0.S24256FES-JAWAHARAT ARRIYADH RIYADH, Saudi Arabia - APS-SM-2.5.24

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

SteelMaster Enquiry

JAWAHARAT MALL RIYADH_APS


Enquiry Ref: 0.S24256FES_APS

Presented By: Shreyas Murumkar


Thursday, May 2, 2024

MEIA

Subset: Steels Protection: 120 Minutes

Sq M Kgs Litres
Total 6162.932 31434.038 22452.884

Subset: Staircase Steels Protection: 120 Minutes

Sq M Kgs Litres
Total 608.213 4015.461 2868.187

Standard: BS.BS5950 - Other

SteelMaster 1200WF - [r9_CF5243]

Page 1
SteelMaster Enquiry
JAWAHARAT MALL RIYADH_APS
Enquiry Ref: 0.S24256FES_APS

Presented By: Shreyas Murumkar


Thursday, May 2, 2024

MEIA

Report Totals Sq M Cans (Number x Can size) Kgs Litres

SteelMaster 1200WF 6771.145 1369 x 18.500 35449.499 25321.071

Unprotected Area 0

Notes:

Standard: BS.BS5950-Other/Congregation.

This schedule is based on the BOQ provided by the client at the time of the enquiry.

Clients are advised to cross-check DFTs against relevant certifications where available.

Clients are advised to cross-check all measures and assumptions used to prepare this report. Jotun shall be advised of any discrepancies accordingly. Jotun cannot be held contractually responsible
for any errors.

All sections are considered to be exposed to fire on 4 sides in the absence of the details.

Members denoted with * are light steel section/s that could not be protected, Jotun have therefore provided DFT based on alternative heavier steel section while the original section is mentioned in the
reference column.

We understand the beams on this project are non-cellular with no holes in their webs.

Staircase steels are treated at storage occupancy.

Standard: BS.BS5950 - Other

SteelMaster 1200WF - [r9_CF5243]

Page 2
SteelMaster Enquiry
JAWAHARAT MALL RIYADH_APS
Enquiry Ref: 0.S24256FES_APS

Presented By: Shreyas Murumkar


Thursday, May 2, 2024

MEIA

Subset: Steels Protection: 120 Minutes

Steel Type Designation Exposure length qty Area Tcrit Use HP/A Product Name WFT DFT Volume Reference
(sides) (m) (#) (m²) (⁰C) (m-¹) (mm) (mm) (litres)

1 EU HE HE 300 B 4 Sides 166.400 1 288.150 530 Column/ALM 115 SteelMaster 1200WF 3.094 2.135 891.536

2 EU HE HE 450 B 4 Sides 176.245 1 357.014 530 Beam 95 SteelMaster 1200WF 2.679 1.849 956.441

3 EU HE HE 550 B 4 Sides 350.100 1 778.506 530 Beam 90 SteelMaster 1200WF 2.559 1.765 1992.197

4 EU IPE IPE 360 4 Sides 8.000 1 10.825 530 Beam 185 SteelMaster 1200WF 4.433 3.059 47.987

5 EU IPE IPE 360 4 Sides 16.000 1 21.650 530 Column/ALM 185 SteelMaster 1200WF 4.433 3.059 95.974

6 EU IPE IPE 450 4 Sides 2885.980 1 4632.471 530 Beam 160 SteelMaster 1200WF 3.931 2.712 18210.244

7 EU IPE IPE 500 4 Sides 4.000 1 6.974 530 Beam 150 SteelMaster 1200WF 3.745 2.584 26.118

8 EU IPE IPE 500 4 Sides 8.000 1 13.949 530 Column/ALM 150 SteelMaster 1200WF 3.745 2.584 52.239

9 EU IPE IPE 600 4 Sides 26.500 1 53.393 530 Beam 130 SteelMaster 1200WF 3.374 2.328 180.148

Total 6162.932 31434.0 22452.884


38

Standard: BS.BS5950 - Other

SteelMaster 1200WF - [r9_CF5243]

Page 3
SteelMaster Enquiry
JAWAHARAT MALL RIYADH_APS
Enquiry Ref: 0.S24256FES_APS

Presented By: Shreyas Murumkar


Thursday, May 2, 2024

MEIA

Subset: Staircase Steels Protection: 120 Minutes

Steel Type Designation Exposure length qty Area Tcrit Use HP/A Product Name WFT DFT Volume Reference
(sides) (m) (#) (m²) (⁰C) (m-¹) (mm) (mm) (litres)

1 EU HE HE 200 A 4 Sides 20.900 1 23.745 520 Beam 210 SteelMaster 1200WF 5.309 3.663 126.062

2 EU HE HE 200 B 4 Sides 114.400 1 131.687 520 Column/ALM 145 SteelMaster 1200WF 3.942 2.720 519.110

3 EU IPE IPE 200 4 Sides 52.000 1 39.947 520 Beam 270 SteelMaster 1200WF 6.350 4.381 253.663 *IPE 140

4 EU IPE IPE 240 4 Sides 12.900 1 11.892 520 Beam 235 SteelMaster 1200WF 5.759 3.973 68.486

5 EU UPN,U,UE UPN 240 4 Sides 507.620 1 400.942 520 Beam 185 SteelMaster 1200WF 4.741 3.271 1900.866

Total 608.213 4015.46 2868.187


1

Standard: BS.BS5950 - Other

SteelMaster 1200WF - [r9_CF5243]

Page 4
SteelMaster Enquiry
JAWAHARAT MALL RIYADH_APS
Enquiry Ref: 0.S24256FES_APS

Presented By: Shreyas Murumkar


Thursday, May 2, 2024

MEIA

JSES Disclaimer
• The Jotun SteelMaster Enquiry System (JSES) has been developed to assist Jotun customers in the estimation of SteelMaster quantities required for intumescent paint
projects. Jotun have taken reasonable care and skill to ensure that, when used correctly, the JSES produces accurate guidance as to the volume of SteelMaster coatings
required. The information provided in this schedule should be verified with the relevant standards and certificates.

• Results are provided without any warranty of any kind, express or implied. Jotun accepts no liability
whatsoever for loss incurred by inaccurate or unreliable results received from the JSES and which is due to human operator input of inaccurate, estimated or erroneous
data.

• Where the operation of the JSES is dependent on third party data no liability is accepted by Jotun in respect of any third party material.

• Unless specifically noted elsewhere in this report, the Dry Film Thicknesses (DFT’s) assume the limiting temperatures as stipulated in the "ASFP Advisory Note" submitted
with this schedule.

• If the composite floor trapezoidal option has been utilised in the enquiry, the operator needs to be made aware that this may not be the most cost effective option. It is an
option to fill the voids between the top of the steel and the floor decking with fire stop blocks which may or may not prove to be a more suitable and competitive option for
the client. The operator should also be aware that for periods of fire resistance in excess of 90 minutes an increased paint film thickness is not an option and the voids must
be filled with fire stop blocks. In any event the operator is deemed to have satisfied themselves with the industry guidelines for these scenarios as laid out in the latest
revision of the ASFP 'Yellow Book.'

• All supplied intumescent thicknesses are theoretical only and the applicator is recommended to include for their normal loss factor (wastage/ coat back/ overspray etc.) in
addition to these quantities.

• Contractors must satisfy themselves with the accuracy of the square metre areas provided in this report.

• Primers and topcoats must be compatible with SteelMaster. SteelMaster should not be exposed to an environment which is outside the manufacturer’s guidance.
Discuss with Jotun for specific system recommendation.

• This schedule is produced using JSES software and cannot be altered or tampered with using any proprietary editing software, the users of this report can verify by
sending the copy of the schedule to FireEstimation@jotun.com

Standard: BS.BS5950 - Other

SteelMaster 1200WF - [r9_CF5243]

Page 5
SteelMaster Enquiry
JAWAHARAT MALL RIYADH_APS
Enquiry Ref: 0.S24256FES_APS

Presented By: Shreyas Murumkar


Thursday, May 2, 2024

MEIA

• The information contained in this report is privileged information and has been produced under the terms of the JSES software license. This information must not be
passed on to any third party without written permission from Jotun.

Standard: BS.BS5950 - Other

SteelMaster 1200WF - [r9_CF5243]

Page 6