Buku II

BAB V. Syarat-Syarat Teknik dan Gambar


BAB V.3: Technical Specification
TSS A.5: Conductors and Accessories

V. TABLE OF CONTENTS

TSS A.5: CONDUCTORS AND ACCESSORIES...........................................................V-1


1. CODES AND STANDARDS...............................................................................V-1
2. GENERAL........................................................................................................... V-1

PEKERJAAN PENGADAAN DAN PEMASANGAN


FAULT CURRENT LIMITER SUTET 500 kV CIBINONG-TAMBUN i
Buku II
BAB V. Syarat-Syarat Teknik dan Gambar
BAB V.3: Technical Specification
TSS A.5: Conductors and Accessories

TSS A.5: CONDUCTORS AND ACCESSORIES

1. CODES AND STANDARDS

Conductors for busbars and all electrical connections in the outdoor substation
bays shall be in accordance with IEC 61089 or equivalent national standards in
respect of current rating and material analysis.
Type of conductor shall be Hard Drawn Aluminum (HAL) or Aluminum Alloy
(AAC) or Thermal Aluminum Conductor (TAL). Size of busbar conductor and
current rating shall be as specified in Schedule of Technical Particulars and
Guarantees. Busbars shall be strung in continuous conductor lengths for each
span.
Conductors and connectors provided for extending existing connections at each
substation shall be identical with the existing equipment except where otherwise
specified.

2. GENERAL

Materials used for busbars and bay conductors shall be stressed to not more
than two-fifths of their elastic limit. Provision shall be made for expansion and
contraction with variation in conductor temperature.
Busbars shall be arranged so that they may be readily extended in length with a
minimum of disturbance to existing equipment.
All necessary clamps and connectors for connections between the busbars, bay
conductors and equipment for the complete the scope of work shall be provided
under this Contract.
Clamps and connectors shall be of an approved type, preferably type tested.
Connections dependent upon site welding techniques will not be permitted.
Busbars and bay conductors shall be so arranged and supported that under no
circumstances, including short circuit conditions, can the clearances between live
metal and earth or earthed metal work or between conductors be less than the
specified distances.
When dissimilar metals are in contact, approved means shall be provided to
prevent electro-chemical action and corrosion. Unless otherwise approved, joints
and surfaces of copper or copper alloy fittings shall be tinned.
Suspension and tension clamps shall be of approved types and shall be as light
as possible. Those for tension clamp of the busbar conductor shall be
compression type. Suspension and tension clamps shall be designed to avoid
any possibility of deforming the stranded conductor and separating the individual
strands.
Tension conductor clamps shall not permit slipping of, or damage to, or failure of
the complete conductor or any part thereof at a load less than 95 per cent of the

PEKERJAAN PENGADAAN DAN PEMASANGAN


FAULT CURRENT LIMITER SUTET 500 kV CIBINONG-TAMBUN 1
Buku II
BAB V. Syarat-Syarat Teknik dan Gambar
BAB V.3: Technical Specification
TSS A.5: Conductors and Accessories

ultimate strength of the conductor.


Clamps and fittings made of steel or malleable iron shall be galvanized.
The Contractor shall supply all busbars, jumpers, necessary connectors and
clamps for connection between the busbars and all apparatus/equipment even if
not specifically mentioned in the tender specification, bill of quantities and
drawings, but necessary for the proper completion of the work.

PEKERJAAN PENGADAAN DAN PEMASANGAN


FAULT CURRENT LIMITER SUTET 500 kV CIBINONG-TAMBUN 2