Acti9 iCT contactors catalogue

Ensure global safety standards compliance


with smart, reliable, connected Type B
Residual Current Circuit Breakers from
Schneider Electric.

schneider-electric.com
Control www.schneider-electric.com

Remote control
Acti9 iCT contactors

IEC/EN 61095
DB123399

DB116619

DB106604

DB122858
As per the above standards:
Acti9 iCT contactors are available in two versions:
DB406142

DB405227

b Contactors without manually-operated


b Contactors with manually-operated.

Acti9 iCT contactors can be combined with auxiliary control, protection and indication functions.
b Acti9 iCT contactors can be used to remote control applications in alternative networks:
v lighting, heating, ventilation, roller blinds, sanitary hot water,
v mechanical ventilation systems, etc,
v load-shedding of non-priority circuits.
b The 3P+N Contactor comes with a reinforced neutral pole. It will bring robustness to control 3-phase loads or single-phase loads requiring
group control.

Contactors Contactors auxiliaries


Acti9 iCT 2P
PB106120-34

PB106124-34

PB106123-34

PB107751-34
PB106115-35

manual control Indication Interference Dual control Control and


Acti9 iCT 3P+N Acti9 iACTs Acti9 iACTc indication 24 V DC
b This auxiliary Acti9 iACTp b Used to control Acti9 iACT24
A9C24763_Image-35

allows indication or b This auxiliary is an a contactor in b Allows control and


control of the "open" interference impulse-type indication of a 230 V AC
or "closed" position suppressor which limits mode or to contactor from the Acti9
of the contactor overvoltages on the combine latched Smartlink or by a PLC,
power contacts control circuit or impulse-type by 24 V DC signals
control orders b Also allows control
by a maintained signal

Time delay Acti9 iATEt


PB106125-34

This auxiliary is used to time delay for Acti9 iCT and iTL.
Acti9 iCT 4P According to cabling, there are 5 possible time delay types:
PB106105-35

v 1 for iTL
v 4 for iCT
Function type A: late closing Function type C: late opening
Delay energizing of contactor b Energize the contactor by closing a push
Function type B: time delay button
b Energize the contactor by closing b The time delay starts when the control
a push button contacts are opened
b The time delay starts as soon as
the control contacts are closed b Operate the contactor for a pre-determined
time from the moment of energizing

Choice of Choice
50 Hz contactors
of 50 Hz contactors
Type Type Contactor Contactor Manually-operated
Manually-operated
contactors contactors
Rating RatingA A16 20
16 25
20 40
25 63
40 100
63 16
100 25
16 40
25 63
40 63
Auxiliaries Auxiliaries Contactors
Contactors that that can be
can be equipped equipped
with with auxiliaries
auxiliaries
iACTs indication
iACTs indication Yes Yes
Yes Yes
Yes Yes Yes Yes
auxiliary auxiliary
iACTpBy
iACTp protection protection
yellow By
Noyellow No
No No
Yes Yes No No
Yes Yes
auxiliary auxiliary
clips clips
iACTc, iATEt iACTc,By iATEt
yellow By
Noyellow No
No No
Yes Yes No No
Yes Yes
controlclips
control auxiliary auxiliary clips
iACT24 iACT24 Non Non
No No (for contactors
Yes Yes (for
230contactors
V - 50 Hz)230 V - 50 Hz) No No (for contactors
Yes Yes (for
230contactors
V - 50 Hz)230 V - 50 Hz)
control auxiliary
control auxiliary

www.schneider-electric.com
Control www.schneider-electric.com

Remote control
Acti9 iCT contactors (cont.)

b Insulated terminals IP20


Yellow clip
b Clip-on system for electrical and
mechanical connections between
contactors u 25 A and their auxiliaries
PB106115-39

b Minimum noise

b Large circuit labeling area

b Mechanical contact
position indicator

b Consistent with the entire Acti9 offer and with


all types of lighting
b Manually-operated contactors have a 4-position
selector switch on their front face:
v automatic operating mode
v temporary "ON" override
v permanent "ON" override: used to lock the
contactor in the ON position during installation
maintenance
v shutdown

Choice of 60 Hz contactors
Contactor Manually-operated contactors
16 25 40 63 40
Contactors that can be equipped with auxiliaries
Yes Yes

No Yes Yes

No Yes Yes

No Yes No

www.schneider-electric.com
Control www.schneider-electric.com

Remote control
Acti9 iCT contactors (cont.)

Catalog numbers
Acti9 iCT contactors - 50 Hz
Type Width in 9 mm
modules
1P Rating (In) Control voltage Contact
(V AC) (50 Hz)
AC7a AC7b
A1 1 16 A 6A 12 1NO A9C22011 2
DB103373-5

24 1NO A9C22111 2
48 1NO A9C22211 2
A2 2 220 1NO A9C22511 2
230…240 1NO A9C22711 2
25 A 8.5 A 220 1NO A9C20531 2
230…240 1NO A9C20731 2
2P
A1 R1 R3 16 A 6A 12 2NO A9C22012 2
DB122915

24 2NO A9C22112 2
48 2NO A9C22212 2
A2 R2 R4 220 2NO A9C22512 2
230...240 2NO A9C22712 2
A1 1 R1 12 1NO+1NC A9C22015 2
DB103377-11

24 1NO+1NC A9C22115 2
220 1NO+1NC A9C22515 2
A2 2 R2 230...240 1NO+1NC A9C22715 2
20 A - 230...240 2NO A9C22722 2
A1 1 3 25 A 8.5 A 24 2NO A9C20132 2
DB103375-10

48 2NO A9C20232 2
220 2NO A9C20532 2
A2 2 4 230...240 2NO A9C20732 2
220 2NC A9C20536 2
230...240 2NC A9C20736 2
40 A 15 A 220...240 2NO A9C20842 4
63 A 20 A 24 2NO A9C20162 4
220...240 2NO A9C20862 4
100 A (*) - 220...240 2NO A9C20882 6
3P
A1 1 3 5 16 A 6A 220…240 3NO A9C22813 4
DB429341

220V~
25 A 8.5 A 220…240 3NO A9C20833 4
240V~
40 A 15 A 220…240 3NO A9C20843 6
A2 2 4 6 63 A 20 A 220…240 3NO A9C20863 6
3P+N
A1 N R1 R3 R5 40 A 15 A 220...240 4NO A9C24740 6
DB429260

220V~
220...240 4NC A9C22740 6
240V~

A2 N R2 R4 R6

A1 N 1 3 5 63 A 20 A 220...240 4NO A9C24763 6


DB429261

220V~
220...240 4NC A9C22763 6
240V~

A2 N 2 4 6

(*) do not use for lighting applications

www.schneider-electric.com
Control www.schneider-electric.com

Remote control
Acti9 iCT contactors (cont.)

Catalog numbers
Acti9 iCT contactors - 50 Hz
Type Width in 9 mm
modules
4P Rating (In) Control voltage Contact
(V AC) (50 Hz)
AC7a AC7b
A1 R1 R3 R5 R7 16 A 6A 24 4NO A9C22114 4
DB122916

220...240 4NO A9C22814 4


220...240 2NO+2NC A9C22818 4
A2 R2 R4 R6 R8 20 A - 220 ...240 4NO A9C22824 4
25 A 8.5 A 24 4NO A9C20134 4
A1 1 3 R1 R3 220...240 4NO A9C20834 4
DB122917

24 4NC A9C20137 4
220...240 4NC A9C20837 4
A2 2 4 R2 R4 220...240 2NO+2NC A9C20838 4
40 A 15 A 220...240 4NO A9C20844 6
A1 1 3 5 7 220...240 4NC A9C20847 6
DB103381-18

63 A 20 A 24 4NO A9C20164 6
220...240 4NO A9C20864 6
A2 2 4 6 8 24 4NC A9C20167 6
220...240 4NC A9C20867 6
A1 1 3 5 R1 220...240 2NO+2NC A9C20868 6
DB122918

220...240 3NO+1NC A9C20869 6


100 A (*) - 220...240 4NO A9C20884 12
A2 2 4 6 R2

(*) do not use for lighting applications

Acti9 iCT manual control contactor 50 Hz


Type Width in 9 mm
modules
2P Rating (In) Control voltage Contact
(V AC) (50 Hz)
AC7a AC7b
A1 1 3 16 A 6A 220 2NO A9C23512 2
DB106317-24

230...240 2NO A9C23712 2


I P
auto 220 1NO+1NC A9C23515 2
O
230...240 1NO+1NC A9C23715 2
A2 2 4
25 A 8,5 A 24 2NO A9C21132 2
A1 1 R1 220 2NO A9C21532 2
DB106318-27

230...240 2NO A9C21732 2


I P
auto 40 A 15 A 24 2NO A9C21142 2
O
220...240 2NO A9C21842 4
A2 2 R2
63 A 20 A 24 2NO A9C21162 4
220...240 2NO A9C21862 4
3P
A1 1 3 5 25 A 8,5 A 220...240 3NO A9C21833 4
DB106319-27

I
40 A 15 A 220...240 3NO A9C21843 6
P
auto
O
A2 2 4 6

www.schneider-electric.com
Control www.schneider-electric.com

Remote control
Acti9 iCT contactors (cont.)

Catalog numbers
Acti9 iCT contactors - 60 Hz
Type Width in 9 mm
modules
1P Rating (In) Control voltage Contact
(V AC) (60 Hz)
AC7a AC7b
A1 1 25 A 8.5 A 127 1NO A9C20431 2
DB103373-5

220 ...240 1NO A9C20631 2

A2 2

2P
A1 R1 R3 A1 1 3 16 A 6A 127 1NO+1NC A9C22415 2
DB122915

DB103375-10

220...240 1NO+1NC A9C22615 2


25 A 8.5 A 127 2NO A9C20432 2
A2 R2 R4 A9C20632 2
A2 2 4 220...240 2NO
127 2NC A9C20436 2
A1 1 R1 220...240 2NC A9C20636 2
DB103377-11

40 A 15 A 127 2NO A9C20442 4


220...240 2NO A9C20642 4
A2 2 R2

3P
A1 1 3 5 25 A 8.5 A 127 3NO A9C20433 4
DB103378-14

220...240 3NO A9C20633 4


40 A 15 A 127 3NO A9C20443 6
A2 2 4 6 220...240 3NO A9C20643 6
63 A 20 A 127 3NO A9C20463 6
220...240 3NO A9C20663 6

Acti9 iCT manual control contactor 60 Hz


Type Width in 9 mm
modules
2P Rating (In) Control voltage Contact
(V AC) (60 Hz)
AC7a AC7b
A1 1 3 40 A 15 A 127 2NO A9C21442 4
DB106317-24

220...240 2NO A9C21642 4


I P
auto
O
A2 2 4

Operation (Manual control contactor)


Position: O Position: auto Position: I Position: I + P
DB123607

Automatic return to
“auto” position

www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors (cont.)

Connection
Type Circuit Rating Lenght Tightening Copper cables
DB123606

tripping torque Rigid Flexible or


with ferrule

DB122945

DB122946
Acti9 iCT PZ1: 4 mm Control 16 - 100 A 9 mm 0.8 N.m 1.5 to 2.5 mm: 1.5 to 2.5 mm:
2 x 1.5 mm2 2 x 2.5 mm2
Power 16 and 25 A 1.5 to 6 mm2 1 to 4 mm2
PZ2: 6 mm 40 A - 63 A 14 mm 3.5 N.m 6 to 25 mm2 6 to 16 mm2
100 A 6 to 35 mm 2
6 to 35 mm2
iACTs, iACTp, PZ1: 4 mm - - 9 mm 0.8 N.m 1.5 to 2.5 mm: 1.5 to 2.5 mm:
iACTc, iATEt 2 x 1.5 mm2 2 x 2.5 mm2

Type Terminals Tightening Copper cables


DB124308

torque Rigid Flexible Flexible or


with ferrule

DB122945

DB123553

DB123554
3.5 mm
PZ1
9 mm
iACT24 Power supply 1 N.m 0.5 to 10 mm2 0.5 to 6 mm2 0.5 to 4 mm2
(N/P) 2 x 0.5 to 2 x 0.5 to 2 x 0.5 to
Input (Y1/Y2) 2 x 2.5 mm2 2 x 2.5 mm2 2 x 2.5 mm2

Ti24 connector connection


Type Catalog Copper cables
DB123580

Spring-loaded
terminals numbers Rigid Flexible
DB122945

DB123553

0.4 x 2.5 mm

Ti24 Interface A9XC2412 1 x 0.5 to 1.5 mm2 1 x 0.5 to 1.5 mm2

Ti24 prefabricated cables connection


Type Catalog numbers Length
Connection for Acti9 Smartlink
6 short prefabricated A9XCAS06 100 mm
PB107754-10

6 medium-sized prefabricated A9XCAM06 160 mm


6 long prefabricated A9XCAL06 870 mm

Connection for PLC type terminals


6 long prefabricated on a single side A9XCAU06 870 mm
PB107755-14

24V
DB404857

Y3
24V
O/C
0V

www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors (cont.)

Technical data
DB123309

Power circuit
Voltage rating (Ue) 1P, 2P 250 V AC
3P, 3P+N, 4P 400 V AC
Frequency 50 Hz or 60 Hz
Type of load See module CA908026
Clip on DIN rail 35 mm.
Endurance (O-C)
Electrical 100,000 cycles
Maximum number of switching operations per day 100
DB123300

Additional characteristics
Insulation voltage (Ui) 500 V AC
Pollution degree 2
Rated impulse withstand voltage (Uimp) 2.5 kV (4 kV for 12/24/48 V AC)
Degree of protection Device only IP20
(IEC 60529) Device in modular IP40
± 30° vertical. enclosure
Operating temperature -5°C to +60°C (1)
Storage temperature -40°C to +70°C
IP20 IP40
DB123311

Tropicalization (IEC 60068-2-30) Treatment 2 (relative humidity 95 % at 55°C)


ELSV compliance (Extra Low Safety Voltage) for 12/24/48 V AC versions
The product control conforms to the SELV (safety extra low voltage) requirements

(1) In the case of contactor mounting in a enclosure for which the interior temperature is in range
between 50°C and 60°C, it is necessary to use a spacer, cat. no. A9A27062, between each
contactor
DB123331

Spacer cat. no. A9A27062

www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors (cont.)

Mounting accessories

DB429257
7 Sealable screw shields 3P, 4P 25 A A9A15921
for top and bottom 2P 40/63 A A9A15922
3P, 40/63 A A9A15923
3P+N, 10
4P
8 9 mm spacer A9A27062
9 Yellow clips A9C15415 11

10 Clip-on terminal markers see module CA907001


11 Comb busbar 3P+N A9XCT712

iCT < 25 A

Auxiliaries
Indication
2 Acti9 iACTs 1NO + 1NC A9C15914
1CO A9C15915
2NO A9C15916
Double control inputs
3 Acti9 iACTc 230 V AC A9C18308
24 V AC A9C18309
Coil suppression blocs
4 Acti9 iACTp 12...48 V AC A9C15919 Only 1 iACTs at
the right of
48...127 V AC A9C15918
Acti9 iCT < 25 A
220...240 V AC A9C15920
Time delay
5 Acti9 iATEt 24...240 V AC A9C15419 iCT u 25 A
Control and indication
6 Acti9 iACT24 230 V AC A9C15924

Only 1 iACTs at
the right of
Acti9 iCT u 25 A

Only 1 iACTc, iATEt, iACTp or iACT24


at the left of Acti9 iCT u 25 A

www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors
Electrical auxiliaries for Acti9 iCT
Indication
Indication Protection
Protection ControlControl
AuxiliariesAuxiliaries
Acti9 iACTs
Acti9 iACTs Acti9 iACTp
Acti9 iACTp Acti9 iACTc
Acti9 iACTc
Type Type Indication Indication Impulse/latched
Impulse/latched
control control
With Open/Close
Withauxiliary
Open/Close
contact
auxiliary contact 2 protection circuits
2 protection circuits
PB106120-34

PB106124-34

PB106123-34
Function Function
b This auxiliary
b This
allows
auxiliary
indication
allows
of the
indication
"open" of the "open"
b This auxiliary
b This
is anauxiliary
interference
is an interference
b This auxiliary,
b This
combined
auxiliary,
withcombined
contactors,
with contactors
or "closed" position
or "closed"
of theposition
contactor
of the
powercontactor
contacts
power contacts
suppressor which
suppressor
limits overvoltages
which limits overvoltages
enables themenables
to be controlled
them to bybe controlled by
on the controlon
circuit
the control circuit 2 order types:2 order types:
v impulse order
v impulse
for localorder
control
for(input
local T)
control (input T)
v latched order
v latched
for centralised
order for
control
centralised control
(input X) (input X)
v the last order
v the
received
last order
takesreceived
priority takes priority

Wiring diagrams
Wiring diagrams
DB123777

DB123778

DB123779

DB123316

DB123315
23 11 23 11 13 13 13 23 13 23 3 1 3 1 T T

24 12 24 12 12 14 12 14 14 24 14 24 4 2 4 2 X X

Mounting Mounting
b Mounted tobthe
Mounted
right of Acti9
to theiCT
right of Acti9 iCT b Mounted tobthe Mounted to the
left of Acti9 b Mounted
left of Acti9
iCT iCT tobthe Mounted
left of Acti9
to the
iCT
left of Acti9 iCT
by yellow clipsby
(1)
yellow clips (1) by yellow clipsby
(1)
yellow clips (1)
b By wires b By wires
Use Use
– – b The iACTpbhas The iACTp has
2 separate and2 separate and power
b Mains Mains power outages:
b outages:
identical
identical circuits, circuits,
allowing allowingvit to
it to be be ms: keeps
< 70 v < 70
its ms:
initialkeeps
statusits initial status
combined withcombined
2 differentwith
one2ondifferent
the v one > on
80 the v > 80 ms: reset
ms: reset
Acti9 by
Acti9 iCT the other iCTwires
the other by wires v put back into put back into
v operation operation by manual
by manual
operation
operation on input X or T.on input X or T.
b Minimum
b Minimum impulse duration:impulse
250 duration:
ms 250 ms
Catalog numbers
Catalog numbers A9C15914 A9C15914
A9C15915 A9C15915
A9C15916 A9C15916 A9C15918 A9C15920
A9C15918 A9C15919 A9C15919 A9C18308
A9C15920 A9C18308
A9C18309 A9C18309

Control voltage
Control
V AC
voltage
24…240
V AC 24…240 48 …127 12
48…48
…127 220
12 …48
…240 230…240
220 …240 230…240
24…48 24…48
(Ue) (Ue)
V DC 24…130 V DC 24…130 – – – –
Control voltage Hzvoltage
Control 50/60Hz 50/60 50/60 50/60 50/60 50/60
frequency frequency
Width in 9 mmWidth in 9 mm1modules
modules 1 2 2 2 2
Auxiliary contact
Auxiliary contact b Mininimum:b10 Mininimum:
mA at 24 V10 mA at 24 V DC/AC
DC/AC – – – –
(breaking capacity)
(breaking capacity) b Maximum: b Maximum:
5 AAC12
v 5 A at 230 VvAC, at 230 V AC, AC12
2 AAC15
v 2 A at 230 VvAC, at 230 V AC, AC15
1 ADC13
v 1 A at 130 VvDC, at 130 V DC, DC13
Number of contacts
Number of contacts 1NO + 1NC 1NO +1CO 1NC 1CO 2NO 2NO – – – –
Operating Operating
°C °C+50°C-5°C to +50°C
-5°C to
temperature temperature
Storage Storage
°C -40°C°C -40°C to +70°C
to +70°C
temperature temperature
Consumption Consumption – – – – OFF load: 3 VA OFF load: 3 VA
Inrush (2): 2 VAInrush (2): 2 VA
Holding (2): 0.2Holding
VA (2)
: 0.2 VA
(1) Electrical
(1) Electrical and mechanical andlink.
mechanical link.
(2) Maximum (2) Maximum of
consumption consumption of all
all contactors contactors controlled.
controlled.
www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors
Electrical auxiliaries for Acti9 iCT (cont.)
ControlControl
(cont.) (cont.)
Acti9 iATEt
Acti9 iATEt
Time delay Time delay
PB106125-34

b This auxiliary
b This
is used
auxiliary
to timeisdelay
used for
to time
Acti9delay
iCT and
for Acti9
iTL. According
iCT and iTL.
to cabling,
Accordingthere
to cabling,
are 5 possible
there are
time5 possible
delay types:
time delay types:
v 1 for iTL v 1 for iTL
v 4 for iCT. v 4 for iCT.
Function type Function
A: late closing
type A: late closing Function type Function
B: time delay
type B: time delay Function type Function
C: late opening
type C: late opening
b Delay energizing
b Delayof contactor.
energizing of contactor.
b Energize theb contactor
Energize the
by closing
contactor by b closing
Energize the b contactor
Energize the
by closing
contactor by Operate theb contactor
b closing Operate the
for contactor for
a push button.a push button. a push button.a push button. a pre-determined
a pre-determined
time from the time
moment
from the moment
b The time delay
b Thestarts
timeasdelay
soonstarts
as theas soon
b The astime
the delay
b The
starts
timewhen
delaythe of energizing.
starts when the of energizing.
control contacts
control
are closed.
contacts are closed.control contacts control
are opened.
contacts are opened.
DB123321

DB124104

DB123323

DB123324

U U U U U U U U
1 1 1 1 1 1 1 1
0 0 0 0 0 0 0 0
A1 1 A1 1 A1 1 A1 1 A1 1 A1 1 A1 1 A1 1
iCT iCT iCT iCT iCT iCT iCT iCT
A2 0 A2 0 t A2 t 0 A2 0 t A2 t 0 A2 0 t A2 t 0 A2 0 t t
T T T T T T T T

b Mounted tobthe
Mounted
left of Acti9
to the
iCT
left
byofyellow
Acti9 iCT
clipsby
(1)
yellow clips (1)

A9C15419 A9C15419

24…240 24…240
24…110 24…110
50/60 50/60

2 2
– –

– –
-20°C to +50°C
-20°C to +50°C

-40°C to +80°C
-40°C to +80°C

Off-load: 5 VAOff-load: 5 VA
Inrush (2): 3 A Inrush (2): 3 A
Holding (2): 0.2Holding
A (2)
: 0.2 A

www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors
Electrical auxiliaries for Acti9 iCT (cont.)
Control and indication
Auxiliary Acti9 iACT24
Type Control and indication 24 V DC
With Ti24 connector
PB107751-34

Function
b This auxiliary allows a contactor to be interfaced with the Acti9 Smartlink interface or a programmable logic controller (PLC)
in 24 V DC (control, O/C indication)
b 230 V AC control
Wiring diagrams
Acti9 Smartlink or PLC Acti9 Smartlink or PLC
DB124313

DB124441
Out In In Out In In

24 V DC 24 V DC
P 24 V Y3 24V O/C 0V
0V P 24 V Y3 24V O/C 0V
0V
Ti24 Ti24
iACT24 iACT24

P P
OFF
ON Auto

Wiring with exclusive selector Wiring for non-exclusive 230 V AC and 24 V DC controls
230 V AC control (Y1 = 0) / 24 V DC control (Y1 = 1)
Mounting
b To the left of the Acti9 iCT contactor using the yellow clips (1).
b When an iACT24 is used, the A1/A2 terminals of the contactors should not be wired. Only the yellow clips integral with the iACT24
should be used for connection to the coil.
Utilization
b 230 V AC interface:
v Y1: enabling of 24 V DC control (Y1 = 1) or inhibition of 24 V DC control (Y1 = 0).
v Y2: 230 V pulse control
b "Ti24" 24 V DC interface:
v Y3: 24 V DC control of Acti9 iCT closing on rising edge and opening on falling edge
v reading of the contactor status (opened or closed) from the position of the integrated O/C auxiliary contact
v monitoring of connection of the "Ti24" terminal block by the upstream system (PLC, supervision system) via the 24 V terminal (in the
centre of the Ti24 terminal block)
Catalog numbers A9C15924

Control voltage V AC 230, +10 %, -15 % (Y2)


(Ue)
V DC 24, ± 20 % (Y3)
Control voltage Hz 50/60
frequency
Insulation voltage V AC 250
(Ui)
Rated impulse kV 8 (OVC IV)
withstand voltage
(Uimp)
Pollution degree 3
Degree of protection IP20B device only
IP40 device in modular enclosure
Width in 9 mm modules 2
Auxiliary contact (O/C) 24 V DC protected output, min. 2 mA, max. 100 mA
Ti24
Contact 1 O/C operating category AC 14
Operating °C -25°C to +60°C
temperature
Storage °C -40°C to +80°C
temperature
Consumption <1 W
Standard IEC/EN 60947-5-1
(1) Mechanical and electrical link.

www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors
Accessories for Acti9 iCT
Security
Accessories Sealable screw shields Yellow clips Spacer
PB104485-15

PB104486-15

PB104487-15

PB106143-10

PB104483-40
Function
b Designed to cover terminals to avoid contact with device screws. b Ensure the mechanical b Required to reduce temperature
b Allow sealing and/or electrical link rise of modular devices installed side
between contactors and by side.
their auxiliaries. b Recommended to separate
b For Acti9 iCT: b For Acti9 iCT: b For Acti9 iCT: b For Acti9 iCT: u 25 A electronic devices (thermostat,
3P, 4P - 25 A 2P - 40/63 A 3P, 3P+N, 4P - 40/63 A programmable clock, etc.) from
electromechanical devices (relays,
contactors).
Set of 10 upstream / 10 downstream 10 5
Catalog numbers A9A15921 A9A15922 A9A15923 A9C15415 A9A27062

Width in 9 mm modules 4 4 6 – 1
Number of poles 3P, 4P 2P 3P, 3P+N, 4P – –

www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors
Accessories for Acti9 iCT
Security
Accessories Sealable screw shields Yellow clips Spacer
PB104485-15

PB104486-15

PB104487-15

PB106143-10

PB104483-40
Function
b Designed to cover terminals to avoid contact with device screws. b Ensure the mechanical b Required to reduce temperature
b Allow sealing and/or electrical link rise of modular devices installed side
between contactors and by side.
their auxiliaries. b Recommended to separate
b For Acti9 iCT: b For Acti9 iCT: b For Acti9 iCT: b For Acti9 iCT: u 25 A electronic devices (thermostat,
3P, 4P - 25 A 2P - 40/63 A 3P, 3P+N, 4P - 40/63 A programmable clock, etc.) from
electromechanical devices (relays,
contactors).
Set of 10 upstream / 10 downstream 10 5
Catalog numbers A9A15921 A9A15922 A9A15923 A9C15415 A9A27062

Width in 9 mm modules 4 4 6 – 1
Number of poles 3P, 4P 2P 3P, 3P+N, 4P – –

www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors
Technical advice for Acti9 iCT (cont.)
Operation of the iACT24
O/C 24 V DC output

DB124314
Acti9 iCT contacts

O/C 24 V DC output

T T

Parameter Min Max


T Time delay between iACT24 closing and indication 100 ms 200 ms

b Minimum duration of 230 V AC pulse (Y2): 200 ms.


b 30 iACT24 closing or opening actuations are authorized per minute: Minimum time
delay between 2 actuations on the iACT4 via Y1,Y2, Y3 (closing or opening of the
Acti9 iCT coil): 220 ms.
b 10 closing or opening actuations spaced 440 milliseconds apart are authorized
following no loading of the iACT24 during a period of 20 seconds.

Wiring with exclusive selector Wiring for non-exclusive 230 V AC and 24 V DC controls
230 V AC control (Y1 = 0) / 24 V DC control (Y1 = 1)
DB124443

DB124444

Out In In Acti9 Smartlink or PLC Out In In Acti9 Smartlink or PLC


24 V DC 24 V DC
0V 0V
P 24 V Y3 24V O/C 0V P 24 V Y3 24V O/C 0V
Ti24 Ti24
iACT24 iACT24

P P
OFF
ON Auto
DB124314

DB124442

Y1 230 V AC Y1 230 V AC

Y2 230 V AC Y2 230 V AC

Y3 24 V DC Y3 24 V DC

Acti9 iCT status Acti9 iCT status

www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors
Technical advice for Acti9 iCT (cont.)
Consumption
Acti9 iCT contactors - 50 Hz
Type
1P Rating (In) Control voltage Consumption Max.
(V AC) (50 Hz) power
AC7a AC7b Holding Inrush
16 A 5A 12 3.8 VA 15 VA 1.3 W A9C22011
24 3.8 VA 15 VA 1.3 W A9C22111
48 3.8 VA 15 VA 1.3 W A9C22211
220 3.8 VA 15 VA 1.3 W A9C22511
230…240 2.7 VA 9.2 VA 1.2 W A9C22711
25 A 8.5 A 220 3.8 VA 15 VA 1.3 W A9C20531
230…240 2.7 VA 9.2 VA 1.2 W A9C20731
2P
16 A 5A 12 3.8 VA 15 VA 1.3 W A9C22012
24 3.8 VA 15 VA 1.3 W A9C22112
48 3.8 VA 15 VA 1.3 W A9C22212
220 3.8 VA 15 VA 1.3 W A9C22512
230...240 2.7 VA 9.2 VA 1.2 W A9C22712
12 3.8 VA 15 VA 1.3 W A9C22015
24 3.8 VA 15 VA 1.3 W A9C22115
220 3.8 VA 15 VA 1.3 W A9C22515
230...240 2.7 VA 9.2 VA 1.2 W A9C22715
20 A 6.4 A 230...240 2.7 VA 9.2 VA 1.2 W A9C22722
25 A 8.5 A 24 3.8 VA 15 VA 1.3 W A9C20132
48 3.8 VA 15 VA 1.3 W A9C20232
220 3.8 VA 15 VA 1.3 W A9C20532
230...240 2.7 VA 9.2 VA 1.2 W A9C20732
220 3.8 VA 15 VA 1.3 W A9C20536
230...240 2.7 VA 9.2 VA 1.2 W A9C20736
40 A 15 A 220...240 4.6 VA 34 VA 1.6 W A9C20842
63 A 20 A 24 4.6 VA 34 VA 1.6 W A9C20162
220...240 4.6 VA 34 VA 1.6 W A9C20862
100 A (*) - 220...240 6.5 VA 53 VA 2.1 W A9C20882
3P
16 A 5A 220…240 4.6 VA 34 VA 1.6 W A9C22813
25 A 8.5 A 220…240 4.6 VA 34 VA 1.6 W A9C20833
40 A 15 A 220…240 6.5 VA 53 VA 2.1 W A9C20843
63 A 20 A 220…240 6.5 VA 53 VA 2.1 W A9C20863
3P+N
40 A 15 A 220...240 6.5 VA 53 VA 2.1 W A9C24740
220...240 6.5 VA 53 VA 2.1 W A9C22740
63 A 20 A 220...240 6.5 VA 53 VA 2.1 W A9C24763

220...240 6.5 VA 53 VA 2.1 W A9C22763


4P
16 A 5A 24 4.6 VA 34 VA 1.6 W A9C22114
220...240 4.6 VA 34 VA 1.6 W A9C22814
220...240 4.6 VA 34 VA 1.6 W A9C22818
20 A 6.4 A 220 ...240 4.6 VA 34 VA 1.6 W A9C22824
25 A 8.5 A 24 4.6 VA 34 VA 1.6 W A9C20134
220...240 4.6 VA 34 VA 1.6 W A9C20834
24 4.6 VA 34 VA 1.6 W A9C20137
220...240 4.6 VA 34 VA 1.6 W A9C20837
220...240 4.6 VA 34 VA 1.6 W A9C20838
40 A 15 A 220...240 6.5 VA 53 VA 2.1 W A9C20844
220...240 6.5 VA 53 VA 2.1 W A9C20847
63 A 20 A 24 6.5 VA 53 VA 2.1 W A9C20164
220...240 6.5 VA 53 VA 2.1 W A9C20864
24 6.5 VA 53 VA 2.1 W A9C20167
220...240 6.5 VA 53 VA 2.1 W A9C20867
220...240 6.5 VA 53 VA 2.1 W A9C20868
220...240 6.5 VA 53 VA 2.1 W A9C20869
100 A (*) - 220...240 13 VA 106 VA 4.2 W A9C20884
(*) do not use for lighting applications

www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors
Technical advice for Acti9 iCT (cont.)
Consumption
Acti9 iCT manual control contactor 50 Hz
Type
2P Rating (In) Control voltage Consumption Max.
(V AC) (50 Hz) power
AC7a AC7b Holding Inrush
16 A 5A 220 2.7 VA 9.2 VA 1.2 W A9C23512
230...240 2.7 VA 9.2 VA 1.2 W A9C23712
220 3.8 VA 15 VA 1.3 W A9C23515
230...240 2.7 VA 9.2 VA 1.2 W A9C23715
25 A 8.5 A 24 3.8 VA 15 VA 1.3 W A9C21132
220 2.7 VA 9.2 VA 1.2 W A9C21532
230...240 2.7 VA 9.2 VA 1.2 W A9C21732
40 A 15 A 24 4.6 VA 34 VA 1.6 W A9C21142
220...240 4.6 VA 34 VA 1.6 W A9C21842
63 A 20 A 24 4.6 VA 34 VA 1.6 W A9C21162
220...240 4.6 VA 34 VA 1.6 W A9C21862
3P
25 A 8.5 A 220...240 4.6 VA 34 VA 1.6 W A9C21833
40 A 15 A 220...240 6.5 VA 53 VA 2.1 W A9C21843
4P
25 A 8.5 A 24 4.6 VA 34 VA 1.6 W A9C21134
220...240 4.6 VA 34 VA 1.6 W A9C21834
40 A 15 A 24 6.5 VA 53 VA 2.1 W A9C21144
220...240 6.5 VA 53 VA 2.1 W A9C21844
63 A 20 A 24 6.5 VA 53 VA 2.1 W A9C21164
220...240 6.5 VA 53 VA 2.1 W A9C21864

Acti9 iCT contactors - 60 Hz


Type

1P Rating (In) Control voltage Consumption Max.


(V AC) (60 Hz) power
AC7a AC7b Holding Inrush
25 A 8.5 A 127 3.8 VA 15 VA 1.3 W A9C20431
220 ...240 2.7 VA 9.2 VA 0.9 W A9C20631
2P
16 A 5A 127 3.8 VA 15 VA 1.3 W A9C22415
220...240 2.7 VA 9.2 VA 0.9 W A9C22615
25 A 8.5 A 127 3.8 VA 15 VA 1.3 W A9C20432
220...240 2.7 VA 9.2 VA 0.9 W A9C20632
127 3.8 VA 15 VA 1.3 W A9C20436
220...240 2.7 VA 9.2 VA 0.9 W A9C20636
40 A 15 A 127 4.6 VA 34 VA 1.6 W A9C20442
220...240 4.6 VA 34 VA 1.6 W A9C20642
3P
25 A 8.5 A 127 4.6 VA 34 VA 1.6 W A9C20433
220...240 4.6 VA 34 VA 1.6 W A9C20633
40 A 15 A 127 6.5 VA 53 VA 2.1 W A9C20443
220...240 6.5 VA 53 VA 2.1 W A9C20643
20 A 127 6.5 VA 53 VA 2.1 W A9C20463
220...240 6.5 VA 53 VA 2.1 W A9C20663

www.schneider-electric.com
Control
Remote control
Acti9 iCT contactors
Dimensions for Acti9 iCT
Dimensions (mm)
68 68
DB123376

DB123609
49 49
18 36 5.5 23.5 36 54 5.5 23.5

81 45 85 45

2.5 2.5

Acti9 iCT 16/25 A Acti9 iCT 40/63 A

68
DB123610

49
54 108 5.5 23.5

85 45

2.5

Acti9 iCT 100 A

73
73
DB123381

DB123382

68
68
49
49
36 54 5.5 23.5
18 36 5.5 23.5

85 45
81 45

2.5 2.5

Acti9 iCT manual control contactor 16/25 A Acti9 iCT manual control contactor 40/63 A

68 68 60
DB123379

DB124316

DB123380

49 49 44
9 5.5 23.5 18 5.5 18 5

81 45 45 81 45
81

iACTs iACT24 iATEt


iACTp
iACTc

www.schneider-electric.com
Schneider Electric is the global specialist in energy management and automation.
With revenues of €25 billion in FY2014, our 170,000 employees serve customers
in over 100 countries, helping them to manage their energy and process in ways
that are safe, reliable, efficient and sustainable. From the simplest of switches
to complex operational systems, our technology, software and services improve
the way our customers manage and automate their operations. Our connected
technologies will reshape industries, transform cities and enrich lives.

At Schneider Electric, we call this Life Is On.

Schneider Electric

United Kingdom Ireland


Stafford Park 5, Head office, Block A
Telford Maynooth Business Campus
Shropshire Maynooth, Co. Kildare
TF3 3BL W23 Y7X0