Professional Documents
Culture Documents
Archive of SID
Archive of SID
I D
NSERC / Hydro-Quebec / UQAC Industrial Chair on Atmospheric Icing of Power Network
Equipment (CIGELE) and Canada Research Chair on Engineering of Power Network
Atmospheric Icing (INGIVRE),
f S
Université du Québec à Chicoutimi, Chicoutimi, Québec, Canada, G7H 2B1
http://www.cigele.ca
*On leave from the Power and Water Institute of Technology (PWIT), Tehran, Iran
http://www.pwit.ac.ir
Abstract:
Some investigations on corona discharge were
e o
freezing precipitation conditions. Corona discharge
and radio interference generated in high voltage
i v
carried out using several inter-electrode distances
and two values of high voltage electrode-point
radii in order to determine electric field strength.
substations and on transmission lines can cause
problems with the reception of radio
communication equipment, and also adversely
c h
The characteristics of pre-breakdown voltage and
current between two electrodes in air insulation
were determined, under 60 Hz ac high voltages.
affect the performance of power line carrier
signals. At higher voltage levels, and certainly at
voltages of 230 kV and above, losses and
r
The methodology for these experiments is interference due to the corona effect can be the
described and the results are discussed and used to dominant factor in determining the physical size of
establish mathematical and empirical models for conductors for transmission lines, as well as the
A
predicting flashover on high voltage devices. The
results confirm that there is good concordance
between the electric fields obtained using the finite
element method and those of experiments.
www.SID.ir
Measuring of Corona Discharge Inception Voltage to Determine Electric Field over the non-homogenous Electrodes in the Air insulatio
1383 - ﺗﻬﺮان- ﻧﻮزدﻫﻤﻴﻦ ﻛﻨﻔﺮاﻧﺲ ﺑﻴﻦ اﻟﻤﻠﻠﻲ ﺑﺮق
especially for different insulation materials, complex boundary conditions. For this purpose,
particularly those used under precipitation several software packages have been introduced,
conditions. one of which is based on MATLAB software,
The electrical properties of insulating materials are known as PDETOOL. The program is designed to
much influenced by the aging process. Natural determine precisely the distribution of electric
aging is caused by electrical and thermal stress potential and electric field for different electrode
and, furthermore, electrical and thermal overload geometries and different insulation materials.
accelerates the process and reduces the dielectric However, the application may exclude highly non-
strength. Electrical aging strictly depends on the uniform electric field distributions (electrode
electric field and it can be initiated by two types of geometry is normally too small in comparing with
discharges, including (i) discharges or breakdowns the minimum distance between the electrodes). For
that cover the entire insulation distance, possibly example, EPRI has developed equation 4 by using
leading to the complete destruction of the device, the image method, for electric field calculation at
or (ii) partial discharges that bridge a part of the the vicinity of the high voltage conductors of
insulation of the device [4]. transmission lines [2-3, 9].
Several reported power outages in cold-climate
regions have been due to flashovers at the surface
of ice and snow covering insulators [5-7]. This is
mostly due to non-uniform voltage distribution
E=
I D V
⎛2⋅D⎞
r × ln⎜ ⎟
⎝ r ⎠
(4)
S
along the ice-covered insulator, when a highly
conductive water film is formed at the ice surface,
in series with air gaps during a melting period. A where r and D are respectively the radius and
considerable voltage drop appears along the air
gaps, and due to the high electric stress, corona
discharge and local arcs appear. These phenomena
have been the subject of study by researchers at
o
voltage.
f
height of the conductor, and V is the applied
e
CIGELE/INGIVRE [5-7].
The main objective of this paper is to determine
V ⎛ ⎞
v
the electric field strength based on corona D
E= ⎜ 0.94 + 0.8 ⎟ (5)
i
discharge inception. Based on the laboratory 4⋅D ⎝ r ⎠
investigations, mathematical and empirical models
h
for predicting flashover on high voltage devices where r and D are the radius of the high voltage
were elaborated. electrode (sphere) and the distance between two
r c
The general solution for the electric field in
electrodes (sphere-plane) respectively. Also, for
cases in which the corona discharge is generated
on the surface of high voltage electrode, Le Roy
has introduced equation 6 to determine maximum
A
insulating systems can be obtained by electrostatic electric field at the point of discharge channel
equations, as follows [8]: (Figure 2).
r ρ
Div( E ) = (1) 2 ⋅V
ε0 E= (6)
r ⎛ 4⋅ D⎞
E = − grad (V ) (2) r ln⎜ ⎟
⎝ r ⎠
where E, V, ρ and ε 0 are electric field, electric where r is the high voltage rod radius and d is the
potential, charge volume, and permittivity of air gap length between the point of initiated corona
respectively. discharge and the ground electrode. It must be
Combining equations 1 and 2 yields; noted that the equations 4, 5 and 6 are presented
ρ for the condition if D>>r.
Div( grad (V )) = − (3)
ε0
2
www.SID.ir
Measuring of Corona Discharge Inception Voltage to Determine Electric Field over the non-homogenous Electrodes in the Air insulatio
1383 - ﺗﻬﺮان- ﻧﻮزدﻫﻤﻴﻦ ﻛﻨﻔﺮاﻧﺲ ﺑﻴﻦ اﻟﻤﻠﻠﻲ ﺑﺮق
V
E= (8)
⎛r +d ⎞
r ln⎜ ⎟
⎝ r ⎠
Figure (1): Electrodes for non-uniform distribution where ‘r’ is equal to the radius of the inner
electric field conductor and ‘d’ is the radial distance between
inner conductor and screen.
D
maximal at the surface of the inner sphere with
radius ‘r’ and can be determined by equation (9).
I V d +r
S
E= ⋅ (9)
r d
e
be equal to the breakdown voltage of the insulation
developed between two plates. With limited plate surface
v
(using Rogowski’s surface) and for 1-cm layer of
i
3- Method for electric field determination air insulation, the breakdown voltage is nearly 32
kv, depending on the atmospheric conditions. In all
As mentioned in Section 2, if the volume charge
h
other cases of electrodes, the critical voltage
density in equation 3 is zero, the electric field leading to corona discharge is smaller than their
c
between electrodes is calculated by solving the breakdown voltage, due to non-uniform electric
Laplace’s equation, considering that the electrodes field distribution. The amplitude of the current
r
are equi-potential surfaces. The following three
electrode configurations can only be calculated
A
precisely by theoretical solution of Laplace’s
equation [1, 11]:
3
www.SID.ir
Measuring of Corona Discharge Inception Voltage to Determine Electric Field over the non-homogenous Electrodes in the Air insulatio
1383 - ﺗﻬﺮان- ﻧﻮزدﻫﻤﻴﻦ ﻛﻨﻔﺮاﻧﺲ ﺑﻴﻦ اﻟﻤﻠﻠﻲ ﺑﺮق
1 cm and the distance between sphere-plane distance is adjusted to 1 cm and the voltage is then
electrode system is less than the diameter of sphere applied. It is observed that, at the instant of
(d<2r). initiation of the bright spot of corona discharge,
breakdown occurs. Indeed, this confirms that in
this electrode system, the electric field is
completely uniform and the maximum value of
electric field is equal to the average. The peak
value of applied voltage is 32.5 kV, generating an
electric field of 32.5 kV/cm, which is the minimum
required to start corona discharge under test
conditions. This electric field strength is selected
as criterion for measuring the electric field for the
other electrode system. For this case, figure 5
shows the potential and electric field distribution
obtained by finite element method.
a) plate-plate electrodes
I D
f S
e o Figure (4) Schematic diagram of the experimental
v
set-up
h i
r c
b) rod-plate electrodes
A
electric field
4
www.SID.ir
Measuring of Corona Discharge Inception Voltage to Determine Electric Field over the non-homogenous Electrodes in the Air insulatio
1383 - ﺗﻬﺮان- ﻧﻮزدﻫﻤﻴﻦ ﻛﻨﻔﺮاﻧﺲ ﺑﻴﻦ اﻟﻤﻠﻠﻲ ﺑﺮق
large spike appears in the current waveform. observed that the electric fields obtained using the
Figure 6 shows an example of the variation of finite element method is very close to those of
applied voltage and current passing through the experiments which are obtained at the condition of
rod-sphere system electrode, as a function of time, 20°C, 75.2 cmHg and relative humidity equal to
when the distance between the electrodes is 1 cm. 24%. Also, the electric field determined by the
The current waveform is not a sinusoidal wave relation used by EPRI [2] is closer to the
because of the occurring the partial discharge experimental value, compared with the electric
corona around the high voltage electrode and it field determined by other equations. This
contains the high order harmonics. comparison can only be valid for highly non-
The electric field was determined for several inter- uniform electric field distributions. Clearly,
electrode distances and the results are shown in additional studies are needed to improve the results
figure 7. Figure 7-a shows the variation of electric for large domains of electrode rod-point radii and
field as a function of radius of the rod point, when distance between the electrodes. Also, the type of
its distance from the sphere is equal to 1 cm. applied voltage and atmospheric conditions should
Figure 7-b shows the variation of electric field as a be considered, as well as using precise methods to
function of distance between the electrodes, when detect corona discharge inception.
the radius of the rod point is 0.92 mm. It may be
I D
f S
e o
i v
a) voltage waveform
c h b) current waveform
Figure (6): Variation of applied voltage and current passing through the rod-sphere system
electrode as a function of time
A r
I
Transmission Line”, 12th Iranian Conference on
Electrical Engineering, ICEE2004, Mashhad,
S
electrodes. 11-13 May 2004
The electric field is measured for several inter- [10]- Le Roy George et al, Les Propriétés
electrode distances and two values of high Diélectrique de l’Air et les très Haute
voltage electrode-point radii. The results
confirm that the electric fields obtained using
the finite element method is very close to those
of experiments. Also, the electric field
o
Tensions’, 1988
f
[11]-F.H. Kreuger, “Industrial High Voltage
(Field, Dielectrics and Constructions)”, Delft
University Press, Netherlands, 1991
e
determined by the relation used by EPRI is [12]- G.D. Theophilus et al, “Problems of Pre-
closer to the experimental results, compared to breakdown Current Measurement in 60 Hz
v
other equations. This comparison is clearly Vacuum Breakdown Studies”, Pergamon press
i
valid for highly non-uniform electric field ltd/ Printed in UK, Vaccum/ volume 20,
distributions. number 1969.
h
[13]- J. Nieto- Salazar, et al. “Transient Current
References: and Light Emission Associated to the
c
Propagation of Pre-breakdown Phenomena in
Water”, CEIDP, 2003
r
[1]- Naidu “High Voltage Engineering”
2001, [14]- Jin Jianming, “The finite element method
[2]- General Electric Co., Transmission Line in electro-magnetics”, J. Wiley & sons, 1993
A
Reference Book “345 kv and above”, 2nd [15]- Klaus-Jürgen Bathe, “Finite element
edition, Electric Power Research Institute, procedures”, Prentice Hall, 199
1982.
[3]- Central Station Engineers of Westinghouse
Electric Corporation, “Electrical Transmission
and Distribution Reference Book”, 4th edition,
1964, USA
[4]- H. Borsi, et al. “Contribution to the
Clarification of Partial Discharge Behavior in
Insulating Liquids Using the Schlieren
Technique” ETEP, Vol 1, No. 5 ,
September/October 1991
[5]- C. Volat, M. Farzaneh and A. Gakwaya
“Dynamic Variations of Potential and Electric
Field Distributions around an Ice-covered
Insulator during Ice Accretion”, IWAIS, Brno,
Czech Republic, 17-20 June, 2002
6
www.SID.ir