DATA SHEET FOR SOLID STATE POLARIZATION CELL :
=f
[50 Amperes Nominal
Steady State AC Current Rating
DC Blocking
(-)3.0 Volts Negative to (+)1.0 Volts Positive
‘Short Duration Fault Current : |Model AESOSKA ~ 5000A@30 Cycle 50Hz
Model AES10KA ~ 10000A@30 Cycle 50Hz
Lightening Surge Current Rating : |50,000 Amperes Crest for 8 to 20usec.
‘Ambient Temperature » [08°C to 65°C |
‘Solid State Polarisation Cell Replacement The device when absolute
voltage across the terminals is (-)3.0 volts Negative to
\(+)1.0 volt Positive.
The device further provides a grounding ( or coupling)
path for steady state AC current of a magnitude Of 50
Amperes.
Solid State Design eliminates the maintenance!
requirements and the potentially hazardous}
electrolytes associated with polarisation cells and have
@ higher DC blocking voltage.
‘The device is made of solid state components which
have an instantaneous response with respect to
voltage, thereby initiating voltage clamping
immediately when the voltage attempts to exceed the
blocking level selected.
Number of Repeated Operations
: |Virtually unlimited under maximum ratings, provided
the operations are not immediately repetitive.
Enclosure
: |Weatherproof IP 55 Enclosure for Safe Area
Explosionproof IP 65 Exd Enclosure for Hazardous
Area
Typical Applications
oP
: [Blocking Stray DC Voltage.
DC Isolation and AC Grounding of Cathodically
Protected Equipment
DC Isolation of Cathodically Protected Equipment from
Power Utility Grounding systems.
Over Voltage Protection from AC Faults, Lightening
and Switching Transients for Monolithic isolating joints.
‘AC Voltage Mitigation.
Mis. Advance Electronic Systems
Mis. Corrpro System
[Drawing Reference
: |GAIL-VSPL-IMS-PCR-001