Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

R

Specifications and Ordering Information


/Seismic Monitor
3500/42M Proximitor

Channels 1 and 2 can perform one function, while channels


3 and 4 perform another (or the same) function.

The primary purpose of the 3500/42M monitor is to provide:

1) Machinery protection by continuously comparing


monitored parameters against configured alarm
setpoints to drive alarms.
2) Essential machine information for both
operations and maintenance personnel.

Each channel, depending on configuration, typically


conditions its input signal into various parameters called
“proportional values”. Alert setpoints can be configured for
each active proportional value and Danger setpoints can
be configured for any two of the active proportional values.

Specifications

Inputs

Signal: Accepts from 1 to 4 proximity,


Description velocity or acceleration transducer
signals.

Input Impedance

The 3500/42M Proximitor®/Seismic Monitor is a 4-channel Standard I/O: 10 k Ω. (Proximitor® and


monitor that accepts input from proximity and seismic Acceleration Inputs).
transducers, conditions the signal to make various vibration
and position measurements, and compares the conditioned TMR I/O: 50 k Ω (Bussed /transducer
signals with user-programmable alarms. Each channel of Configuration), 150 kΩ (Discrete
the 3500/42M can be programmed using the 3500 Rack Transducer Configuration).
Configuration Software to perform any of the following
functions: Power 7.7 Watts, typical.
Consumption:
! Radial Vibration
! Thrust Position Sensitivity
! Eccentricity
! Differential Expansion Radial Vibration: 3.94 mV/µm (100 mV/mil) or
! Acceleration 7.87 mV/µm (200 mV/mil).
! Velocity
! Shaft Absolute Thrust: 3.94 mV/µm (100 mV/mil) or
7.87 mV/µm (200 mV/mil).
Note: The monitor channels are programmed in pairs and
can perform up to two of these functions at a time.

BNC Part Number 143694-01 Page 1 of 10


Revision A, June 2000
Eccentricity: 3.94 mV/µm (100 mV/mil) or Recorder: +4 to +20 mA. Values are
7.87 mV/µm (200 mV/mil). proportional to monitor full-scale.
Individual recorder values are
Differential 0.394 mV/µm (10 mV/mil) or 0. provided for each channel. Monitor
Expansion: 0.787 mV/µm (20 mV/mil). operation is unaffected by short
circuits on recorder outputs.
Acceleration: 10 mV/(m/s2) (100 mV/g).
Voltage 0 to +12 Vdc range across load.
Velocity: 20 mV/(mm/s) pk Compliance Load resistance is 0 to 600 Ω.
(500 mV/(in/s) pk) or (current output):
5.8 mV/(mm/s) pk
(145 mV/(in/s) pk) or Resolution: 0.3662 µA per bit
4 mV/(mm/s) pk ±0.25% error at room temperature
(100 mV/(in/s) pk). ±0.7% error over temperature
range.
Shaft Update rate 100 ms or less.
Absolute, 3.94 mV/µm (100 mV/mil) or
Radial Vibration: 7.87 mV/µm (200 mV/mil). Shaft Absolute The Shaft Absolute I/O modules
Buffered Outputs: have one output for each channel
Shaft group. Each output is short-circuit
Absolute, 3.94 mV/µm (100 mV/mil) or protected.
Direct: 7.87 mV/µm (200 mV/mil).
Shaft Absolute 300 Ω.
Shaft 20 mV/(mm/s) pk Output Impedance:
Absolute, (500 mV/(in/s) pk) or
Velocity: 5.8 mV/(mm/s) pk
(145 mV/(in/s) pk) or Signal Conditioning Specified at +25°C (+77° F).
4 mV/(mm/s) pk
(100 mV/(in/s) pk). Radial Vibration
Frequency Response

Outputs Direct Filter: User-programmable, 4 Hz to 4000


Hz or 1 Hz to 600 Hz.
Front Panel LEDs
Gap Filter: -3 dB at 0.09 Hz.
OK LED: Indicates when the 3500/42M is
operating properly. Not 1X Filter: 60 cpm to 15.8 times running speed.
Constant Q notch filter. Minimum
TX/RX LED: Indicates when the 3500/42M is rejection in stopband of -34.9 dB.
communicating with other modules
in the 3500 rack. Smax: 0.125 to 15.8 times running speed.

Bypass LED: Indicates when the 3500/42M is in 1X & 2X Vector Constant Q Filter. Minimum rejection
Bypass Mode. Filter: in stopband of -57.7 dB.

Buffered The front of each monitor has one Note: 1X & 2X Vector, Not 1X, and Smax
Transducer coaxial connector for each channel. parameters are valid for machine speeds of
60 cpm to 60,000 cpm.
Outputs: Each connector is short-circuit
protected.
Accuracy
Output Impedance: 550 Ω.
Direct and Gap: Within ± 0.33% of full scale typical,
±1% maximum.
Transducer Power -24 Vdc.
Supply:

BNC Part Number 143694-01 Page 2 of 10


Revision A, June 2000
1X & 2X: Within ±0.33% of full-scale typical,
±1% maximum. If added frequency range is required, the 3500/42M can be
configured as a two-channel monitor (use channels 1and 3).
Smax: Within ±5% maximum. This lets you combine the resources normally used for
filtering of two channels and use them for one. The following
Not 1X: ±3% for machine speeds less than table represents the frequency ranges available for each filter
30,000 cpm. option when this is done.
±8.5% for machine speeds greater
than 30,000 cpm.

Thrust and
Differential Expansion Output Without Filter, Low Pass Filter, High With Integration
Frequency Response Type Pass Filter
RMS 10 Hz to 30 kHz 10 Hz to 14.5 kHz
Peak 3 Hz to 30 kHz 10 Hz to 14.5 kHz
Direct Filter: -3 dB at 1.2 Hz.

Gap Filter: -3 dB at 0.41 Hz. Dual Acceleration


Filter Quality: High-Pass: 4-pole (80 dB per
Accuracy: Within ± 0.33% of full-scale typical, decade, 24 dB per octave).
± 1% maximum.
Low-Pass: 4-pole (80 dB per decade, 24 dB per
EIPP Monitor octave).
Frequency Response
Accuracy: Within ± 0.33% of full scale typical,
Direct Filter: -3 dB at 15.6 Hz. ± 1% maximum. Exclusive of filters.
Gap Filter: -3 dB at 0.41 Hz. Dual Velocity
Frequency
Accuracy: Within ± 0.33% of full-scale typical, Response:
± 1% maximum.
RMS: 10 to 5,500 Hz, -3 dB.
Acceleration The following table represents the
Frequency frequency ranges for the 3500/42M Peak or 3 to 5,500 Hz, -3 dB.
Response: under different filtering options. Peak-to-Peak:
Resources used for filtering are
assigned based on channel pairs. It
is possible to select different filtering
options for the two channels of a Filter Quality
channel pair. However, the
frequency response for both High-Pass: 2-pole (40 dB per decade, 12 dB per
channels will be limited to the worst octave).
case frequency response of the
individual channels. Low-Pass: 4-pole (80 dB per decade, 24 dB per
octave).
Output Low Pass Filter, Integration after
Type Without Filter High Pass Filter filters
RMS 10 Hz to 30 kHz 10 Hz to 9.155 kHz 10 Hz to 9.155 kHz Quality: Within ± 0.33% of full scale typical,
Peak 3 Hz to 30 kHz 3 Hz to 9.155 kHz 10 Hz to 9.155 kHz ± 1% maximum. Exclusive of filters.
Velomitor: Full Scale 0-0.5: ±3% Typical
Full Scale 0-1.0: ±2% Typical
Full Scale 0-2.0: ±1% Typical

Shaft Absolute,
Radial Vibration
Frequency Response

BNC Part Number 143694-01 Page 3 of 10


Revision A, June 2000
Direct Filter: User-programmable, 4 Hz to 4000 Alarm Setpoints: Alert levels can be set for each
Hz or 1 Hz to 600 Hz. value measured by the monitor. In
addition, Danger setpoints can be
Gap Filter: -3 dB at 0.09 Hz. set for any two of the values
measured by the monitor. All alarm
1X Vector Filter: Constant Q Filter. Minimum rejection setpoints are set using software
in stopband of -57.7 dB. configuration. Alarms are adjustable
and can normally be set from 0 to
Note: 1X Vector parameters are valid for 100% of full-scale for each
machine speeds of 240 cpm to 60,000 cpm. measured value. The exception is
when the full-scale range exceeds
the range of the transducer. In this
Accuracy case, the setpoint will be limited to
the range of the transducer.
Direct and Gap: Within ± 0.33% of full scale typical, Accuracy of alarms are to within
±1% maximum. 0.13% of the desired value.
1X: Within ±0.33% of full-scale typical, Alarm Time Delays: Alarm delays can be programmed
±1% maximum. using software, and can be set as
follows:
Shaft Absolute,
Velocity Alert: From 1 to 60 seconds in 1 second
Frequency intervals.
Response: Danger: 0.1 seconds or from 1 to 60 seconds
in 1 second intervals.
Peak or User-programmable, 1 to 4,000 Hz,
Peak-to-Peak: -3 dB.
Proportional Values Proportional values are vibration
measurements used to monitor the
Filter Quality
machine. The Proximitor Seismic
Monitor provides the following
High-Pass: 2-pole (40 dB per decade, 12 dB per
proportional values:
octave).
Radial Vibration: Direct, Gap, 1X Amplitude, 1X
Low-Pass: 2-pole (40 dB per decade, 12 dB per
Phase Lag, 2X Amplitude, 2X Phase
octave).
Lag, Not 1X Amplitude, and Smax
Amplitude.
Accuracy: Within ± 0.33% of full scale typical,
± 1% maximum. Exclusive of filters.
Thrust Position: Direct, Gap.
Shaft Absolute ± 6.0% @ 25 C
Differential Direct, Gap.
Buffered Output:
Expansion:
Alarms Eccentricity: Peak-to-peak, Gap, Direct Minimum,
Direct Maximum.

Acceleration: Direct, define as one of the


following: RMS Acceleration or,
peak Acceleration or, RMS Velocity
or, peak Velocity or, Band-pass
peak Acceleration or, Band-pass
peak Velocity.

BNC Part Number 143694-01 Page 4 of 10


Revision A, June 2000
Velocity: Direct, define as one of the Conducted Susceptibility
following: RMS Velocity or, peak ENV 50141, Criteria A
Velocity, peak-to-peak Displacement
or, Band-pass peak Velocity or, Electrical Fast Transient
Band-pass or peak-to-peak EN 61000-4-4, Criteria B
Displacement.
Surge Capability
Shaft Absolute, Direct, Gap, 1X Amplitude, 1X EN 61000-4-5, Criteria B
Radial Vibration: Phase Lag
Shaft Absolute, Shaft Absolute Direct, Shaft Magnetic Field
Velocity: Absolute 1X Amplitude, Shaft EN 61000-4-8, Criteria A
Absolute 1X Phase Lag, Velocity
Direct, Velocity 1X Amplitude, Power Supply Dip
Velocity 1X Phase Lag EN 61000-4-11, Criteria B

Radio Telephone
Environmental ENV 50204, Criteria B
Limits
Low Voltage Directives: Certificate of Conformity: 134036
Operating -30°C to +65°C (-22°F to +150°F)
Temperature: when used with Internal/External EN 61010-1 Safety Requirements
Termination Proximitor®/Seismic I/O
Module.

Operating 0°C to +65°C (32°F to +150°F)


Temperature: when used with Proximitor®/Seismic Hazardous Area Approvals
Internal Barrier I/O Module (Internal
Termination). CSA/NRTL/C: Class 1, Division 2 Groups
A,B,C,D T4 @ Ta = 65 °C
Storage -40°C to +85°C (-40°F to +185°F).
Temperature: Certification Number
BN26744C-18
Humidity: 95%, noncondensing. When used with Internal Barrier I/O Module, refer to
specification sheet 141495-01 for approvals information.

CE Mark Directives
Physical
EMC Directives: Certificate of Conformity: 136669
EN50081-2 Monitor Module

Radiated Emissions Dimensions 241.3 mm x 24.4 mm x 241.8 mm


EN 55011, Class A (Height x Width x (9.50 in x 0.96 in x 9.52 in).
Depth):
Conducted Emissions
EN 55011, Class A Weight: 0.91 kg (2.0 lbs.).

EN50082-2 I/O Modules


(non-barrier)
Electrostatic Discharge
EN 61000-4-2, Criteria B Dimensions 241.3 mm x 24.4 mm x 99.1 mm
(Height x Width x (9.50 in x 0.96 in x 3.90 in).
Radiated Susceptibility Depth):
ENV 50140, Criteria A

BNC Part Number 143694-01 Page 5 of 10


Revision A, June 2000
Weight: 0.20 kg (0.44 lb.).
Shaft Absolute
I/O Modules (barrier)
The Shaft Absolute Channel Type requires the
Dimensions 241.3 mm x 24.4 mm x 163.1 mm following (or later) firmware and software
(Height x Width x (9.50 in x 0.96 in x 6.42 in). revisions:
Depth): 3500/42M Module Firmware – Revision B
3500/01 Software – Version 2.61
Weight: 0.46 kg (1.01 lbs.).
DM2000 Software - Version 3.10.

Rack Space Utilization of the Shaft Absolute Channel Type


Requirements requires the installation of the M version of the
3500 Proximitor/Seismic monitor. This is easily
Monitor Module: 1 full-height front slot. identified on the front panel as 3500/42M.

I/O Modules: 1 full-height rear slot.

Ordering Information

Proximitor® Seismic Monitor


3500/42-AXX-BXX
Option Descriptions

A: I/O Module Type 01 Seismoprobe I/O Module with


Ordering Considerations Internal Terminations
02 Seismoprobe I/O Module with
External Terminations
General 03 TMR I/O Module with External
Terminations.
The 3500/42M Module requires the following (or 04 I/O Module with Internal
later) firmware, and software revisions: Barriers (4 x prox./accel. ch's)
3500/42M Module Firmware – Revision A and Internal Terminations
3500/01 Software – Version 2.50 05 I/O Module with Internal
3500/02 Software – Version 2.20 Barriers (2 x prox./accl. + 2 x
3500/03 Software – Version 1.21 Velomitor channels) and
Internal Terminations
External Termination Blocks cannot be used with 06 I/O Module with Internal
Internal Termination I/O Modules. Barriers (4 x Velomitor
channels) and Internal
When ordering I/O Modules with External Terminations
Terminations, the External Termination Blocks 07 Shaft Absolute I/O Module with
and Cables must be ordered separately. Internal Terminations
08 Shaft Absolute I/O Module with
Bussed External Termination Blocks are to be External Terminations
used with TMR I/O Modules only. 09 Prox/Velom I/O Module with
Internal Terminations
10 Prox/Velom I/O Module with
Internal Barrier I/O Module External Terminations

The 3500 Internal Barrier specification sheet (part


number 141495-01) should be consulted if the
Internal Barrier Option is selected.

BNC Part Number 143694-01 Page 6 of 10


Revision A, June 2000
128710-01 Recorder External Termination
Notes: Block (Terminal Strip connectors).
1. The following table shows the ordering
option and supported transducer types.
140993-01 Shaft Absolute External Termination
Ordering Prox/ Velom Seismo- Block (Euro Style connectors).
Option Accel probe
A 01& A 02 See Note 4 X
A 03 X X
141001-01 Shaft Absolute External Termination
A 04, A 05, See Note 2 Block (Terminal Strip connectors).
& A 06
A 07 & A 08 X X X 125808-08 Proximitor/Velomitor External
A 09 & A 10 X X Termination Block (Euro Style
connectors).
2. The following table shows the ordering
options that are available for Internal 128015-08 Proximitor/Velomitor External
Barriers with this monitor. Termination Block (Terminal Strip
Ch’s 1 & 2 Ch’s 3 & 4 connectors).
A 04 Prox/Accel Prox/Accel
A 05 Prox/Accel Velomitor
Cables
A 06 Velomitor Velomitor
3500 Transducer (XDCR) Signal to External Termination
(ET) Block Cable
129525 -AXXXX-BXX
3. HTVS transducer is supported in A 09 and Option Descriptions
A 10 I/O module type options.
A: Cable Length 0005 5 feet (1.5 metres)
4. Prox/Accel and Velom are 0007 7 feet (2.1 metres)
supported with the A01 & A02 0010 10 feet (3 metres)
options. However, unless 0025 25 feet (7.5 metres)
seismoprobes will be used the 0050 50 feet (15 metres)
appropriate choice is the A09 0100 100 feet (30.5 metres)
and A10 options.
B: Assembly 0 1 Not Assembled
B: Agency Approval 0 0 None Instructions 0 2 Assembled
Option 0 1 CSA/NRTL/C

3500 Recorder Output to External Termination (ET)


External Block Cable
Termination Blocks 129529-AXXXX-BXX
Option Descriptions
125808-02 Seismoprobe External Termination
Block (Euro Style connectors). A: Cable Length 0005 5 feet (1.5 metres)
0007 7 feet (2.1 metres)
128015-02 Seismoprobe External Termination 0010 10 feet (3 metres)
Block (Terminal Strip connectors). 0025 25 feet (7.5 metres)
0050 50 feet (15 metres)
132242-01 Prox/Seismic Bussed TMR External 0100 100 feet (30.5 metres)
Termination Block (Euro Style
connectors). B: Assembly 0 1 Not Assembled
Instructions 0 2 Assembled
132234-01 Prox Seismic Bussed TMR External
Termination Block (Terminal Strip
connectors). Spares

128702-01 Recorder External Termination 140734-02 3500/42M Proximitor/Seismic


Block (Euro Style connectors). Monitor.

BNC Part Number 143694-01 Page 7 of 10


Revision A, June 2000
128229-01 Seismoprobe I/O Module with 00580434 Internal I/O Module connector
Internal Terminations. header, Euro Style, 8 pin. Used on
I/O modules 128229-01 and
128240-01 Seismoprobe I/O Module with 138708-01.
External Terminations.
00580432 Internal I/O Module connector
126632-01 Prox/Seismic TMR I/O Module with header, Euro Style, 10 pin. Used on
External Terminations. I/O modules 128229-01, 138708-01.

00530843 3500/42M Prox/Seismic I/O Module 00502133 Internal I/O Module connector
four-pin connector shunt. header, Euro Style, 12 pin

143489-01 3500/42M Monitor Manual.

135489-01 I/O Module with Internal Barriers


(Internal terminations)
(4 x Prox/Accel).

135489-02 I/O Module with Internal Barriers


(Internal terminations)
(2 x Prox/Accel + 2 x Velomitor).

135489-03 I/O Module with Internal Barriers


(Internal terminations)
(4 x Velomitor).

138708-01 Shaft Absolute I/O Module with


Internal Terminations.

138700-01 Shaft Absolute I/O Module with


External Terminations.

00517018 3500/42M Shaft Absolute I/O


Module eight-pin connector shunt.

140471-01 Prox/Velom I/O Module with Internal


Terminations.

140482-01 Prox/Velom I/O Module with


External Terminations.

00561941 3500/42M Prox/Velom I/O Module


ten-pin connector shunt.

141860-01 & 3500/42M Firmware IC, one of each


141860-02 is required for proper operation.

04425545 Grounding Wrist Strap (single use


only)

04400037 IC Removal Tool

BNC Part Number 143694-01 Page 8 of 10


Revision A, June 2000
Figures

Front and rear view of the Proximitor®/Seismic Monitor

1. Status LEDs 4. I/O Module with External Terminations


2. Buffered Transducer Outputs 5. TMR I/O Module with External Terminations
3. I/O Module with Internal Terminations

BNC Part Number 143694-01 Page 9 of 10


Revision A, June 2000
Additional I/O Modules of the Proximitor®/Seismic Monitor

1. Prox/Velom I/O Module, Internal Terminations 3. Shaft Absolute I/O Module, Internal Terminations
2. Prox/Velom I/O Module, External Terminations 4. Shaft Absolute I/O Module, External Terminations

Data subject to change without notice.


 2000 Bently Nevada Corporation
 used in this document are registered marks of Bently Nevada Corporation

BNC Part Number 143694-01 Page 10 of 10


Revision A, June 2000

You might also like