H3HK Series

INSTALLATION INSTRUCTIONS
Package Electric Heater Kits
Installation of H3HK Heater Kits (208/240V & 460V) in Packaged Air Conditioners & Packaged Heat Pumps.

IMPORTANT
These instructions are primarily intended to assist qualified individuals experienced in the proper
installation of heating and/or air conditioning appliances. Some local codes require licensed
installation/service personnel for this type equipment. All installations must be in accordance
with these instructions and with all applicable national and local codes and standards.
Read these instructions thoroughly before starting the installation. Follow all precautions and
warnings contained within these instructions and on the unit.
DO NOT DESTROY. PLEASE READ CAREFULLY &
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION .......................2
CLEARANCES.............................................................2
GENERAL INFORMATION ..........................................2
ELECTRICAL SUPPLY ................................................3
Installation .................................................................3
Circuit Options ...........................................................3
Circuit Breakers ......................................................3
Breaker Attachment ................................................4
Attaching to Bracket ................................................4
Breaker Removal ....................................................4
Single Circuit Kit .....................................................4
Terminal Blocks .........................................................4
Staged Heat ..............................................................4
Element Installation ...................................................4
Element Power Wiring ...............................................4
AIRFLOW .....................................................................4
FIGURES & TABLES ...................................................5
Fig. 2. Component Locations..................................5
Fig. 3. Element Support Bracket.............................5
Heater Kit Cross References.....................................6
Table 3. P5RD & P5RF - 13 & 15 SEER. ...............6
Table 4. P6SD - 13 SEER ......................................6
Table 5. Q4SE - 14 SEER ......................................7
Table 6. Q5RD & Q5RF - 13 & 15 SEER................7
Table 7. Q6SD - 13 SEER ......................................8
Electrical Data ...........................................................9
Table 8. P5RD - 2, 2.5, & 3 Ton Units .....................9
Table 9. P5RD - 3.5, 4, & 5 Ton Units .....................9
Table 10. P5RF - 2, 3, 4, & 5 Ton Units ................ 10
Table 11. P6SD - 208/230v Single Phase ............ 11
Table 12. P6SD - 208/230v 3-Phase ................... 11
Table 13. P6SD - 460v 3-Phase ........................... 11
Table 14. Q4SE - 2, 3, 4, & 5 Ton Units ................ 12
Table 15. Q5RD - 2 & 2.5 Ton Units ..................... 13
Table 16. Q5RD - 3, 3.5, 4, & 5 Ton Units ............ 13
Table 17. Q5RF - 3, 3.5, 4, & 5 Ton Units ............. 14
Table 18. Q6SD - 208/230v Single Phase ............ 15
Table 19. Q6SD - 208/230v 3-Phase.................... 16
Table 20. Q6SD - 460v 3-Phase........................... 16
Wiring Diagrams ...................................................... 17
#1 - Single Ph. - 5, 8, or 10kW - 1 Circuit ............ 17
#2 - Single Ph. - 5, 8, or 10kW - 2 Circuit ............ 18
#3 - Single Ph. - 15kW - 2 Circuit (AC appl.) ....... 19
#4 - Single Ph. - 15kW - 2 Circuit (HP appl.) ....... 20
#5 - Single Ph. 15kW - 3 Circuit ........................... 21
#6 - Single Ph. 20kW - 2 Circuit ........................... 22
#7 - Single Ph. 20kW - 3 Circuit ........................... 23
#8 - 3 Ph. 208/230V 9kW or 15kW - 1 Circ. ......... 24
#9 - 3 Ph. 208/230V 9kW or 15kW - 2 Circ. ......... 25
#10 - 3 Ph. 460V 9kW or 15kW - 1 Circuit ........... 26

Blower Data ............................................................. 27


Table 21. P5RD Series - Single Phase................. 27
Table 22. P5RF Series - Small Pack .................... 27
Table 23. P6SD Series - Single Phase ................. 28
Table 24. P6SD Series - 3 Phase ......................... 28
Table 25. Q4SE Series - Min. Elec. Heat Airflow .. 28
Table 26. Q5RD Series - Small Pack.................... 29
Table 27. Q5RF Series - Small Pack .................... 30
Table 28. Q6SD Series - Single Phase ................ 31
Table 29. Q6SD Series - 3 Phase ........................ 32

IMPORTANT SAFETY INFORMATION


INSTALLER: Please read all instructions before servicing
this equipment. Pay attention to all safety warnings and
any other special notes highlighted in the manual. Safety
markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not
be ignored. WARNING indicates a potentially hazardous
situation that if not avoided, could result in personal injury
or death. CAUTION indicates a potentially hazardous
situation that if not avoided, may result in minor or moderate
injury or property damage.

WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
Before servicing, disconnect all electrical
power to air handler.
When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.

CLEARANCES
All units are approved for zero clearance to combustibles
when installed according to these instructions and other
instructions included with the unit and other approved
accessories.

GENERAL INFORMATION
The H3HK Heater Kits are approved for use in the
Packaged Air Conditioners and Packaged Heat Pumps
when applied and installed according to these instructions.
See Tables 3 - 7 (pages 6 - 8) for the approved H3HK air
conditioner combinations and the approved H3HK heat
pump combinations. Refer to the National Electric Code
(ANSI/NFPA 70) or in Canada the Canadian Electric
Code Part 1 (CSA C.22.1) and applicable local codes
for overcurrent protection and disconnect requirements.

ELECTRICAL SUPPLY

HEATER
KITS

If the unit was previously installed without electric heat,


the existing supply wiring may not be sufficient to handle
the increased load. See the unit rating label or Tables
8 - 20 (pages 9 - 16) for minimum circuit ampacities and
maximum overcurrent protection ratings. The units with
installed electric heat may be supplied by a single circuit
or by multiple circuits. Additional accessory kits may be
required if single circuit installation and/or circuit breakers
are desired. See Figure 1 for kit identification and Table 1
for accessory descriptions and part numbers.

H3HK005H-01A (5kw)
H3HK008H-01A (8kw)
H3HK010H-01A (10kw)
H3HK015H-01A (15kw)
H3HK015H-21A (15kw)
H3HK020H-01A (20kw)
H3HK020H-21A (20kw)

917166B
917167B
917168B
917169B
917172B
917170B
917173B

3 Phase
208/230v

H3HK-009Q-01A (9kw)

903854B

H3HK-015Q-01A (15kw)

903855B

3 Phase
460v

H3HK-009S-01A (9kw)

903850B

H3HK-015S-01A (15kw)

903851B

1 Phase
208/230v

WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.

4-Pole Single Circuit Adaptor*


Accessories

Circuit Options
The units with electric heat may be wired for single or
multiple circuits and may have circuit breakers or terminal
blocks. NOTE: Circuit breakers installed in the unit are for
short-circuit protection of the internal wiring and to serve
as a unit disconnect. The circuit breakers DO NOT provide
overcurrent protection of the supply wiring.

Whether or not circuit breakers are used in the


units, overcurrent protection must be provided at the
branch circuit distribution panel and sized as shown
in Tables 8 - 20 (pages 9 - 16) or on the unit rating
label and according to the National Electric Code,
Canadian Electrical Code and applicable local codes.

HK

913350

6-Pole Single Circuit Adaptor*

913556

Circuit Breaker, 1 Phase (2-Pole)

913554

Circuit Breaker, 3 Phase (3-Pole)

913740

* Single phase models only

Table 1. Heater Kits & Accessories

Before servicing, disconnect all electrical


power to air handler.
When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.
Installation
Remove the control box access panel. Locate the 9 pin
(12 pin for 3 phase kits) heater plug assembly and remove
the jumper cap. Discard the jumper cap; it will not be used
after installing the heater kits.

PART
NUMBER

DESCRIPTION

In most cases the overcurrent protection specified on


the unit rating label is less than the 60 amp rating of
the circuit breakers used in the units. This is because
the function of the overcurrent protection required
at the distribution panel (field supplied) and the unit
mounted breakers is different.
When circuit breakers are used they must be used on
all circuits. Refer to Tables 3 - 7 (pages 6 - 8) for the
correct circuit breaker for the application.
If the number of circuits listed in Tables 3 - 7 are more
than 1, circuit breakers are required. If single circuit
supply wiring is desired: Use the 4-pole circuit adapter
kit (P/N 913350) when two 2-pole circuit breakers are
used. If 3 circuit breakers are used, the 6-pole circuit
adapter kit (P/N 913556) is required.The single circuit
adapter kits are not applicable to 3-phase units.
If circuit breakers are not being used, proceed to the
Terminal Block section (page 4).

Circuit Breakers
If circuit breakers are used for any circuit, they must be
used for all circuits. Use one breaker for each circuit. See
Tables 3 - 7 (pages 6 - 8).

008

1
Stages
Sequencer

Heater
3-Pkgd. Units
Heater Kit

Electric
Heater KW

No. of Breakers
Electric Code
H=240-1-60

Figure 1. Heater Kit Identification Code

Breaker Attachment
Install the circuit breaker mounting rail to the control panel
with the 4 blunt tip screws provided.
Attaching to Bracket
Attach the circuit breakers in the unit by hooking the
bottom in the base of the circuit breaker onto the left rail
of the bracket and rotating to the right. The circuit breaker
should snap into place. Install the breakers so that the
ON position is to the right. See Figure 2 (page 5) for
component location.
Breaker Removal
Insert a screwdriver into the hole in the release tab and
pull out while rotating the breaker out and to the left. The
white release tab is located at the base of the breaker
under the line side (right) terminals.
Single Circuit Kit (single phase only)
Refer to the instructions included with the single circuit
adapter kit for details on how to configure the adapter.
Install the adapter as shown in the instructions in the
line side (right) of the breakers. Proceed to the Element
Installation section.
Terminal Blocks
Approved H3HK heater kits are shipped with a terminal
block for small package units. For large package units the
terminal block(s) supplied with the kits will not be used.
The electric heater kits will be wired to the existing factory
installed terminal block. If the number of circuits indicated
in Tables 3 - 7 (pages 6 - 8) is 2 or 3, then the circuit
breakers must be used. See Circuit Breakers (page 3).
Staged Heat
To stage the heat on the 15 kw or 20 kw Heater Kits the
factory set wiring will need to be modified. The orange
wire in Pin 2 on the Heat Accessory Plug will be re-routed.
See the Installation Instructions supplied with the HP or
AC for typical thermostat connections.

WARNING:
Rooftop applications with vertical ducts must
have an elbow installed in the supply duct so that
the elements are not directly over a supply grille.

WARNING:
The heater will not function properly if the
elements are not correctly installed.
Element Installation
Remove the blower access panel. Remove the heater
close-off plate(s) in the electric heat panel. When installing
single banks of heaters, position them closest to the blower.
Install the heater kit in the opening with the limit control
towards the top of the unit if the unit is using the side
supply and return duct openings. If the unit is using the

downshot supply and return openings, install the heater


kit in the opening with the limit towards the bottom of
the unit. See Figure 3 (page 5). NOTE: Make sure the
element support rod is inserted into the support bracket.
Fasten the heater with the same screws used to secure
the close-off plates.
Element Power Wiring
Route the main power leads (heavy black & red wires) and
the 9 or 12-pin heat plug through the access hole at the
top of the control panel to the circuit breaker or terminal
block. Connect the 9 or 12-pin heat kit plug to the heat
accessory plug located in the control box. Refer to the
detailed wiring diagrams (pages 17 - 26) for connections.
Make sure that the connections are secure. Select large
package units have additional terminal blocks installed.
The power leads from the heater kit should be attached
to these terminal blocks. Wires needed to connect from
terminal blocks to circuit breakers should be field supplied.
The 6 inch leads are provided with the heater kit to connect
the circuit breaker(s) to the compressor contactor. Mark
the appropriate box on the unit rating plate with an X to
indicate which heater kit has been installed.
IMPORTANT: Torque the circuit breaker lugs to 45 in-lbs.

AIRFLOW
All heater kit temperature rise data in See Tables 21 - 29
(pages 27 - 32) have been calculated using 10kW heaters
(9kW for 3 phase units). For other sized heater kits, use
the following steps below to determine the heat rise for
your particular heater kit.
1. Determine your CFM. NOTE: This data is found by
locating your blower motor tap settings in the data
supplied with the Installation Instructions. See Tables
21 - 29.
2. Locate your heater kits kW value and Btu/h in Table 2.
3. Input the values into the following equation:

Temp Rise: T= (Btu/h)/(CFM*1.08)


NOTE: Generally the heat rise should be 30 - 40 degrees.
Anything above 40 degrees should be avoided.
KW/h

Btu/h

17,060

27,297

30,709

10

34,121

15

51,182

20

68,242

Table 2. kW & Btu/h Ratings

FIGURES & TABLES


SMALL PACKAGE

RELAY

ACCESS HOLE
CONTACTOR

CIRCUIT
BREAKERS

ELECTRIC
HEATING
ELEMENTS
LIMIT SWITCH

CONTACTOR

LARGE PACKAGE
AIR CONDITIONER

LARGE PACKAGE
HEAT PUMP
CAPACITOR
CONTACTOR
RELAY

TERMINAL
BLOCK

DEFROST
BOARD

CAPACITOR

ELECTRIC
HEATING
ELEMENTS

CONTACTOR
TERMINAL BLOCK

TRANSFORMER
BLOWER
RELAY

ELECTRIC
HEATING
ELEMENTS

TERMINAL
BLOCK

TRANSFORMER

CAPACITOR

BLOWER RELAY

CONTACTORS

LIMIT SWITCH
(Shown in position
for downshot flow)

CONTACTORS

LIMIT SWITCH
(Shown in position
for downshot flow)

Figure 2. Location of Major Components

HEATING
ELEMENTS

SUPPORT
BRACKET

Figure 3. Element Support Bracket


5

HEATER KIT CROSS REFERENCES


TONNAGE
SEER
PHASE

UNIT

2 Ton
13 & 15 SEER
Single Phase

P5RD, GP5RD, PPA2RD,


P5RF, PPA2RF

2.5 Ton
13 SEER
Single Phase

P5RD, GP5RD, PPA2RD

3 Ton
13 & 15 SEER
Single Phase

P5RD, GP5RD, PPA2RD


P5RF, PPA2RF

3.5 Ton
13 SEER
Single Phase

P5RD, GP5RD, PPA2RD

4 Ton
13 & 15 SEER
Single Phase

P5RD, GP5RD, PPA2RD


P5RF, PPA2RF

5 Ton
13 & 15 SEER
Single Phase

P5RD, GP5RD, PPA2RD


P5RF, PPA2RF

NOMINAL
KW

HEATER KIT
MODEL

HEATER KIT
PART NUMBER

BREAKERS
REQUIRED

WIRING
DIAGRAM
NUMBER

5
8
10
5
8
10
15
5
8
10
15
5
8
10
15
20
5
8
10
15
20
5
8
10
15
20

H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B

917166B
917167B
917168B
917166B
917167B
917168B
917169B
917166B
917167B
917168B
917169B
917166B
917167B
917168B
917169B
917170B
917166B
917167B
917168B
917169B
917170B
917166B
917167B
917168B
917169B
917170B

None
None
None
None
None
None
2
None
None
None
2
None
None
None
2
2
None
None
None
2
2
None
None
None
2
2

1
1
1
1
1
1
3
1
1
1
3
1
1
1
3
6
1
1
1
3
6
1
1
1
3
6

Table 3. P5RD & P5RF Heater Kit Model Cross Reference (Air Conditioner)

TONNAGE
& PHASE

UNIT

3 Ton, Single Phase

P6SD
GP6SD
PPA2SD

4 Ton, Single Phase

P6SD
GP6SD
PPA2SD

5 Ton, Single Phase

P6SD
GP6SD
PPA2SD

3,4, & 5 TON


3 Phase 208/230V

P6SD

3,4, & 5 TON


3 Phase 460V

P6SD

NOMINAL
KW

HEATER KIT
MODEL

HEATER KIT
PART NUMBER

BREAKERS
REQUIRED

WIRING
DIAGRAM
NUMBER

5
8
10
15
5
8
10
15
20
5
8
10
15
20
9
15
9
15

H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B
H3HK-009Q-01B
H3HK-015Q-01B
H3HK-009S-01B
H3HK-015S-01B

917166B
917167B
917168B
917169B
917166B
917167B
917168B
917169B
917170B
917166B
917167B
917168B
917169B
917170B
903854B
903855B
903850B
903851B

None
None
None
2
None
None
None
2
2
None
None
2
2
3
None
None
None
None

1
1
1
3
1
1
1
3
6
1
1
2
3
7
8
8
10
10

Table 4. P6SD Heater Kit Model Cross Reference - 13 SEER

TONNAGE
& PHASE

UNIT

2 Ton
Single Phase

Q4SE
PPH1SE

3 Ton
Single Phase

Q4SE
PPH1SE

4 Ton
Single Phase

Q4SE
PPH1SE

5 Ton
Single Phase

Q4SE
PPH1SE

NOMINAL
KW

HEATER KIT
MODEL

HEATER KIT
PART NUMBER

BREAKERS
REQUIRED

WIRING DIAGRAM
NUMBER

5
8
10
15
5
8
10
15
5
8
10
15
20
5
8
10
15
20

H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B

917166B
917167B
917168B
917169B
917166B
917167B
917168B
917169B
917166B
917167B
917168B
917169B
917170B
917166B
917167B
917168B
917169B
917170B

None
None
2
2
None
2
2
2
2
2
2
3
3
2
2
2
3
3

1
1
2
2
1
2
2
2
2
2
2
5
7
2
2
2
5
7

Table 5. Q4SE Heater Kit Model Cross Reference - 14 SEER

TONNAGE,
SEER, PHASE

UNIT

2 Ton
13 & 15 SEER
Single Phase

Q5RD, GQ5RD, PPH2RD,


Q5RF, PPH2RF

2.5 Ton
13 SEER
Single Phase

Q5RD, GQ5RD, PPH2RD

3 Ton
13 & 15 SEER
Single Phase

Q5RD, GQ5RD, PPH2RD,


Q5RF, PPH2RF

3.5 Ton
13 SEER
Single Phase

Q5RD, GQ5RD, PPH2RD

4 Ton
13 & 15 SEER
Single Phase

Q5RD, GQ5RD, PPH2RD,


Q5RF, PPH2RF

5 Ton
13 & 15 SEER
Single Phase

Q5RD, GQ5RD, PPH2RD,


Q5RF, PPH2RF

NOMINAL
KW

HEATER KIT
MODEL

HEATER KIT
PART NUMBER

BREAKERS
REQUIRED

WIRING DIAGRAM
NUMBER

5
8
10
5
8
10
15
5
8
10
15
5
8
10
15
20
5
8
10
15
20
5
8
10
15
20

H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B

917166B
917167B
917168B
917166B
917167B
917168B
917169B
917166B
917167B
917168B
917169B
917166B
917167B
917168B
917169B
917170B
917166B
917167B
917168B
917169B
917170B
917166B
917167B
917168B
917169B
917170B

None
None
2
None
2
2
2
None
2
2
2
None
2
2
2
3
2
2
2
2
3
2
2
2
2
3

1
1
2
1
2
2
4
1
2
2
4
1
2
2
4
7
2
2
2
4
7
2
2
2
4
7

Table 6. Q5RD & Q5RF Heater Kit Model Cross Reference (Heat Pump)

TONNAGE
& PHASE

UNIT

2 Ton
Single Phase

Q6SD
GQ6SD
PPH2SDX

2.5 Ton
Single Phase

Q6SD
GQ6SD
PPH2SDX

3 Ton
Single Phase

Q6SD
GQ6SD
PPH2SDX

3.5 Ton
Single Phase

Q6SD
GQ6SD
PPH2SDX

4 Ton
Single Phase

Q6SD
GQ6SD
PPH2SDX

5 Ton
Single Phase

Q6SD
GQ6SD
PPH2SDX

3,4, & 5 TON


3 Phase 208/230V

Q6SD

3,4, & 5 TON


3 Phase 460V

Q6SD

NOMINAL
KW

HEATER KIT
MODEL

HEATER KIT
PART NUMBER

BREAKERS
REQUIRED

WIRING DIAGRAM
NUMBER

5
8
10
15
5
8
10
15
5
8
10
15
5
8
10
15
20
5
8
10
15
20
5
8
10
15
20
9
15
9
15

H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B
H3HK005H-01B
H3HK008H-01B
H3HK010H-01B
H3HK015H-01B
H3HK020H-01B
H3HK-009Q-01B
H3HK-015Q-01B
H3HK-009S-01B
H3HK-015S-01B

917166B
917167B
917168B
917169B
917166B
917167B
917168B
917169B
917166B
917167B
917168B
917169B
917166B
917167B
917168B
917169B
917170B
917166B
917167B
917168B
917169B
917170B
917166B
917167B
917168B
917169B
917170B
903854B
903855B
903850B
903851B

None
2
2
3
None
2
2
3
None
2
2
3
2
2
2
3
3
2
2
2
2
3
2
2
2
3
3
None
2
None
None

1
2
2
5
1
2
2
5
1
2
2
5
2
2
2
5
7
2
2
2
5
7
2
2
2
5
7
8
9
10
10

Table 7. Q6SD Heater Kit Model Cross Reference - 13 SEER

ELECTRICAL DATA
P5RD SERIES - 208/230V - SINGLE PHASE MODELS
SINGLE CIRCUIT
MODEL
P5RD-

024K

030K

036K

042KA

048KA

HEATER
KW

0
5
8
10
0
5
8
10
15
0
5
8
10
15
0
5
8
10
15
20
0
5
8
10
15
20

MCA

18.5
26.8
41.3
51.8
22.1
26.8
41.3
51.8
76.8
26.5
27.6
42.2
52.6
77.6
31.9
31.9
41.1
51.5
76.5
101.5
34.9
34.9
41.1
51.8
76.8
101.8

MULTIPLE SUPPLY CIRCUIT OPTION

REC,
WIRE GAGE
(90 C CU)

MOP

12
10
8
8
10
10
8
8
4
10
10
8
8
4
8
8
8
8
4
3
8
8
8
8
4
3

30
30
45
60
35
35
45
60
80
45
45
45
60
80
50
50
50
60
80
110
50
50
50
60
80
110

CIRCUIT B
(BLOWER & HEATER)

CIRCUIT A
(COMPRESSOR & FAN)
MCA

REC, WIRE GAGE


(90 C CU)

MOP

MCA

REC, WIRE GAGE


(90 C CU)

MOP

50
50
51.5
51.5
51.8
51.8

8
8
8
8
8
8

60
60
60
60
60
60

26.8
27.6
25
50
25
50

10
10
10
8
10
8

30
30
30
60
30
60

NOTE: P5RD 2, 2.5 & 3 ton models have PSC motors. Since the power wires run through the heater plug, keep the blower and heater on
different circuits when adding a heater kit.

Table 8. P5RD Electrical Data (2, 2.5, & 3 Ton Units)


P5RD SERIES - 208/230V - SINGLE PHASE MODELS
SINGLE CIRCUIT
MODEL
P5RD-

042K

048K

060K

HEATER
KW

0
5
8
10
15
20
0
5
8
10
15
20
0
5
8
10
15
20

MCA

32.9
32.9
41.1
51.5
76.5
101.5
37.6
37.6
41.1
51.5
76.5
101.5
44
44
44
51.5
76.5
101.5

MULTIPLE SUPPLY CIRCUIT OPTION


CIRCUIT A
(COMPRESSOR, BLOWER, & FAN)

REC,
WIRE GAGE
(90 C CU)

MOP

8
8
8
8
4
3
8
8
8
8
4
3
8
8
8
8
4
3

50
50
50
60
80
110
60
60
60
60
80
110
70
70
70
70
80
110

CIRCUIT B
(HEATER)

MCA

REC,
WIRE GAGE
(90 C CU)

MOP

MCA

REC,
WIRE GAGE
(90 C CU)

MOP

51.5
51.5
51.5
51.5
51.5
51.5

8
8
8
8
8
8

60
60
60
60
70
70

25
50
25
50
25
50

10
8
10
8
10
8

30
60
30
60
30
60

Table 9. P5RD Electrical Data (3.5, 4, & 5 Ton Units)


9

P5RF SERIES - 208/230V - SINGLE PHASE MODELS


SINGLE CIRCUIT
MODEL
P5RF-

X24K

X36K

X48K

X60K

HEATER
KW

0
5
8
10
0
5
8
10
15
0
5
8
10
15
20
0
5
8
10
15
20

MCA

18.1
26.5
41.1
51.5
26.1
26.5
41.1
51.5
76.5
37.7
37.7
46.2
56.6
81.6
106.6
40.1
40.1
46.2
56.6
81.6
106.6

MULTIPLE SUPPLY CIRCUIT OPTION


CIRCUIT B
(HEATER)

CIRCUIT A
(COMPRESSOR, BLOWER, & FAN)

REC, WIRE
GAGE
(90C CU)

MOP

12
10
8
8
10
10
8
8
4
8
8
8
6
4
3
8
8
8
6
4
3

25
30
45
60
40
40
45
60
80
50
50
50
60
90
110
60
60
60
60
90
110

MCA

REC, WIRE GAGE


(90C CU)

MOP

MCA

REC, WIRE GAGE


(90C CU)

MOP

51.5
56.6
56.6
56.6
56.6

8
6
6
6
6

60
60
60
60
60

25
25
50
25
50

10
10
8
10
8

30
30
60
30
60

Table 10. P5RF Electrical Data (2, 3, 4, & 5 Ton Units)

10

P6SD SERIES - 208/230V - SINGLE PHASE MODELS


SINGLE CIRCUIT
MODEL
NUMBER
P6SD-

HEATER
INSTALLED
NOMINAL KW

CIRCUIT A
(COMPRESSOR & FAN)
MOP
MCA

REC, WIRE GAGE


(90 C CU)

MOP

MCA

REC, WIRE GAGE


(90 C CU)

MOP

0
5

25.8
26.5

10
10

40
40

41.2

45

51.6

60

15

76.6

80

50.0

60

26.6

10

30

32.9

50

32.9

50

41.2

50

10

51.6

60

15
20

76.6
101.6

4
3

80
110

51.6
50

8
8

50
50

26.6
51.6

10
8

30
60

SINGLE CIRCUIT
MODEL
NUMBER
P6SD-

X60K

CIRCUIT B
(BLOWER & HEATER)

10

X36K

X48K

REC, WIRE GAGE


(90 C CU)

MCA

MULTIPLE SUPPLY CIRCUIT OPTION

HEATER
INSTALLED
NOMINAL
KW

MULTIPLE SUPPLY CIRCUIT OPTION

REC, WIRE
MCA
GAGE
MOP
(90 C CU)

CIRCUIT B
(HEATER ONLY)

CIRCUIT A
(COMPRESSOR, BLOWER, & FAN)

CIRCUIT C
(HEATER ONLY)

MCA

REC, WIRE
GAGE
(90 C CU)

MOP

MCA

REC, WIRE
GAGE
(90 C CU)

MOP

MCA

REC, WIRE
GAGE
(90 C CU)

MOP

43.8

70

43.8

70

43.8

70

10

51.5

70

43.8

70

50

60

15
20

76.5
101.5

4
3

80
110

51.5
43.8

8
8

70
70

25
50

10
8

30
60

50

60

NOTE: P6SD 3 & 4 ton models have PSC motors. Since the power wires run through the heater plug, keep the blower and heater on different
circuits when adding a heater kit.

Table 11. P6SD Electrical Data (3, 4, & 5 Ton Units)

P6SD SERIES - 208/230V - 3 PHASE MODELS


MODEL
NUMBER
P6SD-

X36C

X48C

X60C

SINGLE CIRCUIT

HEATER
INSTALLED
NOMINAL KW

MCA

REC, WIRE GAGE


(90 C CU)

MOP

17.0

12

25

28.7

10

30

15

46.8

21.6

10

28.7

10

35

15

46.8

50

29

10

45

9
15

29
46.7

10
8

45
50

P6SD SERIES - 460V - 3 PHASE MODELS


SINGLE CIRCUIT

MODEL
NUMBER
P6SD-

HEATER
INSTALLED
NOMINAL KW

MCA

REC, WIRE GAGE


(90 C CU)

MOP

X36D

0
9

9.4
15.1

14
12

15
15

50

15

24.5

10

25

35

10.9

14

15

16.2

12

15

15

25.7

10

30

14.6

14

15

9
15

14.9
24.3

14
10

15
25

NOTE: P6SD 3 & 4 ton models have PSC motors. Since the power
wires run through the heater plug, keep the blower and heater on
different circuits when adding a heater kit.

Table 12. P6SD Electrical Data (3, 4, & 5 Ton Units)

X48D

X60D

NOTE: P6SD 3 & 4 ton models have PSC motors. Since the power
wires run through the heater plug, keep the blower and heater on
different circuits when adding a heater kit.

Table 13. P6SD Electrical Data


(460v 3 Phase Models)

11

Q4SE SERIES - 208/230V - SINGLE PHASE MODELS


SINGLE CIRCUIT

MODEL
HEATER
NUMBER
KW
Q4SE-

X24K

X36K

X48K

X60K

0
5
8
10
15
0
5
8
10
15
0
5
8
10
15
20
0
5
8
10
15
20

MCA

20
45
59.5
70
95.0
29.3
54.3
68.8
79.3
104.3
38
63
77.6
88.0
113.0
138.0
40.8
65.8
80.4
90.8
115.8
140.8

MULTIPLE SUPPLY CIRCUIT OPTION


CIRCUIT B
(HEATER ONLY)

CIRCUIT A
(COMPRESSOR, BLOWER & FAN)

REC,
WIRE
GAGE
(90 C CU)

MOP

12
8
6
6
4
10
8
6
4
3
8
6
4
4
2
1
8
6
4
4
2
1

30
50
60
70
100
45
60
70
80
110
60
80
90
100
125
150
60
80
90
100
125
150

MCA

REC,
WIRE
GAGE
(90 C CU)

MOP

MCA

REC,
WIRE
GAGE
(90 C CU)

MOP

MCA

REC,
WIRE
GAGE
(90 C CU)

MOP

20
45
29.3
29.3
54.3
38
38
38
38
38
40.8
40.8
40.8
40.8
40.8

12
8
10
10
8
8
8
8
8
8
8
8
8
8
8

30
50
45
45
60
60
60
60
60
60
60
60
60
60
60

50
50
39.6
50
50
25
39.6
50
50
50
25
39.6
50
50
50

8
8
8
8
8
10
8
8
8
8
10
8
8
8
8

60
60
40
60
60
30
40
60
60
60
30
40
60
60
60

25
50
25
50

10
8
10
8

30
60
30
60

NOTES:
Changed circuity to show X-13 motors routed straight to the contactor
* For Maytag TSL, change model number to PPH1SE-X**K

Table 14. Q4SE Electrical Data (2, 3, 4, & 5 Ton Units)

12

CIRCUIT C
(HEATER ONLY)

Q5RD SERIES - 208/230V - SINGLE PHASE MODELS


MODEL
Q5RD-

024K

030K

036KA

048KA

CIRCUIT A
(COMPRESSOR & BLOWER)

REC, WIRE
GAGE
(90 C CU)

MOP

18.1
43.1

12
8

30
50

HEATER
KW

MCA

0
5

CIRCUIT B
(FAN & HEATER)

CIRCUIT C
(HEATER ONLY)

MCA

REC, WIRE
GAGE (90 C CU)

MOP

MCA

REC, WIRE
GAGE (90 C CU)

MOP

MCA

REC, WIRE
MOP
GAGE (90 C CU)
-

57.7

60

10

68.1

70

17.1

12

25

51

60

22.2

10

35

47.2

50

61.8

70

20.8

10

35

41

45

10

72.2

80

20.8

10

35

51.4

60

15

97.2

100

45.8

50

51.4

60

26.5

10

45

51.5

60

66

70

25.4

10

40

40.7

45

10

76.5

80

25.4

10

40

51.1

60

15

101.5

110

50.4

60

51.1

60

34.9

50

59.9

70

33.5

50

26.5

10

30

74.5

90

33.5

50

41

45

10

84.9

90

33.5

50

51.5

60

15

109.9

110

58.5

70

51.5

60

20
20 (3 cir.)

134.9
-

1
-

150
-

33.5

50

51.5

60

50

60

Table 15. Q5RD w/ PSC Indoor Motor Electrical Data (2 & 2.5 Ton Units)

Q5RD SERIES - 208/230V - SINGLE PHASE MODELS


MODEL
NUMBER
Q5RD

036K

042K

048K

060K

HEATER
KW

MCA

0
5

28.5
53.5

CIRCUIT B
(HEATER ONLY)

CIRCUIT A
(COMPRESSOR, BLOWER & FAN)

REC, WIRE
GAGE
(90 C CU)

MOP

10
8

45
60

MCA
-

CIRCUIT C
(HEATER ONLY)

REC, WIRE
REC, WIRE
REC, WIRE
MOP MCA
MOP MCA
MOP
GAGE (90 C CU)
GAGE (90 C CU)
GAGE (90 C CU)
-

68

70

28.5

10

45

39.6

40

10

78.5

80

28.5

10

45

50

60

15

103.5

110

53.5

60

50

60

32.2

50

57.2

70

71.8

80

32.2

50

39.6

40

10

82.2

90

32.2

50

50

60

15

107.2

110

57.2

70

50

60

20

132.2

150

20 (3 circuit)

32.2

50

50

60

50

60

37.6

60

62.6

80

37.6

60

25

10

30

77.2

90

37.6

60

39.6

40

10

87.6

100

37.6

60

50

60

15

112.6

125

62.6

80

50

60

20

137.6

150

20 (3 circuit)

37.6

60

50

60

50

60

40.5

60

65.5

80

40.5

60

25

10

30

80.1

90

40.5

60

39.6

40

10

90.5

100

40.5

60

50

60

15

115.5

125

65.5

80

50

60

20

140.5

150

20 (3 circuit)

40.5

60

50

60

50

60

Table 16. Q5RD w/ ECM Indoor Motor Electrical Data (3, 3.5, 4, & 5 Ton Units)

13

Q5RF SERIES - 208/230V - SINGLE PHASE MODELS

MODEL
NUMBER
Q5RF

X24K

X36K

X48K

X60K

HEATER
KW

MCA

CIRCUIT B
(HEATER ONLY)

CIRCUIT A
(COMPRESSOR, BLOWER & FAN)

REC,
WIRE
GAGE
(90C CU)

MOP

CIRCUIT C
(HEATER ONLY)

MCA

REC,
WIRE
GAGE
(90 C CU)

MOP

MCA

REC,
WIRE
GAGE
(90 C CU)

MOP

MCA

REC,
WIRE
GAGE
(90 C CU)

MOP

18.1

12

25

43.1

45

57.6

60

10

68.1

70

18.1

12

25

50

60

26.1

10

40

51.1

60

65.6

70

26.1

10

40

39.6

40

10

76.1

80

26.1

10

40

50

60

15

101.1

110

51.1

60

50

60

37.7

50

62.7

70

37.7

50

25

10

30

77.3

90

37.7

50

39.6

40

10

87.7

90

37.7

50

50

60

15

112.7

125

62.7

70

50

60

20

137.7

150

20 (3 circuit)

37.7

50

50

60

50

60

40.1

60

65.1

80

40.1

60

25

10

30

79.6

90

40.1

60

39.6

40

10

90.1

100

40.1

60

50

60

15

115.1

125

65.1

80

50

60

20

140.1

150

20 (3 circuit)

40.1

60

50

60

50

60

Table 17. Q5RF Electrical Data (3, 3.5, 4, & 5 Ton Units)

14

Q6SD SERIES - 208/230V - SINGLE PHASE MODELS


SINGLE CIRCUIT
MODEL HEATER
Q6SDKW
MCA

X24K

X30K

X36K

X42K

X48K

X60K

0
5
8
10
15
0
5
8
10
15
0
5
8
10
15
0
5
8
10
15
20
0
5
8
10
15
20
0
5
8
10
15
20

21.1
46.1
60.7
71.1
96.1
24.7
49.7
64.3
74.7
99.7
28.6
53.6
68.1
78.6
103.6
32.9
57.9
72.5
82.9
107.9
132.9
37.6
62.6
77.2
87.6
112.6
137.6
44.1
69.1
83.7
94.1
119.1
144.1

MULTIPLE SUPPLY CIRCUIT OPTION

CIRCUIT A
REC,
(COMPRESSOR, BLOWER & FAN)
WIRE
MOP
REC,
GAGE
MCA
WIRE GAGE
MOP
(90 C CU)
(90 C CU)
10
8
6
6
3
10
8
6
6
3
10
8
6
4
3
8
6
6
4
3
1
8
6
4
4
2
1
8
6
4
4
2
1

30
50
70
80
100
40
60
70
80
100
45
60
70
80
110
50
70
80
90
110
150
60
80
90
100
125
150
70
90
100
110
125
150

21.1
21.1
21.1
21.1
24.7
24.7
24.7
28.6
28.6
28.6
32.9
32.9
32.9
32.9
32.9
37.6
37.6
37.6
37.6
37.6
44.1
44.1
44.1
44.1
44.1

10
10
10
10
10
10
10
10
10
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

30
30
30
40
40
40
45
45
45
50
50
50
50
50
60
60
60
60
60
70
70
70
70
70

CIRCUIT B
(HEATER ONLY)
MCA

REC,
WIRE GAGE
(90 C CU)

39.6
50
50
39.6
50
50
39.6
50
50
25
39.6
50
50
50
25.0
39.6
50.0
50.0
50.0
25.0
39.6
50.0
50.0
50.0

8
8
8
8
8
8
8
8
8
10
8
8
8
8
10
8
8
8
8
10
8
8
8
8

CIRCUIT C
(HEATER ONLY)
REC,
MOP MCA WIRE GAGE MOP
(90 C CU)
40
60
60
40
60
60
40
60
60
30
40
60
60
60
30
40
60
60
60
30
40
60
60
60

25.0
25.0
25.0
25.0
50.0
25.0
50.0
25.0
50.0

10
10
10
10
8
10
8
10
8

30
30
30
30
60
30
60
30
60

NOTE: All circuitry has been changed due to routing the X-13 motors to the contactor.

Table 18. Q6SD Electrical Data - 208/230v Single Phase Models

15

Q6SD SERIES - 208/230V - 3 PHASE MODELS


SINGLE CIRCUIT
MODEL
Q6SD-

X36C

X48C

X60C

HEATER
KW

0
9
15
0
9
15
0
9
15

MCA

MULTIPLE SUPPLY CIRCUIT OPTION

MOP

12
8
6
10
8
6
10
6
6

30
50
70
40
60
80
45
60
80

19.8
46.9
65.0
26.3
53.4
71.5
29.3
56.3
74.4

CIRCUIT B
(HEATER ONLY)

CIRCUIT A
(COMPRESSOR, BLOWER & FAN)

REC,
WIRE GAGE
(90 C CU)

MCA

REC,
WIRE GAGE
(90 C CU)

MOP

MCA

REC,
WIRE GAGE
(90 C CU)

MOP

19.8
26.3
29.3

12
10
10

30
10
45

45.2
45.2
45.2

8
8
8

50
50
50

NOTE: All circuitry has been changed due t routing the X-13 motors to the contactor.

Table 19. Q6SD Electrical Data - 208/230v 3 Phase Models

Q6SD SERIES - 460V - 3 PHASE MODELS


SINGLE CIRCUIT
MODEL
Q6SD-

X36D

X48D

X60D

HEATER
KW

MCA

REC,
WIRE GAGE
(90 C CU)

MOP

0
9
15
0
9
15
0
9
15

10.7
24.8
34.2
12.4
26.5
36
14.8
28.9
38.3

14
10
8
14
10
8
14
10
8

15
25
35
15
30
40
15
30
40

NOTE: All circuitry has been changed due to routing the X-13 motors to the contactor.

Table 20. Q6SD Electrical Data - 460v 3 Phase Models

16

WIRING DIAGRAMS

WIRING DIAGRAM
WHITE

CONTACTOR

BROWN

BLACK

BLACK

RED
RED
ELEMENTS

4
5

BLUE

ORANGE

GRAY

GRAY

8
BLACK
BLACK

COMPRESSOR
CONTACTOR
HEATER KIT PLUG

T2

T1

L2

L1

TERMINAL
BLOCK

CIRCUIT
BREAKER

FIELD WIRING
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE

NOTE: 8 kw & 10 kw shown.

CIRCUIT A

Wiring Diagram #1 - Single Phase - 5 KW, 8 KW, OR 10 KW, 1 Circuit

17

WIRING DIAGRAM
WHITE

CONTACTOR

BROWN

BLACK

BLACK

RED
RED
ELEMENTS

4
5

BLUE

ORANGE

GRAY

GRAY

8
BLACK
BLACK

HEATER KIT PLUG

COMPRESSOR
CONTACTOR
T2

T1

L2

L1

CIRCUIT
BREAKER
CIRCUIT
BREAKER

FIELD WIRING
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE

CIRCUIT A

NOTE: 8 kw & 10 kw shown.

CIRCUIT B

Wiring Diagram #2 - Single Phase - 5 KW, 8 KW, OR 10 KW, 2 Circuit

18

WIRING DIAGRAM
WHITE

BROWN

YELLOW

CONTACTOR

BLACK

RED

BLACK

RED
ELEMENTS

4
5

BLUE

ORANGE

GRAY
CONTACTOR

ELEMENTS
RED

BLACK

GRAY
GRAY

BLACK
BLACK

HEATER KIT PLUG

COMPRESSOR
CONTACTOR

BLACK

T2

T1

L2

L1

TERMINAL
BLOCK

FIELD WIRING
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE

CIRCUIT
BREAKER

CIRCUIT B

CIRCUIT
BREAKER

CIRCUIT A

Wiring Diagram #3 - Single Phase - 15 KW, 2 Circuit (AC Application)

19

WIRING DIAGRAM
WHITE

BROWN

YELLOW

CONTACTOR

BLACK

RED

BLACK

RED
ELEMENTS

4
5

BLUE

ORANGE

GRAY

CONTACTOR
RED

BLACK

ELEMENTS

9
GRAY
GRAY

BLACK
BLACK

HEATER
KIT PLUG

BLACK

COMPRESSOR
CONTACTOR
T2

T1

L2

L1
TERMINAL
BLOCK

CIRCUIT
BREAKER
CIRCUIT
BREAKER
FIELD WIRING
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE

CIRCUIT B
CIRCUIT A

Wiring Diagram #4 - Single Phase - 15 KW, 2 Circuit (Heat Pump Application)

20

WIRING DIAGRAM
WHITE

BROWN

YELLOW

CONTACTOR
BLACK

RED
RED

BLACK
ELEMENTS

4
5

BLUE

ORANGE

GRAY

CONTACTOR
RED

BLACK

ELEMENTS

9
GRAY
GRAY

BLACK
BLACK

HEATER
KIT PLUG

BLACK

COMPRESSOR
CONTACTOR
T2

T1

L2

L1
TERMINAL
BLOCK

CIRCUIT
BREAKER

CIRCUIT
BREAKER

FIELD WIRING
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE

CIRCUIT A

CIRCUIT C

CIRCUIT
BREAKER

CIRCUIT B

Wiring Diagram #5 - Single Phase - 15 KW, 3 Circuit

21

WIRING DIAGRAM
WHITE

BROWN

YELLOW

CONTACTOR

BLACK

RED

BLACK

RED
ELEMENTS

4
5

BLUE

ORANGE

GRAY

CONTACTOR
RED

BLACK

8
RED

BLACK

ELEMENTS
GRAY
GRAY

BLACK
BLACK

HEATER KIT PLUG

BLACK
BLACK

COMPRESSOR
CONTACTOR
T2

T1

L2

L1

TERMINAL
BLOCK

CIRCUIT
BREAKER

CIRCUIT
BREAKER
FIELD WIRING
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE

CIRCUIT B

Wiring Diagram #6 - Single Phase - 20 KW, 2 Circuit

22

CIRCUIT A

WIRING DIAGRAM
WHITE

BROWN

YELLOW

CONTACTOR

BLACK

RED

BLACK

RED
ELEMENTS

4
5

BLUE

ORANGE

GRAY

CONTACTOR
RED

BLACK

8
RED

BLACK

ELEMENTS
GRAY
GRAY

BLACK
BLACK
BLACK
BLACK

HEATER KIT PLUG

COMPRESSOR
CONTACTOR

T2

T1

L2

L1
TERMINAL
BLOCK

CIRCUIT
BREAKER

FIELD WIRING
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE

CIRCUIT A

CIRCUIT
BREAKER

CIRCUIT C

CIRCUIT
BREAKER

CIRCUIT B

Wiring Diagram #7 - Single Phase - 20 KW, 3 Circuit

23

FIELD WIRING
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE

L3

L2

L1

COMPRESSOR
CONTACTOR
T2

T1

YELLOW

T3

RED

TERMINAL
BLOCK

BLACK

RED

YELLOW

BLACK
BROWN

CONTACTOR
BLACK

LIMIT

ELEMENT

BLACK

BLUE

ORANGE

GRAY

ELEMENT

BROWN

GRAY

CONTACTOR

8
9

BROWN

WHITE
BLACK

LIMIT
ELEMENT

HEATER KIT PLUG

Wiring Diagram #8 - 3 Phase - 208/230V 9KW or 15KW, 1 Circuit

24

BROWN

CIRCUIT B

CIRCUIT A

CIRCUIT BREAKER

CIRCUIT BREAKER

RED

L3

L2

L1

COMPRESSOR
CONTACTOR
T3

T2

T1

RED

YELLOW

BLACK

YELLOW

BLACK

FIELD WIRING
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE

BROWN

CONTACTOR
BLACK

LIMIT

ELEMENT

BLACK

BLUE

ORANGE

GRAY

ELEMENT

BROWN

GRAY

CONTACTOR

8
9

BROWN

WHITE
BLACK

LIMIT
ELEMENT

BROWN

HEATER KIT PLUG

Wiring Diagram #9 - 3 Phase - 208/230V 9KW or 15KW, 2 Circuit

25

L3

L2

L1

T3

T2

T1

BLACK

COMPRESSOR
CONTACTOR

FIELD WIRING
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE

YELLOW

RED

BROWN

CONTACTOR
BLACK

BLACK

ORANGE

WHITE

GRAY

CONTACTOR

8
9

BLACK

BLUE

BROWN

ELEMENT

BLACK

LIMIT
ELEMENT

10
11
12

GRAY

HEATER KIT PLUG

Wiring Diagram #10 - 3 Phase - 460V 9KW or 15KW, 1 Circuit

26

LIMIT

BROWN

ELEMENT

BLACK

BROWN

BLOWER DATA
P5RD SERIES SMALL PACK
UNIT

X24K
X30K
X36K

X42K

042KA

X48

048KA

X60

BLOWER
SETTING
Low*
High**
Low
High
Low
High
Tap T1
Tap T2
Tap T3
Tap T4*
Tap T5**
Low
Med**
High
Tap T1
Tap T2**
Tap T3*
Tap T4
Tap T5
Low**
Med
High
Tap T1
Tap T2**
Tap T3
Tap T4*
Tap T5

0.1
HEAT
CFM
RISE

0.2
HEAT
CFM
RISE

External Static Pressure Drop - inches water column


0.3
0.4
0.5
0.6
HEAT
HEAT
HEAT
HEAT
CFM
CFM
CFM
CFM
RISE
RISE
RISE
RISE

847
1104
847
1104
1318
1551
1100
1208
1262
1370
1410
1460
1840
2155
1480
1575
1635
1775
2065
1460
1840
2155
1480
1575
1635
1775
2065

808
1114
808
1114
1284
1521
900
1080
1199
1333
1340
1440
1815
2115
1455
1545
1505
1740
2040
1440
1815
2115
1455
1545
1505
1740
2040

770
1064
770
1064
1248
1477
750
1025
1153
1300
1450
1420
1790
2065
1415
1515
1575
1715
2020
1420
1790
2065
1415
1515
1575
1715
2020

37
29
37
29
24
20
29
26
25
23
22
22
17
15
21
20
19
18
15
22
17
15
21
20
19
18
15

39
28
39
28
25
21
35
29
26
24
24
22
17
15
22
20
21
18
15
22
17
15
22
20
21
18
15

41
30
41
30
25
21
42
31
27
24
22
22
18
15
22
21
20
18
16
22
18
15
22
21
20
18
16

726
1010
726
1010
1207
1434
650
972
1110
1260
1320
1390
1760
2020
1390
1475
1545
1695
1985
1390
1760
2020
1390
1475
1545
1695
1985

44
31
44
31
26
22
49
33
28
25
24
23
18
16
23
21
20
19
16
23
18
16
23
21
20
19
16

664
935
664
935
1160
1388
580
926
1070
1230
1280
1360
1715
1955
1355
1440
1515
1665
1960
1360
1715
1955
1355
1440
1515
1665
1960

NOTES:
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set cooling speed
** Denotes factory set electric heating speed
Table 21. P5RD

Denotes Factory cooling & electric heating speed

48
34
48
34
27
23
54
34
30
26
25
23
18
16
23
22
21
19
16
23
18
16
23
22
21
19
16

562
846
562
846
1110
1342
520
874
1027
1180
1240
1325
1660
1895
1320
1420
1485
1635
1940
1325
1660
1895
1320
1420
1485
1635
1940

56
37
56
37
28
24
61
36
31
27
25
24
19
17
24
22
21
19
16
24
19
17
24
22
21
19
16

CFM
460
710
460
710
1043
1263
480
813
965
1070
1195
1285
1605
1830
1290
1385
1455
1610
1905
1285
1605
1830
1290
1385
1455
1610
1905

0.7
HEAT
RISE
69
44
69
44
30
25
66
39
33
30
26
25
20
17
24
23
22
20
17
25
20
17
24
23
22
20
17

CFM

0.8
HEAT
RISE

536

59

536
957
1180
455
752
906
1010
1150
1235
1535
1740
1255
1345
1425
1580
1850
1235
1535
1740
1255
1345
1425
1580
1850

59
33
27
69
42
35
31
27
26
21
18
25
23
22
20
17
26
21
18
25
23
22
20
17

Series Blower Data - (Single Phase Models)

P5RF SERIES SMALL PACK


UNIT

X24K

X36K

X48

X60

BLOWER
SETTING

0.1
HEAT
CFM
RISE

0.2
HEAT
CFM
RISE

External Static Pressure Drop - inches water column


0.3
0.4
0.5
0.6
HEAT
HEAT
HEAT
HEAT
CFM
CFM
CFM
CFM
RISE
RISE
RISE
RISE

0.7
HEAT
CFM
RISE

0.8
HEAT
CFM
RISE

Tap T1*
Tap T2
Tap T3**
Tap T4***
Tap T5
Tap T1*
Tap T2
Tap T3**
Tap T4***
Tap T5
Tap T1*
Tap T2
Tap T3***
Tap T4**
Tap T5
Tap T1*
Tap T2
Tap T3***
Tap T4**
Tap T5

990
1030
1080
1160
1320
1065
1110
1170
1480
1580
1140
1315
1465
1560
1740
1154
1270
1590
1810
2023

790
850
925
1100
1290
875
955
1110
1450
1545
1040
1280
1435
1525
1710
1097
1233
1531
1786
1998

520
560
800
1040
1250
630
900
1060
1420
1500
980
1230
1400
1500
1680
1060
1204
1504
1757
1968

570
850
1080
394
700
885
1285
1380
790
1080
1245
1350
1545
906
1057
1389
1661
1842

515
815
1030

61
39
31

660
840
1240
1350
745
1030
1200
1315
1510
868
1024
1365
1634
1783

48
38
25
23
42
31
26
24
21
36
31
23
19
18

32
31
29
27
24
30
28
27
21
20
28
24
22
20
18
27
25
20
17
16

40
37
34
29
24
36
33
28
22
20
30
25
22
21
18
29
26
21
18
16

61
56
39
30
25
50
35
30
22
21
32
26
23
21
19
30
26
21
18
16

440
720
1000
1200
580
845
1025
1385
1480
945
1200
1360
1465
1650
1026
1172
1476
1731
1944

72
44
32
26
54
37
31
23
21
33
26
23
22
19
31
27
21
18
16

385
675
960
1165
510
800
985
1355
1450
900
1160
1320
1425
1620
979
1136
1452
1706
1921

NOTES:
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set low cooling & heating speed.
** Denotes factory set high cooling & heating speed.
Table
*** Denotes factory set electric heating speed.

82
47
33
27
62
39
32
23
22
35
27
24
22
20
32
28
22
19
16

615
910
1125
450
755
940
1320
1420
845
1125
1285
1390
1580
946
1095
1419
1681
1884

51
35
28
70
42
34
24
22
37
28
25
23
20
33
29
22
19
17

55
37
29
80
45
36
25
23
40
29
25
23
20
35
30
23
19
17

22. P5RF Series Blower Data - (Small Pack)


27

P6SD SERIES - SINGLE PHASE


UNIT

X36

X48

X60

BLOWER
SETTING
Low*
Medium
High
Low*
Medium
High
Tap T1
Tap T2**
Tap T3*
Tap T4
Tap T5

External Static Pressure Drop - inches water column


0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
RISE
RISE
RISE
RISE
RISE
RISE
RISE
RISE
1153
1367
1610
1584
2026
2361
1515
1580
1740
1960
2090

27
23
20
20
16
13
21
20
18
16
15

1102
1320
1562
1568
1982
2278
1450
1520
1690
1910
2050

29
24
20
20
16
14
22
21
19
17
15

1043
1271
1504
1532
1935
2218
1380
1460
1650
1840
2010

30
25
21
21
16
14
23
22
19
17
16

990
1205
1442
1489
1889
2141
1350
1400
1600
1820
1975

32
26
22
21
17
15
23
23
20
17
16

912
1138
1365
1445
1822
2066
1280
1300
1360
1540
1780

35
28
23
22
17
15
25
24
23
21
18

831
1065
1295
1387
1744
1976
1250
1280
1500
1740
1900

38
30
24
23
18
16
25
25
21
18
17

731
968
1214
1322
1660
1870
1200
1260
1460
1700
1850

43
33
26
24
19
17
26
25
22
19
17

618
845
1109
1236
1554
1758
1160
1230
1390
1600
1790

51
37
28
26
20
18
27
26
23
20
18

NOTES:
Calculated values in matrix are all with 10KW for 1 phase
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set cooling speed
** Denotes factory set electric heating speed

Table 23. P6SD Series Blower Data - (Single Phase)


P6SD SERIES - 3 PHASE
UNIT

X36

X48

X60

BLOWER
SETTING
Low*
Medium
High
Low*
Medium
High
Tap T1
Tap T2**
Tap T3*
Tap T4
Tap T5

External Static Pressure Drop - inches water column


0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
RISE
RISE
RISE
RISE
RISE
RISE
RISE
RISE
1153
1367
1610
1584
2026
2361
1515
1580
1740
1960
2090

25
21
18
18
14
12
19
18
16
15
14

1102
1320
1562
1568
1982
2278
1450
1520
1690
1910
2050

26
22
18
18
14
12
20
19
17
15
14

1043
1271
1504
1532
1935
2218
1380
1460
1650
1840
2010

27
22
19
19
15
13
21
19
17
15
14

990
1205
1442
1489
1889
2141
1350
1400
1600
1820
1975

29
24
20
19
15
13
21
20
18
16
14

912
1138
1365
1445
1822
2066
1280
1300
1360
1540
1780

31
25
21
20
16
14
22
22
21
18
16

831
1065
1295
1387
1744
1976
1250
1280
1500
1740
1900

34
27
22
21
16
14
23
22
19
16
15

731
968
1214
1322
1660
1870
1200
1260
1460
1700
1850

39
29
23
22
17
15
24
23
19
17
15

618
845
1109
1236
1554
1758
1160
1230
1390
1600
1790

46
34
26
23
18
16
25
23
20
18
16

NOTES:
Calculated values in matrix are all with 9KW for 3 phase
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set cooling speed
** Denotes factory set electric heating speed

Table 24. P6SD Series Blower Data - (3 Phase)

Q4SE & PPH1SE


Nominal
KW

CFM

0-5
6-10
11-15
16-20

500
700
900
1100

Switch Number
3
4
5
6
0
1
0
1

0
0
1
1

NOTE: 1-ON, 0=OFF

Table 25. Q4SE/PPH1SE Series Minimum


Electric Heat Airflow - (all models)

28

Q5RD SERIES SMALL PACK


UNIT

024K

030K
036KA

036K

042K

048KA

048K

060K

BLOWER
SETTING
Low T6
Med T5
High T4
Low
High
Low
High
Tap T1
Tap T2**
Tap T3*
Tap T4
Tap T5
Tap T1
Tap T2*
Tap T3**
Tap T4
Tap T5
Low
Med
High
Tap T1
Tap T2**
Tap T3*
Tap T4
Tap T5
Tap T1
Tap T2
Tap T3**
Tap T4*
Tap T5

External Static Pressure Drop - inches water column


0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
RISE
RISE
RISE
RISE
RISE
RISE
RISE
RISE
607
899
1220
847
1104
1318
1551
1100
1208
1262
1370
1410
1480
1575
1635
1775
2065
1460
1840
2155
1480
1575
1635
1775
2065
1370
1470
1550
1810
1890

52
35
26
37
29
24
20
29
26
25
23
22
21
20
19
18
15
22
17
15
21
20
19
18
15
23
21
20
17
17

555
854
1178
808
1114
1284
1521
900
1080
1199
1333
1340
1455
1545
1505
1740
2040
1440
1815
2115
1455
1545
1505
1740
2040
1340
1440
1520
1770
1870

57
37
27
39
28
25
21
35
29
26
24
24
22
20
21
18
15
22
17
15
22
20
21
18
15
24
22
21
18
17

490
802
1133
770
1064
1248
1477
750
1025
1153
1300
1450
1415
1515
1575
1715
2020
1420
1790
2065
1415
1515
1575
1715
2020
1310
1410
1480
1740
1840

64
39
28
41
30
25
21
42
31
27
24
22
22
21
20
18
16
22
18
15
22
21
20
18
16
24
22
21
18
17

437
743
1091
726
1010
1207
1434
650
972
1110
1260
1320
1390
1475
1545
1695
1985
1390
1760
2020
1390
1475
1545
1695
1985
1280
1380
1450
1720
1820

72
43
29
44
31
26
22
49
33
28
25
24
23
21
20
19
16
23
18
16
23
21
20
19
16
25
23
22
18
17

368
670
1024
664
935
1160
1388
580
926
1070
1230
1280
1355
1440
1515
1665
1960
1360
1715
1955
1355
1440
1515
1665
1960
1260
1360
1430
1690
1800

86
47
31
48
34
27
23
54
34
30
26
25
23
22
21
19
16
23
18
16
23
22
21
19
16
25
23
22
19
18

291
601
946
562
846
1110
1342
520
874
1027
1180
1240
1320
1420
1485
1635
1940
1325
1660
1895
1320
1420
1485
1635
1940
1230
1320
1400
1660
1770

109
53
33
56
37
28
24
61
36
31
27
25
24
22
21
19
16
24
19
17
24
22
21
19
16
26
24
23
19
18

255
533
844
460
710
1043
1263
480
813
965
1070
1195
1290
1385
1455
1610
1905
1285
1605
1830
1290
1385
1455
1610
1905
1195
1290
1380
1610
1710

124
59
37
69
44
30
25
66
39
33
30
26
24
23
22
20
17
25
20
17
24
23
22
20
17
26
24
23
20
18

743

43

536
957
1180
455
752
906
1010
1150
1255
1345
1425
1580
1850
1235
1535
1740
1255
1345
1425
1580
1850
1160
1250
1350
1575
1670

59
33
27
69
42
35
31
27
25
23
22
20
17
26
21
18
25
23
22
20
17
27
25
23
20
19

NOTES:
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set cooling speed
** Denotes factory set electric heating speed

Denotes Factory cooling and electric heating speed

Table 26. Q5RD Series Blower Data - (Small Pack)

29

Q5RF SERIES SMALL PACK


UNIT

X24K

X36K

X48

X60

BLOWER
SETTING

External Static Pressure Drop - inches water column


0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
HEAT
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
RISE
RISE
RISE
RISE
RISE
RISE
RISE
RISE

Tap T1*
Tap T2**
Tap T3
Tap T4***
Tap T5
Tap T1*
Tap T2
Tap T3**
Tap T4***
Tap T5
Tap T1*
Tap T2
Tap T3***
Tap T4**
Tap T5
Tap T1
Tap T2*
Tap T3***
Tap T4**
Tap T5

990
1040
1080
1160
1330
1020
1060
1280
1480
1580
1150
1300
1460
1520
1740
1150
1250
1560
1750
1960

32
30
29
27
24
31
30
25
21
20
27
24
22
21
18
27
25
20
18
16

790
850
920
1100
1300
840
900
1240
1450
1550
1090
1270
1430
1480
1710
1100
1200
1530
1700
1930

40
37
34
29
24
38
35
25
22
20
29
25
22
21
18
29
26
21
19
16

560
600
800
1040
1250
600
750
1200
1420
1520
1030
1240
1400
1450
1680
1060
1170
1500
1670
1900

56
53
39
30
25
53
42
26
22
21
31
25
23
22
19
30
27
21
19
17

540
550
720
1000
1200
500
700
1180
1390
1480
1000
1200
1370
1420
1650
1030
1150
1470
1630
1860

59
57
44
32
26
63
45
27
23
21
32
26
23
22
19
31
27
21
19
17

500
680
960
1170

63
46
33
27

620
900
1130

51
35
28

570
850
1080

55
37
29

520
820
1030

61
39
31

650
1140
1360
1450
950
1160
1340
1390
1620
980
1130
1450
1600
1830

49
28
23
22
33
27
24
23
20
32
28
22
20
17

600
1100
1320
1420
900
1120
1300
1360
1590
950
1100
1420
1580
1800

53
29
24
22
35
28
24
23
20
33
29
22
20
18

540
1070
1290
1380
850
1090
1250
1330
1540
900
1060
1390
1560
1770

59
30
24
23
37
29
25
24
21
35
30
23
20
18

500
1010
1240
1350
800
1050
1200
1300
1500
870
1020
1360
1530
1740

63
31
25
23
39
30
26
24
21
36
31
23
21
18

NOTES:
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set low cooling & heating speed.
** Denotes factory set high cooling & heating speed.
*** Denotes factory set electric heating speed.

Table 27. Q5RF Series Blower Data - (Small Pack)

30

Q6SD SERIES (SINGLE PHASE)


External Static Pressure Drop - inches water column
UNIT

X24

X30

X36

X42

X48

X60

0.1

BLOWER
SETTING

Tap T1*
Tap T2**
Tap T3
Tap T4
Tap T5
Tap T1**
Tap T2*
Tap T3
Tap T4
Tap T5
Tap T1**
Tap T2
Tap T3*
Tap T4
Tap T5
Tap T1**
Tap T2
Tap T3
Tap T4*
Tap T5
Tap T1*
Tap T2**
Tap T3
Tap T4
Tap T5
Tap T1
Tap T2**
Tap T3*
Tap T4
Tap T5

0.2

0.3

0.4

CFM

HEAT
RISE

CFM

HEAT
RISE

CFM

HEAT
RISE

1110
1211
1400
1600
1700
1211
1275
1400
1600
1700
1150
1230
1464
1600
1700
1150
1230
1400
1524
1700
1515
1580
1740
1960
2090
1515
1580
1740
1960
2090

28
26
23
20
19
26
25
23
20
19
27
26
22
20
19
27
26
23
21
19
21
20
18
16
15
21
20
18
16
15

869
996
1350
1500
1650
996
1077
1350
1500
1650
1050
1190
1394
1500
1650
1050
1190
1350
1476
1650
1450
1520
1690
1910
2050
1450
1520
1690
1910
2050

36
32
23
21
19
32
29
23
21
19
30
27
23
21
19
30
27
23
21
19
22
21
19
17
15
22
21
19
17
15

529
700
1200
1400
1600
700
940
1200
1400
1600
1000
1120
1332
1400
1600
1000
1120
1200
1424
1600
1380
1460
1650
1840
2010
1380
1460
1650
1840
2010

60
45
26
23
20
45
34
26
23
20
32
28
24
23
20
32
28
26
22
20
23
22
19
17
16
23
22
19
17
16

0.5

CFM

HEAT
RISE

609
1150
1300
1565
609
876
1150
1300
1565
950
1080
1272
1300
1565
950
1080
1150
1379
1565
1350
1400
1600
1820
1975
1350
1400
1600
1820
1975

52
27
24
20
52
36
27
24
20
33
29
25
24
20
33
29
27
23
20
23
23
20
17
16
23
23
20
17
16

0.6

CFM

HEAT
RISE

CFM

HEAT
RISE

1080
1200
1530

29
26
21

1030
1050
1480

31
30
21

807
1080
1200
1530
850
1000
1216
1200
1530
850
1000
1080
1329
1530
1300
1360
1540
1780
1940
1300
1360
1540
1780
1940

39
29
26
21
37
32
26
26
21
37
32
29
24
21
24
23
21
18
16
24
23
21
18
16

732
1030
1050
1480
780
950
1143
1050
1480
780
950
1030
1268
1480
1250
1300
1500
1740
1900
1250
1300
1500
1740
1900

43
31
30
21
41
33
28
30
21
41
33
31
25
21
25
24
21
18
17
25
24
21
18
17

NOTES:
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set coling speed
** Denotes factory set electric heating speed

Table 28. Q6SD Series Blower Data - (Single Phase Models)

31

Q6SD SERIES (3 PHASE)


External Static Pressure Drop - inches water column
Unit

X36

X48

X60

0.1

Blower
Setting

Tap T1**
Tap T2
Tap T3*
Tap T4
Tap T5
Tap T1*
Tap T2**
Tap T3
Tap T4
Tap T5
Tap T1
Tap T2**
Tap T3*
Tap T4
Tap T5

0.2

0.3

0.4

0.5

0.6

CFM

HEAT
RISE

CFM

HEAT
RISE

CFM

HEAT
RISE

CFM

HEAT
RISE

CFM

HEAT
RISE

CFM

HEAT
RISE

1150
1230
1464
1600
1700
1515
1580
1740
1960
2090
1515
1580
1740
1960
2090

25
23
19
18
17
19
18
16
15
14
19
18
16
15
14

1050
1190
1394
1500
1650
1450
1520
1690
1910
2050
1450
1520
1690
1910
2050

27
24
20
19
17
20
19
17
15
14
20
19
17
15
14

1000
1120
1332
1400
1600
1380
1460
1650
1840
2010
1380
1460
1650
1840
2010

28
25
21
20
18
21
19
17
15
14
21
19
17
15
14

950
1080
1272
1300
1565
1350
1400
1600
1820
1975
1350
1400
1600
1820
1975

30
26
22
22
18
21
20
18
16
14
21
20
18
16
14

850
1000
1216
1200
1530
1300
1360
1540
1780
1940
1300
1360
1540
1780
1940

33
28
23
24
19
22
21
18
16
15
22
21
18
16
15

780
950
1143
1050
1480
1250
1300
1500
1740
1900
1250
1300
1500
1740
1900

36
30
25
27
19
23
22
19
16
15
23
22
19
16
15

NOTES:
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set coling speed
** Denotes factory set electric heating speed

Table 29. Q6SD Series Blower Data - (3 Phase Models)

INSTALLER
PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE UNIT OWNER.