Calculate Cable Size and Voltage Drop:
Calculate Voltage Drop and Size of Electrical cable for following data.
Blog Stats
Electrical Details: Electrical Load of 80KW, Distance between Source and Load is 200 Meter, System Voltage 415V
Three Phase, Power Factor is 0.8,Permissible Voltage drop is 5%, Demand Factor is 1, 20,883,456 hits
Cable Laying Detail: Cable is directed buried in Ground in trench at the depth of 1 meter. Ground Temperature is
approximate 35 Deg. No of Cable per Trench is 1. No of Run of Cable is 1 Run.
Soil Details: Thermal Resistivity of Soil is not known. Nature of Soil is Damp Soil. About Jignesh Parmar:
Jignesh Parmar has completed M.Tech (Power
Calculation:
System Control), B.E(Electrical). He is FIE ,MIE
Consumed Load= Total Load x Demand Factor and CEng from Institution of Engineers,India.
Consumed Load in KW= 80 x 1 =80KW Membership No:F-1264873 ,M-1473586.He has
Consumed Load in KVA= KW/P.F more than 21 years experience in Transmission -
Consumed Load in KVA =80/0.8=100KVA Distribution-Electrical Energy theft detection-
Full Load Current= (KVAx1000) / (1.732xVoltage) Electrical Maintenance-Electrical Projects
Full Load Current= (100×1000) / (1.732×415) = 139Amp. (Planning-Designing-Technical Review-
Calculating Correction Factor of Cable from following data : coordination -Execution). He is Presently
Temperature Correction Factor (K1) When Cable is in Air is associate with one of the leading business
group as a Manager at Ahmedabad,India. He has
Temperature Correction Factor in Air :K1 published numbers of Technical Articles in
“Electrical Mirror”, “Electrical India”, “Lighting
Insulation India”,”Smart Energy”, “Industrial
Ambient Temp© Electrix”(Australian Power Publications)
PVC XLPE/EPR Magazines. He is Freelancer Programmer of
Advance Excel and design useful Excel base
60 0.5 0.71
65 0 0.65
Electrical Notes-…
21K followers
70 0 0.58
75 0 0.5
Follow Page
80 0 0.41
Insulation
Ground Temp©
PVC XLPE/EPR BUY ELECTRICAL SOFTWARES
10 1.1 1.07
15 1.05 1.04
20 0.95 0.96
35 0.77 0.89
40 0.71 0.85
45 0.63 0.8
BUY ELECTRICAL SOFTWARES.
50 0.55 0.76
55 0.45 0.71
60 0 0.65
75 0 0.46 85 /100
80 0 0.38
Thermal Resistance Correction Factor (K4) for Soil (When Thermal Resistance of Soil is known):
SEARCH
Copyright © 2018
Soil Thermal Resistivity: 2.5 KM/W
The content in electricalnotes.wordpress.com is
for personal, non-commercial use only. you can
Resistivity K3
not reproduce,republish or communicate any of
the content , including files downloadable from
1 1.18 this website, without the permission of the
copyright owner.The use of this content on any
1.5 1.1 other websites breaches copyright Act. If You
find this content in any other site,it makes the
2 1.05
2.5 1 page you are viewing an infringement of the
copyright.
3 0.96
Recent Posts
Soil Correction Factor(K4) of Soil (When Thermal Resistance of Soil is not known):
Electrical Abstract-Gujarat Fire Prevention and
Life Safety Regulations, 2023
Soil Correction Factor:K4
Quick Reference -Fire Fighting (Part-6)
Very Dry Soil 0.86 Transformer Clearance (Indoor and Outdoor) and
Fire Protection-PART-2
Laying Depth(Meter) Rating Factor Reasons for HV Cable Termination Kit Failure-
Part-1
Archives
Cable Distance Correction Factor(K6)
February 2024 (1)
No of Circuit Nil cable Diameter 0.125m 0.25m 0.5m January 2024 (1)
For selection of Proper Cable following Conditions should be satisfied November 2020 (1)
(1) Cable De rating Amp should be higher than Full Load Current of Load.
October 2020 (2)
(2) Cable Voltage Drop should be less than Defined Voltage drop.
(3) No of Run of Cable >= (Full Load current / Cable De rating Current). September 2020 (1)
(4) Cable Short Circuit Capacity should be higher than System S.C Capacity at that Point. August 2020 (2)
Let’s Select 3.5Core 95 Sq.mm cable for Single run, S.C Capacity =8.2KA. September 2019 (2)
Current Capacity of 95 Sq.mm cable is 200Amp,Resistance=0.41Ω/Km and Reactance=0.074 mho/Km
August 2019 (2)
Total De rating Current of 70 Sq.mm Cable= 200×0.93 =187 Amp.
July 2019 (2)
Voltage Drop of Cable= (1.732x139x(0.41×0.8+0.074×0.6)x200x100)/(415x1x1000)=2.2%
Voltage Drop of Cable=2.2% June 2019 (1)
To decide 95Sq.mm Cable, Cable selection condition should be checked.
May 2019 (2)
(1) Cable De rating Amp (187 Amp) is higher than Full Load Current of Load (139 Amp) =O.K
(2) Cable Voltage Drop (2.2%) is less than Defined Voltage drop (5%) =O.K April 2019 (3)
(3)No of Run of Cable (1) >= (139A / 187A =0.78) =O.K March 2019 (2)
(4) Cable S.C Capacity (8.2KA) is higher than System S.C Capacity at that Point (6.0KA) =O.K
February 2019 (2)
95 Sq.mm Cable satisfied all three condition so It is advisable to use 3.5 Core 95 Sq.mm cable January 2019 (3)
91 Responses to Calculate Cable Size and Voltage Drop October 2017 (1)
You can buy at any time through ONLINE either in Indian Rupees or US$. Go to “Electrical Notes” Page September 2016 (1)
Reply
July 2016 (1)
thank you sir for this good topic November 2011 (2)
Loading...
Reply EEP
Loading...
AI WORKSHOP
Reply
Thanks for such a detailed description of cable selection guide. I was looking for such article from long time. Each
and every thing is explained properly and with examples.
Loading...
Reply
I need busbar calculation formula for control panels applications. I have tried more to find out exact formula for it
but i couldn’t get it, So Kindly help to get me out from this problem. Pages
*How can I calculate busbar size on behalf of Fault Current in Control Panels???* Electrical Calculation
ziddu.com/downloadlink/13…
Rgds,
A.S.Y.RAJA..
Loading...
Reply
Hi..
Thank you very much Jignesh sir for your all hard work and perseverance that you have put to make all electrical
engineers knowledgeable and aware about the practical Electrical enegry or power sector…
I here by just want to make an appeal to you Sir to Upload I.S. STANDARDS FOR ELECTRICAL POWER
GENERATION, TRANSMISSION, DISTRIBUTION AND UTILIZATION..
IS STANDARDS will be more helpful and fruitful to the engineers like us to be a real Electrical engineers..
Loading...
Reply
Jignesh.Parmar says:
February 16, 2014 at 4:37 am
It is totally illegal to Put/ Upload/Share IS standard on net. we have to purchase IS code for study.
that is the reason, I have upload some abstract of IS code.not IS code itself.
Loading...
Reply
How did you get different K factor value? Actually, I want to know the reference of different K factor values,
Please.
Loading...
Hi Sir,
First i would like to say thank you for you sharing the technical knowladge.
just i have find your voltage drop calculation sheet. it has really more data.
Does you have any Solar plant related calculation formats.?
Loading...
kshirod dash says:
February 19, 2014 at 10:02 am
Loading...
Reply
Loading...
Reply
Thanks a lot sir for your efforts to put us through. But please in this calculation of: Full Load Current= (KVAx1000)
/ (1.732xVoltage). Please can you explain this (1.732) value stands for.
Loading...
Reply
devaraj says:
August 18, 2014 at 9:15 pm
Loading...
Reply
M.a.Hussain says:
September 27, 2014 at 6:30 am
Hello sir,
Myself M.a.Hussain, am an electrical engineer graduate i have a doubt in selection of cable section where just
wrote current carrying capacity for the 70 sq mm cable as 170 amps without any formula or derication. i like to
know how do you calculate cable current carrying of a cable
Thank You
Regards
M.a.Hussain
Loading...
Reply
karthik says:
September 29, 2014 at 3:00 pm
Loading...
Reply
padmanaban says:
November 8, 2014 at 11:20 am
I SEARCH LOT OF PAGES FOR CABLE SELECTION. UR PAGE IS VERY VERY HIGHLY SUPERB. I PROUD ABOUT UR
KNOWLEDGE SIR .THANK U
Loading...
Reply
Arunsrikanth says:
December 22, 2014 at 6:16 pm
Sir please give the correct formula how to calculate the size of the cable
Loading...
Reply
CHHABI says:
February 21, 2015 at 11:21 am
Loading...
Reply
CHHABI says:
February 21, 2015 at 11:26 am
Loading...
Reply
Venu says:
February 22, 2015 at 11:17 am
Sir,
I am very thankfull to you in knowing the cable size calculation from the site and i want to bring to your notice
regarding a typing mistake.
In case study to it was written as “Total De rating Current of 70 Sq.mm Cable= 200×0.93 =187 Amp”. as we are
using 95sqmm cable it should be “Total De rating current of 95 Sq.mm cable=200*0.93=187 Amp”.
Loading...
Reply
Dear sir,
I want to know about how to decide or calculate Electrical equipment capacity.Please provide basic formula for
the same.
Loading...
Reply
Govardhan says:
June 20, 2015 at 4:20 am
Loading...
Reply
hj
Loading...
Reply
how to measure HT and LT cable depend upon load voltage drop in HT and LT cable
is same
Loading...
Reply
thank u sir for a great article, but it is very difficult to calculate the resistance and reactance of the cable…….sir plz
add the formulas for how to calculate the reistance and reactance of the cable
Loading...
Reply
Arpita says:
August 20, 2015 at 7:20 am
Sir, i will be very grateful if you please let me know from where do i collect this system S.C. capacity . and there is
another thing i would like to point out, this cable S.C. capacity which you have given as 8.2 KA, is this correct?
Loading...
Reply
Anil says:
November 24, 2015 at 6:32 pm
Total curent rating 500A lenght ofcable 100mtr 400v wat size of cable using
Loading...
Reply
Jacob.N says:
December 21, 2015 at 1:22 pm
sir can you explain what is 0.125m,0.25m ,0.5m in cable distance factor
Loading...
Reply
Can you check this calculation did in cable selection 2… it seems to be wrong..
Reply
Loading...
Reply
sir, your articles are superb,If i was in touch with you physically, we would have discuss more, I appreciate your
work. I will suggest why put them in hard copy people will buy them in a hurry.
please can you send me problems associated with 11kv feeder, and ways of proffering solutions. It is a project i
am working on.
Loading...
Reply
Can you tell me which cable is use in your calculation ?? copper or aluminium ?? And how you calculate the current
capacity of those cables ?? Kindly reply me with your formula/equation of those cable’s phase and ground
Loading...
Reply
it’s excellent.
Loading...
Reply
Gops says:
March 16, 2016 at 6:09 am
1) I have 3.5 core 35sqmm Alu. armed Cable. so pls ask me what is my per phase Amp. capacity and what is total
capacity of 3.5 core 35 sq mm alu armed cable.
2) I have 63 amp 4 pole MCB so what is my per phase current capacity. and total capacity of mcb
Loading...
Reply
Bala says:
March 28, 2016 at 12:21 am
Reply
Dharmendra says:
April 1, 2016 at 12:36 pm
Dear sir
Please let me know about allowable voltage drop between PCC panel to MCC panel?
Loading...
Reply
bala says:
April 9, 2016 at 8:39 am
(Cable S.C Capacity (8.2KA) is higher than System S.C Capacity at that Point (6.0KA) =O.K)
My question is how to calculate Short circuit capacity at that point ? as short circuit capacity of the cable is taken
from the table
Loading...
Reply
Plz Sir clear my concept about my sent issues. which are sent to your email by me
Loading...
Reply
manivannan says:
June 1, 2016 at 12:01 pm
Loading...
Reply
manivannan says:
June 1, 2016 at 12:02 pm
Loading...
Reply
all the cable cos and sine value is same pls ans me sir,
Loading...
Reply
Rizwan says:
November 5, 2016 at 11:07 am
Loading...
Reply
Anil says:
November 16, 2016 at 11:22 am
Dear Sir…thanQ very much for the valuable info about cable designing.Kindly let me know the correction factor for
cables to be laid inside PVC ducts embedded in concrete.
Thanks
Loading...
Reply
is it correct if we derive voltage drop as V = I x Z, where Z = (sqrt(sumsq(r2,x2))?, in above calculation you have
calculated Z = R cos phi + j sin phi, i think here Z is a complex number with some angle to X axis, say Z = R*0.8 +
X*0.6, this gives me a magnitude of Z at 36 degree to X axis. please help on this issue whether which is correct
calculation of Z to arrive at actual voltage drop i.e. V = I*Z?
Loading...
Reply
Naveed says:
January 29, 2017 at 12:33 pm
My load is 4836a three phase tell me standrd size of cable for each phase length is 100feet
Loading...
Reply
Sidhartha says:
February 2, 2017 at 11:43 am
Sir ,
nice explanation.It helped me a lot.
Loading...
Reply
Prajakta says:
May 5, 2017 at 12:00 pm
How can we select the size of flexible wire for power & lighting loads?
Loading...
Reply
Hi, I’m trying to ascertain the size of 3 core wired armoured cable I will need to keep voltage drop to a minimum
level to ensure an existing 100am 240V 18KVa supply is still maintain at that level 300m away from the supplies
supply….on-line calculators suggest I might need a 125mm/6 inch cable? Kind regards Mr Hibbert
Loading...
Reply
nidheesh says:
June 7, 2017 at 12:22 pm
Electrical Load of 2.34KW, Distance between Source and Load is 1000 Meter, System Voltage 415V Three Phase,
Power Factor is 0.8,Permissible Voltage drop is unknown, Demand Factor is 1. What would be the cable size in
laying under the soil with ambient temperature.
Loading...
Reply
Megha says:
June 23, 2017 at 5:57 am
Sir can you share the voltage drop formula for single phase? how we can derived it??
Loading...
Reply
Prasanth says:
July 16, 2017 at 7:06 pm
Loading...
Reply
Prasanth says:
July 16, 2017 at 7:07 pm
Loading...
Reply
MD AFSAR says:
September 7, 2017 at 11:55 am
dear sir help me to calculate Rcos#and jsin# where value of cos# is 0.8 and sin# is 0.6 but how to calculate value
of R and j
Loading...
Reply
Sir plz send me voltage drop calculation for 180 amp. For 3.5C*120 sq.mm lt cable for 1 cable and 2 cable
Loading...
Reply
T Alagumari says:
October 31, 2017 at 2:22 pm
I want 4 core (multistrand core) copper wire pvc insulated cable which should carry 150 amps current 440v , ph
Loading...
Reply
Dear Sir , Greetings on my behalf to Your good self . Would You mind to explain against “No. of Cable / Trench” for
Your Excel Programme titled “Calculate Cable Size & Voltage Drop” ?
Loading...
Reply
Loading...
Reply
archana says:
April 18, 2018 at 3:27 am
Loading...
Reply
Partha says:
May 9, 2018 at 7:21 am
In case of voltage drop calculation, 139 A has been considered for calculation against 159. If I am wrong, please
correct me…
Loading...
Reply
Vairam says:
June 18, 2018 at 7:45 am
Sir let can you explain how can you tell 95sq mm cable amps 200 and resistance ,reactance, shorts circuit current
8.2ka .please tell reason behind this.
Loading...
Reply
Hi Sir,
Your blog & respective calculations are very clear to understand. I want to know how we can do the calculation for
DC cable sizing. will it be the same procedure to calculate?
one of my senior suggested me to do only voltage drop calculation, no need to apply derating factors. If so..why
we don’t need to apply derating factors to calculate cable size for DC system? Pls suggest.
Best Regards
Siddharth Jain
Loading...
Reply
Loading...
Reply
SKJ says:
July 14, 2019 at 4:25 am
Can u suggest what will be maximum distance length of point wiring with conduit and wiring is considered as per
code reference in commercial project?
Loading...
Reply
Loading...
Reply
Bharath says:
September 25, 2019 at 10:27 am
Electricals
Loading...
Reply
Bharath says:
September 25, 2019 at 10:31 am
Electrical
Loading...
Reply
Dear sir
I can’t understood how to get current capacity of cable.u take direct value of 79 and95 sq mm cable rattling in
dalution
Loading...
Reply
Loading...
Reply
Hello Jignesh
Loading...
Reply
manikandan c says:
September 14, 2020 at 1:22 pm
from where u r getting this formula and can u tell the indian standard code mentioning the above formula
Loading...
Reply
parallax1957 says:
March 4, 2021 at 5:44 pm
Hello Jignesh. I have attempted to connect with you via the email in tha past. I have purchased your (39) Street
Light Pole Voltage Drop Calculation-UNLOCK (1.1.19) and advise you, that your method is not as per NEC. I am a
professional engineer in Canada (check my registration with PEO) and can help you to adapt your product to NEC
and CSA standard. Please advise.
Loading...
Reply
Loading...
Reply
Roshan says:
April 25, 2022 at 11:16 am
Where will we get the cable details as you mentioned here 70 mm 170 amp, resistance 0.57, reactance 0.077
95 mm 200 mm resistance 0.041, reactance 0.074
I have gone through different information available on the net it’s different so
Loading...
Reply
M.Ganabathy says:
August 25, 2022 at 5:32 pm
Dear sir, kindly i need voltage drop limit in 11KV cable. & where its mention mumbai electricity board in india.
kindly share
Loading...
Reply
M S says:
October 17, 2022 at 12:23 pm
(4) Cable S.C Capacity (8.2KA) is higher than System S.C Capacity at that Point (6.0KA) =O.K
Sir, please guide that how did you get the Value of S C Capacity Like 8.2 KA & 6.0 KA.
Please Guide
Loading...
Reply
sir please guide me, while calculate cable size from transformer to PCC panel, Which load we can take, connected
load to PCC or maximum demand of PCC panel.
Loading...
Reply
Puthiyaraj says:
January 23, 2023 at 11:45 am
We laid ac cable in ground in trench. Which one we choosing current carrying capacity of the 70 sqmm cable :
Ground – 170A, Duct – 140A
Loading...
Reply