ELECTRICAL PLAN

GENERAL NOTES : ELECTRICAL SYMBOLS :


WHEREVER REQUIRED AND NECESSARY, JUNCTION BOXES AND CTV CABLE TV OUTLET
ALL ELECTRICAL WORKS AND INSTALLATIONS SHALL CONFORM M KILOWATT HOUR METER
WITH THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, FULL BOXES OF PROPER SIZES SHALL BE INSTALLED AT
NATIONAL ELECTRICAL CODE RULES AND REGULATIONS OF THE CONVENIENT AND INCONSPICOUS LOCATION, ALTHOUGH SUCH T TELEPHONE OUTLET
ENFORCING AUTHORITY AND POWER COMPANY. BOXES ARE NOT SHOWN IN THE PLANS NOR MENTIONED IN THE SERVICE ENTRANCE
SPECIFICATIONS. FLOOR MOUNTED CONDUIT OUTLET
SERVICE ENTRANCE SHALL BE SINGLE - PHASE , 60 HZ. SYSTEM FM
ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING BRANCH CIRCUIT WP WEATHERPROOF OUTLET
ALL CONDUITS SHALL BE IN POLYVINYL CHLORIDE (PVC ) EXCEPT
HEIGHTS ABOVE THE FINISHED FLOOR LINE, UNLESS HOMERUNTO PANELBOARD
FOR MAIN SERVICE ENTRANCE WHICH IS RSC PIPE
OTHERWISE NOTED : R RANGE OUTLET
ALL WIRINGS SHALL BE INSTALLED IN CONDUIT PIPES EMBEDDED "LP"
INSIDE HOLLOW BLOCK STRUCTURES, SLABS, WALLS, COLUMNS, WALL SWITCHES 1200 MM. PANELBOARD REF REFRIGERATOR OUTLET
PARTITIONS AND /OR RUN CONCEALED BETWEEN DOUBLE WALL DUPLEX CONVENIENCE OUTLET 300 MM. 0R 150 MM ABOVE WORKTABLE
WOODEN PARTITIONS AND INSIDE THE CEILING SPACES WHERE PORCELAIN RECEPTACLE
AIRCONDITIONING UNIT OUTLET AT CONV. HEIGHT NEAR THE EQPT. HD HAND DRYER
THE USE OF CONCEALED CONDUIT WIRING IS IMPRACTICABLE,
TEL. & CABLE TV OUTLET 300 MM. OR 150 MM. ABOVE WORKTABLE WITH 9 WATTS LED BULB
SURFACE METAL WIRING MAY BE USED. EMBEDDED CONDUIT
WATERHEATER OUTLET AT CONV. HEIGHT NEAR THE EQPT. PINLIGHT WITH LED BULB ( 5 WATTS
UNLESS OTHERWISE SPECIFIED, THE SMALLEST WIRE AND
PANEL BOARD 1800 MM. FROM CENTER OF PANEL TO F.F.L.
CONDUIT PIPE TO BE USED SHALL BE NO. 3.5 MM² THW AND 20 CONCEALED CONDUIT
ENCLOSED AIR CIRCUIT BREAKER
MM² DIA. PVC, RESPECTIVELY.
ALL WORKS AND INSTALLATIONS SHALL BE DONE UNDER CLOSE (RATED AS INDICATED ON THE PLANS CCTV CCTV

SUPERVISION OF A REGISTERED ELECTRICAL ENGINEER. WL WALL LAMP


DUPLEX CONVENIENCE OUTLET

ACU AIRCONDITIONING OUTLET EX CEILING MOUNTED EXHAUST FAN


UTP CAT6 WIRE CABLE
CCTV MONITOR
WP WEATHER PROOF OUTLET
P.B - PULL BOX / SQUARE BOX THIRD FLOOR LEVEL
R RANGE OUTLET
F.B - EXHAUST FAN
REF REFREGERATOR OUTLET

THIRD FLOOR LEVEL


W.F. C.F. - CEILING FAN (ORBIT TYPE)
WALL FAN OUTLET

S a,b SWITCHES (LETTERS DENOTES NO. OF GANG CCTV CCTV

T5 CONCEALED FLOURESCENT

UTP CAT6 WIRE CABLE

SECOND FLOOR LEVEL

SECOND FLOOR LEVEL

CCTV CCTV CCTV CCTV CCTV CCTV CCTV CCTV CCTV TEL. TEL. CATV CATV

MDP "PP1A" "PP1B" "LP1A" "LP1B" "PP2" "LP2" "PP3" "LP3"


UTP CAT6 WIRE CABLE
CCTV MONITOR @ OFFICE

UPPER GROUND LEVEL

2 2 2 2
2-30mm THHN , 1-8mm THHN , 40mmØ RSC 2-14mm THHN , 1-5.5mm THHN , 25mmØ RSC
CCTV CCTV CCTV TEL. TEL. CATV CATV
UPPER GROUND LEVEL ( ELECTRICAL ROOM)

GROUND WIRE , 1-22mm 2 THHN

UTP CAT6 WIRE CABLE

CCTV MONITOR @ OFFICE

POWER SUPPLY SINGLE PHASE


230 V , 3W , 60 HZ LOWER GROUND LEVEL
2 2
2-250mm THHN , 1-30mm THHN (G) , 100mmØ RSC

M KWHM

ECB 400A,2P,230V 2 TELEPHONE,CATV & CCTV DIAGRAM


NOT TO SCALE
EE-1
LOWER GROUND LEVEL

GROUND WIRE , 1-30mm 2 THHN (G)

GROUND ROD
20mm dia. x 3000mm COPPER ROD
1 RISER DIAGRAM
NOT TO SCALE
EE-1
SCHEDULE OF LOADS : MDP SCHEDULE OF LOADS : LIGHTING "LP1A" SCHEDULE OF LOADS : LIGHTING "LP1B" SCHEDULE OF LOADS : TYPICAL LIGHTING "LP2" & "LP3"

BRANCH / CKT. BRANCH / CKT. BRANCH / CKT. BRANCH / CKT.


CKT. LOAD DESCRIPTION VA PER VOLTS BREAKER SIZE OF HOMERUN CKT. LOAD DESCRIPTION VA PER VOLTS BREAKER SIZE OF HOMERUN CKT. LOAD DESCRIPTION VA PER VOLTS BREAKER SIZE OF HOMERUN CKT. LOAD DESCRIPTION VA PER VOLTS BREAKER SIZE OF HOMERUN
NO. CKT. (WIRES & CONDUITS ) NO. CKT. (WIRES & CONDUITS ) NO. CKT. (WIRES & CONDUITS ) NO. CKT. (WIRES & CONDUITS )
AF P AT AF P AT AF P AT AF P AT
2 - 30 mm² THHN +1-8mm² THHN (G)
1 PP1A 15760 230 100 2 100 , 40 mm Ø PVC 1 LIGHTING OUTLET 1700 230 50 2 20 2 - 3.5 mm² THHN, 20 mm ØC PVC 1 LIGHTING OUTLET 1600 230 50 2 20 2 - 3.5 mm² THHN, 20 mm ØC PVC 1 LIGHTING OUTLET 1600 230 50 2 20 2 - 3.5 mm² THHN, 20 mm ØC PVC
2 - 30 mm² THHN +1-8mm² THHN (G)
2 PP1B 18440 230 100 2 100 , 40 mm Ø PVC 2 1700 2 1600 2 1600

2 - 14 mm² THHN +1-5.5mm² THHN


3 LP1A 9600 230 60 2 100 (G) , 25 mm Ø PVC 3 1000 3 1400 3 1600

2 - 14 mm² THHN +1-5.5mm² THHN


4 LP1B 10700 230 60 2 100 (G) , 25 mm Ø PVC 4 1200 4 1700 4 1600

2 - 14 mm² THHN +1-5.5mm² THHN


5 LP2 14800 230 60 2 100 5 SPARE 1000 5 1400 5 1600
(G) , 25 mm Ø PVC
2 - 14 mm² THHN +1-5.5mm² THHN
6 LP3 14800 230 60 2 100 6 SPARE 1500 6 1500 6 1600
(G) , 25 mm Ø PVC
2 - 14 mm² THHN +1-5.5mm² THHN
7 PP2 10240 230 60 2 100 7 SPARE 1500 7 SPARE 1500 7 1600
(G) , 25 mm Ø PVC
2 - 14 mm² THHN +1-5.5mm² THHN
8 PP3 10240 230 60 2 100 TOTAL 9600 TOTAL 10700 8 1600
(G) , 25 mm Ø PVC

TOTAL 104580 TOTAL CONNECTED LOAD = 9600 VA TOTAL CONNECTED LOAD = 10700 VA 9 1000
USE : 2 - 14 mm²THHN, 1-5.5 mm² THHN (G) IN 32 mmØ RSC. USE : 2 - 14 mm²THHN, 1-5.5 mm² THHN (G) IN 32 mmØ RSC.

TOTAL CONNECTED LOAD = 104580VA USE : 2 - 250 mm²THHN, 1-30 mm² THHN (G) IN 75 mmØ RSC. I @ 80 % D. F. = 9600(.80 ) I @ 80 % D. F. = 10700(.80 ) 10 SPARE 1000
= 33.39 AMPS. MCCB : 60AT, 2P, 230V, 100AF, BOLT ON TYPE = 37.22 AMPS. MCCB : 60AT, 2P, 230V, 100AF, BOLT ON TYPE
230 Use minimum of 10kAIC for all MCCB 230 Use minimum of 10kAIC for all MCCB
I @ 80 % D. F. = 104580(.80 ) = 363.76 AMPS. TOTAL 14800
MCCB : 400AT, 2P, 230V, 400AF
230 Use minimum of 10kAIC for all MCCB
TOTAL CONNECTED LOAD = 14800 VA USE : 2 - 14 mm²THHN, 1-5.5 mm² THHN (G) IN 32 mmØ RSC.

I @ 80 % D. F. = 14800(.80 ) = 51.48 AMPS. MCCB : 60AT, 2P, 230V, 100AF, BOLT ON TYPE
230 Use minimum of 10kAIC for all MCCB

SCHEDULE OF LOADS : POWER "PP1A" SCHEDULE OF LOADS : POWER "PP1B" SCHEDULE OF LOADS : TYPICAL POWER "PP2" & "PP3"

BRANCH / CKT. BRANCH / CKT. BRANCH / CKT.


CKT. LOAD DESCRIPTION VA PER VOLTS BREAKER SIZE OF HOMERUN CKT. LOAD DESCRIPTION VA PER VOLTS BREAKER SIZE OF HOMERUN CKT. LOAD DESCRIPTION VA PER VOLTS BREAKER SIZE OF HOMERUN VOLTAGE DROP & SHORT CIRCUIT CALCULATION
NO. CKT. (WIRES & CONDUITS ) NO. CKT. (WIRES & CONDUITS ) NO. CKT. (WIRES & CONDUITS )
AF P AT AF P AT AF P AT

100 MVAsc SHORT CIRCUIT CALCULATION


1 CONVENIENCE OUTLET 1620 230 50 2 20 2 - 3.5 mm² THHN, 20 mm ØC PVC 1 CONVENIENCE OUTLET 1620 230 50 2 20 2 - 3.5 mm² THHN, 20 mm ØC PVC 1 CONVENIENCE OUTLET 1620 230 50 2 20 2 - 3.5 mm² THHN, 20 mm ØC PVC

MVAb = 100
2 1260 2 1620 2 1620
T1
100 kVA,1PH Calculate Short Circuit Fault at ECB:
3 1260 3 1260 3 1080
3% Xu = MVAb = 100 = 1 p.u.
4 EXHAUST FAN FULL BOX 1000 4 1080 4 1620 MVAsc. 100

5 CEILING FAN 600 5 1080 5 1620 XT1 = %Zt1 x MVAb = 0.03 x 100 = 30 p.u.
MVAt1. 0.10
2-250mm2 THHN , 50m
6 CEILING FAN 800 6 720 6 1080 Xc = Zc/305m x L x MVAb = 0.05/305 x 50 x 100 = 15.4 p.u.
2 - 5.5 mm² THHN,1-3.5mm² THHN, 2 - 5.5 mm² THHN,1-3.5mm² THHN, kV 2 2
7 SPLIT TYPE (1.5 TR ) 3220 30 7 SPLIT TYPE (1.5 TR ) 3220 30 7 CEILING FAN 800 0.23
25 mm ØC 25 mm ØC
2 - 5.5 mm² THHN,1-3.5mm² THHN, 2 - 5.5 mm² THHN,1-3.5mm² THHN,
Zth = Xu + Xt1 + Xc = 1 + 30 + 15.4 = 46.4 p.u.
8 MOTOR PUMP 3000 30 25 mm ØC 8 SPLIT TYPE (1.5 TR ) 3220 30 25 mm ØC 8 CEILING FAN 800
6 6
2 - 5.5 mm² THHN,1-3.5mm² THHN, 2 - 5.5 mm² THHN,1-3.5mm² THHN, Ifsc = MVAb x 10 = 100 x 10 = 9,370 Amps or 9.37 kA
9 MOTOR PUMP 3000 30 25 mm ØC 9 SPLIT TYPE (1.5 TR ) 3220 30 25 mm ØC 9 SPARE
V x Zth 230 x 46.4
10 SPARE 10 CEILING FAN 700 20 TOTAL 10240
9.37 kA Calculate Votage Drop at ECB:
11 SPARE 11 CEILING FAN 700 20
TOTAL CONNECTED LOAD = 10240VA USE : 2 - 14 mm²THHN, 1-5.5 mm² THHN (G) IN 32 mmØ RSC. 2.67% VD
E = IR
12 SPARE
I @ 80 % D. F. = 10240(.80 ) +.25 (14) = 39.12 AMPS. MCCB : 60AT, 2P, 230V, 100AF, BOLT ON TYPE
ECB 400A
230
I = 363 Amp.
TOTAL 15760 TOTAL 18440 Use minimum of 10kAIC for all MCCB
Conductor : 250 mm2 , Z = 0.050/305m (Table 9.1.1.9 PEC)

TOTAL CONNECTED LOAD = 15760 VA USE : 2 - 30 mm²THHN, 1-8 mm² THHN (G) IN 40 mmØ RSC. TOTAL CONNECTED LOAD = 18440 VA USE : 2 - 30 mm²THHN, 1-8 mm² THHN (G) IN 40 mmØ RSC. Length - 50 m

I @ 80 % D. F. = 15760(.80 ) +.25 (14) = 58.32 AMPS. MCCB : 100AT, 2P, 230V, 100AF,BOLT ON TYPE I @ 80 % D. F. = 18440(.80 ) +.25 (14) = 67.64 AMPS. MCCB : 100AT, 2P, 230V, 100AF, BOLT ON TYPE R = 0.050/305m x 50m = 0.0082 ohm
230 230
Use minimum of 10kAIC for all MCCB Use minimum of 10kAIC for all MCCB
VD = 2 IR = 2 x 374 x 0.0082 = 6.13 volts

%VD = 6.13 x 100 % = 2.67%


230
39.20
EX
a a a a a a

3.05
a a a
S1 a,b,c
a

5.18
S1

DOWN TO S3W b b b b b b b b b EX
b

1.96
@ LOWER GROUND
S1 S1
DOWN TO S3W
@ LOWER GROUND
c
c c c c c c

2.09
S3 a,b,c S3 a,b,c S3 a,b,c
LP1B
2 LP1B
S3W S1 1 S3W

15.70
e d e d

5.33

1.20
d e d e d
PB

S2 d,e
S3 j,k,l
S1 h,i

4.73
S1 h,i S1
EX EX S 1 f,h
j EX EX
j i S2 S2 g
k
S1 S1 LP1B
f f f 3 S1
i i i i

5.18
j k f
j f S1
h h
"LP3"

2.52
MANAGERS ROOM h h h "PP3"
"MDP"
LP1B
j LP1B 4 "PP1A"
j k i i i i g g g g "LP2"
6 S2 g,f S2 g,f "PP2" "LP1B" "LP1A" "PP1B"
LP1B
5

1.20
LIGHTING OUTLET LIGHTING OUTLET
UNDERNEATH LANDING STAIR UNDERNEATH LANDING STAIR
2 UPPER GROUND FLOOR LIGHTING LAYOUT
SCALE 1:100 M.
EE-3
3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00

WALL MOUNTED EXHAUST FAN

39.20
f
f

g g h h
5.18

5.18
f b b b

h
g g h S1
S1 b
S3 f,g,h

i i j j j k k LP1A
S3W S1 1 S3W
STAIR WELL
15.70

5.33

5.33
LP1A
i 4 n
PB
LP1A
i i j j j k k k 2
i n
S3 i,j,k S1 l
S 2 d,e,c
S3 c,m,n m
l c m
d n
b b

MANAGERS ROOM
5.18

5.18
a
LP1A
3
b b
c e
l c m m n
S3 a,b

a
a
1 LOWER GROUND FLOOR LIGHTING LAYOUT LIGHTING OUTLET WALL MOUNTED EXHAUST FAN LIGHTING OUTLET
SCALE 1:100 M.
EE-3 UNDERNEATH LANDING STAIR UNDERNEATH LANDING STAIR

3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
0.60
39.20

b b b b b b b b b b b b b b b b

5.18

5.18
a a a a a a a a
DOWN TO S3W DOWN TO S3W
@ UPPER GROUND @ UPPER GROUND
b b b b
b b b b b b b b b b b b

S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1
b b b b

EX EX EX EX EX EX EX EX
S3W S2 a,b, S2 a,b, S2 a,b, S 2 a,b, S2 a,b, S2 a,b, S2 a,b, S2 a,b, S3W
LP2 LP2 LP2 LP2

15.70
c d 4 c d 3 c d 2 c 1

5.33

5.33
d

S2 c,d LP2 LP2 LP2 LP2 LP2


8 7 6 5 PB
S 2 a,b, S2 a,b, S2 a,b, S2 a,b, S2 a,b, S2 a,b, S2 a,b, S2 a,b,

EX EX EX EX EX EX EX EX
b b b b
S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1

b b b b b b b b b b b b
b b b b

a a a a a a a a

5.18

5.18
b b b b b b b b b b b b b b b b

2 THIRD FLOOR LIGHTING LAYOUT LIGHTING OUTLET 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00 LIGHTING OUTLET
SCALE 1:100 M.
EE-4 UNDERNEATH LANDING STAIR UNDERNEATH LANDING STAIR

39.20

b b b b b b b b b b b b b b b b
5.18

5.18
a a a a a a a a
DOWN TO S3W DOWN TO S3W
@ UPPER GROUND @ UPPER GROUND
b b b b
b b b b b b b b b b b b

S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1
b b b b
EX EX EX EX EX EX EX EX
S3W S2 a,b, S2 a,b, S 2 a,b, S2 a,b, S2 a,b, S2 a,b, S2 a,b, S2 a,b, S3W
LP2 LP2 LP2 LP2
15.70

4 3 2 1
5.33

5.33
c d c d c d c d

S2 c,d LP2 LP2 LP2 LP2 LP2


8 7 6 5 PB
S 2 a,b, S2 a,b, S2 a,b, S2 a,b, S2 a,b, S2 a,b, S2 a,b, S2 a,b,

EX EX EX EX EX EX EX EX
b b b b
S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1

b b b b b b b b b b b b
b b b b

a a a a a a a a
5.18

5.18
b b b b b b b b b b b b b b b b
0.60

1 SECOND FLOOR LIGHTING LAYOUT LIGHTING OUTLET 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00 LIGHTING OUTLET
SCALE 1:100 M.
EE-4 UNDERNEATH LANDING STAIR UNDERNEATH LANDING STAIR
39.20
PP1B PP1B PP1B
9 9 9

NOTES : 4 NO.

3.05
PP1B
FLR. MOUNTED C.O. 9

IN EVERY BUNKBEDS AT THE DORMERS' ROOM(TWO OUTLETS),

5.18
FM FM HD
1 @ THE STUDY TABLE AND 1 @ THE BED AREA.

1.96
HD

FM FM

2.09
PP1B
2

15.70
PP1B

5.33

1.20
1

ECB RATED ; 30AT,2P.230V,(NEMA 3R) PB


2
WITH 2-5.5mm THHN,1-3.5mm TW IN 25mmØ C

4.73
PP1B
PP1B 4
6 PP1B
5
MANAGERS ROOM

5.18
"LP3" PP1B

2.52
3 "MDP"
"PP3"
PP1B "PP1A"
7 "LP2" "PP2" "LP1B" "LP1A" "PP1B"

PP1B
8

1.20
2 UPPER GROUND FLOOR POWER LAYOUT
SCALE 1:100 M.
EE-5
3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00

5.18 39.20

5.18
PP1A
1
15.70

5.33

5.33
PB

PP1A
2

PP1A PP1A
8 MANAGERS ROOM MOTOR PUMP
MOTOR PUMP 9
5.18

5.18
PP1A
3

PP1A
7

ECB RATED ; 30AT,2P.230V,(NEMA 3R)


1 LOWER GROUND FLOOR POWER LAYOUT 2
WITH 2-5.5mm THHN,1-3.5mm TW IN 25mmØ C
SCALE 1:100 M.
EE-5 FOR OWNER' SUITE & INTERNET LAB. ( TYP. )
3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
0.60
NOTES : 39.20
IN EVERY BUNKBEDS AT THE DORMERS' ROOM(TWO OUTLETS),
1 @ THE STUDY TABLE AND 1 @ THE BED AREA.

5.18

5.18
PP2 PP2 PP2 PP2
4 3 2 1

15.70

5.33

5.33
PB

PP2 PP2 PP2 PP2


8 7 6 5

5.18

5.18
2 THIRD FLOOR POWER LAYOUT
SCALE 1:100 M.
EE-6 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00

39.20
5.18

5.18
PP2 PP2 PP2 PP2
4 3 2 1
15.70

5.33

5.33
PB
5.18

5.18
PP2 PP2 PP2
PP2 7 6 5
0.60

8
1 SECOND FLOOR POWER LAYOUT
SCALE 1:100 M.
EE-6 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
39.20

3.05
5.18

1.96
CF CF CF CF CF CF CF

PP1B
S1 CF 10

2.09
S2 CF S2 CF S2 CF

15.70

5.33

1.20
PB

4.73
S 1 CF S1 CF S1 CF
S2 CF
PP1B
S1 CF 11
S1 CF

5.18
CF CF CF
CF CF
"LP3"
CF CF

2.52
"MDP"
MANAGERS ROOM "PP3"
"PP1A"
"LP2" "PP2" "LP1B" "LP1A" "PP1B"

1.20
2 UPPER GROUND FLOOR CEILING FAN LAYOUT
SCALE 1:100 M.
EE-7
3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00

39.20
5.18

5.18
CF CF CF CF
CF CF

PP1A
S1 CF 5
S1 CF
S4 CF
PP1A
4
15.70

5.33

5.33
PB
2 2
F.B. FOR EXHAUST FAN WITH 2-3.5mm THHN & 1-2.5mmm THHN,20mmØ C (TYP.)

S1 CF S1 CF PP1A
S5 CF 6
MANAGERS ROOM
5.18

5.18
CF CF CF CF CF CF CF

CF
S2 CF

1 LOWER GROUND FLOOR CEILING FAN LAYOUT


SCALE 1:100 M.
EE-7
3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
0.60
39.20

5.18

5.18
CF CF CF CF CF CF CF CF

PP2
7

15.70

5.33

5.33
PB

S 1 CF S1 CF S1 CF S1 CF S 1 CF S1 CF S1 CF S1 CF
PP2
8

CF CF CF CF CF CF CF CF

5.18

5.18
2 THIRD FLOOR CEILING FAN LAYOUT 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
SCALE 1:100 M.
EE-8

39.20
5.18

5.18
CF CF CF CF CF CF CF CF

PP2
7
15.70

5.33

5.33
PB

S1 CF S1 CF S1 CF S1 CF S1 CF S1 CF S1 CF S1 CF
PP2
8

CF CF CF CF CF CF CF CF
5.18

5.18
0.60

1 SECOND FLOOR CEILING FAN LAYOUT 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
SCALE 1:100 M.
EE-8
39.20
NOTE:
USE UTP CAT6 TO ALL CONNECTION CABLE.
CCTV CCTV CCTV CCTV

3.05
5.18

1.96
TO OFFICE
UTP CAT6 CABLE
CCTV

2.09
CCTV

15.70

5.33

1.20
TO OFFICE
UTP CAT6 CABLE

CCTV

4.73
TO OFFICE
UTP CAT6 CABLE
CCTV

TO OFFICE CTV CTV


UTP CAT6 CABLE

5.18
EQUIPMENT RACK
TO OFFICE @ UPPER GROUND
TO OFFICE MANAGERS ROOM UTP CAT6 CABLE "LP3"
UTP CAT6 CABLE

2.52
"MDP"
"PP3"
TEL TEL "PP1A"
"LP2" "PP2" "LP1B" "LP1A" "PP1B"
CCTV

1.20
2 UPPER GROUND FLOOR TEL.,CATV & CCTV LAYOUT
SCALE 1:100 M.
AUX-1
3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00

39.20

CTV

TO OFFICE @ LOWER GROUND


UTP CAT6 CABLE
CCTV
5.18

5.18
15.70

5.33

5.33
TO OFFICE @ LOWER GROUND
UTP CAT6 CABLE

EQUIPMENT RACK

MANAGERS ROOM
CCTV
5.18

5.18
CTV

CTV
TO OFFICE @ LOWER GROUND
TEL UTP CAT6 CABLE

CCTV TEL

1 LOWER GROUND FLOOR TEL.,CATV & CCTV LAYOUT


SCALE 1:100 M. TO OFFICE @ LOWER GROUND
AUX-1 UTP CAT6 CABLE

3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
0.60
NOTE:
USE UTP CAT6 TO ALL CONNECTION CABLE. 39.20

5.18

5.18
15.70
CCTV CCTV

5.33

5.33
TO OFFICE @ UPPER GROUND
UTP CAT6 CABLE

5.18

5.18
2 THIRD FLOOR TEL.,CATV & CCTV LAYOUT
AUX-2 SCALE 1:100 M. 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00

39.20
5.18

5.18
15.70

CCTV CCTV
5.33

5.33
TO OFFICE @ UPPER GROUND
UTP CAT6 CABLE
5.18

5.18
0.60

1 SECOND FLOOR TEL.,CATV & CCTV LAYOUT 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
SCALE 1:100 M.
AUX-2
NOTE: 39.20
LEGEND: USE UTP CAT6 TO ALL CONNECTION CABLE.
PC
D.O. D.O. D.O. D.O. D.O. D.O.

3.05
PC

MDF MAIN DISTRIBUTION FRAME PC PC

5.18
MD PC PC
DC DATA CABINET
PC PC
D.O DUPLEX OUTLET

1.96
RT
PC PC

RT ROUTER PC PC

D.O. D.O. D.O. D.O. D.O. D.O. PC


PR PRINTER

2.09
PC
TO MANAGERS OFFICE TV
PC PERSONAL COMPUTER @ UPPER FLOOR LEVEL MD
CEILING CABLE USING
MD MODEM UTP CAT6 CABLE

15.70

5.33

1.20
TV TELEVISION

ACCESS POINT

UTP CAT6 CABLE

4.73
SD CONVENTIONAL
SMOKE DETECTOR D.O. TV

D.O.
MANAGERS ROOM MD

5.18
PR D.O. D.O.
PR
D.O.
TEL.
MDF
TEL.

2.52
PC DC
TEL.
PC PC
MD
2 UPPER GROUND FLOOR NETWORK COMMUNICATION LAYOUT
SCALE 1:100 M.
AUX-3

1.20
DECK SLAB ABOVE STAIR ACCESS POINT TO CEILING
DATA CABLE @ HALLWAY
3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
UTP CAT 6
CABLE

39.20
THIRD FLOOR

ACCESS POINT TO CEILING


DATA CABLE @ HALLWAY

UTP CAT 6
5.18

5.18
CABLE

TO MANAGERS OFFICE
SECOND FLOOR @ LOWER FLOOR LEVEL
CEILING CABLE USING
MANAGERS OFFICE ACCESS POINT TO CEILING UTP CAT6 CABLE
DATA CABLE @ HALLWAY

TO OFFICE, STUDY HALL,


ISOLATION ROOM AND
MDF COMPUTER ROOM
TO MANAGERS OFFICE
@ UPPER FLOOR LEVEL
DATA CABINET UTP CAT6 CABLE
15.70
LINKED EACH OTHER

5.33

5.33
UPPER GROUND FLOOR
MANAGERS OFFICE ACCESS POINT TO CEILING
DATA CABLE @ HALLWAY
UTP CAT 6
CABLE

DATA CABINET TV
D.O.
DC
LOWER GROUND FLOOR
MANAGERS ROOM
MD
TEL. D.O. D.O.
5.18

5.18
3 NETWORK COMMUNICATION DIAGRAM TEL.

SCALE NDTS.
AUX-3 PC

PC
PR

1 LOWER GROUND FLOOR NETWORK COMMUNICATION LAYOUT


SCALE 1:100 M.
AUX-3
3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
0.60
LEGEND: NOTE:
USE UTP CAT6 TO ALL CONNECTION CABLE. 39.20

MDF MAIN DISTRIBUTION FRAME

DC DATA CABINET

5.18

5.18
D.O DUPLEX OUTLET
RT ROUTER

PR PRINTER

PC PERSONAL COMPUTER
MD MODEM
TO MANAGERS OFFICE
TV TELEVISION @ UPPER FLOOR LEVEL

15.70

5.33

5.33
CEILING CABLE USING
UTP CAT6 CABLE
ACCESS POINT

UTP CAT6 CABLE

SD CONVENTIONAL
SMOKE DETECTOR

5.18

5.18
1 SECOND FLOOR NETWORK COMMUNICATION LAYOUT
SCALE 1:100 M. 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
AUX-4

39.20
5.18

5.18
TO MANAGERS OFFICE
15.70

@ UPPER FLOOR LEVEL


5.33

5.33
CEILING CABLE USING
UTP CAT6 CABLE
5.18

5.18
0.60

1 SECOND FLOOR NETWORK COMMUNICATION LAYOUT


SCALE 1:100 M.
AUX-4
3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
TF WIRE #18
1 2 3 4 5 6 7 8 9 10 11
in a 12" PVC PIPE 39.20
SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD
D
FDASCP

M M M

3.05
B B B
THIRD FLOOR SD

5.18
TF WIRE #18 SD

in a 12" PVC PIPE


SD
SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD

1.96
FDASCP

SD SD SD
M M M
SD
B B B
SECOND FLOOR C SD

2.09
TF WIRE #18
in a 12" PVC PIPE

SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD ZONE
FDASCP

15.70

5.33

1.20
M M M
SD

B B B SD SD SD SD
UPPER GROUND FLOOR
TF WIRE #18
in a 12" PVC PIPE

SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD

4.73
B
FDASCP

M M M SD

B B B
LOWER GROUND FLOOR

5.18
SD SD SD SD SD SD SD

2.52
3 (FDAS) SINGLE LINE DIAGRAM SD
ZONE
SCALE NDTS 2
AUX-5 ZONE
3
A

1.20
2 UPPER GROUND FLOOR LAYOUT(FDAS ) 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
SCALE 1:100 M.
AUX-5 1 2 3 4 5 6 7 8 9 10 11
39.20
D
5.18

5.18
SD SD SD SD SD SD SD

ZONE
1

C
15.70

5.33

5.33
SD SD SD SD SD SD SD

ZONE
2

B
5.18

5.18
SD SD

SD SD SD SD SD

ZONE
3
A
1 LOWER GROUND FLOOR LAYOUT(FDAS )
SCALE 1:100 M.
AUX-5
3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00
0.60
1 2 3 4 5 6 7 8 9 10 11
39.20
D

5.18

5.18
SD SD SD SD SD SD SD SD

ZONE
1

15.70

5.33

5.33
SD SD SD SD SD

ZONE
2

5.18

5.18
SD SD SD SD SD SD SD SD

ZONE
3

A
2 THIRD FLOOR LAYOUT(FDAS)
AUX-6 SCALE 1:100 M. 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00

1 2 3 4 5 6 7 8 9 10 11
39.20
D
5.18

5.18
SD SD SD SD SD SD SD SD

ZONE
1

C
15.70

5.33

5.33
SD SD SD SD SD

ZONE
2

B
5.18

5.18
SD SD SD SD SD SD SD SD

ZONE
3

A
0.60

1 SECOND FLOOR LAYOUT(FDAS)


SCALE 1:100 M.
AUX-6 3.30 4.15 4.10 4.10 4.10 4.10 4.10 4.10 4.15 3.00