Technical Specifications of Variable Frequency Drives (with Panel and DOL Bypass
system)
Abbreviations:
AC : Alternating Current
BIS : Bureau of Indian Standards
BS : British Standard
CBCT : Core Balance Current Transformer
CFL : Compact Fluorescent Lamp
DC : Direct Current
DCS : Distributed Control System
DOL : Direct On Line
ELR : Earth Leakage Relay
EM : Electromagnetic
IEC : International Electro technical Commission
IEEE : Institute of Electrical and Electronics Engineers
IGBT : Insulated Bipolar Transistor
IO : Input/output
IP : Ingress Protection
IS : Indian Standard
LED : Light Emitting Diode
MCB : Miniature Circuit Breaker
MCCB : Moulded Case Circuit Breaker
MTBF : Mean Time Between Failure
NEMA : National Electrical Manufacturer's Association
PCC : Point of Common Coupling
PEM : Project Engineering Management
PLC : Programmable Logic Controller
PO : Purchase Order
PVC : Poly Vinyl Chloride
THD : Total Harmonic Distortion
VDE : Verband Deutscher Electrotechniker
VFD : Variable Frequency Drive
2.2 In case of imported equipment, the standards of the country of origin shall be
applicable if these standards are equivalent or more stringent than the applicable Indian
standards.
2.3 The equipment shall also conform to the provisions of relevant rules and regulations
of Central Electricity Authority and other statutory regulations currently in force in the
country as amended up to date.
5.4 Cooling
Cooling system shall include well-dimensioned panel, adequate cooling airflow path,
module cooling fan and if necessary, panel cooling fan. Vendor shall ensure that the panel
dimensions and flow paths have been designed for continuous running at the specified
ambient without overheating. For fan cooled drives, redundant ventilating fans shall be
provided. Alarm is to be provided for cooling fan failure.
5.5 Equipment/ Component Specification
5.5.1 Power Converter
i. The static power converter shall consist of a line side power converter for
operation as a rectifier and a load side power converter for operation as a fully controlled
inverter.
ii. Normally, for all output short circuits, the inverter shall interrupt the current
before any semi-conductor fuse blows. For internal short circuits, semi-conductor fuse
protection shall be provided, and for faults upstream of semi-conductor fuses, the
converter shall be able to withstand a three-phase short circuit current until interrupted by
normal breaker operation. In case of fuse less design, the failure shall be limited to the
particular device, without causing any damage to other parts of the power module. There
must be clear annunciation of the failure of the device.
5.5.4.3 Bypass feature with breaker/power contactor along with necessary protection &
metering shall be provided by Purchaser. All interlocks as required for safe and reliable
operation of VFD system along with bypass feeder provided by Purchaser shall be
provided in VFD system. Necessary space for terminating power cables from owner’s
bypass feeder in VFD panel after the output contactor/Load break switch shall be
provided.
A typical scheme has been enclosed in these specifications.
5.5.5 Protection, Control, Metering and Indication/ Annunciation
i.) The manufacturer shall provide all the necessary system control,
protection; alarm equipment and metering for the entire drive system and its auxiliary
equipment.
ii.) Automatic sequence control shall include start-up of cooling system,
interlock checking, automatic start and run-up of drive, planned and emergency
shutdown. The same shall be processed through microprocessor based system.
5.5.10 Indications
The following indications shall be provided as a part of the Operator Control panel.
i.) Motor running
ii.) Motor stopped
iii.) VFD System Fault
iv.) System ready to start
v.) AC mains ON
vi.) Drive 'ON'
vii.) Motor zero speed
viii.) Drive ON VFD
ix.) Drive ON Bypass
Potential free contacts of items i)-to iv) each, shall be wired separately for indications in
DCS/ECS system.
5.5.11 Metering
Digital display of the following parameters shall be as a part of the Operator Control
Panel, selectable by the operator.
i.) Input AC voltage
ii.) Input AC frequency
iii.) Input AC Current
iv.) Output voltage
v.) DC Bus Voltage
vi.) Output current VFD/ Bypass
vii.) Output frequency
viii.) Drive thermal state
ix.) Motor speed
x.) Motor energy meter
xi.) 4-20 mA AI and AO
Necessary transducer shall be provided with 4-20mA output for indicating motor speed
5.5.12 Annunciations
Potential free contacts shall be provided for following annunciations and shall be wired
up to terminal block for owner's use for remote monitoring:
x.) Rectifier fuse failure/Drive fault
xi.) Main AC failure
xii.) Inverter fuse failure/Drive fault
xiii.) Inverter overload
xiv.) Inverter high temperature/Drive fault
xv.) Failure of panel cooling system
xvi.) Motor failed to start/Drive fault
xvii.) “Drive run” and “Drive fault” signal to be provided separately.
All drive internal faults will be annunciated as drive fault.
The VSDS shall be suitable for the load characteristics and operation duty of the driven
equipment, the equipment shall be suitable for continuous operation.
The converter cooling air will be at the switch room temperature. If cooling fans are used,
redundancy shall be provided. The cooling shall be fan assisted through the converter
cubicle and will be exhausted back into the switch room.
The converter rating shall be determined by the Converter Vendor as per details of the
load provided in the data sheet
9.0 Painting
9.1 All metal surfaces shall be thoroughly cleaned and de-greased to remove mill
scale, rust, grease and dirt. Fabricated structures shall be pickled and then rinsed to
remove any trace of acid. The under-surface shall be prepared by applying a coat of
phosphate paint and a coat of yellow zinc chromate primer. The under-surface shall be
made free from all imperfections before undertaking the finishing coat.
9.2 After preparation of the under surface, the switchboard shall be provided with
epoxy based powder coating. The color shade of the final paint shall be as per
manufacturer’s standard, unless otherwise specified. Panel finish shall be free from
imperfections like pinholes, orange peels, runoff paint, etc.
Technical Specifications for Variable Frequency Drive System Page 14 of 19
9.3 All unpainted steel parts shall be zinc passivated, cadmium plated or suitably
treated to prevent rust and corrosion. If these parts are moving elements, then these shall
be greased.
10.4 The following Routine, Type and Special Tests shall be conducted on the
complete VFD drive system (as defined in C1.1.0) above as per IEC 61800-2:
10.4.1 Routine Tests
i.) Insulation Test
ii.) Light Load and Functional Test
iii.) Checking of Auxiliary Devices
iv.) Checking the properties of the control equipment
v.) Checking the Protective Devices
vi.) High Voltage test
vii.) Test capability to ride through voltage dips upto 20%
The equipment shall be divided in to several shipping sections for protection and ease of
handling during transportation. The equipment shall be properly packed for transportation
by ship/rail or trailer. The panels shall be wrapped in polyethylene sheets before being
placed in wooden crates/cases to prevent damage to the finish. Crates/ cases shall have
skid bottoms for handling. Special notations such as 'Fragile', 'This side up', 'Weight',
'Owner's particulars', 'PO nos.' etc., shall be clearly marked on the package together with
other details as per purchase order.
The equipment may be stored outdoors for long periods before installation. The packing
should also be suitable for outdoor storage areas with heavy rains/high ambient
temperature unless otherwise agreed.
The VFD shall be supplied with the 2 CDs/Pendrives of PC based software for
programming, measurement of online parameters, downloading and analysis of fault,
disturbance and event records. The software shall be compatible with MS Windows 7
and above. 2 Nos of communication cables and suitable converters for communication
with PC/ Laptop shall be supplied with the VFD.
12.0 Warrantee
12.1 All equipments shall be warranted against manufacturing defects for 36 months
All drawings shall be property of IOCL. Editable soft copies of drawings shall be
submitted for updation and modifications of drawings by the IOCL, in case any
modification or changes are done by the owner in future. The soft copies such submitted
drawings shall be in AutoCad and PDF (both) formats. If drawings are not in AutoCad
format, necessary licensed software shall also be provided along with the drawings.
If any software is required for monitoring, events and parameter access, programming etc,
same shall be supplied free of cost.
16.0 Miscellaneous
16.1 Bidder shall submit the VFD details in attached data sheet for evaluation of the
offer. Relevant brochure shall be attached with the technical bid.
16.2 Evaluation of technical part shall be done strictly on the basis of confirmation
of technical specifications by the bidder. No reference to catalogue / manual etc shall be
made for evaluation. However in case of any discrepancy, query can be raised by the
IOCL, but it shall be binding on the bidder to supply material as per accepted technical
specifications only. Deviations, if any, shall be submitted separately in the deviation
statement only, subject to acceptance.
16.3 Organisational chart and hierarchal reporting structure (at least for division /
business unit level) shall be submitted after placement of purchase order for escalation of
complaints. Names, designations, Phone nos ( mobile and landline) , email ids and
addresses of all the concerned shall be submitted and shall be updated and intimated time
to time to Engineer In Charge.
16.4 The Vendor shall give the details of after sale/service facilities available in
India and approximate time for repair jobs.