(1.1) Purpose:- To Remove the Total Suspended Solid (TSS) particles & dirt of particle size greater than 50 Micron, and thereby Reducing the SDI(Silt Density Index) Load of feed Water, Which can foul the R.O. Membrane.
(2.2) Specification :-
PRESSURE-VESSEL:
Quantity offered : One No
Type : Down Flow – 30” X 60” / 2.5” TOP & BOTTOM OPENING WITH FAPT & TRIPOD STAND.
MOC : FRP – Epoxy Resin impregranated glass fibre
Roving wound in helical format on frp liner.
Size : 13” X 54”
Diameter of Tank : 13” Height of Tank. : 54” Wall thickness of Tank. : 10.0 mm.frp + 12.5mm hdpe liner. Testing Pressure : 10 bar ( 10 kgf. / cm2 ) = 150 psig. Operating Flow rate : 1 M3 / Hr. @ 30 m Head Operating Pressure : 2.5 – 3.5 Kg. / cm2. Make & Brand : Stracture from Pentair / Advance / Aventure HT. CAMMA.
VALVE:
Make : Inetiative / UKL / PREHAR / PENTAIR
Valve Type : MULTI PORT – SINGLE LEVER VALVE MOC : NORYL . SIZE OF MPV : 25 NB / 25 MM. MAX. FLOW RATE : 3700 LITRE / HOUR. WORKING FLOW RATE : 1,000 LITRE /HOUR ( 1 M3 / HR.) MAX. WORKING : 6 BAR. ( 6.0 kgf. / cm2 ) = 90 psig. PRESSURE WORKING PRESSURE : 2.5 – 3.5 BAR ( 2.5 – 3.5 kgf./ cm2 ) = 37.5 – 52.5 psig. WORKING FLOW : DOWN FLOW.
MEDIA:
Mixed Bed of Sand Media consisting of following.
(i) Gravels (ii) Pebbles (iii) Quartz Sand & (iv) Anthracite Bed Depth is 800mm – 1000mm. Average Porosity of bed is 50 micron particulate size
(02)ACTIVATED CARBON FILTER (ACF)
(3.1) Purpose:- To Remove the Total Organic Matter/Compound (TOC)
In Raw Water , thereby water gets free from Colour, Smell & Odor, that was due to Organic Impurities. Activated Carbon can adsorb the free Chlorine containing in feed Water/ Raw Water, that is essential to save the R.O Membrabe
(3.2) Specification :-
PRESSURE-VESSEL:
Quantity offered : One No
Type : Down Flow – 13 X 54 / 2.5” TOP & BOTTOM OPENING WITH FAPT & TRIPOD STAND.
MOC : FRP – Epoxy Resin impregranated glass fibre
Roving wound in helical format on frp liner. Size : 13” X 54” Diameter of Tank : 13” Height of Tank. : 54” Wall thickness of Tank. : 10.0 mm.frp + 12.5mm hdpe liner Testing Pressure : 10 bar ( 10 kgf. / cm2 ) = 150 psig. Operating Flow rate : 1 M3 / Hr. @ 30 m Head Operating Pressure : 2.5 – 3.5 Kg. / cm2. Make & Brand : Stracture from Pentair / Advance / Aventure HT. CAMMA.
VALVE:
Make : Inetiative / UKL / PREHAR / PENTAIR
Valve Type : MULTI PORT – SINGLE LEVER VALVE MOC : NORYL . SIZE OF MPV : 25 NB / 25 MM. MAX. FLOW RATE : 3700 LITRE / HOUR. WORKING FLOW RATE : 1,000 LITRE /HOUR ( 1 M3 / HR.) MAX. WORKING : 6 BAR. ( 6.0 kgf. / cm2 ) = 90 psig. PRESSURE WORKING PRESSURE : 2.5 – 3.5 BAR ( 2.5 – 3.5 kgf./ cm2 ) = 37.5 – 52.5 psig. WORKING FLOW : DOWN FLOW. MEDIA: