 for system printer and for connection to a dial-in
terminal unit.
1. The dial-in port shall allow remote access to the FACP for programming changes
and system diagnostic routines. Access by a remote terminal shall be by
encrypted password algorithm.
P. Printout of Events: On receipt of signal, print alarm, supervisory, and trouble events.
Identify zone, device, and function. Include type of signal (alarm, supervisory, or
trouble), and date and time of occurrence. Differentiate alarm signals from all other
printed indications. Also print system reset event, including the same information for
device, location, date, and time. Commands initiate the printing of a list of existing
alarm, supervisory, and trouble conditions in the system and a historical log of events.
Q. Primary Power: 24-V dc obtained from 220-V ac service and a power-supply module.
Initiating devices, notification appliances, signaling lines, trouble signal, supervisory
signal, supervisory and digital alarm communicator transmitter and shall be powered by
the 24-V dc source.
1. The alarm current draw of the entire fire alarm system shall not exceed 80
percent of the power-supply module rating.
2. Power supply shall have a dedicated fused safety switch for this connection at
the service entrance equipment. Paint the switch box red and identify it with
"FIRE ALARM SYSTEM POWER."
R. Secondary Power: 24-V dc supply system with batteries and automatic battery charger
and an automatic transfer switch.
1. Batteries: Battery shall be of the sealed, maintenance free type, 24-volt nominal
Vented, wet-cell pocket, plate nickel cadmium sized with 25 percent reserve
capacity for future expansion.
S. Surge Protection:
1. Install surge protection on normal ac power for the FACP and its accessories.
Comply with Division 26 Section "Transient-Voltage Suppression for Low-Voltage
Electrical Power Circuits" for auxiliary panel suppressors.
2. Install surge protectors recommended by FACP manufacturer. Install on all
system wiring external to the building housing the FACP.
A. General Description:
1. UL 268 listed/, operating at 24-V dc, nominal.
2. Integral Addressable Module: Arranged to communicate detector status (normal,
alarm, or trouble) to the FACP.
3. Plug-in Arrangement: Detector and associated electronic components shall be
mounted in a plug-in module that connects to a fixed base. Provide terminals in
the fixed base for connection of building wiring.
4. Self-Restoring: Detectors do not require resetting or readjustment after actuation
to restore them to normal operation.
5. Integral Visual-Indicating Light: LED type. Indicating detector has operated and
power-on status.
6. Remote Control: Unless otherwise indicated, detectors shall be analog-
addressable type, individually monitored at the FACP for calibration, sensitivity,
and alarm condition, and individually adjustable for sensitivity from the FACP.
a. Rate-of-rise temperature characteristic shall be selectable at the FACP for
8 or 11 deg C per minute.
KEO/19-3262-0000 28 3100/10 Fire Detection and Alarm System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
b. Fixed-temperature sensing shall be independent of rate-of-rise sensing
and shall be settable at the FACP to operate at 57 or 68 deg C.
c. Provide multiple levels of detection sensitivity for each sensor.
C. Multi-Criteria Detector
1. Heat sensor, combination rate-of-rise and fixed temperature
2. Photoelectric Smoke sensor - Detector Sensitivity shall be between 0.008 and
0.011 percent/mm smoke obscuration when tested according to UL 268A / KFF
approved.
D. Beam-Type Smoke Detector: Each detector shall have the following features:
1. The projected beam type smoke detector shall be listed to UL 268 listed and
shall consist of up to two integrated transmitters, receiver detector heads and
single low level remote control unit.
2. The beam detector heads shall include an integral built-in laser pointer to assist
prism mounting.
3. The beam detector shall feature automatic gain control which will compensate for
gradual signal deterioration from dirt accumulation on the lenses.
4. The beams detector heads shall include self-correcting motorized head feature to
ensure unit is always receiving maximum signal available and shall automatically
compensate for building shift.
5. The unit shall include a low level remote display and control unit with LCD read-
out for set-up, reporting and testing of up to two separate detector heads.
6. The system shall be capable of programming alarm thresholds of 10% to 60% in
1% increments. The system shall be capable of programming delay to fault and
delay to alarm from 2 seconds to 30 seconds in 1 second increments.
7. Test and acceptance of the system shall be carried out by using the UL approved
internal electronic obscuration fire test. The projected beam type smoke detector
shall be a 4-wire 24 VDC device
D. Continuous Linear Heat-Detector System: Consists of detector cable and control unit.
1. Detector Cable: Rated detection temperature 68 deg C. Listed for "regular"
service and a standard environment. Cable includes two steel actuator wires
twisted together with spring pressure, wrapped with protective tape, and finished
with PVC outer sheath. Each actuator wire is insulated with heat-sensitive
material that reacts with heat to allow the cable twist pressure to short circuit
wires at the location of elevated temperature.
2. Control Unit: Two-zone or multi-zone unit as indicated. Provides same system
power supply, supervision, and alarm features as specified for the central FACP.
3. Signals to the Central FACP: Any type of local system trouble is reported to the
central FACP as a composite "trouble" signal. Alarms on each detection zone
are individually reported to the central FACP as separately identified zones.
A. Ultraviolet type with solid-state amplifier-switching circuit set for 10-second delay, unless
otherwise indicated.
1. Mounting: Plug-in base, interchangeable with smoke-detector bases.
2. Integral Addressable Module: Arranged to communicate detector status (normal,
alarm, or trouble) to the FACP.
A. LPG Gas Detector 0-100% LEL, 4-20mA - Catalytic sensor - Explosion Proof Enclosure,
IP 65
B. The gas detector has a 12-24 Vdc power supply and a standard 4-20 mA 3-wiresoutput
and three relays
A. Description: Equipped for mounting as indicated and with screw terminals for system
connections.
1. Combination Devices: Factory-integrated audible and visible devices in a single-
mounting assembly.
B. Bells: Electric-vibrating, 24-V dc, under-dome type; with provision for housing the
operating mechanism behind the bell. Bells shall produce a sound-pressure level of 94
dBA, measured 3 m from the bell. 254-mm size, unless otherwise indicated. Bells are
weatherproof where indicated.
C. Sounders Horns: Electric-vibrating-polarized type, 24-V dc; with provision for housing
the operating mechanism behind a grille. Horns shall produce a sound-pressure level of
90 dBA, measured 3 m from the horn.
D. Strobes Visible Alarm Devices: Xenon strobe lights listed under UL 1971, with clear or
nominal white polycarbonate lens mounted on an aluminum faceplate. The word "FIRE"
is engraved in minimum 25-mm- high letters on the lens.
1. Rated Light Output: Candela Level as noted in the drawings..
2. Strobe Leads: Factory connected to screw terminals.
A. Remote status and alarm indicator and test stations, with LED indicating lights. Light is
connected to flash when the associated device is in an alarm or trouble mode. Lamp is
flush mounted in a single-gang wall plate. A red, laminated, phenolic-resin identification
plate at the indicating light identifies, in engraved white letters, device initiating the
signal and room where the smoke detector or valve is located. For water-flow switches,
A. Description: Units are equipped for wall or floor mounting as indicated and are complete
with matching door plate.
1. Electromagnet: Requires no more than 3 W to develop 111-N holding force.
2. Wall-Mounted Units: Flush mounted, unless otherwise indicated.
3. Rating: 24-V ac or dc.
4. Rating: 240V ac.
A. Provide Remote LCD Annunciator with the same “look and feel” as the FACP operator
interface. The Remote LCD Annunciator shall use the same Primary Acknowledge,
Silence, and Reset Keys, Status LEDs and LCD Display as the FACP.
B. Annunciator shall have super-twist LCD display with two lines of 40 characters each.
Annunciator shall be provided with four (4) programmable control switches and
associated LEDs.
C. Under normal conditions the LCD shall display a “SYSTEM IS NORMAL” message and
the current time and date.
E. The LCD shall display the following information relative to the abnormal condition of a
point in the system:
1. 40 character custom location label.
2. Type of device (e.g., smoke, pull station, water flow).
3. Point status (e.g., alarm, trouble).
F. Operator keys shall be key switch enabled to prevent unauthorized use. The key shall
only be removable in the disabled position. Acknowledge, Silence and Reset operation
shall be the same as the FACP.
A. The mimic panel will be similar in style and finish to the control panel and be available in
A4 sized formats. It will be sighted in a conspicuous and well-lit area, preferably the
entrance where the fire-fighting team will arrive.
B. The panel will be a standard unit will all site specific information being programmed “on
site”, this information will be held on an EPROM integrated circuit, which may be
modified at a later date to encompass any site changes.
D. Should a full discharge of the cells take place, then the system shall be capable of
completely re-charging the cell within a 24hr period.
E. The mimic panels shall be connected on the same 2-wire loop as the sensors and
sounders. Also within the panel, terminals will be provided to allow a loop spur
connection to be made as standard.
F. A CAD drawing of the area covered by the system shall locate between clear perspex
sheets and retained within the mimic lid, overlaying an array of hi-brightness LEDs. This
provides pin-point accuracy in determining the location of a fire and the flexibility to tailor
the Customers’ requirements.
A. Shall connect one supervised initiating device circuit or zone of conventional alarm
initiating devices (any normally open dry contact device) to the fire alarm control panel
signaling line circuit Loop.
C. The modules shall provide address-setting means on the module using rotary switches
or using neuron ID. The modules shall also store an internal identifying code that the
control panel shall use to identify the type of module.
D. The Monitor module shall be with1 input / 2 input / 3 input as indicated in drawings
F. The module shall have an LED that is controlled by the panel to indicate module status.
Coded signals, transmitted from the panel, can cause the LED to blink, latch on, or latch
off.
H. The module shall mount in a standard electrical box or to a surface mounted backbox.
I. The module will use SEMS screws for easy wiring. Wiring terminals shall be easily
accessible for troubleshooting without removal from electrical box.
A. Addressable relay modules shall allow a compatible control panel to switch discrete
contacts by code command.
B. The relay module shall provide Form-C contacts rated for a minimum of 2.0 Amps
resistive or 1.0 Amps inductive , which operate as a double pole double throw switch.
The module shall allow the control panel to switch these contacts on command.
C. The module shall not provide supervision for the notification appliance circuit (NAC).
D. Module shall have both normally open and normally closed connections available for
field wiring.
E. The modules shall provide address-setting means on the module using rotary switches
or using neuron ID . The modules shall also store an internal identifying code that the
control panel shall use to identify the type of module.
F. The module shall have an LED that is controlled by the panel to indicate module status.
Coded signals, transmitted from the panel, can cause the LED to blink, latch on, or latch
off.
H. The module shall mount in a standard electrical box or to a surface mounted backbox.
I. The module will use SEMS screws for easy wiring. Wiring terminals shall be easily
accessible for troubleshooting without removal from electrical box.
B. The disconnection of the supervision shall provide verification to the panel that the
control relay state changed.
C. The external power supply shall always be relay isolated from the communication loop.
D. The control module shall transmit full analog measurement of the supervised wiring
back to the panel and can be used to detect impedance changes or other special test
functions.
G. The module shall have an LED that is controlled by the panel to indicate module status.
Coded signals, transmitted from the panel, can cause the LED to blink, latch on, or latch
off.
I. The module shall mount in a standard electrical box or to a surface mounted backbox.
J. The module will use SEMS screws for easy wiring. Wiring terminals shall be easily
accessible for troubleshooting without removal from electrical box
A. On/Auto/Off switches and status indicators (LEDS) shall be provided for monitoring and
manual control of each fan, damper, HVAC control unit, stairwell pressurization fan, and
smoke exhaust fan. To ensure compliance the units supplied shall meet the following UL
categories: UUKL, PAZX, UDTZ, QVAX as well as the requirements of NFPA 90A,
HVAC, and NFPA 92 & 92, Smoke Control. The control System shall be field
programmable for either NFPA 90A operation or NFPA 92 operation to allow for future
use and system expansion.
A. The OFF LED shall be Yellow, the ON LED shall be green, the Trouble/Fault LED shall
be Amber/Orange for each switch. The Trouble/Fault indicator shall indicate a trouble in
the control and/or monitor points associated with that switch. In addition, each group of
eight switches shall have two LEDS and one momentary switch which allow the
following functions: An Amber LED to indicate an OFF-NORMAL switch position, in the
ON or OFF position; A Green LED to indicate ALL AUTO switch position; A Local
Acknowledge/Lamp Test momentary switch.
B. Each switch shall have the capability to monitor and control two addressable inputs and
two addressable outputs. In all modes, the ON and OFF indicators shall continuously
follow the device status not the switch position. Positive feedback shall be employed to
verify correct operation of the device being controlled. Systems that indicate on/off/auto
by physical switch position only are not acceptable.
C. All HVAC switches (i.e., limit switches, vane switches, etc.) shall be provided and
installed by the HVAC contractor.
D. It shall be possible to meet the requirements mentioned above utilizing wall mounted
custom graphic.
B. BACnet Gateway
1. The BACnet Gateway shall utilize a Windows based operating system.
TheBACnet Gateway shall provide an interface between Fire Alarm Control
Panels and clients using BACnet/IP communications protocol.
2. The clients will be required to subscribe to Event Notification objects per FACP
andwill receive device information as BACnet objects via the subscription.
3. The BACnet Gateway shall be compatible with the FACP panels.
4. The BACnet Gateway shall monitor a single via the NUP port or monitor up to 14
nodes on the dedicated with a maximum combined object count of 15,000.
Multiple BACnet Gateways can be used for networks with more than 15 nodes
total.
5. The BACnet Gateway shall be PC programmable using the BACnet Gateway
6. Configuration Tool on a compatible computer that is using Windows® XP
Operating System.
C. Modbus Gateway
1. The Modbus Gateway shall utilize a Windows based operating system. The
Modbus Gateway provides a communications link between networks that use the
Modbus/TCP communications protocol and the FACP resident on a Fire network.
The Modbus protocol will be consistent with Modbus Application Protocol
Specification v1.1b.
2. The Modbus Gateway shall be compatible with the FACPs.
3. The Modbus Gateway shall monitor up to four compatible Fire network nodes
and provide data such as event type, active/ inactive, enabled/disabled,
acknowledged/ unacknowledged, device type, analog value (4-20mA module
only) and system troubles.
4. The Modbus Gateway will support reads of up to 100 registers at a time for digital
5. Values and 10 registers reads at a time for analog values.
KEO/19-3262-0000 28 3100/18 Fire Detection and Alarm System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
6. The Modbus Gateway Configuration Tool, using a Windows® XP Operating
7. System compatible computer, will be used to configure the Modbus Gateway.
A. Wire and cable for fire alarm systems shall be Fire Rated as per Local Civil Defense
requirements.
B. The wire and cable should Low smoke Zero Halogen type.
PART 3 - EXECUTION
B. HVAC: Locate detectors not closer than one meter from air-supply diffuser or return-air
opening.
C. Heat Detectors in Elevator Shafts: Coordinate temperature rating and location with
sprinkler rating and location.
D. Single-Station Smoke Detectors: Where more than one smoke alarm is installed within
a dwelling or suite, they shall be connected so that the operation of any smoke alarm
causes the alarm in all smoke alarms to sound.
E. Remote Status and Alarm Indicators: Install near each smoke detector and each
sprinkler water-flow switch and valve-tamper switch that is not readily visible from
normal viewing position.
F. Audible Alarm-Indicating Devices: Install not less than 150 mm below the ceiling. Install
bells and horns on flush-mounted back boxes with the device-operating mechanism
concealed behind a grille.
G. Device Location-Indicating Lights: Locate in public space near the device they monitor.
H. FACP: Surface mount with tops of cabinets not more than 1800 mm above the finished
floor.
I. Annunciator (Repeater): Install with top of panel not more than 1800 mm above the
finished floor
A. Wiring Method:
1. Cables and raceways used for fire alarm circuits, and equipment control wiring
associated with the fire alarm system, may not contain any other wire or cable.
2. Fire-Rated Cables: Use of 2-hour fire-rated fire alarm cables.
KEO/19-3262-0000 28 3100/19 Fire Detection and Alarm System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Signaling Line Circuits: Power-limited fire alarm cables shall not be installed in
the same cable or raceway as signaling line circuits unless separated properly as
recommended by the manufacturer.
C. Cable Taps: Use numbered terminal strips in junction, pull, and outlet boxes, cabinets,
or equipment enclosures where circuit connections are made.
D. Color-Coding: Color-code fire alarm conductors differently from the normal building
power wiring. Use one color-code for alarm circuit wiring and a different color-code for
supervisory circuits. Color-code audible alarm-indicating circuits differently from alarm-
initiating circuits. Use different colors for visible alarm-indicating devices. Paint fire
alarm system junction boxes and covers red.
E. Risers: Install at least two vertical cable risers to serve the fire alarm system. Separate
risers in close proximity to each other with a minimum 1-hour-rated wall, so the loss of
one riser does not prevent the receipt or transmission of signals from other floors or
zones.
F. Wiring to Remote Alarm Transmitting Device: 25-mm conduit between the FACP and
the transmitter. Install number of conductors and electrical supervision for connecting
wiring as needed to suit monitoring function.
3.03 IDENTIFICATION
3.04 GROUNDING
A. Ground the FACP and associated circuits. Install a ground wire from main service
ground to the FACP.
B. Perform the following field tests and inspections and prepare test reports:
1. Before requesting final approval of the installation, submit a written statement
using the form for Record of Completion shown in NFPA 72.
KEO/19-3262-0000 28 3100/20 Fire Detection and Alarm System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Perform each electrical test and visual and mechanical inspection listed in
NFPA 72. Certify compliance with test parameters. All tests shall be conducted
under the direct supervision of a NICET technician certified under the Fire Alarm
Systems program at Level III.
3. Visual Inspection: Conduct a visual inspection before any testing. Use as-built
drawings and system documentation for the inspection. Identify improperly
located, damaged, or nonfunctional equipment, and correct before beginning
tests.
4. Testing: Follow procedure and record results complying with requirements in
NFPA 72.
a. Detectors that are outside their marked sensitivity range shall be replaced.
5. Test and Inspection Records: Prepare according to NFPA 72, including
demonstration of sequences of operation.
3.06 ADJUSTING
B. Follow-Up Tests and Inspections: After date of Substantial Completion, test the fire
alarm system complying with testing and visual inspection requirements in NFPA 72.
Perform tests and inspections listed for three monthly, and one quarterly, periods.
C. Semiannual Test and Inspection: Six months after date of Substantial Completion, test
the fire alarm system complying with the testing and visual inspection requirements in
NFPA 72. Perform tests and inspections listed for monthly, quarterly, and semiannual
periods. Use forms developed for initial tests and inspections.
D. Annual Test and Inspection: One year after date of Substantial Completion, test the fire
alarm system complying with the testing and visual inspection requirements in NFPA 72.
Perform tests and inspections listed for monthly, quarterly, semiannual, and annual
periods. Use forms developed for initial tests and inspections.
A. The complete installation shall be tested and commissioned by the supplier and the
contractor. The contractor shall be responsible to demonstrate the operation of the
system to the satisfaction of the Client's personnel. The contractor shall submit the
testing and commissioning reports for the Engineers review outlining all deficiencies and
course of action. The contractor shall ensure all deficiencies outlined are rectified,
retested, and certified.
A. The Contractor shall prepare fully detailed Operation and Maintenance Manuals for the
system and submit to the Engineer for his approval.
3.10 MAINTENANCE
B. The contractor during that period shall provide labor and parts warranty on the installed
system. During that period, the contractor shall be responsible for the regular inspection
and maintenance as recommended by the manufacturer.
END OF SECTION
SITE CLEARING
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section. The Contractor is fully
responsible for all permits according to the local regulations and shall bear all costs
A. Furnish all labor, materials, plant, equipment and appliances and perform all necessary
operations to execute the work of this section. This section includes the following:
1. Clear site of trees, plant life and grass.
2. Remove complete root system of trees and shrubs.
3. Remove surface debris.
4. Disposal of removed materials away from site and in a legal manner in full
compliance with Local Authorities rules and regulations.
B. Section Includes:
1. Protecting existing vegetation to remain.
2. Removing existing vegetation.
3. Stripping and stockpiling topsoil.
C. Related Sections: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
1. Section 31 2000 - Earthworks
2. Section 31 2319 - Dewatering
3. Appendix A - Geotechnical Report
1.02 DEFINITIONS
A. Subsoil: All soil beneath the topsoil layer of the soil profile and typified by the lack of
organic matter and soil organisms.
B. Surface Soil: Soil that is present at the top layer of the existing soil profile at the Project
site. In undisturbed areas, the surface soil is typically topsoil; but in disturbed areas
such as urban environments, the surface soil can be subsoil.
C. Topsoil: Top layer of the soil profile consisting of existing native surface topsoil or
existing in-place surface soil and is the zone where plant roots grow.
D. Topsoil: Top layer of the soil profile consisting of existing native surface topsoil or
existing in-place surface soil and is the zone where plant roots grow. Its appearance is
generally friable, pervious, and black or a darker shade of brown, gray, or red than
underlying subsoil; reasonably free of subsoil, clay lumps, gravel, and other objects
more than 50 mm in diameter; and free of subsoil and weeds, roots, toxic materials, or
other non-soil materials.
B. Approval from local authorities for erection of site fence and signboards.
A. Except for stripped topsoil and other materials indicated to be stockpiled or otherwise
remain Owner's property, cleared materials shall become Contractor's property and
shall be removed from Project site.
A. Traffic: Minimize interference with adjoining roads, streets, walks, and other adjacent
occupied or used facilities during site-clearing operations.
1. Do not close or obstruct streets, walks, or other adjacent occupied or used
facilities without permission from Owner and authorities having jurisdiction.
2. Provide alternate routes around closed or obstructed traffic ways if required by
Owner or authorities having jurisdiction.
D. Prohibit heat sources, flames, ignition sources, and smoking within or near protection
zones.
E. Soil Stripping, Handling, and Stockpiling: Perform only when the topsoil is dry or slightly
moist.
PART 2 - PRODUCTS
2.01 MATERIALS
KEO/19-3262-0000 31 1000/2 Site Clearing
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
A. Satisfactory Soil Material: Requirements for satisfactory soil material are specified in
Section 31 2000 "Earth Moving" and Section 32 9113 "Soil Preparation".
PART 3 - EXECUTION
3.01 CLEARING
A. Access:
1. Clear areas required for access to site and execution of work.
B. Undergrowth
1. Clear site of bushes, shrub and undergrowth without disturbing subsoil.
2. Grub out and dispose of large roots.
C. Remove any curbs and other obstacles on site. Dispose of materials, away from site
and in a legal manner.
3.02 PREPARATION
A. Protect and maintain benchmarks and survey control points from disturbance during
construction.
B. Locate and clearly identify trees, shrubs, and other vegetation to remain or to be
relocated. Wrap a 25-mm blue vinyl tie tape flag around each tree trunk at 1350 mm
above the ground.
D. Remove erosion and sedimentation controls and restore and stabilize areas disturbed
during removal.
C. Stockpile topsoil away from edge of excavations without intermixing with subsoil. Grade
and shape stockpiles to drain surface water. Cover to prevent windblown dust and
erosion by water.
1. Limit height of topsoil stockpiles to 1800 mm.
2. Do not stockpile topsoil within protection zones.
3. Test stockpiled top soil in accordance to testing in section 32 9113 "Soil
Preparation".
4. Dispose of surplus topsoil. Surplus topsoil is that which exceeds quantity
indicated to be stockpiled or reused.
END OF SECTION
EARTHWORKS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section. The Contractor is fully
responsible for all permits according to the local regulations and shall bear all costs.
A. Furnish all labour, materials, tools and equipment and perform all services and
operations necessary for earthwork including, but not limited to, the following:
1. Destroy all ants' nests and vermin encountered during excavation.
2. Preparing subgrades for slabs-on-grade, walks and pavements.
3. Excavating and backfilling for buildings and structures.
4. Excavating and backfilling trenches for buried mechanical and electrical utilities
and pits for buried utility structures.
5. Excavation for utility connections.
6. Grading to level as per grading plans.
7. Compacted fill, preparing subgrades for slabs-on-grade and precast pavers.
8. Disposal of surplus and waste materials.
B. The Contractor shall obtain all approvals, permits and pay all relevant fees (for 24hrs
day work schedule) associated with excavation and disposal of excavated materials.
C. Related Sections: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
1. Section 02 3000 - Subsurface Investigation
2. Section 03 3000 - Cast-in-Place Concrete.
3. Section 31 2319 - Dewatering.
4. Section 31 3116 - Termite Control
5. Section 31 5000 - Excavation Support and Protection.
6. Divisions 21, 22, 23, 26, 27, and 28 Sections for installing underground
mechanical and electrical utilities and buried mechanical and electrical
7. Appendix A - Geotechnical Report
1.02 REFERENCES
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contract. Product manufacture, testing and
installation shall comply with the following references unless otherwise stated in the
specification or otherwise approved, but not limited to:
1. ASTM D 448: Classification for Sizes of Aggregate for Road and Bridge
Construction.
2. ASTM C 422: Particle Size Analysis of Soils.
3. ASTM D 698: Test Methods for Laboratory Compaction Characteristics of
Soil Using Standard Effort 600 kN-m/m³.
4. ASTM D 1556: Test Method for Density and Unit Weight of Soil in Place by
the Sand-Cone Method.
KEO/19-3262-0000 31 2000/1 Earthworks
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
5. ASTM D 1557: Test Method for Laboratory Compaction Characteristics of
Soil Using Modified Effort 2,700 kN-m/m³.
6. ASTM D 2216: Laboratory Determination of Water (Moisture) Content of
Soil, Rock, and Soil Aggregate Mixtures.
7. ASTM D 2487: Classification of Soils for Engineering Purposes (Unified
Soil Classification System)
8. ASTM D 2937: (R 1990) Density of Soil in Place by the drive-Cylinder
Method.
9. ASTM D 4253: Test Methods for Maximum Index Density of Soils Using a
Vibratory Table.
10. ASTM D 4318: Liquid Limit, Plastic Limit, and Plasticity Index of Soils.
11. ASTM D 4754: Test Methods for Minimum Index Density of Soils and
Calculation of Relative Density.
1.03 DEFINITIONS
F. Bedding Course: Layer placed over the excavated subgrade in a trench before laying
pipe.
G. Borrow: Soil material obtained off-site when sufficient approved soil material is not
available from excavations.
H. Unyielding Material: Unyielding material shall consist of rack and granular soils with
stones greater than 50 mm, in any dimension or as defined by the pipe manufacturer,
whichever is smaller.
I. Unstable Material: Unstable material shall consist of material too wet to properly work.
K. Fill: Compacted structural fill to raise the grade to required level to receive foundation
and grade slab.
M. Utilities include on-site underground pipes, conduits, ducts, and cables, as well as
underground services within buildings.
1.04 SUBMITTALS:
A. Construction Activity Pollution Prevention Plan to prevent pollution due to Soil Erosion,
Waterway Sedimentation and Airborne Dust Generation. A plan need to be drawn in line
with EPA Construction General Permit ,(Copy is available for inspection with the
Engineer ).The EPA’s Construction General Permit outlines requirements of NPDES (
National Pollutant Discharge Elimination System). The Affected Area need to be
graveled at perimeter and sloped inward. The entry of Vehicles need to be graveled to
prevent soil carry over.
C. Technical Data:
1. Catalogues of heavy equipment used for excavation and earth removal.
D. Shop Drawings
1. Prepared by or under the supervision of a qualified professional engineer
2. Shop drawings including plan of complete site showing area and extent of
excavation, and capping of any existing underground utilities to remain.
a. Shop drawings shall show profiles, formation levels, pits, transitions etc.
G. Material Test Reports: From a qualified testing agency indicating and interpreting test
results for compliance of the following with requirements indicated:
1. Classification according to ASTM D 2487 of each on-site and borrow soil material
proposed for fill and backfill.
2. Laboratory compaction curve according to ASTM D 698, ASTM D 1557 for each
on-site and borrow soil material proposed for fill and backfill.
3. Report of actual unconfined compressive strength and/or results of bearing tests
of each stratum testing.
4. Particle size analysis shall be in accordance with ASTM D422-63.
5. Sieve analysis shall be in accordance with ASTM C136 and ASTM D422 on
sieves conforming to ASTM E11.
6. Liquid Limit and Plasticity Index: One liquid limit and plasticity index shall be
performed for each sieve analysis. Liquid limit and plasticity index shall be in
accordance with ASTM D4318.
I. Excavation Supervisor: Allow for employing full time on site, an experienced and
qualified excavation supervisor. Submit with the Tender, full resume details of the
KEO/19-3262-0000 31 2000/3 Earthworks
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
Supervisor. No excavation shall start until the Engineer has approved the nominated
Supervisor.
B. Testing and Inspection: Testing and inspection shall be the responsibility of the
Contractor and shall be performed at no additional cost to the Employer.
1. Testing Facilities: Test shall be performed by an approved commercial testing
laboratory. No work requiring testing will be permitted until the facilities have
been inspected and approved by the Engineer.
2. Notice Period: Provide agreed notice to enable the Engineer to be present, if so
desired, at whatever inspections or tests are performed.
a. Notice Period: No Less Than
b. Inspection on Site 1 Day.
c. Tests performed on Site 1 Day.
d. Material inspections or tests to be witnessed offsite 5 Days.
3. Accept responsibility for providing, controlling, calibrating and maintaining
inspection, measuring and test equipment suitable to demonstrate that the Works
comply with the specified requirement. Make this or similar equipment available
to the engineer whenever required for examination of the Works.
A. Demolish and completely remove from site existing underground utilities. Coordinate
with utility companies to shut off services if lines are active.
1. The location of known services shall be confirmed by trial pits prior to excavation
works.
2. Obtain the authorities’ existing services NOC to proceed with the earth works and
obtain all necessary information and drawings to identify the existing services.
D. Nature of Excavation:
1. Include for excavating in any type of ground encountered.
2. Include for breaking up rock materials, materials so firmly cemented as to
possess the characteristics of rock, concrete or masonry structures, or any other
hard or compacted materials encountered in excavations, all at the Contractor's
cost.
E. Protection
1. Barricade open excavations made as part of earthwork operations and post with
warning lights. Operate warning lights as recommended by the Engineer.
PART 2 - PRODUCTS
A. General: Provide borrow soil materials when sufficient satisfactory soil materials are not
available from excavations.
1. To be free from plastic fines and weakly cemented lumps of sand.
2. To be homogeneous and at the optimum moisture content for compaction
purposes when placed.
3. Sand layers which present liquefaction potential below structural filling must be
compacted so that they reach a minimum cone resistance of 5 MPa.
4. Any slopes required will be as shown on drawings.
5. Water: Water used for compacting fill shall be clean and free from oil, grease,
organic matter, suspended fine sediment and other deleterious substances.
C. Unsatisfactory Soil Materials: ASTM D 2487 soil classification groups ML. MH, CL, CH,
OL, OH, and PT. Satisfactory subgrade soil which are rendered unsuitable by the
Contractor due to inadequate site and/or excavation drainage or due to negligence by
working (remolding) or compacting otherwise satisfactory in place subgrade soils under
adverse moisture conditions, as determined by the Geotechnical Engineer, and shall be
removed and replaced with satisfactory fill material or shall be worked or altered until
rendered suitable as determined by the Geotechnical Engineer at no additional cost to
the Employer.
I. Filter Material: Narrowly graded mixture of natural or crushed gravel, or crushed stone
and natural sand; ASTM D448; coarse-aggregate grading Size 67; with 100 percent
passing a 25-mm sieve and zero to 5 percent passing a 4.75-mm sieve.
K. Impervious Fill: Clayey gravel and sand mixture capable of compacting to a dense
state.
2.01 EQUIPMENT
A. General
1. The equipment utilized in carrying out earthwork and related work shall be in
good working conditions, and the Contractor shall maintain them in such
condition for the duration of the Contract.
2. The Contractor shall supply adequate equipment as deemed necessary for the
proper execution of the Work.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine related work and surfaces before starting the work of this Section. Report in
writing, conditions, which will prevent the proper provision of this work. Beginning the
work of this Section without reporting unsuitable conditions shall constitute acceptance
of conditions by the Contractor. Any required removal, repair, or replacement of the
work caused by unsuitable conditions should be done at no additional cost to the
Employer.
3.02 PREPARATION
A. Protect structures, utilities, sidewalks, pavements, and other facilities from damage
caused by settlement, lateral movement, undermining, washout, and other hazards
created by earthwork operations.
C. Make provision for all temporary work, scaffolding, staging, timbering, strutting and other
works as may be necessary and required for the proper, safe and efficient performance
and construction of the works intended and all works incidental thereto in an expeditious
manner. Be responsible for any damage done to roads, mains, cables, including safety
to persons and property, by the execution of the work.
D. The cost of furnishing, placing and removing the temporary works shall be included in
the Tender for the work.
E. Examine related work and surfaces before starting the work of this Section. Report in
writing, conditions, which will prevent the proper provision of this work. Beginning the
work of this Section without reporting unsuitable conditions shall constitute acceptance
of conditions by the Contractor. Any required removal, repair, or replacement of the
work caused by unsuitable conditions should be done at no additional cost to the
Employer.
F. Be acquainted with all site conditions. Should utilities not shown on Drawings be found
during excavation, promptly submit Contractor’s proposed action. Failure to do so will
result in liability for any and all damage thereto arising from operations subsequent to
discovery of such utilities not shown on Drawings.
3.03 DEWATERING
A. Prevent surface water and ground water from entering excavations, from ponding on
prepared subgrades, and from flooding Project site and surrounding area.
B. Protect subgrades from softening, undermining, washout, and damage by rain or water
accumulation.
KEO/19-3262-0000 31 2000/7 Earthworks
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Reroute surface water runoff away from excavated areas. Do not allow water to
accumulate in excavations. Do not use excavated trenches as temporary
drainage ditches.
2. Dewatering system is specified in Section 31 2319.
A. Generally:
1. Excavate to the depths and profiles shown on the Drawings or as directed.
2. Allow sufficient working space where necessary for the erection of earthwork
support system.
3. Report any unexpected subsurface conditions and discontinue affected work in
area, until notified to resume work.
4. Any soft material, or non compactable material found at the bottom of excavated
areas shall be removed and replaced with acceptable bedding material, placed in
lifts not exceeding 150mm and compacted as further described.
5. Unless otherwise described in the Contract, all topsoil to a minimum depth of
200mm shall be removed from the areas of cut and fill and, unless surplus to
requirements, stockpiled for re-use for the soiling of slopes of cuttings and
embankments, berms, verges, central reserves and for the provision of beds for
the cultivation of trees and shrubs.
6. The Contractor shall make his own arrangements for stockpiling of topsoil and/or
suitable material and for the provision of sites for the purpose. The permission of
the Engineer is necessary for proposed stockpiles within the Site Area.
7. The works are to be set out from the primary datum level(s) and setting out
point(s) indicated on the drawings or from information provided by the Engineer.
The Contractor shall submit his proposals for setting out and controlling the
alignment of the works, to the Engineer and obtain his approval prior to the start
of construction. The Contractor shall furnish to the Engineer details of the level
and location of all temporary benchmarks and reference points that he
establishes.
B. Excavated Formations:
1. In made up ground excavate foundations down to a natural bearing formation of
undisturbed subsoil, unless otherwise instructed.
2. Obtain instructions if a natural bearing formation of undisturbed subsoil:
a. Is obtained at a lesser depth than that shown on the Soils Report.
b. Is not obtained at the depth shown on the Soils Report.
3. If, after inspection, formation becomes unsuitable for any reason, excavate
further and backfill with approved material all at the Contractor's expense.
A. Excavate surfaces under walks and pavements to indicated lines, cross sections,
elevations, and subgrades.
A. Excavate trenches to uniform widths to provide the following clearance on each side of
pipe or conduit. Excavate trench walls vertically from trench bottom to 300 mm higher
than top of pipe or conduit, unless otherwise indicated.
1. Clearance: 300 mm each side of pipe or conduit or as indicated.
B. Trench Bottoms: Excavate and shape trench bottoms to provide uniform bearing and
support of pipes and conduit. Shape subgrade to provide continuous support for bells,
joints, and barrels of pipes and for joints, fittings, and bodies of conduits. Remove
projecting stones and sharp objects along trench subgrade.
1. For pipes and conduit less than 150 mm in nominal diameter and flat-bottomed,
multiple-duct conduit units, hand-excavate trench bottoms and support pipe and
conduit on an undisturbed subgrade.
2. For pipes and conduit 150 mm or larger in nominal diameter, shape bottom of
trench to support bottom 90 degrees of pipe circumference. Fill depressions with
tamped sand backfill.
3. Excavate trenches 150 mm deeper than elevation required in rock or other
unyielding bearing material to allow for bedding course.
C. All manholes and other structures shall be founded on undisturbed ground or thoroughly
compacted ground. Excavation shall be carried out to the grade necessary.
D. Hand excavation must be applied along the parts where existing cables, water, gas and
oil mains, sewers etc. cross the trench or in the main roads where traffic is likely to be
unreasonably disturbed by the use of machines. In other places hand or machine
excavation may be used. Excavation by machine must not normally be executed
deeper than 15cm above the bottom of the trench. Be held responsible for making good
all damage to road surfaces and private lands caused by the other use of mechanical
excavators.
A. Open-cut excavation should be braced and sheeted adequate to the strength design to
protect persons, property, traffic on the work or to prevent caving and harmful sinking.
Be responsible for adequacy of any required sheeting and bracing. Be responsible for
any accidents to people, any damage done to roads, mains, cables, pipes, sewers, etc.
by the execution of the work. When close sheeting is required, it shall be so driven as to
prevent adjacent soil from entering the excavation either below or through such
sheeting. Sheeting and bracing shall be provided as a standard for excavations 1.50m
and above depth. Where sheeting and bracing are used, trench widths shall be
increased accordingly. The strength design of the system of supports should be based
on the principles of soil mechanics as they apply to the materials encountered. Sheeting
and bracing must always comply with approved safety requirements.
B. The Engineer’s Representative reserves the right to order the sheeting to be driven to
the full depth of the excavation or to such additional depths as may be required for the
protection of the work.
C. Bracing must be removed when the backfilling has reached the respective levels of such
bracing. Sheeting must be removed after the backfilling has been completed or has
been brought up to such an elevation as to permit its safe removal.
B. Proof roll subgrade with heavy pneumatic-tired equipment to identify soft pockets and
areas of excess yielding. Do not proof roll wet or saturated subgrades.
1. Completely proof-roll subgrade in one direction, repeating proof-rolling in
direction perpendicular to first direction.
A. Backfill any excavations taken wider or deeper than required with mass concrete 3Mpa,
28-day cylinder compressive strength.
A. Stockpile borrow soil materials and satisfactory excavated soil materials. Stockpile soil
materials without intermixing. Place, grade, and shape stockpiles to drain surface
water. Cover to prevent windblown dust.
1. Stockpile soil materials away from edge of excavations.
A. Place and compact backfill in excavations promptly, but not before completing the
following:
1. Construction below finish grade including, where applicable, dampproofing and
waterproofing.
2. Surveying locations of underground utilities for record documents.
3. Inspecting and testing underground utilities.
4. Removing concrete formwork.
5. Removing trash and debris.
6. Removing temporary shoring and bracing, and sheeting.
7. Installing permanent or temporary horizontal bracing on horizontally supported
walls.
A. Place and compact bedding course on trench bottoms and where indicated. Shape
bedding course to provide continuous support for bells, joints, and barrels of pipes and
for joints, fittings, and bodies of conduits.
B. Backfill trenches excavated under footings and within 450 mm of bottom of footings with
satisfactory soil compacted in layers not exceeding 200mm; fill with concrete to
elevation of bottom of footings.
C. The trench for pipes to a depth of 30cm above the top of the pipe shall be backfilled by
hand or by approved mechanical methods. Use special care in placing this portion of
the backfill so as to avoid injuring or moving the pipe. The backfill material shall be
placed in 15cm layers and compacted by tamping.
D. Backfill under permanent pavement shall be placed in 15cm layers and compacted by
tamping. Power tampers of an effective approved type shall be used.
F. Fill voids with approved backfill materials while shoring and bracing, and as sheeting is
removed.
G. Place and compact final backfill of satisfactory soil material to final subgrade elevation.
H. Install warning tape directly above utilities, 300 mm below finished grade, except 150
mm below subgrade under pavements and slabs or as directed.
B. Plow, scarify, bench, or break up sloped surfaces steeper than 1 vertical to 4 horizontal
so fill material will bond with existing material.
A. Uniformly moisten or aerate subgrade and each subsequent fill or backfill layer before
compaction to within 2 percent of optimum moisture content.
1. Do not place backfill or fill material on surfaces that are muddy.
2. Remove and replace, or scarify and air-dry, otherwise satisfactory soil material
that exceeds optimum moisture content by 2 percent and is too wet to compact to
specified dry unit weight.
A. Place backfill and fill materials in layers not more than 200 mm in loose depth for
material compacted by heavy compaction equipment, and not more than 100 mm in
loose depth for material compacted by hand-operated tampers.
B. Place backfill and fill materials evenly on all sides of structures to required elevations,
and uniformly along the full length of each structure.
C. Compact soil to not less than the following percentages of maximum dry unit weight
according to ASTM D 1557:
1. Under structures, building slabs, steps, and pavements, scarify and re-compact
top 300 mm of existing subgrade and each layer of backfill or fill material at 95
percent.
2. Under planting areas, scarify and recompact top 150 mm below subgrade and
compact each layer of backfill or fill soil material at 90percent.
3. For utility trenches, compact each layer of initial and final backfill soil material at
90 percent.
3.17 GRADING
A. General: Uniformly grade areas to a smooth surface, free from irregular surface
changes. Comply with compaction requirements and grade to cross sections, lines, and
elevations indicated.
1. Provide a smooth transition between adjacent existing grades and new grades.
2. Cut out soft spots, fill low spots, and trim high spots to comply with required
surface tolerances.
C. Site Grading: Slope grades to direct water away from buildings and to prevent ponding.
Finish subgrades to required elevations within the following tolerances:
1. Planting areas or Unpaved Areas: Plus or minus 25 mm.
2. Pavements: Plus or minus 13 mm.
B. Proceed with subsequent earthwork only after test results for previously completed work
comply with requirements.
D. When testing agency reports that subgrades, fills, or backfills have not achieved degree
of compaction specified, scarify and moisten or aerate, or remove and replace soil to
depth required; recompact and retest until specified compaction is obtained.
3.19 PROTECTION
A. Protecting Graded Areas: Protect newly graded areas from traffic and erosion. Keep
free of trash and debris.
A. Disposal: Remove surplus satisfactory soil and waste material, including unsatisfactory
soil, trash, and debris, and legally dispose of it off Employer’s property.
END OF SECTION
DEWATERING
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section. The Contractor is fully
responsible for all permits according to the local regulations and shall bear all costs.
A. Work shall include, but not necessarily be limited to the following: Designing. furnishing,
installing, maintaining, operating, monitoring and removal of temporary dewatering
systems as required to lower and control water levels and hydrostatic pressures;
disposing of pumped water; constructing, maintaining, observing and removing of
equipment and instrumentation for control of the system, all to the approval of the
Engineer.
B. Dewatering includes lowering the water table and intercepting seepage which would
otherwise emerge from the slopes or bottom of the excavation; increasing the stability of
excavated slopes; preventing loss of material from beneath the slopes or bottom of the
excavation; improving the excavating and hauling characteristics of on soil; preventing
rupture or heaving of the bottom of an excavation; and disposing of pumped water.
D. Preventing of surface water from entering the site from buildings, streets or the ground
surface and diverting the surface water away from the site.
E. The Contractor shall obtain all approvals, permits and pay all relevant fees (for 24hrs
day work schedule) associated with Dewatering.
H. Related Sections: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
1. Section 02 3000 - Subsurface Investigation
2. Section 31 2000 - Earthworks
3. Appendix A - Geotechnical Report
1.02 DESIGN
A. The Contractor is responsible for the adequacy of the dewatering system. Design
dewatering systems to meet the following performance requirements.
B. Methods may include sump pumping, single or multiple stage well point or jet eductor
well point systems, deep wells, or combinations thereof.
C. Locate dewatering facilities where they will not interfere with utilities and construction
work to be done by others.
1.03 SUBMITTALS
B. Before installation of the dewatering systems, submit information and shop drawings to
the Engineer showing the following:
1. The proposed type of dewatering systems;
2. Arrangements, locations and depths of system components.
3. Methods of disposal of pumped water including approval of authorities.
4. During dewatering, record every 24 hours readings of groundwater observation.
D. Field Test Report: Before starting excavation, submit test results and computation
demonstrating that dewatering system is capable of meeting performance requirements.
A. Surface Drainage: Intercept and divert precipitation, and surface water, away from
excavation through the use of dikes, ditches, pipes, sumps or other means.
B. Drainage of Excavated Areas: Provide and maintain ditches of adequate size to collect
surface and seepage water, which may enter the excavations. Divert the water into
sumps and drain or pump into a temporary conduit for discharge.
PART 2 - PRODUCTS
(NOT APPLICABLE)
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine areas and conditions affecting performance of Work under this Section.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 DEWATERING
A. Keep the Engineer advised of any changes made to accommodate field conditions and,
on completion of the dewatering system installation, revise and resubmit information
drawings, as necessary to show the installed configuration.
C. Maintain the water level at such lower elevations that no danger to structures can occur
because of buildup of excessive hydrostatic pressure and maintain the water level a
minimum of 600mm below the bottom of blinding levels.
D. Monitor daily the depth of groundwater lowering by using observation wells and/or
piezometers.
1. Observation Wells:
KEO/19-3262-0000 31 2319/3 Dewatering
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
a. Provide, take measurements and maintain adequate number of observation
wells (piezometers) and such additional observation wells as may be
required by the Engineer.
b. Observe and record daily the elevation of the groundwater and peizometric
water levels in observation wells. Provide each observation wells
(piezometers) with high Level Indication Instrumentation having audio-
visual (Light and Sound) alarm buzzer. Alarm buzzer shall be operated
automatically when ground water level exceeds the specified controlled
water level.
c. Repair or replace observation wells that become inactive, damaged, or
destroyed within 24 hours. If required, suspend construction activities
areas where observation wells are not functioning properly until reliable
observations can be made. Add or remove water from observation well
risers to demonstrate that the observation wells are functioning properly.
d. Remove observation wells only when directed by the Engineer.
E. Survey nearby structures to ensure that detrimental settlements are not occurring at
these structures due to dewatering operations.
F. Provide, maintain and work such engines, pumps, pipe work, chutes and other things
necessary to keep sub-soil or accumulated water at a level below the bottom of the
permanent works for such periods as required for the Project and as directed. After
raising the water herein referred to, at once convey it away in such a manner as not to
cause any nuisance or injury.
G. Pumping must be done in such a way that fine-grained material is not washed out and
carried away. If necessary, a drainage filter should be arranged at the pumping shaft.
H. Provide standby equipment, installed and available, for immediate operation as may be
required, to adequately maintain the dewatering on a continuous basis in the event that
part of the system becomes inadequate or fails. In the event dewatering requirements
are not satisfied due to inadequacy or failure of the dewatering system, perform such
work as may be required to restore damaged structure and foundation soils at no
additional expense to the Employer.
I. Ensure that all pipes and structures when laid or constructed are secured against
floating by backfilling or by some other approved means. The site staff shall be alerted
at all times to take action necessary in the event of flooding.
J. Notify the Engineer in the event of a disturbance to the foundation soils caused by an
interrupted or inadequate dewatering system. Take all corrective measures necessary
at no additional expense.
M. Remove dewatering system only when directed by the Engineer and should meet the
following criteria;
1. Weight of structure exceeds the hydrostatic uplift due to water pressure by 25%.
a. The Contractor shall submit calculations to satisfy the above requirement.
KEO/19-3262-0000 31 2319/4 Dewatering
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3.03 RECORDS
A. Observe and record daily the elevation of the groundwater during the period that the
dewatering system is in operation. Submit details on weekly basis.
END OF SECTION
TERMITE CONTROL
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Furnish all labor, materials, equipment and perform all operations and services
necessary in the treatment for termite control of backfill soil retaining walls; foundation
and grade slabs above water table.
B. Related Section: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
1. Section 03 3000 - Cast-in-Place Concrete.
2. Section 31 2000 - Earthworks
1.02 SUBMITTALS
C. To ensure operation, do not apply soil treatment to excessively wet soils or during
inclement weather. Comply with handling and application instructions of the soil toxicant
manufacturer.
1.05 COORDINATION
A. Coordinate soil treatment application with excavating, filling, and grading and concreting
operations. Treat soil under footings, grade beams, and ground-supported slabs, before
construction.
1.06 WARRANTY
A. Special Warranty: Written warranty, signed by applicator and Contractor certifying that
termite control work, consisting of applied soil termiticide treatment, will prevent
infestation of subterranean termites.
B. If subterranean termite activity is discovered during warranty period, Contractor will re-
treat soil and repair or replace damage caused by termite infestation.
PART 2 - PRODUCTS
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine substrates, areas, and conditions, with Applicator present, for compliance with
requirements for moisture content of the soil, interfaces with earthwork, slab and
foundation work, and other conditions affecting performance of termite control. Proceed
with application only after unsatisfactory conditions have been corrected.
A. General: Comply with the most stringent requirements of local authorities and with
manufacturer's written instructions for preparing substrate. Remove all extraneous
sources of wood cellulose and other edible materials such as wood debris, tree stumps
and roots, stakes, formwork, and construction waste wood from soil and around
foundations.
B. Soil Treatment Preparation: Remove foreign matter and impermeable soil materials that
could decrease treatment effectiveness on areas to be treated. Loosen, rake, and level
soil to be treated, except previously compacted areas under slabs and footings.
Termiticides may be applied before placing compacted fill under slabs if recommended
by termiticide manufacturer.
C. Fit filling hose connected to water source at the site with a backflow preventer.
A. General: Comply with the most stringent requirements of local authorities and with
manufacturer's written instructions for preparing substrate. Remove all extraneous
sources of wood cellulose and other edible materials
B. Post signs in areas of application to warn workers that soil termiticide treatment has
been applied. Remove signs after areas are covered by other construction.
C. Application: Provide quantity required for application at the label volume and rate for the
maximum specified concentration of termiticide, according to manufacturer’s
recommendation for the backfill soil material (from excavation or borrowed soil).
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section. The Contractor is fully
responsible for all permits according to the local regulations and shall bear all costs
A. The Drawings show an indicative layout for works associated with excavation support
and protection of basement and foundations.
B. Design, furnish all labor, materials, tools and equipment and perform all services and
operations necessary for the complete supply and installation of the following:
1. The excavation support and protection system shall be designed to allow for the
final excavation levels shown on the Drawings
2. Excavation support and protection system necessary to protect existing
buildings, streets, walkways, utilities, and other improvements and excavation
against loss of ground or caving embankments.
3. Inspection and maintenance of excavation support and protection system.
4. Minimum 20KPa construction surcharge load shall be considered in design of
shoring.
5. Removal of shoring and bracing, as required.
E. Related Sections: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
1. Section 02 3000 - Subsurface Investigation
2. Section 31 1000 - Site Cleaning
3. Section 31 2000 - Earthworks
4. Section 31 2319 - Dewatering.
5. Appendix A - Geotechnical Report
B. Ground Anchors
1. Design and execution of ground anchorages shall comply with BS 8081 and BS
EN 1537.
2. Anchors shall be stressed anchors in soil or rock.
3. Temporary anchors shall be designed such that the minimum service life is not
less than two years.
4. The following minimum safety factors shall apply: Tendon = 1.6; Ground/grout
interface = 2.5; Proof load factor = 1.25.
5. The anchors shall be held in with wedges, or threaded bar with bearing plate and
bolt, no welding shall be allowed for this purpose.
6. Tension couplers shall be used for anchors longer than 12m. No welding of
anchor bars is permitted.
A. Engineer the excavation support and protection system to prevent adjacent surfaces
such as roads, streets, sidewalks and landscaping from settling below their original, as
found levels and conditions.
C. Engineer the excavation support and protection system to prevent the sides of the
excavation for the building, and the mechanical and electrical services to the building,
from caving in and from imposing loads on foundation walls and footings at least until 7
days after the Ground Floor slab bas been poured and all below grade waterproofing is
completed.
D. Engineer excavation support and protection system and tie-back systems to permit
unobstructed installation of membrane and wall reinforcement. Locate tie-backs away
from slab/foundation wall junction to ensure no interference with construction of the
foundation wall and waterproofing. Anchor heads must be recessed into the excavation
support and protection system.
E. Engineer excavation support and protection system to prevent any damage to existing
adjacent buildings, structures and Utilities.
F. Provide the Engineer with sufficient advance notice of engineering data information and
shop drawings submissions, shop fabrications, field installation and other phases of the
work of this Section to permit review and inspections of the Works for compliance with
the Contract Documents.
G. The Contractor shall be responsible for making prompt and continuous evaluations of
the test data and written weekly reports of the systems performance and whenever
necessary, taking immediate steps to correct any deficiencies in the capacities of
individual members or providing other corrective measures which may be required to
prevent damage or excessive movement.
H. For the stability and safety of the existing structures, engage a geotechnical specialist
registered in Kuwait, who shall, based on his findings submit a geotechnical summary
report, elaborating on the adequacy of the excavation supporting system, methods and
procedures of construction or any other precautions deemed to be necessary to secure
the stability and safety of the adjoining structures and pavement throughout the
construction stages.
1.04 SUBMITTALS:
B. The Contractor is to supply a method statement for the execution of the work endorsed by
a qualified Geotechnical Engineer.
D. Approvals: The Contractor shall be responsible for obtaining all necessary permits from
all regulatory authorities having jurisdiction prior to commencement of shoring system
installation.
C. The Contractor must be familiar with below grade soil and water conditions in the project
area and have proven experience with the type of work specified in this Section. The
Contractor’s site foreman must be familiar with below grade soil and water conditions in
the project area and have proven experience with direction workers in the type of work
specified in this Section.
A. Before starting work, verify governing dimensions and elevations. Verify condition of
adjoining properties. Take photographs to record any existing settlement or cracking of
structures, pavements, and other improvements. Prepare a list of such damages,
verified by dated photographs, and signed by Contractor and others conducting
investigation.
A. Protect and maintain existing active sewer, water, gas, electricity and other utility
services and structures outside the property line but within the working area.
B. Co-ordinate with all utilities authorities and pay all related fees for relocating the required
utilities, including all design and installations fees.
C. Notify municipal agencies and service utility companies and comply with requirements of
governing authorities and agencies for protection, relocation, removal, and
discontinuance of services.
A. Work shall comply with all rules, regulations, laws and ordinances of all authorities having
jurisdiction.
B. Obtain all necessary permits. Obtain written permission from adjoining property owners if
proposed systems of ground anchors will project beyond the vertical projection of the
contract limit lines. Submit such permissions with shop drawings.
C. Co-ordinate the design and placement of ground anchors with existing utilities to the
satisfaction of the affected authorities having jurisdiction and obtain all necessary
permits.
PART 2 - PRODUCTS
2.01 MATERIALS
D. Structural Steel: ASTM ASTM A 36/A 36M, ASTM A 690/A 690M or ASTM A 992/A
992M.
PART 3 - EXECUTION
3.01 PREPARATION
A. Protect structures, utilities, sidewalks, pavements, and other facilities from damage
caused by settlement, lateral movement, undermining, washout, and other hazards that
could develop during excavation support and protection system operations.
1. Shore, support and protect utilities encountered and designated to be retained.
B. Install excavation support and protection systems to ensure minimum interference with
roads, streets, walks, and other adjacent occupied and used facilities.
1. Do not close or obstruct streets, walks or other adjacent facilities without
permission from the authorities. Provide alternate routes around closed or
obstructed traffic ways if required.
D. Monitor excavation support and protection systems daily during excavation progress
and for as long as excavation remains open. Promptly correct bulges, breakage, or
other evidence of movement to ensure that excavation support and protection systems
remain stable.
A. Engage an Inspection and Testing Agency for quality control of work of this Section.
The cost of inspection and testing services shall by paid for under the works of this
Section by the Contractor. The Engineer, on acceptance of the excavation support and
protection system proposal, will establish the terms of reference for the Inspection and
Testing firm.
B. The Independent Testing Agency will conduct tests on materials used in the
construction of the system, including concrete, reinforcing steel, and tie-back anchors,
and report on compliance with the Contractor’s approval proposal.
A. The Contractor for the work of this Section shall be responsible for all costs and pay all
costs for remedial work as may be necessary to adjust excavation support and
KEO/19-3262-0000 31 5000/6 Excavation Support And Protection
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
protection system so that required lines and levels are obtained. These costs would
include such items as total replacement of portions of the system not installed correctly
or greatly misaligned etc. The Contractor shall be liable for any delays to the
construction schedule and related costs to the Owner incurred due to the need for
remedial work.
B. Co-operate and co-ordinate his work with all below grade trades and ensure their work
is complete or being sufficiently complete to avoid interference with, or damage to, any
part thereof during removal of the system.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 GENERAL
A. All sub-base and base courses, whether aggregate, bitumen, or sand asphalt, shall be
furnished and installed as indicated on the Drawings
PART 2 - PRODUCTS
2.01 MATERIALS
A. Aggregate sub-base and base courses shall consist of natural and/or crushed, screened
fine and coarse aggregates blended to the specified gradation. The aggregates for sub-
base and base courses shall be blended in a central mixing plant, as specified in the
Standard Specifications. Alternatively, the desired gradation for the aggregate sub-base
and base courses may be achieved by processing through gradation screens at the
crusher or quarry.
B. Use and/or mixing of the site excavated materials or borrow materials with the supplied
aggregate materials for sub-base and base courses is not acceptable for the
construction of the aggregate sub-base or base course layers.
A. The final gradation of aggregate sub-base and base courses delivered to site, as
proposed by the Contractor and approved by the Engineer shall be subject to the
following tolerances during construction:
1. Passing 25mm sieve and larger ± 6%
2. Passing sieves 4.75mm (No. 4) to 19mm (No. ¾”) ± 5%
3. Passing sieves 425μm (No. 40) to 2mm (No. 10) ± 4%
4. Passing 75μm (No. 200) ± 2%
A. General
1. The works described below shall consist of furnishing and placing one (1) or
more layers of Recycled Crushed Aggregate (RGA), including additives if
required, on a prepared surface in accordance with the Specifications and in
conformity with the lines, grades, thicknesses and typical cross-sections shown
on the plans or established by the Engineer.
B. Materials
KEO/19-3262-0000 32 1116.16/1 Subbase And Base Courses
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Materials shall conform to the requirements for the class of "Recycled Crushed
Aggregate Base Course" specified on the plans or directed by the Engineer. All
RGA sub-base material shall be free from dirt, organic matter, shale or other
deleterious matter and shall be of such quality that it will bind readily to form a
firm stable sub-base.
2. Components: Crushed concrete aggregates shall consist of clean, hard, durable,
angular fragments of rock, concrete and sand fragments of uniform quality
complying with the general requirements specified in Clause 2.2,
3. The use of crusher fines passing the 4.75 sieve which are not produced from
crushing concrete, shall be subject to approval in writing by the Superintendent to
the proposed source and nature of these materials and the proposed amounts to
be added.
4. Physical Requirements: All base course RGA shall conform to the physical
requirements described below, for each Class of Aggregate.
5. Foreign material in the fraction retained on the 4.75 sieve shall not exceed the
percentages by mass specified:
C. Grading Requirements
1. The material for "Granular RGA Sub-base" shall conform to the requirements
specified for the class of sub-base noted on the plans. The requirements for each
class of sub-base are as follows:
2. Class A Sub-base: Class A Sub-base shall consist of well-graded RGA with sand
and silt, conforming to the following requirements:
a. ASTM (D1241-00)
b. Sieve Percent Passing
1) 50mm 100
2) 9.5mm 30 - 65
3) 4.75mm 25 – 55
4) 2.00mm 15 - 40
5) 0.425mm 8 - 20
6) 0.075mm 2-8
c. Loss by Abrasion Test (AASHTO T 96) 40% maximum
d. Liquid Limit (AASHTO T89) 25 maximum
e. Plasticity Index (AASHTO T 90) 4 maximum
f. Sand Equivalent (AASHTO T 176) 25 minimum
g. CBR on remoulded sample (BS 1377 120% minimum
h. Test 16) after 4 days soaking
3. Class B Sub-base: Class B Sub-base shall consist of uniform mixtures of RGA
with sand, silt and clay, conforming to the following requirements:
ASTM (D1241-00)
Percent Passing
Sieve Size
25.0mm 100
9.5mm 50 - 85
4.75mm 35 - 65
2.00mm 25 - 50
0.425mm 15 - 30
0.075mm 5 - 15
D. Acceptance
1. When the stationary plant method is used, the aggregate will be accepted
immediately following mixing, based on periodic samples taken from the pug mill
output. When a road mix method is used, the aggregate will be accepted after
necessary blending and before laying, based on samples taken from the
combined windrow for each layer. Acceptance of the material by the Engineer
does not constitute acceptance of the sub-base, only that the material is
approved for use in the sub-base.
KEO/19-3262-0000 32 1116.16/3 Subbase And Base Courses
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
E. Equipment
1. Equipment shall be according to the type and number outlined in the Contractor's
detailed Programme of Work, as approved by the Engineer.
F. Construction Requirements
1. Groundwater Levels and Protection: The Contractor must establish the high
water table levels (HWT) along the length of the road, relative to the accepted
National benchmark. Should the base of the proposed road be within 1 metre of
the HWT, an impermeable barrier will be required to be installed to prevent
groundwater coming in contact with the RGA sub-base.
2. Preparation of Subgrade: The Contractor shall, as part of the Work of sub-base,
prepare the sub grade. The formation of the subgrade will vary by either placing
the "Granular RGA Sub-base" on the roadway surface as previously constructed
or by excavating sufficient material from the roadway and placing the "Granular
RGA Sub-base" on the subgrade obtained thereby. In either case, the subgrade,
shall as hereinafter described, be brought to the lines, grades and typical section
shown on the plans for the bottom of the "Granular RGA Sub-base". All soft and
yielding material or other portions of the subgrade, which will not compact
readily, when rolled or tamped, shall be removed, and all loose rock or boulders
found in the excavation shall be removed or broken off to a depth of not less than
fifteen (15) centimetres below the surface of the subgrade. All holes or
depressions made by the removal of material, as described above, shall be filled
with approved material, and the whole subgrade brought to line and grade and
compacted to density designated on the plans or directed by the Engineer.
3. Spreading: Sub-base aggregates shall be spread on subgrade which has been
approved by the Engineer. Sub-base which has been placed on a subgrade not
approved by the Engineer shall be removed at the Contractor's expense.
4. Sub-base aggregate shall be spread on the approved subgrade in layers not
exceeding fifteen (15) centimetres in compacted depth. Spreading shall be done
by means of approved mechanical box spreaders, distributing the material to the
required width and loose thickness. Where the required sub-base thickness is
greater than fifteen (15) centimetres, the material shall be placed in layers of
equal thickness, in no case shall a layer be less than seven and one half (7.5)
centimetres thick. Under no circumstances shall Class A Sub-base be dumped in
a pile on the Subgrade.
5. The material shall be handled so as to avoid segregation. Segregated materials
shall be remixed until uniform. Suitable precautions shall be taken to prevent
rutting of the subgrade during the spreading of the sub-base materials. No
hauling or placement of material will be permitted when, in the judgment of the
Engineer, the weather or road conditions are such that the hauling operations will
cause cutting or rutting of the subgrade or cause contamination of the sub-base
material.
6. Compaction: The moisture content of the sub-base material shall be adjusted
prior to compaction, by watering with approved sprinkler trucks or by drying out,
as directed by the Engineer, to that required to obtain the specified density for
sub-base. Sub-base shall be compacted to an average value of 100% of the
M.D.D. as determined according to AASHTO T 180 Method D with no single
value below ninety eight (98%).
7. The sub-base aggregate shall be compacted by means of approved compaction
equipment progressing gradually from the outside towards the centre with each
succeeding pass uniformly over-lapping the previous pass. Rolling shall
continuous until the entire thickness of each layer is thoroughly and uniformly
compacted to the specified density. Rolling shall be accompanied by sufficient
A. General
1. The works described below shall consist of furnishing and placing one (1) or
more layers of recycled glass aggregate (RGA), including additives if required, on
a prepared surface in accordance with the Specifications and in conformity with
B. Materials
1. Materials shall conform to the requirements for the class of "Recycled Crushed
Aggregate Base Course" specified on the plans or directed by the Engineer. All
RGA for base course shall consist of crushed rock, crushed concrete stone
fragments including sand.
2. Components: Crushed concrete aggregates shall consist of clean, hard, durable,
angular fragments of rock, concrete and sand fragments of uniform quality
complying with the general requirements specified in Clause 2.2.
3. The use of crusher fines passing the 4.75 sieve which are not produced from
crushing concrete, shall be subject to approval in writing by the Superintendent to
the proposed source and nature of these materials and the proposed amounts to
be added.
4. Physical Requirements: All base course RGA shall conform to the physical
requirements described below, for each Class of Aggregate.
5. Foreign material in the fraction retained on the 4.75 sieve shall not exceed the
percentages by mass specified:
6. Grading Requirements: Coarse materials for Glass Aggregate Base Course shall
conform to the following grading requirements:
ASTM (D2940)
Percent Passing
Sieve Size
50mm
100
37.5mm
95 - 100
19mm
70 – 92
9.5mm
50 – 70
4.75mm
35 – 55
0.60mm
12 – 25
0.075mm
0-8
C. Acceptance
1. When the stationary plant method is used, the aggregate will be accepted
immediately following mixing, based on periodic samples taken from the pug mill
output. When a road mix method is used, the aggregate will be accepted after
necessary blending and before laying, based on samples taken from the
combined windrow for each layer. When the aggregate is a total aggregate, it
may be accepted at the crusher. Acceptance of the material by the Engineer
does not constitute acceptance of the base course, only that the material is
approved for use in the base course.
D. Equipment
1. Equipment shall be according to the type and number outlined in the Contractor's
detailed Programme of Work as approved by the Engineer.
E. Construction Requirements
1. Groundwater Levels and Protection: The Contractor must establish the high
water table levels (HWT) along the length of the road, relative to the accepted
National benchmark (New Abu Dhabi Datum (NADD)). Should the base of the
proposed road be within 1 metre of the HWT, an impermeable barrier will be
required to be installed to prevent groundwater coming in contact with the RGA.
2. Subgrade Preparation: The Contractor shall, as part of the Work and prior to the
delivery of materials for the base course, prepare the roadbed surface by
sprinkling blading, rolling and lightly scarifying where necessary, until the proper
crown is obtained. However, in the process of shaping the roadbed, the originally
compacting crust or top portion of the roadbed shall be disturbed as little as
possible. When completed and ready for base course construction the roadbed
shall be well compacted, smooth, hard and uniform, all irregularities having been
bladed out and rolled down.
F. Method of Construction
1. Handling of RGA: Handling of RGA, including the loading of trucks and
stockpiling, shall be effected in such a manner as to minimise segregation.
2. Combining Aggregates and Water: Aggregates for base course shall be
combined into a uniform mixture and water added only in a central mixing plant
before final placement of the material; Mixing and watering by windrows will not
be permitted. When binder is to be added, it shall be combined with the
aggregate base by thoroughly mixing binder and aggregate base in the central
mixing plant.
3. The moisture added to the aggregates shall be that required, as designated by
the Engineer, to obtain the specified density thereby preparing an aggregate
completely ready for compaction after spreading on the roadbed. In no case will
be wetting of aggregates in stockpiles or trucks be permitted.
4. Spreading and Combining Aggregates: Unless otherwise specified, aggregate for
base course shall be delivered to the roadbed as an uniform mixture and shall be
placed on the existing roadway, prepared sub-base or prepared subgrade, as the
case may be, in an uniform layer or layers not exceeding fifteen (15) centimetres
in compacted depth, including any binder that is to be blended on the road.
Spreading shall be done by means of approved self-propelled stone box
KEO/19-3262-0000 32 1116.16/7 Subbase And Base Courses
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
spreaders, distributing the material to the required width and loose thickness.
When the required base thickness is greater than fifteen (15) centimetres, the
materials shall be spread in layers of equal thickness.
5. The material shall be so handled, as to avoid segregation. If an aggregate
spreader causes segregation in the material, or leaves ridges or other
objectionable marks on the surface which cannot be eliminated easily or
prevented by adjustment of the spreader operation, the use of such spreader
shall be removed and replaced with well-graded material. No "skin" patching
shall be permitted.
6. No hauling or placement of material will be permitted when, in the judgment of
the Engineer, the weather or road conditions are such as hauling operations will
cause cutting or rutting of the road surface or cause contamination of the base
course material.
7. Compaction: If directed by the Engineer, prior to starting the aggregate base
operation, the Contractor shall construct trial lengths in accordance with
subparagraph 4.4 "Compaction Trials" in Section 3.2 "Granular Sub-base".
8. RGA shall be laid and compacted in a manner which will not result in segregation
of the material and at a moisture content which allows the compaction stated.
9. Immediately after placing, the base course material shall be compacted. The
material shall be compacted to an average density of 100% of M.D.D. as
determined according to AASHTO T 180 Method D with no single value below
ninety-eight (98%) percent. The Field determination of density shall be made in
accordance with AASHTO T 191. The percent of density shall be adjusted to
compensate for the weight and volume of aggregate larger than the aggregate
used in the compaction control test where applicable.
10. Rolling shall be continued until the entire thickness of each layer is thoroughly
and uniformly compacted to the density specified. The final rolling of the
compacted base course shall be done with a self-propelled roller. Rolling shall be
accompanied by sufficient blading in a manner approved by the Engineer, to
insure smooth surface, free from ruts or ridges and having the proper section and
crown. When additional water is required, it shall be added in the amount and
manner approved by the Engineer. Each layer of base course must be
completely compacted by the Contractor and approved by the Engineer, prior to
the delivery of the materials for a succeeding layer. The surface of the material
shall be free from movement on completion of the compaction.
11. The surface of the finished base course will be tested with a three (3) metre
straight-edge by the Engineer at selected locations. The variation of the surface
from the testing edge of the straight-edge between any two (2) contacts with the
surface shall at no point exceed six (6) millimetres when measured in any
direction. The base course shall be compacted to the thickness and cross-
section as shown on the plans and shall not vary by more than five (5)
millimetres from the required elevation. All humps and depressions and thickness
deficiencies exceeding the specified tolerances shall be corrected by removing
the defective work or by adding new material, as directed by the Engineer.
12. If the material for the base course is laid and compacted in more than one (1)
layer, the Contractor shall plan and coordinate the Work in such a manner that
the previously placed and compacted layers be allowed ample time for drying
and development of sufficient stability, before vehicles hauling materials for the
succeeding layers or other heavy equipment are permitted on the base. Prior to
placing the succeeding layers of material, the top of the underlayer shall be made
sufficiently moist to insure bond between the layers. The edges and edge slopes
of the base course shall be bladed or otherwise dressed to conform to the lines
and dimensions shown on the plans and present straight, neat and workmanlike
lines and slopes as free of loose material as practicable.
KEO/19-3262-0000 32 1116.16/8 Subbase And Base Courses
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
13. The Contractor shall also plan the Work and handle the various operations so
that the least amount of water will be lost by evaporation from uncompleted
surfaces. If the Contractor delays placing of succeeding layers of base course
material to the extent that additional water must be applied to prevent ravelling or
excessive dripping, the application of such water shall be at the Contractor's
expense not be considered as the basis for a claim for additional compensation.
Water shall be applied at such times and in such quantities as directed by the
Engineer, and the Engineer shall have full authority to require the suspension of
all other Works on the project to insure the proper maintenance of previously
compacted material. If after the base is compacted, any areas are above or
below proper grade and true elevations, such areas shall be loosened and after
having had additional materials added or excess material removed, as the case
may require, shall be reconstructed as described herein. If after the base is
compacted, any areas fail to meet the specified density and gradation
requirements, they shall be loosened or removed as directed by the Engineer
and reconstructed as described herein.
A. The concrete work shall be furnished and constructed in accordance with the
requirements of Section V, Concrete Works, of the ADM Standard Specifications and as
specified herein.
B. The concrete work shall include all formwork for ornamentation, all inserts embedded in
the concrete, and all grout as indicated on the Drawings and as directed by the
Engineer.
C. All materials shall comply with all requirements of Section V of the ADM Standard
Specifications and as specified herein.
PART 3 - EXECUTION
A. INSTALLATION
B. The subgrade and/or aggregate base course for pedestrian and vehicular concrete
paving blocks shall be prepared as per the Standard specifications and contract
drawings, as applicable.
C. After preparation of the subgrade or aggregate base course for the concrete paving
blocks, as applicable, place 5 cm of bedding sand complying with either the
requirements of BS 7533: Part 3:1997, Category III or as per the grading limits specified
in the table below.
D. The bedding sand shall be uniformly mixed over the compacted subgrade or aggregate
base course, as applicable for pedestrian or vehicular areas, and screeded uniformly to
grade approximately 10 to 15 mm higher than required. Place the concrete paving
blocks in the approved pattern as close together as possible such that the spaces of the
E. The joints in the paving blocks shall be filled with sand complying BS 7533: Part 3: 1997
by sweeping in the jointing sand. The grading limits for the jointing sand specified in BS
7533: Part 3 are indicated in the table below.
G. The concrete paving blocks shall then be tamped down with a mechanical plate vibrator
until pavers are uniformly level, true to grade and free of any movement. The
mechanical plate vibrator shall be equipped with a rubber pad on the tamping face to
minimize damage to the finish surface and appearance of the paving blocks.
END OF SECTION
PART 1 - GENERAL
1.01 SUMMARY
B. Section Includes:
1. Integrally colored Concrete exterior concrete pavements.
1.03 REFERENCES
1.04 SUBMITTALS
B. Product Data: Submit manufacturer's complete technical information sheets for the
following:
1. Color Admixture.
2. Concrete Surface Retarder.
3. Sealer.
4. Bonding Agent.
D. Samples for Initial Selection: Manufacturer's color charts showing full range of colors
available including decorative aggregate type and color.
KEO/19-3262-0000 32 1318/1 Exposed Aggregate Concrete Finishing
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
E. Qualification Data: For firms indicated in "Quality Assurance" article, including list of
completed projects.
B. Concrete Contractor Qualifications: Concrete work shall be performed by firm with five
years experience and must have successfully completed not less than 6 projects
comparable in scale and complexity.
1. Statement of Contractor Qualifications
2. Submit list of at least 5 completed projects including project name, project
address and owner contact information.
C. Comply with the requirements of ACI 301, ACI 302 IR, ACI 303.1, ACI 304, ACI 305,
ACI 306, and ACI 316.
D. Obtain each specified material from same source and maintain high degree of
consistency in workmanship throughout Project.
D. Comply with professional practices described in ACI 305R and ACI 306R.
A. One week prior to placement of concrete a meeting shall be held at the Contractors
site office to discuss the Project and application methods.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 MATERIALS
B. Concrete Retarder –Concrete Surface Retarder; ready to use liquid form surface
retarder for exposing the aggregates of the concrete or approved equivalent.
D. Bonding Agent –Bonding Slurry; ready to use, single component, polymer modified,
cement based slurry for adhering overlays and new concrete to existing concrete
surfaces or approved equivalent.
E. Dry Mix Concrete – Basis of Design: Factory blended concrete conforming to 2.4
Concrete Mix Design, treated with Integral Color Admixture or approved equivalent.
2.03 COLORS
C. Do not add calcium chloride to mix as it causes mottling and surface discoloration.
PART 3 - EXECUTION
3.01 PREPARATION
A. Insure that the concrete substrate is free of moving cracks and honor all joints in the
substrate into the new concrete surface.
B. For a bonded slab construction, apply Bonding Slurry to existing concrete surface in
accordance with manufacturer's instructions.
B. Concrete shall be struck to specified level with wood or metal straight edge.
C. The concrete surface shall be further leveled and consolidated with highway
magnesium straight edge and/or magnesium bull float.
D. Float concrete surfaces with wood or magnesium float or derby as soon as concrete
surface has taken its initial set and bleed water has dissipated from the surface. Do
not over work the concrete surface in order to avoid driving the aggregates down into
the concrete.
KEO/19-3262-0000 32 1318/4 Exposed Aggregate Concrete Finishing
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3.03 EXPOSING THE AGGREGATES
A. Once the concrete surface hardness has reached sufficient stiffness, apply Concrete
Surface Retarder in accordance with manufacturer instructions. Use a solvent-
resistant sprayer to apply the retarder to the surface.
B. Allow the concrete to set overnight or as permitted by weather conditions, then wash
the surface of the concrete to remove the top paste and expose the aggregates. For
best results use a high pressure washer. Take care not to use excessive pressure and
dislodge the aggregates.
C. Do not use plastic sheeting to cure the concrete. For best results use water flooding
to cure the concrete.
D. After the initial curing period, apply clear coat sealer in accordance with manufacturer’s
instructions.
D. Protect floor surface from damage until final inspection and acceptance by Owner.
3.05 TOLERANCES
A. Minor variations in color, aggregate distribution, and appearance are expected and
acceptable.
END OF SECTION
UNIT PAVING
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Section Includes:
1. Precast concrete curbs
2. Stone curbs
3. Precast concrete pavers
4. Natural Stone pavers
B. Related Sections:
1. Section 07 9200 "Joint Sealants" for Joint sealants for expansion joints of paving.
2. Section 31 2000 "Earth Moving" for Granular base under unit pavers.
3. Section 03 3000 "Cast in Place Concrete" for concrete base under unit pavers.
B. Mockups: Build mockups to verify selections made under Sample submittals and to
demonstrate aesthetic effects and set quality standards for materials and execution.
Mock up samples to be 3m x 3m for each paving type including interfaces as required
by the Architect.
1. Location of mock ups to be agreed with Architect.
2. Approved mockups may become part of the completed Work if undisturbed at
time of Substantial Completion.
A. Store pavers on elevated platforms in a dry location. If units are not stored in an
enclosed location, cover tops and sides of stacks with waterproof sheeting, securely
tied.
B. Store cementitious materials on elevated platforms, under cover, and in a dry location.
Do not use cementitious materials that have become damp.
C. Store aggregates where grading and other required characteristics can be maintained
and contamination avoided.
A. Cold-Weather Protection: Do not use frozen materials or materials mixed or coated with
ice or frost. Do not build on frozen subgrade or setting beds. Remove and replace unit
paver work damaged by frost or freezing.
PART 2 - PRODUCTS
A. Concrete Pavers: Paving units complying with ASTM C 936and resistant to freezing
and thawing when tested according to ASTM C 67, made from normal-weight
aggregates.
1. Manufacturers: Subject to compliance with requirements, provide products by
one of the following:
KEO/19-3262-0000 32 1400/2 Unit Paving
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. Thickness: Refer to landscape drawings and material schedule for details
3. Face Size and Shape: Refer to landscape drawings and material schedule for
details
4. Finish: Refer to landscape drawings and material schedule for details
5. Color: Refer to landscape drawings and material schedule for details
B. Concrete Pavers: Solid paving units, made from normal-weight concrete with a
compressive strength not less than 41 MPa, water absorption not more than 5 percent
according to ASTM C 140, and no breakage and not more than 1 percent mass loss
when tested for freeze-thaw resistance according to ASTM C 67. Tactile pavers to be
accordance with UK standard: DD CEN/TS 15209:2008 - Tactile paving surface
indicators produced from concrete, clay and stone.
1. Manufacturers: Subject to compliance with requirements, provide products by
one of the following:
2. Thickness: Refer to landscape drawings and material schedule for details
3. Face Size and Shape: Refer to landscape drawings and material schedule for
details
4. Finish: Refer to landscape drawings and material schedule for details
5. Color: Refer to landscape drawings and material schedule for details
C. Match Architect's samples for color, finish, and other stone characteristics relating to
aesthetic effects.
E. Face Size: Refer to landscape drawings and material schedule for details
2.03 ACCESSORIES
A. Provide stone sealers for all natural stone and for concrete pavers within designated
food and beverage zones within the park.
1. Type: Impregnator solvent based sealer
2. Manufacturers:
3. Subject to compliance with requirements, provide products by one of the
following:
4. Application: Apply to a clean dry, cured surface free from debris, dust, oil, grease
stains and the likes, in accordance to manufacturers direction. Apply repeat coats
if deemed necessary by the Architect. All surrounding materials and surfaces to
be properly protected from excess material.
5. Protect from traffic immediately after application until totally cured in accordance
to manufacturer's recommendations.
C. Color and Texture: Refer to landscape drawings and material schedule for details
2.05 ACCESSORIES
A. The following fillers to be used as expansion joints between curbs at 10m intervals:
1. Compressible Foam Filler: Preformed strips complying with ASTM D 1056,
Grade 2A1.
A. Sand for Leveling Course: Sound, sharp, washed, natural sand or crushed stone
complying with gradation requirements in ASTM C 33 for fine aggregate.
B. Sand for Joints: Fine, sharp, washed, natural sand or crushed stone with 100 percent
passing No. 16 (1.18-mm) sieve and no more than 10 percent passing No. 200 (0.075-
mm) sieve.
1. Provide sand of color needed to produce required joint color.
D. Herbicide: Commercial chemical for weed control, registered with the EPA. Provide in
granular, liquid, or wettable powder form.
C. Water: Potable.
A. General: Comply with referenced standards and with manufacturers' written instructions
for mix proportions, mixing equipment, mixer speeds, mixing containers, mixing times,
and other procedures needed to produce setting-bed and joint materials of uniform
quality and with optimum performance characteristics. Discard mortars and grout if they
have reached their initial set before being used.
C. Packaged Grout Mix: Proportion and mix grout ingredients according to grout
manufacturer's written instructions.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine areas indicated to receive paving, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 PREPARATION
A. Preparation: Ensure that all underground utility lines are located and will not interfere
with the proposed edging installation before beginning work. Locate border line of
edging with string or other means to assure border straightness and curves as
designed.
B. Remove substances from concrete substrates that could impair mortar bond, including
curing and sealing compounds, form oil, and laitance.
C. Sweep concrete substrates to remove dirt, dust, debris, and loose particles.
A. Do not use unit pavers with chips, cracks, voids, discolorations, or other defects that
might be visible or cause staining in finished work.
KEO/19-3262-0000 32 1400/5 Unit Paving
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. Mix pavers from several pallets or cubes, as they are placed, to produce uniform blend
of colors and textures.
C. Cut unit pavers with Pavers shall be cut with a motor driven water-cooled, cut-off wheel
masonry saw using a diamond blade to provide clean, sharp, un-chipped edges. Cut
units to provide pattern indicated and to fit adjoining work neatly. Use full units without
cutting where possible. Hammer cutting is not acceptable.
1. For concrete pavers, a block splitter may be used.
D. Handle protective-coated brick pavers to prevent coated surfaces from contacting backs
or edges of other units. If, despite these precautions, coating does contact bonding
surfaces of brick, remove coating from bonding surfaces before setting brick.
E. Joint Pattern: All paver to be set out using fixed string lines off a fixed perpendicular or
aligned surface.
F. Pavers over Waterproofing: Exercise care in placing pavers and setting materials over
waterproofing so protection materials are not displaced and waterproofing is not
punctured or otherwise damaged. Carefully replace protection materials that become
displaced and arrange for repair of damaged waterproofing before covering with paving.
1. Provide joint filler at waterproofing that is turned up on vertical surfaces unless
otherwise indicated; where unfilled joints are indicated, provide temporary filler or
protection until paver installation is complete.
G. Tolerances: Do not exceed 1/32-inch (0.8-mm) unit-to-unit offset from flush (lippage)
nor 1/8 inch in 10 feet (3 mm in 3m) from level, or indicated slope, for finished surface of
paving.
H. Expansion and Control Joints: Provide for sealant-filled joints at locations and of widths
indicated on structural engineer’s drawings. Provide compressible foam filler as backing
for sealant-filled joints unless otherwise indicated; where unfilled joints are indicated,
provide temporary filler until paver installation is complete. Install joint filler before
setting pavers. Sealant materials and installation are specified in Section 07 9200 "Joint
Sealants."
I. Expansion and Control Joints: Provide cork joint filler at locations and of widths
indicated. Install joint filler before setting pavers. Make top of joint filler flush with top of
pavers.
J. Provide edge restraints as indicated. Install edge restraints before placing unit pavers.
1. Where pavers set in mortar bed are indicated as edge restraints for pavers set in
aggregate setting bed, install pavers set in mortar and allow mortar to cure
before placing aggregate setting bed and remainder of pavers. Cut off mortar
bed at a steep angle so it will not interfere with aggregate setting bed.
2. Where pavers embedded in concrete are indicated as edge restraints for pavers
set in aggregate setting bed, install pavers embedded in concrete and allow
concrete to cure before placing aggregate setting bed and remainder of pavers.
Hold top of concrete below aggregate setting bed.
K. Provide steps made of pavers as indicated. Install paver steps before installing adjacent
pavers.
1. Where pavers set in mortar bed are indicated for steps constructed adjacent to
pavers set in aggregate setting bed, install steps and allow mortar to cure before
placing aggregate setting bed and remainder of pavers. Cut off mortar bed at a
steep angle so it will not interfere with aggregate setting bed.
KEO/19-3262-0000 32 1400/6 Unit Paving
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
L. Cutting: Cut unit pavers with motor-driven masonry saw equipment to provide clean,
sharp, unchipped edges. Cut units to provide pattern indicated and to fit adjoining work
neatly. Use full units without cutting where possible. Hammer cutting is not acceptable.
Where cut pieces turn out to be less than 7.5cm in any dimension they shall be replaced
by 15cm x 25cm, cut to fit.
A. Compact soil subgrade uniformly to at least 95 percent of ASTM D 698 / ASTM D 1557
laboratory density.
B. Proof-roll prepared subgrade to identify soft pockets and areas of excess yielding.
Excavate soft spots, unsatisfactory soils, and areas of excessive pumping or rutting, as
determined by Architect, and replace with compacted backfill or fill as directed.
C. Place separation geotextile over prepared subgrade, overlapping ends and edges at
least 12 inches (300 mm).
D. Place aggregate base, compact to 100 percent of ASTM D 1557 maximum laboratory
density, and screed to depth indicated.
E. Place leveling course and screed to a thickness of 1 to 1-1/2 inches (25 to 38 mm),
taking care that moisture content remains constant and density is loose and uniform
until pavers are set and compacted.
F. Treat leveling course with herbicide to inhibit growth of grass and weeds.
G. Set pavers with a minimum joint width as indicated on landscape detail drawings, being
careful not to disturb leveling base. If pavers have spacer bars, place pavers hand tight
against spacer bars. Use string lines to keep straight lines. Fill gaps between units that
exceed 30mm with pieces cut to fit from full-size unit pavers.
1. When installation is performed with mechanical equipment, use only unit pavers
with spacer bars on sides of each unit.
H. Vibrate pavers into leveling course with a low-amplitude plate vibrator capable of a
3500- to 5000-lbf (16- to 22-kN) compaction force at 80 to 90 Hz. Use vibrator with
neoprene mat on face of plate or other means as needed to prevent cracking and
chipping of pavers. Perform at least three passes across paving with vibrator.
1. Compact pavers when there is sufficient surface to accommodate operation of
vibrator, leaving at least 36 inches (900 mm) of un-compacted pavers adjacent to
temporary edges.
2. Before ending each day's work, compact installed concrete pavers except for 36-
inch (900 mm) width of un-compacted pavers adjacent to temporary edges
(laying faces).
3. As work progresses to perimeter of installation, compact installed pavers that are
adjacent to permanent edges unless they are within 36 inches (90 mm) of laying
face.
4. Before ending each day's work and when rain interrupts work, cover pavers that
have not been compacted and cover leveling course on which pavers have not
been placed with non-staining plastic sheets to protect them from rain.
I. Spread dry sand and fill joints immediately after vibrating pavers into leveling course.
Vibrate pavers and add sand until joints are completely filled, then remove excess sand.
Leave a slight surplus of sand on the surface for joint filling.
KEO/19-3262-0000 32 1400/7 Unit Paving
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
J. Do not allow traffic on installed pavers until sand has been vibrated into joints.
A. Saturate concrete sub-base with clean water several hours before placing setting bed.
Remove surface water about one hour before placing setting bed.
B. Apply mortar bed over bond coat; spread and screed mortar bed to uniform thickness at
sub-grade elevations required for accurate setting of pavers to finished grades
indicated.
C. Mix and place only that amount of mortar bed that can be covered with pavers before
initial set. Before placing pavers, cut back, bevel edge, and remove and discard setting-
bed material that has reached initial set.
D. Place pavers before initial set of cement occurs. Immediately before placing pavers on
mortar bed, apply uniform 1/16-inch- (1.5-mm-) thick bond coat to mortar bed or to back
of each paver with a flat trowel.
E. Tamp or beat pavers with a wooden block or rubber mallet to obtain full contact with
setting bed and to bring finished surfaces within indicated tolerances. Set each paver in
a single operation before initial set of mortar; do not return to areas already set or
disturb pavers for purposes of realigning finished surfaces or adjusting joints.
I. Cure grout by maintaining in a damp condition for seven days unless otherwise
recommended by grout or liquid-latex manufacturer.
A. Remove and replace unit pavers that are loose, chipped, broken, stained, or otherwise
damaged or that do not match adjoining units. Provide new units to match adjoining
units and install in same manner as original units, with same joint treatment and with no
evidence of replacement.
C. Cleaning: Remove excess grout from exposed paver surfaces; wash and scrub clean.
END OF SECTION
AGGREGATE SURFACING
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. The works specified in this section cover all works necessary to prepare, construct and
finish the exterior hard landscape works of the development in coordination with soft
landscape, landscape lighting and other site works and contractors. Works include but
are not limited to the following as per drawings:
1. Dune sand.
2. Gravel surfacing.
1.03 SUBMITTALS
1.04 COMPLIANCE
A. All works shall be carried out in accordance with the requirements of the relevant safety
codes and Local Authority requirements for this work.
A. The Contractor shall supply at time of tender certification of suitability of all materials
and installation techniques for use in the United Arab Emirates (U.A.E.) including but not
limited to climatic conditions, expected maintenance regimes etc.
A. Where materials used in this section have been specified elsewhere in this document,
the relevant clauses shall apply to this section. Materials and workmanship that have not
KEO/19-3262-0000 32 1500/1 Aggregate Surfacing
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
been individually specified shall be of international first class quality and the minimum
standard acceptance shall be the relevant British Standard where applicable.
PART 2 - PRODUCT
B. The product shall comply with BS EN 1176 and be installed to a layer thickness of 100
mm more than that found by laboratory testing to achieve the required critical fall height.
C. The product shall have been tested in accordance with the requirements of BS EN
1176.
A. Filter fabric shall be laid under all aggregate surfaces to provide a free draining
separation layer between the associated sub-base and aggreagate surfacing lapped
300mm and secured at the joints.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine surfaces indicated to receive paving, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance of
Work under this Section. Do not proceed with installation until unsatisfactory conditions
have been corrected.
3.02 PREPARATION
A. Proof-roll prepared subgrade surface to check for unstable areas and areas requiring
additional compaction. Do not proceed with installation until deficient subgrades have
been corrected.
A. General:
1. The Contractor shall make full allowance for the installation of dune sand and
stone gravel where and as described further in the drawings and documents.
B. Installation
1. Aggregate surfacing shall be laid over filter fabric layer. Where placed in areas
without planting, aggegate surfacing shall be installed over a compacted – 95%
sub base. The Contractor shall supply a sample area for approval by the
Engineer.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Furnish all labor, materials, tools and equipment and perform all services and operations
necessary for the complete supply and installation of supply and installation of the
following as per drawings.
1. Traffic painted markings.
2. Removable rubber speed bumps at Basement Parking area
B. Related Sections: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
1. Section 07 1800 - Traffic Coatings
1.02 REFERENCES
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contract unless otherwise indicated. Product
manufacture, testing and installation shall comply with the following references in the
specification or otherwise approved including:
1. ASTM D 412 Standard Test Methods for Vulcanized Rubber and
Thermoplastic Elastomers - Tension
2. ASTM D 624 Standard Test Method for Tear Strength of Conventional
Vulcanized Rubber and Thermoplastic Elastomers
3. ASTM D 792 Standard Test Methods for Density and Specific Gravity
(Relative Density) of Plastics by Displacement
4. ASTM D 2240 Standard Test Method for Rubber Property – Durometer
Hardness
5. ASTM D 4280 Standard Specification for Extended Life Type,
Nonplowable, Raised Retroreflective Pavement Markers
1.03 SUBMITTALS:
A. Product Data: For each type of product indicated. Include the following:
1. Construction details and dimensions.
2. Anchoring and mounting requirements, including requirements for cutouts in
other work and substrate preparation.
3. Material and finish descriptions.
B. Certificates Submittals
1. Traffic-calming devices shall be factory stamped as being in compliance
with local guidelines.
1.06 WARRANTY
A. Submit a written warranty signed by Contractor agreeing to repair or replace Work under
this Section that fails in materials and workmanship at no additional cost within specified
warranty period.
1. Traffic markings 3 years
2. Speed bumps 2 years
3. Wheel stoppers 2 years
PART 2 - PRODUCTS
2.01 MATERIALS
A. Anchors and Inserts: use non-ferrous metal or hot-dipped galvanized anchors and
inserts for exterior installations and elsewhere as required for corrosion resistance.
Furnished inserts as required to be set into concrete or masonry work.
A. Traffic Paint: Alkyd-resin ready mixed, complying with AASHTO M 248, type F
1. Color: White / Yellow.
A. Speed Guards: Supply and installation of car-speed breakers including all speed guard
units and all fastening systems including long expansion bolts.
KEO/19-3262-0000 32 1716/2 Manufactured Traffic-Calming Devices
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Size: 460 mm width x 75mm height at the centre, tapering to zero heights at the
ends. Length per unit is 250mm.
2. Units are installed with alternating yellow and black colour. A black colour
specific end unit has to be installed at each end of the speed-breaker.
3. Reflective red colour eyes (protected from wheel impact) must be incorporated in
each unit, on either sides.
4. Each unit is designed for an expansion bolt fixing on either side.
5. Physical properties of the rubber
a. Hardness (BS 903 A57) 68-73 shore A
b. Special gravity (BS 903 A1) 1.48 – 1.51
c. Tensile strength (BS 903 A2) 120 kg/cm2 (min)
d. Elongation at break (BS 903 A2) 400% (min)
e. Tear strength (BS 903 A3) 40 N/mm (min)
f. Ozone resistance (BS 903 A43) No cracks
g. Compression set (BS 903 A6) 20% max
6. The car speed-breakers shall be installed only after complete coating of the floor.
7. Fixing must be done with min galvanized steel bolt anchors compatible with
concrete floors. Expansion bolts must be minimum 100 mm long.
PART 3 - EXECUTION
3.01 INSTALLATION
A. General: Locate all units and accessories, using mounting methods of the type
described and in compliance with the applicable standards.
1. Install speed guards and wheel stoppers as per recommendations of the
manufacturer.
A. After installation, clean soiled sign surfaces according to the manufacturer's instructions.
Protect units from damage until time for completion.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and other Division 01 Specification Sections, apply to this Section. Refer to
Hardscape Material schedule LS-GN-043.
A. Furnish all labor, materials, plant, tools and equipment, and perform all operations
necessary for the complete supply and installation of play surface and edging as
indicated on schedule and drawings.
1.03 DEFINITIONS
A. Critical Height: Standard measure of shock attenuation. According to CPSC No. 325,
this means "the fall height below which a life-threatening head injury would not be
expected to occur."
1.05 SUBMITTALS
C. Samples for Initial Selection: For each type of playground surface system indicated.
1. Include similar Samples of playground surface system and accessories involving
color selection.
D. Samples for Verification: For each type of playground surface system indicated.
KEO/19-3262-0000 32 1816.13/1 Playground Protective Surfacing
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Provide stepped samples on backing large enough to illustrate build-up of
flooring.
C. Source Limitations: Obtain playground surface system materials through one source
from a single manufacturer.
1. Provide secondary materials including adhesives, primers and repair materials of
type and from source recommended by manufacturer of playground surface
system materials.
A. Weather Limitations: Proceed with installation only when existing and forecasted
weather conditions permit playground surface system installation to be performed
according to manufacturers' written instructions and warranty requirements.
1.08 COORDINATION
1.09 WARRANTY
PART 2 - PRODUCTS
B. Mix:
1. Base layer and top layer rubber granules mixed with MDI binder in precise ratios
as per manufacturer’s recommendation.
2. Base Layer: Mix base layer SBR with MDI binder at manufacturer advised ratios
and pour/screed to required thickness. Allow 24 hours for curing.
3. Top Layer: Mix top layer EPDM with MDI binder at manufacturer advised ratios
and pour/screed to required thickness. Allow 24 hours for curing before use.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine surfaces indicated to receive paving, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance of
Work under this Section. Do not proceed with installation until unsatisfactory conditions
have been corrected.
3.02 PREPARATION
A. Testing Agency: A qualified independent testing and inspecting agency to perform field
tests and inspections and prepare test reports.
C. Remove and replace applications of playground surface system where test results
indicate that it does not comply with requirements.
3.05 PROTECTION
A. Prevent traffic over system for not less than 48 hours after installation.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section. Refer to Hardscape
plan drawings series; Material schedule LS-GN-043; and Typical Hardscape details series.
A. Furnish all labour, materials, tools and equipment and perform all services and
operations necessary for the complete supply and installation of exterior stone cladding
and copings on walls with mechanical anchors or mortar and steel wires as shown on
landscape drawings.
B. Related Section: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
1. Section 03 3000 - Cast-in-place Concrete.
2. Section 07 9200 - Joint Sealants.
1.02 REFERENCES
A. All reference to standards, regulations and requirements of statutory bodies shall mean
the latest published editions at the time of contract. Product manufacture, testing and
installation shall comply with the following references unless otherwise stated in the
specification or otherwise approved.
1. ASTM A 276: Specification for Stainless Steel Bars and Shapes.
2. ASTM C 97: Test Methods for Absorption and Bulk Specific Gravity of
Dimension Stone.
3. ASTM C 119: Terminology Relating to Dimension Stone.
4. ASTM C 99: Test methods for Modulus of Rupture of Dimensional stone.
5. ASTM C 144: Specification for Aggregate for Masonry Mortar.
6. ASTM C 170: Test Method for Compressive Strength of Dimensional
Stone.
7. ASTM C 568: Specification for Limestone.
8. ASTM C 615: Specification for Granite Dimension Stone.
9. ASTM C 616: Specification for Quartz-Based Dimension Stone Sandstone
10. ASTM C 880: Test Method for Flexural Strength of Dimensional Stone.
11. ASTM C 1201: Test Method for Structural Performance of Exterior
Dimension Stone Cladding Systems by Uniform Static Air Pressure Difference
12. ASTM C 1242: Guide for the Selection, Design, and Installation of Exterior
Dimension Stone Anchors and Anchoring Systems.
13. ASTM C 1354: Test Method for Strength of Individual Stone Anchorages in
Dimension Stone.
14. ASTM E 488: Test Methods for Strength of Anchors in Concrete and Masonry
Elements.
15. ASTM F 593: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs.
16. ANSI A 118.3: Specifications for Epoxy Adhesive Grout.
17. ANSI A 118.4: Specifications for Latex-Portland Cement Mortar.
KEO/19-3262-0000 32 3249/1 Exterior Stone Cladding
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1.03 PERFORMANCE REQUIREMENTS
B. Control of Corrosion and Staining: Prevent galvanic and other forms of corrosion as well
as staining by isolating metals and other materials from direct contact with incompatible
materials. Use materials that do not stain exposed surfaces of stone and joint materials.
1.04 DEFINITIONS
A. Polished Finish: Smooth finish that produces sharp, mirror like reflections. Reflected
images of overhead fluorescent tubes have straight lines without visible distortion when
viewed at arm’s length.
B. Honed Finish: Smooth, non reflective finish similar to that produced by grinding with a
400 to 1200 grit abrasive; with a gap not exceeding 0.13 mm when faces are tested for
flatness with a 600 mm straightedge.
C. Filled Finish: Travertine slabs, filled with cement or epoxy and then polished or honed
to produce typical finish.
D. Split face; A rugged, uneven, concave-convex finish that reveals reflections from the
crystal is produced by the splitting action of a guillotine.
F. Bush-Hammered finish: A rough textures finish that is developed by pounding stone with
a hammer that has square end divided into number of pyramid points.
G. Antique Finish: Textured finish with stone tumbled with sand, pebbles or ball bearings
to create a weathered, textured, aged finish.
1.05 SUBMITTALS:
A. Product Data: For variety of stone, stone accessory, and other manufactured products
indicated.
C. Stone for verification: Include five samples 300 x 300 mm for each color, finish and
variety of stone, showing the full range of variations in appearance characteristics.
A. Mockups: Before installing stone cladding, build mockups to verify selections made
under sample Submittals and to demonstrate aesthetic effects and qualities of materials
and execution. Build mockups to comply with the following requirements, using
materials indicated for the completed Work:
1. Locate mock-up in the location and of the size indicated or, if not indicated, as
directed by the Engineer and/or Landscape Architect.
2. Mockup shall be complete with adjoining material to the satisfaction of the
Engineer and/or Landscape Architect. If the required standard is not achieved,
the Contractor shall replace (at the contractors cost) until the required standard is
achieved as judged by the Engineer and/or Landscape Architect.
3. Demonstrate the proposed range of aesthetic effects and workmanship.
4. Obtain written approval of mock-up from the Engineer and/or Landscape
Architect before starting paving.
5. Maintain mock-ups during construction in an undisturbed condition as a standard
for judging the completed Work.
6. Mock up shall become part of finished work if approved by the Engineer and/or
Landscape Architect at the time of Substantial Completion
A. Stones shall be carefully packed for shipment using all reasonable care and customary
precautions against damage in transit. Lift stone with wide-belt slings; do not use wire
rope or ropes that might cause staining. Move stone, if required, using dollies with
cushioned wood supports.
B. Polyethylene or other suitable plastic film shall be placed between wood and finished
surfaces of completely dry stone. No material which may cause staining or discoloration
shall be used for blocking or packing.
C. Each pallet shall bear the identification label with information regarding stone type, size,
thickness finish and Quarry Source/location/vendor information.
E. Upon receipt at the site or storage yard, the pallets shall be stacked on platforms at
least 100 mm above the ground. Extreme care shall be taken to prevent staining or
discoloration during storage.
F. Store and handle stone and related materials to prevent deterioration or damage due to
moisture, temperature changes, contaminants, corrosion, breaking, chipping, or other
causes. Arrange to distribute weight evenly and to prevent damage to stone. Use non-
staining, waterproof covers as an overall protective covering. Ventilate under covers to
prevent condensation.
1.09 WARRANTY
PART 2 - PRODUCTS
2.01 GENERAL
A. Stone Suppliers
C. Sealers
A. Provide stone that is free of cracks, seams, and starts impairing structural integrity or
function.
B. Quarry stone in a manner to ensure as-quarried block orientations yield finished stone
with required characteristics.
C. All stone shall be of soundness, texture, graining, color, finish and tone matching the
approved sample.
D. Stone type:
KEO/19-3262-0000 32 3249/4 Exterior Stone Cladding
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2.05 PHYSICAL CHARACTERISTICS OF STONE
A. Provide anchors and anchoring systems and attachments of type and size required to
support stone works and fabricated in accordance with ASTM C 1242 from the following
metals for conditions and anchors indicated below:
1. Stainless steel: ASTM A 666, Type 316, to support loads imposed without
exceeding allowable design stresses, for anchors in direct contact with stone and
the fasteners connecting them to other anchors and to building structure.
A. Portland Cement: ASTM C 150, Type I or Type II. Provide natural color or white
cement as required to produce mortar color indicated.
1. Low-Alkali Cement: Portland cement for use with limestone shall contain not
more than 0.60 percent total alkali when tested according to ASTM C 114.
D. Water: Potable.
E. Grout shall be shrink free type and as recommended by the manufacturer for the type of
tiles. There shall be a preliminary trial area (for each type of tiles) grouted to check that
they can be cleaned off satisfactorily. Where it causes discoloration on tiles after
cleaning, apply a protective wax coating on tiles before grouting.
A. Wire Tiebacks: 3.0-mm diameter, stainless steel wire. As deemed necessary by the
project engineer for all walls over 2m in height and stone over 20mm thk.
A. General: Comply with referenced standards and with manufacturers' written instructions
for mix proportions, mixing equipment, mixer speeds, mixing containers, mixing time,
and other procedures needed to produce mortar of uniform quality and with optimum
performance characteristics.
1. Do not use admixtures, including pigments, air-entraining agents, accelerators,
retarders, water-repellent agents, antifreeze compounds, or other admixtures,
unless otherwise indicated. Do not use calcium chloride.
2. Combine and thoroughly mix cementitious materials, water, and aggregates in a
mechanical batch mixer, unless otherwise indicated. Discard mortar when it has
reached initial set.
C. Pointing Mortar: Comply with ASTM C 270, Proportion Specification, for types of mortar
indicated. Provide pointing mortar mixed to match samples approved by engineer
and/or Landscape architect. Or complying with the following:
1. Point stone with Type N mortar.
A. General: Fabricate stone units in sizes and shapes required to comply with
requirements indicated, including details on Drawings and Shop Drawings.
C. Cut and drill sinkages and holes in stone for anchors, fasteners, supports, and lifting
devices as indicated or needed to set stone securely in place; shape beds to fit
supports.
D. Cut stone to produce pieces of thickness, size, and shape indicated and to comply with
fabrication and construction tolerances recommended by applicable stone association
or, if none, by stone source, for faces, edges, beds, and backs.
1. Cut stone to produce joints of uniform width and in locations indicated.
2. Clean backs of stone to remove rust stains, iron particles, and stone dust.
3. Factory fabricate corner/return units as one piece using stainless steel dowel as
required, set in epoxy resin.
4. Finish exposed faces and edges of stone to comply with requirements indicated
for finish and to match approved samples and mockups.
5. Carefully inspect finished stone units at fabrication plant for compliance with
requirements for appearance, material, and fabrication. Replace defective units.
6. Grade and mark stone for overall uniform appearance when assembled in place.
Natural variations in appearance are acceptable if installed stone units match
range of colors and other appearance characteristics represented in approved
samples and mockups.
7. Fabricate units straight and true to size and shape with edges and corners
precise and true so each unit complies with the following tolerances:
a. Dimensional Tolerances:
1) Thickness: 3 mm.
2) Face dimension: 1.5 mm.
3) Face variation from rectangular: 1.5 mm.
b. Flatness Tolerances: Variation from true plane or flat surfaces as
determined by a 1.2 m dimension in any direction shall not exceed the
following tolerances:
1) Polished finishes: 1 mm.
2) Flamed finishes: 1.5 mm.
3) Bush Hammered: 3-5mm.
4) Honed Finishes: 1mm.
2.011 FINISHES
A. Stone
KEO/19-3262-0000 32 3249/6 Exterior Stone Cladding
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Finishes shall be uniform and non-directional unless otherwise approved.
2. Finishing shall apply to all surfaces exposed in the finished work.
3. For finish type: Refer to material schedule drawing.
A. Surface sealer for stone: Colorless, breathable water repellent/impregnator which will
impart water repellent properties to stone, prevent damage from soiling, fungus and
mold growth. Product shall not affect the color and physical properties of stone initially
and over time. Sealer recommended by stone fabricator and acceptable to Engineer.
Seal back surfaces and edges of stone and cut edges prior to installation. Seal front
surfaces of stone after installation
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine surfaces to receive exterior stone cladding and conditions under which stone
cladding will be installed, with Installer present, for compliance with requirements for
installation tolerances and other conditions affecting performance.
1. For the record, prepare written report, endorsed by Installer, listing conditions
detrimental to performance of dimension stone cladding.
2. Proceed with installation only after unsatisfactory conditions have been
corrected.
3.02 PREPARATION
A. Advise installers of other work about specific requirements for placement of inserts,
flashing reglets, and similar items to be used by stone cladding Installer for anchoring
and supporting of dimension stone cladding. Furnish installers of other work with
Drawings or templates showing locations of these items.
C. Clean the face of stone surfaces that are dirty or stained by removing soil, stains, and
foreign materials before setting. Clean stone by thoroughly scrubbing with fiber brushes
and then drenching with clear water. Use only mild cleaning compounds that contain no
caustic or harsh materials or abrasives.
A. Distribute units of acceptable ranging color or texture evenly over the entire installation
to avoid patches or streaks, to produce a homogeneous blending of all units. If an
acceptable pattern or grain direction is apparent, due to natural appearance of stone, or
finishing, install units so that pattern or grain is in one direction unless otherwise
directed.
C. Set stone work level, plumb, square and true with uniform joints, aligned and flush with
adjacent units. Chipped, broken or blemished units shall be rejected.
D. Cooperate fully with the masonry, cast-in-place concrete and structural steel sections
and schedule this work to coordinate with the work of those sections.
E. Execute dimension stone cladding installation by skilled mechanics and employ skilled
stone fitters at Project site to do necessary field cutting as stone is set.
1. Use power saws with diamond blades to cut stone. Produce lines cut straight
and true, with edges eased slightly to prevent snipping.
F. Set stone to comply with requirements indicated on Shop Drawings. Install anchors,
supports, fasteners, and other attachments indicated or necessary to secure stone
cladding in place. Shim and adjust anchors, supports, and accessories to set stone
accurately in locations indicated with uniform joints of widths indicated and with edges
and faces aligned according to established relationships and indicated tolerances.
A. Variation from Plumb: For vertical lines and surfaces of walls, and external corners do
not exceed 3 mm in 3 m, 6mm in 6 m, or 9 mm in 12 m or more.
B. Variation in Plane between Adjacent Stone Units (Lipping): Do not exceed 1.5-mm
difference between planes of adjacent units.
A. Stone Facing around water features: Set stone by adhering to plaster backing with
water-cleanable epoxy adhesive
B. Stone Facing: Set stone by adhering to leveling mortar backing with polymer-modified
adhesive.
1. Thin Bed Method: Install latex portland cement mortar in compliance with current
revisions of ANSI A108.02 (3.11), ANSI A108.5. Use the appropriate trowel
notch size to ensure proper bedding of the stone selected. Work the latex
portland cement mortar into good contact with the substrate and comb with
notched side of trowel. Spread only as much latex portland cement mortar as
can be covered while the mortar surface is still wet and tacky. When installing
spread latex portland cement mortar onto the back of (i.e. ‘back-butter’) each
piece/sheet in addition to trowelling latex portland cement mortar over the
substrate. Beat each piece/sheet into the latex portland cement mortar with a
beating block or rubber mallet to insure full bedding and flatness. Allow
installation to set until firm. Clean excess latex portland cement mortar from
stone face and joints between pieces.
D. Grout stone joints to comply with ANSI A108.10 and manufacturer's written instructions.
1. Grout joints as soon as possible after initial set of setting bed. Force grout into
joints, taking care not to smear grout on adjoining stone and other surfaces.
2. Cure grout as per manufacturer’s instructions.
A. Prepare joints and apply sealants of type and at locations indicated to comply with
applicable requirements in Division 07 Section "Joint Sealants."
A. Upon completion of installation of the work of this Section, allow examination for cracks
and other damage and defects in the installed stone. Replace defective units.
A. Remove and replace broken, chipped, stained, or otherwise damaged stone, defective
joints, and dimension stone cladding that does not match approved samples and
mockups. Damaged stone may be repaired if approved.
B. Replace in a manner that results in stone cladding's matching approved samples and
mockups, complying with other requirements, and showing no evidence of replacement.
C. Clean exterior stone, using clean water and stiff-bristle fiber brushes. Do not use wire
brushes, acid-type cleaning agents, cleaning agents containing caustic compounds or
abrasives, or other materials or methods that could damage stone.
END OF SECTION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
B. It is the intent of the specifications and drawings that the finished irrigation system is
complete in every aspect and shall be ready for operation satisfactory to the owner.
C. The work shall include all materials, labor, services, transportation, and equipment
necessary to perform the work as indicated on the drawings, in these specifications,
and as necessary to complete the contract.
D. Best general practice and first-class materials are to be used for all contract works
whether expressly specified, noted or implied in the contract documents or as May
otherwise be required to undertake and complete the works in accordance with the
design intent of the contract documents. the apparent silence of the specification,
drawings or other contract documents as to any detail or the apparent omission from
them of a detailed description concerning any point, shall be regarded as meaning that
only the best general practice is to be used. All interpretations of the specifications will
be made on this basis.
The contractor shall seek clarification from the Engineer for any apparent conflict or
discrepancy between drawings, specifications, irrigation bill of quantities,
manufacturer’s recommendations and other contract documents, prior to commencing
work.
A. The contractor will work with the design team to ensure that the work is complete. Do
not proceed with any aspect of the work which is unclear or which has not been
specifically authorized by the owner.
B. Due to the scale of the drawings, it is not possible to indicate all offsets, fittings,
sleeves, etc., which may be required. The contractor shall carefully investigate the
structural and finished conditions affecting all of his work and plan his work
accordingly, furnishing such fittings, etc. as may be required to meet such conditions.
KEO/19-3262-0000 32 8100/1 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
Drawings are generally diagrammatic and indicative of the work to be installed. The
work shall be installed in such a manner as to avoid conflicts between irrigation
systems, planting, and architectural features.
C. All work called for on the drawings by notes or details shall be furnished and installed
whether or not specifically mentioned in the specifications. When an item is shown on
the plans but not shown on the specifications or vice versa, it shall be deemed to be
as shown on both. The owner’s authorized representative shall have final authority for
clarification.
D. The contractor shall not willfully install the irrigation system as shown on the drawings
when it is obvious in the field that obstructions, grade differences or discrepancies in
area dimensions exist that might not have been considered in engineering. Such
obstructions or differences should be brought to the attention of the owner’s authorized
representative as soon as detected.
1.04 SUBMITTALS
B. Material
1. All Materials described in the specifications are to be submitted for approval
prior to installation.
2. The contractor shall submit samples of all Materials, which are proposed to be
used in the system prior to their installation.
3. Any materials installed which are not approved may be rejected and the
contractor shall replace them, at his own cost, with acceptable items.
1.05 INSPECTIONS
A. The contractor shall permit the Engineer and owner’s authorized representative to visit
and inspect at all times any part of the work and shall provide safe access for such
visits.
B. The contractor shall be solely responsible for notifying the architect, owner, and
governing agencies, a minimum of 48 hours in advance, where and when the work is
ready for testing. Should any work be covered without testing or acceptance, it shall
be, if so ordered, uncovered at the contractor's expense.
KEO/19-3262-0000 32 8100/3 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. Inspections will be required for the following at a minimum:
1. System layout.
2. Pressure test of irrigation mainline (2 hours at 8.62 bars (125 psi) or 120% of
static water pressure, whichever is greater.) mainline pressure loss during test
shall not exceed 0.14 bars (2 psi).
3. Final inspection prior to start of maintenance period.
4. Final inspection prior to turnover.
D. Site observations and testing will not commence without the field record drawings as
prepared by the contractor. Record drawings must complete and up to date for each
site visit.
E. Work that fails testing and is not accepted will be retested. Hourly rates and expenses
of the architect, owner’s authorized representative, and governing agencies for re-
inspection or retesting will be paid by the contractor at no additional expense to owner.
A. The contractor shall verify and be familiar with the locations, sizes and details of points
of connection provided as the source of water and electrical supply to the irrigation
system.
B. The contractor shall verify and be familiar with the existing irrigation systems in areas
adjacent to and within the project area of work.
C. Irrigation design is based on the available dynamic water pressure and flow shown on
the drawings. Contractor shall verify water pressure and flow on the project prior to the
start of construction. Should a discrepancy exist, notify the Engineer and owner has
authorized representative prior to beginning construction.
D. The contractor shall protect all existing utilities and features to remain on and adjacent
to the project site during construction. Contractor shall repair, at his own cost; all
damage resulting from his operations or negligence.
E. The irrigation contractor shall coordinate with the general contractor for installation of
required sleeves.
F. Prior to cutting into the soil, the contractor shall locate all cables, conduits, sewer septic
tanks, and other utilities as are commonly encountered underground and he shall take
proper precautions not to damage or disturb such improvements. If a conflict exists
between such obstacles and the proposed work, the contractor shall promptly notify
the Engineer and owner’s authorized representative, who will arrange for relocations.
The contractor will proceed in the same manner if a rock layer or any other such
conditions are encountered.
A. All materials supplied for this project shall be new and free from any defects. All
defective materials shall be replaced immediately at no additional cost to the owner.
C. Provide at least one English speaking person who shall be present at all times during
execution of this portion of the work and who shall be thoroughly familiar with the type
of materials being installed and the manufacturer's recommended methods of
installation and who shall direct all work performed under this section.
D. All local and municipal laws, rules and regulations governing or relating to any portion
of this work are hereby incorporated into and made a part of these specifications, and
their provisions shall be carried out by the contractor. Anything contained in these
specifications shall not be construed to conflict with any of the above rules and
regulations. However, when these specifications and drawings call for or describe
materials, workmanship, or construction of a better quality, higher standard, or larger
size than is required by the above rules and regulations, the provisions of these
specifications and drawings shall take precedence.
E. The contractor shall secure the required licenses and permits including payments of
charges and fees, give required notices to public authorities, verify permits secured or
arrangements made by others affecting the work of this section.
A. Dispose of waste, trash, and debris shall be done in accordance with applicable laws
and ordinances and as prescribed by authorities.
C. The contractor shall remove and dispose of rubbish and debris generated by his work
at frequent intervals or when ordered to do so by the owner’s authorized
representative.
D. At the time of completion, the entire site shall be cleared of tools, equipment, rubbish
and debris, which shall be disposed of off-site in a legal disposal area.
1.09 COMPLETION
A. At the time of the pre-maintenance period inspection, the architect, owner’s authorized
representative, and governing agencies will inspect the work, and if not accepted, will
prepare a list of items to be completed by the contractor. Punch list to be checked off
by contractor and submitted to the Engineer or owner’s authorized representative prior
to any follow-up meeting. This checked off list to indicate that all punch list items have
been incomplete. At the time of the post-maintenance period, the work will be re-
inspected and final acceptance will be made in writing by the architect, owner has
authorized representative, and governing agencies.
B. Any settling of trenches which may occur during the one-year period following
acceptance shall be repaired to the owner's satisfaction by the contractor without any
additional expense to the owner. Repairs shall include the complete restoration of all
damage to planting, paving or other improvements of any kind because of the settling
and subsequent repair work.
C. The owner’s authorized representative shall have the final authority on approving and
accepting all portions of the work.
A. Type: Screen
B. Standard: NA
C. Material:
1. Body: Plastic
2. Frame Polypropylene
3. Screen: Stainless steel 316
D. Flow rate:
Filter Size Up to Flow Rate (gpm)
1” 26
1.5” 88
2” 110
I. Housing dimensions:
Filter Size Depth (cm) Width (cm)
1” 17 19
1.5” 24 16
2” 25 27
J. Warranty: 3 years
A. Pipe:
1. Standard: BS EN ISO 1452-2:2009
2. Kitemark™ Approved: Yes
3. Class E&D
4. Joint:
A. Solvent Cements
B. Push Fit
5. Preferred color: Dark grey.
6. Preferred pipe segment length: 6m.
7. Warranty: 10 years
B. Fittings:
KEO/19-3262-0000 32 8100/6 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1. Standard: BS EN ISO 1452-3:2010
2. Kitemark™ Approved: Yes
3. Warranty: 10 years
A. Standard: BS 3506:1969
B. Class: C
E. Warranty: 10 years
A. Standard: BS 3506:1969
B. Class: E
E. Warranty: 10 years
A. Standard: BS1972-67
B. Material: LDPE
C. Class: C
E. Color: Black
F. Size: ½”
G. Warranty: 5 years
B. Material: Polypropylene
C. Size: length: 22 cm
D. Warranty: 1 year
KEO/19-3262-0000 32 8100/7 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2.07 WARNING TAPE
G. Warranty: 5 year
B. Standard:
1. Body: EN-GJS-400-18
2. Bonnet: EN-GJS-400-18
3. Coating: 300 µ
4. Wedge: EN-GJS-400-18
5. Spindle: ST 1.4021
6. Flanges: BS EN 1092-2:1997
7. Test: EN1074
F. Sizes: DN 50 to DN 200
G. Warranty: 10 years
B. Standard
1. Body: EN-GIS-400-18
2. Bonnet: EN-GIS-400-18
3. Coating: 300 µ
4. Wedge: EN-GIS-400-18
5. Spindle: ST 1.4021
6. Threads: ISO 228
7. Test: EN1074
F. Warranty: 10 years
B. Standard:
1. Flange: BSEN 1092-2
2. Coating: DIN30677-2
C. Material:
1. Body: Coated ductile iron
2. Bonnet: Coated ductile iron
3. Bolts and nuts: Stainless steel
4. Gasket: EPDM
D. PN: 16 bar
E. Weight 24 kg
F. Warranty: 10 years
B. Standard: NA
C. Material:
1. Body: Polyoxymethylen
2. Float: Polyoxymethylen
3. Seal: Elastomer
4. Orifice: Brass
5. Valve Plug Brass
6. Valve Seat: Brass
D. PN: 6 bar
E. Weight: 0.9 kg
F. Warranty: 10 years
A. Valve:
1. Type: Forward flow design
2. Normally: Closed
3. Material:
a. Body: Glass filled nylon
b. Bonnet: Glass filled nylon
c. Diaphragm: EPDM
KEO/19-3262-0000 32 8100/9 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
d. Bolt and nut: Stainless steel
4. Activation: Electric
5. Flow: 5-220 gpm
6. Maximum operating pressure: 220 psi
7. Burst pressure: 750 psi
8. Manual flow control: Yes
9. Special port for the solenoid: Yes
10. Self-cleaning metering rod: Yes
11. Internal & external manual bleed: Yes
12. Built in Schrader valve: Yes
13. Warranty: 5 years
B. Pressure regulator:
1. Serviceable under pressure Yes
2. Dial design Yes
3. Size: NA
4. Warranty: 5 years
B. Material:
1. Body: Brass
2. Spring: Stainless steel
E. Accessories to include:
Locking cover, hose swivel, key & hose
F. Warranty 3 years
A. Power: Mains
B. Material: Plastic
E. Program number 99
F. Supports up to
1. 8 master valves. Yes
2. 8 flow sensors. Yes
M. Warranty: 3 years
A. Type Cloud
A. Impeller GFN
G. Accuracy: ± 1%
I. Output: Pulse
J. Warranty: 1 Year
2.017 CABLES
KEO/19-3262-0000 32 8100/11 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
A. Type: Irrigation control cable UF
B. Standard: UL listed
C. Material:
1. Insulation: Polyvinyl Chloride
2. Jacket: Impregnated Polyethylene
3. Conductor: Copper
D. Number of conductors: 2
G. Size: 14 AWG
H. Warranty: 1 year.
B. Standard: NA
C. Material: Polypropylene
F. Dimension:
1. Length: 9.4 cm
2. Diameter: 2.5 cm
G. Warranty: 1 year
A. Body:
1. Type: Pop up
2. Standard: NA
3. Material:
a. Body: Plastic
b. Stem: Plastic
c. Screen: Plastic
d. Spring: Stainless steel
e. Wiper seal: Elastomer
4. Built in:
a. Pressure regulator
b. Check valve
c. Two piece ratcheting mechanism
5. Debris pockets Yes
6. Zero flush seal on pop up Yes
KEO/19-3262-0000 32 8100/12 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
7. Pre-installed flush plug Yes
8. Dimension:
a. Body height: 6”
b. Pop up height: 4”
c. Exposed diameter: 2.25”
d. Inlet: 0.5”
9. Female Threads Inlet Yes
10. Warranty: 5 years
B. Nozzle:
1. Type: MPR Rotary
2. Radius: 4 to 5.5 m and 5.5 to 7.5 m
3. Material:
a. Nozzle: Plastic
b. Filter: Plastic
c. Adjustment screw: Stainless steel
4. Optimum Operating Pressure 2.5 bar
5. Precipitation rate 15.2 mm/h
6. The angel of trajectory 1 to 30 degree
7. Radius reduction Yes
8. Removable screen filter Yes
9. Color coded Yes
10. Warranty: 3 years
A. Body:
1. Type: Pop up
2. Standard: NA
3. Material:
a. Body: Plastic
b. Stem: Plastic
c. Screen: Plastic
d. Spring: Stainless steel
e. Wiper seal: Elastomer
4. Built in:
a. Pressure regulator
b. Check valve
c. Two piece ratcheting mechanism
5. Debris pockets Yes
6. Zero flush seal on pop up Yes
7. Pre-installed flush plug Yes
8. Dimension:
a. Body height: 6”
b. Pop up height: 4”
c. Exposed diameter: 2.25”
9. Warranty: 5 years
B. Bubbler:
1. Type: Pressure compensating
2. Flow: 0.25, and 0.5 gpm
3. Threads Female
4. Warranty: 1 year
KEO/19-3262-0000 32 8100/13 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2.021 ROOT WATERING SYSTEM
A. Basket:
1. Material Polyethylene
2. Length: 45 cm
3. Width 10 cm
4. Rigid mesh material Yes
5. Integrated bubbler Yes
6. Pre-configured with swing joint Yes
7. Warranty: 3 years
B. Grate
1. Material Polyethylene
2. Size 10 cm
3. Locking grate cover Yes
4. Warranty: 3 years
C. Bubbler:
1. Type: Pressure compensating
2. Check valve Yes
3. Flow: 0.25, and 0.5 gpm
4. Warranty: 1 year
B. Standard NA
D. Self-flushing: Yes
E. UV-resistant Yes
A. Inline emitter:
1. Type: Inline
2. Standard ISO 9261:2004
3. Material: Plastic
4. Pressure compensating Yes
5. Flow Type Turbulent
6. Self-flushing Yes
7. Clogging resistant Yes
8. Constant flow range 0-60⁰
KEO/19-3262-0000 32 8100/14 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
9. Coefficient of variation <5%
10. Operating pressure: 0.5 – 4.5 bar
11. Required filtration: 150 mesh
12. Flow: 3.5 l/h AND 2.4 l/h
13. Spacing 30.5 & 46 cm
14. Warranty: 7 years
B. Drip tubing:
1. Type: Drip tubing
2. Standard ISO 9261:2004
3. Material: LDPE
4. Minimum carbon black 2.8%
5. OD 16 mm
6. WTH 1.1 mm
7. Warranty: 7 years
C. Fittings:
1. Type Bush
2. Standard: NA
3. Material: High impact plastic & ABS
4. UV-resistant: Yes
5. Warranty: 3 Years
A. Inline emitter:
1. Type: Inline emitter
2. Standard: NA
3. Material:
A. Body: Polyethylene blend
B. Cover: Polyethylene blend
C. Diaphragm: Silicone
D. Copper Chip: Pure copper
4. Pressure compensating Yes
5. Flow Type Turbulent
6. Self-flushing Yes
7. Copper shield technology Yes
8. Clogging resistant Yes
9. Constant flow range 4-43⁰
10. Coefficient of variation <5%
11. Operating pressure: 0.58 – 4.14 bar
12. Required filtration Min: 120 mesh
13. Flow: 0.92 gph
14. Spacing 30 .5 cm
15. Warranty: 7 years
B. Drip tubing:
1. Type: Drip tubing
2. Standard NA
3. Material: LDPE
4. Minimum carbon black: UV protection
5. OD: 16 mm
KEO/19-3262-0000 32 8100/15 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
6. WTH: 1.2 mm
7. Warranty: 7 years
C. Fittings
1. Type Insert
2. Standard NA
3. Material: Acetal thermoplastic
4. UV-resistant: Yes
5. Warranty: 3 years
D. Auxiliary equipment:
1. Operation indicator.
2. Secondary filtration.
3. Quick coupling valve.
4. Flush valve.
B. Standard NA
C. Loading Capabilities: 15 KN
D. Material:
1. Body & Cover: Nitrogen Foamed HDPE
2. Bolt and nut: Stainless steel
3. Identification tag: Aluminum
E. Duty: Light
F. Bolt Hex-bolt
L. Dimension:
PART 3 - EXECUTION
A. Inspections:
1. Examine surfaces, substrates and conditions for compliance with requirements
of other sections in which that related work is specified, and determine if
surfaces, substrates not proceed with work of this Section until unsatisfactory
conditions have been corrected in a manner acceptable to the Installer. Starting
installation constitutes acceptance of surfaces substrates and conditions.
2. Verify that irrigation system may be installed in strict accordance with all
pertinent codes and regulations, the original design, the referenced standards,
and the manufacturer's recommendations.
B. Discrepancies:
1. In the event of discrepancy, immediately notify the Engineer or Owner’s
Authorized Representative.
2. Do not proceed with installation in areas of discrepancy until all discrepancies
have been resolved.
C. Grades:
1. Before starting work, carefully check all grades to determine that work may
safely proceed, keeping within the specified material depths with respect to
finish grade 2. Final grades shall be accepted by the Engineer and Owner’s
Authorized Representative before work on this section will be allowed to begin.
D. Field Measurements:
1. Make all necessary measurements in the field to ensure precise fit of items in
accordance with the original design. Contractor shall coordinate the installation
of all Irrigation materials with all other work.
2. All scaled dimensions are approximate. The Contractor shall check and verify
all size dimensions prior to proceeding with work under this section.
3. Exercise extreme care in excavating and working near existing utilities.
Contractor shall be responsible for damages to utilities, which are caused by
his operations or neglect.
E. Diagrammatic Intent:
The Drawings are essentially diagrammatic. The size and location of equipment
and fixtures are drawn to scale where possible. Provide offsets in piping and
changes in equipment locations as necessary to conform to structures and to
avoid obstructions or conflicts with other work at no additional expense to
Owner.
F. Layout:
1. Prior to installation, the Contractor shall stake out all pressure supply lines,
routing and location of sprinkler heads, valves, points of connection, and
automatic controllers.
2. Layout irrigation system and make minor adjustments required due to
differences between Site and Drawings. Where piping is shown on Drawings
under paved areas, but running parallel and adjacent to planted areas, install
the piping in the planted areas.
KEO/19-3262-0000 32 8100/17 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
G. Water Supply:
1. Prior to starting work, the Contractor shall verify the locations, sizes and type
of water connections provided for the irrigation connection. In the event of
discrepancy, immediately notify the Engineer or Owner’s Authorized
Representative.
2. Connections to, or the installation of, the water supply shall be at the locations
shown on the Drawings. Minor changes caused by actual site conditions shall
be made at no additional expense to Owner.
3.02 PIPING
B. Carefully inspect all pipe and fittings before installation, removing dirt, scale, burrs,
and reaming. Install pipe with all markings up for visual inspection and verification.
D. All lines shall have a minimum clearance of 100mm from each other and 300mm from
the lines of other trades.
F. In solvent welding, use only the specified primer and solvent cement and make all
joints with accordance with the manufacturer's recommended methods including
wiping all excess solvent from each weld. Allow solvent welds at least 15 minutes
setup time before moving or handling and 24 hours curing time before filling.
I. For plastic-to-metal connections, work the metal connections first. Use a non-
hardening pipe dope an all threaded plastic-to-metal connections, except where noted
otherwise. All plastic-to-metal connections shall be made with metal female adapters.
3.03 CONTROLLER
A. The exact location of the controller shall be approved by the Engineer or Owner’s
Authorized Representative before installation. The electrical service shall be
coordinated with this location.
C. The contractor shall be responsible for the final electrical hook up to the irrigation
controller.
A. Low voltage control wiring shall occupy the same trench and shall be installed along
the same route as the pressure supply lines whenever possible. When routing with the
mainline is not possible, the control wiring shall be installed at the same depth below
grade as the mainline piping. More than one wire is placed in a trench; the wiring shall
be taped together in a bundle at intervals of 3m. Bundle shall be secured to the
mainline with tape at intervals of 6m.
B. All connections shall be of an approved type and shall occur in a valve box. Provide
a 900mm service loop at each connection.
3.05 VALVES
A. Gate valves, ball valves, check valves, automatic control valves, quick coupler valves,
and air release valves shall be installed as indicated on the Drawings and as per
manufacturer’s recommendations.
B. Valve shall be installed in gravel, sand and shrub areas whenever possible and away
from other existing utility services.
A. Valve boxes shall be installed as indicated on the Drawings and as per manufacturer’s
recommendations.
B. Valve boxes shall be installed in gravel, sand and shrub areas whenever possible and
away from other existing utility services
C. Each valve box shall be installed on a foundation of 20 mm gravel backfill, 0.06 cubic
meters minimum. The gravel shall be installed on top of a single layer of landscape
fabric and the fabric shall be wrapped up and over all outlets on the box sides to
prevent soil and sand from entering the valve box.
D. Valve boxes shall be installed with their tops 15 mm above the surface of surrounding
finish grade in lawn areas and 80mm above finish grade in ground cover areas.
E. Valve boxes shall be aligned and spaced evenly as indicated on the Drawings. All
valve boxes shall be installed with their edges parallel to all adjacent boxes. When
installed adjacent to paving or hardscape, the boxes shall be aligned parallel to the
hardscape and installed with offsets as indicated in the Drawings.
F. Valve boxes shall be secured with the required locking bolts, nuts and washers prior
to final turnover.
C. Sprinkler heads shall be adjusted to completely cover the landscape area, providing
100% head-to-head coverage. Sprinkler heads shall be adjusted to prevent overspray
onto adjacent paving, buildings, walls and trees.
D. Drip tubing shall be staked in place using jute staples to prevent movement of the
tubing during back filling of the plant pits.
E. Spacing of heads and drip tubing shall not exceed maximum recommended by the
manufacturer.
B. Drip system Y filters shall be clean frequently during the maintenance period to remove
rocks, sand and pipe cutting debris from the filter element.
A. Prior to installation of irrigation heads and drip rings, the valves shall be opened and
a full head of water used to flush out the lines and risers.
B. Irrigation heads shall be installed after flushing the system has been completed.
C. Drip systems with flush valves shall be flushed immediately after the installation of the
drip tubing to insure removal of any debris in the pipelines.
A. Contractor shall adjust pressure regulators on the automatic control valves, align all
heads, and check the coverage of each system prior to coverage test.
B. The water pressure at the automatic control valve shall be adjusted to provide the
operating pressure indicated in the drawings at the farthest and highest head on the
valve zone.
E. Automatic control valves are to be adjusted so that the drip tubing operates at the
pressure recommended by the manufacturer.
A. Do not allow or cause any of the work of this section to be covered up or enclosed
until it has been observed, tested and accepted by the Architect, Owner’s Authorized
Representative, and governing agencies.
B. The Contractor shall be solely responsible for notifying the Architect, Owner’s
Authorized Representative, and governing agencies, a minimum of 48 hours in
advance, where and when the work is ready for testing.
C. All constant pressure mainline piping shall be pressure tested. Pipes shall be tested
after center loading and generally with joints exposed. Center loading shall be
sufficient to prevent buckling or deformation due to application of pressure. Pressure
testing pressures and test duration shall be as indicated in these Specifications.
D. All mainline fittings shall be left exposed for the purpose of this test and shall be
inspected for evidence of leakage. Any major breaks in the mainline requiring
shutdown of the test shall cause the test to be re-run entirely.
E. When the irrigation system is completed, the Contractor shall perform a coverage test
of each system in its entirety to determine if the water coverage for the planted areas
is complete and adequate in the presence of the Architect. Coverage testing for
overhead spray irrigated areas shall be performed prior to any planting. Drip system
coverage testing shall be performed after the installation of the irrigation system and
planting.
F. The Contractor shall furnish all materials and perform all work required to correct any
inadequacies of coverage due to deviations from the plans, or where the system has
been willfully installed as indicated on the Drawings when it is obviously inadequate,
without bringing this to the attention of the Architect. The Engineer shall accept this
test and Owner’s Authorized Representative and accomplished before starting any
planting.
G. Each item of electrical equipment, cable and complete system shall be thoroughly
inspected and tested before finally placing in service under the full responsibility of the
Contractor. All tests shall be made in compliance with respective regulations,
recommendations and standards.
H. Any modifications or repairs deemed necessary upon completion of the tests should
be executed at the Contractor's expenses. Further tests shall be carried out on any
modified or repaired equipment until it is certified trouble free and acceptable for its
intended service. All testing shall be demonstrated to the Consultant in a timely
manner, mutually to be agreed.
I. Final inspection, pre-maintenance, will not commence without the hand drawn, field
copy as-built record drawings as prepared by the Contractor. Final inspection, pre-
turnover, will not commence without the AutoCAD based as-built record drawings as
prepared by the Contractor.
KEO/19-3262-0000 32 8100/21 Automatic Irrigation System
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
J. Final inspection, pre-turnover, will not commence without the required Contractor
turnover items indicated in the Specifications.
3.013 MAINTENANCE
A. During the maintenance period, the Contractor shall adjust and maintain the irrigation
system in an operational condition providing complete irrigation coverage to all
intended plantings.
B. During the maintenance period, the contractor shall clean and flush all drip system and
Y filters on a monthly basis.
A. Clean up shall be made as each portion of the work progresses. Refuse and excess
dirt shall be removed from the site, all walks and paving shall be broomed, and any
damage sustained on the work of others shall be repaired to original conditions.
B. Prior to final turnover, the Contractor shall provide a final cleanup of the site to the
satisfaction of the Engineer and the Owner’s Authorized Representative.
END OF SECTION
PLANTING PREPARATION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. Preparing planting areas as indicated on the plans and within the specifications.
A. The Contractor shall arrange for the Engineer to inspect a sample area of minimum 3m2
installed planting medium for approval.
B. The Contractor shall arrange for the Engineer to inspect all levels for approval prior to
installation of irrigation.
1.04 SUBMITTALS
C. Samples:Submit samples of :
1. Agricultural Soil: 1 Kg.
2. Organic Soil Amendments; 0.25 Kg of each specified.
3. Inorganic Soil Amendments; 0.25 Kg of each specified.
4. Water: samples of landscape waters in use shall be submitted, as required for
suitability analysis of irrigation water.
D. Soils reports are to be submitted by the Contractor for all soils to be used for
landscaping purposes in the work. The Contractor shall arrange for an approved
independent analyst to prepare a physical and chemical analysis of the soil and
irrigation water to be used. The analysis shall also provide recommendations on soil
amendments and fertilizer applications. The report shall be submitted to the Engineer for
review and approval before soil is placed. In the case of imported soil, the report shall
be submitted at least 10 days prior to delivery to the site. The report shall identify the
source(s) from which imported soils are to be furnished. At a minimum, the soil shall be
analyzed for:
1. total salts (electro-conductivity of soil solution)
2. soil pH
3. exchangeable sodium, calcium, magnesium and potassium
4. available phosphates
5. organic matter as a percentage
6. available zinc, manganese, iron and boron and other trace elements
7. total sulphates
E. The soil analysis shall provide a recommendation for fertilizers and other amendment
requirements and quantities which when incorporated with the soil will provide the
required nutrient levels for vigorous plant growth.
F. During installation, soil samples shall be taken at the rate of one in every 20 delivered
loads or as directed by the Engineer, and analyzed. The results will be compared with
the original samples to ensure consistency and compatibility of supply.
B. All planter preparation is supplied and installed in accordance with the relevant
specifications in this division 32.
A. Perform work with personnel with minimum five years experience in the work required of
this Section under direction of a skilled foreman.
B. All landscape materials shall be shipped with certificates of inspection as required by the
Engineer. All product manufacturer’s certified analysis for standard packaged products
used in the landscape planting work shall be submitted to the Engineer for review.
PART 2 - PRODUCT
A. Soil shall be obtained from well drained arable land approved by the Engineer before its
use. It shall be free draining, non-toxic and capable of sustaining healthy plant growth.
Soil shall not contain calcium carbonate, subsoil, refuse, roots, noxious weeds,
phytotoxic materials, rocks, sticks, brush, litter, construction debris or any other
deleterious materials. Soil shall be supplied from approved resources from the
Municipality.
B. Agricultural Soil: Obtain the agricultural soil component of the planting soil mix from one
approved source. It shall conform to the following physical and chemical characteristics:
1. Physical Characteristics
a. Material passing a No. 10 sieve 100%
b. Material passing a No. 35 sieve 90 - 100%
c. Material passing a No. 140 sieve 0 - 10%
d. Material passing a No. 270 sieve 0 - 3%
2. Chemical Characteristics
a. Salinity (ECe x 1000) less than 2
b. SAR (Sodium Absorption Ratio) less than 1
c. Boron (saturation extract) less than 0.5 ppm
d. PH less than 8.0
3. Organic Amendment:
a. Physical Characteristics
1) Material passing 9.51mm (3/8") sieve 100%
2) Material passing 6.35mm (1/4") sieve 90 - 100%
3) Material passing 2.38mm (No. 8) sieve 50 - 60%
4) Material passing 0.50mm (No.35) sieve 0 - 20%
5) Bulk Density 300 - 400 kg/m3
b. Chemical Characteristics
1) Organic Matter greater than 85%
2) PH 5.0 - 6.5
3) Salinity (ECe x 1000) 0.5 - 2.0
4) Total Nitrogen 0.7 - 2.0
5) Available Phosphorous 100 - 500 ppm
6) CEC (meq/100 gms) 80 - 120 ppm
7) Boron (by hot water extraction) less than 5 ppm
8) SAR less than 2.0
9) Organic amendment shall be one of the following or approved
equal in manufacturer’s sealed containers and shall be nitrogen
stabilized.
C. SOIL SAMPLES
1. Upon identification of every source of soil, representative samples of soil shall be
analysed for all the above characteristics and results compared with those from
the original sample. These results will then be submitted to the Engineer.
D. STORAGE
1. Soil shall be stored in heaps no greater than one and a half metres high. Soil
heaps shall be protected from undue compaction and no construction or waste
material shall be stored on or mixed with the soil.
H. Soil Sulphur: Finely ground agricultural sulphur of not less than 90% purity.
J. Herbicide: As approved.
K. The planting soil mix for all types of planting shall be:
1. Agricultural Soil 75% by volume
2. Organic Soil Amendment 25% by volume
3. 1 kg/cu metre soil sulphur.
4. 2 kg/cu metre fertilizer.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine substrates, areas and conditions affecting performance of Work under this
Section. Proceed with installation only after unsatisfactory conditions have been
corrected.
3.02 PREPARATION
B. Adjacent work installed under other sections of this specification, shall be kept clean and
free of soil, and other materials incidental to this work.
C. Provide barricades, temporary fencing, signs or policing as may be necessary for the
protection of all planted areas until they are accepted.
A. The Contractor shall make full allowance for the removal of any debris from the planting
areas and remove this to a dump site unless otherwise directed by the Engineer. The
Contractor shall allow for dumping fees and transportation of debris as required.
KEO/19-3262-0000 32 9100/6 Planting Preparation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
B. If the Contractor is unclear as to the status of debris they shall seek clarification from the
Engineer.
A. Pits and Trenches: Excavate circular pits with sides sloped inward. Trim base leaving
center area raised slightly to support root ball and assist in drainage. Do not further
disturb base. Scarify sides of plant pit smeared or smoothed during excavation.
1. Excavate approximately three times as wide as ball diameter for balled and
burlapped stock.
2. Excavate at least 300 mm wider than root spread and deep enough to
accommodate vertical roots for bare-root stock.
A. The Contractor shall examine areas to receive landscaping for compliance with
requirements and conditions affecting performance of work in this Section. The
Contractor shall not proceed with plant operations until unsatisfactory conditions are
discussed with the Engineer and corrected.
B. The Contractor shall determine the location of above grade and underground utilities
and perform work in a manner which will avoid damage to them. Damage to
underground utilities shall be repaired at the Contractor’s expense.
C. When conditions detrimental to plant growth are encountered, such as rubble, adverse
drainage or obstructions, the Contractor shall notify the Engineer prior to planting.
D. The Contractor shall verify that sub-grades are as indicated in the project
documentation.
E. Grade stakes shall be maintained until removal of them is mutually agreed upon by all
parties concerned.
F. When grades are encountered that are detrimental to finished grading and planting
operations, the Contractor shall notify the Engineer prior to planting.
A. All perennial weeds shall be treated with an approved herbicide and the period of time
recommended by the manufacturer shall be allowed to elapse prior to commencing
grading operations.
B. Grading operations shall occur when the sub-soil is reasonably dry and workable.
C. Areas to be graded shall be graded to smooth flowing contours with all minor hollows
and ridges removed. Rock projections and boulders shall be removed and disposed of
at a location as agreed with the Engineer.
D. Non-cohesive, light subsoil shall be loosened with a 3-tine ripper to a depth of 300 mm
at 600 mm centres. Stiff clay and other cohesive subsoil shall be loosened with a single
tine ripper to a depth of 450 mm at 1 m centres.
A. Grades shall be brought to the finished ground levels as indicated on the Project
Drawings or as agreed with the Engineer to a tolerance of ± 12 mm. Grading shall be
carried out in such a manner that even gradients are formed between the spot levels
indicated on the Project Drawings. No depressions shall remain which could collect
standing water.
A. The Contractor is responsible for the supply and installation of planting medium to the
planting areas as per the plans and details provided. The Contractor is responsible for
installing planting medium to all planter areas to meet the required levels and depths.
B. Planting medium shall be installed to achieve tolerances specified for finished level of
soil, and when reasonably dry and workable, graded to smooth, flowing contours with all
minor hollows and ridges removed. Finished ground level adjoining buildings shall be
kept 150mm below the level of the damp-proof course.
C. The Contractor shall ensure that planting medium levels allow for any expected
settlement following installation. Levels shown are finished following settlement. Planting
medium shall be graded back from edges. Planting medium shall be installed to allow
installation of mulch layer. No spill over edges shall be permitted.
D. The planting soil shall be placed in planting areas and compacted using water saturation
to the full mix depth. The area shall be levelled to within plus or minus 50mm and then
again be thoroughly irrigated with water to eliminate air pockets and settle soil. The soil
shall be evenly moistened to a depth of 300mm. After the irrigation system has been
installed, recompact and settle all disturbed areas and fine grade to a smooth
continuous grade. There shall be no uneven surfaces greater than plus or minus 15mm.
E. After a period of ten days, all germinating weeds shall be removed from the area and
the soil shall be relevelled to form a smooth continuous grade.
END OF SECTION
SOIL PREPARATION
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Section includes planting soils and layered soil assemblies specified by composition of
the mixes.
B. Related Requirements:
1. Section 31 1000 "Site Clearing" for topsoil stripping and stockpiling.
2. Section 32 9200 "Turf and Grasses" for placing planting soil for turf and grasses.
3. Section 32 9300 "Plants" for placing planting soil for plantings.
1.02 DEFINITIONS
B. Backfill: The earth used to replace or the act of replacing earth in an excavation. This
can be amended or un-amended soil as indicated.
D. Compost: The product resulting from the controlled biological decomposition of organic
material that has been sanitized through the generation of heat and stabilized to the
point that it is beneficial to plant growth.
F. Layered Soil Assembly: A designed series of planting soils, layered on each other, that
together produce an environment for plant growth.
G. Manufactured Soil: Soil produced by blending soils, sand, stabilized organic soil
amendments, and other materials to produce planting soil.
H. NAPT: North American Proficiency Testing Program. An SSSA program to assist soil-,
plant- and water-testing laboratories through inter-laboratory sample exchanges and
statistical evaluation of analytical data.
I. Organic Matter: The total of organic materials in soil exclusive of un-decayed plant and
animal tissues, their partial decomposition products, and the soil biomass; also called
"humus" or "soil organic matter."
J. Planting Soil: Existing, on-site soil; imported soil; or manufactured soil that has been
modified as specified with soil amendments and perhaps fertilizers to produce a soil
mixture best for plant growth.
N. Subsoil: Soil beneath the level of subgrade; soil beneath the topsoil layers of a naturally
occurring soil profile, typified by less than 1 percent organic matter and few soil
organisms.
O. Surface Soil: Soil that is present at the top layer of the existing soil profile. In
undisturbed areas, surface soil is typically called "topsoil"; but in disturbed areas such
as urban environments, the surface soil can be subsoil.
B. Samples: For each bulk-supplied material, 4Ltr volume of each in sealed containers
labeled with content, source, and date obtained. Each Sample shall be typical of the lot
of material to be furnished; provide an accurate representation of composition, color,
and texture.
B. Sample Collection and Labeling: Have samples taken and labeled by Contractor in
presence of Architect under the direction of the testing agency.
1. Number and Location of Samples:
a. Minimum of 1 per 5 HA representative soil samples from varied agreed
locations directed by Architect for existing soils.
b. Minimum of 1 sample per 1000m3 delivered load of sweet soil sand
delivered to site for mixing.
2. Procedures and Depth of Samples: According to USDA-NRCS's "Field Book for
Describing and Sampling Soils."
3. Division of Samples: Split each sample into two, equal parts. Send half to the
testing agency and half to Owner for its records.
4. Labeling: Label each sample with the date, location keyed to a site plan or other
location system, visible soil condition, and sampling depth.
B. Physical Testing:
1. Soil Texture: Soil-particle, size-distribution analysis by one of the following
methods according to SSSA's "Methods of Soil Analysis - Part 1-Physical and
Mineralogical Methods":
KEO/19-3262-0000 32 9113/3 Soil Preparation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
a. Sieving Method: Report sand-gradation percentages for very coarse,
coarse, medium, fine, and very fine sand; and fragment-gradation (gravel)
percentages for fine, medium, and coarse fragments; according to USDA
sand and fragment sizes.
b. Hydrometer Method: Report percentages of sand, silt, and clay.
2. Total Porosity: Calculate using particle density and bulk density according to
SSSA's "Methods of Soil Analysis - Part 1-Physical and Mineralogical Methods."
3. Water Retention: According to SSSA's "Methods of Soil Analysis - Part 1-
Physical and Mineralogical Methods."
4. Saturated Hydraulic Conductivity: According to SSSA's "Methods of Soil
Analysis - Part 1-Physical and Mineralogical Methods"; at 85% compaction
according to ASTM D 698 (Standard Proctor).
C. Chemical Testing:
1. CEC: Analysis by sodium saturation at pH 7 according to SSSA's "Methods of
Soil Analysis - Part 3- Chemical Methods."
2. Clay Mineralogy: Analysis and estimated percentage of expandable clay
minerals using CEC by ammonium saturation at pH 7 according to SSSA's
"Methods of Soil Analysis - Part 1- Physical and Mineralogical Methods."
3. Metals Hazardous to Human Health: Test for presence and quantities of RCRA
metals including aluminum, arsenic, barium, copper, cadmium, chromium, cobalt,
lead, lithium, and vanadium. If RCRA metals are present, include
recommendations for corrective action.
4. Phytotoxicity: Test for plant-available concentrations of phytotoxic minerals
including aluminum, arsenic, barium, cadmium, chlorides, chromium, cobalt,
copper, lead, lithium, mercury, nickel, selenium, silver, sodium, strontium, tin,
titanium, vanadium, and zinc.
F. Recommendations for sweet sand soils: Based on the test results, state
recommendations for soil treatments and soil amendments to be incorporated to
KEO/19-3262-0000 32 9113/4 Soil Preparation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
produce satisfactory planting soil suitable for healthy, viable plants indicated. Include, at
a minimum, recommendations for nitrogen, phosphorous, and potassium fertilization,
and for micronutrients.
G. Recommendations for existing site soils: Based on the test results, state
recommendations for soil treatments to remove / sterilise and or cap contaminates.
B. Bulk Materials:
1. Do not dump or store bulk materials near structures, utilities, walkways and
pavements, or on existing turf areas or plants.
2. Provide erosion-control measures to prevent erosion or displacement of bulk
materials, discharge of soil-bearing water runoff, and airborne dust reaching
adjacent properties, water conveyance systems, or walkways.
3. Do not move or handle materials when they are wet.
4. Accompany each delivery of bulk fertilizers and soil amendments with
appropriate certificates.
PART 2 - PRODUCTS
A. General: Soil amendments, fertilizers, and rates of application specified in this article
are guidelines that may need revision based on testing laboratory's recommendations
after preconstruction soil analyses are performed.
D. Sand: Clean, washed, natural or manufactured, free of toxic materials, and according to
ASTM C 33/C 33M. Sand shall be sweet sand or marine washed sand free of calcium
carbonate, subsoil, refuse, roots, noxious weeds, phytotoxic materials, rocks, sticks,
brush, litter, construction debris or any other deleterious materials. The soil shall be
approved by the Engineer before its use. It shall be free draining, non-toxic and capable
of sustaining healthy plant growth. It should have good water holding capacity and
minimal runoff or erosion characteristics.
1. The sand will have the following composition:
Element Value
pH value: not less than 6.5 or not more than 8
Electrical conductivity: less than 2500 micromhos /cm
(2.5 dS / m) saturated extract at 25ºC
Free carbonates: less than 0.5% air dried
Chlorides: less than 200 ppm in saturated extract
Sulphates: less than 200 ppm in saturated extract
Exchangeable sodium: less than 15% in neutral
normal ammonium acetate
Boron: less than 1.5 ppm, hot water soluble
Sodium less than 250 ppm
Magnesium less than 100 ppm
Nitrates less than 75 ppm
2. Grading of material:
B. Shredded Coconut Fiber: Coconut fiber shall be finely shredded coconut fibre pith free
from chemical additives, sterilents and shall have more than 98% organic matter.
1. Physical Characteristics:
2. Chemical Characteristics:
Element Value
Organic matter >85%
PH 5.0 - 6.5
Salinity (ECe x 1000) 0.5 - 2.0
Total Nitrogen 0.7 - 2.0
Available Phosphorous 100 - 500 ppm
CEC (meq/100 gms) 80 - 120 ppm
Boron (by hot water extraction) <5 ppm
SAR less than 2.0 <2.0
C. Soil Inoculant - Myccoriza: For individual planting pits consiting of select edendo and
ectomycorrhizae fungi to promote the rapid development of root growth
1. Application: To be applied to each Palm, tree and shrub pit in accordance with
manufacturers recommendations.
2. Manufacture: To be confirm and approved by Landscape Architect and Client.
2.04 FERTILIZERS
D. Organic Fertiliser: 100% Natural and heat treated. The content of Organic matter and
plant nutrient elements of this fertiliser should not be less than 50%. Primary and
secondary elements as percentages and trace elementsas ppm should be indicated on
the packing.
2.05 ANTI-DESICCANT
A. Emulsion form for spray application to provide a protective film over plant surface and
permeable enough to permit transpiration. Application should be made prior to
transportation of palm, tree and plant material to project site.
1. Product: To be delivered in containers of the manufacturer, mixed according to
the manufacturer's directions. Manufacturer to be confirm and approved by
Landscape Architect and Client.
PART 3 - EXECUTION
3.01 GENERAL
B. Verify that no foreign or deleterious material or liquid such as paint, paint washout,
concrete slurry, concrete layers or chunks, cement, plaster, oils, gasoline, diesel fuel,
paint thinner, turpentine, tar, roofing compound, or acid has been deposited in planting
soil.
C. Proceed with placement only after unsatisfactory conditions have been corrected.
A. General: Apply manufactured soil on-site in its final, blended condition. Do not apply
materials or till if existing soil or subgrade is muddy or excessively wet.
B. Subgrade Preparation: Till subgrade to a minimum depth of 450 mm. Remove stones
larger than 75 mm in any dimension and sticks, roots, rubbish, and other extraneous
matter and legally dispose of them off Owner's property.
1. Apply approximately half the thickness of planting soil over prepared, loosened
subgrade. Mix thoroughly into top 50 mm of subgrade (unless soil testing for
existing site soil recommends for existing soils to be capped). Spread remainder
of planting soil.
KEO/19-3262-0000 32 9113/8 Soil Preparation
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. Application: Spread planting soil to total depth as indicated on the planting detail
drawings, but not less than required to meet finish grades after natural settlement. Do
not spread if soil or subgrade is frozen, muddy, or excessively wet.
1. Lifts: Apply planting soil in lifts not exceeding 300 mm in loose depth for material
compacted by compaction equipment, and not more than 150 mm in loose depth
for material compacted by hand-operated tampers.
E. Finish Grading: Bring soil to grades as indicated on drawings and to the final approval of
the Architect, using specificied soil mix.
1. Finish grading shall insure proper drainage of the site as determined by the
Architect.
2. Grade planting soil to a smooth, uniform surface plane with loose, uniformly fine
texture. Roll and rake, remove ridges, and fill depressions to meet finish grades
3. All areas shall be graded so that the final grades will be 25mm below adjacent
paved areas, sidewalks, valve boxes, headers, tree well grates, planter rims,
clean-outs, drains, manholes, etc., or as indicated on plans for turf, and 40mm for
shrubs and groundcovers.
4. Surface drainage shall be away from all building foundations.
5. Eliminate all erosion scars prior to commencing maintenance period.
6. Compact all soil to final grades: Minimum 65%, maximum 75%, .
A. Finish Grading: Grade surface to a smooth, uniform surface plane with loose, uniformly
fine texture. Roll and rake, remove ridges, and fill depressions to meet finish grades.
A. Soil will be considered defective if it does not pass tests and inspections.
C. Label each sample and test report with the date, location keyed to a site plan or other
location system, visible conditions when and where sample was taken, and sampling
depth.
3.05 PROTECTION
3.06 CLEANING
B. Remove surplus soil and waste material including excess subsoil, unsuitable materials,
trash, and debris and legally dispose of them off Owner's property unless otherwise
indicated.
1. Dispose of excess subsoil and unsuitable materials on-site where directed by
Owner.
END OF SECTION
PLANTS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Section Includes:
1. Plants.
2. Tree stabilization.
3. Landscape edgings.
B. Related Requirements:
1. Section 01 5639 "Temporary Tree and Plant Protection" for protecting, trimming,
pruning, repairing, and replacing existing trees to remain that interfere with, or
are affected by, execution of the Work.
2. Section 32 9200 "Turf and Grasses" for turf (lawn) and erosion-control materials.
3. Section 32 9113 - "Soil Preparation" for soil mixes
1.02 DEFINITIONS
A. Backfill: The earth used to replace or the act of replacing earth in an excavation.
B. Balled and Burlapped Stock: Plants dug with firm, natural balls of earth in which they
were grown, with a ball size not less than diameter and depth recommended by ANSI
Z60.1 for type and size of plant required; wrapped with burlap, tied, rigidly supported,
and drum laced with twine with the root flare visible at the surface of the ball as
recommended by ANSI Z60.1.
C. Balled and Potted Stock: Plants dug with firm, natural balls of earth in which they are
grown and placed, unbroken, in a container. Ball size is not less than diameter and
depth recommended by ANSI Z60.1 for type and size of plant required.
E. Fabric Bag-Grown Stock: Healthy, vigorous, well-rooted plants established and grown
in-ground in a porous fabric bag with well-established root system reaching sides of
fabric bag. Fabric bag size is not less than diameter, depth, and volume required by
ANSI Z60.1 for type and size of plant.
H. Pests: Living organisms that occur where they are not desired or that cause damage to
plants, animals, or people. Pests include insects, mites, grubs, mollusks (snails and
slugs), rodents, unwanted plants (weeds), fungi, bacteria, and viruses.
J. Planting Soil: Existing, on-site soil; imported soil; or manufactured soil that has been
modified with soil amendments and perhaps fertilizers to produce a soil mixture best for
plant growth. See Section 32 9113 "Soil Preparation" for planting soils.
K. Plant; Plants; Plant Material: These terms refer to vegetation in general, including trees,
shrubs, vines, ground covers, ornamental grasses, bulbs, corms, tubers, or herbaceous
vegetation.
L. Root Flare: Also called "trunk flare." The area at the base of the plant's stem or trunk
where the stem or trunk broadens to form roots; the area of transition between the root
system and the stem or trunk.
M. Stem Girdling Roots: Roots that encircle the stems (trunks) of trees below the soil
surface.
1.03 COORDINATION
A. Coordinate final positions with all underground utility lines, chambers, openings,
structural footings and the like. All trees and palms to be staked during installation of
services to ensure clashes are avoided.
B. Coordination with Turf Areas (Lawns): Plant trees, shrubs, and other plants after finish
grades are established and before planting turf areas unless otherwise indicated.
1. When planting trees, shrubs, and other plants after planting turf areas, protect
turf areas, and promptly repair damage caused by planting operations.
A. Qualification Data: For landscape Installer. Include list of similar projects completed by
Installer demonstrating Installer's capabilities and experience. Include project names,
addresses, and year completed, and include names and addresses of owners' contact
persons.
B. Product Certificates: For each type of manufactured product, from manufacturer, and
complying with the following:
1. Manufacturer's certified analysis of standard products.
2. Analysis of other materials by a recognized laboratory made according to
methods established by the Association of Official Analytical Chemists, where
applicable.
D. Non packaged bulk materials delivered to site: Submit a certificate, of delivery slip with
each delivery of material in bulk. Certificates shall state source, quantity, or weight, type
and analysis and date of delivery along with an analysis completed by an approved
independent testing laboratory - if requested by the Architect.
E. Plant Material: All Plant material to be delivered to site with a nursery growers
certificate.
B. Provide quality, size, genus, species, and variety of plants indicated, complying with
applicable requirements in ANSI Z60.1.
1. Specimen plant materials may be observed at source prior to delivery to site if
determined appropriate by Architect.
2. Upon delivery of plant material to site:
a. All plant material shall be subject to observation and may be approved or
rejected the Architect or Owner’s Authorized Representative for quality,
size and variety prior to installation. Such approval shall not impair the
right of observation and rejection during the progress of work for size and
condition of ball or root mass, latent effects, diseases, pests or injuries.
b. If any defective or non-complying plants are found during observations,
they will be rejected.
c. All rejected plant material shall be removed from the site within a
minimum of 2 working days.
3. Workmanship: Observation of site at critical stages of work.
a. If applicable, observation of drainage material on-structure prior to
installation of soil separator if required.
b. If applicable observation of soil separator on-structure prior to installation
of soil.
c. Observation for approval of landscape finish grading and soil preparation
before
d. installation of plant material:
e. During this observation the Architect may request that samples of the
planting soil be analyzed by an approved laboratory to assure its
compliance with these Specifications.
f. Notification of exception shall be for the Contractor to correct deficiencies
in the soil preparation to render it in compliance with these specifications.
Corrections shall be made prior to any planting, or, at the Architect's
option, the installation of container sized plants may proceed if the
corrections can be made later without affecting the quality of the work.
The Contractor shall notify the Architect in writing when the deficiencies
have been corrected.
g. Observation of planting installation.
h. Observation of tree staking/tree guying.
4. Material and Workmanship:
a. Observation by the Architect will be made at substantial
completion/delivery of all materials, construction and installation work
required by the Contract prior to commencement of the plant
establishment period. The plant establishment period shall not commence
until all deficiencies found by this observation have been corrected and
written notice of start of commencement has been received from the
Architect. All materials shall be installed prior to this observation with the
following exceptions:
1) Items waived by the Architect for this observation for reasons of
substantiated unavailability, or in appropriate season or weather.
2) Items which do not affect the health or growth of the plantings.
b. Periodic observation shall be made of the work of the Contract during
plant establishment period wherein the approval of monthly progress
payments will be contingent upon approved monthly quality reports by the
Owner’s Representative.
KEO/19-3262-0000 32 9300/5 Plants
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. Measurements: Measure according to ANSI Z60.1. Do not prune to obtain required
sizes.
1. Trees and Shrubs: Measure with branches and trunks or canes in their normal
position. Take height measurements from or near the top of the root flare for
field-grown stock and container-grown stock. Measure main body of tree or
shrub for height and spread; do not measure branches or roots tip to tip. Take
caliper measurements (150 mm) above the root flare for trees up to (100-mm)
caliper size, and (300 mm) above the root flare for larger sizes.
2. Other Plants: Measure with stems, petioles, and foliage in their normal position.
D. Plant Material Observation: Architect may observe plant material either at place of
growth or at site before planting for compliance with requirements for genus, species,
variety, cultivar, size, and quality. Architect may also observe trees and shrubs further
for size and condition of balls and root systems, pests, disease symptoms, injuries, and
latent defects and may reject unsatisfactory or defective material at any time during
progress of work. Remove rejected trees or shrubs immediately from Project site.
1. Notify Architect of sources of planting materials seven days in advance of
delivery to site.
B. Bulk Materials:
1. Do not dump or store bulk materials near structures, utilities, walkways and
pavements, or on existing turf areas or plants.
2. Provide erosion-control measures to prevent erosion or displacement of bulk
materials; discharge of soil-bearing water runoff; and airborne dust reaching
adjacent properties, water conveyance systems, or walkways.
3. Accompany each delivery of bulk materials with appropriate certificates.
4. The Contractor shall notify the Architect 7 calendar days in advance of delivery of
all plant materials and shall submit an itemized list of the plants in each delivery.
C. Deliver bare-root stock plants within 24 hours of digging. Immediately after digging up
bare-root stock, pack root system in wet straw, hay, or other suitable material to keep
root system moist until planting. Transport in covered, temperature-controlled vehicles,
and keep plants cool and protected from sun and wind at all times.
D. Do not prune trees and shrubs before delivery. Protect bark, branches, and root
systems from sun scald, drying, wind burn, sweating, whipping, and other handling and
tying damage. Do not bend or bind-tie trees or shrubs in such a manner as to destroy
their natural shape. Provide protective covering of plants during shipping and delivery.
Do not drop plants during delivery and handling.
F. Store bulbs, corms, and tubers in a dry place at 60 to 65 deg F (until planting.
G. Apply antidesiccant to trees and shrubs using power spray to provide an adequate film
over trunks (before wrapping), branches, stems, twigs, and foliage to protect during
digging, handling, and transportation.
H. Wrap trees and shrubs with burlap fabric over trunks, branches, stems, twigs, and
foliage to protect from wind and other damage during digging, handling, and
transportation.
I. Deliver all plant blocks with legible identification labels, state correct plant name and
size indicated on plant list using durable waterproof labels with water-resistant ink which
will remain legible for at least 60 days.
J. All plants to be delivered to temporary shaded nursery for hardening off and storage
until planting zones are ready for implementation.
K. Move plants from temporary nursery to final planting area after preparations for planting
have been completed, and install immediately. If planting is delayed more than six
hours after moving, set plants and trees in their appropriate aspect (sun, filtered sun, or
shade), protect from weather and mechanical damage, and keep roots moist.
1. Set balled stock on ground and cover ball with soil, peat moss, sawdust, or other
acceptable material.
2. Do not remove container-grown stock from containers before time of planting.
3. Water root systems of plants stored on-site deeply and thoroughly with a fine-
mist spray. Water as often as necessary to maintain root systems in a moist, but
not overly wet condition.
A. Field Measurements: Verify actual grade elevations, service and utility locations,
irrigation system components, and dimensions of plantings and construction contiguous
with new plantings by field measurements before proceeding with planting work.
B. Planting Restrictions: Plant during one of the following periods. Coordinate planting
periods with maintenance periods to provide required maintenance from date of
Substantial Completion.
1. Planting Season: October - April
C. Weather Limitations: Proceed with planting only when existing and forecasted weather
conditions permit planting to be performed when beneficial and optimum results may be
obtained. Apply products during favorable weather conditions according to
manufacturer's written instructions and warranty requirements.
1.011 WARRANTY
A. Special Warranty: Installer agrees to repair or replace plantings and accessories that
fail in materials, workmanship, or growth within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Death and unsatisfactory growth, except for defects resulting from abuse,
lack of adequate maintenance, or neglect by Owner.
b. Structural failures including plantings falling or blowing over.
c. Faulty performance of tree stabilization, edgings and tree grates.
d. Deterioration of metals, metal finishes, and other materials beyond normal
weathering.
2. Warranty Periods: From date of planting completion.
KEO/19-3262-0000 32 9300/7 Plants
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
a. Trees, Shrubs, Vines, and Ornamental Grasses: 12 months.
b. Ground Covers, Biennials, Perennials, and Other Plants: 12months.
c. Annuals: Three months.
3. Include the following remedial actions as a minimum:
a. Immediately remove dead plants and replace unless required to plant in
the succeeding planting season.
b. Replace plants that are more than 25 percent dead or in an unhealthy
condition at end of warranty period.
c. A limit of one replacement of each plant is required except for losses or
replacements due to failure to comply with requirements.
d. Provide extended warranty for period equal to original warranty period, for
replaced plant material.
e. Remove and replace defected material within 15days.
PART 2 - PRODUCTS
2.01 GENERAL
A. General: Furnish nursery-grown plants true to genus, species, variety, cultivar, stem
form, shearing, and other features indicated in Plant List, Plant Schedule, or Plant
Legend indicated on Drawings and complying with ANSI Z60.1; and with healthy root
systems developed by transplanting or root pruning. Provide well-shaped, fully
branched, healthy, vigorous stock, densely foliated when in leaf and free of disease,
pests, eggs, larvae, and defects such as knots, sun scald, injuries, abrasions, and
disfigurement.
1. Trees with damaged, crooked, or multiple leaders; tight vertical branches where
bark is squeezed between two branches or between branch and trunk ("included
bark"); crossing trunks; cut-off limbs more than (20 mm) in diameter; or with stem
girdling roots are unacceptable.
2. Collected Stock: Do not use plants harvested from the wild, from native stands,
from an established landscape planting, or not grown in a nursery unless
otherwise indicated.
B. Provide plants of sizes, grades, and ball or container sizes complying with ANSI Z60.1
for types and form of plants required. Plants of a larger size may be used if acceptable
to Architect, with a proportionate increase in size of roots or balls. The size of the plants
shall correspond with that normally expected for species as specified on drawings. The
minimum acceptable size of all plants measured before pruning with the branches in
normal position, shall comply with the measurements, if any, specified on the drawings
in the list of plants to be furnished. Plants larger in size than specified may be used with
the approval of the Architect, but the use of larger plants shall not change the contract
price.
C. All plants not in compliance with the requirements herein specified, will be considered
defective and such plants, whether in place or not, shall be marked as rejected and
immediately removed from the site of the work and replaced with new plants at the
Contractor's expense. The plants shall be of the species, variety, size, and conditions
KEO/19-3262-0000 32 9300/8 Plants
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
specified herein or as shown on the drawings. Under no conditions shall there be any
substitutions of plants or sizes listed on the accompanying plans, except with the
express consent of the Architect.
D. Labeling: Label at least one plant of each variety, size, and caliper with a securely
attached, waterproof tag bearing legible designation of common name and full scientific
name, including genus and species. Include nomenclature for hybrid, variety, or
cultivar, if applicable for the plant.
2.03 FERTILIZERS
2.04 MULCHES
A. Organic Mulch: Free from deleterious materials and suitable as a top dressing of trees
and shrubs, consisting of one of the following:
1. Type: Wood and bark chips or shedded palm - material to be approved by
Architect.
2. Size Range - Percent Passing Sieve Size:
a. 90-100% 25.4 mm
b. 80-100% 12.7 mm
c. 20-60% 6.35 mm
3. Color: Natural.
B. Mineral Mulch: Hard, durable stone, washed free of loam, sand, clay, and other foreign
substances, of the following type, size range, and color in areas specifically indicated on
drawings:
1. Type: Crushed stone or gravel Granite chips.
2. Size Range: As per material schedule.
3. Color: Uniform color range as per material schedule for Architects approval.
2.05 PESTICIDES
A. General: Pesticide registered and approved by the EPA and Qatar State, acceptable to
authorities having jurisdiction, and of type recommended by manufacturer for each
specific problem and as required for Project conditions and application. Do not use
restricted pesticides unless authorized in writing by authorities having jurisdiction.
A. Trunk-Stabilization Materials: Pipe Tree Stakes: Schedule 40 steel pipe, 50mm diameter
by 3000mm long with threaded cap primed and painted before installation with 2 coats
flat black exterior enamel. Touch up in field to match shop condition.
1. Cinch-Tie – Black virgin flexible vinyl meeting ASTm-D-412; with double
backlocking configuration; galvanized roofing nail, 2 1000mm length corded
rubber ties with bolts, nuts and 2 washers on each end.
2. Flags: Standard surveyor's plastic flagging tape, white, (150 mm) long.
3. Wood Deadmen: Pressure treated softwood timbers 750x100x50mm horizontals
secured to 2no. 100mm2 x 600mm stakes with 10x100mm galvanised lag
screws.
4. Guy Cables - Where used: Five strand - 4.8mm dia galvanised steel cable with
zinc-coated turnbuckles to a minimum of 75mm long with 2no. galvanised eye
bolts. Cables protected with reinforced green rubber garden hose. Cables
spaced at 120degree spacing around the tree.
1. Properties:
Property/Test method Units Value
Mechanical Properties
Grab Tensille Strength ASTM D 4632
Strength @ Ultimate kN (lbs) 0.71 (160)
Elongation @ Ultimate % 50
Mullen Burst Strength kPa 2239
ASTM D 3786 (psi) (325)
Trapezoidal Tear Strength kN 0.27
ASTM D 4533 (lbs) (60)
Puncture Strength kN 0.42
ASTM D 4833 (lbs) (95)
UV Resistance after 500 hrs.
ASTM D 4355 5 strength 70
Hydraulic Properties
Apparent Opening Size US Sieve 70
(AOS) ADTM D 4751 mm 0.212
Permittivity
ASTM D 4491 soc 1.5
Flow Rate l/min/m' 4889
ASTM D 4491 (gal/min/ft') (120)
Packaging
Roll Width metres 4.6
Roll Length metres 4.6
G. Mycorrhizal Fungi: Dry, granular inoculant containing at least 5300 spores per lb 0.45
kg of vesicular-arbuscular mycorrhizal fungi and 95 million spores per lb 0.45 kg of
ectomycorrhizal fungi, 33 percent hydrogel, and a maximum of 5.5 percent inert
material.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine areas to receive plants, with Installer present, for compliance with
requirements and conditions affecting installation and performance of the Work.
1. Verify that no foreign or deleterious material or liquid such as paint, paint
washout, concrete slurry, concrete layers or chunks, cement, plaster, oils,
gasoline, diesel fuel, paint thinner, turpentine, tar, roofing compound, or acid has
been deposited in soil within a planting area.
C. Proceed with installation only after unsatisfactory conditions, deficiencies have been
corrected or plants replaced.
3.02 PREPARATION
A. Protect structures, utilities, sidewalks, pavements, and other facilities and turf areas and
existing plants from damage caused by planting operations.
C. Lay out individual tree and shrub locations and areas for multiple plantings. Stake
locations, outline areas, adjust locations when requested, and obtain Architect's
acceptance of layout before excavating or planting. Make minor adjustments as
required.
D. Lay out plants at locations directed by Architect. Stake locations of individual trees and
shrubs and outline areas for multiple plantings.
A. General: Prepare planting area for soil placement and mix planting soil according to
Section 32 9113 "Soil Preparation".
B. Placing Planting Soil: Place premixed soil mix planting soil over exposed subgrade. No
insitu soil mixing allowed unless directed by Architect.
C. Before planting, obtain Architect's acceptance of finish grading; restore planting areas if
eroded or otherwise disturbed after finish grading.
B. Backfill Soil: Subsoil and topsoil removed from excavations may be used as backfill soil
unless otherwise indicated.
E. Fill excavations with water and allow to percolate away before positioning trees and
shrubs.
A. Prior to Planting the Contractor must carry out the following inspections:
1. Verify that root flare is visible at top of root ball according to ANSI Z60.1. If root
flare is not visible, remove soil in a level manner from the root ball to where the
top-most root emerges from the trunk. After soil removal to expose the root flare,
verify that root ball still meets size requirements.
2. Roots: Remove stem girdling roots and kinked roots. Remove injured roots by
cutting cleanly; do not break.
3. Identify genus/species of all supplied palms including particular cultivar/variety.
4. Identify all supplied palms as male or female, fruiting/non-fruiting.
B. Planting Procedure:
1. Maximum duration of handling shall be 48 hours.
2. All root ball sizes shall be in proportion to height of tree, minimum root ball size
shall be 1 meter by 1.2 meter deep.
3. All trunk diameters shall be in proportion to tree height and all trunks shall be
straight with diamond cut pattern on trunks.
4. Anticipated caliper size variation ranges from 45cm to 60cm in diameter. Only
straight vertical trunks will be accepted.
5. All palm tree pits shall be excavated to 2 meters square by 2 meters deep.
6. Place designated soil mix at the bottom of the plant pit to range of depth from
300mm to 600mm depth.
7. At each hole, place 2 liters Myccoriza over designated soil mix layer.
8. Locate and stabilize each palm into the plant pit. Backfill perimeter of plant pit
with sweet sand to 500mm below the ultimate finish graded soil levels. Check
that palms are vertical/plumb and stabilized vertically.
9. Water in soil to remove air pockets and stabilize vertically for each palm.
10. Place additional 5 liters Myccoriza into the hole.
11. Backfill remaining sweet sand to finish grade and construct a water basin.
12. Check that finish soil levels at each palm are anticipated at range to Golf
construction finish grade, plus or minus150mm to 200mm.
13. All palms shall be guaranteed for a period of 720 days from the agreed upon
date of final acceptance. Mutually agreed periodic maintenance reviews and a
regular protocol for specific site visits will be reviewed with other team members
in order to establish acceptance protocols for water application and for
replacements of dead/ declining palm.
14. After palms have been installed for a period of 10 days, all palms shall be
checked and adjusted to straighten and to insure any trees that have shifted from
vertical axis.
15. Any appurtenant apparatus, such as slings, straps, eye buckles and paint on
trunks shall be completely removed in a manner that does not injure palm bark or
structure. No frond ties shall be removed until the supplier/contractor has
provided said instruction. All final trunk cleaning shall be done at the time frond
ties are removed.
A. Inspection: At time of planting, verify that root flare is visible at top of root ball according
to ANSI Z60.1. If root flare is not visible, remove soil in a level manner from the root ball
to where the top-most root emerges from the trunk. After soil removal to expose the
root flare, verify that root ball still meets size requirements.
B. Roots: Remove stem girdling roots and kinked roots. Remove injured roots by cutting
cleanly; do not break.
C. Balled and Burlapped Stock: Set each plant plumb and in center of planting pit or trench
with root flare (25mm) above adjacent finish grades.
1. Backfill: Mix. Designated planting soil mix - Section 32 9113 "Soil Preparation"
2. After placing some backfill around root ball to stabilize plant, carefully cut and
remove burlap, rope, and wire baskets from tops of root balls and from sides, but
do not remove from under root balls. Remove pallets, if any, before setting. Do
KEO/19-3262-0000 32 9300/14 Plants
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
not use planting stock if root ball is cracked or broken before or during planting
operation.
3. Backfill around root ball in layers, tamping to settle soil and eliminate voids and
air pockets. When planting pit is approximately one-half filled, water thoroughly
before placing remainder of backfill. Repeat watering until no more water is
absorbed.
4. Place planting tablets equally distributed around each planting pit when pit is
approximately one-half filled. Place tablets beside the root ball about (25mm)
from root tips; do not place tablets in bottom of the hole.
a. Quantity: As indicated on Drawings
5. Continue backfilling process. Water again after placing and tamping final layer of
soil.
D. Balled and Potted and Container-Grown Stock: Set each plant plumb and in center of
planting pit or trench with root flare (25mm) above adjacent finish grades.
1. Backfill: Designated planting soil mix - Section 32 9113 "Soil Preparation"
2. Carefully remove root ball from container without damaging root ball or plant.
3. Backfill around root ball in layers, tamping to settle soil and eliminate voids and
air pockets. When planting pit is approximately one-half filled, water thoroughly
before placing remainder of backfill. Repeat watering until no more water is
absorbed.
4. Place planting tablets equally distributed around each planting pit when pit is
approximately one-half filled. Place tablets beside the root ball about (25 mm)
from root tips; do not place tablets in bottom of the hole.
a. Quantity: As per manufacturers recommendations.
5. Continue backfilling process. Water again after placing and tamping final layer of
soil.
E. Fabric Bag-Grown Stock: Set each plant plumb and in center of planting pit or trench
with root flare (25mm) above adjacent finish grades.
1. Backfill: Designated planting soil mix - Section 32 9113 "Soil Preparation"
2. Carefully remove root ball from fabric bag without damaging root ball or plant.
Do not use planting stock if root ball is cracked or broken before or during
planting operation.
3. Backfill around root ball in layers, tamping to settle soil and eliminate voids and
air pockets. When planting pit is approximately one-half filled, water thoroughly
before placing remainder of backfill. Repeat watering until no more water is
absorbed.
4. Place planting tablets equally distributed around each planting pit when pit is
approximately one-half filled. Place tablets beside the root ball about (25mm)
from root tips; do not place tablets in bottom of the hole.
a. Quantity: As per manufacturers recommentations.
5. Continue backfilling process. Water again after placing and tamping final layer of
soil.
F. Slopes: When planting on slopes, set the plant so the root flare on the uphill side is
flush with the surrounding soil on the slope; the edge of the root ball on the downhill side
will be above the surrounding soil. Apply enough soil to cover the downhill side of the
root ball.
A. Remove only dead, dying, or broken branches. Do not prune for shape.
A. Trunk Stabilization by Upright Staking and Tying: Install trunk stabilization as follows
unless otherwise indicated:
1. Upright Staking and Tying: Stake trees of (50mm through 125mm) caliper.
Stake trees of less than (50mm) caliper only as required to prevent wind tip out.
Use a minimum of one stake of length required to penetrate at least (450mm)
below bottom of backfilled excavation and to extend to the dimension indicated
on Drawings above grade. Set vertical stakes and space to avoid penetrating
root balls or root masses.
2. Upright Staking and Tying: Stake trees with three stakes for trees up to (3.6 m)
high and (63mm) or less in caliper (Unless otherwise directed by Architect); three
stakes for trees less than (4.2 m) high and up to (100 mm) in caliper. Space
stakes equally around trees.
3. Support trees with bands of flexible ties at contact points with tree trunk. Allow
enough slack to avoid rigid restraint of tree.
4. Support trees with two strands of tie wire, connected to the brass grommets of
tree-tie webbing at contact points with tree trunk. Allow enough slack to avoid
rigid restraint of tree.
B. Trunk Stabilization by Staking and Guying: Install trunk stabilization as follows unless
otherwise indicated on Drawings. Stake and guy trees more than (4.2 m) in height and
more than (75 mm) in caliper unless otherwise indicated.
1. Site-Fabricated, Staking-and-Guying Method: Install no fewer than three guys
spaced equally around tree.
a. Securely attach guys to stakes (760 mm) long, driven to grade. Adjust
spacing to avoid penetrating root balls or root masses. Provide
turnbucklefor each guy wire and tighten securely.
b. For trees more than (150 mm) in caliper, anchor guys to wood deadmen
buried at least (900 mm) below grade. Provide turnbuckles for each guy
wire and tighten securely.
c. Support trees with bands of flexible ties at contact points with tree trunk
and reaching to turnbuckles. Allow enough slack to avoid rigid restraint of
tree.
d. Support trees with guy cable, connected to the brass grommets of tree-tie
webbing at contact points with tree trunk and reaching to turnbuckle
compression spring. Allow enough slack to avoid rigid restraint of tree.
e. Attach flags to each guy wire, (760 mm) above finish grade.
f. Paint turnbuckles with luminescent white paint.
C. Palm dead man guying: Carry out in accordance with manufacturers details.
A. Install root barrier where trees are planted within 1200 mm of paving or other hardscape
elements, such as walls, curbs, and walkways, unless otherwise indicated on Drawings.
B. Align root barrier vertically, and run it linearly along and adjacent to the paving or other
hardscape elements to be protected from invasive roots.
KEO/19-3262-0000 32 9300/16 Plants
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
C. Install root barrier continuously for a distance of 2000 mm in each direction from the tree
trunk, for a total distance of (4000)mm per tree. If trees are spaced closer, use a single
continuous piece of root barrier.
1. Position top of root barrier according to manufacturer's written recommendations.
2. Overlap root barrier a minimum of (300 mm) at joints.
3. Do not distort or bend root barrier during construction activities.
4. Do not install root barrier surrounding the root ball of tree.
A. Set out and space ground cover and plants other than trees, shrubs, and vines in even
rows with triangular spacing.
B. Use planting soil for backfill as per Section 32 9113 "Soil Preparation"
D. For rooted cutting plants supplied in flats, plant each in a manner that minimally disturbs
the root system but to a depth not less than two nodes.
E. Work soil around roots to eliminate air pockets and leave a slight saucer indentation
around plants to hold water.
F. Water thoroughly after planting, taking care not to cover plant crowns with wet soil.
G. Protect plants from hot sun and wind; remove protection if plants show evidence of
recovery from transplanting shock.
B. Shovel-Cut Edging (where directed): Separate mulched areas from turf areas, curbs,
and paving with a 45-degree, (100mm to 150mm) deep, shovel-cut edge.
B. Fill in, as necessary, soil subsidence that may occur because of settling or other
processes. Replace mulch materials damaged or lost in areas of subsidence.
C. Apply treatments as required to keep plant materials, planted areas, and soils free of
pests and pathogens or disease. Use integrated pest management practices when
possible to minimize use of pesticides and reduce hazards. Treatments include physical
controls such as hosing off foliage, mechanical controls such as traps, and biological
control agents.
A. Apply pesticides and other chemical products and biological control agents according to
authorities having jurisdiction and manufacturer's written recommendations. Coordinate
applications with Owner's operations and others in proximity to the Work. Notify Owner
before each application is performed.
A. General: Repair or replace existing or new trees and other plants that are damaged by
construction operations, in a manner approved by Architect.
1. Submit details of proposed pruning and repairs.
2. Perform repairs of damaged trunks, branches, and roots within 24 hours, if
approved.
3. Replace trees and other plants that cannot be repaired and restored to full-
growth status, as determined by Architect.
B. Remove and replace trees that are more than 25 percent dead or in an unhealthy
condition or are damaged during construction operations that Architect determines are
incapable of restoring to normal growth pattern within 15days of notification.
1. Provide new trees of same size as those being replaced with matching height,
spread and caliper.
2. Species of Replacement Trees: Same species being replaced.
A. During planting, keep adjacent paving and construction clean and work area in an
orderly condition. Clean wheels of vehicles before leaving site to avoid tracking soil
onto roads, walks, or other paved areas.
B. Remove surplus soil and waste material including excess subsoil, unsuitable soil, trash,
and debris and legally dispose of them off Owner's property.
C. Protect plants from damage due to landscape operations and operations of other
contractors and trades. Maintain protection during installation and maintenance periods.
Treat, repair, or replace damaged plantings.
D. After installation and before Substantial Completion, remove nursery tags, nursery
stakes, tie tape, labels, wire, burlap, and other debris from plant material, planting areas,
and Project site.
A. Maintenance Service for Trees and Shrubs: Provide maintenance by skilled employees
of landscape Installer. Maintain as required in "Plant Maintenance" Article. Begin
maintenance immediately after plants are installed and continue until plantings are
acceptably healthy and well established, but for not less than maintenance period
below:
1. Maintenance Period: 12 months from date of planting practical completion.
B. Maintenance Service for Ground Cover and Other Plants: Provide maintenance by
skilled employees of landscape Installer. Maintain as required in "Plant Maintenance"
Article. Begin maintenance immediately after plants are installed and continue until
plantings are acceptably healthy and well established, but for not less than maintenance
period below:
1. Maintenance Period: 12 months from date of planting practical completion.
END OF SECTION
PLANTING ACCESSORIES
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.01 SUMMARY
A. Section Includes:
1. Planting Screens
2. Pedestrian Screens
3. Tree Stakes & Ties
4. Root ball fixing systems
B. Division 5 - Metals
1.03 REFERENCES
1.04 SUBMITTALS
A. Submit listed submittals in accordance with Conditions of the Contract and Division 01
Submittal Procedures Section.
1. Product Data: Submit Manufacturer’s product data sheet for specified products.
2. Shop Drawings: Show layout, sizes, dimensions, details, and installation of railing
frame components. Include Details of rope attachment, tensioning methods,
hardware, and tensioning and mounting methodology.
3. Samples: Submit samples of rope and/or hardware, as required by specifier.
4. Quality Assurance/Control Submittals:
KEO/19-3262-0000 32 9400/1 Planting Accessories
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
a. Test reports: Submit any test report demonstrating compliance with
intended use and code requirements.
b. Certificates: Submit manufacturer’s certificate that product meets or
exceeds specified requirements
5. Closeout Submittals: Submit the Following:
a. Warranty: Submit manufacturer’s standard warranty documents
b. Maintenance Data: Include manufacturer’s standard cleaning and
maintenance instructions to avoid detrimental actions to finishes and
performance.
A. Qualifications:
1. Installer Qualifications: Installer should be experienced in performing work of this
section and should have specialized in installation of work similar to that required
for this project.
B. Mock-Ups:
1. Install at project site or appropriate location a job mock-up using acceptable
products and manufacturer approved installation methods. Obtain Employer’s
and Engineer’s approval of product, application, and workmanship standards.
Comply with Division1 Quality Control Section.
2. Maintenance and Disposal: Maintain mock-up during construction for
workmanship comparison.
A. General: Comply with Division 1 Product Requirements Sections Ordering: Comply with
manufacturer’s ordering instructions and lead time requirements to avoid construction
delays.
C. Storage and Protection: Store materials protected from exposure to harmful weather
conditions and at temperature and humidity conditions recommended by manufacturer.
Store cartons and panels in a secure location in a dry place at the project site.
1.07 WARRANTY
PART 2 - PRODUCT
B. Hessian bands shall be 75mm wide to lengths necessary for wrapping tree trunks and
main branches.
A. The contractor shall supply, erect and maintain a pedestrian strong fence around lawn
areas until an established sward is attained. Once achieved the contractor shall remove
fence and arisings from site and refurbish any lawn as necessary. The Contractor shall
supply an installed sample of the proposed fencing system off-site for approval by the
Engineer.
A. All stakes shall be double stakes of timber, straight, free of projections and pointed at
one end. The stakes shall be pressure impregnated with non-injurious wood
preservative to be applied at least two weeks before use.
B. Stakes shall be as indicated on drawings; the length below ground to be one metre
minimum and the length above to be 1.8m, unless otherwise approved by the Engineer.
A. Tree ties shall be fabricated from UV resistant material, be fully adjustable to allow for
tree growth and shall be:
1. Rainbow Chainlock Range C219 – Chainlock No.4 (25.4 x 2.5mm) or approved
equivalent and shall be of consistent type throughout the site as shown on
drawing.
A. Provide Root Ball protection mesh, anchors, galvanized tension cable, ratchet
tensioners as indicated on drawings or as recommended by the manufacturer.
PART 3 - EXECUTION
3.02 EXAMINATION
A. Supply items required to be cast into concrete or embedded in masonry with setting
templates, to appropriate sections.
B. Take field measurements after permanent end terminations are in place and prior to
preparation of shop drawings and fabrication, to ensure fitting of work.
3.04 INSTALLATION
A. Install cable plant support system in accordance with manufacturer's instructions and
the approved shop drawings.
H. After final adjustment provide tamper resistant locktight materials on all fittings.
3.05 CLEANING
C. Remove from project site and legally dispose of construction debris associated with this
work.
3.06 PROTECTION
END OF SECTION
PLANTING MAINTENANCE
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
A. The works specified in this section cover all works necessary to maintain the exterior
soft landscape works of the development in coordination with hard landscape, irrigation,
landscape lighting and other site works and contractors. The works shall be carried out
at areas detailed on drawings.
B. Furnish and supply all materials, equipment and labour for maintenance of all
landscaped areas installed as part of this contract.
C. The work shall include, but not be limited to mowing, weed control, insect control,
disease control, pruning, replacement of sub-standard or dead plant material.
D. Perform all work in a manner to comply with the original installation specifications.
1.02 GENERAL
A. The Contractor is responsible for the on-going maintenance of the exterior planted
areas. The Contractor is responsible for all maintenance during the contract period.
B. Begin maintenance of plant materials immediately after planting and continue until
termination of warranty period.
C. This contract includes a 24 month maintenance period from the date of Taking Over
Certificate. The Contractor is responsible for ensuring the continued good health and
good growth of all plants throughout the maintenance period. It is anticipated that the
Contractor will visit the site at least weekly and more frequently when needed such as
during dry periods to monitor the irrigation system or hand watering as required to
ensure the continued good health and growth of all plants.
F. The Contractor shall include the cost of training personnel employed by the Employer
for the entire Maintenance period.
G. All chemicals, fertilizers, pesticides and herbicides shall be locked in specially designed
containers and maintained through the maintenance period to avoid spillage or
accidental inhalation. Pollution from spills or litter shall be removed from the
landscaping areas during normal maintenance.
H. Soil and Fertility: Use of fertilizers and soil additives are to be kept to an absolute
minimum. Soils are to have salinity levels and nutrient levels checked quarterly to inform
use of fertilizers.
B. This manual shall be submitted for approval at least two weeks prior to Date of Taking
Over Certificate.
1.04 REPORTING
A. During the maintenance period the Contractor shall replace at the Contractor's expense
any dead or unhealthy plant material. This does not include the replacement of plants
removed or killed by vandalism by others. Any plants removed or killed by vandalism
shall be reported to the Engineer. The Engineer may instruct a variation for the
replacement of the plant material.
A. The Contractor shall be responsible for the supply, cartage and spreading of fertiliser.
B. A proprietary fertiliser suited to the species and approved by the Employer or nominated
representative shall be applied at 6 months, 12 months, 18 months, 24 months where
plants are showing signs of lack of fertility, or to ensure maximum health and vigour in
all grades of shrubbery as identified above.
2.03 WEEDS
A. The Contractor shall carry out detailed inspections of the planted areas at least
fortnightly and programme to control the weeds within twenty four (24) hours of the
inspection. Weeds shall be controlled manually unless approved otherwise by the
Employer or nominated representative. When hoeing/pulling care shall be taken to avoid
damage to plants and their roots. Where area is not mulched the top 20mm of soil is to
be cultivated to a fine tilth. The soil shall not be mixed with mulch when removing
weeds.
2.04 MULCH
A. The Contractor will be responsible for the maintenance, top up, supply, cartage and
spreading of mulch to maintain a depth of 100mm at all times.
B. Mulching shall be carried out on an ongoing basis and at least 6 monthly to all palms
and garden areas unless specifically excluded.
C. The process of installation of mulch includes levelling of soil surface to remove humps
and hollows, and removal of weeds and grass prior to mulching. The Contractor shall
be responsible for controlling regrowth of weeds.
F. The Contractor shall ensure that other materials including soil are not mixed with the
mulch during the work.
G. Edges shall be checked and rebuilt or repaired as necessary prior to mulching. Where
necessary the soil level shall be reduced. Edges shall hold mulch without spillage. The
edges shall not be damaged when placing the mulch.
H. Note that some garden areas may be sloping, and that mulches will require additional
maintenance to keep the edges in specification. Where mulched gardens are on a
slope, the Contractor shall maintain the mulch at 75mm depth across the whole garden.
The contractor shall rake mulch uphill from lower portions regularly to maintain the
specified mulch depth. Spilt mulches shall be collected and spread over adjacent
gardens on each visit.
I. When mulch is applied all low branches and foliage shall be lifted and mulch worked
around the plants. No mulch shall be spilled over the edges of gardens onto surrounding
surfaces. The mulch shall be spread evenly to the correct depth.
J. Where it is known that mulch affects certain species the Employer or nominated
representative shall instruct the Contractor to use alternative mulches approved by the
Employer or nominated representative.
2.05 PRUNING
A. Pruning will be required on shrubs and trees throughout the year to maintain a high
standard of presentation, display and plant vigour. Paths, roads, all other accessways
and windows are to be kept clear of excess growth.
D. Pruning for form, shape and size is to be carried out within two weeks of an instruction
from the Employer or nominated representative at the Contractor’s expense.
F. All prunings shall be removed to waste as they arise leaving the gardens and
surrounding surfaces area in a clean and tidy condition.
G. Spent flowerheads are to be removed including but not limited to the following species:
Agapanthus, arthropodium.
H. The Contractor shall carry out detailed inspections of the shrubbery’s monthly and plan
to remove dead and irrecoverable plants within three (3) days of the inspection. The
Contractor shall report the removal of dead and irrecoverable plants in their monthly
report.
A. GROUND COVERS:
1. Cleaning: Planted area must be clear of any litter, dust, sand, debris and spillage.
2. Edging: Ground cover area must be maintained well, around cabinets, kerbs,
plastic edging, planted areas, flower beds, lamp posts etc.
3. Trimming: Must be maintained in the required shape and structure and as per
instruction received from Engineer / Department
4. Patches & Gaps: Planted area must be free of any gaps / dry patches.
5. Weeds Control: Planted area must be well cultivated and free of any type of
weeds.
6. Health & Vigor: Planted area must be healthy & vigorous.
B. SHRUBS:
1. Cleaning: Area around shrubs including basins must be clear of any weeds, litter,
and debris.
2. Pruning: Shrubs must be free of diseased, dry, broken & malformed branches.
3. Shrub Basin: Shrub basins must be well constructed & cultivated.
4. Shrubs Stake: Newly planted shrubs must be supported by wooden stakes
5. Health & Vigour: Plants must be green, healthy, vigorous & free of dust.
6. Dead Shrubs: Any dead shrubs shall be removed and replaced by the same
type.
C. TREES:
1. Cleaning: Area around trees including basins must be clear of any weeds, litter,
and debris.
D. PALMS:
1. Cleaning: Area around palms including basins must be clear of any weeds, litter,
and debris.
2. Remove Dead / Dry Fronds (Taseef): Dead and dry frond must be removed as
per the approved method statements.
3. Remove Fronds Basis (Takreeb): Frond basis must be removed as per the
approved method statements.
4. Palm Basin: Palm basin must be well constructed & cultivated.
5. Health & Vigour: Palms must be green, healthy, vigorous & free of dust.
6. Palms Off-Shoots (Suroom): All palm off-shoots must be removed according to
the approved method statement.
7. Palm Dry Stalk & Spathes: Dry male and female stalks and spathes (ezok) must
be removed.
8. Dead Palms: Any dead palms shall be removed and Replaced by the same plant
species.
2.07 TURF
A. The Contractor is responsible for ensuring that a clean, stone free, stable synthetic turf
system is established and maintained by the completion of the maintenance period.
A. The Contractor shall be responsible for the supply, cartage and placement of supports.
B. Prior to installation, the Contractor shall supply a sample of supports for approval by the
Engineer and Employer or nominated representative. These shall be inconspicuous and
matched throughout the Contract area. Guys, ties and supports shall be added,
replaced and adjusted as necessary to allow for growth and prevent chaffing. Ties shall
be tightened as necessary to support the plant. The Contractor shall ensure that all
stakes are sound and are sufficiently inserted to prevent lateral movement. Broken
stakes shall be replaced within 24 hours of discovery by the Contractor or notification by
the Engineer.
C. Stakes shall be installed and maintained taut and be the same height throughout the
Contract area, or lesser approved area.
D. The Contractor shall carry out detailed inspections of stakes monthly and plan to make
repairs, remove redundant tapes, tags, ties and other encumbrances to the satisfaction
of the staking specifications within twenty four (24) hours of the inspection.
E. Plants must be supported in such a way as to protect the plant and stem from damage.
F. The Contractor shall inspect and make good all damaged and defective stakes. The
Contractor shall check stakes for looseness, breaks and decay and replace as
necessary. If any plant has grown sufficiently to be self-supporting the Contractor shall
remove the support, ties and fill any holes with soil, lightly compacted.
G. Where chaffing has occurred, the Contractor shall reposition tie(s), insert a spacer or
replace the support to prevent further chaffing.
A. The Contractor is responsible for the monitoring and control of plant health, pests and
diseases within the Contract area. To affect this, the Contractor shall make inspections
in conjunction with other inspections and activities and arrange for eradication or
treatment of the health problem within five (5) days of inspection. Any health problem
shall be reported to the Employer or nominated representative.
B. The Contractor shall be pro active in the reporting and treatment of anything affecting
the well being of the plants. In particular significant adverse conditions, dieback or
browning of leaves, branches, or any other signs.
C. Where soil borne fungal disease such as Phytophora become evident the Contractor
shall supply and apply “Trichopel” pellets or approved equivalent according to
manufacturer’s recommendation to affected areas and other areas likely to be affected.
D. Where damage from desiccation or wind damage starts to occur an anti-transpirant shall
be applied. The Contractor shall allow to supply and apply Anti-transpirants or other
suitable treatment to prevent further desiccation in accordance with the manufacturer’s
recommendations.
A. Where reference is made to edges and/or hard surfaces elsewhere in this document,
this section shall apply.
1. EDGES
2. Edges include but are not limited to; All grass and garden edges, kerbs, paths,
structures including seats, tables and furniture, signs, statues and sculpture,
water features and ponds, rubbish bins, rocks, buildings, retainers, fences, the
interface between grass and the trunks of trees and shrubs, around trees, mulch
edges, poles, posts, cesspits, drains, roadways, footpaths and car parks, drains
and the like.
3. Edges shall be maintained so that they hold any loose materials from
encroaching onto neighbouring surfaces. Where materials do escape onto
surrounding surfaces they are to be removed or reused as appropriate.
B. HARD SURFACES
1. Hard surfaces include, but are not limited to, all paths, car parks and paved
areas, wooden decking, boardwalks, bridges, stone and retaining walls, drain
grates within the scheduled areas. These surfaces are to be maintained free of
weeds, grass and moss or other vegetative material and all loose soil, mulch, or
other material.
A. Where possible, eroding soil material, surface runoff and subsurface flow that may
transport soil contaminants into the marine environment, potentially causing such issues
as pollution, turbidity and eutrophication should be avoided.
B. Vegetation shall be controlled so it does not exceed the maximum height and maximum
spread. At least 99 percent of the total edge length shall be satisfactorily treated and the
overall appearance of the garden/reserve shall be satisfactory.
C. NOTE: There are many instances where only either maximum height or maximum
spread are applicable at any edge.
D. Maximum Height: The maximum height in millimetres (mm) above firm ground level that
vegetation shall be allowed to reach at the edge defined in table below.
E. Maximum Spread: The maximum distance in millimetres (mm) that vegetation shall be
allowed to reach from the edge defined in table below.
F. Where manual methods of control are used the protruding vegetation shall be cut by use
of clippers or some other mechanical device that make a precise, even cut. A
proprietary edging machine shall be used against kerbs, concrete paths, mowing strips
etc.
G. Any spraying control methods shall use non-toxic materials approved by the Employer
or nominated representative in accordance with the Landscape Specification.
H. Where the edge is not defined the edge shall be controlled when the vegetation varies
more than the maximum spread defined in the Table over two (2) metres from a straight
line or natural curve.
I. All weeds shall be removed from within hard surfaces including but not limited to car
parks, walkways, paths etc. All moss shall be prevented from building up on paths such
that the path becomes slippery.
B. Dead, missing or defective plant material or turf shall be replaced. Replaced plants will
be of the same size and species as originally specified.
C. Weed plant beds and saucers. Prior to inspection treat these areas with an application
of approved pre-emergent herbicide.
D. Remove stakes, guy wires and wrappings from plants as directed by the Engineer.
G. A final inspection, if required, shall be undertaken by the Engineer to determine that the
deficiencies noted in the preliminary inspection have been corrected. The time for this
inspection shall be established in writing.
END OF SECTION
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions, Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes:
1. Water Distribution piping and related components outside the building for
potable water supply.
B. Related Sections:
1. Section 03 3000 : Cast-in-Place Concrete
2. Section 31 2300 : Excavation
3. Section 31 2313 : Backfilling
4. Section 31 2333 : Trench Excavation, Pipe Installation and Backfill
5. Section 33 3328 : HDPE Pressure Pipe and Fittings
6. Section 33 3327 : Ductile Iron Pipe and Fittings
1.3 REFERENCES
A. AWWA C 151 Ductile Iron Pipe, Centrifugally Cast in Metal Moulds or Sand
Lined Moulds, for Water or Other Liquids.(ISO - 2531)
B. AWWA C 110 Ductile Iron and Grey Iron Fittings 75 mm (3 inch) through
1200 mm (48 inch) nom. dia. for Water and Other Liquids (ISO
- 2531)
C. AWWA C 111 Rubber Gasket Joints for Ductile Iron and Grey Iron Pressure
Pipe and Fittings
D. AWWA C 105 Polyethylene Encasement for Ductile Iron piping for Water and
Other Liquids
E. AWWA C 104 Internal Cement Lining for Potable Water Supply Piping
G. AWWA C 203 External Coating for Ductile Iron Pipes and Fittings
K. BS 1560 / 4504 Circular flanges for pipes, valves and fittings - Class / PN
designated (ANSI B 16.5 / B 16.1 / B 16.24)
O. BS 5151 Specification for Cast Iron Gate (parallel slide) Valves for
General Purposes
P. BS 5152 Specification for Cast Iron Globe and Globe stop and Check
valves for general purposes purposes
Q. BS 5153 Specification for Cast Iron Check Valves for general purposes
S. BS 5159 Specification for Cast Iron and Cast Steel Ball Valves for
General Purposes
BB. AASHTO T 180 Moisture Density Relations of Soils using 10 lbs 4.54 kg)
Rammer
CC. AWWA C 601 Standard Methods for the Examination of Water and
Wastewater
1.4 SUBMITTALS
A. Product data, samples and shop drawings shall be submitted in accordance with the
Conditions of Contract.
1. Manufacturers printed brochures and catalogues (one original and three copies)
with relevant information highlighted (or irrelevant information struck out), along
with write up of selection criteria
2. General piping layout drawings to a scale not smaller than 1:1000 and detail
plans to a scale not smaller than 1:250, along with profiles to a suitable scale.
Indicate dimensions, method of field assembly and components.
B. Coordination Drawings: For piping and specialties including relation to other services in
same area, drawn to scale. Show piping and specialty sizes and valves, specialty
locations and elevations.
E. Operation and Maintenance Data: For water valves and specialties to include in
emergency, operation and maintenance manuals.
F. Project record documents of all works installed under this section shall be submitted in
accordance with the General Conditions of Contract.
G. Three (3) hard bound copies of “Operation and Maintenance Manual" shall be
submitted in accordance with the General Conditions of Contract, with complete data
for each piece of equipment installed, as detailed below:
1. Manual shall contain:
a. Table of contents
b. Material submittal with the Engineer's and local authorities’ approval
c. Manufacturer's installation instructions
d. Manufacturer's assembly details
e. Replacement, parts number listings and description
f. Preventive maintenance schedules listing frequency of service and or
replacement.
g. Lubrication materials, equivalents and schedules
h. Name and addresses of manufacturer, sales and service agency and
local representative / distributor including telephone and fax numbers
i. Names and address of Contractor's maintenance department, including
emergency contact telephone numbers
2. Contents of the manual shall be arranged in sections with tags, grouping each
class of equipment as piping, valves and control gear, pumps, controls, etc.
3. Contents of each section shall be arranged in sequence as listed above (Item 2)
H. Comprehensive, priced list of tools and spare parts clearly cross-referenced with As-
Built Drawings and Operation and Maintenance Manuals; as recommended by the
manufacturer. Prices offered shall be valid during the maintenance period.
D. Valves and similar control gear shall have manufacturer's name, pressure rating and
size cast-on the valve body.
F. For each product specified, provide from the same manufacturer throughout, where
possible.
C. Handling: Use sling to handle valves if size requires handling by crane or lift. Rig
valves to avoid damage to exposed parts. Do not use hand wheels or stems as lifting
or rigging points.
E. Valves shall be delivered and stored in shipping containers with labelling in place. Plug
and ball valves shall be kept in open position and gate / globe valves in closed position
to prevent damage to valve seats. Flange / thread protectors shall be retained on the
valves, until installation, to prevent damage to the flange faces / threads.
F. Protect stored piping from moisture and dirt. Store piping on elevated racks. Do not
exceed structural capacity of floor when storing inside.
H. Store plastic piping protected from direct sunlight. Support to prevent sagging and
bending.
A. Test certificates from third party agencies shall be furnished in respect of the following:
1. Conformance of coating / lining materials with minimum requirements of
reference standards in respect of:
a. Impact strength, and
b. Chemical resistance as confirmed by immersion of the finished product in
acid, alkali and de-ionized water
2. Verification / certification of the physical dimensions and unit weights of
samples of pipes, fittings and valves
3. Hydraulic pressure tests of each piece of pipes, fittings and valves
4. Chemical composition of samples from each batch of pipes, fittings and
valves.
PART 2 PRODUCTS
2.1 PIPING
1. D.I pipe and fitting shall confirm to the requirements of Section 33 3327
A. Valve Boxes: Comply with AWWA M44 for cast-iron valve boxes, if required. Include
top section, adjustable extension of length required for depth of burial of valve, plug and
bottom section with base that fits over valve and with a barrel approximately 5 inches
(125 mm) in diameter.
1. Operating Wrenches: Steel, tee-handle with one pointed end, stem of length to
operate deepest buried valve, and socket matching valve operating nut.
A. Air-Release Valves:
1. Manufacturers: Subject to compliance with requirements, provide products approved by
the concerned ministry.
A. Pillar hydrants and buried valves shall be supported on concrete pedestals resting on
undisturbed soil.
B. Buried piping shall be supported by concrete thrust blocks resting on undisturbed soil at
all changes of direction, size or elevation to counter the thrust forces.
3.1 EARTHWORK
A. Comply with excavating, trenching, and backfilling requirements in Division 31.
3.2 CO-ORDINATION
A. Contractor shall study all drawings and specifications and familiarize with the details
and the work of other trades.
B. Contractor shall ensure that the work under this section shall not interfere with those of
other trades and are compatible with them prior to placing orders, fabrication and
installation.
C. Templates, patterns, setting out plans and other items shall be furnished for
incorporation in the works of other trades. Contractor shall ensure timely placement of
sleeves, inserts and the like.
D. Where work is installed in close proximity to or will interfere with work of other trades,
the Contractor shall assist in working out satisfactory space arrangements. Composite
shop drawings shall be prepared, to a suitable scale, showing how the work is installed
in relation to the work of other trades.
E. Contractor shall resolve conflicts in requirements with other trades. Only those, which
cannot be solved without changes to structure or those, which involves major changes
to system design, shall be referred to the Engineer.
3.3 PREPARATION
A. Pipes shall be cut perpendicular to the axis, with approved cutting tools, ends tapered
by a grinder and a fast drying coal tar coat shall be applied at the bared areas.
B. Scale and dirt, on inside and outside and weld splatter shall be removed before
assembly.
C. Coating on ductile iron pipes and fittings shall be repaired with approved paint
(recommended by the manufacturer) where factory coating has been damaged.
D. Piping connections to valves and equipment shall be made with flanges.
E. Spigot ends which joins the fitting sockets to form a locked mechanical joint as
specified for chamber piping shall be machined to have an annular groove into which
the locking ring is engaged. Contractor shall obtain the control gauges from the pipe
manufacturer to check the location and cross section of the groove before carrying out
the machining operation. It is recommended to carry this out in a workshop on a lathe
or to perform the work with an on-site machine. After the groove is machined a fast
drying coal tar coat shall be applied on the cut.
3.4 INSPECTION BEFORE INSTALLATION
A. Materials shall be carefully inspected and examined for cracks and other defects while
suspended above the trench immediately before installation in final position.
A. Pipes shall be laid and connected at the required depth in straight line and true to the
gradient on an even foundation, for the full length of the barrel, with the sockets facing
up the gradient, including necessary fittings.
B. While jointing pipes, a mark shall be made to check the position of the end of the barrel.
In view of the flexibility of the joint, a gap 5 to 10 mm wide shall be left between the
ends of the pipes. Rubber rings shall be lubricated with graphite paste. When pipes are
laid in curves, the pipe may not be bent sideways until the connection has been made.
C. Piping shall be kept free of earth, dirt, and extraneous matter and clean every pipe after
installation by special cleaning tools approved by the Engineer. Contractor shall furnish
mirrors, lamps and necessary personnel as directed, to enable Engineer to inspect the
drainage pipeline at any time during construction.
D. Pipe shall not be laid when conditions are unsuitable, in the opinion of the Engineer.
A. Piping shall be installed in such a way that conserves space and does not interfere with
the use of space.
B. Minimum clearances shall be provided between piping covered by this Section and
those of other trades.
C. Pipes shall be handled with utmost care so as not to subject the pipes to shocks, which
may crack or break the internal lining. Pipes with damaged concrete lining shall not be
used.
F. Piping shall be protected against the ingress of foreign material before the pipe is
placed in the new line. If the fitting or valve cannot be placed into the trench and in
place, without getting earth into it, each end shall be covered with a heavy, tightly
woven canvas bag of suitable size before lowering them into the trench. The bag shall
be left there until the connection is to be made to the adjacent pipe.
G. If the pipe contains dirt, then the interior shall be cleaned and swabbed with a
bactericidal solution, formed from one of the compounds listed in AWWA C 601-54 or
approved equal. Chlorinated lime and water mixture shall not be used.
H. Water-Main Connection: Connect water main to the fresh water supply pipes from
pump room according to requirements of AHJ and of size and in location indicated on
the drawings.
J. Install ductile-iron, water-service piping according to AWWA C600 and AWWA M41.
1. Install encasement for piping according to ASTM A 674 or AWWA C105.
K. Bury piping with depth of cover over top at least 30 inches (750 mm) below level of
maximum frost penetration, and according to the following unless otherwise indicated
on the drawings:
1. Under Driveways: With at least 36 inches (910 mm) of cover over top.
2. In Loose Gravelly Soil and Rock: With at least 12 inches (300 mm) of additional
cover.
L. Install piping by tunneling or jacking, or combination of both, under streets and other
obstructions that cannot be disturbed.
M. Install underground piping with restrained joints at horizontal and vertical changes in
direction. Use restrained-joint piping, thrust blocks, anchors, tie-rods and clamps, and
other supports.
A. Install couplings, flanges, flanged fittings, unions, nipples, and transition and special
fittings that have finish and pressure rating same as or higher than systems pressure
rating for aboveground applications unless otherwise indicated.
B. Install unions adjacent to each valve in tubing NPS 2 (DN 50) and smaller.
D. Remove scale, slag, dirt, and debris from outside and inside of pipes, tubes, and fittings
before assembly.
G. Flanged Joints: Select appropriate gasket material in size, type, and thickness suitable
for water service. Join flanges with bolts according to ASME B31.9.
H. Dissimilar Materials Piping Joints: Use adapters compatible with both piping materials,
with OD, and with system working pressure.
A. During the manufacture and installation and after completion of works; the system,
sections of the system or its components shall be tested in the presence of the
Engineer, as directed below or elsewhere. Contractor shall furnish testing instruments
and accessories as directed by the Engineer.
1. Basic materials for conformity with the specified standards
2. Supports and anchors for ability to withstand required loads
3. Piping in general for line, level, gradient and water tightness
B. Use test procedure prescribed by AHJ or, if method is not prescribed by AHJ, use
procedure described below.
C. Piping in chambers / tunnels shall be tested only after checking the proper installation
of fittings and the locking ring. Bolts shall be tightened correctly and no component that
may be detached (and cause accidents) when the piping is subjected to test pressure
shall be left loose.
A. Utility connections shall be executed using appropriate joints, after tests are completed
and temporary testing arrangement(s) be removed.
B. Contractor shall co-ordinate with relevant Sections, obtain all necessary information on
available utility mains, obtain approvals and permits, and pay all fees and expenses in
this respect.
1. Fresh Water - MEW Water Department
3.13 DISINFECTION
D. Proper care shall be exercised in the storage of liquid chlorine, hypochlorite or other
disinfecting agents. These shall be stored in tightly closed containers inaccessible to
children or unauthorized persons. Manufacturer's instructions shall be followed, to the
approval of the Engineer, in the storage and handling of these chemicals.
E. pH of water to be treated shall be adjusted to between 7.4 and 7.6 by adding alkali
(caustic soda or soda ash) or acid (hydrochloric acid) prior to the addition of the
disinfecting agent.
F. Water mixed with disinfectant, sufficient to produce between 5 to 10 ppm (mg/L) free
chlorine after 12 hours, shall be fed slowly into the pipeline and maintained for 12
hours. Dosage shall not be exceeded without the approval of the Engineer.
G. Treatment shall be repeated if final disinfectant residual tests less than 5 ppm after 12
hours, at any outlet.
A. System shall be flushed, until residual chlorine is equal to that of incoming water or 1.0
ppm, disposing off the water in a manner approved by the Engineer.
B. System shall be charged with water intended for the service and kept under pressure.
Pipe work shall never be left partially filled, under any circumstance.
C. Samples shall be taken no sooner than 24 hours after charging, from remote outlet(s)
and from the water entry and analysed in accordance with AWWA C 601 and results of
the analysis shall be submitted to the Engineer.
D. System shall be drained, flushing and re-charged, where results of water analysis are
not satisfactory.
3.15 IDENTIFICATION
END OF SECTION
PART 1 - GENERAL
1.01 REQUIREMENT
A. The Contractor shall provide wet-barrel fire hydrants, complete and operable in
accordance with the requirements of the Contract Documents.
A. The Work of the following Section applies to the Work of this Section. Other Sections of
the Specifications, not referenced below, shall also apply to the extent required for
proper performance of this Work.
1. Section 01330 – Submittals.
2. Section 09980 – Linings and Protective Coatings for Concrete.
3. Section 15110 – Valves, General.
A. The following standards have been referenced in this Section of the Specifications:
1. ANSI/AWWA C503 Wet Barrel Fire Hydrants
2. AWWA C550 Protective Epoxy Interior Coatings for Valves and
Hydrants.
PART 2 - PRODUCTS
A. Construction: Fire hydrants where required by the Kuwait Fire Brigade, or indicted, shall
be of the wet-barrel type, in accordance with ANSI/AWWA C 503. Wet-Barrel Fire
Hydrants shall have a buried section of ductile iron or steel and a break-away flange
connected to the hydrant head. Each hydrant shall be isolated by an individual, buried
gate valve with cast iron box and cover. The hydrant head shall have a minimum of one
connection to suit the normal Kuwait Fire Brigade hose connectors and one 63mm hose
connection, except where otherwise required by the local fire department. The hose
connection shall be of brass or bronze. The hydrant inlet shall be not less than 150mm
KEO/19-3262-0000 33 1219/1 Water Utility Distribution Fire Hydrants
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
in diameter. The hose and steamer connections shall be provided with cast iron caps
and metal chains. All bolts, nuts, and washers shall be of Type 316 stainless steel,
unless otherwise required for structural reasons. The hydrants shall be tested to 20 Bar
Gauge and they shall be suitable for a working pressure of 10 Bar Gauge. All interior
and exterior surfaces shall be coated in accordance with AWWA C 550 and Section
09870 and painted ANSI safety yellow in accordance with local codes.
PART 3 - EXECUTION
3.01 INSTALLATION
A. All fire hydrants shall be installed in strict accordance with the manufacturer’s published
recommendations, AWWA Standards, and all applicable codes, All installations shall be
to the satisfaction of the Kuwait Fire Brigade and Kuwait Municipality.
B. All hydrant isolating valves with slip joints, friction type, or calked joint connections shall
be harnessed to the main pipe by means of welded steel harness sets, or clamps and
steel rods, designed for this purpose. All hydrants with other than flanged inlets shall be
installed with a concrete thrust block, calculated for the maximum expected water
pressure, with allowances for surge.
END OF SECTION
PART 1 - GENERAL
1.01 SUMMARY
A. This section specifies installation and testing for Sanitary Sewerage systems and
includes, but is not limited to, the following:
1. General Requirements
2. Pipe testing
3. Connections to existing pipelines
4. Over pumping and flow diversion.
B. For trench excavation, pipe installation, and backfill see Section 31 2315.
1.03 REFERENCES
A. Product manufacture, testing and installation shall comply with the following references,
unless otherwise stated in the specifications, or unless otherwise approved by Engineer.
1.04 DEFINITIONS
A. The following definitions shall pertain to words or phrases as utilized in this section.
1. "uPVC" shall mean unplasticised polyvinyl chloride.
2. HDPE" shall mean high density polyethylene.
3. "RCP" shall mean reinforced concrete pipe.
4. "DI" shall mean ductile iron.
5. "Pipe Surround" shall mean that material directly below, around and above the
pipe.
6. "Formation" shall mean the bottom of the trench excavation, or in some cases, fill
just below the pipe surround.
7. "Stanks" shall mean barriers to flowing water within granular pipe surround
material
A. The Contractor shall provide all labour, materials and equipment necessary for providing
a complete operating system.
B. Responsibility for the safety and soundness of all material shall rest with the Contractor.
C. Contractor is advised to carry out any tests (at his cost) needed to satisfy himself
regarding the soundness of the pipes, fittings and jointing materials prior to acceptance
testing by the Engineer.
D. Pipe materials to be utilised shall be as shown on the drawings, or as described in the
particular and general specifications.
E. Each type of pipe and fittings shall be furnished by a single manufacturer,
unless otherwise accepted by the Engineer.
1.06 SUBMITTALS
A. Product Approval
1. The Contractor shall submit sufficient information to the Engineer, prior to
purchase according to Section 01 3300, in order to verify compliance with the
specifications. Such information shall include at least the following:
a. Manufacturers name
b. Suppliers name
c. Product name (if applicable)
d. Product description
e. Manufacturers technical data
f. Storage instructions
g. Installation instructions
C. Method Statements
1. The Contractor shall provide method statements meeting the requirements of
Section 01 4000, for at least the following activities, or as requested by the
Engineer.
a. Pipe testing.
KEO/19-3262-0000 33 3000/2 Sanitary Sewerage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
b. Manhole and chamber construction.
c. Pump station connection.
d. Pipe installation including backfill compaction methods for flexible
(uPVC and HDPE) pipes.
D. Shop Drawings
1. The Contractor shall submit shop drawings according to Section 01 3300 for
at least the following items:
a. Manhole and chamber construction
b. Pump station construction.
B. “ Inspection Request” for at least the following items, shall be submitted to the Engineer
during the on-site installation work, prior to proceeding with the following activities.
Minimum notification time shall be 24 hours.
1. Pipe testing.
2. Backfilling.
3. Reinforcing Steel for Cast-in-situ Concrete.
4. Formwork for Cast-in-Situ Concrete.
5. Placing of Cast-in-Situ Concrete.
A. General requirements for delivery, storage and handling of products and materials shall
be specified in Section 01 6000 – “Product Requirements”.
B. Specific requirements shall be as specified in the relevant specification section
governing the manufacture and installation of the material or product in question.
C. Additional requirements may be required as per the manufactures recommendations
and/or the directives of the Engineer.
1. Transportation, handling and storage shall at all times be performed in a manner
to avoid product damage.
2. Only nylon slings shall be allowed for lifting products. Steel chains, clamps or
cables shall not be allowed for lifting purposes, unless approved by the Engineer.
a. Steel chains or cables may be allowed for securing products during
transport of storage, provided protective padding or timber blocking is
utilized.
3. Do not store products directly on the ground, unless approved by the engineer.
4. Visually inspect all products upon delivery and report any damage to the
Engineer.
a. Any products damaged during delivery, storage or installation shall be
marked and set aside.
b. Proposals for repair of any damaged products shall be submitted in
writing to the Engineer for approval.
KEO/19-3262-0000 33 3000/3 Sanitary Sewerage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
c. No repairs to damaged products shall be attempted, without the
Engineer’s approval.
d. Any damaged products deemed unsuitable for repair by the Engineer
shall be removed from site and replaced at the Contractors expense.
PART 2 - PRODUCTS
A. RCP and fittings shall comply with the requirements of Section 33 3101 - "Reinforced
Concrete Pipe and Fittings".
B. Ductile Iron Pipes shall comply with the requirements of Section 33 3327 - "Ductile Iron
C. Polymer Concrete Pipes shall comply with the requirements of Section 33 3103 –
“Polymer Concrete Pipes”.
D. uPVC Pipes and fittings shall conform to the requirements of Section 33 3330 – “uPVC
Pipes and Fittings”.
E. HDPE Pipes and fittings shall conform to the requirements of Section 33 3102 – “HDPE
Gravity Sewer Pipes and Fittings” and Section 33 3328 – “HDPE Pressure Pipe and
Fittings”.
A. Pipe surround shall conform to the requirements of Section 31 2315 – “Trenching”, and
to the requirements of the specific pipe material specification.
A. GRP fabrication as listed below shall comply with the requirements of Section 06 6200.
1. Ladders and safety cages
2. Manhole benching, liner shafts
3. Wet well or chamber liners
4. Gratings
5. Sealing plates.
2.04 CONCRETE
A. Concrete and accessories shall comply with the relevant sections in Division 3 of these
specifications.
A. Concrete linings and protective coatings shall comply with the requirements of Section
09 9730
A. Pumps, valves, gates and appurtenances shall comply with the requirements found in
other Divisions of these Specifications.
A. Pipeline warning tape shall comply with the requirements of Section 31 2315.
A. Pipeline marker posts shall comply with the requirements of Section 31 2315.
PART 3 - EXECUTION
A. Trench excavation, pipe installation and backfill shall comply with Section 31 2315,
unless otherwise approved by the Engineer.
A. For the purposes of cleaning and inspection, the term gravity 'pipelines' includes those
laid in heading or by pipe- jacking or microtunneling or similar techniques.
B. The Contractor shall submit for approval, his proposed method for cleaning the gravity
pipeline. Such cleaning system shall not damage the pipeline in any way.
C. During and after construction the Contractor shall take reasonable measures, including
the provision of stoppers plugs and headwalls where appropriate, to prevent the ingress
of deleterious matter into pipelines.
D. After backfilling pipe trenches and completing manholes, chambers, hatch boxes etc.,
and before the trench surfaces are reinstated, the interior of pipelines shall be cleaned
of silt and debris by approved methods for inspection by the Engineer as follows: -
1. Pipelines of 800mm nominal internal diameter and smaller shall have a loose
plug passed through them to show that they are clear of obstruction and free
from deflection. For flexible pipelines the loose plug shall be dimensioned to
suit the permissible minimum deflected diameter of the pipe.
2. Pipelines greater than 800mm nominal internal diameter will, after
cleaning, be inspected from the inside and the Contractor shall
provide a suitable trolley, ventilation and safety equipment, and any other
plant and labour necessary for this purpose, if required by the Engineer.
3. All pipelines will be inspected again before commissioning or taking over
(whichever is sooner) and, if required by the Engineer, shall be cleaned again in
whole or in part. The final precommissioning inspection for pipelines with
nominal internal diameter of 1800mm or less shall be by CCTV camera with
KEO/19-3262-0000 33 3000/5 Sanitary Sewerage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
videocassette tape in accordance with Section 31 2315. The tape recordings
shall become the property of the Ministry. Pipelines with nominal internal
diameters greater than 1800mm shall be inspected at final precommissioning in
accordance with Item 2 (i.e. from inside by trolley).
A. During and after construction the Contractor shall take reasonable measures, including
the provision of stoppers, plugs and headwalls where appropriate, to prevent the ingress
of deleterious matter into pipelines.
B. The Contractor shall clean the interior of each pipe joint as it is laid and install temporary
closure pieces on the ends of the pipeline whenever work is stopped or disrupted to
keep the pipeline clean.
C. Pressure lines shall be flushed with water until all silt and sand is removed and the line
flows clean prior to hydrostatic pressure testing.
D. All pressure lines that will transport chlorinated water (potable, treated effluent, etc.)
shall be subjected to disinfection with chlorine in accordance with the applicable
AWWA standards and EPA rules and regulations.
A. For the purpose of inspection and testing, the term ‘pipelines’ includes those laid in
heading or by pipe-jacking or microtunneling, or similar techniques.
B. Prior to commencement of flushing or testing, approval shall be obtained to the quality
and methods of providing and disposing of all fluids used for flushing or testing purpose.
C. If permission is given to use new or existing pipelines or culverts which are not part of a
live system, they shall be thoroughly cleaned of all silt and any resulting damage made
good after use.
D. If lagoons for the storage of such fluids are permitted, they must be suitably protected
with fencing and attended by day and night to prevent access by the general public and
will not be sited adjacent to buildings. Approved means of preventing the formation of
mosquito larvae on the surface of the lagoons will be employed.
E. Testing of pipelines shall in all cases be carried out in the presence of the engineer. the
Contractor shall provide complete plant an all struts, thrust blocks, etc., as may be
necessary for effectively testing the pipelines to the specified pressures.
F. For both gravity and pressure pipelines, only testing of new or replaced sections of
pipelines and fittings will be required under the Contract, in accordance with this
Specification, unless detailed otherwise. Such testing will be carried out before making
final connections to the existing network. However, where tees or other fittings
are inserted into existing pipelines, and where lengths of pipeline are replaced, no
backfilling will be allowed at the tees or fittings or at the joints between new and existing
pipework until the pipeline has been returned to service and a visual inspection of all
such fittings and joints made with the network under pressure.
G. Should any inspection be unsatisfactory or any test fail, the Contractor shall
replace defective pipes, leaking joints or otherwise re-execute defective work as
instructed, following which, cleaning and testing will be repeated until the
Engineer certifies the pipeline to be satisfactory.
J. Deflection Testing
1. All flexible pipelines (HDPE, uPVC, etc) shall be subjected to deflection tests at
site, as detailed herein and in the particular pipe specification of these
documents.
a. The above requirement shall not apply to pipes 100mm dia. and smaller.
4. Pipe surround shall be removed from all sections of pipe failing to meet the
specified deflection criteria.
a. Undamaged pipes may be rebackfilled and tested again.
b. All action taken to correct the pipe deflection shall be at the Contractor’s
expense.
c. Relaid sections shall be tested in accordance with item number 3 above.
5. If the permanent set or deflection, after removal of pipe surround, exceeds the
limits set out above, the pipes shall be deemed to be damaged and will
therefore be rejected.
a. Pipes so rejected shall be indelibly marked, removed from the site and
replaced at the Contractor's expense.
A. All non-pressure (gravity) pipelines of 800mm nominal internal diameter and smaller
shall be given a preliminary test when the pipeline is bedded and jointed but before
backfilling and a final test after backfilling. Unless otherwise instructed, non-pressure
pipelines shall be tested in sections between manholes. In addition, pipelines shown as
straight lines on the Project Drawings shall be subjected to a light test between
manholes to verify alignment.
1. Preliminary test for pipelines with 800mm internal diameter or less:
a. Air shall be pumped into the pipeline until a pressure of l00mm head of
water is indicated on a water manometer and the pressure shall not fall to
less than 75mm during a period of 5 minutes.
b. The Contractor will not be permitted to commence testing later than 4
hours after sunrise or earlier than 4 hours before sunset during the
summer period unless otherwise directed by the Engineer.
B. All non-pressure (gravity) pipelines larger than 800mm nominal internal diameter shall
be internally inspected, pressure tested and also tested for infiltration when laid below
the ground water table. Internal inspection shall be in accordance with Article 3.02.
1. The Contractor shall, carry out tests on every joint by means of an approved joint
testing apparatus or by hydrostatically testing the pipeline. Test pressures shall
be in accordance with item ‘C’ below.
a. The part of the pipeline under test shall be filled with water under
pressure to meet the requirements of Item ‘C’ below.
b. The test pressure shall be sustained for a period of 30 minutes and the
volume of water required to maintain the test pressure shall be
determined in an approved manner. The test will not be considered
satisfactory if the rate of loss of water from a full pipeline exceeds 1 litre
per hour per metre of diameter per 30 metres of length of pipeline under
test.
2. For any joint of a pipeline that fails this test additional joint sealing will be
required to be carried out by approved resin/gel/grout injection techniques at
the Contractor's cost.
3. The Contractor shall repair any joint with visible leakage.
D.Infiltration Test:
1. The measured infiltration shall not exceed 1 litre per hour per metre diameter per
30 metres of length of pipeline under test.
a. Pipes 600mm and larger, and smaller sizes if directed by the Engineer,
laid below the groundwater table shall be subjected to an infiltration test.
b. The infiltration test shall be conducted after dewatering activities have
been suspended for at least 7 days.
c. The Contractor shall include in his method statement complete details
for the measurement of any infiltration
d. For any pipeline that fails the infiltration test the Contractor must
propose measures to remedy the situation and execute such measures
at his own cost to achieve compliance with this requirement.
2. For any joint of a pipeline with nominal internal diameter 600mm and greater,
which fails this test additional joint sealing will be required to be carried out by
approved resin/gel/grout injection techniques at the Contractor's cost.
E. Final Inspection:
1. After backfilling and prior to commissioning, all pipelines shall be inspected by
CCTV camera and a video recording taken of the survey.
KEO/19-3262-0000 33 3000/9 Sanitary Sewerage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
2. The Contractor shall prepare a report of the pipelines in an approved format to
the satisfaction of the Engineer. Both the report and the video recording shall
become the property of the MPW.
A. CCTV surveys shall be carried out on all gravity pipelines after backfilling in accordance
with specification Section 31 2315.
B. All pipelines shall be inspected by CCTV camera with a video recording taken of
the survey after backfilling and prior to commissioning in accordance with Section 31
2315.
C. The Contractor shall prepare a report of the pipelines in an approved format to the
satisfaction of the Engineer. Both the report and the video recording shall become the
property of the MPW.
D. The Contractor shall repair all defects discovered by the CCTV inspection at no cost to
the Ministry. The line segments so repaired shall be re-inspected by CCTV.
A. All pressure mains shall be tested in sections not exceeding 1000 metres in length.
1. Each pipeline or section thereof shall be filled with water and all air removed as
far as possible.
2. The pressure shall be raised by pumping until the test pressure is reached and
the pressure shall be maintained at this pressure by further pumping until it is
steady
3. Pumping shall be stopped and the time taken for the observed pressure to fall by
one metre shall be recorded.
4. Pumping shall then be resumed and the quantity of water pumped in order to
restore the test pressure shall be recorded and pumping stopped.
5. The test shall be held at pressure for 2 hours without pumping and if the pressure
does not fall by more than 1 metre the pumping shall be resumed and the
quantity of water pumped in order to restore the test pressure shall be recorded
and the pumping stopped and the time recorded as 2 hours.
6. The rate of loss shall be calculated as the recorded quantity divided by the
recorded time of 2 hours.
7. Pressure testing against valves:
a. The Contractor should note that since valves cannot be guaranteed
to be perfectly driptight, testing against closed valves connected to
existing or operating systems shall not be permitted. Testing against
other closed valves (including air valves) not so connected may be
attempted if designed provided the valves are suitably anchored against
thrust.
b. Testing against valve chambers or other structures is prohibited.
c. No claims will be entertained on account of leaking valves, or any other
difficulties encountered, including the isolation of certain lengths of
pipework for testing.
8. The Contractor shall install air release cocks at all high points if not equipped
with air release valves at no cost to the Ministry if required to release trapped air
in order to pass the test.
9. The test pressure shall be such that the entire pipeline or section being
tested is subjected to 1.5 times the working pressure. When the pipeline is
connected to a pump and can be subjected to the pumps shutoff head
C. In addition to any tests of individual joints or other interim tests, which may be, specified
elsewhere, the Contractor shall submit all parts of the pipelines after all sections have
been joined to a final hydrostatic test at operating pressure.
1. The test shall be conducted as required for the individual sections except that the
test pressure shall be set at the actual operating pressure.
A. After interim testing has been satisfactorily completed, all pressure lines shall be given a
final pressure test to be carried out on the entire length of the pipeline, after all sections
have been joined together.
B. Final pipeline test pressures and procedures shall be conducted as described
under interim pressure testing.
A. General
1. Unless noted otherwise, manholes shall be constructed on gravity sewers:
a. At each change of gradient or direction.
b. At each change in diameter.
c. At each intersection with other pipes.
d. At such other points as shown on the Drawings.
e. As directed by the Engineer.
2. Concrete work shall not begin until the pipe fittings to be cast into the manhole
walls, are on site. No "box outs" will be allowed, unless approved by the
Engineer.
a. Thereafter the manhole shall be cast, water-proofed and backfilled as
quickly as possible.
3. Channel inverts shall be accurately laid to meet pipe invert elevations.
4. Channel bends in the benching are to be as "slow" as possible, by
setting the manholes "off-center" at changes in direction.
5. All pipelines adjoining structures (i.e. at entries and exits to manholes) shall have
a flexible joint adjacent to each structure, as detailed on the drawings.
6. Unless noted otherwise, all sewage manholes shall have protective GRP
lining, benching and tops, conforming to Section 06 6200 "Glass
Reinforced Plastic Fabrications".
7. Benching shall be formed with in-situ C40/20 mass concrete with exposed
finish, protected by 12mm thick chemically resistant (epoxy) mortar to finished
levels.
8. Unless otherwise noted, all exterior surfaces below grade shall be covered
with waterproof membrane, in accordance with Section 07 1300.
9. Unless noted otherwise, all exterior exposed concrete surfaces shall be epoxy
coated according to Section 09 9730.
10. Manhole covers in traffic areas shall be set to the paved area profile and be flush
with the paved area surface.
11. Manhole covers located in non-traffic areas shall be set to an elevation as
shown on the drawings, or as directed by the Engineer.
12. Unless otherwise noted, all manhole covers exposed to sewage or sewage
gases shall incorporate a push fit GRP sealing plate.
13. Unless noted otherwise, hand railing shall be stainless steel Type 316.
a. All safety chains, fixing bolts and other hardware shall be stainless steel
Type 316.
b. Safety chains shall be 8mm nominal size, unless noted otherwise.
14. Where drop manholes are indicated they shall be as shown on the
Drawings and shall be formed where the upstream length of sewer enters a
manhole at a level 1 metre or greater above the manhole invert level.
15. All manholes shall be watertight on completion.
16. Manholes shall be tested in accordance with the requirements of this clause.
17. The Contractor shall take all measures, deemed necessary by the
Engineer, to ensure that manholes are not left in a flooded or unprotected
condition.
D. Manholes manufactured from Polymer Concrete shall meet the following minimum
standards and full details shall be submitted for review and approval by the Engineer.
1. All resin shall be vinylester.
2. Manhole structure shall have sufficient weight to prevent floatation.
E. Manhole covers shall be non-vented except for 10 percent of the total number. The 10
percent shall be vented and supplied with activated carbon filter baskets. The vented
units shall be installed where shown on the Project Drawings or as directed by
the Engineer.
A. General
1. For any pressure mains within the system, valve chambers and/or junction
chambers shall be constructed at each intersection with other pipes and at
other points as shown on the Drawings.
2. Concrete work shall not begin until the pipe fittings to be cast into the chamber
walls are on site.
a. Thereafter the chamber shall be cast, water-proofed and backfilled as
quickly as possible.
b. No. "box outs" will be allowed.
1. All pipes cast into chamber walls shall be fitted with a temporary
internal "jig" to ensure that proper alignment and flange orientation
is maintained between all interconnecting pipes and fittings during
casting
a. Jigs may be made from uPVC pipes, HDPE pipes or steel
tubing.
3. Short lengths of pipe with flexible joints shall be provided at entry and exit to all
chambers.
4. Unless otherwise shown on the drawings, all exterior surfaces below grade shall be
covered with waterproof membrane, in accordance with Section 07 1300.
5. Unless otherwise noted, all interior and exterior exposed surfaces shall be epoxy
coated according to Section 09 9730.
6. Manhole covers in traffic areas shall be set to the paved area profile and be flush with
the paved area surface.
7. Manhole covers located in non-traffic areas shall be set to an elevation as shown on the
drawings, or as directed by the Engineer.
8. Hand railing, if shown on the drawings shall be aluminium.
a. All fixing bolts and other hardware shall be stainless steel Type 316.
KEO/19-3262-0000 33 3000/14 Sanitary Sewerage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
9. Safety chains and other hardware as required shall be stainless steel Type 316.
a. Size shall be 8mm, unless noted otherwise.
10. All chambers shall be watertight on completion.
a. No testing for leakage of water into chambers shall be conducted, unless in the
opinion of the Engineer, it is deemed necessary.
11. The Contractor shall take all measures, deemed necessary by the Engineer, to
ensure that chambers are not left in a flooded or unprotected condition.
a. If the designated covers are not on site after placing the cover slab, a temporary
plywood cover shall be securely fitted in all openings.
A. The Contractor shall test 10 percent of all manholes, to be selected at random by the
Engineer.
B. Manholes shall be hydrostatically tested to at least one metre above the crown of the
highest connection into the manhole being tested.
C. The selected manholes shall be tested for watertightness. Each manhole shall be filled
with clean water to the test level and shall stand for a period of three days, to allow for
absorption. The structure shall be considered satisfactory if, subsequent to this period,
there shall be no fall in level over a period of 24 hours (after making due allowance for
rainfall and evaporation) and no visible leaks.
D. Should a manhole fail to pass it shall be repaired and retested. If more than 2 percent
of the total manholes fail the Contractor shall submit to the Engineer for his
approval a proposal to correct the situation.
E. All cost associated with testing and repairs shall be of the Contractor's expense.
A. For pressure mains, the Contractor shall construct thrust blocks at all
unrestrained changes in pipe direction greater than seven degrees as well as at
all tee and "Y" connections and/or at locations as shown on the drawings.
1. Thrust blocks shall be constructed to the dimensions shown on the Drawings,
unless otherwise approved by the Engineer.
2. Thrust blocks are designed for the soil parameters designated in the applicable
soil report.
a. If actual ground conditions differ from the soil reports, the Engineer
shall be notified.
b. Where actual ground conditions do not meet anticipated soil
conditions, the Engineer may redesign the thrust block.
c. Where considerably better ground conditions, such as rock, are
encountered, the dimensions of a particular thrust block may be
reduced, with the Engineer’s approval.
d. Supporting calculations for any reduced size thrust blocks must be
submitted to the Engineer at least 72 hours before construction of that
particular thrust block commences.
3. Unless otherwise specified or directed, thrust blocks shall be provided on
pipelines laid to gradients steeper than 1:20.
a. Up to 1:15 every third pipe.
b. Up to 1:10 every second pipe.
c. At 1:5 every pipe shall be anchored.
4. Concrete shall extend to undisturbed ground on thrust faces (of thrust blocks) and on
both faces of anchor blocks.
5. Each thrust block shall be designed to have a sufficient bearing area and shall be
placed to transmit safely the unbalanced force to the surrounding area.
KEO/19-3262-0000 33 3000/15 Sanitary Sewerage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
6. Thrust blocks shall be cast-in-place (Grade C40 concrete) between the pipe fitting
and the trench wall or trench bottom, as the case may be.
7. Bearing faces of the block shall be placed against freshly cut, undisturbed sound
material.
8. If the thrust exceeds the bearing value of the surrounding soil, the soil may be
precompacted, with the Engineer’s approval, before placing concrete.
9. All concrete shall be kept behind the sockets and flanges of fittings.
10. Formwork may be constructed, with the approval of the Engineer, wherever
necessary to confine the concrete to the prescribed dimensions for the thrust block.
a. All formwork timber shall be removed before testing.
11. Thrust blocks shall, unless otherwise shown, or directed by the Engineer, be so
placed that the pipes, fittings and joints will be accessible for repair.
A. At the locations shown on the Drawing, or directed by the Engineer, the Contractor shall
connect the new pipelines to the existing pipelines or structures, but not until the new
works have passed the final tests.
B. Existing mains and service pipes shall only be cut using special equipment approved by
the Engineer.
1. Cuts shall be perpendicular to the centre line of the pipe and special care shall
be taken with respect to the location of the cut, to ensure that the new pipework
shown on the Drawings may be installed.
2. The Contractor shall agree with the Engineer, the exact length of existing
pipework to be removed.
C. The Contractor shall take every precaution to prevent any dirt or extraneous material
from entering the existing main or service pipe.
D. The Contractor shall have available, at the connection site, sufficient dewatering pumps
to keep the excavation dry at all times.
1. Work shall be carried out in a clean and efficient manner.
2. The Client may put the interconnection into use as soon as possible after
its installation and will carry out an inspection to detect any evidence of leakage.
a. Any remedial work necessary to eliminate leakage shall be carried
out by the Contractor.
b. No pipework shall be covered or backfilled until the Engineer is totally
satisfied that the interconnection is free of all leakage.
A. The Contractor shall maintain sewage flow arising from any source.
1. The Contractor shall submit his proposed method of overpumping or flow
diversion to the Engineer for approval, prior to the start of construction.
2. The proposed method shall include proposed alignments and design
requirements of the discharge to the terminal point.
B. Contractor shall furnish, install and operate pumps, plugs, conduits and other equipment
required to divert flow around the pipe segment upon which work is to be performed.
1. Sewage shall not be allowed to flow into gutters, streets, or over sidewalks.
2. After the work has been completed, tested and accepted by the Engineer, flow
shall be restored to normal.
C. Pipe Stoppers
E. Pumping Equipment
Overpumping shall be carried out from one manhole to another located downstream.
1. Pumping system shall be of sufficient capacity to handle peak existing flow.
2. Pumping shall be done by the Contractor in such a manner that no damage to
public or private property results and no nuisance or public health problem is
created.
3. Pumped sewage shall be in an enclosed hose or pipe that is free of all leaks and
shall be re-inserted into the sewage system.
4. The Contractor shall verify the peak average flows ahead of time and shall
design his pumping system accordingly.
a. The Contractor shall submit his design for the Engineer's approval.
END OF SECTION
PART 1 - GENERAL
1.01 SUMMARY
A. This section specifies the manufacture, installation and testing of HDPE gravity sewer
pipe and fittings.
1. Additional installation and field testing requirements will be found in the related
sections listed below.
1.02 DEFINITION
A. The following definitions shall pertain to words or phases as utilised in this Section.
1. HDPE shall mean High Density Polyethylene
2. Profile wall shall mean a pipe wall construction that presents an essentially
smooth surface in the waterway but includes ribs or other shapes, which can
be either solid or hollow that help brace the pipe against diametrical
deformation.
A. Related Section: Related work to be coordinated and used in conjunction with this
specification includes but is not restricted to:
1. Section 01 3300 - Submittal Procedures
2. Section 01 4000 - Quality Requirements
3. Section 31 2300 - Excavation and Fill
4. Section 31 2315 - Trenching
5. Section 33 3000 - Sanitary Sewerage Utilities
6. Section 33 3913 - Sanitary Utility Sewerage Manholes, Frames, and
Covers
1.04 REFERENCES
A. Product manufacture, testing and installation shall comply with the following
references, unless otherwise stated in the specifications or unless otherwise approved
by the Engineer.
1. ASTM D2321 Standard Practice for Installation of Thermoplastic Pipe for
Sewers and Other Gravity-Flow Applications.
2. ASTM D2837-98A Standard Test Method for Obtaining Hydrostatic Design
Basis for Thermoplastic Pipe Materials.
3. ASTM D3350 Standard Specification for Polyethylene Plastic Pipe and
Fittings Materials
4. ASTM F 894-95 Standard Specification for Polethylene (PE) Large
Diameter Profile Wall Sewer and Drain Pipe
5. ASTM D3350-99 Standard Specifications for Polyethylene Plastics Pipe and
Fittings Materials
B. HDPE pipes shall be installed by open cut methods only except when the plans
specifically detail insertion into an existing sewer.
A. Pipes
1. HDPE Gravity Sewer Pipes may be Solid Wall or Profile Wall.
2. Contractor shall submit calculations covering the soil pressure on the buried
pipe and restraint of expansion or contraction. Restraint anchors shall be
provided if required. Manholes may be regarded as such restraint blocks,
provided that they can be shown to provide the necessary resistance.
3. Where pressure pipe is designated for non-pressure applications, the minimum
SDR shall be supplied and manufacturing shall conform to the designated
pressure class, unless otherwise approved by the Engineer.
4. Pipes shall be suitable for sustained operating temperatures of up to 45°C.
5. Pipe lengths shall be in accordance with the manufacturers recommendations
as approved by the Engineer.
6. When pipe lengths greater than 6 m are supplied the socket depths shall be
greater than Amin specified in EN 13476-1 Table 6.
7. The Contractor shall provide the proper equipment and slings necessary to
handle the length of pipe being used.
8. Pipe bedding and pipe surround shall be as indicated on the Project Drawings
and Section 31 2315 of these specifications.
B. Joints
1. All joints shall be spigot and socket type with flexible elastomeric sealing rings.
a. Welded joints may not be used under any circumstances.
2. All elastomeric joint seals (rubber gaskets) shall be obtained from the pipe
manufacturer.
3. All joints shall be capable of withstanding a minimum external pressure of 50
Kpa without infiltration as per DIN 16961-2, in both the straight and misaligned
positions.
C. Special Fittings
1. All special fittings, even if manufactured elsewhere, shall be obtained from the
pipe manufacturer, unless approved otherwise by the Engineer.
2. Pipe system shall include double socket type HDPE couplings using
elastomeric joint seals that can be utilised anywhere along the barrel of the
pipe.
1.06 SUBMITTALS
A. All pipes and fittings shall be submitted for approval according to Section 01 3300.
B. Different sizes and types of pipes and fittings, even if from the same manufacturer,
shall be placed in separate submittals.
C. The manufacturer shall provide proof of successful past use of the proposed pipes
and fittings on work of a similar environment and scope to that for this Project.
D. As a minimum, the submittal shall include the following:
1. The Contractor shall develop and submit a Method Statement according to
Section 01 4000 - “Quality Requirements”, to cover all aspects of installation
of HDPE Pipes and Fittings
a. Product Data: Manufacturer’s Specifications and Installation
instructions. Test results that show compliance with the Contract
Documents.
b. Method Statement: Method Statement shall include details on
connection of pipe to manhole lining material to insure protection of
concrete on lined concrete manholes.
c. Shop Drawings: Detailed drawings shall be submitted to the Engineer
for approval. These shall show all relevant details including:
i. Connections at manholes
ii. Joining to existing mains
iii. Couplings and Thrust Blocks
iv. Stanks
v. Joint details
vi. The Contractor shall furnish the Engineer with samples of the
proposed connection between the pipe and manhole lining
when used with lined concrete manholes and provide testing
as required by the Engineer.
d. Samples:
i. One sample of each type
A. Prior to dispatch from the factory, the Contractor shall notify the Engineer in
sufficient time to allow the Engineer, or his representative, to inspect the pipes and
fittings, if so desired.
1. All notifications shall be made by written Inspection Requests, in accordance
with Section 01 4000.
a. An advance copy may be faxed to the Engineer’s office, but the original
must arrive before the scheduled day of inspection.
2. Minimum notification times shall be as follows:
a. 24 hours on site
b. 72 hours for areas within Kuwait
c. 3 weeks outside of Kuwait
KEO/19-3262-0000 33 3102/3 HDPE Gravity Sewer Pipe And Fittings
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
1.08 DELIVERY, STORAGE AND HANDLING
A. Pipes, fittings and specials shall be delivered, handled and stored according to
the manufacturer’s recommendations along with the following provisions:
1. Transportation, handling and storage shall at all times be performed in a manner
to avoid product damage.
2. Only nylon slings shall be allowed for lifting pipes and fittings. Steel chains,
clamps or cables shall not be allowed for lifting purposes.
a. Nylon slings shall be used for securing pipes during transport and storage.
b. Pipes shall be unloaded from trucks by crane. Under no
circumstances shall pipes be tipped onto the ground.
3. Do not store pipes on rough or rocky ground.
4. Pipes shall be stored under a shade, in such a manner as to allow air to circulate
freely among the pipes and thereby avoid excessive build up of heat in the pipes.
5. Visually inspect all pipes upon delivery and report any damage to the Engineer.
a. Any pipes damaged during delivery, storage or installation shall be
marked and set aside.
b. Proposals for repair of any damaged pipes shall be submitted in writing to
the Engineer for approval.
c. No repairs to damaged pipes shall be attempted without the Engineer’s
approval.
d. Any damaged pipes deemed unsuitable for repair by the Engineer
shall be removed from site and replaced at the Contractors expense.
6. Elastomeric sealing rings (rubber gaskets) shall be stored in closed containers,
out of direct sunlight, until needed.
PART 2 - PRODUCTS
A. HDPE pipes shall be manufactured in metric sizes according to the relevant ISO
standards.
B. HDPE pipes shall be manufactured in accordance with the requirements of EN 13476-
1
C. HDPE pipes shall have a minimum Ring Stiffness of 8KN/m2 as tested per ISO 9969.
D. Elastomeric sealing rings (rubber gaskets) shall be made from EPDM.
E. Pipe sizes shall be as shown on the drawings, unless otherwise approved by the
Engineer.
1. The designated sizes on the drawings refer to nominal external diameters for
Solid Wall Pipes and internal diameter for profile wall pipes.
F. Gravity sewer pipes shall meet the following SDR requirements. 'SDR' is the Standard
Dimension Ratio, which is defined as the ratio of pipe diameter (measured at midpoint
of wall) to pipe wall thickness.
1. Solid Wall Pipes shall have a SDR of 18 or better.
2. Profile Wall Pipes shall have an effective SDR of 18 or better.
3. Profile Wall Pipes shall meet the following requirements in addition to the
specified SDR.
a. The tensile strength of the seam on spirally wound pipe shall be
measured in accordance with EN 13476-1 Table 15.
b. The minimum waterway thickness shall be equal to or greater e5
specified in Table 6 of EN 13476-1.
A. The base resin shall have a cell classification according to ASTM D 3350 for pipes
and injection molded fittings as follows. The selected resin shall also be capable of
meeting all other requirements within this specification. Compounds that have a
higher cell classification in one or more properties shall be acceptable provided the
other product requirements are met.
B. The resin shall also meet the following requirements. The test shall be carried out in
the form of a solid wall pipe made from the relevant extrusion.
B. Pipe shall be tested for ‘Resistance to Water Jetting’ in accordance with WIS 4-35-01
as detailed in Article 6.10 and Appendix C.
1. The test shall be modified such that the minimum test pressure shall be 180 Bar.
C. Pipe shall be tested for ‘Resistance to Longitudinal Bending’ in accordance with WIS
4-35-01 as detailed in Article 6.11 and Appendix D.
2.05 CONCRETE
A. Concrete and accessories shall comply with the relevant sections in Division 03 of
these specifications.
PART 3 - EXECUTION
* Numbers shown are the average of the vertical and horizontal deflections
individual measurements of either the vertical or horizontal diameter may
show deflections, by comparison to the reference diameter, of four times the
value listed above.
The mandrel shall have a cylindrical cross section, with a diameter not smaller
than 1mm less than the minimum acceptable pipe diameter, given in the table
above.
Notes:
1. Pipes whose deflection at any time has exceeded this value will not be
accepted for incorporation into the work. This test may utilise a mandrel and
shall be carried out not less than 1 year after completion of backfilling, but prior
to expiry of guarantee period.
2. The Contractor should note that 10 percent of the total installed cost
(pipe, bedding, backfill and testing) shall be withheld until completion of testing
of flexible pipe.
3. To be measured after placing of the surround material, and after
withdrawal of trench sheeting to above the crown of the pipe, but before
backfilling. For non-pressure pipes, the permissible percentage deflection
will be accepted only as an elongation of the vertical diameter, and no
reduction will be acceptable at this stage.
KEO/19-3262-0000 33 3102/7 HDPE Gravity Sewer Pipe And Fittings
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4. To be measured not less than four weeks after completion of backfilling.
5. The Contractor's attention is drawn to all applicable parts of Section 33 3000 -
"Sanitary Sewerage Utilities" for details of required tests.
END OF SECTION
PART 1 - GENERAL
1.01 SUMMARY
A. Storm water surface drainage system is designed to collect, carry away and dispose off
the following:
1. Rain water discharge on the roofs and floors of buildings.
2. Rain water discharge on promenades, car parking areas and streets.
3. Sub-soil drainage from sand pits and planters.
B. This section specifies installation and testing for Storm Water Drainage and includes,
but is not limited to, the following:
1. Gullies, Drain Trenches and Manholes
2. Storm Water Drainage Lines
3. Cast iron accessories like Covers, Frames, Step Irons etc.
4. Storm Water Out-falls
C. For trench excavation, pipe installation, and backfill see Section 31 2315
1.03 REFERENCES
A. Product manufacture, testing and installation shall comply with the following
KEO/19-3262-0000 33 4000/1 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
references, unless otherwise stated in the specifications, or unless otherwise
approved by the Engineer.
1. DIN 807 - 4HD PE pipes; dimensions
2. DIN 8075 - HDPE pipes; general quality requirements
3. DIN 19535 - HDPE pipes and fittings for hot water resistant waste
and soil installations within buildings (ISO 8770 / 8772)
4. DIN 19537 - HDPE pipes and fittings for drainage and sewerage
5. BS 8500-1 - Concrete. Method o f specifying and guidance for
the specifier
6. BS 8500-2 - Concrete. Specification for constituent materials and
concrete
7. BS EN 206-1 - Concrete. Specification, performance, production and
conformity
8. BS 5911 - Pre-cast Concrete Pipes, Fittings and Ancillary
Products
9. BS 5911 Part 2 - Specification for Inspection Chambers and Street
Gullies
10. BS 5911 Part 100 - Specification for non-reinforced and reinforced pipes
and fittings with flexible joints
11. BS EN 681 - Elastomeric seals. Material requirements for pipe joint
seals used in water and drainage applications.
Vulcanized rubber.
12. BS EN 124 - Gully tops and manhole tops for vehicular and
Pedestrian areas. Design requirements, type testing,
marking, quality control
13. BS EN ISO 1461 - Hot dip galvanized coatings on fabricated iron and
steel articles. Specifications and test methods
14. BS EN 13101 - Steps for underground man entry chambers.
Requirements, marking, testing and evaluation of
conformity
15. BS EN 1561 - Founding. Grey cast irons
16. BS 5493 - Code of Practice for protective coating of Iron and
Steel Structures against Corrosion
17. BS 3416 - Black B i t u m e n C o a t i n g S o l u t i o n s f o r Cold
Application (AASHTO M 115: Asphalt for Damp-
proofing and Water-proofing)
18. AASHTO T 180 -Moisture Density Relations of Soils using 10 lbs (4.54
kgs) Rammer
19. ASTM D2321 -Standard Practice for Installation of Thermo Plastic Pipes
for Sewers and other Gravity Flow Applications
1.04 DEFINITIONS
A. The following definitions shall pertain to words or phrases as utilised in this section.
1. "uPVC" shall mean unplasticised polyvinyl chloride.
2. "HDPE" shall mean high density polyethylene.
3. "RCP" shall mean reinforced concrete pipe.
4. "DI" shall mean ductile iron.
5. "Pipe Surround" shall mean that material directly below, around and above the
pipe.
KEO/19-3262-0000 33 4000/2 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
6. "Formation" shall mean the bottom of the trench excavation, or in some cases, fill
just below the pipe surround.
7. "Stanks" shall mean barriers to flowing water within granular pipe surround
material.
A. The Contractor shall provide all labour, materials and equipment necessary for
providing a complete operating system.
B. Responsibility for the safety and soundness of all material shall rest with the Contractor.
C. Contractor is advised to carry out any tests (at his cost) needed to satisfy
himself regarding the soundness of the pipes, fittings and jointing materials prior to
acceptance testing by the Engineer.
D. Pipe materials to be utilised shall be as shown on the Project Drawings, or as described
in the particular and general specifications.
E. Each type of pipe and fittings shall be furnished by a single manufacturer,
unless otherwise accepted by the Engineer.
1.06 SUBMITTALS
A. Product Approval
1. The Contractor shall submit sufficient information to the Engineer, prior to
purchase according to Section 01 3300, in order to verify compliance with the
specifications. Such information shall include at least the following:
a. Manufacturers name
b. Suppliers name
c. Product name (if applicable)
d. Product description
e. Manufacturers technical data
f. Storage instructions
g. Installation instructions
B. Material samples shall be submitted as required in the relevant sections within these
specifications, or as requested by the Engineer.
C. Method Statements
1. The Contractor shall provide method statements meeting the requirements of
Section 01 4000, for at least the following activities, or as requested by the
Engineer.
a. Pipe testing.
b. Manhole and chamber construction.
c. Pipe installation including backfill compaction methods for flexible (uPVC
and HDPE) pipes.
D. Shop Drawings
1. The Contractor shall submit shop drawings according to Section 01 3300
including:
a. Manufacturers printed brochures and catalogues (one original and three
copies) with relevant information highlighted (or irrelevant information
struck out), along with write up of selection criteria
KEO/19-3262-0000 33 4000/3 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
b. General piping layout drawings to a scale not smaller than 1:1000
c. Detailed piping layout plans to a scale of 1: 250 along with profiles
d. Builders work plans to a scale of 1:100 / 1:50 as required
e. Installation details of:
• Manholes, interceptors, sleeves and penetrations etc. to a scale of
1:50
• Manhole covers and items of similar nature to a scale of 1:10
f. Calculations / details to substantiate the shop drawings
E. Project record documents and As-built Drawings of all works installed under this section
shall be submitted in accordance with the General Conditions of Contract.
A. Prior to dispatch from the factory, the Contractor shall notify the Engineer, in
KEO/19-3262-0000 33 4000/4 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
sufficient time to allow the Engineer or his representatives to inspect and test the
products, if so desired.
1. All notifications shall be made by written "Inspection Requests" in accordance
with Section 01 4000 - "Quality Requirements".
a. An advance copy may be faxed to the Engineers office, but the original
must arrive before the scheduled day of inspection.
B. "Inspection Requests" for at least the following items, shall be submitted to the Engineer
during the on-site installation work, prior to proceeding with the following
activities. Minimum notification time shall be 24 hours.
1. Pipe testing.
2. Backfilling.
3. Reinforcing Steel for Cast-in-Situ Concrete.
4. Formwork for Cast-in-Situ Concrete.
5. Placing of Cast-in-Situ Concrete
A. General requirements for delivery, storage and handling of products and materials shall
be as specified in Section 01 6000 - "Product Requirements".
B. Specific requirements shall be as specified in the relevant specification section
governing the manufacture and installation of the material or product in question.
C. Additional requirements may be required as per the manufactures
recommendations and/or the directives of the Engineer.
D. Products shall be delivered, handled and stored according to the
manufacturer’s recommendations along with the following provisions:
1. Transportation, handling and storage shall at all times be performed in a manner
to avoid product damage.
2. Only nylon slings shall be allowed for lifting products. Steel chains, clamps or
cables shall not be allowed for lifting purposes, unless approved by the Engineer.
a. Steel chains or cables may be allowed for securing products during
transport or storage, provided protective padding or timber blocking is
utilised.
A. Where temporary road closures, road diversions or construction detours are required,
the Contractor shall:
1. Execute the work at the time when the traffic is least congested. If, in the opinion
of the Engineer, the work may result in unacceptable inconvenience to traffic, the
work shall be carried out during the night time.
2. Carry ou t his various activities at such times and in such a manner
that no disturbance is caused to the public.
3. Provide safe pathways not less than 1.20 m wide for pedestrians and traffic lanes
not less than 3.5 m wide for vehicles, and control traffic by means of traffic
signals or by other means wherever required as approved by the Engineer.
4. Provide in all cases, fencing, signs, light signals, floodlights, and watchmen to
ensure that no mishaps will befall the public or properties in locations.
5. Reinstate to original condition and make good without delay.
A. The Contractor shall maintain a continuous record of all field deviations from
the Drawings, if any, as approved by the Engineer. At the completion of the
Contract, the Contractor shall submit to the Engineer a set of the latest revisions
of all plans and specifications marked to show the works "as built". A set shall
include 2 prints of all drawings together with the originals.
B. The Contractor shall prepare As built drawings of the work as
constructed/renovated including preparation of schedules, giving details such as
pipe diameters, and invert levels, all to be presented in a form approved by the
Engineer.
A. The Contractor shall refer to and comply with the current regulations and specifications
of the service authorities before commencing any work adjacent to other utilities.
This requirement will not relieve the Contractor of responsibility for taking every
precaution to avoid damage to these utilities and he shall be held responsible for the
cost of repair of all damage and other liability claims in accordance with the Conditions
of Contract and the Specification.
A. The Contractor shall not deposit the earth obtained from excavation and/or store up
or deploy equipment, tools and plant necessary in locations that will affect the safety of
the public, public services, or properties and/or in such a way that impedes
traffic to pedestrians and any other works or public authorities or private concerns.
B. The Contractor will be held responsible for the sufficiency of his safety measures and
will be liable for keeping the Works safe at all times.
C. Nuisance from noise and dust:
1. The Contractor shall take all precautions, which, in the opinion of the Engineer,
are necessary to minimize nuisance arising from noise and dust when
working in the vicinity of residences, lecture halls and offices. All engine-driven
machines shall be fitted with efficient silencers, which are not necessarily
those supplied by the manufacturers of the engines or plant, and if
necessary, plant shall be screened with acoustic materials. If, in the
opinion of the Engineer, it is unreasonable or undesirable for pumps, or
concrete mixers to be driven by combustion engines, the Contractor shall,
when so required, provide electric motors to operate the plant.
2. Compressed air operated road breakers, tools, and ventilation equipment
shall be effectively muffled or shall be of a design having a low noise frequency.
3. The Contractor shall utilize submersible pumping plant, which is electrically
powered so as to avoid any nuisance or disturbance to the general public. The
pumping plant may be supplied with power from a diesel engine
generator which shall be acoustically insulated so that the emitted noise
level shall not exceed 65 dBA measured at a distance of 3m from the
equipment. The Engineer shall approve all the noise level near houses, and
sound installation procedures to keep the noise nuisance to the minimum.
A. The Contractor shall keep the constructions site neat and clean to the satisfaction of the
Engineer by daily removal of unwanted material arising from demolished pipes
and manholes, sewer cleaning, and excavations, rubbish, temporary installations,
and daily cleaning to remove windblown sand and other debris. All debris shall be
removed from the site to a public disposal location approved by the Municipality. The
disposal location may be at any distance from the project site, and may be changed
by the municipality during the time of construction. The Contractor shall determine any
requirements for the disposal of construction material at the approved location. The
Contractor shall allow for this in his rates.
B. Upon final completion of the Works, the Contractor shall clear away and remove from
the site all remaining constructional plant, surplus materials, rubbish, and temporary
works of every kind and leave the whole of the site clean to the satisfaction of the
Engineer.
C. The Contractor shall pump out underground water and/or percolating water that
is encountered in the excavations and dispose of such water to places indicated by
KEO/19-3262-0000 33 4000/7 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
the Engineer. The Engineer may allow the disposal of such water in rainwater
gullies providing there is no technical hindrance. The Contractor shall not dispose of
water into sewer pipes, roads, private property, or open areas such as parks or
undeveloped lots.
D. The Contractor shall provide all treatment units, power, chemicals and labor required to
remove hydrogen sulfide from pumped out water prior to discharge. Hydrogen
sulfide shall be treated and removed so that air quality and discharged
water quality is maintained within EPA standards at all times.
A. Unless otherwise directed by the Engineer, all open excavations and other hazardous
areas shall be totally enclosed from all sides by temporary fencing. Temporary fencing is
detailed on MPW Standard Drawing.
B. In all cases, locations of the temporary fencing proposed by the Contractor shall be
submitted to the Engineer for approval prior to installation. The Contractor shall not
commence any works until the associated temporary fencing is erected and the
installation has been approved by the Engineer.
C. Damaged sections of temporary fencing shall be repaired or replaced promptly
to maintain at all times the standard of fencing and installations as initially
approved. Temporary fencing shall not be removed from any location without
the prior written approval of the Engineer.
A. The Contractor shall protect streets and sidewalks and shall repair damage caused
by construction activity. The Contractor shall comply with local rules and
regulations in connection with the use of streets.
B. Allow for protecting and maintaining all pipes, ducts and cables met in excavations,
for keeping all ditches gullies and channels clear and unobstructed and for making
good any change caused to public or private roads, paths, kerb and drains and paying
all cost and charges incurred.
PART 2 - PRODUCT
2.02 CEMENT
A. Cement used for the drainage works shall be fresh and of approved quality
KEO/19-3262-0000 33 4000/8 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
Portland sulphate resisting cement Type V, complying with the requirements of ASTM
C150.
A. Concrete elements of any class for drainage works, whether pre-cast or in-situ, shall be
carried out in accordance of Division 3.
B. Concrete shall be in accordance with Section 03 3005 and the following classes:
1. Class C 20 for bed or haunch or encasement to pipes
2. Class C 40 with nominal 10mm aggregate for benching, minimum 20 mm thick
with smooth hard finish
3. Class C 20 for blinding
4. Class C 40 for Reinforced Concrete works
A. The Contractor shall make necessary arrangements to verify the conformity of pipes
to the specification requirements and tests outlined hereinafter, prior to
importing the concrete pipes to the site. The Engineer may, at his discretion, supervise
all such tests.
B. Pipes and fittings shall be in accordance with the following
1. Reinforced Concrete Pipe (RCP) and fittings shall comply with the
requirements of Section 33 3101 - “Reinforced Concrete Pipe and Fittings” as
modified herein.
2. Un-reinforced Concrete Pipe and Fittings shall comply with the requirements
herein.
3. uPVC Pipes and fittings shall confirm to the requirements of Section 33
3330 - “uPVC Pipe and Fittings”
4. HDPE Pipes and fittings shall confirm to the requirements of Section 33
3102 - “HDPE Gravity Sewer Pipe and Fittings”
Table VI-1
Crushing strength of Un-reinforced Pipes
Nominal internal dia. Minimum crushing strength
of pipe in mm (kgf/Linear meter)
250 2350
300 2380
350 2600
400 2800
450 3000
500 3800
600 4000
D. In the event that, after installation, the pipe fail to meet the line test or other
requirements, the defective pipe shall be removed and replaced or encased with
minimum 150 mm thick Class C 20 concrete made from Type V cement as per ASTM
150.
E. Pipes of the above mentioned diameters shall be laid and protected in accordance with
the typical MPW Drawings (MPW No. RA / D / TP - 6) and Section 31 2315 -
“Trenching". Where these two standards conflict the most restrictive shall apply.
F. Pipes laid in depths less than one meter or more than five meters to top of pipe must be
encased in class C 20 concrete.
G. Joints for un-reinforced concrete pipes shall be elastomeric type rings, maintained
in place in such a manner that ensures watertight joints during the specified tests, and
the subsequent life of the installed pipes.
KEO/19-3262-0000 33 4000/10 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
H. Pipes and joints shall have the following marked indelibly, immediately after taking from
the mould(s):
1. Name of manufacturer
2. Date of manufacture and serial number
3. Nominal diameter
I. Nominal diameters shall refer to internal diameters of pipes and the nominal length of a
pipe shall be the effective length of the installed pipe.
J. Internal and external surfaces of the pipes shall be smooth and without repair
patches. Pipes and joints shall be checked for dimensions and tolerances with
special gauges, supplied by the Contractor. Tolerances on the pipe dimensions shall
be as follows:
1. Nominal diameter: ± 5 mm for 250 to 500 mm nominal diameter
2. Free space between the grooves: ± 2 mm for 250 to 500 mm diameter
3. Wall thickness at the base at the sides and at the top: + 20 mm and - 10
mm. Consideration shall be given to the required clearance between the
grooves for proper jointing
4. Nominal length: ± 20 mm
A. Pre-cast units, purchased from the Cement Products Factory of the National
Industries Company (NIC) in Kuwait.
A. Lightly reinforced, sulphate resisting cement concrete rings of 150 mm thickness, 1,000
mm internal diameter and suitable length from the Cement Products Factory of
the National Industries Company (NIC) in Kuwait - class K 300.
B. Manhole rings shall be joined with the manhole shaft using sand cement mortar
(3:1). External walls shall be treated with three coats of liquid asphalt to a finished
thickness of not less than 2 mm.
C. Benching and coating of inner and outer surfaces of the manhole shall be similar to that
of the cast-in-situ manholes.
2.17 STEELWORK
A. Steel work shall be fabricated from structural steel sections and fasteners,
all in accordance with Division 05
B. Unless otherwise specified, structural steel work shall be rust protected in
accordance with Section 09 9713 - “Steel Coatings”
PART 3 - EXECUTION
3.01 COORDINATION
A The Contractor shall notify other ministries and authorities whose service might
be affected by the Works regarding his program. He shall also submit every two
weeks details of the work contemplated for execution in order to enable the service
KEO/19-3262-0000 33 4000/12 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
authorities to inspect and/or to indicate their service on the site to take any
measures deemed necessary.
B. The Contractor shall study Drawings and specifications and familiarize with the
structural and architectural details and the work of other trades.
C. It shall be ensured that the work under this section will not interfere with those of other
trades and are compatible with the architectural finishes, prior to placing
orders, fabrication and installation.
D. Other Sections shall be furnished with necessary templates, patterns, setting out
plans and other items for incorporation in the works or for leaving necessary provisions
for the work. Ensure timely placement of sleeves, inserts and the like.
E. Where work is installed in close proximity, to or will interfere with other works,
the Contractor shall assist in working out satisfactory space arrangements. Composite
shop drawings shall be prepared to a suitable scale, showing how the work is
installed in relation to the work of other trades.
F. Conflicts in requirements with other trades shall be resolved by the Contractor. Only
those conflicts, that cannot be solved without changes to structure or those
which involve changes to system design, shall be referred to the Engineer.
A. Materials shall be carefully inspected and examined for cracks and other defects
while suspended above the trench immediately before installation in final position.
B. Materials which do not conform to the specifications or which are found to be defective
or damaged shall be rejected and removed from the works. If more than 10 percent of
the materials are rejected, the Engineer has the right to reject the whole consignment.
A. Trench excavation, pipe installation and backfill shall comply with Section 31
2315, unless otherwise approved by the Engineer.
B. Jointing shall be in accordance with the requirements of the particular specifications
for the pipe being used and the following.
1. When jointing pipe, a mark shall be made to check the position of the end of
the barrel after the joint is made.
2. The rubber rings shall be lubricated with a lubricant approved by
the pipe manufacturer. Joint lubricant shall be delivered to the site in
unopened containers.
3. A gap of 5mm to 10mm shall be left between the ends of the pipes to allow for
joint flexibility.
4. The pipeline joints shall not be deflected when pipes are laid in curves, until the
join has been made.
A. For the purposes of cleaning and inspection, the term gravity 'pipelines' includes
those laid in heading or by pipe- jacking or microtunnelling or similar techniques.
B. The Contractor shall submit for approval, his proposed method for cleaning the
gravity pipeline. Such cleaning system shall not damage the pipeline in any way.
C. During and after construction the Contractor shall take reasonable measures,
including the provision of stoppers plugs and headwalls where appropriate, to prevent
the ingress of deleterious matter into pipelines.
D. After backfilling pipe trenches and completing manholes, chambers, hatch boxes etc.,
and before the trench surfaces are reinstated, the interior of pipelines shall be cleaned
of silt and debris by approved methods for inspection by the Engineer as follows:-
1. Pipelines of 800mm nominal internal diameter and smaller shall have a loose
KEO/19-3262-0000 33 4000/14 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
plug passed through them to show that they are clear of obstruction and
free from deflection. For flexible pipelines the loose plug shall be
dimensioned to suit the permissible minimum deflected diameter of the pipe.
2. Pipelines greater than 800mm nominal internal diameter will, after
cleaning, be inspected from the inside and the Contractor shall provide
a suitable trolley, ventilation and safety equipment, and any other plant and
labour necessary for this purpose, if required by the Engineer.
3. All pipelines will be inspected again before commissioning or taking over
(whichever is sooner) and, if required by the Engineer, shall be cleaned again in
whole or in part.
A. For the purposes of inspection and testing, the term 'pipelines' includes those laid
in heading or by pipe- jacking or microtunnelling or similar techniques.
B. Prior to commencement of testing, approval shall be obtained to the quality and
methods of providing and disposing of all fluids used for testing purposes.
C. If permission is given to use new or existing pipelines or culverts, which are not part of a
live system, they shall be thoroughly cleaned of all silt and any resulting damage made
good after use.
D. If lagoons for the storage of such fluids are permitted, they must be suitably
protected with fencing and attended by day and night to prevent access by the general
public and will not be sited adjacent to buildings. Approved means of preventing the
formation of mosquito larvae on the surface of the lagoons will be employed.
E. Testing of pipelines shall in all cases be carried out in the presence of the Engineer.
The Contractor shall provide complete plant and all struts, thrust blocks, etc., as
may be necessary for effectively testing the pipelines to the specified pressures.
F. Should any inspection be unsatisfactory or any test fail, the Contractor shall
replace defective pipes, leaking joints or otherwise re-execute defective work as
instructed, following which, cleaning and testing will be repeated until the
Engineer certifies the pipeline to be satisfactory.
G. The Contractor shall take care that during periods of rainfall or flooding of trenches from
other causes, lengths of completed pipelines, which have not been backfilled may
be subject to flotation. He shall take precautions and measures to avoid any such
flotation. If pipelines are subject to flotation they shall be removed and completely
relaid to the Engineer's satisfaction.
H. General
1. The Contractor shall submit a method statement in accordance with Section
01 4000 for the Engineer's approval, covering details of his proposed
methods and programme for testing (including details of test equipment).
2. The Contractor shall provide all labour, materials and supplies necessary for
carrying out testing and cleaning including water, pumps, gauges, piped
connections, stop ends and all other temporary works. The Contractor shall also
include details for the disposal of water used for testing.
KEO/19-3262-0000 33 4000/15 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3. Test pressure shall be measured by U-tube manometer or standing water
columns.
4. Pipelines shall be properly secured and supported before being put under test.
a. At pipe ends, provide for transmitting the end thrust into the sides of the
trenches.
b. Ensure that anchorage of bends is sufficient and thrusts from all branch
outlets are properly restrained.
5. The Contractor may at any stage of construction carry out such tests as he
considers desirable, to check materials and workmanship on the pipeline.
a. This shall not relieve the Contractor of his obligations to complete all
testing designated under the Contract.
6. All water required for testing and cleaning the pipelines shall be potable
water or irrigation water and shall be provided by the Contractor, at his cost.
7. All flexible gravity sewer pipelines (uPVC, HDPE) must be tested for deflection.
8. The Engineer shall have power to require the Contractor to vary any test
procedure or pressure, as the Engineer thinks fit, at no extra cost to the Ministry.
9. The Contractor shall submit an inspection request to the Engineer, in accordance
with Clause. 1.07 “Quality Control" to test a section of pipeline, after having
satisfied himself that the section of pipeline to be tested in the presence of
the Engineer is satisfactory in all aspects.
10. The Contractor should note that neither the satisfactory testing of a pipeline,
section of a pipeline or any other pipework, nor the acceptance of such
testing by the Engineer or his representative, shall in any way relieve the
Contractor of any of his responsibilities and obligations under the Contract.
11. When leakage or infiltration exceeds the amount allowed by the specifications,
the Contractor shall, at his own expense, make the necessary repairs or
replacements in accordance with the specifications, to reduce the leakage
or infiltration to the specified limits.
12. Any individual detectable leaks shall be repaired, regardless of the results of the
test, unless otherwise accepted by the Engineer.
I. Deflection Testing
1. All flexible gravity sewer pipelines (HDPE, uPVC, etc) shall be subjected to
deflection tests at site, as detailed herein and in the particular pipe
specification of these documents.
a. The above requirement shall not apply to pipes 100mm dia. and smaller.
4. Pipe surround shall be removed from all sections of pipe failing to meet the
specified deflection criteria.
a. Undamaged pipes may be re-backfilled and tested again.
b. All action taken to correct the pipe deflection shall be at the Contractor’s
expense.
KEO/19-3262-0000 33 4000/16 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
c. Re-laid sections shall be tested in accordance with item number 3 above.
5. If the permanent set or deflection, after removal of pipe surround, exceeds the
limits set out above, the pipes shall be deemed to be damaged and will
therefore be rejected.
a. Pipes so rejected shall be indelibly marked, removed from the site and
replaced at the Contractor's expense.
A. All gravity pipelines of 800mm nominal internal diameter and smaller shall be given
a preliminary test when the pipeline is bedded and jointed but before backfilling and a
final test after backfilling. Unless otherwise instructed, non-pressure pipelines shall be
tested in sections between manholes. In addition, pipelines shown as straight
lines on the Project Drawings shall be subjected to a light test between manholes to
verify alignment.
1. Preliminary test for pipelines with 800mm internal diameter or less:
a. Air shall be pumped into the pipeline until a pressure of l00mm head of
water is indicated on a water manometer and the pressure shall not fall
by more than 75mm during a period of 5 minutes.
b. The Contractor will not be permitted to commence testing later than 4
hours after sunrise or earlier than 4 hours before sunset during the
summer period unless otherwise directed by the Engineer.
2. Final test for pipelines with 800mm internal diameter or less:
a. Water test shall be conducted on segments of pipe between manholes.
b. The pipe work shall be completely filled with fresh water to a head of 1500
mm above the crown of the pipe at the highest end (not exceeding 6000
mm above the crown at the lowest end of the pipe work segment).
Steeply graded pipe work shall be tested in sections so as not exceed the
above limit.
c. Unless otherwise agreed by the Engineer, the test shall commence one
hour after the filling of the line, at which point the test column shall be
made up to the required test head.
d. The loss of water over a period of 30 minutes period shall be measured
by the addition of water to the test column.
e. The pipe work under test shall be deemed to have passed the test if the
loss of water does not exceed 0.12 liters per hour per 100 meters of
pipe per mm of internal diameter.
f. If the pipe work fails in the test or shows any signs of leakage, the
Contractor shall rectify the defects or replace the pipe work at his
expense.
g. The Contractor shall use only fresh water for the tests and
arrange for its transport in and out of the site.
B. All gravity pipelines larger than 800mm nominal internal diameter shall be
internally inspected, pressure tested and also tested for infiltration when laid below
the ground water table. Internal inspection shall be in accordance with Article 3.05.
1. The Contractor shall, carry out tests on every joint by means of an approved
joint testing apparatus or by hydrostatically testing the pipeline.
a. The pipe work shall be completely filled with fresh water to a head of 1500
KEO/19-3262-0000 33 4000/17 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
mm above the crown of the pipe at the highest end (not exceeding 6000
mm above the crown at the lowest end of the pipe work segment). Steeply
graded pipe work shall be tested in sections so as not exceed the above
limit.
b. Unless otherwise agreed by the Engineer, the test shall commence one
hour after the filling of the line, at which point the test column shall be
made up to the required test head.
c. The loss of water over a period of 30 minutes period shall b measured
by the addition of water to the test column.
d. The pipe work under test shall be deemed to have passed the test if the
loss of water does not exceed 0.12 liters per hour per 100 meters of
pipe per mm of internal diameter.
2. For any joint of a pipeline that fails this test additional joint sealing will be
required to be carried out by approved resin/gel/grout injection techniques at
the Contractor's cost.
3. The Contractor shall repair any joint with visible leakage.
C. Infiltration Test:
1. The measured infiltration shall not exceed 0.12 liters per hour per 100 meters of
pipe per mm of internal diameter of pipeline under test.
a. Pipes 600mm and larger and smaller sizes if directed by the Engineer, laid
below the groundwater table shall be subjected to an infiltration test.
b. The infiltration test shall be conducted after dewatering activities have
been suspended for at least 7 days.
c. The Contractor shall include in his method statement complete details for the
measurement of any infiltration.
d. For any pipeline that fails the infiltration test the Contractor must
propose measures to remedy the situation and execute such measures at
his own cost to achieve compliance with this requirement.
2. For any joint of a pipeline with nominal internal diameter greater than 800mm,
which fails this test additional joint sealing will be required to be carried out by
approved resin/gel/grout injection techniques at the Contractor's cost.
3. The Contractor shall repair any joint with visible leakage.
3.08 MANHOLES
A. General
1. Unless noted otherwise, manholes shall be constructed on gravity sewers:
a. At each change of gradient or direction.
b. At each change in diameter.
c. At each intersection with other pipes.
d. At such other points as shown on the Drawings.
e. As directed by the Engineer.
2. Concrete work shall not begin until the pipe fittings to be cast into the manhole
walls, are on site. No "box outs" will be allowed, unless approved by the
Engineer.
a. Thereafter the manhole shall be cast, water-proofed and backfilled as
quickly as possible.
3. Channel inverts shall be accurately laid to meet pipe invert elevations.
KEO/19-3262-0000 33 4000/18 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
4. Channel bends in the benching are to be as "slow" as possible, by
setting the manholes "off-center" at changes in direction.
5. All pipelines adjoining structures (i.e. at entries and exits to manholes) shall
have a flexible joint adjacent to each structure, as detailed on the drawings.
6 Benching shall be formed with in-situ C40/20 mass concrete with smooth
hard exposed finish.
7. Unless otherwise noted, all exterior surfaces below grade shall be covered
with waterproof membrane, in accordance with Section 07 1300.
8. Manhole covers in traffic areas shall be set to the paved area profile and be flush
with the paved area surface.
9. Manhole covers located in non-traffic areas shall be set to an elevation as shown
on the drawings, or as directed by the Engineer.
10. Where drop manholes are indicated they shall be as shown on the Drawings
and shall be formed where the upstream length of sewer enters a manhole at
a level 1 metre or greater above the manhole invert level.
11. All manholes shall be watertight on completion.
12. Manholes shall be tested in accordance with the requirements of this clause.
13. The Contractor shall take all measures, deemed necessary by the
Engineer, to ensure that manholes are not left in a flooded or unprotected
condition.
a. If the designated covers are not on site after placing the cover slab, a
temporary plywood cover shall be securely fitted in all openings.
A. The Contractor shall test 10 percent of all Storm Water Drainage System manholes, to
be selected at random by the Engineer.
B. Manholes shall be hydrostatically tested to at least one metre above the crown of the
highest connection into the manhole being tested.
C. The selected manholes shall be tested for watertightness. Each manhole shall be filled
with clean water to the test level and shall stand for a period of three days, to allow for
absorption. The
structure shall be considered satisfactory if, subsequent to this period, there shall be no
fall in level over a period of 24 hours (after making due allowance for rainfall
and evaporation) and no visible leaks.
D. Should a manhole fail to pass it shall be repaired and retested. If more than 2 percent
of the total manholes fail the Contractor shall submit to the Engineer for his
approval a proposal to correct the situation.
E. All cost associated with testing and repairs shall be of the Contractor's expense.
KEO/19-3262-0000 33 4000/19 Storm Drainage Utilities
12 Neighborhood Centers
Public Authority for Housing & Welfare, Kuwait
3.10 CONNECTIONS TO EXISTING PIPELINES:
A. At the locations shown on the Drawing, or directed by the Engineer, the Contractor shall
connect the new pipelines to the existing pipelines or structures, but not until the new
works have passed the final tests.
B. The Contractor shall take every precaution to prevent any dirt or extraneous material
from entering the existing main or service pipe.
C. The Contractor shall have available, at the connection site, sufficient dewatering pumps
to keep the excavation dry at all times.
1. Work shall be carried out in a clean and efficient manner.
2. The Client may put the interconnection into use as soon as possible
after its installation and will carry out an inspection to detect any evidence of
leakage.
a. Any remedial work necessary to eliminate leakage shall be carried out by
the Contractor.
b. No pipework shall be covered or backfilled until the Engineer is totally
satisfied that the interconnection is free of all leakage.
A. The Contractor shall maintain Storm Water flow arising from any source.
1. The Contractor shall submit his proposed method of overpumping or flow
diversion to the Engineer for approval, prior to the start of construction.
2. The proposed method shall include proposed alignments and design
requirements of the discharge to the terminal point.
B. Contractor shall furnish, install and operate pumps, plugs, conduits and other equipment
required to divert flow around the pipe segment upon which work is to be performed.
1. After the work has been completed, tested and accepted by the Engineer, flow
shall be restored to normal.
END OF SECTION