DI-0 AGT -L LOCAL / REMOTE – AGITATOR
DI-1 AGT -R RUN FEEDBACK – AGITATOR
DI-2 AGT -T TRIP FEEDBACK – AGITATOR
DI-3 LSL – FT01 LEVEL SWITCH LOW – FEED TANK
DI-4 LSH – FT01 LEVEL SWITCH HIGH – FEED TANK
CAT # 6ES72211BH320XB0
6ES72211BH320X
B0
75, Fortune North Industrial Park, B/H GEB Sub Station, Beside Gamathi Hotel, Near Nana Chiloda Circle, Naroda, Ahmedabad
– 382330 Contact : +91 88660 00275 / E-mail : pacesol.ahd@gmail.com
CONTROL SYSTEM AND HMI REQUIREMENTS
In Auto Mode the Pump will be Operated through Auto Sequence if Any. For this to Happen Local
/ Remote Selection Switch Input has to be ON.
In Auto Mode there might be Interlock Bit for Each Pump. Once the Interlock is OK then and then
Only the Pump must Run.
In Manual Mode, the Pump will be Operated Manual by Pressing the Start / Stop Push Button
Provided on the Panel. For this Action the Local / Remote Selection Switch Input has to be OFF.
Analog Scaling
Each Analog Input Shall be Configured as per our Regular Standard / Functions Like Engineering
Set Values (Upper and Lower) + Alarm Setting. This is Applicable for all the 4 Analog Input
channels.
PID Loop
Hooter
Hooter When Any Pumps Gets Tripped / Alarm Condition Occurs for Analog Value / 4 No of
Level Switch Conditions.
Ack Pust Button for Hooter Silence.
75, Fortune North Industrial Park, B/H GEB Sub Station, Beside Gamathi Hotel, Near Nana Chiloda Circle, Naroda, Ahmedabad
– 382330 Contact : +91 88660 00275 / E-mail : pacesol.ahd@gmail.com
Auto - Interlocks
Flow PID Loop Should ONLY be Executed Only when the Feed Pump is Running.
Feed Pump Should STOP when the Level Inside the Feed Tank Drops Below Low Level Switch.
Feed Pump : AUTO Operation Should be Controlled Based on HIGH Level Switch and LOW Level
Switch. On HIGH, Pump Should Start Automatically. On LOW, Pump Should Stopped
Automatically. However if the Level is Between HIGH and LOW Level then Operator can START
the Pump from the HMI by Giving the START Command.
Same Auto START / STOP Logic is Applicable for Condensate Pump.
ATFD Motor Should Start Only when the Feed Pump is Running.
Blower Motor Should Start Only when the ATFD is Running.