1MRG042112 - en Relion - 670 - 650 - Series - SAM600-IO - Version - 2

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

Relion® 670 650 series and

SAM600-IO version 2.2.6 Ed2 and


Ed2.1 - PIXIT

Date 2023-02-21

Based Upon UCAIug Server PIXIT Template version 22

Document Review Summary:

Reviewer Role Reviewer Organization Review Review Sta-


Name Date tus

Architect Johan Sälj PGGA/GAP/TPTB 2023-03-01 No remarks


To be re-
vised

PREPARED STATUS SECURITY LEVEL


2023-03-01 Carl Byman Approved Internal
APPROVED DOCUMENT KIND
2023-03-03 Johan Svensson Declaration of conformity
TITLE
Relion® 670 650 series and SAM600-IO version 2.2.6 Ed2 and Ed2.1 - PIXIT
OWNING ORGANIZATION DOCUMENT ID REV. LANG. PAGE
2877 GA Products 1MRG042112 A en 1/26
Hitachi Energy Sweden AB © 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

Contents
1. Introduction .................................................................................................................................................. 3

2. PIXIT for Documentation ............................................................................................................................. 3

3. PIXIT for Configuration ................................................................................................................................ 3

4. PIXIT for Association model ........................................................................................................................ 3

5. PIXIT for Server model ................................................................................................................................. 5

6. PIXIT for Data set model .............................................................................................................................. 7

7. PIXIT for Substitution model ....................................................................................................................... 7

8. PIXIT for Setting group control model ....................................................................................................... 8

9. PIXIT for Reporting model ........................................................................................................................... 8

10. PIXIT for Logging model ............................................................................................................................ 10

11. PIXIT for GOOSE publish model ............................................................................................................... 12

12. PIXIT for GOOSE subscribe model ........................................................................................................... 13

13. PIXIT for GOOSE performance .................................................................................................................. 16

14. PIXIT for IEC 61869-9 publisher –Not supported .................................................................................... 16

15. PIXIT for IEC 61869-9 subscriber –Not supported ................................................................................. 17

16. PIXIT for Control model ............................................................................................................................. 18

17. PIXIT for Time synchronisation model ..................................................................................................... 22

18. PIXIT for File transfer model ..................................................................................................................... 24

19. PIXIT for Service tracking model .............................................................................................................. 25

20. Revisions .................................................................................................................................................... 26

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 2/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

1. Introduction
This document specifies the protocol implementation extra information for testing (PIXIT) of the IEC 61850 inter-
face in
Relion 670 series (REB670, REC670, RED670, REG670, REL670, RER670, RES670 and RET670),
Relion 650 series (REB650, REC650, RED650, REL650, REQ650 and RET650) and
Relion SAM600-IO
all of version 2.2.6, with firmware version 2.2.19.1 and when configured in Edition 2 or 2.1 mode.

Together with the PICS and the MICS the PIXIT forms the basis for a conformance test according to IEC 61850-
10. The PIXIT entries contain information, which is not available in the PICS, MICS, TICS documents or SCL
file.

Each table specifies the PIXIT for applicable ACSI service model as structured in IEC 61850-10. The “Ed” column
indicates if the entry is applicable for IEC 61850 Edition 1 and/or Edition 2. A hyphen (“-“) in the Ed column
indicates the PIXIT entry is not applicable for any version.

2. PIXIT for Documentation

ID Ed Description Value / Clarification

Do1 2 How to expose required firmware versions not pre- Firmware versions are presented on
sent in the datamodel the local HMI

<additional items>

3. PIXIT for Configuration


ID Ed Description Value / Clarification

Cf1 2 Can IED tool export ICD file or IID file (SICS I12) ICD: Y

IID: Y

<additional items>

4. PIXIT for Association model


ID Ed Description Value / Clarification

As1 1 Maximum number of clients that can set-up an asso- 8


ciation simultaneously

As2 1,2 TCP_KEEPALIVE value. The recommended range 10 seconds


is 1..20s

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 3/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

As3 1,2 Lost connection detection time 25 seconds


Note:
TCP_KEEPIDLE = 10 s
TCP_KEEPCNT = 3
TCP_KEEPINIT = 8 s
TCP_KEEPINTVL = 5 s
10 s after association start to begin
sending keepalive, and 15 s (3 * 5 s) to
detect lost connection.

As4 - Authentication is not supported yet

As5 1,2 What association parameters are necessary for suc- Transport selector Y
cessful association:
Session selector Y
Called values:
Presentation selector Y

AP Title N

AE Qualifier N

Calling values: Transport selector n/a

Session selector n/a

Presentation selector n/a

AP Title n/a

AE Qualifier n/a

Note: Association request is not sup-


ported

As6 1,2 If association parameters are necessary for associa- Transport selector 0001
tion, describe the correct Called values:
Session selector 0001

Presentation selector 00000001

AP Title n/a

AE Qualifier n/a

Calling parameters: Transport selector n/a

Session selector n/a

Presentation selector n/a

AP Title n/a

AE Qualifier n/a

Note: Association request is not sup-


ported

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 4/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

As7 1,2 What is the maximum and minimum MMS PDU size Max MMS PDU size 32000 bytes

Min MMS PDU size 1024 bytes

As8 1,2 What is the maximum start up time after a power 180 seconds
supply interrupt

As9 1,2 Does this device function only as test equipment? N

(test equipment need not have a non-volatile config-


uration; but it cannot be part of the substation auto-
mation system)

As10 2 How does the server behave when the associate re- N/A
quest fails

<additional items>

5. PIXIT for Server model


ID Ed Description Value / Clarification

Sr1 1,2 Which analogue value (MX) quality bits are supported Validity:
(can be set by server)
Y Good,

Y Invalid,

N Reserved,

Y Questionable
Detail Quality

Y Overflow

Y OutofRange

N BadReference

N Oscillatory

N Failure

Y OldData

N Inconsistent

N Inaccurate

Miscellaneous:

Y Source

Y Test

Y OperatorBlocked

See Remark 1.

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 5/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

Sr2 1,2 Which status value (ST) quality bits are supported Validity:
(can be set by server)
Y Good,

Y Invalid,

N Reserved,

Y Questionable

Detail Quality

N BadReference

N Oscillatory

N Failure

Y OldData

N Inconsistent

N Inaccurate

Miscellaneous:

Y Source

Y Test

Y OperatorBlocked
Note: Operator blocked functionality
is only supported on LN class XCBR
and XSWI containing DPC. No other
CDCs are supported.
See Remark 1.

Sr3 - What is the maximum number of data object refer- Deprecated


ences in one GetDataValues request

Sr4 - What is the maximum number of data object refer- Deprecated


ences in one SetDataValues request

Sr5 1 Which Mode values are supported 1 On Y

[On-]Blocked Y

Test Y

Test/Blocked Y

Off Y
Note 1: LD0/LLN0 (Root LD) ac-
cepts the values On, Blocked, Test

1 IEC 61850-6:2009 clause 9.5.6 states that if only a subrange of the enumeration value set is supported, this
shall be indicated within an ICD file by an enumeration type, where the unsupported values are missing

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 6/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification


and Test/Blocked but not Off for Mod.
Only values ON and Off are ac-
cepted by the individual LNs for Mod.
Other values results in negative re-
sponse.
Note 2: If the PST setting “Remote-
ModControl” is set to “Off” (default),
all writes to Mod will be rejected.

<additional items>

Remark 1: Writes to the data attribute subQ accepts the values Invalid, Good, Test, Questionable + Operator-
Blocked and Invalid + OperatorBlocked.

6. PIXIT for Data set model


ID Ed Description Value / Clarification

Ds1 1 What is the maximum number of data elements in one maxAttributes = 330
data set (compare ICD setting) maximum FCDAs = 150
-> whatever limit is reached first.

Ds2 1 How many persistent data sets can be created by one No online creation
or more clients

(this number includes predefined datasets)

Ds3 1 How many non-persistent data sets can be created by No online creation
one or more clients

<additional items>

7. PIXIT for Substitution model


ID Ed Description Value / Clarification

Sb1 1 Are substituted values stored in volatile memory N

<additional items>

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 7/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

8. PIXIT for Setting group control model


ID Ed Description Value / Clarification

Sg1 1 What is the number of supported setting groups for Maximum 6, default value = 1
each logical device The amount of setting groups is set
in the configuration.
There is only one setting group con-
trol block, it is defined in the Root LD.

Sg2 1,2 What is the effect of when and how the non-volatile The settings are directly stored in
storage is updated volatile memory, the non-volatile stor-
age is updated by a background pro-
(compare IEC 61850-8-1 §16.2.4)
cess. Normally within a minute after
ConfirmEditSGValues.

Sg3 1 Can multiple clients edit the same setting group N

Sg4 1 What happens if the association is lost while editing a The SE values changes are lost, the
setting group EditSG is reset to 0

Sg5 1 Is EditSG value 0 allowed Y

Sg6 2 When ResvTms is not present how long is an edit set- 60 seconds
ting group locked

Sg7 2 Can the active setting group be changed locally Y

Can a setting in the active setting group be changed Y


locally
<additional items>

9. PIXIT for Reporting model


ID Ed Description Value / Clarification

Rp1 1 The supported trigger conditions are integrity Y

(compare PICS) data change Y

quality change Y

data update Y

general interrogation Y

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 8/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

Rp2 1 The supported optional fields are sequence-number Y

report-time-stamp Y

reason-for-inclusion Y

data-set-name Y

data-reference Y

buffer-overflow Y

entryID Y

conf-rev Y

segmentation Y

Rp3 1,2 Can the server send segmented reports Y


(when not supported the device shall refuse an as-
sociation request with a smaller than minimum
PDU size)

Rp4 1,2 Mechanism on second internal data change notifi- Send report immediately
cation of the same analogue data value within
buffer period (Compare IEC 61850-7-2 Ed2
§17.2.2.9)

Rp5 1 Multi client URCB approach Each URCB is visible to one client
only, independent of indexed of
(compare IEC 61850-7-2:2003 §14.2.1)
non-indexed URCB.

Note: The defined URCB can be


seen by all clients, but changes
from one client can only be seen by
that client.

Rp6 - What is the format of EntryID Deprecated

Rp7 1,2 What is the buffer size for each BRCB or how 50000 bytes for each used BRCB
many reports can be buffered (max. 100 BRCB instances)

Rp8 - Pre-configured RCB attributes that are dynamic, Deprecated


compare SCL report settings

Rp9 1 May the reported data set contain:

- structured data objects Y

- data attributes Y

Rp10 1,2 What is the scan cycle for binary events 3 ms

Is this fixed, configurable Fixed

Rp11 1 Does the device support to pre-assign a RCB to a Y (*)


specific client in the SCL

Rp12 2 After restart of the server is the value of ConfRev Restored from original configuration
restored from the original configuration or retained
prior to restart

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 9/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

Rp13 1,2 Does the server accept any client to configure / en- Y
able an RCB with
BRCB.ResvTms=-1 or URCB.Resv=T?
IP-address N
What fields are used to do the identification?
AP-Title N

AE-Qualifier N

<other field> N

Rp14 1,2 a) When BRCB.ResvTms is exposed, what is the a) Implicit / Auto - reservation
default value for BRCB.ResvTms if client does not
- Ed 1.0 => N/A (not available)
write (must be > 0)
- Ed 2.0 => 60 seconds (but because
of “Rp13” any client can connect
=> after loss of TPAA the BRCB in-
stance is free immediately)

- Ed 2.1 => N/A (client must write


BRCB.ResvTms)

or
or
b)
b) When BRCB.ResvTms is not exposed, what is
the internal reservation time - Ed 1.0 and Ed 2.0 => 0 seconds
(must be >= 0)
- Ed2.1 = N/A (BRCB.ResvTms must
Note: for Amd1 the client shall always write be exposed)
ResvTms and ResvTms is mandatory
(note: both cannot be N/A)

Rp15 2 Is data model db=0 supported N

<additional items>
(*) In case of unbuffered reporting the Resv attribute will be set to 'true' for pre-assigned URCBs. How-
ever the device will not block other clients from connecting the RCBs. Client has to utilise the pre-assign
information from SCL to enable the correct RCB instance.

10. PIXIT for Logging model


ID Ed Description Value / Clarification

Lg1 1,2 What is the default value of LogEna N/A

(Compare IEC 61850-8-1 §17.3.3.2.1, the default


value should be FALSE)

Lg2 - What is the format of EntryID Deprecated

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 10/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

Lg3 1,2 Are there multiple Log Control Blocks that specify N/A
the Journaling of the same MMS NamedVariable
and TrgOps and the Event Condition

(Compare IEC 61850-8-1 §17.3.3.3.2)

Lg4 - Pre-configured LCB attributes that cannot be Deprecated, the information is al-
changed online ready available in SCL

Lg5 1 Which TrgOps are supported for logging dchg N/A

qchg N/A

(note Ed2 and up requires support for dupd N/A


all TrgOps)
integrity N/A

<additional items>

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 11/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

11. PIXIT for GOOSE publish model


ID Ed Description Value / Clarification

Gp1 1,2 Can the test (Ed1) / simulation (Ed2) flag in the N
published GOOSE be set

Note: simulation is intended for test equipment

Gp2 1 What is the behaviour when the GOOSE publish NdsCom=T


configuration is incorrect
DUT keeps GoEna=F

Gp3 1,2 Published FCD supported common data classes ACD, ACT, APC, ASG, BSC, CMV,
are DPC, INC, ING, INS, MV, ORG,
SPC, SPG, SPS, ENC, ENS
Arrays are not supported

Gp4 1,2 What is the maximum value of TAL (maxTime) Configured by SCL GoCB

Is it fixed or configurable MaxTime 60 000 ms

Gp5 1,2 What is the fastest retransmission time 1 ms

Gp6 - Can the GOOSE publish be turned on / off by us- Deprecated


ing SetGoCBValues(GoEna)
See PICS –SetGoCBValues

Gp7 1,2 What is the initial GOOSE sqNum after restart sqNum = 1

Gp8 1 May the GOOSE data set contain:

- structured data objects (FCD) Y

- timestamp data attributes Y

Gp9 1,2 Does Server or ICT refuse GOOSE payload da- Y


taset length greater than SCSM supports?

<additional items>

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 12/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

12. PIXIT for GOOSE subscribe model


ID Ed Description Value / Clarification

Gs1 1,2 What elements of a subscribed GOOSE mes- Y destination MAC address
sage are checked to decide the message is
Y APPID
valid and the allData values are accepted? If
yes, describe the conditions. Y gocbRef

Notes: Y timeAllowedtoLive

the VLAN tag may be removed by an Ethernet Y datSet


switch and shall not be checked
Y goID
the simulation flag shall always be checked
N T
(Ed2)
Y stNum
the ndsCom shall always be checked
Y sqNum

Y simulation / test

Y confRev

Y numDatSetEntries

Y out-of-order dataset members

Note 1: GOOSE with wrong dataset


order will result in not updating data
with mismatching type.

Note 2: GOOSE with TAL = 0ms is


not checked since TAL= 0ms is
treated as GOOSE with TAL = 100ms.

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 13/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

Gs2 1,2 When is a subscribed GOOSE marked b) message does not arrive by 2x TAL +
as lost 100ms

(TAL = time allowed to live value from the Note 1: GOOSE with TAL= 0ms is treated
last received GOOSE message) as GOOSE with TAL = 100ms and ac-
cepted.

Note 2: Not received GOOSE data, at


timeout the internal value will be substituted
with default value and quality set to invalid
Note 3: Following wrong/missmatching
elements in the GOOSE header are lead-
ing to invalid data for the application after
2*TAL timeout:
- AppID
- gocbRef
- missing goID

Following wrong/missmatching elements


in the GOOSE header are leading to im-
mediate invalid data for the application:
- datSet
- goID
- test
- confRev
- ndsCom
- numDatSetEntries, checked in header
of the message, but not that actual
DatSetEntries match

Note 4:
DataSetEntries are checked for type
match. Not matching types will result in not
updating data with mismatching type val-
ues.

Note 5:
Mismatching numDatSetEntries in header
compared to real entries lead to updating
the matching ones and ignoring the non-
existing or too many ones

Note 6:
GOOSE with wrong dataset order will re-
sult in not updating data with mismatching
type.

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 14/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

Gs3 1,2 What is the behaviour when one or more sub- Internal data is set to invalid if
scribed GOOSE messages is not received or 2*TAL+100ms (time allowed to live) of
syntactically incorrect (missing GOOSE) received GOOSE times out. If there is
no timeout but sqNum is jumping for-
ward (missing individual messages) the
data is still accepted and threated as
valid.

Note: At timeout, the internal value will


be substituted with default value and
quality set to invalid.

Gs4 1,2 What is the behaviour when a subscribed sqNum is monitored for internal error
GOOSE message is out-of-order tracking, but data is still accepted in
case of stNum change.

Gs5 1,2 What is the behaviour when a subscribed Is ignored


GOOSE message is duplicated

Gs6 1 Does the device subscribe to GOOSE mes- Y, with the VLAN tag
sages with/without the VLAN tag
Y, without the VLAN tag

Gs7 1 May the GOOSE data set contain:

- structured data objects (FCD) Y

- timestamp data attributes Y

Gs8 1,2 Subscribed FCD supported common data ACD, ACT, ASG, BSC, CMV, DPC, INC,
classes are ING, INS, MV, SPC, SPG, SPS, ENC,
ENS
Arrays are not supported

Gs9 1 Are subscribed GOOSE with test=T (Ed1) / Y


simulation=T (Ed2) accepted in test/simulation
When subscribed GOOSE is received
mode
with simulated = T device will not accept
unless parameter AllowSimulation = Yes
and Sys.LPHD.Sim.stVal=true

Gs10 1,2 Max number of dataset members Unlimited

Gs11 1 Is Fixed-length encoded GOOSE supported Y


Note: Ed2 Am1 requires support

Gs12 Amd1 Is IEC 62351-6 security supported N

Gs13 Amd1 How does the subscriber handle incoming The incoming GOOSE will be treated as
data flagged as test when the destination invalid. The values will be substituted
LN.Beh is On or Blocked? with default values

Is this behavior: fixed

<additional items>

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 15/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

13. PIXIT for GOOSE performance


ID Ed Description Value / Clarification

Gf1 1,2 Performance class P1 = 3 ms

Gf2 1,2 GOOSE ping-pong processing method Scan cycle based

Gf3 1,2 Application logic scan cycle (ms) Max. 100 ms

Min. 3 ms

Gf4 1 Maximum number of data attributes in GOOSE da- 150


taset (value and quality has to be counted as sepa-
rate attributes)

<additional items>

14. PIXIT for IEC 61869-9 publisher –Not supported

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 16/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

15. PIXIT for IEC 61869-9 subscriber –Not supported

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 17/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

16. PIXIT for Control model


ID Ed Description Value / Clarification

Ct1 1 What control models are supported DOns: Y

(compare ICD file for Ed2) SBOns: N

DOes: Y

SBOes: Y

Ct2 1,2 Is the control model fixed, configurable Fixed


and/or dynamic
Can be changed for some functions
using the PCM 600 IED tool.

Ct3 - Is TimeActivatedOperate supported Deprecated


(compare PICS or SCL)

Ct4 - Is “operate-many” supported (compare Deprecated, see sboClass in


sboClass) datamodel (ICD)

Ct5 1 Will the DUT activate the control output Y


when the test attribute is set in the Se-
lectWithValue and/or Operate request
(when N test procedure Ctl2 is applica-
ble)

Ct6 - What are the conditions for the time (T) Deprecated
attribute in the SelectWithValue and/or
Operate request

Ct7 - Is pulse configuration supported (com- Deprecated


pare pulseConfig)

Ct8 1,2 What is the behaviour of the DUT when Y synchrocheck


the check conditions are not set Y interlock-check
DUT uses the check value to perform
the check (Ed2)
This is only applicable for CSWI.pos,
otherwise ignored.
This behaviour is: Fixed

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 18/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

Ct9 1,2 Which additional cause diagnosis are N Unknown


supported Y Not-supported
Y Blocked-by-switching-hierarchy
N Select-failed
Y Invalid-position
Y Position-reached
N Step-limit
Y Blocked-by-Mode
Y Blocked-by-process
Y Blocked-by-interlocking
Y Blocked-by-synchrocheck
Y Command-already-in-execution
N Blocked-by-health
Y 1-of-n-control
Y Abortion-by-cancel
Y Time-limit-over
N Abortion-by-trip

Y Object-not-selected

Edition 1 specific values:

N Parameter-change-in-

execution (Ed1 semantics)

Edition 2 specific values:

Y Object-already-selected

N No-access-authority

N Ended-with-overshoot

N Abortion-due-to-deviation

N Abortion-by-communication-loss

Y Blocked-by-command

Y None

Y Inconsistent-parameters

Y Locked-by-other-client

N Parameter-change-in-execution
(Ed2 semantics)

Ct10 1,2 How to force a “test-not-ok” respond with Issued on negative response due to
SelectWithValue request addCause values e.g. Time-limit-over,
blocked-by-interlocking etc. And the
TEST-bit is set when issuing the com-
mand.

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 19/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

Ct11 1,2 How to force a “test-not-ok” respond with Not Supported


Select request

Ct12 1,2 How to force a “test-not-ok” respond with DOns: Issues on negative response
Operate request due to e.g. wrong switching hierarchy
or interlocking.

SBOns: Not Supported

DOes: Issues on negative response


due to e.g. wrong switching hierarchy
or interlocking.

SBOes: Issued on negative response


due to addCause values e.g. Time-
limit-over, blocked-by-interlocking etc.
And the TEST-bit is set when issuing
the command.

Ct13 1,2 Which origin categories are accepted in Y bay-control (1)


control direction
Y station-control (2)

Y remote-control (3)

Y automatic-bay (4)

Y automatic-station (5)

Y automatic-remote (6)

Y maintenance (7)

N process (8)

Note: orCat is only checked for DPC


and SPC DATA’s for the logical node
types CSWI, ATCC, SPC8GAPC,
VSGAPC and SLGAPC (*). This
means that the check of Local/Re-
mote switch will only occur for these
attributes.

Note: (1) and (4) requires that both


local and remote commands are al-
lowed

Ct14 1,2 What happens if the orCat value is not DOns: Rejected for the above(*)
supported or invalid
SBOns: Not Supported

DOes: Rejected for the above(*)

SBOes: Rejected for the above(*)

Rejected means returning addCause


Blocked-by-switching-hierarchy

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 20/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

Ct15 1,2 Does the IED accept a SelectWithValue / DOns: Y


Operate with the same control value as
SBOns: N/A
the current status value
DOes: Y

SBOes: Y

Configurable Y
Is this behaviour configurable

Ct16 1 Does the IED accept a select/operate on DOns: N


the same control object from 2 different
SBOns: N/A
clients at the same time
DOes: N

SBOes: N

Ct17 1 Does the IED accept a Select/Se- SBOns: N/A


lectWithValue from the same client when
SBOes: N
the control object is already selected (Tis-
sue #334)

Ct18 1 Deprecated

Ct19 - Can a control operation be blocked by Deprecated


Mod=Off or [On-]Blocked (Compare
PIXIT-Sr5)

Ct20 1,2 Does the IED support local / remote op- Y


eration

Ct21 1,2 Does the IED send an InformationReport SBOns: N/A


with LastApplError as part of the Operate
DOns: N
response- for control with normal security

Ct22 2 How to force a “parameter-change-in-ex- SBOns:


ecution”
SBOes:

“Parameter-change-in-execution” not
Supported

Ct23 1,2 How many SBOns/SBOes control objects SBOns: n = “N/A“


can be selected at the same time?
SBOes: n = “multiple”

Ct24 1,2 Can a controllable object be forced to Y


keep its old state e.g. Internal Controlla-
ble Objects may not be accessible to
force this, whereas a switch like Circuit
Breaker outside the DUT can?

Ct25 1,2 When CDC=DPC is supported, is it pos- Y


sible to have DPC (Controllable Double
Point) go to the intermediate state? (00)

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 21/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

Ct26 1,2 Name an enhanced security control point DOes: LD0/CTRL/SCSWI.Pos


(if any) with a finite operate timeout
SBOes: LD0/CTRL/SCSWI.Pos

Specify the operate timeout (in millisec-


DOes: 30000 ms (default, configu-
onds)
rable in PST)

SBOes: 30000 ms (default, configu-


rable in PST)

(ctlModel must be set to SBO Enh in


PCM600)

Ct27 2 Does the IED support control objects with DOns: Y


external signals?
SBOns: N/A

DOes: Y

SBOes: Y

Ct28 Deprecated, kept as placeholder

Ct29 Amd1 Does the IED support DOns: Y, orCat 1 or 4: N


XCBR/XSWI.Loc=False and
SBOns: N/A
LLN0/CSWI.Loc=True
DOes: Y, orCat 1 or 4: N

SBOes: Y, orCat 1 or 4: N
When yes, does the IED accept the con-
trol when orCat=1 or 4 Local

Ct30 2 What is the Operate timeout? Configurable in PCM600 (parameter


tExecutionFB, default value 30 s)

operTimeout in datamodel (as RO)

17. PIXIT for Time synchronisation model


ID Ed Description Value / Clarification

Tm1 1 What time quality bits are supported (may be set Y LeapSecondsKnown
by the IED)
Y ClockFailure
Note: Ability to set ClockNotSynchronized and
Y ClockNotSynchronized
LeapSecondKnown is mandatory in Ed2

Tm2 1,2 Describe the behaviour when all time server(s) Assert CNS after lost detection time
cease to respond
The event timestamps get ClockFail-
ure and ClockNotSynchronized status.

What is the time server lost detection time 33 seconds for PTP
5 minutes for SNTP

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 22/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

ID Ed Description Value / Clarification

Tm3 1,2 How long does it take to take over the new time 16 seconds for PTP
from time server For SNTP it depends on how much the
time differ, from 2 seconds to 12
minutes.

Tm4 1,2 When is the time quality bit “ClockFailure” set Upon start of the IED, until synchroni-
zation is received.
As the time system is self-adjusted,
the clock failure is set when the esti-
mated deviation exceeds a certain
value. Due to the good internal accu-
racy, this deviation occurs in the order
of > 30 days.

Tm5 1 When is the time quality bit “Clock not Synchro- When connection to all time servers is
nized” set lost (see PIXIT-Tm2)

Note: For Ed2 and up, CNS is set ac-


cording to PIXIT Tm2

Tm6 - Is the timestamp of a binary event adjusted to the Deprecated


configured scan cycle

Tm7 1 Does the device support time zone and daylight Y


saving

Tm8 1,2 Which attributes of the SNTP response packet are Y Leap indicator not equal to 3
validated
N Mode is equal to SERVER

Y OriginateTimestamp is equal
to value sent by the SNTP client as
Transmit Timestamp

Y RX/TX timestamp fields are


checked for reasonableness

Y SNTP version 3 and/or 4

N other (describe)

Tm9 1,2 When COMTRADE files are supported do these Supported Y


have local time or UTC time and is this configura- The START Time inside the
ble
COMTRADE file is in local time.
The file time attribute of the individual
file(s) is in local time, but the zip-file is
in UTC
No, not Configurable

<additional items>

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 23/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

18. PIXIT for File transfer model


ID Ed Description Value / Clarification

Ft1 1 What is the structure of files and directories Flat file system with pseudo folders

Where are the COMTRADE files stored /COMTRADE/

Are COMTRADE files zipped and what files are For COMTRADE 1999 there are two
included in each zip file Zip files
drec_x.zip incl.: .hdr, .cfg and .dat
drec_xh.zip incl.: .hdr
The .hdr file in the drec_x.zip file con-
tain extra information.
For COMTRADE 2013 there is one
drec_x.zip incl.: .cff file.

The IED can also create Through


Fault Reports. The through fault re-
ports are stored in a flat file system
with pseudo folder
“/FAULTREPORT/”.
The report files are zip xml-files.

Ft2 1,2 Directory names are separated from the file “/” or “\” for FTP
name by
“/” for MMS

Ft3 1 The maximum file name size including path (rec- 200 chars
ommended 64 chars)

Ft4 1,2 Are directory/file name case sensitive Not case sensitive

Ft5 1,2 Maximum file size for SetFile Not Supported

Ft6 1 Is the requested file path included in the MMS Y


fileDirectory respond file name
(Ed2: always complete path)

Ft7 1 Is the wild card supported in the MMS fileDirec- Yes, wild card = * or “.” or empty string
tory request

Ft8 1,2 Is it allowed that 2 clients get a file at the same Y same file
time
Y different files

Ft9 1,2 Which files can be deleted Only COMTRADE, see remark 1, and
FAULTREPROT files

<additional items>
Remark1: For COMTRADE 99; when one of the files (drec_x.zip, drec_xh.zip) is deleted, the IED itself will re-
move the other disturbance file.

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 24/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

19. PIXIT for Service tracking model


ID Ed Description Value / Clarification

Tr1 2 Which ACSI services are tracked by LTRK.GenTrk Associate, Abort, Release,
SetEditSGValue and DeleteFile

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 25/26
© 2023 Hitachi Energy. All rights reserved.
RELION® 670 650 SERI ES AND SAM60 0 -IO VERSION 2.2.6 ED2 AND E D2.1 - PIXIT

20. Revisions
Rev. Page (P) Description Date Dept./Init.
Chapt. (C)
A All New Document 2023-02-21
TPTB/CB

STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE


Approved Internal 1MRG042112 A en 26/26
© 2023 Hitachi Energy. All rights reserved.