Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable or constant flow.
Suitable Actuators
Non-Spring Spring
B329 ARB(X) AFB(X)
D C
H1 H2
Technical Data 2117
Service chilled, hot water, up to 60% glycol
Flow Characteristic A-port equal percentage, B-port modified E F B
for constant common port flow A
Controllable Flow Range 75°
Size [mm] 1.25” [32] ARB, ARX
End Fitting NPT female ends
Body forged brass, nickel plated A B C D E F H1 H2
Ball stainless steel 10” 3.96” 6.76” 5.51” 1.73” 2.14” 0.75” 0.5” [15]
[254] [101] [172] [140] [44] [54] [20]
Stem stainless steel
Stem Packing EPDM (lubricated)
Seat Teflon® PTFE
Seat O-ring EPDM (lubricated)
Characterized Disc stainless steel
Date created, 11/06/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.
Flow Pattern
D C
E F B
A
A B C D E F
11.36” 3.96” [101] 8.8” [224] 7.55” [192] 3.15” [80]
[289]
D
C
H1 H2
E F B
A
A B C D E F H1 H2
9.69” 3.96” 7.45” 6.2” 1.73” 2.14” 1.39” 0.75”
[246] [101] [190] [158] [44] [54] [34] [20]
D C
E F B
A
AFRB, AFRX
A B C D E F
10.57” 3.96” [101] 6.9” [175] 5.65” [144] 2.14” [54] 1.26” [32]
[269]
Wiring Diagrams
24 VAC Transformer
INSTALLATION NOTES A 1 3 46 47
A Actuators with appliance cables are numbered. Line Blk (1) Common
Provide overload protection and disconnect as required. Volts Red (2) + Hot
Only connect common to negative (-) leg of control circuits. Position (–) Pnk (4) Y Input
2
Feedback VDC (+) Org (5) U Output
A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2
to 10 VDC.
On/Off
Control signal may be pulsed from either the Hot (Source) or Common
(Sink) 24 VAC line.
For triac sink the Common connection from the actuator must be 24 VAC Transformer (AC Only) 1 10 46 47
connected to the Hot connection of the controller. Position feedback
cannot be used with a triac sink controller; the actuator internal Line Blk (1) Common
common reference is not compatible. Volts Red (2) + Hot
IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number
Wht (3) Y1 Input
40155).
Actuators may be controlled in parallel. Current draw and input Pnk (4) Y2 Input
46 Position (–)
impedance must be observed.
Feedback VDC (+) Org (5) U Output
Master-Slave wiring required for piggy-back applications. Feedback
47
from Master to conrol input(s) of Slave(s). Floating Point
Meets cULus requirements without the need of an electrical ground
connection. 24 VAC Transformer A 1 3 5 46 47
! WARNING! LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing and troubleshooting of this Line Blk (1) Common
product, it may be necessary to work with live electrical components. Volts Red (2) + Hot
Have a qualified licensed electrician or other individual who has been
properly trained in handling live electrical components perform these Ω 500 Ω
1/4 watt
tasks. Failure to follow all electrical safety precautions when exposed to Control Signal (–)
live electrical components could result in death or serious injury. VDC / mA (+) Wht (3) Y Input
VDC/mA Control
Position (–)
Pnk (4) Y2 Input
Feedback VDC (+) Org (5) U Output
PWM Control
Override Control
Slave
1
Blk (1) Common
Red (2) + Hot
Master - Slave
Date created, 12/04/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.