Saic A 1004 02
Saic A 1004 02
Saic A 1004 02
01 6-Sep-15
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Fill Placement and Compaction Inspection SAIC-A-1004 24-Mar-16 CIVIL-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Under foundations with static loads over 320kPa and foundations for
vibrating or heavy machinery and pavements, 85% of relative density
SAES-A-114
B5 (ASTM D4253/ASTM D4254) for cohesionless soils or 95% of of the
Sec. 6.3.6.2
maximum density as determined by ASTM D1557 for cohesive
materials.
Compacted surfaces of fill and backfill shall be finish graded to the cross
SAES-A-114
B10 sections, lines, grades and elevations as indicated on the drawings (PIP
Sec. 6.3.7
CVS 02100 Sec 4.3.7.12)
REMARKS:
REFERENCE DOCUMENTS:
1- SAES-A-114 -- Excavation and Backfill, 23, February, 2010
2- SACSM -- Saudi Aramco Construction Safety Manual, October 2011
3- PIP CVS02100 -- Site Preparation, Excavation and Backfill Specification, April 2007
Contractor / Third-Party Saudi Aramco
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date: