1. Introduction
This document specifies the protocol implementation extra information for testing (PIXIT) of the IEC 61850 inter-
face in
Relion 670 series (REB670, REC670, RED670, REG670, REL670, RER670, RES670 and RET670),
Relion 650 series (REB650, REC650, RED650, REL650, REQ650 and RET650) and
Relion SAM600-IO
all of version 2.2.6, with firmware version 2.2.19.1 and when configured in Edition 2 or 2.1 mode.
Together with the PICS and the MICS the PIXIT forms the basis for a conformance test according to IEC 61850-
10. The PIXIT entries contain information, which is not available in the PICS, MICS, TICS documents or SCL
file.
Each table specifies the PIXIT for applicable ACSI service model as structured in IEC 61850-10. The “Ed” column
indicates if the entry is applicable for IEC 61850 Edition 1 and/or Edition 2. A hyphen (“-“) in the Ed column
indicates the PIXIT entry is not applicable for any version.
Do1 2 How to expose required firmware versions not pre- Firmware versions are presented on
sent in the datamodel the local HMI
<additional items>
Cf1 2 Can IED tool export ICD file or IID file (SICS I12) ICD: Y
IID: Y
<additional items>
As5 1,2 What association parameters are necessary for suc- Transport selector Y
cessful association:
Session selector Y
Called values:
Presentation selector Y
AP Title N
AE Qualifier N
AP Title n/a
AE Qualifier n/a
As6 1,2 If association parameters are necessary for associa- Transport selector 0001
tion, describe the correct Called values:
Session selector 0001
AP Title n/a
AE Qualifier n/a
AP Title n/a
AE Qualifier n/a
As7 1,2 What is the maximum and minimum MMS PDU size Max MMS PDU size 32000 bytes
As8 1,2 What is the maximum start up time after a power 180 seconds
supply interrupt
As10 2 How does the server behave when the associate re- N/A
quest fails
<additional items>
Sr1 1,2 Which analogue value (MX) quality bits are supported Validity:
(can be set by server)
Y Good,
Y Invalid,
N Reserved,
Y Questionable
Detail Quality
Y Overflow
Y OutofRange
N BadReference
N Oscillatory
N Failure
Y OldData
N Inconsistent
N Inaccurate
Miscellaneous:
Y Source
Y Test
Y OperatorBlocked
See Remark 1.
Sr2 1,2 Which status value (ST) quality bits are supported Validity:
(can be set by server)
Y Good,
Y Invalid,
N Reserved,
Y Questionable
Detail Quality
N BadReference
N Oscillatory
N Failure
Y OldData
N Inconsistent
N Inaccurate
Miscellaneous:
Y Source
Y Test
Y OperatorBlocked
Note: Operator blocked functionality
is only supported on LN class XCBR
and XSWI containing DPC. No other
CDCs are supported.
See Remark 1.
[On-]Blocked Y
Test Y
Test/Blocked Y
Off Y
Note 1: LD0/LLN0 (Root LD) ac-
cepts the values On, Blocked, Test
1 IEC 61850-6:2009 clause 9.5.6 states that if only a subrange of the enumeration value set is supported, this
shall be indicated within an ICD file by an enumeration type, where the unsupported values are missing
<additional items>
Remark 1: Writes to the data attribute subQ accepts the values Invalid, Good, Test, Questionable + Operator-
Blocked and Invalid + OperatorBlocked.
Ds1 1 What is the maximum number of data elements in one maxAttributes = 330
data set (compare ICD setting) maximum FCDAs = 150
-> whatever limit is reached first.
Ds2 1 How many persistent data sets can be created by one No online creation
or more clients
Ds3 1 How many non-persistent data sets can be created by No online creation
one or more clients
<additional items>
<additional items>
Sg1 1 What is the number of supported setting groups for Maximum 6, default value = 1
each logical device The amount of setting groups is set
in the configuration.
There is only one setting group con-
trol block, it is defined in the Root LD.
Sg2 1,2 What is the effect of when and how the non-volatile The settings are directly stored in
storage is updated volatile memory, the non-volatile stor-
age is updated by a background pro-
(compare IEC 61850-8-1 §16.2.4)
cess. Normally within a minute after
ConfirmEditSGValues.
Sg4 1 What happens if the association is lost while editing a The SE values changes are lost, the
setting group EditSG is reset to 0
Sg6 2 When ResvTms is not present how long is an edit set- 60 seconds
ting group locked
quality change Y
data update Y
general interrogation Y
report-time-stamp Y
reason-for-inclusion Y
data-set-name Y
data-reference Y
buffer-overflow Y
entryID Y
conf-rev Y
segmentation Y
Rp4 1,2 Mechanism on second internal data change notifi- Send report immediately
cation of the same analogue data value within
buffer period (Compare IEC 61850-7-2 Ed2
§17.2.2.9)
Rp5 1 Multi client URCB approach Each URCB is visible to one client
only, independent of indexed of
(compare IEC 61850-7-2:2003 §14.2.1)
non-indexed URCB.
Rp7 1,2 What is the buffer size for each BRCB or how 50000 bytes for each used BRCB
many reports can be buffered (max. 100 BRCB instances)
- data attributes Y
Rp12 2 After restart of the server is the value of ConfRev Restored from original configuration
restored from the original configuration or retained
prior to restart
Rp13 1,2 Does the server accept any client to configure / en- Y
able an RCB with
BRCB.ResvTms=-1 or URCB.Resv=T?
IP-address N
What fields are used to do the identification?
AP-Title N
AE-Qualifier N
<other field> N
Rp14 1,2 a) When BRCB.ResvTms is exposed, what is the a) Implicit / Auto - reservation
default value for BRCB.ResvTms if client does not
- Ed 1.0 => N/A (not available)
write (must be > 0)
- Ed 2.0 => 60 seconds (but because
of “Rp13” any client can connect
=> after loss of TPAA the BRCB in-
stance is free immediately)
or
or
b)
b) When BRCB.ResvTms is not exposed, what is
the internal reservation time - Ed 1.0 and Ed 2.0 => 0 seconds
(must be >= 0)
- Ed2.1 = N/A (BRCB.ResvTms must
Note: for Amd1 the client shall always write be exposed)
ResvTms and ResvTms is mandatory
(note: both cannot be N/A)
<additional items>
(*) In case of unbuffered reporting the Resv attribute will be set to 'true' for pre-assigned URCBs. How-
ever the device will not block other clients from connecting the RCBs. Client has to utilise the pre-assign
information from SCL to enable the correct RCB instance.
Lg3 1,2 Are there multiple Log Control Blocks that specify N/A
the Journaling of the same MMS NamedVariable
and TrgOps and the Event Condition
Lg4 - Pre-configured LCB attributes that cannot be Deprecated, the information is al-
changed online ready available in SCL
qchg N/A
<additional items>
Gp1 1,2 Can the test (Ed1) / simulation (Ed2) flag in the N
published GOOSE be set
Gp3 1,2 Published FCD supported common data classes ACD, ACT, APC, ASG, BSC, CMV,
are DPC, INC, ING, INS, MV, ORG,
SPC, SPG, SPS, ENC, ENS
Arrays are not supported
Gp4 1,2 What is the maximum value of TAL (maxTime) Configured by SCL GoCB
Gp7 1,2 What is the initial GOOSE sqNum after restart sqNum = 1
<additional items>
Gs1 1,2 What elements of a subscribed GOOSE mes- Y destination MAC address
sage are checked to decide the message is
Y APPID
valid and the allData values are accepted? If
yes, describe the conditions. Y gocbRef
Notes: Y timeAllowedtoLive
Y simulation / test
Y confRev
Y numDatSetEntries
Gs2 1,2 When is a subscribed GOOSE marked b) message does not arrive by 2x TAL +
as lost 100ms
(TAL = time allowed to live value from the Note 1: GOOSE with TAL= 0ms is treated
last received GOOSE message) as GOOSE with TAL = 100ms and ac-
cepted.
Note 4:
DataSetEntries are checked for type
match. Not matching types will result in not
updating data with mismatching type val-
ues.
Note 5:
Mismatching numDatSetEntries in header
compared to real entries lead to updating
the matching ones and ignoring the non-
existing or too many ones
Note 6:
GOOSE with wrong dataset order will re-
sult in not updating data with mismatching
type.
Gs3 1,2 What is the behaviour when one or more sub- Internal data is set to invalid if
scribed GOOSE messages is not received or 2*TAL+100ms (time allowed to live) of
syntactically incorrect (missing GOOSE) received GOOSE times out. If there is
no timeout but sqNum is jumping for-
ward (missing individual messages) the
data is still accepted and threated as
valid.
Gs4 1,2 What is the behaviour when a subscribed sqNum is monitored for internal error
GOOSE message is out-of-order tracking, but data is still accepted in
case of stNum change.
Gs6 1 Does the device subscribe to GOOSE mes- Y, with the VLAN tag
sages with/without the VLAN tag
Y, without the VLAN tag
Gs8 1,2 Subscribed FCD supported common data ACD, ACT, ASG, BSC, CMV, DPC, INC,
classes are ING, INS, MV, SPC, SPG, SPS, ENC,
ENS
Arrays are not supported
Gs13 Amd1 How does the subscriber handle incoming The incoming GOOSE will be treated as
data flagged as test when the destination invalid. The values will be substituted
LN.Beh is On or Blocked? with default values
<additional items>
Min. 3 ms
<additional items>
DOes: Y
SBOes: Y
Ct6 - What are the conditions for the time (T) Deprecated
attribute in the SelectWithValue and/or
Operate request
Y Object-not-selected
N Parameter-change-in-
Y Object-already-selected
N No-access-authority
N Ended-with-overshoot
N Abortion-due-to-deviation
N Abortion-by-communication-loss
Y Blocked-by-command
Y None
Y Inconsistent-parameters
Y Locked-by-other-client
N Parameter-change-in-execution
(Ed2 semantics)
Ct10 1,2 How to force a “test-not-ok” respond with Issued on negative response due to
SelectWithValue request addCause values e.g. Time-limit-over,
blocked-by-interlocking etc. And the
TEST-bit is set when issuing the com-
mand.
Ct12 1,2 How to force a “test-not-ok” respond with DOns: Issues on negative response
Operate request due to e.g. wrong switching hierarchy
or interlocking.
Y remote-control (3)
Y automatic-bay (4)
Y automatic-station (5)
Y automatic-remote (6)
Y maintenance (7)
N process (8)
Ct14 1,2 What happens if the orCat value is not DOns: Rejected for the above(*)
supported or invalid
SBOns: Not Supported
SBOes: Y
Configurable Y
Is this behaviour configurable
SBOes: N
Ct18 1 Deprecated
“Parameter-change-in-execution” not
Supported
DOes: Y
SBOes: Y
SBOes: Y, orCat 1 or 4: N
When yes, does the IED accept the con-
trol when orCat=1 or 4 Local
Tm1 1 What time quality bits are supported (may be set Y LeapSecondsKnown
by the IED)
Y ClockFailure
Note: Ability to set ClockNotSynchronized and
Y ClockNotSynchronized
LeapSecondKnown is mandatory in Ed2
Tm2 1,2 Describe the behaviour when all time server(s) Assert CNS after lost detection time
cease to respond
The event timestamps get ClockFail-
ure and ClockNotSynchronized status.
What is the time server lost detection time 33 seconds for PTP
5 minutes for SNTP
Tm3 1,2 How long does it take to take over the new time 16 seconds for PTP
from time server For SNTP it depends on how much the
time differ, from 2 seconds to 12
minutes.
Tm4 1,2 When is the time quality bit “ClockFailure” set Upon start of the IED, until synchroni-
zation is received.
As the time system is self-adjusted,
the clock failure is set when the esti-
mated deviation exceeds a certain
value. Due to the good internal accu-
racy, this deviation occurs in the order
of > 30 days.
Tm5 1 When is the time quality bit “Clock not Synchro- When connection to all time servers is
nized” set lost (see PIXIT-Tm2)
Tm8 1,2 Which attributes of the SNTP response packet are Y Leap indicator not equal to 3
validated
N Mode is equal to SERVER
Y OriginateTimestamp is equal
to value sent by the SNTP client as
Transmit Timestamp
N other (describe)
<additional items>
Ft1 1 What is the structure of files and directories Flat file system with pseudo folders
Are COMTRADE files zipped and what files are For COMTRADE 1999 there are two
included in each zip file Zip files
drec_x.zip incl.: .hdr, .cfg and .dat
drec_xh.zip incl.: .hdr
The .hdr file in the drec_x.zip file con-
tain extra information.
For COMTRADE 2013 there is one
drec_x.zip incl.: .cff file.
Ft2 1,2 Directory names are separated from the file “/” or “\” for FTP
name by
“/” for MMS
Ft3 1 The maximum file name size including path (rec- 200 chars
ommended 64 chars)
Ft4 1,2 Are directory/file name case sensitive Not case sensitive
Ft7 1 Is the wild card supported in the MMS fileDirec- Yes, wild card = * or “.” or empty string
tory request
Ft8 1,2 Is it allowed that 2 clients get a file at the same Y same file
time
Y different files
Ft9 1,2 Which files can be deleted Only COMTRADE, see remark 1, and
FAULTREPROT files
<additional items>
Remark1: For COMTRADE 99; when one of the files (drec_x.zip, drec_xh.zip) is deleted, the IED itself will re-
move the other disturbance file.
Tr1 2 Which ACSI services are tracked by LTRK.GenTrk Associate, Abort, Release,
SetEditSGValue and DeleteFile
20. Revisions
Rev. Page (P) Description Date Dept./Init.
Chapt. (C)
A All New Document 2023-02-21
TPTB/CB